Visonic K980D User Manual

/2*,&$/2*,&$$0
Dual-Technology Microwave/PIR Intrusion Detectors
)($785(6
Cylindrical optics improves detection and false alarm immunity.
True Motion Recogniti on™ (TMR) algorithm ( patented) distin-
guishes between the true motion of a human body and other disturbances which invariably cause false alarms
DRO-stabilized MW microstrip technology (patented)
MW Motion Simulator simulates the effect of a human body
moving in the MW field (for MW self-test - patent pending)
Range control for adjusting the MW coverage
Integral swivel bracket for wall or ceiling installation
Sealed chamber protects the pyroelectric element from insects.
PIR self-test by applying a short heat pulse (LOGICA-AM only)
Programmable motion event
counter (1 or 2 events)
Simple-to-use, t w o-position vertical adjust ment
TEST input to enable/disable the walk test LED remotely (per new European standard)
Open collector t rouble output
Anti-masking protection
(LOGICA-AM only)
White l ight protection.
63(&,),&$7,216
Input Voltage: 9 to 16 VDC Current Drain: About 28 mA @ 12 VDC
PIR SECTION Detector: Low noise dual -element pyroelectric sensor Tripping Indicati on: LED flashes green for up to 5 seconds Motion Event Verification Counter: Selec table, 1 or 2 events Lens Data (No. 105DH - see Figure 2)
No. of Beams: 36 in two layer s (curtain beams in bottom layer) Max. Coverage: 12 x 12 m (40 x 40 ft) / 90 field of view
Vertical Adjustment: FAR and NEAR, by sliding the circuit board
along a two-positi on scale.
MW SECTION Oscillator: Microstrip DRO-stabili zed Doppler module Frequency: 10.525 or 2.45 GHz Detection Range: Adjustable from 25% to 100% (3 m to 12 m) Tripping Indicati on: LED glows green for up to 5 seconds
ALARM, TAMPER & TROUBLE DATA Alarm Indication: LED glows red for 1.3 to 5 seconds if both
detectors trip Relay Contacts: N.C., rat ed at 0.1 A resistive / 30 VDC; 18 resistor in series with cont acts
Alarm Duration: 1.3 to 5 seconds Tamper Switch: N.C., rated at 50 mA resist ive / 30 VDC Trouble Output: Open col lector, 100 mA max., with 18
in series and 47 k
Masking Detection Delay (LOGICA-AM only): About 60 seconds Trouble/ Masking Indicat ion: LED alter nately f lashes gr een and
red and TRB output pulls LOW until t he detector is r eset.
pull-up (see Figur e 11)
resistor
MOUNTING Height: Up to 3.6 m (12 ft) Room Size: 8 - 12 m (24 -
40 ft) in the “FAR” position; 2 - 8 m (6 - 24 ft) in the NEAR position.
Bracket Adjustment: 20 downward, 20 left and right.
Installation Options: Surface or corner (without bracket); surface or ceiling (with bracket)
ENVIRONMENTAL RFI Protection: >30 V/m up to
1000 MHz.
Operating Temperatur es:
-10C to 50C (14F to 122F).
Storage Temperatures: -20C to 60C (-4F to 140F).
Compliance with Standards: Complies with Part 15 of the FCC
Rules. Meets the European Counc il Dir ec ti ve EMC 89/336/ EEC & 92/31/EEC, and bears the CE mark and certif ication.
PHYSICAL Size (H x W x D): 117 x 65 x 47 mm (4-5/8 x 2-9/16 x 1-7/8 in.). Weight: 109 g (3.85 oz) without bracket, 124 g (4.4 oz) with
bracket.
