Vishay Nobel WST 3 Operating Instructions, Quick Installation

GB
Transmitter
WST 3
From prog. name W001A100
Operating instructions, Quick installation
Transmitter WST 3
Contents
Introduction
....................................................................... 2
Operating instruction
General .......................................................... 3
Power supply .................................................. 3
Start-up .......................................................... 3
Views in Operating mode ............................... 4
Taring ............................................................. 5
Display of Gross/Net ...................................... 5
Zero setting .................................................... 6
Installation
Mechanical installation ................................... 7
Electrical installation ...................................... 7
Set-up programme deltaCOM ........................ 8
Quick set-up, calibration
General .......................................................... 9
Common parameters ..................................... 9
Data sheet calibration .................................. 13
Dead weight calibration ................................ 16
Parameter survey
...................................................................... 20
Quick set-up list
................................................................ App. 1
1
Operating instructions, Quick installation
Introduction
WST 3 is a high performance transmitter, designed for industrial measuring by means of strain gauge transducers. It can be used as a slave unit, communicating with a network master/PLC by Modbus or Profibus. The network can be used for transmission of commands and measurement values and also for set-up of the transmitter. The compact transmitter is easy to install on a DIN rail or a flat surface.
This instruction includes the basic installation and quick set-up, required for correct measurement with the transmitter.
Additional installation and set-up of more functions, not covered by this description, can also be performed. For a complete transmitter description, refer to publication 600 630:
WST 3 Technical Manual
This description deals with the following points:
Measurement by the WST 3 panel.
Quick installation.
‘Quick set-up’ for WST 3.
Data sheet calibration.
Deadweight calibration in two points.
Set-up programme deltaCOM.
This description does NOT deal with the following points:
Connection of relay output.
Complete set-up (password, filters etc.).
Adjustment of levels and relay functions.
Adjustment of the analogue output.
Using the Modbus and Profibus communication.
Table calibration.
Troubleshooting.
Diagnostics.
Transducer
Digital inputs
Figure 1. All connections to WST 3 are made through terminal block or connector.
2
WST 3
24 V DC
Analogue output
Relay outputs
Modbus
Profibus-DP
Control unit, Profibus
Control unit (deltaCOM) or External display
Transmitter WST 3
Operating instructions
General
This section describes the display and the function key operation when WST 3 is in normal Operating mode.
Power supply
Power supply to the transmitter should not be turned off during week-ends and over­night. Continuous power supply to electronics and transducers prevents moisture condensation in the units.
Start-up
As soon as power is connected to the transmitter, start-up is performed. The text ‘WST 3’, the programme name and the serial number of the transmitter are displayed for about five seconds. Then WST 3 is automatically switched over into Operating mode. (If the transmitter is set for operator start-up, the text ‘Press ENTER to start WST’ is displayed until the function key to the right is pressed and the transmitter enters Operating mode.)
If an error occurs the start-up halts and an error message is displayed. Error codes and error corrections are described in the Technical Manual for WST 3, section 8, Troubleshooting.
As WST 3 enters in Operating mode, the first view is a standard view. It contains the measurement value, status of the used relays (R1:/R2: '1' = on or '0' = off) and at the lower right corner an area with information about the Modbus communication. In this area 'EXT' means serial communication to an external display. An 'address' means that the transmitter is set for Modbus communication with a master unit, and the address flashes as a message to the transmitter is received. If the area is empty this means that the serial communication is not in use.
Net 123.4 kg R1:1 R2:1 001
WST 3
Figure 2. Front view of WST 3 in Operating mode. A weight value and
information about relay status and Modbus address is displayed.
3
Operating instructions, Quick installation
Views in Operating mode
As WST 3 is in Operating mode the views Weight value and Profibus status are always available. The remaining views can be set On or Off by parameters under 'Main menu General'.
Function keys by swiftly pressing From any view, WST 3 switches to Quick set-up mode as the function key
and are used for selection among the available views and
WST 3 can always be switched to the Weight value view.
is pressed for 2 seconds.
Weight value, normal view.
This view is always available. It is the first view displayed after start-up, reset or set-up mode. The upper line displays the actual weight value as net weight (Net) or gross weight. The lower line displays status for the used relays, R1:/R2: '1' = on or '0' = off, and an area for the Modbus address or information about the serial communication.
