Visonic GLASSTECH User Manual

GLASSTECH
Glass Break Detector
1. INTRODUCTION
1. INTRODUCTION
1. INTRODUCTION1. INTRODUCTION
The GlassTech is a revolutionary, microprocessor-controlled glass-break detector using original sound image recognition methods that differ from those used by other glass break detectors. Sophisticated techniques are applied in the GlassTech for reliable distinction between the sound pattern created when breaking glass framed in an outer wall, and the sound patterns created when breaking unframed glass, bottles, plates, etc.
The GlassTech's remarkable qualities were achieved by systematic analysis of the acoustic effects in the frequency, time and amplitude domains. Diverse room reverberations were also studied, to discover how local acoustics affected the recognition of true as well as false alarms.
The digital signal processing carried out by the GlassTech relates to several time phases, from the initial impact on the glass window to the final sound of falling fragments. Sounds undergo statistical analysis based on 18 different sound signatures. A
2. SPECIFICATIONS
2. SPECIFICATIONS
2. SPECIFICATIONS2. SPECIFICATIONS
Supply Voltage: 9 - 16 VDC Current Consumption: 20 mA approx. (standby), 25 mA approx.
(on alarm). Maximum Detection Range: 10 m (30 ft) radius at 170° if glass
size is 30 x 60 cm (1 x 2 ft) to 3 x 3 m (10 x 10 ft); 7m (21 ft) radius at 170° if glass size is 30 x 30 cm (1 x 1 ft) to
30 x 60 cm (1 x 2 ft).
Glass Types: Plate, tempered, wired & laminated. Glass Size: 0.3 x 0.3 m (1 x 1 ft) to 3 x 3 m (10 x 10 ft). Glass Thickness: Plate: 2.4 to 6.4 mm (3/32 to 1/4");
tempered: 3.2 to 6.4 mm (1/8 to 1/4 in.); laminated: 3.2 to 6.4 mm (1/8 to 1/4 in.); wired: 6.4 mm (1/4 in.).
Room Size: Not larger than 15 x 15 m (45 x 45 ft); Not smaller than 3 x 3 m (10 x 10 ft).
Min. Distance from Protected Glass: 1.2 m (4 ft). Sensor Type: Electret Microphone. Relay Output: Normally closed (fail-safe) contacts with 18
resistor in series. Rating - 0.1A resistive / 30 VDC.
Alarm Duration: Relay contacts open for about 3 sec. Alarm Indications: GREEN LED flickers in response to audio
sounds; lights steadily while in TEST mode. RED LED - lights for 3 seconds on alarm, and latches ON if the
LATCH jumper is set to ON.
sound that does not qualify as a true alarm is not automatically identified as a false alarm unless positively recognized as such.
The GlassTech has an alarm memory that can be enabled or disabled with a jumper. If the alarm memory is enabled, the red alarm LED illuminates and latches upon alarm (see para. 3.7).
An important feature of the GlassTech is that upon power up, it automatically runs self-test diagnostic routines (see para. 4.3A), and checks the local ambient conditions. The diagnostic self-test is repeated periodically, to verify trouble-free operation of the electronic circuitry. Models with the -AM suffix also run an anti­masking routine (see Para. 4.3B) at 30 minute intervals, to verify that the microphone is neither masked nor damaged.
The GlassTech can take part in perimeter zone protection, without worrying about occasional shattering of glassware, bottles and food plates or other sounds produced by common appliances and utensils.
Power-Up Self Test Indication: Green and red LEDs flash alternately.
Trouble Indication: Green and red LEDs light steadily. Trouble (TRB) Output: Open collector type, 100 mA max. Test Period Timeout: 5 minutes. Tamper Switch: Normally closed. Rating - 50 mA resistive / 30
VDC. Do not wire in series with the alarm relay contacts.
RFI Immunity: >30 V/m up to 1 GHz (not verified by UL). Mounting: Surface mounting on walls and ceilings. Optional Mounting Accessories:
BR-1: swivel bracket, adjustable 30° down and 45° left, 45° right. BR-3: same as BR-1, with ceiling adapter.
Operating Temp.: -10°C to 50°C (14°F to 122°F). Storage Temp.: -20°C to 60°C (-4°F to 140°F). Dimensions (H x W x D): 68 x 51 x 23 mm (2-11/16 x 2 x 7/8 in.). Weight: 50 gr (1-3/4 oz). Color: White. Patents: U.S. Patents 5,515,029 and 5,608,377.
MODELS AVAILABLE GLASSTECH (UL-Listed): Surface-mounted model. GLASSTECH-AM (UL-Listed): Surface mounted model with
anti- masking. Compliance with Standards: EN 50131-1 Grade 2, Class II
3. INSTALLATION
3. INSTALLATION
3. INSTALLATION3. INSTALLATION
3.1. Mounting - General Guidelines
The GlassTech is suitable for inclusion in perimeter loops that protect occupied and unoccupied sites.
The protected pane should measure at least 30 x 30 cm (1 x 1 ft). Optimum results will be obtained with glass panes sized 30 x 60 cm (1 x 2 ft) to 3 x 3 m (10 x 10 ft). Glass types and thickness are given in Section 2.
The detection range of the GlassTech is exemplified in Figure 1, where two windows are protected by a single detector. Since room acoustics influence the effective detection range, typical rather than maximum ranges are shown.
Note:
For glass panes between 30 x 30 cm (1 x 1 ft) and 30 x 60 cm (1 x 2 ft), the range is limited to 7 m. (21 ft).