PATENTS U.S. Patents 5,237,330 and 5,693,943 (other patents pending)
Installation Instructions
Figure 1. General View
Figure 2. Coverage Pattern
,167$//$7,21
,QVWDOODWLRQ+LQW V
To minimize false alarms:
Do not aim at heat sources
Mount on solid, st able surfaces
DE1835 1
Do not expose to air drafts Do not install outdoors
Prevent direct sunlight from
reaching the detector
Do not install behind partitions
Keep wiring away from electrical power cables
In addition, a few important rules mus t be observed while selec ting a mounting location:
Microwave radiation passes through glass and non-metallic walls.
A.
Be sure to adjust the MW range s o that it does not exceed the room limits, or else motion in the next room or moving traffic along the outer side of the wall will cause the MW detector to trip.
Large reflecting objects (es pecially metals) in t he coverage area
B.
can distort the mi crowave detector's coverage pattern. If two LOGICA units are inst al l ed i n the same room or on opposite
C.
sides of a shared wall, they should not fac e each other and m ust be mounted at least 2 meters apart.
Do not install the LOGICA in places where one of the two
D .
detector circuits alarms constantly or intermittently, due to environmental interference.
LOGICA-AM users are advised to mount the unit in locations
E .
where inadvertent approach to less than 1 m (3 ft) from the detector is unlikel y to occur.
0RXQWLQJZLWKRXW6 ZL YHO%UDFNHW
A .
Remove the front cover as s hown in Figure 3.
Figure 3. Cover Removal
B .
Loosen the vertical adjustment screw, slide the PCB down and remove it via the “keyhole” (see Figure 4).
C .
Pull the PCB straight out and put it aside until required again.
D .
Refer to Figure 5 and punch out the mounti ng knockouts at the rear wall of the base (for surface mounting) or at the angled sides (for corner mounting).
Punch out any one of the wiri ng knockouts shown in Figure 5.
E.
Hold the base against the wall at the selected installation
F.
Figure 4.
location, mark the points for drilling and drill the holes (inser t the plastic dowel s supplied if nec essary).
Pass the wires through the wiring inlets into the base and
G.
attach the base to the wall using the screws supplied. Return the PCB to its pl ace within the base.
H.
Proceed to wire the t erminal block as instruct ed in Para. 3.5.
I.
PCB Removal
Figure 5. Inside View
0RXQWLQJZLWK6ZL YHO  %U DFNHW
A .
Remove the front cover as s hown in Figure 3.
B .
Remove the PCB (see Figure 4) and put it temporarily aside.
C.
Punch out the large knockout in t he round bulge at the t op part of the base (see Figure 6)
Figure 6. Attaching the Bracket
D .
Assemble the bracket as shown in Figure 6.
E .
Rotate the bracket to the desired position (refer to Figure 7) but do not yet tighten the screw fully.
Punch out the selected wiring
F .
knockouts in the bracket base (see Fig. 8).
Press the bracket against the
G .
mounting surface and mark the points for drilling. Drill out the holes and insert plastic dowels, if necessary. Attach to the wall with the 2 screws.
Route the cable through
H .
the bracket and into the detector as shown in Figure 9.
Attach the bracket to the
I .
mounting surface us ing the two screws supplied.
Tilt down or swivel the
J.
detector to face t he desired direction. Fig. 10 s hows the various possibilities of tilting and swiveling.
Figure 7.
Wall and Ceiling Positions
Figure 8. Bracket Rear
Figure 9. Routing the Cable
2 DE1835
Figure 10. Tilt/Swivel Limits
:LULQJ
Refer to Figure 11 and connect wires to the terminal block in the following order:
Terminal: TAMP (tamper switch)
Connect to: Normally closed 24-hour tamper zone of the control panel.
Details: Upon remo­val of the cover, the tamper contacts will open.
Terminal: NC (alarm relay) Connect to: Normally closed burglar protect i on zone. Details: Upon alarm or power failure, the output relay's normally
closed contacts open.
Terminal: TRB (trouble output) Connect to: 24-hour trouble zone Details: The TRB open collector output will be grounded upon
detector malfunction or upon masking (LOGICA-AM only), thus triggering the trouble zone.
