Vinotemp VINO8500SSD, VINO4500SSD, VINO2500SSD, WM2585SFCD, VINO6500SSD User Manual

...
VINO2500SSD, 4500SSD VINO6500SSD, 8500SSD
Installer’s Instruction
Federal law requires that WINE-MATE split cooling systems be
installed by an EPA certified refrigeration technician.
WINE-MATE split system is shipped as components and is ready for use only after a certified refrigeration technician has properly installed, chatged and tested the system. Proper installation is critical. Vinotemp can only warrant the quality of the components. The installation and proper operation of the system must be warranted by the installer. Installation of the system must be done in accordance with all state and local building codes. The condensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer. These lines must be properly sized for the distance between the two units. After the units and the lines are installed, the system must be pressure tested. If no leaks are found, evacuate and charge system with R134A. Refrigerant amount will vary depending on the length of line set.
1. Condensing Unit
Place the condensing units WM250-850SCU in a properly ventilated location. If it is not, heat exhausted by the condensing unit will build up and the cooling system will not operate properly.
Leave minimum 5 feet clearance for the exhaust side and leave minimum 1 foot clearance for the fresh air intake side.
Condensing unit shall be elevated to avoid possible flooding and shaded from direct sun. It shall not be exposed to temperatures higher than 110
°F or lower than 45 °F (optional low ambient kit for 20 °F).
2. Evaporator Unit
The WM25-85SFCD evaporator units shall be installed for ceiling mount with air supply on both sides and air return on the bottom.
Supply and return air flow from the evaporator unit shall be unobstructed for at least 1 foot.
There is a gravity drain line so that it can not be installed above the evaporator unit. Otherwise a condensation pump must be used.
3. Air Sensor
The air sensor can be located in the wine room or the return air area, but not the supply air area.
4. Refrigeration Piping and Charging
NOTES: ALWAYS USE THE SUPERHEAT AND SUBCOOLING, PRESSURE READINGS TO CHARGE REFRIGERANT PROPERLY, THE LISTED CHARGES ARE FOR REFERENCE ONLY.
The installation order starts from condensing unit (including the receiver), liquid line filter-drier, moisture-liquid indicator (sight glass), liquid line, evaporator unit (including liquid line solenoid valve and thermostatic expansion valve or automatic expansion valve), suction line, and returning to condensing unit.
The subcooling at the condensing unit shall be around 10°F. The charge may be complete when there are no more bubbles forming in the sight glass.
If equipped with a TXV, the evapor ator superheat is set around 8-10 °F for a 10 °F TD system at factory.
If equipped with an AXV, the valve is set around 38-40°F at factory and the superheat at the evaporator unit shall be around 9-18°F under low and high load at 75°F ambient temperature.
Low side pressure: 33 psig
High side pressure: 130 psig at 75 °F ambient temperature and 150 psig
at 90 °F ambient temperature
The line sizes and refrigerant charges are listed as follows.
MODEL
VINO-
2500SSD
VINO-
4500SSD
VINO-
6500SSD
VINO-
8500SSD
REFRIGERATION
LINES
< 50 FT < 50 FT < 50 FT < 50 FT
LIQUID
LINE
1/4"
OD
1/4"
OD
1/4"
OD
3/8"
OD
SUCTION
LINE
3/8” OD 1/2” OD 1/2” OD 1/2” OD 5/8” OD 1/2” OD 5/8” OD 1/2” OD
DRAIN
LINE
CHARGE
R134a/
20 OZ
R134a/
26 OZ
R134a/
32 OZ
R134a/
38 OZ
- 1 -
5. Pressure, Superheat and Subcooling Readings
NOTES: THE VALVES MUST BE IN THE MIDDLE POSITIONS TO READ PROPERLY.
Complaint Possible Causes
a. High suction pressure and low head pressure b. High suction pressure and low head pressure Low superheat and low subcooling c. High suction pressure and high head pressure Low superheat and high subcooling d. High to normal suction pressure and high head pressure Low subcooling e. High suction pressure and high head pressure Low subcooling f. High suction pressure and high head pressure High superheat g. Low suction pressure and low head pressure High superheat and low subcooling h. Low suction pressure and low to normal head pressure High superheat and high subcooling
i. Low suction pressure and low head pressure Low subcooling j. Low suction pressure and low head pressure Low superheat and low subcooling k. Low suction pressure and low to normal head pressure High superheat and normal to high subcooling l. Low suction pressure and normal head pressure High superheat and normal subcooling m. Low suction pressure and high head pressure High superheat and high subcooling n. Low suction pressure and high head pressure High superheat and high subcooling o. low to normal suction pressure and high head pressure High to normal superheat and high subcooling
a. Compressor may be bad b. Expansion valve opened, too
much oil
c. Overcharge d. Non-condensable gas e. Air restricted, dirty condenser,
bad condenser fans
f. High room temperature, high
evaporator load
g. Undercharge h. Liquid line restricted after
receiver, solenoid valve restricted
i. Suction line restricted j. Air restricted at evaporator,
evaporator iced
k. Evaporator restricted l. Expansion valve restricted m. Both evaporator and condenser
restricted
n. Liquid line restricted before
receiver
o. Condenser restricted
6. Valve Operation
SPINDLE BACK POSITION SPINDLE FRONT POSITION SPINDLE MIDDLE POSITION
Fig. 2.1 Valve Operation
- 2 -
Loading...
+ 5 hidden pages