Vimar 01546 Installation Manual

Instructions manual
KNX weather station art. 01546
Installation manual
Table of Contents
GENERAL FEATURES AND FUNCTIONALITY from page 5
COMMUNICATION OBJECTS
GENERAL FEATURES AND FUNCTIONALITY
4
For all the details about the Well-contact Plus system, refer to the installer manual that can be downloaded from the Software Product Software Well-contact Plus section on the website www.vimar.com.
5
VIMAR group
General features and functionality
GENERAL FEATURES AND FUNCTIONALITY
KNX weather station
Weather station, KNX standard, power supply 12-32 Vdc or 12-24 Vac. Can be integrated with the By-me home auto­mation system.
General information
The device measures quantities such as temperature, wind speed, rainfall, and brightness whose values can be used for viewing on supervisors or, on exceeding a threshold, to activate automation systems in the installation. The KNX weather station 01546 can be integrated with the By-me home automation system via a dedicated configuration using the EasyTool Professional software.
Characteristics
• Auxiliary supply voltage AUX: 12-32 V , 12-24 V~ SELV
• AUX current draw: 100 mA max, ripple 10% Current draw from the Bus: 10 mA
• Terminals:
- Auxiliary power supply AUX
- TP bus connector
• Configuration push-button
• Configuration LED
• Configuration LED: 254 max
• Possible associations: 255 max
• Communication objects: 109
• Rain sensor heating: approximately 1.2 W
• Temperature measurement range: -40°C to +80°C
• Definition (temperature): 0.1°C
• Accuracy (temperature):
- 1°C with -10°C - +85°C
- 1.5°C with -25°C - +150°C
• Wind measurement range: 0 - 70 m/s
• Definition (wind): <10% of the reading
• Accuracy (wind): 25% with 0 - 15 m/s with an angle of incidence of 45° and mounting on a suitable support
• Brightness measurement range: 0 - 150,000 Lux
• Definition (brightness):
- 1 Lux with 0-120 Lux
- 2 Lux with 121-1,046 Lux
- 63 Lux with 1,047-52,363 Lux
- 423 Lux with 52,364-150,000 Lux
• Accuracy (brightness): 35%
• Operating temperature: -30°C - +50°C (outdoor use)
• Protection class: IP44
• Dimensions: 96x77x118 mm (W x H x D)
• Weight: approximately 170 g
Operation
Brightness measurement: the current brightness is measured by the specific sensor.
Wind measurement: the strength of the wind is measured electronically and is quiet and reliable even in the event of hail, snow and sub-zero temperatures.
The weather station is also able to detect whirlwinds and updraughts.
Precipitation measurement: the weather station is equipped with a sensor with a heated surface so that only the raindrops and snowflakes (and therefore not fog or dew) are measured as precipitation. Once it has stopped raining or snowing, the sensor dries quickly and the precipitation message is turned off.
Temperature measurement: the weather station measures the value of the current ambient temperature.
Control outputs for all values: the limit values can be set via the respective parameters or via the ETS communication objects.
8 AND logic gates and 8 OR logic gates each one with 4 inputs: the control operations themselves as well as the 8 logic inputs (in the form of communication objects) can be used as inputs for the AND and OR logic gates; the output of each gate can be configured as 1 bit or as 2 x 8 bits.
IMPORTANT: Press the configuration button to assign the physical address to the device.
Behaviour after switching on the Bus
Switching on the Bus: the state will be set based on the setting of the parameters and the corresponding telegrams sent over the Bus.
Behaviour after reset
As for Bus on.
FRONT VIEW.
01546
1
2
4
3
5 6
+
-
1. Fast spring terminal for auxiliary power supply AUX; terminal assignment is independent of polarity (+/- or -/+). Use a solid cable of cross­section up to 1.5 mm2 or a stranded cable.
2. Connector for connecting the cable of the precipitation sensor located
under the front cover of the weather station.
3. Space for feeding through the power supply cable and the Bus cable.
4. KNX TP Bus connector (-, +). We recommend using the KNX cable art. 01890 using a corrugated pipe for the outside or to protect the cable from UV radiation.
5. Configuration button.
6. Configuration LED.
6
KNX weather station
No. ETS name Function Description Type
Flag 1
Priority
C R W T U I
0 Night control output Output
Sends the command over the BUS when the "Night" condition occurs (1 = Night | 0 = Day).
1 bit C R - T - - Low
1 Rain control output Output
Sends the command over the BUS when the "Rain" condition occurs (1 = Rain | 0 = No Rain).
1 bit C R - T - - Low
2 Logic input 1 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
3 Logic input 2 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
4 Logic input 3 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
5 Logic input 4 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
6 Logic input 5 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
7 Logic input 6 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
8 Logic input 7 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
9 Logic input 8 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
10
Temperature sensor error
Output
Indicates malfunctioning of the weather station temper­ature sensor (0 = OK | 1 = NOT OK).