Zero setting.
This view is made available by parameter 'Zero function'. It displays the actual weight value as net weight (Net) or gross weight.
As gross weight is displayed it can be set to zero by the ENTER-key
.
By zero setting of the gross weight, the actual tare value is also set to zero.
Start up/Reset
Weight value
Always On
Net 123.4 kg R1:1 R2:1 001
Zero setting
Set On/Off in Zero function
Analogue output signal
Set On/Off in More views
Level settings
Set On/Off in More views
Input signal
Set On/Off in More views
S/N:, Progr.
Set On/Off in More views
Profibus status
Always On
Net 123.4 kg Zero
Net 123.4 kg
5.430 V 001
L1 99999.9 kg L2 0.0 kg
0.18200mV/V
R1:1 R2:1 001
S/N: XX-XXXX Progr. XXXXXXXX
Profibus-DP 010
Online
Figure 3. WST 3 in Operating mode can always display Weight value and Profibus status.
Depending on the setting, alternative views can also be displayed.
4
Transmitter WST 3
Analogue output.
This view can be made available by parameter 'More views'. The upper line displays the actual weight value as net weight (Net) or gross weight. The lower line displays the analogue output signal and the Modbus information area.
Level settings.
This view can be made available by parameter 'More views'. The upper line displays the switching level used by 'Level/Setpoint 1' and the lower line displays the switching level used by 'Level/Setpoint 2'.
Input signal.
This view can be made available by parameter 'More views'. The upper line displays the actual transducer input signal in mV/V. The lower line displays status for the used relays, R1:/R2: '1' = on or '0' = off, and the Modbus information area.
S/N:, Progr.
This view can be made available by parameter 'More views'. The upper line displays the transmitter serial number and the lower line displays the name of the installed programme.
Profibus status.
This view is always available. The upper line displays the Profibus address of the transmitter and the lower line contains status information for the Profibus communication.
Taring
Taring means storing the actual gross weight as a tare value and switching WST 3 over to display of net weight. The net weight is the difference between the gross weight and the tare value. Taring of WST 3 is always possible as the weight value is valid. Taring is performed as digital input IN1 (terminal 15) is activated with 24 VDC.
The tare value is automatically set to zero by zero setting of the WST 3.
Display of Gross/Net
By weight display, an area to the left of the weight value displays 'Net' when the net weight is displayed. If the area is empty, the displayed weight is the gross weight. Switching between display of net weight and gross weight takes place as digital input IN2 (terminal 16) is activated with 24 VDC.
5
Operating instructions, Quick installation
Zero setting
Minor correction of the zero setting can be performed during normal operation from the ‘Zero setting’ view, see page 4.
But to perform a basic zero setting of the gross weight, the normal operation must be interrupted and the following sequence carried out with WST 3 in set-up mode. This type of zero setting is a part of the calibration sequences, but a separate zero setting may also be needed, for example if the equipment on the scale has been changed, influencing the weight.
Procedure for basic zero setting
1. Check that the scale is unloaded before performing the zero setting.
2. Switch to set-up mode by holding ESCAPE (
3. Enter the valid password, if this is demanded.
4. The text ‘Main menu Quick set-up’ is displayed. Press ENTER (
5. The first parameter name, ‘Language’, is displayed. Press
for ‘Set zero’ is a live weight value.
6. Press to the left on the lower line.
(The zero setting can be cancelled by pressing
7. Press and hold The cursor disappears and a live weight value is displayed.
8. Press (The ‘Zero offset’ value can be used for set-up of a replacement unit.)
9. Press The display changes to ‘Main menu Exit set-up.’
10. Press The display changes to ‘Save changes? No Esc. Yes’.
a number of times until ‘Set zero’ is displayed. The parameter value
. The parameter value is set to zero and a flashing cursor appears
, read and make a note of the ‘Zero offset’ value in Appendix 1.
.
.
).
for 2 seconds to confirm the new setting.
) pressed for 2 seconds.
)
(Press
11. Press or
Press
12. WST 3 restarts with the selected zero setting.
6
(Esc.) if you do not wish to exit from the set-up mode.)
