KNX weather station
Weather station, KNX standard, power supply 12-32 Vdc or 12-24 Vac. Can be integrated with the By-me home auto­mation system.
General information
The device measures quantities such as temperature, wind speed, rainfall, and brightness whose values can be used for viewing on supervisors or, on exceeding a threshold, to activate automation systems in the installation. The KNX weather station 01546 can be integrated with the By-me home automation system via a dedicated configuration using the EasyTool Professional software.
Characteristics
• Auxiliary supply voltage AUX: 12-32 V , 12-24 V~ SELV
• AUX current draw: 100 mA max, ripple 10% Current draw from the Bus: 10 mA
• Terminals:
- Auxiliary power supply AUX
- TP bus connector
• Configuration push-button
• Configuration LED
• Configuration LED: 254 max
• Possible associations: 255 max
• Communication objects: 109
• Rain sensor heating: approximately 1.2 W
• Temperature measurement range: -40°C to +80°C
• Definition (temperature): 0.1°C
• Accuracy (temperature):
- 1°C with -10°C - +85°C
- 1.5°C with -25°C - +150°C
• Wind measurement range: 0 - 70 m/s
• Definition (wind): <10% of the reading
• Accuracy (wind): 25% with 0 - 15 m/s with an angle of incidence of 45° and mounting on a suitable support
• Brightness measurement range: 0 - 150,000 Lux
• Definition (brightness):
- 1 Lux with 0-120 Lux
- 2 Lux with 121-1,046 Lux
- 63 Lux with 1,047-52,363 Lux
- 423 Lux with 52,364-150,000 Lux
• Accuracy (brightness): 35%
• Operating temperature: -30°C - +50°C (outdoor use)
• Protection class: IP44
• Dimensions: 96x77x118 mm (W x H x D)
• Weight: approximately 170 g
Operation
Brightness measurement: the current brightness is measured by the specific sensor.
Wind measurement: the strength of the wind is measured electronically and is quiet and reliable even in the event of hail, snow and sub-zero temperatures.
The weather station is also able to detect whirlwinds and updraughts.
Precipitation measurement: the weather station is equipped with a sensor with a heated surface so that only the raindrops and snowflakes (and therefore not fog or dew) are measured as precipitation. Once it has stopped raining or snowing, the sensor dries quickly and the precipitation message is turned off.
Temperature measurement: the weather station measures the value of the current ambient temperature.
Control outputs for all values: the limit values can be set via the respective parameters or via the ETS communication objects.
8 AND logic gates and 8 OR logic gates each one with 4 inputs: the control operations themselves as well as the 8 logic inputs (in the form of communication objects) can be used as inputs for the AND and OR logic gates; the output of each gate can be configured as 1 bit or as 2 x 8 bits.
IMPORTANT: Press the configuration button to assign the physical address to the device.
Behaviour after switching on the Bus
Switching on the Bus: the state will be set based on the setting of the parameters and the corresponding telegrams sent over the Bus.
Behaviour after reset
As for Bus on.
FRONT VIEW.
01546
1
2
4
3
5 6
+
-
1. Fast spring terminal for auxiliary power supply AUX; terminal assignment is independent of polarity (+/- or -/+). Use a solid cable of cross­section up to 1.5 mm2 or a stranded cable.
2. Connector for connecting the cable of the precipitation sensor located
under the front cover of the weather station.
3. Space for feeding through the power supply cable and the Bus cable.
4. KNX TP Bus connector (-, +). We recommend using the KNX cable art. 01890 using a corrugated pipe for the outside or to protect the cable from UV radiation.
5. Configuration button.
6. Configuration LED.
Page 6
6
KNX weather station
No. ETS name Function Description Type
Flag 1
Priority
C R W T U I
0 Night control output Output
Sends the command over the BUS when the "Night" condition occurs (1 = Night | 0 = Day).
1 bit C R - T - - Low
1 Rain control output Output
Sends the command over the BUS when the "Rain" condition occurs (1 = Rain | 0 = No Rain).
