CERTIF IC AT IO N...........................................................................................................................................................................7
ABOUT THIS MANUAL .............................................................................................................................................................7
ABOU T THE VIPER A/C AIR CONDITIONING SER VICE CENTER........................................................7
THE MACHINE.......................................................................................................................................................................................8
BAS IC COMPONE NTS............................................................................................................................................................8
CONTROLS AND CONTROL SYS TEM...................................................................................................................10
FUNCTION SELECTOR KEYBOARD.........................................................................................................................11
STATUS AND ALARM PANEL ..........................................................................................................................................12
MEA SUREMENT SETTING................................................................................................................................................13
PREPAR ATION FOR USE........................................................................................................................................................13
RECHARGE AN A/C SYSTEM.........................................................................................................................................18
3
IN STRU CTIONS M ANUAL
RECOVERING THE REFRIGERANT IN THE HOSES...................................................................................19
EMP TYING THE U SED OIL TANK................................................................................................................................21
CASE CARE...................................................................................................................................................................................21
AIR CONDITIONING HOSE MAINTENANCE.......................................................................................................21
CALIBRA TING THE ELECTRONIC SCALE............................................................................................................21
Congratulations on the purchase of your new VIPER VR-6000 Air Conditioning Service
Center. The following safety inform ation is provided as guidelines to help you operate your
new system under the safes t possible conditions. Any equipment that us es chemicals can
be potentiallydangerous to use when safetyor safe handling instructions are not known or
not followed. The following s afety instructions are to provide the us er with the information
neces sary for s afe use and operation. Please read and retain these instructions for the
co ntinued s afe use of your s ervice s y stem.
SAFET Y INFORMA TION
Every craftsman respects the tools with which theywork. They know that the tools repres ent
years of constantly improved designs and developments. The true crafts man also knows
that tools are dangerous if misused or abus ed. To reduce risk of discomfort, illness or even
death,read, understand and followthe following safetyinstructions . In addition, make certain
that anyone else that uses this equipment, understands and follows these s afety
instructions as well.
4
INSTRUCTIONS MA NUAL
REA D ALL SAFETY INFORMA TION CAR EF UL LY before attempting to install, operate or
service this equipment. Failure to comply with thes e instructions could result in personal
injury and/or propertydamage.
RETAIN THEFOLLOWING SAFETYINFORMATION FOR FUTURE REFERENCE.
Publis hed s tandards onsafetyare available. Theyare listed in ADDITIONAL SAFETY
INFORMATION at the end of this SA FETYSUMMA RY.
TheNational Electrical Code, Occupational Safetyand Health Actregulations, local industrial
codes and local inspection requirem ents also provide a basis for equipment installation,
use and s ervice.
• The following safetyalert symbols identify im portant safety mess ages in this
manual.
• When you see one of the s ymbols s hown here, be alert to the possibility of
pers onal injuryand carefullyread them ess age that follows.
ELECTRICAL SHOCK HAZARDS
WAR NING:
• To reduce the risk of electric shock, unplug the air service center from the
outletbefore attempting any maintenance or cleaning. Turning off controls will
not reduce this risk.
• Do not operate the VR-6000 with a damaged cord or plug — replace the cord or plug
immediately. To reduce the risk of damage to electric plug and cord, disconnect
chargerbypulling on theplug ratherthan the cord.
• An extension cord should not be used unless absolutely necessary. Use of an
improper extens ion cord could resultin a risk of fire and electric shock. Ifextens ion cord
must be us ed, make s ure:
a. That pins on plug of extension cord are the s ame number, size, and shape as
thoseonplugonrecycler.
b.That extens ion cord is properly wired and ingood electrical condition;and
c. That the wire size is large enough forthe lengthof cord as specified below:
Length of cord in feet:2550100150
AWG size ofcord:1612108
MOT ION HAZ ARDS
WAR NING:
• Engine parts that are in motion and unexpected movement of a vehicle can
injure or kill. When working near moving engine part, wear snug fit clothing
and keep hands and fingers away from moving parts. Keep hoses and tools
clear of moving parts. Always stay clear of m oving engine parts. Hoses and
tools can be thrown through the air ifnotkept clear ofmoving engineparts.