(No) to cancel the change and return to the previous zero setting,
(Yes) to save the new zero setting in WST 3.
Transmitter WST 3
Installation
Mechanical installation
Each transmitter WST 3 contains several circuit boards, built into a protective plastic housing which can be snap-mounted on a 35 mm wide DIN rail, or mounted on a flat surface by two 4 mm screws. The transmitter should have at least 10 mm free space on each side.
Electrical installation
For the electrical connections to the connector and terminal blocks of the transmitter shielded cables are needed, except for the power supply. All cables should be routed so that electromagnetic interference from power cables is avoided. Cable connection is shown in the diagrams below.
Transducer input
Terminals 1 – 7 (8). Transducer connection should be handled with great care to achieve best measuring data. Integrated transducer cables may not be shortened.
NOTE!
Transducer cables must be routed at least 200 mm away from 230/380 V, 50/60 Hz power cables. By cables with other frequencies or high power, an even wider distance is preferable.
4-wire connection should be used if the integrated transducer cable can be connected directly at WST 3. By 4-wire connection, excitation and sense must be interconnected at the transmitter, see diagram below. The cable shield and
terminal 5 should be
connected to earth via the mounting rail. 6-wire connection should be used if the integrated cable must be lengthened or if several
transducers should be connected to the transmitter. Connect the cable shield and
terminal 5 to earth via the mounting rail. In the diagram
below connections are shown for the junction box SL-4 from Vishay Nobel.
4-wire connection
Excitation +
Excitation -
Signal +
Transducer
Junction box SL-4
Exc.+
J11 J12
Sign.­Exc.-
J13
Sign.+
J14
Exc.+ Sign.­Exc.­Sign.+
Exc.+
Sign.­Exc.­Sign.+
J1
J21 J22
J23 J24
J2
J31
J32
J33
J34
J3
J41 J42
J43 J44 J4
R
Transducer
Transducer
Transducer
7
CAL
J101
J102
J103
J104
J106
J108
J105
J59J58
J107
J10
Signal -
6-wire connection
EXC+
1
SENSE+
2
EXC–
3 4
SENSE–
5
SHIELD
6
SIGN.+
7
SIGN.–
8
CAL
EXC+
1 2
SENSE+
3
EXC–
4
SENSE–
5
SHIELD
6
SIGN.+
7
SIGN.–
8
CAL
Operating instructions, Quick installation
Power supply
Terminals 17, 18. The transmitter is powered by 24 V DC. Rail mounted power supplies can be ordered from Vishay Nobel.
Analogue output
Terminals 24, 25. The measurement value is presented at the analogue output as a current or voltage signal, according to the choice in the set-up. Connect the cable shield to ground, preferably to a ground terminal at the mounting rail.
+24 V DC
0 V (24)
+
17
18
24
25
+
24V
-
OUT+ OUT–
Digital inputs
Terminal 15, 16. Connection of +24 VDC to the digital inputs causes Taring and Gross/Net switching respectively. Connect the cable shield to ground, preferably to a ground terminal on the mounting rail.
Serial communication
Terminals 19 – 23. The transmitter has a serial port for RS-485 on 2-wires or 4-wires with common earth (COM). If necessary, a converter unit can be connected to adapt the interfaces.
The line must have 120 ohm terminating resistors at both ends. At WST 3 they should be mounted on separate terminals and connected according to the diagrams. Refer to manufacturer instructions for termination at the control unit (PC), or at a possible converter unit.
Connect the cable shield to ground, preferably to a ground terminal at the mounting rail.
Taring
Gross/Net
120Ω
120Ω
120Ω
terminal 18
15 IN1 16
19 20 21 22 23
19 20 21 22 23
24 V +
2-wire
*
Terminating resistor on separate
*
terminals at the last unit on the line.
4-wire
*
*
IN2
TXD– TXD+
RXD– RXD+ COM.
TXD– TXD+
RXD– RXD+ COM.
Terminating resistor on separate
*
terminals at the last unit on the line.
Set-up programme deltaCOM
Transmitter WST 3 should be connected to transducer(s) and power supply. Then it is possible to perform a set-up from the front panel or from a connected PC with Windows 95/98/2000/XP/NT4.0. A diskette with the set-up programme deltaCOM is included in the WST 3 delivery. This diskette also contains instructions for connection and set-up of the serial communication between the transmitter and the PC.
