Vinotemp WINE-MATE VINO2500HZD, WINE-MATE VINO1500HZD Service Manual

WINE-MATE Cooling Unit
Service Manual
VINO1500HZD VINO2500HZD
Vinotemp International Inc.
www.winemate.com
SAFETY INFORMATION
- 1 -
TABLE OF CONTENTS
1. Introduction………………………………………………..3
I. Goals and Objectives…………………….…...……………………………3
II. R134a Refrigerant Service Information.....................…………..…….3
2. Component Information and Access………………….5
I. Model and Serial Label Location…………………………………………5 II. Component Access…………………………………………………………6
1) Removing the Outer Cover…………………………..……………...…..6
2) Removing the Inner Styrofoam Cover…..……………………………..6
3) Removing the Fan Plate….…………………..…………………………..8
4) Removing the Electronic Controller……………..……………………..9
5) Removing the Thermistor………………………………………………..9
6) Removing Fan Motors…………………………………………………...10
7) Removing the Start Relay and Overload Protector …………….....10
8) Removing the Compressor……..………………………………………11
9) Removing the Condenser……..………………………………………..12
10) Removing the Evaporator…..…………………………………………..12
3. Servicing and Diagnosis……………………………….13
I. Identifying Component Problems........…….…….………………….13
1) Terminal Block………………………………………………………….13
2) Compressor……………………………………………………………….14
3) Start Relay…………………………………………………………………15
4) Overload Protector.………………………………………………………16
5) Electronic Controller……………………………………………………16
6) Thermistor..………………………………………………………………..17
7) Fan Motors.………………………………………………………………..17 II. Wiring Diagram.….……..…………………………………..……………..18
III. Troubleshooting Chart.…....…………….………………………………19
4. Customer Support………………………………………22
5. Warranty Information…………………………………..23
I. Limited Warranty …………………………………..……………………..23 II. Limitation of Implied Warranty.………………………………………….24
- 2 -
1. Introduction
VINOTEMP assumes no responsibility for any repairs made on products by anyone other than authorized service technician
This manual has been prepared to provide the information on installing, servicing, troubleshooting and repairing procedures for the WINE-MATE VINO1500HZD & 2500 HZD cooling units.
I. Goals and Objectives
The goal of this manual is to provide detailed information that will enable the service personnel to properly install and repair the cooling unit, and troubleshoot and diagnose malfunctions.
The objectives of this manual are that the service personnel will
Fully understand the proper safety precautions
Successfully install the cooling unit
Successfully troubleshoot and diagnose malfunctions
Successfully perform necessary repairs
Successfully return the cooling unit to proper operational status
II. R134a Refrigerant Service Information
This cooling unit uses R134a refrigerant. This refrigerant requires synthetic ester oil in the compressor. This cooling system does not tolerate contamination from any of the following:
Other refrigerants
Moisture
Petroleum-based lubricants
Silicone lubricants
Cleaning components
Rust inhibitors
Leak detection dyes
Any other types of additive
As a result, the following precautions shall be observed:
Use equipment dedicated to R134a sealed system only.
Use R134a refrigerant for back-flushing.
- 3 -
Use dry nitrogen to purge the system.
Do not overcharge the refrigeration system.
Do not leave replacement compressor open to the atmosphere for more
than 10 minutes.
Do not operate the compressor without refrigerant charge in the system.
Do not use the compressor if the rubber plugs on the replacement
compressor appear to have been tampered or removed.
Always replace the filter-drier when performing any repairs on the sealed system.
The filter-drier must be cut from the sealed system. Never unbraze the filter-drier from system tubing. Applying heat will drive moisture back into sealed system.
Table 1-1 Health and Safety Handling of R134a
Allowable Overall Exposure Limit 1,000 ppm Vapor Exposure to Skin No Effect Liquid Exposure to Skin Can cause frostbite Vapor Exposure to Eyes Can cause very slight irritation Liquid Exposure to Eyes Can cause frostbite Above Minimum Exposure Limit Can cause asphyxiation, tachycardia
and cardiac arrhythmia's. Wear appropriate skin and eye care.
Spill Management Combustible sources. Evacuate or
ventilate area. May decompose if in contact.
Fire and Explosion Hazards Made with flames and heating
elements. Container may explode if heated due to pressure rise. Combustion products are toxic.
Storage Conditions The procedures/rules for R12 also
apply to R134a. Reclaim
- 4 -
2. Component Information and Access
This section provides you the component information and access inside the cooling unit. The components and their locations are shown Figures 2-1 through 2-11 below.
I. Model Number & Serial Label and Component Locations
Label
- 5 -
Figure 2-1
II. Component Access
1) Removing the Outer Cover
1. Unplug the WINEMATE cooling unit or disconnect power.
2. Remove the WINEMATE cooling unit from the enclosure.
3. To remove the outer cover, remove all screws from each side and on the top.
2) Removing the Inner Styrofoam Covers
Once the outer cover is removed, this will expose the inner styrofams. The top large Styrofoam cover seals off the condenser and evaporator fan compartments. To gain access to the other components, the styrofoam covers will need to be
removed. To separate the top styrofoam covers, a knife can be used to cut along
the seam and through the seal. Take care as not to damage any wiring or the styrofoam pieces.
- 6 -
Figure 2-2
Figure 2-3
- 7 -
Figure 2-4
Loading...
+ 17 hidden pages