VINO1500SSW VINO2500SSW
VViinnootteemmpp IInntteerrnnaattiioonnaall CCoorrpp..
READ AND SAVE THESE INSTRUCTIONS
wwwwww..vviinnootteemmpp..ccoomm
TABLE OF CONTENTS
Important Safety Information….........................................2
Features & Specifications.…………………….……………..3 Cellar Construction…………………………….……………..6 Installer’s Instruction…………….…..….……..……………..7 Electrical Wiring………..……….…..….……..……………..14 Temperature Control & Humidity Adjustment….……….16 Care Guide…………………………………………………….19 User’ Troubleshooting…….………………………………...20 Customer Support……………………………………………23 Warranty……………………………………………………….24
- 1 -
Important Safety Information
WARNING:
DO NOT USE A GROUND FAULT INTERRUPTER (GFI).
A DEDICATED 20 AMP CIRCUIT IS REQUIRED.
- 2 -
MODEL
VINO-
1500SSW
VINO-
2500SSW
Features and Specifications
Wine-Mate split cooling systems VINO1500SSW and 2500SSW are designed and used to provide a cold temperature between 50~65 properly insulated wine room at a normal environment.
The wine room will maintain humidity of 50~70% RH even when the environment becomes dry and humid. These temperatures and humilities are optimized for long term storage of wine.
SSW units consist of a condensing unit and an evaporator unit, and they are connected by a liquid line and an insulated suction line.
The SSW condensing units can be located away from the evaporator units and wine cellars as far as 50 ft, which will bring you quiet operation.
The SSW evaporator units are designed for installation in a wine rack or between two wall studs, making them an ideal choice for small and medium wine rooms.
The dimensions and capacities are specified as follows:
EVAP UNIT
W”xD”xH”
WM-
15SFCW
16x5.5 x36
WM-
25SFCW
16x5.5 x36
COND UNIT
L”xD”xH”
WM-150SCU
18x12 x14
WM-250SCU
18x12 x14
Btu/h, CFM
(55/90°F)
1500/105 150 cu ft R134a
2500/175 250 cu ft R134a
CAPACITY
(55/75°F)
REFRIGERANT
ELECTRICAL
EVAP UNIT/ COND UNIT
115V-60HZ-
0.35A /115V­115V-60HZ-
0.71A /115V-
NOTE: CAPACITY IS DETERMINED UNDER THE CELLAR AND AMBIENT TEMPERATURES OF 55°F AND 75°F WITH R11 INTERIOR AND R19 EXTERIOR INSULATIONS. ANY LOWER CABINET AND HIGHER AMBIENT TEMPERATURES WILL REDUCE THE CAPACITY.
CAUTION: LOW AMBIENT TEMPERATURE KIT IS REQUIRED IF THE INSTALLATION AREA WILL BE BELOW 50°F.
CAUTION: LIQUID AND SUCTION LINES MAY DIFFER FROM WHAT ARE SHOWN HERE, PLEASE CHECK ON THE UNITS FOR PROPER INSTALLATION.
NOTE: LEAVE MINIMUM 3” CLEARANCE FOR ELECTRICAL WIRING AND REFRIGERATION PIPING.
°F for a
WEIGHT(lb) EVAP UNIT/ COND UNIT
60HZ-3.1A
60HZ-5.7A
26/30
28/40
- 3 -
Parts included:
Condensing Unit (discharge and suction valves installed) + Liquid Filter + Liquid Indicator Evaporator Unit (liquid line solenoid valve and expansion valve installed) Temperature Controller + Air Sensor
Fig. 1 WM15~25SFCW Evaporator Unit
- 4 -
Fig. 2 WM150~250SCU Condensing Unit
Fig. 3 Liquid Filter Fig. 4 Liquid Indicator
- 5 -
Cellar Construction
This is only a guide and shall be considered as minimum requirements. All interior walls and floors shall have a vapor barrier and a minimum of R11
insulation. All exterior walls and ceiling shall have a vapor barrier and a minimum of R19 insulation. The vapor barrier shall be installed on the warm side of the insulation. All joints, door frames, electrical outlets or switches and any pipes or vents that go through the enclosure shall be sealed to prevent air and moisture leakage into the room. Concrete, rock, and brick are not insulation or vapor barriers.
Doors shall be of a minimum size, insulated to at least R11 and tightly sealed with high quality weather stripping. Be sure to seal the bottom of the door and fill gap between the door’s frame and wall before installing the cap molding. In order to maintain 55 °F in the wine cellar, the ambient temperature surrounding the enclosure shall not exceed the temperature of the enclosure by more than 25 °F. No enclosure wall shall receive direct sun or strong wind.
Lighting shall be of low wattage, with a timer to insure lights are not left on when the enclosure is not occupied.
The cooling system will not be able to maintain the proper temperature if fresh moisture-laden air is constantly being introduced to the enclosure. Symptoms of this condition are; unit runs all the time with only a slight reduction in temperature and/or water overflows from the unit. Because of the temperature difference between the inside and outside, very small cracks can allow large amounts of outside air to enter into the enclosure. Please be aware that moisture can pass through solid concrete, paint and wood. Often a newly constructed room contains fresh wood, paint, concrete and other building materials. These materials contain large amounts of moisture. When placed into operation in this type of environment, the system will work harder to remove this extra moisture resulting in increased “run” time.
- 6 -
Installer’s Instruction
Federal law requires that WINE-MATE split cooling systems be
installed by an EPA certified refrigeration technician.
WINE-MATE split system is shipped as components and is ready for use only after a certified refrigeration technician has properly installed, evacuated, charged and tested the system. Proper installation is critical. Vinotemp can only warrant the quality of the components. The installation and proper operation of the system must be warranted by the installer. Installation of the system must be done in accordance with all state and local building and electrical codes. The condensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer. These lines must be properly sized for the distance between the two units. After the units and the lines are installed, the system must be pressure tested. If no leaks are found, evacuate and charge system. Refrigerant amount will vary depending on the length of line set.
1. Condensing Unit
Place the condensing units WM150SCU and 250SCU in a properly ventilated location. If it is not, heat exhausted by the condensing unit will build up and the cooling system will not operate properly.
Condensing unit shall be elevated to avoid possible flooding and shaded from direct sun. It shall not be exposed to temperatures higher than 110
°F or lower than 50 °F (optional low ambient kit available).
Leave minimum 5 ft clearance for the exhaust side and leave minimum 1 foot clearance for the fresh air intake side.
CAUTION: IF THE CONDENSING UNIT IS EQUIPPED WITH A LOW AMBIENT CONDITION KIT, DO NOT TURN ON THE COMPRESSOR UNTIL THE CONDENSING UNIT HAS BEEN POWERD FOR 24 HOURS.
- 7 -