Visonic TMD-560 PG2 User Manual

TMD-560 PG2
Wireless PowerG Temperature Detector
1. INTRODUCTION
The TMD-560 PG2 is a wireless PowerG detector used with the PowerMaster alarm system. The detector is designed to update the alarm system control panel upon any change of temperature. The control panel then generates an alarm message when the temperature has reached a certain temperature point. A restore message is generated when it crosses back the threshold temperature point. There are a number of selectable fixed temperature points at the control panel and the user can enable one or more temperature point. The TMD-560 PG2 can be used in instances where temperature detection is critical. Other examples of detector usage are as follows:
Activating and deactivating pipe heaters at locations where low temperatures may
cause the water in pipes to freeze.
Warn of possible electrical device malfunction due to high or low temperature levels. Alerting elderly people of a significant rise or drop in room temperature.
The TMD-560 PG2 detects both indoor and outdoor temperatures. The detector monitors room temperature using an internal sensor. For outdoor or refrigerator installations, a waterproof temperature probe (optional) is used.
When the probe is connected, the temperature measurement is performed only by the probe sensor. When the probe is not connected and its terminals are shorted, the temperature measurement is performed only by the detector's internal sensor.
Once the predefined temperature is reached, the alarm system control panel sends a notification to the central station or uses the PGM/X-10 controls to switch on a connected appliance, for example, a heater or air conditioner.
Note: When using the temperature probe to monitor refrigerator temperature, the temperature probe is installed inside the refrigerator, while the detector is installed on the wall or ceiling. For outdoor installations, the temperature probe is installed outdoors, while the detector is installed indoors.
Based on the unique PowerG technology, the TMD-560 PG2 includes a "smart" anti- collision transmission sequence mechanism that prevents collisions with transmitted messages from other PowerG devices.
For further reliability, the TMD-560 PG2 tamper switch is activated when the detector cover (see Figure 2) is removed. Operating power is obtained from an on-board 3 V Lithium battery. A weak battery will result in a “low battery” message.
Features
The TMD-560 PG2 is compatible with PowerMaster control panels. Internal temperature sensor An external temperature optional probe (cat. no. 99-300890) enables outdoor and refrigerator temperature sensing Fully supervised PowerG detector Long battery life Low battery supervision Probe disconnected supervision Link quality indication
Installation Instructions
Figure 1. TMD-560 PG2 with Temperature Probe
2. INSTALLATION, ENROLLING AND CONFIGURING
2.1. Mounting and Battery Insertion
1. Installation: The TMD-560 PG2 can be installed indoors on walls or on ceilings and in any direction. For installing outdoors or on refrigerators use the
temperature probe (see Figures. 1 and 3). Mount the bracket in the monitored area as close as possible to the control panel to ensure optimum reception of the RF signal.
If there is a short circuit between the two probe terminals (factory default) the detector measures the temperature using its internal sensor. If the probe terminals are not shorted, the internal sensor is disabled and the temperature is measured by the probe.
Note: Open probe terminals generate a "Probe Disconnected Trouble" transmission.
2. Insert the battery between the battery clips (see Figure 2), at the correct polarity. For proper operation, only a Lithium battery (type CR123 or equivalent) should be used. Note: When replacing a battery, it is necessary to wait 30 seconds between removing the used battery and inserting the new one. Caution! Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the manufacturer's instructions.
D-303471 TMD-560 PG2 Installation Instructions 1
Figure 2. Mounting
Figure 3. Temperature Probe Mounting
1. Insert a flat-edged screwdriver into the slot and push upward to remove cover.
2. Remove screw.
3. Separate base from cover.
4. Flex catch and remove P.C. board.
5. Mark and drill 2 holes in the mounting surface. Fasten
base with 2 countersunk screws.
6. Reinsert P.C. board into base and connect the two wires of the probe to the terminal block.
A. Terminal Jumper B. Enroll button C. LED D. Internal Temperature Sensor
2.2. Enrollment
Refer to the PowerMaster panel's Installer Guide and follow the procedure under the "02:ZONES/DEVICES" option of the Installer Menu. A general description of the procedure is provided in the following flow chart.
Step 1 Step 2 Step 3 Step 4
Enter the Installer menu and select “02:ZONES/DEVICES
02:ZONES/DEVICES
Select "ADD NEW DEVICE" See Note 1
Step 5 Step 6 Step 7 Step 8
Configure Location parameter
MODIFY DEVICES
Enter PARTITIONS. See Note
2
means scroll and select
Notes: [1] If the temperature detector device is already enrolled you can configure the temperature detector device parameters via the “Modify Devices”
option – see Step 2.
PARTITIONS will appear only if PARTITIONING was previously enabled in a panel that supports the Partitioning feature (for further
[2]
details, see "Partitioning" in the PowerMaster Installer Guide).
Enroll the device or enter the device ID
ENROLL NOW or ADD NEW DEVICES
ENTR ID:XXX-XXXX
Assign partitions to the detector by pressing the
the panel
Z06:P1 P2 P3
,
and buttons on
Select the desired detector number for the new flood detector
Z06:Temp. Sensor
ID No. 250-XXXX
Continue to section 2.3
Z06.DEV SETTINGS Z06.LOCATION Z06.PARTITIONS
2.3. Configuring the Temperature Device Parameters
Enter the menu and follow the configuration instructions for the TMD-560 PG2 temperature detector device as described in the following table.
This option is available only through the DEFINE DEFAULTS settings, (for further details, see the PowerMaster Installer Guide).
2 D-303471 TMD-560 PG2 Installation Instructions
Z06:DEV SETTINGS
Option Configuration Instructions
TEMPERATURE C/F
VERY HOT > 35C
Set the detector to detect temperatures in either Celsius or Fahrenheit.
Options: Celsius C (default) or Fahrenheit F.
Define whether or not the control panel will report a "very hot" alert when the temperature rises above 35C (95F) for at least 10 minutes. Alert restore will occur when the temperature drops below 34C (93F) for the duration of 10 minutes.
Loading...
+ 2 hidden pages