Visonic MCT-560 User Manual

MCT-560
English
Wireless Temperature Detector Installation Instructions
Detectores de Temperatura Supervisionado Sem Fios PowerCode Instruções de Instalação
Español
Detector de Temperatura inalámbrico, instrucciones de Instalación.
ENGLISH
Fig. 1 – GB/US: MCT-560 with Temperature Probe / PT: MCT-560 com Sonda de Temperatura / SP: Sonda de Temperatura
1. General
The MCT-560 is a fully supervised wireless PowerCode detector used with the PowerMax Pro (Ver. 5), PowerMax COMPLETE, and Amber alarm systems. The detector alerts the alarm system control panel upon detecting critical indoor or outdoor temperatures. The detector generates an alarm message when its sensor detects that the temperature has reached a certain temperature point. A restore message is generated when it crosses back the threshold temperature point. There are a total of four fixed temperature points and the user can enable one or more temperature point. The MCT-560 can be used in instances where temperature detection is critical.
Other examples of detector usage are as follows:
Activating and deactivating pipe heaters at locations where low
temperatures may causes the water in pipes to freeze.
Warn of possible electrical device malfunction due to high or low
temperature levels.
Alerting elderly people of a significant rise or drop in room temperature.
The MCT-560 detects both indoor and outdoor temperatures. The detector monitors room temperature using an internal sensor. For outdoor or refrigerator installations, a waterproof temperature probe (optional) is used.
When the probe is connected, the temperature measurement is performed only by the probe sensor. When the probe is not connected, the temperature measurement is performed only by the detector's internal sensor.
Once the predefined temperature is reached, the detector wirelessly updates the alarm system control panel which then sends a notification to the central station or uses the PGM/X-10 controls to switch on a connected appliance, for example, a heater or air conditioner.
Note: When using the temperature probe to monitor refrigerator temperature, the temperature probe is installed inside the refrigerator, while the detector is installed on the wall or ceiling. For outdoor installations, the temperature probe is installed outdoors, while the detector is installed indoors.
Upon alarm, a digital message is transmitted, composed of the unit ID followed by message data.
Since messages transmitted by the MCT-560 might collide with transmissions from other PowerCode detectors, a "smart" anti­collision transmission sequence is used.
The MCT-560 tamper switch is activated when the MCT-560 is removed form the mounting surface or when the MCT-560 securing screw (see Fig. 4 point 1) is removed. A periodic supervision message is transmitted automatically once every 15 or 60 minutes, or according to local requirements. An LED lights whenever alarm, alarm restore or tamper events are reported. Operating power is obtained from an on-board 3 V Lithium battery. A weak battery will result in a “low battery” message.
Features
The MCT-560 is compatible with supporting versions of PowerMax
Pro, PowerMax COMPLETE, and Amber.
Note: There is no backward compatibility with PowerMax and Amber models produced before the year 2007.
Internal sensor
An external temperature probe (cat. no. 99-300890) enables
outdoor and refrigerator temperature sensing
Four selectable temperatures
Fully supervised PowerCode detector
Front and back tamper
Long battery life
Low battery supervision
Probe disconnected supervision
Alert transmission indication using an LED
2. Specifications
Frequency (MHz): 315, 433.92, 868.95, 869.2026 or other frequency
per local requirements.
Communication Protocol: PowerCode Detector's ID Code: 24-bit digital word, over 16 million combinations,
pulse width modulation Temperature Alarm or Tamper Message Repetition: Repetitive transmission (once every 15 minutes) until the alarm is restored.
Supervision: Signaling at 60 min. (USA) or 15 min. (Europe) intervals. RFI protection: >20 V/m 80 to 2000 MHz Temperature measurement accuracy (internal sensor or optional probe): ±1.5°C (±2.7°F) Probe cable length: 3.5m Power Source: 3V Lithium CR-2 type battery, Panasonic, Sanyo or equivalent Transmission LED: Lights for 2 sec when reports alarm, alarm
restore or tamper events. Battery Life Expectancy: – For supervision signaling every 60 min - up to 10 years typical use. – For supervision signaling every 15 min - up to 8 years typical use. Battery Supervision: Automatic transmission of battery condition data as part of any status report.
Operating Temperature (indoor): -20°C to 50°C (-4°F to 122°F). Probe Operating Temperature (outdoor): -30°C to 70°C (-22°F to 158°F). Storage Temperature (indoor): -20°C to 60°C (-4°F to 140°F). Dimensions: 92 x 36.5 x 31 mm (3-5/8 x 1-7/16 x 1-1/4 in.). Weight (excluding battery): 50 g (1.8 oz) Compliance with Standards: CFR47 (FCC) part 15, ICES-003:04,
EN300220, EN301489, EN60950
This device complies with Part 15 of the FCC Rules and RSS-210 of Industry and Science Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
device complies with the essential requirements and provisions of
This Directive 1999/5/EC of the European Parliament and of the Council of 9 March 1999 on radio and telecommunications terminal equipment.