Alternative: A buzzer or an interface relay may be connec ted acros s the TRB output and the 12 VDC (+) terminals.
Terminal: TST (TES T i nput) Connect to: +12 VDC or ground potential (depending on the setti ng
of DIP switch SW-3) via a test switch. Details: Applying the trigger voltage to the TST input will enable the
dual color LED for walk testing.
Terminals: 12 V (+) and (–) Connect to: A power source within the range of 9 to 16 VDC. Details: It is advisable to connect the power source only after all
other connections have been completed and recheck ed. Dis- connect the AC mains from the alarm control panel and veri fy that t he vol tage supplied to the detector is above 9 Volts with the backup bat tery as the only power source.
Use RTV to seal the base opening(s) to prevent insects from
Note:
entering the detector.
Figure 11. Terminal Block Wiring
9LVXDO,QGLFDWLRQV
The dual color LED is used to signal various alarm and trouble messages as shown in Table 1 below:
Table 1. Interpreting the Visual Indications
Visual Indication
None Steady green (5 s) Flashing green Steady red (5 s) Flashing red and
green (alternately)
Notes:
1. D uring walk testing, the green light glows steadily (MW detection) or flashes
(PIR detection), depending on which one of the two detectors discovered the movement first. Upon subsequent discovery of the movement by the other detector, the green light goes off and the red light glows (alarm).
2. If the LED maintains alternate red and green flashing beyond the warm-up
period, a malfunction or masking has been diagnosed. Replace the unit without delay.
Significance
No detection MW walk-test detection
PIR walk-test detecti on
Alarm: MW + PIR detection
- Trouble or masking is being detected by the self t est circuitry, or
- Initial warm-up routine (stops 30 seconds after power up).
0RGH6HOHFWRU
The DIP switch mode selector is mounted on the unit’s PC board (see Figure 5). It controls four functions as demons­trated in Figure 12 and as detailed in Table 2.
Figure 12. DIP Switch Mode Selec tor
Table 2. Mode Selector Switc h functions
Switch State Function Default SW-1 OFF One motion event trips the PIR ON
ON Two motion events trip the PI R
SW-2 OFF The walk-test LED is disabled* ON
ON The walk-test LED is enabled
SW-3 OFF Ground potential (–) enables the LED; OFF
floating terminal disables the LED
ON Floating terminal (or +12VDC) enables
the LED; ground potential disabl es test.
SW-4 OFF Output relay opens upon alarm OFF
ON Output relay opens upon alarm and
also when trouble is detected.
The LED may be enabled remotely with a test sw itch connected to
*
the TST input as shown in Figure 11.
9HUWLFDO$GM XVW PHQW
The vertical adjustment scale for the PIR detector is loc ated at the lower right edge of the PC board (refer to Figure 5). Two positions are available - FAR and NEAR. All new LOGICA units are set to t he FAR position. To adjust, loosen the vertic al adjustment screw, slide the PC board along the vertical slot until the pointer indicates the required position on the scale (s ee Figure 13). When done, tight en the adjustment screw firmly.
7KH3RZHUXS3URFHVV
After connecting the (+) and (–) t erminals to the power source, the LOGICA starts a 60-sec ond warm-up period, indicated by al ternate flashing of the green and red lights .
Caution! If the alternate flashing of the red and green lights does not stop within 60 seconds , a failure has been detected by the self-test circuitry, or, if you are dealing wi th the LOGICA-AM, the unit may be masked (refer to Para. 3.6).
:KDW+DSSHQVLQ&DVHRI0DVNLQJ"
If an attempt is made to sti ck mask ing material over the l ens or put a masking object close to the lens (LOGICA-AM only), a trouble alert will result about 60 seconds after m asking:
The LED will flash red and green alternately;
The TRB output will pull to ground and will remain grounded until
the detector is reset (see Para. 3.14 for procedure).