1 bit C R - T - - Low
2 Logic input 1 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
3 Logic input 2 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
4 Logic input 3 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
5 Logic input 4 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
6 Logic input 5 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
7 Logic input 6 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
8 Logic input 7 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
9 Logic input 8 Input
Input that can be enabled to be used for performing the logic functions made available by the weather station.
1 bit C R W - - - Low
10
Temperature sensor error
Output
Indicates malfunctioning of the weather station temper­ature sensor (0 = OK | 1 = NOT OK).
1 bit C R - T - - Low
11 Wind sensor error Output
Indicates malfunctioning of the wind sensor (0 = OK | 1 = NOT OK).
1 bit C R - T - - Low
12
Measured value temperature
Output
Lets you know the temperature measured by the weather station in °C.
2 bytes C R - T - - Low
13
Min/max temperature request
Request
Requests the weather station to send the measured minimum and maximum temperature values over the Bus.
1 bit C R W - - - Low
14
Measured min. temper­ature value
Sends min. temperature
Lets you know the minimum temperature measured by the weather station in °C.
2 bytes C R - T - - Low
15
Measured max. tem­perature value
Sends max. temperature
Lets you know the maximum temperature measured by the weather station in °C.
2 bytes C R - T - - Low
16
Min/max temperature reset
Temperature reset
Deletes the saved minimum and maximum temperature values.
1 bit C R W - - - Low
17 Temperature 1 LV Default value
Temperature 1 limit value: to set the setpoint of the limit value
2 bytes C R - T - - Low
18 Temperature 1 LV Actual value Temperature 1 limit value: to read the actual limit value 2 bytes C R W - - - Low
19 Temperature 2 LV Default value
Temperature 2 limit value: to set the setpoint of the limit value
2 bytes C R - T - - Low
20 Temperature 2 LV Actual value Temperature 2 limit value: to read the actual limit value 2 bytes C R W - - - Low
List of existing communication objects and standard settings
Continues
C = Communication; R = Read; W = Write; T = Transmission; U = Enable update
ETS parameters and communication objects
Page 7
7
VIMAR group
COMMUNICATION OBJECTS
KNX weather station
No. ETS name Function Description Type
Flag 1
Priority
C R W T U I
21 Temperature 3 LV Default value
Temperature 3 limit value: to set the setpoint of the limit value
2 bytes C R - T - - Low
22 Temperature 3 LV Actual value Temperature 3 limit value: to read the actual limit value 2 bytes C R W - - - Low
23 Temperature 4 LV Default value
Temperature 4 limit value: to set the setpoint of the limit value
2 bytes C R - T - - Low
24 Temperature 4 LV Actual value Temperature 4 limit value: to read the actual limit value 2 bytes C R W - - - Low
25 Control output Temp 1 LV Temperature 1 Limit Value control output. 1 bit C R - T - - Low
26 Control output Temp 2 LV Temperature 2 Limit Value control output. 1 bit C R - T - - Low
27 Control output Temp 3 LV Temperature 3 Limit Value control output. 1 bit C R - T - - Low
28 Control output Temp 4 LV Temperature 4 Limit Value control output. 1 bit C R - T - - Low
29
Measured value wind speed
Output
Lets you know the wind speed measured by the weath­er station in m/s.
2 bytes C R - T - - Low
30
Request for max. wind strength
Request
Requests the weather station to send the measured maximum wind speed value over the Bus.
1 bit C R W - - - Low
31
Max. measured wind strength value
Sends the maximum wind strength
Lets you know the maximum wind speed measured by the weather station in m/s.