• The unexpected movement of a vehicle can injure or kill. When working on a vehicle,
always set the parking brake or block the wheels of the vehicle being s erviced.
FUME HAZARDS
WAR NING:
• FU MES , GASES, AND VAPORS CAN CAUSE D ISCOMFOR T, ILLNESS, AND
DEATH! To reducethe risk ofdiscomfort, illness, or death, read, unders tand,
and follow the following s afety instructions. In addition, make certain that
5
IN STRU CTIONS M ANUAL
anyone else that uses this equipment, understands and follows thes e safety
instructions as well.
• Avoid breathing AC refrigerant and lubricant vapor m ist. Exposure may irritate eyes,
nose, and throat. To remove HFC-134a from the AC system, use service equipm ent
certified tomeet the requirem ents of SAE J2210 (HFC-134a recycling equipment).
• Additional health and safety information may be obtained from additional refrigerant
and lubricant m anufacturers.
• Always perform vehicle servi ce in a properly ventilated area. Never run an engine
withoutproper ventilationforits exhaust.
• Stop the recycling proces s if you develop momentary eye, nose, or throat irritation as
this indicates inadequate ventilation. Stop work and take necess ary steps to im prove
ventilation inthe work area.
HEAT/FREEZ ING HAZARDS
WAR NING:
• When under press ure, refrigerants become liquid. When accidentally
releas ed from the liquid state they evaporate and become gaseous. As they
evaporate,they can freeze or fros tbite tissue very rapidly. When these gases
are breathed, the lungs can be s eriously damaged. If sufficient quantities are
taken into the lungs, death can result. If you believe you have expos ed your lungs to
releas ed refrigerant, seek immediate medical assis tance.
• Refrigerants can cause frostbite and severe burns to exposed skin. Refrigerants are
under pressure and canbe forcibly sprayedin all directions ifcarelessly handled. Avoid
contact with refrigerants and always wear hand coverings and make certain other
exposed s kin is properly covered.
• Refrigerants can also s everely injure or cause permanent blindness to unprotected
eyes. Refrigerants are under press ure and can be forcibly s prayed in all directions if
carelessly handled. Avoid contact with refrigerants andalways wear safetygoggles.
EXPLOSION/FLAME HAZARDS
WAR NING:
• Never recover anything other than the approved refrigerants as specified on
theVR-6000. Alternate refrigerants m ay contain flam mables such as butane
or propaneand can explode or cause a fire. Recovering alternate refrigerants
will also void the warranty on your VIPER VR-6000.
• For generalsafetyreasons, attheend ofthe working day or in between services (when
services do not immediatelyfollow), s ee to it that all valves on hoses and tanks are
clos ed.
ADDIT ION AL SAFE T Y INFO R M AT IO N
For additionalinformation concerning s afety,refer tothe following s tandards.
ANSI Standard Z87.1 Safe Practice For Occupation And Educational Eye And Face
Protection obtainable from the American National Standards Institute, 11 W 42nd St, New
York, NY 10036, Telephone (212) 642-4900, Fax(212) 398-0023, www.ansi.org.
6
INSTRUCTIONS MA NUAL
INTRODUCTION
GENERAL
Thank you for purchasing a VIPER VR-6000 Air Conditioning Service Center. Your VR-6000
is Underwriters Laboratories Inc.® approved, incompliance with SAE J 2210 (1991). We are
dedicated to s olvingthe issues surrounding the s afe containment and proper management
ofCFC’S.Your new VR-6000 incorporates the latest technology and state of the art features
toaid you in servicing air conditioning and refrigeration systems. We hope you get as much
enjoyment using this equipment as we diddesigning and building it.
CERTIFICA T ION
All technicians opening the refrigeration circuit in autom otive air conditioning systems must
now be certified in refri gerant recovery and recycling procedures to be in compliance with
Section 609 of the Clean Air Act Amendments of 1990. For inform ation on certification call
MACS Worldwide at (215) 631-7020.