Through deltaCOM it is possible to find all modules communicating with the PC, and to study and edit all set-up parameters for these modules.
8
Transmitter WST 3
Quick set-up, calibration
General
Set-up of all parameters in WST 3 can be performed from the control unit by serial communication, using the programme deltaCOM. Set-up can also be performed from the transmitter front panel, for example the ‘Quick set-up’ of certain parameters described in this section.
Calibration is essential to get correct measurement results. Two calibration methods are available in the ‘Quick set-up’: Data sheet calibration, for calibration when transducer data are available and the installation is free from disturbing mechanical forces. Dead weight calibration, normally the most accurate calibration method, where known weights are used to give well defined loads on the scale.
Before selection of calibration method, the value of some common parameters must be set.
All parameter values from the calibration should be noted in the set-up list, see Appendix 1. These values are useful later, if the transmitter must be replaced.
Common parameters
These parameters define: the language, measurement unit and resolution used by the transmitter, and also the capacity and signal type for the analogue output.
Set-up
1. Access ‘Quick set-up’
At normal operation WST 3 displays the actual weight value. Status for the internal relays (R1/R2) in use and the transmitter Modbus address are also displayed.
123.4 kg R1:1 R2:1 001
Press and hold the ESCAPE key for 2 seconds.
Main menu Quick set-up
2 seconds
This switches the transmitter into Set-up mode, displaying the main menu for ‘Quick set-up’. As WST 3 is in Set-up mode, normal measuring functions are interrupted!
9
Operating instructions, Quick installation
2. Showing the parameters.
Press ENTER.
Language English
The first parameter in ‘Quick set-up’ will be displayed.
3. Edit the language (a choice parameter).
‘Language’ is a choice parameter with a number of alternatives available. Press ENTER to make editing possible.
Language English
A cursor starts flashing to the left on the parameter value line.
Press to the previous alternative, until the correct alternative is displayed.
+ to step forwards to next alternative, or press to step backwards
Language (alternatives)
Press ENTER for 2 seconds to accept the displayed alternative.
Language English
2 seconds
The cursor disappears and the displayed alternative is activated.
4. Edit the measurement unit for the transmitter.
By this parameter, the measurement unit for the measurement value is defined. Press + to get parameter ‘Measurement unit’ displayed.
Measurement unit kg
Press and edit the value like in point 3. above.
if the measurement unit should be edited,
10
Transmitter WST 3
5. Edit the transmitter resolution.
With this parameter, the number of decimals and the resolution of the last digit of the measurement value are defined. This parameter influences all measurement values using the measurement unit.
Press
+ to get parameter ‘Resolution’ displayed.
Resolution
0.1 kg
Press like in point 3. on page 10.
In the following examples, resolution with two decimals is used.
6. Edit the transmitter capacity (numeric parameter). This parameter defines the capacity of the transmitter, i.e. the weight value that
corresponds to full range at the analogue output.
Press
if the resolution should be edited, and make the editing
+ to get the parameter ‘Capacity’ displayed.
Capacity
500.00 kg
Press ENTER to make editing possible.
Capacity
0500.00 kg
A cursor starts flashing to the left on the parameter value line, indicating which digit that can be edited.
Press ENTER to move the cursor, step by step to the right in the parameter value, to the digit to edit.
Capacity
0500.00 kg
Press
When necessary, press ENTER again to move the cursor to another digit to edit. Press ENTER for 2 seconds when the capacity parameter value is correct.
+ (or ) until the wanted digit value is displayed (1 in this example).
(repeated)
Capacity
0100.00 kg
Capacity
100.00 kg
2 seconds
The cursor disappears, and the edited parameter value becomes active.
11
Operating instructions, Quick installation
7. Edit the analogue output type.
The signal type for the analogue output is defined by parameter ‘Ana. output type’ that has a number of alternatives.
Press
+ to get parameter ‘Ana. output type’ displayed.
Ana. output type 4-20mA
Press like in point 3. on page 10.
8. Chose a calibration type.
Press
if the parameter should be edited, and make the editing
+ to get the parameter ‘Calibration type’ displayed.