2 bytes C R - T - - Low
32
Reset max. wind strength
Wind strength reset Deletes the saved maximum wind strength value. 1 bit C R W - - - Low
33 Wind speed 1 LV Default value
Wind speed 1 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
34 Wind speed 1 LV Actual value Wind speed 1 limit value: to read the actual limit value 2 bytes C R W - - - Low
35 Wind speed 2 LV Default value
Wind speed 2 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
36 Wind speed 2 LV Actual value Wind speed 2 limit value: to read the actual limit value 2 bytes C R W - - - Low
37 Wind speed 3 LV Default value
Wind speed 3 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
38 Wind speed 3 LV Actual value Wind speed 3 limit value: to read the actual limit value 2 bytes C R W - - - Low
39 Control output
Wind 1 LV
Wind Speed 1 Limit Value control output. 1 bit C R - T - - Low
40 Control output Wind 2 LV Wind Speed 2 Limit Value control output. 1 bit C R - T - - Low
41 Control output Wind 3 LV Wind Speed 3 Limit Value control output. 1 bit C R - T - - Low
42
Measured value brightness
Output
Lets you know the brightness measured by the weather station in lux.
2 bytes C R - T - - Low
43
Limit value brightness 1
Default value
Brightness 1 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
44
Limit value brightness 1
Actual value Brightness 1 limit value: to read the actual limit value 2 bytes C R W - - - Low
Continued
Continues
C = Communication; R = Read; W = Write; T = Transmission; U = Enable update
ETS parameters and communication objects
Page 8
8
No. ETS name Function Description Type
Flag 1
Priority
C R W T U I
45
Limit value brightness 2
Default value
Brightness 2 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
46
Limit value brightness 2
Actual value Brightness 2 limit value: to read the actual limit value 2 bytes C R W - - - Low
47
Limit value brightness 3
Default value
Brightness 3 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
48
Limit value brightness 3
Actual value Brightness 3 limit value: to read the actual limit value 2 bytes C R W - - - Low
49 Control output
Brightness 1 LV
Brightness 1 Limit Value control output. 1 bit C R - T - - Low
50 Control output
Brightness 2 LV
Brightness 2 Limit Value control output. 1 bit C R - T - - Low
51 Control output
Brightness 3 LV
Brightness 3 Limit Value control output. 1 bit C R - T - - Low
52
Limit value twilight 1
Default value
Twilight function 1 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
53
Limit value twilight 1
Actual value
Twilight function 1 limit value: to read the actual limit value
2 bytes C R W - - - Low
54
Limit value twilight 2
Default value
Twilight function 2 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
55
Limit value twilight 2
Actual value
Twilight function 2 limit value: to read the actual limit value
2 bytes C R W - - - Low
56
Limit value twilight 3
Default value
Twilight function 3 limit value: to set the setpoint of the limit value
2 bytes C R W T U - Low
57
Limit value twilight 3
Actual value
Twilight function 3 limit value: to read the actual limit value
2 bytes C R W - - - Low
58
Twilight 1 LV control output
Output Twilight 1 Limit Value control output. 1 bit C R - T - - Low
59
Twilight 2 LV control output
Output Twilight 2 Limit Value control output. 1 bit C R - T - - Low
60
Twilight 3 LV control output
Output Twilight 3 Limit Value control output. 1 bit C R - T - - Low
61 Logic AND 1 Control output Logic output AND 1 at 1 bit. 1 bit C R - T - - Low
62 Logic AND 1 Output A at 8 bits Output A at 8 bits of the logic output AND 1. 1 bytes C R - T - - Low
63 Logic AND 1 Output B at 8 bits Output B at 8 bits of the logic output AND 1. 1 bytes C R - T - - Low
64 Logic AND 2 Control output Logic output AND 2 at 1 bit. 1 bit C R - T - - Low