3. Preparation for Use
Follow the instructions in Figs. 2 and 3 showing how to open the detector cover and gain access to the DIP switch.
A. Function Switches
The MCT-560 has a 4-position DIP switch function selector (Fig. 3) that enables selection of up to 4 temperatures at which the detector will send an alert. Each switch lever enables one temperature alert. All switches are set to OFF, by default. Setting a switch to ON enables the MCT-560 to detect the matched temperature as listed in Table 1.
Table 1. Alarm and restore conditions
point#
T1
T2
T3
T4
Application
Freezer fault
Freezing temp sensing
Cold temp sensing
Hot temp sensing
Alarm condition Restore condition Temp.
Threshold Duration
Temp rises above -10°C
°F)
(14 Temp drops below 7°C
(45°F)
Temp drops below 19°C
66°F)
(
Temp rises above 35°C
(95°F)
[min]
Threshold Duration
Temp drops
30
below -1
12°F)
( Temp rises
10
above 8°C
(46°F)
Temp rises
10
above 20°C
68°F)
(
Temp drops
10
below 34°C
(93°F)
[min]
10
1°C
10
10
10
D-300872 1
Duration: The temperature must pass beyond the threshold for the required duration in order to generate an alarm or restore transmission.
B. Setting the Switches
Set the function switches as desired prior to applying power (see Fig. 2). To enable temperature alarms, select at least one temperature point according to Table 2. Use a ball point pen or another pointed object to shift the switch levers.
Table 2. Getting acquainted with the function selector
Sw- Temperature
off on Default
point
SW1 SW2 SW3 SW4
T1 Disable Enable T2 Disable Enable T3 Disable Enable T4 Disable Enable
OFF OFF OFF OFF
C. LED indications
Power up
Tamper close
Tamper open
T1/T2/T3/T4 Alarm
T1/T2/T3/T4 Restore
Low battery
Probe disconnect
Supervision expiry time
Event LED
Flashes for 10 sec
On for 2 sec
OFF
4 Installation, Enrolling and Testing
1. Installation:
The MCT-560 can be installed indoors on walls or on ceilings and in any direction. For installing outdoors or on refrigerators use the temperature probe (see Figs. 1 and 3).
WARRANTY
Visonic Ltd. and/or its subsidiaries and its affiliates ("the Manufacturer") warrants its products hereinafter referred to as "the Product" or "Pr oducts" to be in conformance with its own plans and specifications and to be free of defects in materials and workmanship under normal use and service for a period of twelve months from the date of shipment by t he Manufacturer. The Manufacturer's obligations shall be limited within the warranty period, at its opt ion, to repair or replace the product or any part thereof. The Manufacturer shall not be responsible for dismantling and/or reinstallation charges. To exercise the warranty the product must be returned to the Manufactur er freight prepaid and insured. This warranty does not apply in the following cases: improper installation, m isuse, failure to follow installation and operating instructions, alteration, abuse, accident or tampering, and r epair by anyone other than the Manufacturer. This warranty is exclusive and expressly in lieu of all other w arranties, obligations or liabilities, whether written, oral, express or implied, including any warranty of merchant ability or fitness for a particular purpose, or otherwise. In no case shall the Manufacturer be liable to anyone for any consequential or incidental damages for breach of this warranty or any other warranties what soever, as aforesaid. This warranty shall not be modified, varied or extended, and the Manufacturer does not authorize any person to act on its behalf in the modification, variation or extension of this warranty. This warranty shall apply to the Product only. All products, accessories or attachments of others used in conjunct ion with the Product, including batteries, shall be covered solely by their own warranty, if any. The Manufacturer shall not be liable for any damage or loss whatsoever, whether directly, indirect ly, incidentally, consequentially or otherwise, caused by the malfunction of the Product due to products, accessor ies, or attachments of others, including batteries, used in conjunction with the Products.
Mount the bracket in the monitored area as close as possible to the control panel to ensure optimum reception of the RF signal. If there is a short circuit between the two probe terminals (factory default) the detector measures the temperature using its internal sensor. If the probe terminals are not shorted, the internal sensor is disabled and the temperature is measured by the probe.
Note: Open probe terminals generate a "Probe Disconnected Trouble" transmission.
2. Insert the battery between the battery clips (see Fig. 2), at the correct polarity. For proper operation, only a Lithium battery
(Panasonic / Sanyo type CR2 or equivalent) should be used.
Note: When replacing a battery, it is necessary to wait 30 seconds between removing the used battery and inserting the new one.
3. Enrolling: Enroll the detector's ID into the alarm system memory according
to the alarm system installation instructions. When in Enrolling mode, press the tamper switch to activate transmission.
4. Mounting the detector: Mount the MCT-560 on the bracket.
5. Tamper test: Perform a tamper test to ensure reception between the MCT-560
and the control panel. Activate the Tamper function by removing the MCT-560 from its bracket as shown in Figure 4 step 1.