Calibration type Data sheet
The value points out which type of calibration that was performed last time. Two calibration types can be chosen in ‘Quick set-up’: Data sheet and Deadweight.
As a new calibration shall be performed, WST 3 must first be set for editing, indicated by a cursor at the parameter value. Then one of the alternatives must be chosen and accepted.
If a new calibration shall be performed, press ENTER to switch the transmitter into set-up mode.
Calibration type Data sheet
A cursor starts flashing to the left on the parameter value line.
Chose an alternative for the parameter like in point 3. on page 10. When
the calibration can start. The choice of calibration type determines which parameters will follow:
For Data sheet, se point 9. on page 13. For Deadweight, se point 9. on page 16.
is pressed for 2 seconds, the chosen calibration type gets active and
12
Transmitter WST 3
Data sheet calibration
This calibration type can be used when transducer data is available, the load is evenly distributed on the support points and the weighing installation is not influenced by disturbing external forces.
Before editing of the following parameters is started, set-up of common parameters, described in points 1. – 8. on pages 9 – 12 should be performed.
9. Edit the conversion factor.
If the ‘Data sheet’ alternative was chosen at 8. on page 12, next parameter will be ‘Conv. factor’. This parameter defines a constant by which a weight value, expressed in the measurement unit, should be multiplied to be expressed in the data sheet unit. Default value for the parameter, 9.80665, can be used when the data sheet unit is Newton (N) and the measurement unit is ‘kg’. If data sheet unit and measurement unit are equal, the value should be 1.00000.
Press
+ to get the parameter ‘Conv. factor’ displayed.
Conv. factor
9.80665
Press ENTER to make editing possible.
Conv. factor
9.80665
A cursor starts flashing to the left on the parameter value line. Now editing can be performed for each digit individually. See point 6. on page 11 (numeric parameter).
Press ENTER for 2 seconds when the conversion factor is set to a correct value.
Conv. factor
9.80665
2 seconds
Cursor and leading zeros disappear, and the edited conversion factor will be active.
10. Edit the number of transducers.
This parameter defines the total number of support points for the load, including transducers and fixed supports.
Press
+ to get the parameter ‘Number of transd’ displayed.
Number of transd 3
Press like in point 6. on page 11 (numeric parameter).
13
if the parameter value should be edited, and make the editing
Operating instructions, Quick installation
11. Set the rated load for one transducer.
It is assumed that all transducers connected to the transmitter have the same rated load and impedance. The rated load for one transducer, expressed in the data sheet unit used to calculate the conversion factor (see 9. on page 13), should be entered.
NOTE! If the data sheet value is for instance 5 kN, this parameter should be set to 5 000 (N).
Press
+ to get the parameter ‘Rated load’ displayed.
Rated load
2000.0
Press like in point 6. on page 11 (numeric parameter).
12. Set the rated output for the transducers.
Rated output for each transducer, a value in mV/V, is given in the data sheet. For fixed support points the rated output should be set to ”0.00000”.
Press
if the parameter value should be edited, and make the editing
+ to get the parameter ‘Rated output 1’ displayed.
Rated output 1
2.03900 mV/V
Press like in point 6. on page 11 (numeric parameter).
Parameters will follow for the number of support points given at 10. on page 13. Set the parameter value to the rated output for each transducer/fixed support.
13. Set the scale to zero.
This parameter displays the weight value with the actual settings (but with one decimal more than what is set in ‘Resolution’). Use it to set the weight value to ‘zero’.
if the parameter value should be edited, and make the editing
Press
+ to get parameter ‘Set zero’ displayed, and check that the scale is unloaded.
Set zero XXXX.XXX kg
Press ENTER to set the parameter value to zero.
Set zero +0000.00 kg
The value is set to zero with leading sign and a flashing cursor. Press ENTER for 2 seconds.
Set zero
0000.000 kg
2 seconds
The cursor disappears and the zero setting is accepted.
14
Transmitter WST 3
14. Read the zero offset.
By installation of a replacement transmitter later, it is useful to know the total zero offset value for the scale.
Press
+ to get parameter ‘Zero offset’ displayed.
Zero offset X.XXX kg
Make a note of the zero offset value in the Quick set-up list, appendix 1.
