Vinotemp WINE-MATE VINO4500DS, WINE-MATE VINO8500DS, WINE-MATE VINO6500DS Installation & Operation Manual

wwwwww..wwiinneemmaattee..ccoomm
WINE-MATE Ducted System
VINO4500DS VINO6500DS VINO8500DS
VViinnootteemmpp IInntteerrnnaattiioonnaall CCoorrpp..
READ AND SAVE THESE INSTRUCTIONS
wwwwww..vviinnootteemmpp..ccoomm
TABLE OF CONTENTS
Important Safety Information…..........................................2
Features & Specifications.…………………….……………..3
Cellar Construction.…………………………….……………..5
Installer’s Instruction…………….…..….……..……………..6
Temperature Control & Humidity Adjustment....…………9
Service Guide………………….……………………………...12
Electrical Wiring…………….……………………………...18
Care Guide…………………………………………………….24
User’ Troubleshooting…….………………………………...25
Customer Support……………………………………………28
Warranty……………………………………………………….29
- 1 -
Important Safety Information
WARNING:
DO NOT USE A GROUND FAULT INTERRUPTER (GFI).
A DEDICATED 20 OR 30 AMP CIRCUIT IS REQUIRED (4500DS OR 6500-
8500DS).
- 2 -
Features and Specifications
WINE-MATE ducted system VINO4500-8500DS are designed and used to provide a cold temperature between 50~65 wine room at a normal environment.
The wine room will maintain humidity of 50~70% RH even when the environment becomes dry and humid. These temperatures and humilities are optimized for long term storage of wine.
The DS ducted systems are designed for both outdoor and indoor installation.
Back-curved impeller fans are good for total 50 ft long duct to cut the operation noise.
Self-contained ready for use with no extra refrigeration tubing in the field.
°F for a properly insulated
Fig. 1 VINO4500-8500DS FEATURES
- 3 -
Fig. 2 VINO4500- 8500DS DIMENSIONS
The dimensions and capacities are specified as follows:
MODEL
VINO-4500DS 45X34X23 4500/380 1000 cu ft R134a 115V-60HZ-8A 140 VINO-6500DS 45X34X23 6500/490 1500 cu ft R134a 115V-60HZ-14A 170 VINO-8500DS 45X34X25 8500/750 2000 cu ft R134a 115V-60HZ-17A 220
DIMENSION
L”xW”xH”
Btu/h, CFM
(55/90
°F)
CAPACITY
(55/75°F)
REFRIGERANT ELECTRICAL WEIGHT(lb)
NOTE: CAPACITY IS DETERMINED UNDER THE CELLAR AND AMBIENT TEMPERATURES OF 55°F AND 75°F WITH R11 INTERIOR AND R19 EXTERIOR INSULATIONS. ANY LOWER CABINET AND HIGHER AMBIENT TEMPERATURES WILL REDUCE THE CAPACITY.
CAUTION:
LOW AMBIENT TEMPERATURE KIT IS REQUIRED IF THE INSTALLATION AREA WILL BE BELOW 50°F.
CAUTION: LIQUID AND SUCTION LINES MAY DIFFER FROM WHAT ARE SHOWN HERE, PLEASE CHECK ON THE UNITS FOR PROPER INSTALLATION.
Parts included:
Self-contained Cooling Unit Temperature Controller (4.5”LX4.5”WX3.75”D) + Air Sensor
- 4 -
Cellar Construction
This is only a guide and shall be considered as minimum requirements. All interior walls and floors shall have a vapor barrier and a minimum of R11
insulation. All exterior walls and ceiling shall have a vapor barrier and a minimum of R19 insulation. The vapor barrier shall be installed on the warm side of the insulation. All joints, door frames, electrical outlets or switches and any pipes or vents that go through the enclosure shall be sealed to prevent air and moisture leakage into the room. Concrete, rock, and brick are not insulation or vapor barriers.
Doors shall be of a minimum size, insulated to at least R11 and tightly sealed with high quality weather stripping. Be sure to seal the bottom of the door and fill gap between the door’s frame and wall before installing the cap molding. In order to maintain 55 °F in the wine cellar, the ambient temperature surrounding the enclosure shall not exceed the temperature of the enclosure by more than 25 °F. No enclosure wall shall receive direct sun or strong wind.
Lighting shall be of low wattage, with a timer to insure lights are not left on when the enclosure is not occupied.
