Visonic MCT-427, MCT-426 User Manual

MCT
MCT----426
MCTMCT
426,
426426
, MCT
MCT----427
, ,
MCTMCT
427
427427
Supervised Wireless PowerCode Smoke / Heat and Smoke Detector
1. DESCRIPTION AND APPLICATIONS
MCT-426 (photoelectric smoke detector) and MCT-427 (heat and photoelectric smoke detector) are automatic fire detectors with integral audible signal for open area protection, designed to sense heat or smoke (not flame) and fitted with a PowerCode type UHF transmitter. MCT-426 / MCT-427 provides early warning of developing fire by sounding an alarm with its built-in alarm horn, and by transmitting a coded alarm signal to a PowerCode receiver or to a compatible wireless alarm control panel. For UL and ULC approved installation use PowerMax+ or PowerMax Pro/Complete/Express control panels. MCT-427 will activate a fire alarm upon either smoke or heat condition. With two fire sensors (heat and smoke), the MCT-427 detector may shorten the time to fire alarm activation. It must be borne in mind, though that effective prewarning of fire accidents is only possible if the detector is located, installed and maintained as described here. In alarm condition, the buzzer sound can be stopped for 8 minutes (UL) and 10 minutes (EN) by pressing the TEST/MUTE switch. It will not restore the alarm condition, but will temporarily silence the buzzer while you correct the condition. After 8 minutes (UL) and 10 minutes (EN), the detector restarts the alarm buzzer sound.
2. SPECIFICATIONS
2. SPECIFICATIONS
2. SPECIFICATIONS2. SPECIFICATIONS
Alarm Sound Level: 85 dB at 3 m (10 feet) TRANSMITTER AND CODING Operating Frequency (MHz): 315, 433.92, 868.95, 869.2125 or other
frequency, according to local requirements. Transmitter's ID Code: 24-bit digital word, over 16 million combinations, pulse width modulation.
Overall Message Length: 36 bits Supervision: Automatic signaling at 60-minute intervals (315 MHz version), 15-
minute interval (433.92, 868.95, 869.2125 MHz versions) or according to the local standards. Tamper Alerts: Tamper event (removal of the unit from its bracket) is reported once. Tamper restore is reported when the tamper switch is restored. Transmission Indicator: Yellow LED lights upon transmission (visible only when LED function is pre-defined, see par. 3.7).
ALARM REPORT:
Every 20 seconds for the first 3 minutes. Then, every 3 minutes until 30 minutes have elapsed.
Alarm stops reporting after 30 min., or if the detector goes into "alarm restore".
After 30 minutes, an alarm bit will be sent as part of the supervision message.
ELECTRICAL DATA Power Source: 3 Volt CR123A / CR17450 lithium.
Note: The CR17450 battery shall not be used in UL/c-UL applications.
Operation Voltage: From 2.7 V to 3 V. Current Drain: 18 µA standby, 70 mA max. in operation Smoke Density:
Europe: 0.09 – 0.14 dB/m USA: 1.44%/ft to 2.74%/ft Canada: 1.29%/ft to 2.27%/ft obs
Note: For UL/c-UL installations, Smoke Density is 0.91%/ft to 2.47%/ft for USA and 0.91%/ft to 2.27%/ft for Canada.
Heat Sensor Alarm Threshold: 60° C (±3°) / 140° F (±5°)
Note: For UL/c-UL installations, Heat Sensor Alarm Threshold is 68°C (154°F).
Cover Range: 50 – 100 cubic meters (1770 – 3530 cubic ft.) Battery Supervision: Automatic transmission of battery status data as part of any
transmitted message.
3. INSTALLATION
3. INSTALLATION
3. INSTALLATION 3. INSTALLATION
3.1 Disassembly
Separate the unit from its mounting bracket as shown in Figure 2.
Note: The TEST/MUTE switch functions as TEST switch (in normal operation) or as MUTE switch (in alarm condition).
The tamper switch actuator (Fig. 3) is pressed against the bracket when the unit is attached to the bracket. Removal of the unit from the bracket causes the switch contacts to open, creating a tamper event, which is reported by the transmitter to the alarm system control panel.
Battery Life Expectancy: Battery life exceeds the minimum life required by UL 268 and CAN/ULC-S531-02. Visonic warrantees the life of the battery for 5 years. Audible and Visual Low Battery Warning: Built-in horn beeps every 30 seconds simultaneously with red LED flashing (for up to 30 days when the battery voltage drops).
Caution! Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the manufacturer's instructions.
Audible and Visual Degraded Chamber Sensitivity Warning: Built-in horn beeps every 30 seconds in the middle of red LED flashing intervals – indicates that the detector must be replaced. Clean Warning Transmission: When the detector’s chamber becomes dirty, a Trouble signal that indicates the need to clean the detector is sent to the control panel. A dirty chamber can cause the detector to operate at high sensitivity. If this message persists after cleaning, you may need to replace the detector.