ABO UT THIS MANUAL
This manual includes a SAFETY SUMMARY, machine PREPARATION FOR USE,
OPERATION procedures, and MAINTENANCE instructions , for the VIPER VR-6000 Air
Conditioning Service Center. Anyone intending to use the VR-6000 s hould becom e familiar
with ALL the information included in this manual (especiallythe SAFETYSUMMARY) before
attempting to us e it.
Bef ore operating this machine for the first time, per form all PREPA RATION FOR USE
instructions . Ifyour new machine is not properly prepared to perform a service, your service
data could be erroneous. In order to properly perform a complete air conditioning service,
follow all procedures in the order presented. Pleas e take the time to study this m anual
before operating the machine. Then keep this m anual clos e at hand for future reference.
Pleas e pay close attention to the SAFETY SUMMARY and all WARNINGS and CAUTIONS
provided throughout this m anual. To activate the published warranty, mail in the attached
warrantycard.
CAUTION: The VR-6000 is intended for indoor use only.
ABOUT THE VIPER A/C AIR CO NDITIONING SERVICE CENTER
The ozone layer around the earth’s atmos phere is a thin protective covering. It acts as a
shield against the sun’s destructiveultravioletrays. Without the ozone layer the very exis tence
of our planet would be in question. Scientific studies show that the ozone layer is being
destroyed at an alarming rate. It has been es tablished that emissions from refrigerants,
such as R-12, contain chlorofluorocarbons (CFC’s), which are the leading caus e of ozone
depletion. One CFC molecule has been s hown to destroyup to 100,000 ozone molecules.
Your VIPER VR-6000 incorporates a highly accurate electronic scale for determ ining
charging weights, etc. Other functions can also beperformed with the electronic scale as you
will discover during the operating procedures. Either standard or m etric units of measure
can be selected. Your new VIPER VR-6000 has been designed s pecifically touse R-134a, to
operatewithin theobjectives oftheMontreal Protocol.
7
IN STRU CTIONS M ANUAL
THE MACHINE
BASIC COMPONENTS
Refer tofig 1, 2, 3 & 4:
a) ControlConsoleb) Valves
c) Handled) High/Low Pressure Threaded Connectors
e) New Oil Containerf) StorageTank
g) Desiccant Filtersh) Electronic Scale
i) Heater Blanketj) Main Power Switch
k) Socket forElectrical Supply Plugl) Fuse
m) Used OilContainern) Serial Port
o) Moisture Indicatorp) Vacuum Pump
q) Wheelsr) AirPurge Valve
8
9
IN STRU CTIONS M ANUAL
CONTROLS AND CONTROL SYSTEM
Refer toFig 5:
(A1) Lowpressure gauge forA/Csystem
(A2) High press ure gauge forA/C system
(A4) Pres sure gauge for s torage tank
(A6) Emergency/alarms panel
(A7) Display
(A8) Key pad controls
(A9) Operations selector panel
A4
A6
A7
A8
Fig.5: ControlPanel
A2
A1
A9
10
INSTRUCTIONS MA NUAL
FUNCTION SELECTOR KEYBOARD
Refer toFig 6:
(T1) REFRIGERANTAVAILABLE LEDindicator: when lit, the display reports the weightof the
available refrigerantin the storage tank.
(T2) RECHARGE LED indicator (flashes during the CHARGING phase).
(T3) RECOVERYLED indicator (flashes during the RECOVERY phas e).
(T4) EVACUATE LED indicator (flas hes during the VACUUMphase).
(T5) HOLD: flashes at the end ofthe recovery during the OIL DISCHARGE phase.
(T6) SEL key: Selects the operation to be performed. Every time this keyis press ed one of
theLEDs from T1 through T4 will light in sequence; the LED alongside each operation
indicates that theoperation m ay be started or that it is being performed (flashing LED).
(T7) INCREA SE key: Each time this key is press ed dur ing the operations relative to set ting
thetime and the quantity, the value of the flas hing digit on the displaywill be increased
byone unit.