DE1835 3
Figure 13. Vertic al Adjustment
6HWWLQJWKH0RWL RQ(YHQW &RXQWHU
If you wish to set the PIR detector for maximum false alarm immunity, shift DIP switch No. 1 (SW-1) to ON. In this position, two consecutive motion events are r equi red t o tr i p the PI R detec t or . For faster catch perf ormance, shift SW -1 to OFF. In t his position, only one motion event is required to trip the PIR detector.
3,5:DON7HVW
A. Rotate the MW RANGE control ful ly counterclockwise to MIN. B. Verify that DIP switch SW-2 is set to ON (the LED is enabled). C. Mount the front cover in pl ace. D. Walk into t he detector' s field of view at the expected far edge
of the coverage area. The green l ight should flas h for up to 5 seconds each time your motion is detec ted.
Note: If the green light glows steadily for up to 5 seconds, your motion has been detected by the MW detector .
E. If PIR detecti on is not obtai ned at the far end of the coverage
area, remove the front cover and re-adjust the vertical position. Replac e the cover and retest .
0::DON7HVW
A. Remove the front cover. B. Verify that the MW RANGE contr ol is set fully count ercloc kwis e
to MIN and that DIP switch SW-2 is set to ON (LED is enabled).
C. Start by moving into the cover age area at the far edge. The
LED should light green for up to 5 seconds each time your motion is detect ed.
D. If your motion was not detec ted at the far edge, advance the
MW RANGE control slightly clockwise toward MAX and try again until your motion is detected reliably at the far edge.
Caution! The MW detecti on range must not exceed the far edge of the desired coverage area.
E. W alk across the coverage area at various ranges and verify
that your motion is consistentl y detected.
Note: I f PIR trips interfere wit h your test, disable the PI R by inserting a small pi ece of cardboard in front of the sensor.
$ODUP:DON7HVW
A. Set DIP swi tch SW-2 to ON (the LED is enabled). B. Install the front cover in place. C. Walk acros s the detector’s field of vi ew in different directi ons,
at various distances from the detector, and verify proper alarming throughout the detector's coverage area (the red light glows for 1.3 to 5 seconds).
D. When done, remove the cover and set DIP switch SW -2 to
OFF to prevent unauthorized tracing of the coverage pattern.
E. Remount the cover and fasten it to the base usi ng the small
screw at the bottom.
Attention! To assure pr oper functi on of the det ector, the range and coverage area should be checked at least twice a year. Furthermore, it is r ecommended that users perform a walk test at the far end of the c overage patt ern to ass ure an al arm signal prior to each time the alarm system is armed.
5HVHWWLQJDIWHU 7U RXEOH
In case of trouble alert, proceed as follows:
Search for masking mat erial on t he lens or a mas king object in front of the lens and remove them, if found.
Reset the detector by walk tes ting: c ross its f ield of view at the far end, causing it to alarm several times.
If everything is bac k to nor mal, t he LED should s top f lashi ng, and the TRB output should revert to the open-circuit state (dis­connected from the ground).
Note: If walk testing does not cause the trouble alert to stop, recheck for masking. Once masking is ruled out, the trouble is probably due to defective PIR or MW circuitry. Replacing the detector unit will solve this problem.
/2*,&$ $0
0,6&(//$1(286&200(176
This device has been tested and f ound to com ply with the li mit s for a Class B digital device, pursuant to Part 15 of the FCC Rules. Thes e limits are designed t o provide reasonable protection against harmful interference in residential installations. This equipment generates, uses and can radiate radio frequency energy and, if not instal led and used in accordance with the instructions, may cause harmful interference to radio and televis ion reception. However, there is no guarantee that interference will not occur in a particular ins tallation. I f
:$55$17<
:$55$17<
Visonic Ltd. and/or its subsidiaries and its affiliates ("the Manufacturer") warrants its products hereinafter referred to as "the Product" or "Products" to be in conformance with its own plans and specifications and to be free of defects in materials and workmanship under normal use and service for a period of twelve months from the date of shipment by the Manufacturer. The Manufacturer's obligations shall be limited within the warranty period, at its option, to repair or replace the product or any part thereof. The Manufacturer shall not be responsible for dismantling and/or reinstallation charges. To exercise the warranty the product must be returned to the Manufacturer freight prepaid and insured.