15. Exit ‘Quick set-up’.
Press ESCAPE to get to ‘Main menu Exit set-up’.
Main menu Exit set-up
16. Save the changes.
Before ‘Quick set-up’ is closed, the new parameter values should be saved, i.e. copied to a specific memory in the transmitter. Alternatively the new values can be cancelled, and all parameters will resume the values they had before ‘Quick set-up’ was started.
Press ENTER to get the sub menu displayed.
Save changes? No Esc. Yes
(Press Press
Press In both cases ‘Quick set-up’ is finished. The transmitter switches over to
Operating mode, displaying a measurement value that depends on the load and the valid parameter values.
if you do not wish to exit from the set-up mode.)
to answer ‘Yes’, and save the new parameter values.
to answer ‘No’, and cancel the new parameter values.
000.00 kg R1:1 R2:1 001
The scale is now ready for use.
15
Operating instructions, Quick installation
Dead weight calibration
This is the most accurate calibration type. It requires that known weights to at least two-thirds of the scale capacity are available. Below, a dead weight calibration in two points is described.
Before editing of these parameters is started, set-up of common parameters, described in point 1. – 8. on pages 9 – 12 should be performed.
9. Set the value for calibration point 1.
If the ‘Deadweight’ alternative was chosen at 8. on page 12, next parameter will be ‘Value cal. p.1’. This parameter defines the known load on the scale for the lower calibration point.
Press
+ to get the parameter ‘Value cal. p.1’ displayed.
Value cal. p.1 X.XX kg
The displayed parameter value is the load on the scale that was set for the lower calibration point in the last calibration, normally zero (= unloaded scale).
Press ENTER.
Value cal. p.1 XXXX.XXX kg
Actual measurement value for the scale is displayed (as a ‘live’ weight value) with a cursor and one decimal more than what is set in parameter ‘Resolution’. Check the load on the scale (normally unloaded).
Press ENTER again to make editing possible.
Value cal. p.1 +0000.00 kg
The displayed parameter value is the value for the lower calibration point from the last calibration, with leading sign and a cursor.
The parameter value can be edited, according to point 6. on page 11 (numerical parameter), to correspond to the actual load on the scale, normally zero.
Press ENTER for 2 seconds.
Value cal. p.1 X.XX kg
2 seconds
This finishes the editing and the load that is set for the lower calibration point is displayed without cursor.
16
Transmitter WST 3
10. Set the value for calibration point 2.
This parameter defines the known load on the scale for the higher calibration point.
Press
+ to get the parameter ‘Value cal. p.2’ displayed.
Value cal. p.2
500.00 kg
The displayed parameter value is the load on the scale that was set for the higher calibration point in the last calibration.
Press ENTER.
Value cal. p.2 XXXX.XXX kg
Actual measurement value for the scale is displayed (as a ‘live’ weight value) with a cursor and one decimal more than what is set in parameter ‘Resolution’.
Load the scale with known weights to at least two thirds of the scale capacity. Press ENTER again to make editing possible.
Value cal. p.2 +0500.00 kg
The displayed parameter value is the value for the higher calibration point from the last calibration with leading sign and a cursor.
The parameter value can be edited, according to point 6. on page 11 (numerical parameter), to correspond to the actual load of known weights on the scale.
Press ENTER for 2 seconds.
Value cal. p.2 XXX.XX kg
2 seconds
Editing is finished and the load that is set for the higher calibration point is displayed without cursor.
11. Read the transducer signal for calibration point 1 (read only).
By possible installation of a replacement unit later, it is useful to know the values of the transducer signal for the two calibration points.
Press
+ to get parameter ‘Transd.sign. p.1’ displayed.
Transd.sign. p.1 X.XXXXX mV/V
Make a note of the parameter value in the Quick set-up list, appendix 1.
17
Operating instructions, Quick installation
12. Read the transducer signal for calibration point 2 (read only).
Press
+ to get parameter ‘Transd.sign. p.2’ displayed.
Transd.sign. p.2 X.XXXXX mV/V
Make a note of the parameter value in the Quick set-up list, appendix 1.
13. Set the scale to zero.
This parameter displays the weight value with actual settings (but with one decimal more than what is set in ‘Resolution’). Use it to set the weight value to ‘zero’ for the unloaded scale.