(T8) ARROW key: Each time this key is pres sed while a displayvalue is flas hing during the
operations relative to settingthe time and the quantity, a different digitwill be s elected for
modification (selected digit will flas h).
(T9) ENTER key: Pres sing this keywhen a LED corresponding to an operation is lit but not
flashing will permit modifying the evacuation time, and desired charging weight. After
setting the desiredvalue pres s the keyagain tocomplete the process.
(T10) GOkey: Press ing this keywill s tart theoperation indicated bythelighted LED
(T11) STOP key: Press ing this keywill stop the operation indicated bytheflashing LED.
(T12) °Fkey:Pres sing this keythedisplay will s how the bottle temperaturein Celsius degree
11
IN STRU CTIONS M ANUAL
or Fahrenheit degree.
(T13) Display: According to the operation s elected, displays the evacuation time, tank
temperature, or weightof available refrigerant.
STATUS AND ALARM PANEL
See Fig 7:
(C1) REPLACE FILTER: the Low side refrigerant filter/dryer must be changed when the led
“REPLACE FILTER” lights up.When recovering new refrigerant this light m ay come on
prem aturely. Itm aybe reset bypres sing theSEL keywhile turning onthe machine.
(C2) HIGH PRESSURE: Lights and emits an acoustic signal when the press ure of the fluid
in the circuit exceeds 290 ps i (20 bar). The RECOVERY operation is automatically
interrupted. This will occur if you attempt to recover refrigerant with the tank valves
clos ed, and will require some disass embly to reset (s ee TROUBLE SHOOTING
section)
(C3) TANK FULL: Lights and emits an acous tic signal when the bottle is filled to more than
80% of maximum capacity, approximately 40 lbs.The RECOVERY operation is
automatically interrupted. You may use the CHARGING function to remove refrigerant
from the s torage tank.
(C4) LOW REFRIGERANT: Lights and emits an acoustic s ignal when the quantity of
refrigerant fluid contained in the bottle is low, near 4 lbs (~2 kg). You will need to add
additional refrigerantto continue with a CHARGING function.
C1
C2
C3
C4
Fig.7: Front v iews
12
INSTRUCTIONS MA NUAL
MEASUREMENT SETTING
When power is turned on to your new VIPER VR-6000, the keypad displaywill show the gas
weight in the service tank. The display can be set to read in either metric or standard
measurements , proceed as follows:
• Switch off the VR-6000.
• Press the SEL, GO, and ENTER keys simultaneous ly while turning on the VR-6000.
Them achinewill change from one system ofunits ofmeasurementtothe other.
VIPER VR-6000 SPECIFICAT IONS
Electrical Input:115 Vac, 8 A,60 Hz
Am bient Operating Temperature Range:50° F (10° C) to120° F (48.9°C)
ApproximateShipping Weights:170 lbs.
PREPARATION FOR USE
GENERAL
Your VIPER VR-6000 Air Conditioning Service Center is shipped completelyassembled and
100% pre-tested. Your VIPER VR-6000 needs to be prepared before it can be used to
s e rvice a v ehicle's ai r conditioning s ystem .
PREPARATION
Thefollowing s teps,forthe most part, are used only toprepare your VR-6000 for operation.
1.Remove the s hipping carton.
2.Lift outtheVR-6000 from the palletto the ground.
3.Loosen the scale hand screw (s ee Figure 9) that is under the scale platform. It is
tightened to preventdamage to thescale during shipment. Turn counter clockwis e six
full turns. Note: If youdo notloosen the scale hand screwunder the scale platform, the
scale will remain inoperable.
131415
IN STRU CTIONS M ANUAL
OPERATION INSTRUCTIONS
RECOVER AND RECYCLE REFRIGERANT FROM AN AC SYSTEM
1. Be sure that the shutoffvalves are off prior toattaching to a vehicleAC s ystem.
2. Attach themachine to the high and low sides of the AC system to be serviced. The R -
134a hoses have SAE approved s hut-off valves (quick disconnects). The hoses are
shut off when disconnected from the AC system and are open only when connected
with the knurledknobs turnedclockwise. Slide thecollar ofthe fitting back and pres s to
theappropriate fitting.
