O= O, 1=20 sees, [2=30 sees],Partition 1 t
3=45 sees, 4=60 sees; 5=90 sees. “1” max. for UL installations.
Zone Type 02 Entry Delay= Zone Type 01 Delay +30 sees.
Exit Delay = Zone Type 01 Entry Delay + 40 sees.
O= no; [1 = yes].Partition 1 t
[0= no]; 1 = yes.Partition 1 t
O= no; [1 = yes].“1”. for UL installations.
❑ Partition 2 to
❑ Partition 2 to
❑ Partition 2 to
to
DIALERPROGRAMMING(40+53)
In fields *40, *41, *42, enter up to the number of digits shown. Do not fill unused spaces. Enter O-9; #+11 for ‘*’; #+12 for ‘#’;
#+13 for a pause.
*4O
PABX ACCESS CODE
PRIMARY PHONE
Ml
*42
SECONDARYPHONE
PRIMARY SUBS ACCT # (PART’N 1)
*43
PRIMARY SUBS ACCT # (PART’N 2)
*45
t Entry of a number other than one specified
will give unpredictableresults.
No.
No.
Enter 4 digits. If fewer than 4 digits are entered, exit by
pressing *(and press 41, if entering next field). To clear entries from field,
press @@I.
Enter up to 12 digits.
Do not fill unused spaces. If fewer than 12 digits entered, exit by pressing *
(and press 42, if entering next field). To clear entries from field, press* 41 *.
Enter up to 12 digits.
Do not fill unused spaces. If fewer than 12 digits entered, exit by pressing *
(and press 43, if entering next field). To clear entries from field, press *42*.
PRIMARY RECEIVER
~]
PRIMARY RECEIVER
~]*46 SECONDARY SUBS ACCT # (PART’N 2) ~1
Enter O-9; #+1 1 for B; #+12 for C; #+13 for D; #+14 for E; [#+15 for F].
Enter * as 4th digit, if 3+1 dialer reporting is to be used. If only 3 digits
used, exit by pressing * (and press next field).
To clear entries from field, press *43*,*44*,*45*, or *6*.
Examples:
*44 SECONDARY SUBS ACCT# (PART’N 1) ~]
For Acct No. 1234, enter
For Acct No. B234, enter: #+11121314
For Acct No. 123, enter:
of a number other than one specified will give unpredictable results.
t Entry
*56
ZONE ASSIGNMENT/ALARMREPORT CODES —This field is an interactive mode. Fill in the required data on the
worksheet below (and on next page) and follow the programmingprocedure in the installation manual.
ZONES ON CONTROL:
ZONE
DESCRIPTIONTYPE
Wired Zone 1‘
Wired Zone 2
Wired Zone 3
Wired Zone 4
Wired Zone 5
Wired Zone 6
Wired Zone 7 t
Wired Zone 8“
Expansion Module
Supervision
Duress
Console Panic (1 & *, or A)ml
Console Panic (3& #, or C)~~
Console Panic (*& #, or B)ml
●Zone 1 can be used
$Zone 7 can be used for optional Keyswitch; shows as 77 for Zone Type (iT).
as a 2-wire Fire zone.
ZONE
(Rj
m
m
m
m
m
m
m
m
m
m
lfCent. Sta. /S A/OTonaWATS line: [O= Pulse Dial]; l =Tone Dial
If Cent. Sta. /S on a WATS line:2 = Pulse Dial :3 = Tone Dial.
L = LEARNED RF INPUT Used with 5800 RF Loop Input Devices. Record transmitter input number.
Zone Nos. are from 01 to 63, 92, 95, 96, 99. Some are pre-assigned.
With Field *25 set for auxiliary wired loops (421 9, or 4229), use Zone Nos. 10-17 for loops A-H.
With Field *22 set for RF (5800), use Zone Nos. 18-63 if 4219/4229 is ALSO used, or 10-63 if 4219/4229 is NOT used.
Exarnp/e: To select “Alarm/Alarm Restore”, and
“Open/Close”, enter 9 (1 + 8); To select all, enter#15.
Default = “3.
Note: System messages are logged when any non-zero
selection is made.
*91
OPTION SELECTION
“O for UL installations.
PHONE LINE MONITOR ENABLE
*92
[0= Not used]
1 = Keypad display
2 = Keypad display plus keypad trouble sound
3 = Same as “2, plus Device #2 STARTS. If either partition
Note Device #2 must either be programmed to be
STOPPED in field *8O or STOPPED by Code+ # + 8 + 2.
procedure in instructions.
in instructions.
when line is faulted
is armed, external sounder activates also.
(Also entered from field
[0= None]; 4= AAV ❑
III
m
u
•1
❑
ARM AWA’f/STAYRPT CODE
*66
t 2nd digit is automatically sent as the 2nd digit of the
zone alarm report code programmed in *56, if
expanded or 4+2 reporting is selected.
tt 2nd digit is automatically sent as the user number if
expanded or 4+2 reporting is selected.
