Vinotemp WINEMATE VINO-1500SS, WINEMATE VINO-1900SS Installation Instructions Manual

VINO1500SS VINO1900SS
Installer’s Instruction
Federal law requires that WINEMATE split cooling systems be
installed by an EPA certified refrigeration technician.
WINEMATE split system is shipped as components and is ready for use only after a certified refrigeration technician has properly installed, evacuated, charged and tested the system. Proper installation is critical. Vinotemp can only warrant the quality of the components. The installation and proper operation of the system must be warranted by the installer. Installation of the system must be done in accordance with all state and local building electrical codes. The condensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer. These lines must be properly sized for the distance between the two units. After the units and the lines are installed, the system must be pressure tested. If no leaks are found, evacuate and charge system. Refrigerant amount will vary depending on the length of line set.
1. Condensing Unit
Place the condensing unit in a properly ventilated location. If it is not, heat exhausted by the condensing unit will build up and the cooling system will not operate properly.
Condensing unit shall be elevated to avoid possible flooding and shaded from direct sun. It shall not be exposed to temperatures higher than 110
than 50 °F (optional low ambient kit available).
Leave minimum 5 feet clearance for the exhaust side and leave minimum 1 foot clearance for the fresh air intake side.
°F or lower
CAUTION: DO NOT SWITCH ON THE COMPRESSOR IF THE CONDENSING UNIT IS EQUIPPED WITH A LOW AMBIENT CONDITION KIT UNTIL THE UNIT HAS BEEN PLUGGED IN FOR 24 HOURS.
2. Valve Operation (Condensing unit)
BACK POSITION FRONT POSITION MIDDLE POSITION
Fig. 1 ROTALOCK Valve Operation
BACK POSITION FRONT POSITION MIDDLE POSITION
Fig. 2 Base Valve Operation
1 - Process & Manometer; 2 - Receiver/Compressor Suction 3 - Liquid/Suction Line; 4 - Pressure Control
Back Position: Process and manometer port closed for normal operation Front Position: Connection to liquid or suction line closed Middle Position: All ports open for evacuation, charge and manometer reading
3. Evaporator Unit
The WM-15SFC evaporator units shall be installed for ceiling mount with the air supply towards horizontally and air return on the bottom.
The WM-19SFC evaporator unit shall be ins t alled for wall mount with the air supply towards top and air return on the sides.
Supply and return air flow from the evaporator unit shall be unobstructed for at least 1 foot.
- 1 -
Loading...
+ 4 hidden pages