65 Logic AND 2 Output A at 8 bits Output A at 8 bits of the logic output AND 2. 1 bytes C R - T - - Low
66 Logic AND 2 Output B at 8 bits Output B at 8 bits of the logic output AND 2. 1 bytes C R - T - - Low
67 Logic AND 3 Control output Logic output AND 3 at 1 bit. 1 bit C R - T - - Low
68 Logic AND 3 Output A at 8 bits Output A at 8 bits of the logic output AND 3. 1 bytes C R - T - - Low
69 Logic AND 3 Output B at 8 bits Output B at 8 bits of the logic output AND 3. 1 bytes C R - T - - Low
70 Logic AND 4 Control output Logic output AND 4 at 1 bit. 1 bit C R - T - - Low
71 Logic AND 4 Output A at 8 bits Output A at 8 bits of the logic output AND 4. 1 bytes C R - T - - Low
Continues C = Communication; R = Read; W = Write; T = Transmission; U = Enable update
Continued
ETS parameters and communication objects
KNX weather station
Page 9
9
VIMAR group
Continued
Continues C = Communication; R = Read; W = Write; T = Transmission; U = Enable update
No. ETS name Function Description Type
Flag 1
Priority
C R W T U I
72 Logic AND 4 Output B at 8 bits Output B at 8 bits of the logic output AND 4. 1 bytes C R - T - - Low
73 Logic AND 5 Control output Logic output AND 5 at 1 bit. 1 bit C R - T - - Low
74 Logic AND 5 Output A at 8 bits Output A at 8 bits of the logic output AND 5. 1 bytes C R - T - - Low
75 Logic AND 5 Output B at 8 bits Output B at 8 bits of the logic output AND 5. 1 bytes C R - T - - Low
76 Logic AND 6 Control output Logic output AND 6 at 1 bit. 1 bit C R - T - - Low
77 Logic AND 6 Output A at 8 bits Output A at 8 bits of the logic output AND 6. 1 bytes C R - T - - Low
78 Logic AND 6 Output B at 8 bits Output B at 8 bits of the logic output AND 6. 1 bytes C R - T - - Low
79 Logic AND 7 Control output Logic output AND 7 at 1 bit. 1 bit C R - T - - Low
80 Logic AND 7 Output A at 8 bits Output A at 8 bits of the logic output AND 7. 1 bytes C R - T - - Low
81 Logic AND 7 Output B at 8 bits Output B at 8 bits of the logic output AND 7. 1 bytes C R - T - - Low
82 Logic AND 8 Control output Logic output AND 8 at 1 bit. 1 bit C R - T - - Low
83 Logic AND 8 Output A at 8 bits Output A at 8 bits of the logic output AND 8. 1 bytes C R - T - - Low
84 Logic AND 8 Output B at 8 bits Output B at 8 bits of the logic output AND 8. 1 bytes C R - T - - Low
85 Logic OR 1 Control output Logic output OR 1 at 1 bit. 1 bit C R - T - - Low
86 Logic OR 1 Output A at 8 bits Output A at 8 bits of the logic output OR 1. 1 bytes C R - T - - Low
87 Logic OR 1 Output B at 8 bits Output B at 8 bits of the logic output OR 1. 1 bytes C R - T - - Low
88 Logic OR 2 Control output Logic output OR 2 at 1 bit. 1 bit C R - T - - Low
89 Logic OR 2 Output A at 8 bits Output A at 8 bits of the logic output OR 2. 1 bytes C R - T - - Low
90 Logic OR 2 Output B at 8 bits Output B at 8 bits of the logic output OR 2. 1 bytes C R - T - - Low
91 Logic OR 3 Control output Logic output OR 3 at 1 bit. 1 bit C R - T - - Low
92 Logic OR 3 Output A at 8 bits Output A at 8 bits of the logic output OR 3. 1 bytes C R - T - - Low
93 Logic OR 3 Output B at 8 bits Output B at 8 bits of the logic output OR 3. 1 bytes C R - T - - Low
94 Logic OR 4 Control output Logic output OR 4 at 1 bit. 1 bit C R - T - - Low
95 Logic OR 4 Output A at 8 bits Output A at 8 bits of the logic output OR 4. 1 bytes C R - T - - Low
96 Logic OR 4 Output B at 8 bits Output B at 8 bits of the logic output OR 4. 1 bytes C R - T - - Low
97 Logic OR 5 Control output Logic output OR 5 at 1 bit. 1 bit C R - T - - Low
98 Logic OR 5 Output A at 8 bits Output A at 8 bits of the logic output OR 5. 1 bytes C R - T - - Low
99 Logic OR 5 Output B at 8 bits Output B at 8 bits of the logic output OR 5. 1 bytes C R - T - - Low
COMMUNICATION OBJECTS
ETS parameters and communication objects
KNX weather station
Page 10
10
No. ETS name Function Description Type