Note: This transmission applies to the PowerMax+ (version F and higher) and PowerMax Pro/Complete/Express control panels only.
PHYSICAL DATA Operating Temperature: -10°C to 50°C (14°F to 122°F).
Note: For UL/c-UL installations, Operating Temperature is 0°C to 38°C (32°F to 100°F).
Relative Humidity: 10% to 85% Dimensions: MCT-426 120 mm (4.7") x 58 mm (2.3")
Weight (including battery): 165 g (5.8 oz) Compliance with Standard:
Designed to comply with:
Installation Instructions
TEST / MUTE
BUTTON
&
LEDS
2
Rotate the
detector
anticlockwise
and pull it from
the bracket
BUZZER
HOLE
Figure 1. General View (MCT-427)
MCT-427 120 mm (4.7") x 63 mm (2.5")
MCT-426/427 Europe: (868.95, 433.92 and 869.2125 MHz):
EN54-7 (except for § 4.2), EN 14604. EN 54-5 Class A2-S (except for § 4.4), EN 60950, EN 300220, EN 301489, EN 50130-4.
USA: 315MHz (FCC) CFR47 Part 15 Canada: (315 MHz): RSS210
MCT-426/427 USA (315MHz): UL 268 MCT-426/427 CANADA (315MHz): CAN/ULC-S531-02
BRACKET DETECTOR
1
Hold the
bracket with
one hand
Figure 2. Separating the Detector from Its Bracket
D-302151 MCT-426, MCT-427 Installation Instructions 1
3.2 Audible and Visual Indications
2 short beeps every
The dual color LED and buzzer are used to signal various alarm and trouble messages as shown in Table 1 below:
Condition
Smoke alarm Flash every
Heat alarm(***) Flash every
Tamper alarm(*)
Standby
Low battery
Smoke sensor trouble
Low sensitivity alarm
Heat sensor trouble(***)
Need to clean 2 flashes every 30
Test
* The tamper alarm will mute for 3 minutes at first power on, and will revert
to normal mode when the tamper switch condition is changed. ** Delay of 15 sec. between buzzer beep and LED operation *** MCT-427 only
Table 1. Visual and Audible Indications
Visual Indication (LEDs)
Red
500ms
500ms
-
Flash every 30 sec.
Flash every 30 sec.
Flash every 60 sec.
Flash every 30 sec.(**)
Flash every 60 sec.
sec.
See par. 3.7
3 Flashes every 60 sec.
5 Flashes every 60 sec.
Yellow
-
-
-
-
-
-
-
3 long beeps every 4 sec.
3 long beeps every 4 sec.
Long beep every 2 sec.
Short beep every 30 sec.
Short beep every 60 sec.
Short beep every 30 sec.
Short beep every 60 sec.
30 sec.
Audio
Indication
-
3.3 Battery Connection and Initial Test
Attention: The detector battery cover is fitted with a red button that prevents the detector from locking onto bracket if there is no battery inside. The smoke detector is supplied with a 3V CR123A / CR17450 battery. Battery connection for both types of batteries is illustrated in Figure 3a and 3b below.
3 volts CR123A
Open battery cover and connect the battery to its t e rm in al s ( w i th ou t insulator). Verify proper polarity.
3 volts CR17450
Transmission LED ON/OFF
button
Battery cover
Tamper
switch
Open battery cover and connect the battery to its terminals.
Transmission LED ON/OFF
Battery cover
Figure 3a. Battery Connection for CR123A
button
Tamper
switch
Figure 3b. Battery Connection for CR17450
Note: When the battery first makes contact, the alarm horn may sound for one
second. This indicates that the battery is connected properly.
Close the cover, then press the test button (see fig. 1) for about 5 seconds, (for further details see par. 3.6).
3.4 Resetting the Transmitter Module and Enrolling its PowerCode ID
The detector has a wall / rear tamper switch to alert removal of detector. The tamper switch actuator, extending through a hole in the base (see Figure 3), is pressed against the bracket when the unit is attached to the bracket.
Removal of the unit from the bracket will cause the switch contacts to open, creating a tamper event, which will be reported by the transmitter to the control panel. Refer to the control panel’s installation instructions and follow the procedure given there for enrolling transmitter IDs in the control panel's memory. When required to initiate a transmission for enrollment, press the smoke detector’s test button (see fig. 1) until the built-in horn sounds, or press the tamper switch.
Note: It is much easier to carry out this operation while holding the MCT-426 / MCT-427 in your hand, close to the control panel.
2
D-302151 MCT-426, MCT-427 Installation Instructions
Loading...
+ 4 hidden pages