Press
+ to get parameter ‘Set zero’ displayed, and check that the scale is unloaded.
Set zero XXXX.XXX kg
Press ENTER to set the parameter value to zero.
Set zero +0000.00 kg
The value is set to zero with leading sign and a flashing cursor. Press ENTER for 2 seconds.
Set zero
0000.000 kg
2 seconds
The cursor disappears and the zero setting is accepted.
14. Read the zero offset.
By possible installation of a replacement unit later, it is useful to know the total zero offset value for the scale.
Press
+ to get parameter ‘Zero offset’ displayed.
Zero offset X.XXX kg
Make a note of the zero offset value in the Quick set-up list, appendix 1.
18
Transmitter WST 3
15. Exit ‘Quick set-up’.
Press ESCAPE to get to ‘Main menu Exit set-up’.
Main menu Exit set-up
16. Save the changes.
Before ‘Quick set-up’ is closed, the new parameter values should be saved, i.e. copied to a specific memory in the transmitter. Alternatively the new values can be cancelled, and all parameters will resume the values they had before ‘Quick set-up’ was started.
Press ENTER to get the sub menu displayed.
Save changes? No Esc. Yes
(Press Press
Press In both cases ‘Quick set-up’ is finished. The transmitter switches over
to Operating mode, displaying a measurement value that depends on the load and the valid parameter values.
if you do not wish to exit from the set-up mode.)
to answer ‘Yes’, and save the new parameter values.
to answer ‘No’, and cancel the new parameter values.
000.00 kg R1:1 R2:1 001
The scale is now ready for use.
19
Operating instructions, Quick installation
Parameter survey
Operating mode
Start up/Reset
Weight value
Set-up mode,
Quick set-up
123.4 kg
R1:1 R2:1 001
for 2 seconds
Enter password:
(Wrong)(Correct)
Main menu
Quick set-up
Shown only if 'Security lock' is On.
Main menu
Exit set-up
Calibration type
Data sheet
Conv. factor
9.80665
Number of transd
3
Rated load
2000.0
Language
English
Measurement unit
kg
Resolution
0.1 kg
Capacity
500.0 kg
Ana.output type
4-20mA
Calibration type
Dead weight
Value cal. p.1
0.0 kg
Value cal. p.2
500.0 kg
Transd.sign. p.1
0.00000 mV/V
Save changes?
No Esc. Yes
Shown only if any changes have been done.
20
Shown for the entered number of transducers.
Rated output 1
2.03900 mV/V
Rated output 2
2.03900 mV/V
Rated output 3
2.03900 mV/V
Rated output 4
2.03900 mV/V
Set zero
00123.40 kg
Zero offset
0.00 kg
Transd.sign. p.2
1.66631 mV/V
Set zero
00123.40 kg
Zero offset
0.00 kg
The diagram shows the parameters in ‘Quick set-up’ and how
the function keys are used to view the parameters.
Transmitter WST 3
Quick set-up list for WST 3 Address: ...........
Location/Notes: ..............................................................................................................
Programme name: .............................. Ser. no.: ........................ Date: ....................
Parameter Default Set-up name value value
Language English ........................... ...........................
Measurement unit kg ........................... ...........................
Resolution 0.1 ........................... ...........................
Capacity 500.0 ........................... ...........................
Ana. output type 4–20mA ........................... ...........................
Calibration type Data sheet ........................... ...........................
Conv. factor 9.80665 ........................... ...........................
Number of transd 3 ........................... ...........................
Rated load 2000.0 ........................... ...........................
Rated output 1 2.03900 ........................... ...........................
Rated output 2 2.03900 ........................... ...........................
Rated output 3 2.03900 ........................... ...........................
Rated output 4 2.03900 ........................... ...........................
Value cal. p.1 0.0 ........................... ...........................
Value cal. p.2 500.0 ........................... ...........................
Transd.sign. p.1 0.00000 ........................... ...........................
Transd.sign. p.2 1.66631 ........................... ...........................
Zero offset 0.00 ........................... ...........................
Appendix 1
Quick set-up list.
Operating instructions, Quick installation
Publication 600 675 R3 Ä.O.: 950 267 © Vishay Nobel AB, 03-12
Subject to changes without notice.
Loading...