Flag 1
Priority
C R W T U I
100 Logic OR 6 Control output Logic output OR 6 at 1 bit. 1 bit C R - T - - Low
101 Logic OR 6 Output A at 8 bits Output A at 8 bits of the logic output OR 6. 1 bytes C R - T - - Low
102 Logic OR 6 Output B at 8 bits Output B at 8 bits of the logic output OR 6. 1 bytes C R - T - - Low
103 Logic OR 7 Control output Logic output OR 7 at 1 bit. 1 bit C R - T - - Low
104 Logic OR 7 Output A at 8 bits Output A at 8 bits of the logic output OR 7. 1 bytes C R - T - - Low
105 Logic OR 7 Output B at 8 bits Output B at 8 bits of the logic output OR 7. 1 bytes C R - T - - Low
106 Logic OR 8 Control output Logic output OR 8 at 1 bit. 1 bit C R - T - - Low
107 Logic OR 8 Output A at 8 bits Output A at 8 bits of the logic output OR 8. 1 bytes C R - T - - Low
108 Logic OR 8 Output B at 8 bits Output B at 8 bits of the logic output OR 8. 1 bytes C R - T - - Low
Continued
ETS parameters and communication objects
C = Communication; R = Read; W = Write; T = Transmission; U = Enable update
KNX weather station
Number of communication objects Max. number of group addresses Max. number of associations
109 254 255
Page 11
11
VIMAR group
ETS parameters and communication objects
COMMUNICATION OBJECTS
KNX weather station
Reference ETS parameters
Behaviour in the event of a power failure and when power is restored.
Behaviour if there is no Bus voltage or auxiliary voltage:
The device transmits no data.
Behaviour if there is no Bus voltage or auxiliary voltage and subsequent programming or restarting:
The device sends all the measured values, control outputs and the status of the logic gates according to the behaviour set by the parameters in the "General Settings". When powering up, information will be sent with a settable delay.
General settings
General settings
ETS text
Available values
Comment
[
Default value
]
Send measured values periodically all
5 s ... 2 h
[
5 s
]
Send control outputs peri­odically all
5 s ... 2 h
[
5 s
]
Send logic outputs periodically all
5 s ... 2 h
[
5 s
]
Logic input communication objects
do not enable enable
[
do not enable
]
Night control output com­munication object
Do not send
Send with change
Send reversed with change
Send with change and cyclically
Send reversed with change and cyclically
[Send with change]
Rain control output com­munication object
Do not send
Send with change
Send reversed with change
Send with change and cyclically
Send reversed with change and cyclically
[Send with change]
Control output transmission delay after Power up and programm.
5 s ... 2 h
When powering up and after program­ming, the weather station waits for the set time delay before transmitting the control outputs.
[
10 s
]
Maximum speed of the telegram
1... 20 telegrams per second
[5 telegrams per second]
Page 12
12
ETS parameters and communication objects
KNX weather station
Temperature
Temperature
ETS text
Available values
Comment
[
Default value
]
Measured value
Do not send
Send cyclically
Send with change
Send with change or cyclically
[
Send cyclically
]
Starting from a temperature change of
0.5 °C ... 5 °C
It is displayed when selecting "Send with change" for the measured value
[0.
5 °C
]
Temperature offset 0.1°C
-50...50
[0]
Transmit and reset the min. and max temperature value on request
do not enable
Enables/disables the communication objects 13-14-15 and 16. 13-Min/max temper­ature request. 14-Measured min. temperature value. 15-Measured max. temperature value. 16-Min/max temper­ature reset.
enable
[
do not enable
]
Use error object
No
Enables/disables communication object: 10- Temperature sensor error
Yes
[No]
Limit value 1
off
on
[
off
]
Limit value 1,2,3,4
When the above parameter Limit Value is selected as on it is necessary to set its characteristics and those of the Control output too.