• Blue hose to the low side of AC system
• Red hose to thehigh s ide of AC system
3. Set MAIN POWER (k, Figure 3) ON.
4. Open the valves on the s ervice hoses by turning the knurled knob clockwise (Figure
12). This will allow refrigerant to flow tothe vehicle.
5. Observe the pressure readings on the low and high side manifold gauges. If the
readings are zero,then repair AC system leak orproceed to vacuum phas e.
6. Open the High Side andLow Side valves on the controlpanel ofthe machine.
7. Press and hold the SEL keyuntil the LED corresponding to “RECOVERY” lights; then
pres s GO. At this point the RECOVERY/RECYCLING phase will begin and the
“Recovery” LEDwill flas h.
8. During the RECOVERY/RECYCLING phas e the amount of refrigerant recovered from
thevehicle will be displayed. Upon completion of the recovery phase the machine will
stop and hold three m inutes.
9. During this time themachine automatically discharges the us ed oil. It will be necess ary
to m onitor this oil dumping to determ ine the am ount of oil that must be added to the
vehicle. When the oil discharge is complete, measure, record and em pty the oil
discharge bottle. This amount will be added to the AC system before charging. When
there is noincrease insystem pressure, the vacuum pump will start and evacuate the
input oil s eparator insidethe VR-6000.
10. If, during this 3-minute time period, the residual refri gerant left in the A/C system
caus es the pres sure to increase, themachine will automatically resume recovering the
refrigerant. When this phase is complete the machine will sound and audible alarm,
and switch to the REF RIGERANT A VAILA BLE display.
11. Clos e the High Side andLow Side panel valves.
12. Setthe MAIN POWER switchOFF.
13. Disconnect the machine if desired. (See DISCONNECTING THE MACHINE FROM A
VEHICL E.)
14. Make necess ary repairs tothe A/C system being serviced.
REMO VING NON-CONDENSABLE GASES
As non-condensable gases accumulate in the refrigerant storage tank, excessive pres sure
is created. The m ost noticeable symptom of excess press ure is a slow down of refrigerant
flow duringtherecovery process. Inm ost cases, you will not notice a reduction in refrigerant
recovery rate until the nominal press ure in the storage tank is 20 ps ig above the normal
pres sure, as listed on the purge chart. C he ck for non-condensable gases after eachrecovery phase. The table provided below (Figure 13)is used to determine when an exces s
ofnon-condensable gases has accumulated in the refrigerants torage tank.
16
INSTRUCTIONS MA NUAL
Proceedas follows:
“REFRIGERANT AVAILABLE” LED must light, if it is neces sary pres s the SEL key to switch
th e ligh t to “R EFRIGERANT AVA ILABL E” LED.
1. Press once the “°F” key in order to display the refrigerant tank temperature (in
Fahrenheit degree), press it a s econd time to display the temperature in Celsius
degree)
2. Read thestoragetank pressure ofthetank gauge
3. Find the temperature in the TEMP °F column for that tank then read the associated
PR ESSURE colum n in ps ig.
4. If the related TANK PRESSURE gauge (A4, fig.5) reads LOWER or EQUAL than the
nominal press ure listed in the table for the respective tank temperature, IT IS NOT
NECESSARY to vent the non-condensablegases from the tank.
5. If the related TANK PRESSURE gauge (A4, fig.5) reads HIGHER than the nominal
pres sure listed in the table for the respective tank temperature, you s hould vent the
non-condensable gases from the tank. This is accom plished byopening the air purge
valv e as shown in figures 1,2,3, & 4.
6. Press the STOP keyto exit the reading of the tank temperature
7. Slowly open the air purge valve (r,fig.2) counterclockwise (turn ~20 degree)
8. Once openedthe air purge valve r,(fig.2)check the tank press ure gauge and the value
shown bythe display.
9. Close the air purge valve when the tank pres sure comes down to the nominal
pres sure listed in the table.