The cooling system will not be able to maintain the proper temperature if fresh moisture-laden air is constantly being introduced to the enclosure. Symptoms of this condition are; unit runs all the time with only a slight reduction in temperature and/or water overflows from the unit. Because of the temperature difference between the inside and outside, very small cracks can allow large amounts of outside air to enter into the enclosure. Please be aware that moisture can pass through solid concrete, paint and wood. Often a newly constructed room contains fresh wood, paint, concrete and other building materials. These materials contain large amounts of moisture. When placed into operation in this type of environment, the system will work harder to remove this extra moisture resulting in increased “run” time.
- 5 -
Installer’s Instruction
Federal law requires that WINE-MATE ducted cooling systems
be installed by an EPA certified refrigeration technician.
WINE-MATE ducted system is shipped ready for use only after a certified refrigeration technician has properly installed the system. Proper installation is critical. Vinotemp can only warrant the quality of the components. The installation of the system must be warranted by the installer. Installation of the system must be done in accordance with all state and local building and electrical codes.
- 6 -
Fig. 3 DS System Installation
1. Location
Place the unit in a properly ventilated location. If it is not, heat exhausted by the condensing unit will build up and the cooling system will not operate properly.
Cooling unit shall be elevated to avoid possible flooding and shaded from direct sun. It shall not be exposed to temperatures higher than 110 °F or lower than 50 °F (optional low ambient kit available).
Leave minimum 5 feet clearance for hot air exhaust and leave minimum 1 foot clearance for the fresh air intake.
There is a gravity drain line and the unit shall be installed level or with a slight angle toward the drain connection.
Supply air flow shall be unobstructed for at least 12” for free installation or 2” for deflector installation and return air shall be unobstructed for 6”.
Overall combined supply + return or exhaust + intake duct length can be up to 50 ft long.
2. Mounting
The unit must be mounted on a floor or slab that is level and strong enough to support up to 300lb.
There are six ½” bolts required to secure the unit base.
3. Customer Wiring
Use 14 AWG wires
If it is VINO4500DS without low ambient kit, go to the next step. Connect
the wires in the outlet box of the condensing unit to the power lines
Connect the wires in the outlet box of the evaporator unit to the temperature controller and then connect the controller to the power lines.
4. Air Sensor and Temperature Controller
The air sensor is recommended to place in the wine room 5 ft above the floor but not air dead area.
If it is in a return duct, the evaporator fans shall be running all the time. Due to the temperature differential the temperature setting needs to be adjusted in order to maintain the proper wine room temperature.
If the temperature controller is mounted away from the air sensor, use 18 gauge wires to extend the air sensor if needed.
5. Air Flow (Evaporator unit)
It is necessary to check the air flow to meet the specified CFM. It may use fan speed control to adjust the system refrigeration performance to achieve 8-10
room temperature is maintained 55
°F differential between return air and supply air while wine
°F. Turn the control knob clockwise to
decrease the air flow or counter-clockwise to increase the air flow.
- 7 -
Fig. 4 Fan Speed Control
6. Intake and Exhaust Guards
If the intake and exhaust are located outdoor, protection guards may be required.
MODEL INSULATED DUCT DRAIN LINE
VINO-4500DS 8” DIA 7/8” OD VINO-6500DS 10” DIA 7/8” OD VINO-8500DS 10” DIA 7/8” OD
7. Unit Operating
Turn on the fan speed control.
Press digital controller to turn on the unit.
CAUTION: IF THE CONDENSING UNIT IS EQUIPPED WITH A LOW AMBIENT CONDITION KIT, DO NOT TURN ON THE COMPRESSOR UNTIL THE CONDENSING UNIT HAS BEEN POWERD FOR 24 HOURS.
l
- 8 -
Temperature Control & Humidity Adjustment
1. Temperature Setting
Set the temperature at 55
On initial start-up, the time required to reach the desired temperature
will vary, depending on the quantity of bottles, temperature setting and surrounding temperature.
Allow 24 hours to stabilize the temperature for each new temperature setting operation
1. Use of the controller
°F for the optimum aging of wine
Fig. 5 Digital Controller (4.25”L X 3.75D X 4.25”H)
1) Keys SET: To display target set point; in programming mode it selects a parameter or
confirm an operation.
(DEF): To start a manual defrost.
(UP): To see the maximum stored temperature; in programming mode it
browses the parameter codes or increases the displayed value.
(DOWN): To see the minimum stored temperature; in programming mode it
browses the parameter codes or decreases the displayed value.
: To turn on/off the power to the unit.
+ : To lock/unlock the keypad.
SET+ SET+ : To return to the temperature display.
2) Display
During normal operating conditions, the display shows the value measured by the air regulation probe. In case of active alarm, the temperature flashes alternately to the code alarm.
: To enter in the programming mode.
- 9 -
Loading...
+ 21 hidden pages