RF XMTR LOW BAT REPORT CODE
*67
CANCEL REPORT CODE
*68
Part.11111~
RESTORE REPORT CODES (*70-*76)
*7O
ALARM RESTORE RPT CODE
2nd digit is automatically sent as the 2nd digit of the —
zone alarm report code programmed in *56, if
expanded or 4+2 reporting is selected.
21 = Arming-Away39= Any Fire Alarm
22= Disarming (Code + OFF)
31 = End of Exit Time
32= Start of Entry Time
33= Any Burglary Alarm
36= *’At Bell Timeout*’*
*’ Use O
*** Or at Disarming, whichever occurs earlier.
ACTIONEVENTLISTSYST OP’N
(A)(EV)(ZL)(n)(P)
“START” ZONE LIST: Upon alarm, fault, or trouble of ANY zone on this list, device action will START.
‘STOP RESTORE of ZONE LIST: Upon restore of ALL zones on this list, device action will STOP. It
Not Used06= 24 Hr Silent
Armin@tay
(Any)forPartition No. (P) entry.
START
ZONE
ZONE TYPE PART’N
No.
RESTORE ofZONE TYPE PART’N
ZONE LISTISYST OP’N
STOP
● either or both ●
(ZL)(ZT)
❑❑0❑
n❑n❑
n❑n❑
0❑0❑
❑❑
❑❑
❑
❑
❑
“1”if Powerline Carrier Device is being used, enter “O if relay is being used.
need not be same list as used for START.
07= 24 Hr Audible
08= 24 Hr Aux
09= Fire Trouble
10= Interior w/Delay
24= Silent Burglary
38= Chime
40= Bypassing
41 = **AC Power Failure
42=
●*System Battety Low
43= Communication Failure
Note: Any zone in “Z7oin,7g into akrrm
fault, or trouble WI I actuate relay. ‘
An zone of that type that restores
{WII stoo relav action.
52= KiSSOff
58= Duress
In normal operation mode:
Note:
Code + # + 7 + N Key Entry starts Device N.
Code + # + 8 + N Key Entry stops Device N.
n❑
n❑
III❑
loo❑
Inn❑
R
-6-
*81
ZONE LISTS FOR OUTPUT DEVICES – This is an interactive mode. Fill in the required data on the worksheet
below and follow the procedure in the installation manual as you enter the data during the displays and prompts that
appear in sequence.
Note:Record desired zone numbers below. More or fewer boxes than shown maybe needed, since any list may
include any or all of system’s zone numbers.
Zone List 1: Started or stopped by zone numbers (enter 00 to end entries).
❑0❑ 0,❑0❑0,❑ 0,❑ n❑0❑ 0❑ 0❑netc
Zone List 2: Started or stopped by zone numbers (enter 00 to end entries).
❑0,❑ n❑n❑n❑ n,❑ 0❑n❑ 0,❑ 0❑mtc
Zone List
3: Started or stopped by zone numbers (enter 00 to end entries).
❑ 0,❑ 0❑ 0❑0,❑ 0❑0❑0❑ 0❑ n,IIlnetc
SPECIALMESSAGES
OC =
OPEN CIRCUIT (no communicationbetween Console and Control).
EE or ENTRY ERROR= ERROR (invalid field number entered; re-enter valid field number).
After powering up, AC, dl (disabled) or System Busy and NOT READY will be displayed after approximately 4 seconds. This
will revert to READY in appx. 1 minute, which allows PIRS, etc. to stabilize. To bypass this delay, press: [#] + [0].
If E4 or E8 appears, more zones than the expansion units can handle have been programmed.Correct the programmingand
then completely de-power and re-power the control to clear this indication and remove the disable indication.
TO ENTER PROGRAMMINGMODE:
POWER UP, then depress [*] and [#] both at once, within 50 seconds of powering
1.
OR
Initially, key Installer Code (4+ 1 + 1 +2) plus 8 + O + O.
2.
OR
If different InstallerCodeis Droarammed.kev: New I nstaller Code + 8 + O + O.
3.
(if *98 was used to exit previous~, method 1 ~bove must be used to enter the program mode again)
TO EXIT PROGRAMMINGMODE:
*98Exits programming mode and preventsre-entry by Installer Code + 8+ O+ O. If *98 is used to exit programming
mode, system must be powered down, and method 1 above used to enter the programmingmode.
*98Exits programmingmode and a//ows re-entry by Installer Code + 8 + O + O or: Power-up, then press “*” and “#”
within 50 seconds of power up.
up.
-7-
(ADEIvICOJ
ALARMDEVICEMANUFACTURINGCO.
165 Eileen Way, Syosaet, New York 11791
A DIVISION OF PITIWAY CORPORATION
Copyright @ 1995 PITTWAY CORPORATION
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.