Figure 1. Coverage Pattern
Window
1
DE1896- GlassTech Installation Instructions 1
170°
Window
2
GlassTech
You will obtain best detection and maximum false alarm protection by observing the following rules:
A. Select the location carefully: Mount the GLASSTECH in the
same room with the protected glass pane, preferably on a wall facing the glass, or on an adjoining wall or on the ceiling.
B. Do not mount the detector on the same wall as the
protected glass pane.
C. Observe room size limits: Avoid installation in rooms larger
than 15 x 15 meters (45 x 45 ft) and sites where the ceiling is higher than 4.5 m (15 ft).
IMPORTANT: Adding detectors in a room larger than
specified will not overcome this limitation.
D. Do not install too close to the glass: Mount the detector at
least 1.2 m (4 ft) away from the protected glass, or from any wall with glass.
E. Do not install in rooms smaller than 3 x 3 m (10 x 10 ft): It
would be impractical to install in display windows or display cases (that have two or more flexible walls - glass, plywood, plexiglass).
F. Keep away from noise sources: Electrical power cables, air-
conditioners, air compressors, blowing air ducts, and loud noise sources such as powerful speakers, doors etc.
G. Avoid installation in room corners: Room corners are not
an ideal mounting location, especially if the protected glass is smaller than 30 x 60 cm (1 x 2 ft).
H. Do not install at all in very noisy areas: Avoid small
kitchens and rooms with noisy machinery or production. Multiple sound sources create a difficult environment for glass break detectors.
I. Select a stable mounting surface: Brick and concrete walls
are ideal, drywall is also suitable.
J. Ensure an obstacle-free sound path: A direct line between
detector and protected glass is very important - detection around corners cannot be guaranteed. Internal wooden shutters in the sound path may prevent detection.
K. Never ignore sound muffling, lined or insulated drapes:
All these could adversely affect the detector's performance.
L. Beware of damp places: The unit is not sealed and may fail
to function due to excess moisture.
M. Use a swivel bracket if required: Two optional brackets are
available (see Paragraph 3.6).
Additional points to consider: A. GlassTech is designed to detect shattering of glass framed in an
outside wall. Breaking unframed glass (bottles, plates etc.) within the room will be identified as a false alarm.
B. GlassTech is not designed to detect the breaking of any type of
hinged glass doors. Do not use it for this purpose.
C. Despite the GlassTech's high degree of sophistication, in rare
cases and under specific conditions, certain noise bursts can duplicate the sound image of window glass breakage.
D. The GlassTech is not intended to detect events such as glass
cracking by applying slow pressure or glass breaking by drilling or firing bullets at the glass. Glass break detectors should be backed up by interior detectors.
E. The GlassTech is not guaranteed to detect window breakage if
any type of plastic film is adhered to the inside surface of the glass.
F. The GlassTech is not guaranteed to detect double-glass
window breakage.
G. Before running any wiring, we recommend to mount the detector
temporarily at the chosen location, power it up from a 9 or 12 volt battery and test the effective detection range with a glass break sound simulator (as instructed in Para. 4.2). The test can be repeated several times in several locations until the optimum mounting point is determined.
C. Insert a screwdriver blade into the slot at the right side of the
PCB (see Figure 4) and dislodge the printed circuit board from the right-side retaining tab. Remove the printed circuit board and put it aside carefully.
3.3 Surface Mounting (GlassTech & GlassTech-AM)
The unit can be mounted directly on a flat surface or on an optional swivel bracket (see Paragraph 3.6). Use countersunk head screws (supplied) through the two holes in the base to attach the base firmly to the wall or to the ceiling. Be sure to pass the wires into the base through the wiring inlet. If the wires are routed down from the ceiling, use the vertical wiring channel at the rear of the base. Then carry on as directed in paragraph 3.5.
BASE
MOUNTING
HOLES
IMPORTANT! USE
SCREWS WITH
COUNTERSUNK
HEADS.
WIRING
INLET
WIRING
CHANNEL
INSERT FINGERNAIL HERE
TO REMOVE TRIM STRIP
RETAINER
TAB FOR PCB
PRINTED
CIRCUIT BOARD
FRONT COVER
TEST SWITCH
ACCESS HOLE
TRIM
STRIP
Figure 2. GlassTech - Exploded View
3.5 Mounting - Final Procedure
A. Push the detector's printed circuit board into the base, until it
snaps into place, held firmly by the retainer tabs at both sides.
B. Set the jumpers as required for the particular installation (see
Para. 3.7).
C. Complete the wiring as described in Para. 3.8. D. Remount the front cover. Fasten it with the screw and push
the trim strip back into place.
Caution! with the-AM model, the front cover must be put
in place within 60 seconds after power up. Otherwise, the unit will adapt itself to the "no cover" condition and a trouble alert will result when the cover is put back (see Section 4.3B).
3.6. Optional Mounting Brackets (Fig. 3)
Two optional mounting brackets are available: BR-1 Surface Mounted: Swivel, surface-mounted bracket for
greater flexibility when facing the protected window. The BR-1 is adjustable 30° downward and 45° left, 45° right.
BR-3 – Ceiling Mounted: Swivel bracket kit for easy installation on ceilings. Consists of the BR-1 and a ceiling mounting adapter.
Note: corner
installation is not
recommended
Figure 3. Optional Swivel Mounting Brackets
3.2 Disassembling the Detector (Fig. 2)
To disassemble the detector proceed as follows: A. Pry loose one side of the trim strip, with a fingernail or a small
screwdriver. If the trim strip doesn't come loose easily, try the other side. Remove the trim strip and save it for later use.
B. Remove the screw that fastens the front cover to the base and
take the cover off.
2 DE1896- GlassTech Installation Instructions
Loading...
+ 2 hidden pages