This warranty does not apply in the following cases: improper installation, misuse, failure to follow installation and operating instructions, alteration, abuse, accident or tampering, and repair by anyone other than the Manufacturer.
This warranty is exclusive and expressly in lieu of all other warranties, obligations or liabilities, whether written, oral, express or implied, including any warranty of merchantability or fitness for a particular purpose, or otherwise. In no case shall the Manufacturer be liable to anyone for any consequential or incidental damages for breach of this warranty or any other warranties whatsoever, as aforesaid.
This warranty shall not be modified, varied or extended, and the Manufacturer does not authorize any person to act on its behalf in the modification, variation or extension of this warranty. This warranty shall apply to the Product only. All products, accessories or attachments of others used in conjunction with the Product, including batteries, shall be covered solely by their own warranty, if any. The Manufacturer shall not be liable for any damage or loss whatsoever, whether directly, indirectly, incidentally, consequentially or otherwise, caused by the malfunction of the Product due to products, accessories, or attachments of others, including batteries, used in conjunction with the Products.
this device does cause such int erference, which can be verified by turning the device off and on, the user is encouraged to elim inat e the interference by one or more of the following measures: – Re-orient or re-locate the receiving antenna. – Increase the distance between the device and the recei ver. – Connect the device to an outlet on a circui t different f rom the one
which supplies power to the receiver.
– Consult the dealer or an experienced radio/TV technician.
The Manufacturer does not represent that its Product may not be compromised and/or circumvented, or that the Product will prevent any death, personal and/or bodily injury and/or damage to property resulting from burglary, robbery, fire or otherwise, or that the Product will in all cases provide adequate warning or protection. User understands that a properly installed and maintained alarm may only reduce the risk of events such as burglary, robbery, and fire without warning, but it is not insurance or a guarantee that such will not occur or that there will be no death, personal damage and/or damage to property as a result.
The Manufacturer shall have no liability for any death, personal and/or bodily injury and/or damage to property or other loss whether direct, indirect, incidental, consequential or otherwise, based on a claim that the Product failed to function.
However, if the Manufacturer is held liable, whether directly or indirectly, for any loss or damage arising under this limited warranty or otherwise, regardless of cause or origin, the Manufacturer's maximum liability shall not in any case exceed the purchase price of the Product, which shall be fixed as liquidated damages and not as a penalty, and shall be the complete and exclusive remedy against the Manufacturer.
Warning: The user should follow the installation and operation instructions and among other things test the Product and the whole system at least once a week. For various reasons, including, but not limited to, changes in environmental conditions, electric or electronic disruptions and tampering, the Product may not perform as expected. The user is advised to take all necessary precautions for his/her safety and the protection of his/her property.
6/91
VISONIC LTD. (ISRAEL): P.O.B 22020 TEL-AVIV 61220 ISRAEL. PHONE: (972-3) 645-6789, FAX: (972-3) 645-6788 VISONIC INC. (U.S.A.): 10 NORTHWOOD DRIVE, BLOOMFIELD CT. 06002-1911. PHONE: (860) 243-0833, (800) 223-0020 FAX: (860) 242-8094 VISONIC LTD. (UK): UNIT 1, STRATTON PARK, DUNTON LANE, BIGGLESWADE, BEDS. SG18 8QS. PHONE: (01767) 600857 FAX: (01767) 601098
Internet Web Site: www.visonic.com VISONIC LTD. 1999 LOGICA DE1835- (REV. 1, 5/99)
4 DE1835
Loading...