Fig.13:Normal R-134° containerpressure chart
17
IN STRU CTIONS M ANUAL
VACUUM PHASE
1. Upon completion of the RECOVERYphase it is poss i ble to start the vacuum phase by
opening the high- and low-pres sure valves, press ing the SEL key until the LED
corresponding to “EVACUATE”lights , andthen pressing GO. The vacuum time can be
set as follows. Press SEL until the“EVACUATE” LED lights, then press ENTER; at this
point the first digit on the left of the displaywill begin to flash. Pres s the INCREASE key
until the desired digit appears. Likewise, pres s the ARROW and INCREASE keys to
change the other digits. When s etting is complete, pres s the ENTER key to confirm the
vacuum time value.
2. During the vacuum phase, the display will clock its duration. Leave the machine
running until the displayreads 0000 and the pump stops autom atically.
3. Close all the valves and read the vacuum value on press ure gauges (A1) and (A2).
Wait for about 2 minutes, and then check that the pressure has not increased during
the interval. An increase in press ure s ignals leaks in the A/C system. Locate and
eliminate the leaks ; repeatthevacuum phase.
WARNING: Avoid breathing A/C refrigerant and lub ricant vapor mist. Exp osure may
irritate eyes, nose, and throat. To remove HFC-134a from the A/C system, use service
equipment certified to meet the requirements of SAE J2210 (HFC-134a recycling
eq uipment). Additional health and saf ety information may be obtained from add itional
refrigerant and lubricant manufacturers.
NE W OIL INJ ECTI ON
You caninjectvirgin lubricating oil into the vehicle A/C s ystem at this time. Make certain that
theOil ChargeBottle has sufficient quantity of oil. Cautiously open the Oil Charge valve until
thes ame amount of oilthatwas recovered in theRECOVERYAND RECYCLING operation is
removedfrom thecontainer and replaced back into the vehicle's A/C s ystem. The oil will be
drawn into the vehicle A/C s ystem bythe deep vacuum that was obtained while evacuating.
Thes ubsequent charging ofrefrigerantwill ensureall ofthe oilwill be charged from the lines
and hoses.
RECH AR GE AN A/ C SYST EM
WARNING: Always w ear safety goggles and hand protection when working with
refrigerants. Failure to follow these procedures may result in serious injury. Due to the
extreme cold temperatures associated with the use of refrigerants, any contact with the
eye can cause bli ndne ss and contact with the bare skin can cause burns or frostbite.
CAUTION: W hen charging a veh icle do not lean on the machine as this may affect the
scale readings. Inaccurate weight measurements may result. The vehicle system can
be damaged if weights are not measured accurat ely.
During this phase, the correct refrigerant charge is returned tothe vehicle’s A/C system.
1. Press the SELkeyuntil the“RECHARGE”LED lights.
2. Proceedas described below tosetthe quantity ofrefrigerant fluid to be charged. Press
the ENTER key. The firs t digit on the left of the display will begin to flash. Pres s the
INCREASE keyuntil thedesired valueappears. (Digits read in pounds and ounces, or
kilogram s.)Likewise, press the ARROW and INCREASE keys to change the values of
the other digits. Press ENTER when setting is completed to confirm the values . The
quantityof fluid required for filling the s ystem is usually reported on a data plate in the
engine compartm ent of the vehicle. If the quantity is not known, cons ult the relevant
system operating and maintenance m anuals.
18
INSTRUCTIONS MA NUAL
3. Open the high- andlow-pressure valves (if previously closed) and press the GO key.
4. Themachine will s top automatically when the preset quantity has been charged. If the
A/C s ystem press ure increases to equal the tank press ure, and the charge is not
complete, it will be necessary to draw the remaining refrigerant into the system using
thevehicle compressor as outlined below.
5. Close the high- and low-pressure valves.
6. Start thevehicle motor andswitch on the A/C s ystem, and allow both to run for atleast 3
minutes. At this point thesystem will be at steady state and it will be possible to check
thehigh and low side values on therelative pres sure gauges .
7. Disconnect ONLY the high-press ure quick-connect coupling (if necessary, switch the
engine off). Then, with the A/C system still running, open the high and low press ure
taps toforce the A/C system to draw up the refrigerantcontained inthe hoses.