1 bit C R - T - - Low
11 Wind sensor error Output
Indicates malfunctioning of the wind sensor (0 = OK | 1 = NOT OK).
1 bit C R - T - - Low
12
Measured value temperature
Output
Lets you know the temperature measured by the weather station in °C.
2 bytes C R - T - - Low
13
Min/max temperature request
Request
Requests the weather station to send the measured minimum and maximum temperature values over the Bus.
1 bit C R W - - - Low
14
Measured min. temper­ature value
Sends min. temperature
Lets you know the minimum temperature measured by the weather station in °C.
2 bytes C R - T - - Low
15
Measured max. tem­perature value
Sends max. temperature
Lets you know the maximum temperature measured by the weather station in °C.
2 bytes C R - T - - Low
16
Min/max temperature reset
Temperature reset
Deletes the saved minimum and maximum temperature values.
1 bit C R W - - - Low
17 Temperature 1 LV Default value
Temperature 1 limit value: to set the setpoint of the limit value
2 bytes C R - T - - Low
18 Temperature 1 LV Actual value Temperature 1 limit value: to read the actual limit value 2 bytes C R W - - - Low
19 Temperature 2 LV Default value
Temperature 2 limit value: to set the setpoint of the limit value
2 bytes C R - T - - Low
20 Temperature 2 LV Actual value Temperature 2 limit value: to read the actual limit value 2 bytes C R W - - - Low
List of existing communication objects and standard settings
Continues
C = Communication; R = Read; W = Write; T = Transmission; U = Enable update
ETS parameters and communication objects
7
VIMAR group
COMMUNICATION OBJECTS
KNX weather station
No. ETS name Function Description Type
Flag 1
Priority
C R W T U I
21 Temperature 3 LV Default value
Temperature 3 limit value: to set the setpoint of the limit value
2 bytes C R - T - - Low
22 Temperature 3 LV Actual value Temperature 3 limit value: to read the actual limit value 2 bytes C R W - - - Low
23 Temperature 4 LV Default value
Temperature 4 limit value: to set the setpoint of the limit value
2 bytes C R - T - - Low
24 Temperature 4 LV Actual value Temperature 4 limit value: to read the actual limit value 2 bytes C R W - - - Low
25 Control output Temp 1 LV Temperature 1 Limit Value control output. 1 bit C R - T - - Low
26 Control output Temp 2 LV Temperature 2 Limit Value control output. 1 bit C R - T - - Low
27 Control output Temp 3 LV Temperature 3 Limit Value control output. 1 bit C R - T - - Low
28 Control output Temp 4 LV Temperature 4 Limit Value control output. 1 bit C R - T - - Low
29
Measured value wind speed
Output
Lets you know the wind speed measured by the weath­er station in m/s.
2 bytes C R - T - - Low
30
Request for max. wind strength
Request
Requests the weather station to send the measured maximum wind speed value over the Bus.
1 bit C R W - - - Low
31
Max. measured wind strength value
Sends the maximum wind strength
Lets you know the maximum wind speed measured by the weather station in m/s.
2 bytes C R - T - - Low
32
Reset max. wind strength
Wind strength reset Deletes the saved maximum wind strength value. 1 bit C R W - - - Low
33 Wind speed 1 LV Default value
Wind speed 1 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
34 Wind speed 1 LV Actual value Wind speed 1 limit value: to read the actual limit value 2 bytes C R W - - - Low
35 Wind speed 2 LV Default value
Wind speed 2 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
36 Wind speed 2 LV Actual value Wind speed 2 limit value: to read the actual limit value 2 bytes C R W - - - Low
37 Wind speed 3 LV Default value
Wind speed 3 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
38 Wind speed 3 LV Actual value Wind speed 3 limit value: to read the actual limit value 2 bytes C R W - - - Low
39 Control output
Wind 1 LV
Wind Speed 1 Limit Value control output. 1 bit C R - T - - Low
40 Control output Wind 2 LV Wind Speed 2 Limit Value control output. 1 bit C R - T - - Low
41 Control output Wind 3 LV Wind Speed 3 Limit Value control output. 1 bit C R - T - - Low
42
Measured value brightness
Output
Lets you know the brightness measured by the weather station in lux.
2 bytes C R - T - - Low
43
Limit value brightness 1
Default value
Brightness 1 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
44
Limit value brightness 1
Actual value Brightness 1 limit value: to read the actual limit value 2 bytes C R W - - - Low
Continued
Continues
C = Communication; R = Read; W = Write; T = Transmission; U = Enable update
ETS parameters and communication objects