Note: Since the cover is removed and power is applied, a tamper
situation exists. Verify that the MCT-560 transmits (the LED lights briefly).
When you are satisfied that tamper alert is transmitted properly,
close the MCT-560 front cover on to return the tamper switch to its normal position. Then, secure the front cover to the base with the case closure screw.
The Manufacturer does not represent that its Product may not be compromised and/or circum vented, or that the Product will prevent any death, personal and/or bodily injury and/or damage to property resulting from burglary, robbery, fire or otherwise, or t hat the Product will in all cases provide adequate warning or protection. User understands that a properly installed and ma intained alarm may only reduce the risk of events such as burglary, robbery, and fire without warning, but it is not insurance or a guarantee that such will not occur or that ther e will be no death, personal damage and/or damage to property as a result.
The Manufacturer shall have no liability for any death, personal and/or bodily injury and/or damage to property or other loss whether direct, indirect, incidental, consequential or otherwise, based on a claim that the Product failed to function. However, if the Manufacturer is
held liable, whether directly or indirectly, for any loss or damage arising under t his limited warranty or otherwise, regardless of cause or origin, the Manufacturer's maxim um liability shall not in any case exceed the purchase price of the Product, which shall be fixed as liquidated damages and not as a penalty, and shall be the complete and exclusive remedy against the Manufacturer. Warning: The user should follow the installation and operation instructions and among other things test the Product and the whole system at least once a week. For various reasons, including, but not limited to, changes in environmental conditions, electric or electronic disruptions and tampering, the Product may not perform as expected. The user is advised to take all necessar y precautions for his /her safety and the protection of his/her property. 6/91
W.E.E.E. Product Recycling Declaration For information regarding the recycling of this product you must contact the company from which you orignially purchased it. If you are discarding this product and not returning it for repair then you must ensure that it is returned as identified by your supplier. This product is not to be thrown away with everyday waste. European Directive 2002/96/EC Waste Electrical and Electronic Equipment.
PORTUGUÊS
1. Introdução
O MCT-560 é um detector PowerCode sem fios totalmente supervisionado, compatível os sistemas PowerMaxPro (Ver. 5), PowerMax COMPLETE e sistemas de TeleAssistência Amber. O detector avisa o sistema de controle logo que detecte temperaturas críticas quer no interior, quer no exterior do local de instalação. O detector gera uma mensagem de alerta quando o seu sensor atinge uma determinada temperatura. Quando a temperatura regressa aos valores pré-estabelecidos é enviada uma mensagem de restauração. Existem quatro níveis de temperatura definidos e o utilizador pode escolher um ou mais níveis de temperatura.
O MCT-560 pode ser utilizado em situações em que a detecção da temperatura é fundamental.
Outros exemplos da utilização do detector tais como:
Para activar ou desactivar sistemas de aquecimento de condutas,
em locais em que as baixas temperaturas podem provocar a congelação da água nos canos.
Aviso de possível avaria de dispositivo eléctrico devida a níveis
de temperatura elevados ou baixos.
Alertar os idosos para mudanças significativas de temperatura no
interior.
O MCT-560 detecta as temperaturas no interior e no exterior do local de instalação. O detector monitoriza a temperatura interior utilizando um sensor interno. Para o exterior ou instalações de refrigeração, é utilizada uma sonda de temperatura à prova de água (opcional).
2 D-300872
Quando a sonda está ligada, a medição da temperatura é realizada apenas pelo sensor da sonda. Quando a sonda não está ligada, a temperatura é medida apenas pelo sensor interno do detector.
Assim que a temperatura pré-definida seja atingida, o detector sem fios informa o painel de controle do sistema que depois envia uma notificação para os telefones particulares, central receptora ou utiliza os controlos PGM/X-10 para activar ou desactivar um dispositivo eléctrico, como por exemplo, um aquecedor ou um ar condicionado.
Nota: Quando se utiliza a sonda de temperatura para controlar a temperatura do frigorífico, a sonda de temperatura é instalada dentro do frigorífico, enquanto que o detector é instalado na parede ou no tecto. No caso de instalações exteriores, a sonda de temperatura é instalada no exterior, enquanto que o detector é instalado no interior.
Em presença de uma situação de alarme, o código de identificação do detector é enviado, utilizando uma sequência de transmissão anti­colisão, evitando que as mensagens transmitidas pelo MCT-560 possam interferir com outras transmissões dos detectores PowerCode.
O interruptor de sabotagem do MCT-560 é activado quando o detector é retirado do local de instalação ou quando o parafuso de segurança (ver Fig. 4, ponto 4) é removido. Além disso, cada 15 ou 60 minutos, conforme os requisitos locais, é transmitida uma mensagem periódica de supervisão. Através de um indicador luminoso informa-se a presença de um alarme, mensagem de restauração ou sabotagem.