8. After about 1 (one) minute, disconnect the low-pres sure couplings of the VIPER VR-
6000 from the vehicle A/C system and switch off the engine.
WARNING: W hen removing hoses from the vehicle, use extreme caution. Wear gloves
and eye protection.Take care not to allow ref rigerant to ent er the eyes. Liquid refrigerant
wil l cau se severe burns and/or frostbi te to exposed skin, blindness if sprayed into the
eyes, andeven the possibility of death ifinhaled.
RECOVERING THE REFRIGERANT IN THE HOSES.
1. Set the MAIN POWER switch ON and open the high s ide and low side valves on the
front of the machine.
2. Press andhold theSEL keyuntil the LEDuntil the LED corresponding to “RECOVERY”
lights; then pres s GO. At this point the RECOVERY/RECYCLING phase will begin; the
“REC OVER Y” LED w ill fl as h.
3. When all of the refrigerant has been removed from the hoses, the machine will
automatically shut off and the lamp in thes witch will extinguish.To avoid going through
an “unneces sary and time consum ing oil dumpingphase”,press the stop keyas soon
as press ure in low press ure hose reaches zero.
4. Close the High Side Valve and Low Side Valve andturn off the m achine’s main power.
19
IN STRU CTIONS M ANUAL
MAINTENANCE
REPLACING REFRIGERANT FILTER/DRYER
TheVIPER VR-6000 is equipped with two high side refrigerant filters/dryers and a low side
refrigerantfilter/dryer (see figure14). Inorder to maintain high qualityrecycled refrigerant:
• The low s ide refrigerant filter/dryer must be changed when the VR-6000 displays the
service alarm [SERV]and the led“REPLACE FILTER” lights up.
NOTE: When recovering new refrigerantas when the machine is first placed in service
this alarm will light abnormally early and may be cleared by pres sing the “SEL” key
while turningon themachine.
• The high-pres sure refrigerant filters/dryers m ust be replaced after approximately 30
hours of operation or 150 servicejobs.
ATTENTION: Use only CloreAutomotive Filters PartNo. 315-032-000 (Low )
andPart No. 315-035-666(High).
When changing the high pressure filters it is recomm ended that you disconnect the liquid
hose from thestorage tank (close the hose valve and the liquid tank valve first), and recover
the refrigerant from the machine with another m achine through the liquid hose. Then
proceed as described below:
1
2
3
Fig.14: Dryer filters
20
INSTRUCTIONS MA NUAL
If the high and low gauges indicate positive pressure, then recover the refrigerant in the
hoses back into the storagetank.
1. Disconnect the machine from main power supply.
2. Puton gloves and s afetygoggles.
3. Remove the rear plas ticcover.
4. Close the valves on the storage tank.
5. Close the L.P. filter-tap. (3)
6. Working slowlyand carefully, unscrew the couplings atthe inlet and outlettothe filters.
7. Loosen thefilterclamps .
8. Replace thefilters, taking care to insertthem in thecorrect direction. (1,2)
9. Tighten the clamps and the couplings at the inlet and outletto the filters.
10. Open the valves on the s torage tank.
11. Open the L.P. filter- tap. (3)
12. Replace the rear plastic cover.
13. Reconnect and switch on the MACHINE.
14. During the firs t 10 seconds (when the service alarm [SERV] is displayed), press the
SEL key.
15. Type in thefiltercode 0014 tocancel thealarm (use the
16. Charge andrecover about 8 oz.of refrigerant to chargethe machine circuit.
17. SwitchofftheMACHINE
18. Disconnectthemachine from main power supply.
CAUTION: Replace the oldfilter with the new one as quickly as possible in order to avoid
possible con tami nation with the humidity inthe ambient air.
INCREASE and ARROW keys).
EMPTYING THE USED OIL TANK
This operation must be performed after everyrecovery.
Procedure: remove the tank from its lodging and unscrew the cap; empty the tank into a
container forused oils, Replace the cap and replace the container inits lodging.
