DE1812 3
TST INPUT LOGIC
The dual color LED may be enabled remotely for walk testing with a
test switch connected to the TST input as shown in Figure 6:
TST input grounded - LED active
TST input floating or high (+12V) - LED inactive (unless mode
switch 2 is ON).
3.4 The Power-up Process
After connecting the (+) and (–) terminals to the power source, the
DUET-AM starts a 60-second warm-up period, indicated by alternate
flashing of the green and red lights.
Caution! If the alternate flashing of the red and green lights does not
stop within 60 seconds, a failure has been detected by the self-test
circuitry or, if mode switch 3 is set to ON, the unit may be masked
(refer to Para. 3.5).
3.5 What Happens in Case of Masking?
Attention! The following procedure is true only while mode switch 3
is in the ON position.
If an attempt is made to stick masking material over the lens or put a
masking object close to the lens, a trouble alert will result about 60
seconds after masking:
• The LED will flash red and green alternately;
• The TRB relay will open and will remain so until masking is
removed and the detector is reset (see Para. 3.13 for
procedure).
3.6 Visual Indications
The dual color LED is used to signal various alarm and trouble
messages as shown in Table 1 below:
Table 1. Interpreting the Visual Indications
Visual Indication
Significance
None No detection
Steady green (5 seconds) MW walk-test detection
Flashing green PIR walk-test detection
Steady red (5 seconds) Alarm: MW + PIR detection
Flashing red and - Trouble is being detected (or
green (alternately) masking if mode switch 3 is ON)
- Initial warm-up routine (stops 60
seconds after power up).
Notes:
1. During walk testing, the green light glows steadily (MW detection)
or flashes (PIR detection), depending on which one of the two
sensors discovered the movement first. Upon subsequent discovery
of the movement by the other sensor, the green light goes off and
the red light glows (alarm).
2. If the LED maintains alternate red and green flashing beyond the
warm-up period, a malfunction has been diagnosed (or, if mode
switch 3 is ON, the detector may be masked).
3.7 Mode Selector
The DIP switch mode selector is mounted on the unit’s PC board
(see Figure 4). It controls four functions as demonstrated in
Figure 7.
ON
- 2 MOTION EVENTS
TRIGGER AN ALARM
OFF
- 1 MOTION EVENT
TRIGGERS AN ALARM
ON
1
2
3
4
ON
- ALARM RELAY OPENS
UPON ALARM, MASKING AND
SELF-TEST FAILURE EVENTS.
OFF
- ALARM RELAY OPENS
UPON ALARM AND MASKING
(APPLICABLE TO DUET-AM G3
ONLY) EVENTS.
ON
- LED PERMANENTLY
ENABLED
OFF
- LED DISABLED -
ENABLED VIA TST INPUT
ON
- ANTI-MASKING
ENABLED
OFF
- ANTI MASKING
DISABLED
NOTE:
SWITCH POSITION S SHOWN ARE FACTORY DEFAULTS
Figure 7. DIP Switch Mode Selector
3.8 Vertical Adjustment
The vertical adjustment scale for the PIR sensor is located at the
upper right edge of the PC board (refer to Figure 4). Three positions
are available - FAR, MID and NEAR. All new DUET-AM units are set
to the FAR position. To adjust, loosen the vertical adjustment screw,
slide the PC board along the vertical slot until the pointer indicates the
required position on the scale (see Figure 8). When done, tighten the
adjustment screw firmly.
Figure 8. Vertical Adjustment
Caution! With swivel brackets in use, the effective detection
ranges may differ from those indicated in Figures 2 and 8.
3.9 Setting the Motion Event Counter
If you wish to set the PIR sensor for maximum false alarm
immunity, shift DIP switch No. 1 (SW-1) to ON. In this position, two
consecutive motion events are required to trip the PIR sensor. For
faster catch performance, shift SW-1 to OFF. In this position, only
one motion event is required to trip the PIR sensor.
3.10 PIR Walk Test
A. Rotate the MW RANGE control fully counterclockwise to MIN.
B. Make sure that the LED is enabled, either by setting mode
switch SW-2 to ON or by grounding the TST input.
C. Mount the front cover in place.
D. Walk into the detector's field of view at the expected far edge
of the coverage area. The green light should flash for up to 5
seconds each time your motion is detected.
Note: If the LED lights green steadily for up to 5 seconds,
your motion has been detected by the MW sensor.
E. If PIR detection is not obtained at the far end of the coverage
area, remove the front cover and re-adjust the vertical
position. Replace the cover and retest.
3.11 MW Walk Test
A. Remove the front cover.
B. Verify that the MW RANGE control is set fully counterclockwise
to MIN and enable the LED either by setting mode switch SW-2
to ON or by grounding the TST input.
C. Start by moving into the coverage area at the far edge. The
LED should light green for up to 5 seconds each time your
motion is detected.
D. If your motion was not detected at the far edge, advance the
MW RANGE control slightly clockwise toward MAX and try
again until your motion is detected reliably at the far edge.
Caution! The MW detection range must not exceed the far
edge of the desired coverage area.
E. Walk across the coverage area at various ranges and verify
that your motion is consistently detected.
Note: MW LEVEL CONTROL (see figure 4) may need to be set to
maximum for achieving maximum area coverage.
3.12 Alarm Walk Test
A. Make sure that the LED is enabled, either by setting mode
switch SW-2 to ON or by grounding the TST input.
B. Install the front cover in place.
C. Walk across the detector’s field of view in different directions,
at various distances from the detector, and verify proper
alarming throughout the detector's coverage area (the LED
lights red for 1.3 to 5 seconds).
D. When done, disable the LED by setting set switch SW-2 to
OFF or by disconnecting the TST input (leaving it "floating").