CASE CARE
Ifthe case of the unit becomes soiled, clean with a m ild detergent and a clean rag. Do not
use solvents – some solvents may cause a deterioration of the material and harm your A/C
Service Center.
AIR CONDITIONING HOSE MAINTENANCE
Them anufacturer recomm ends that the hose s eals be checked periodically and replaced at
thebeginning of each season,at minimum. Contactyour local distributor when replacem ent
seals areneeded.
CALIBRATING THE ELECTRONIC SCALE
This operation s hould be performed when the s cale values displayed are out of line with
known values.The operations listed below must be performed with the maximum attention
and care. Always observe the precautions outlined in this section. Always place the weights
carefully on the scale plate, one at a time. Always place the weights the center of the scale
plate.Proceed as explained below tocalibrate the s cale (see fig. 1,2, 3, & 4). Disconnectthe
machinefrom m ain power supply. Procure a known reference weight (50 lbs). Remove the
plasticcover onthe rear of the m achineto access the machine bottle. Close the blue and red
valves on the storage tank. Remove the s torage tank locking bolts. Separate the heater
21
IN STRU CTIONS M ANUAL
blanket(i) from the s torage tank (donot touch or disconnect the wires of the heater blanket).
Extreme care must be taken when removing the storage tank, so as to avoid pulling
wires loose anddamaging the copper tubing.
Remove the s torage tank (f) from its seat, leavingthe heater blanket around the s cale plate.
Rest the s torage tank on a stand at least 10” in height. Switch on the MACHINE. Be careful
not to touch any electrical wires . Wait at least 10 s econds and press STOP to s ilence the
alarm . Press the INCREASE and ARROW keys s imultaneously and hold down for about 5
seconds. The value displayed at this point will correspond to the scale zero value. Press
down lightlyon the s cale plate; the value should increase. If it does not, replace the charge
cell. Press the ENTER key to m emorize the value. In this phase, take care that nothing
touches the s cale plate). Place the reference weight (50 lbs) carefully at the center of the
scale plate andcheck that the displayed value increases accordingly. Press the SEL keyand
us e the INCREA SE & ARROW keys to typ e in the 4 figures of the ref erence weight. Press
ENTER. The display reading should be the reference weight minus the weight of the em pty
bottle (tare weight).
Remove the reference weight. Switch off the machine and disconnect from main power
supply. Replace the s torage tank in its s eat on the scale plate. Switch on the MACHINE,
taking care not to touch any electrical wires . Check calibration: place a known reference
weight onthe bottle and check that the displayed availability value increases bythe value of
theknown reference weight±2%. Removethe reference weight. Switch off the m achine and
disconnect from m ain s upply.Replace thestoragetank lockingbolts . Open the red and blue
storage tank valves. Replace the rear plas ticcover.
NOTE: In order to check the scale calibration the unit must be displaying a positive value for
REFRIGERANT AVAI LABLE,if the display is reading zero additional weight must be added
to the top of the tank to get a positive reading. The known weight is then added and the
change in weightis verified as the k nown weight.
VACUUM PUMP
Perform the operations listedbelow on a routine basis in order to ensure good operation of
thevacuum pump.
M.1) Oil top- u p
M.2) Oil change
M.3) Decontam in ation
When topping-up or replacing the pump oil, us e onlyVIPER No.793091Vacuum Pump Oil.
M.1) Oil top-up
This operation must be performed when the level of the oil falls to less than half on the
indicator (4 - Figure 15). To refill the oil, perform the steps listed below in the order given.
Refer toFigure 13.
1. Disconnect the VR-6000from m ain power supply.
2. Unscrew the filling cap (3).
3. Pour oil into the tank until theoil level is about half on theindicator (4).
4. Replace theoil cap (3)and tightendown.
M.2) Oil change
The vacuum pump oil must be replaced once a season and in any case every time the
refrigerant filters are replaced. The oil m ust also be changed whenever it changes color,
becom ing dark and turbid, since this is a s ign that it has been contaminated and has
absorbed humidity. Before beginning the oil change procedure, procure a container of
22
23
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.