Limit value on
ETS text
Available values
Comment
[
Default value
]
The limit value will be set by the
Parameter
Communication object
Communication object saving the last value
[
Parameter
]
Limit value in 0.1°C
-300 ...800
[200]
Hysteresis of the limit value in 0.1°C
0..100 See par. Hysteresis
on page 20
[30]
ETS text
Available values
Comment
[
Default value
]
Limit value 2
off
on
[
off
]
Limit value 3
off
on
[
off
]
Limit value 4
off
on
[
off
]
Continues
Continued
Continues
Page 13
13
VIMAR group
ETS parameters and communication objects
COMMUNICATION OBJECTS
KNX weather station
ETS text
Available values
Comment
[
Default value
]
On delay
none, 1s, 1min...2h
[none]
Off delay
none, 1s, 1min...2h
[none]
Output activates with
LV upper = ON | LV - lower hyst. = OFF
LV lower = ON | LV + lower hyst. = OFF
[LV upper = ON | LV - lower hyst. = OFF]
Control output communica­tion object LV 1 temperature
Do not send
Send with change
Send reversed with change
Send with change and cyclically
Send reversed with change and cyclically
[Do not send]
Continued
Limit value set by "Comm. object saving the last value"
Note: If the threshold value is set by a communication object, the threshold value must be specified during configuration because this value remains valid until the 1st object is sent with the new threshold value. In the case of weather stations that have already been put into service, the last threshold value sent by the communication object is used. If a threshold is set once using the parameter or a communication object, the last set threshold value remains until a new threshold value is transmitted by a communication object. The last threshold values set by the communication objects are saved in EEPROM memory, so as to preserve the values during a power failure that are then available when power is restored.
Wind
ETS text
Available values
Comment
[
Default value
]
Measured value
Do not send
Send cyclically
Send with change
Send with change or cyclically
[
Send cyclically
]
Starting from a change in wind strength of:
1m/s...4m/s
It is displayed when selecting "Send with change" and "Send with change and cyclically"
[1m/s
]
Transmit and reset the max wind strength value on request
do not enable
Enables/disables the communication ob­jects 30-31 and 32. 30- Request for max. wind strength 31-Max. measured wind strength value. 32-Reset max. wind strength.
enable
[
do not enable
]
Use error object
No
Enables/disables communication object: 11- Wind sensor error.
Yes
[No]
Limit value 1
off
on
[
off
]
Wind
ETS text
Available values
Comment
[
Default value
]
Limit value 2
off
on
[
off
]
Limit value 2
off
on
[
off
]
Continues
Continued
Page 14
14
ETS parameters and communication objects
KNX weather station
Limit value 1,2,3
When the above parameter Limit Value is selected as on it is necessary to set its characteristics and those of the Control output too.
ETS text
Available values
Comment
[
Default value
]
The limit value will be set by the
Parameter
Communication object
Communication object saving the last value
[
Parameter
]
Limit value in 0.1 m/s
0 ...350
[40]
Hysteresis of the limit value in 0.1 m/s
0..250 See par. Hysteresis
on page 20
[20]
On delay
none, 1s, 1min...2h
[none]
Off delay
none, 1s, 1min...2h
[none]
Output activates with
LV upper = ON | LV - lower hyst. = OFF
LV lower = ON | LV + lower hyst. = OFF
[LV upper = ON | LV - lower hyst. = OFF]
Control output commu­nication object LV 1 wind strength
Do not send
Send with change
Send reversed with change
Send with change and cyclically
Send reversed with change and cyclically
[Do not send]
Limit value on
Note: If the threshold value is set by a communication object, the threshold value must be specified during configuration because this value remains valid until the 1st object is sent with the new threshold value. In the case of weather stations that have already been put into service, the last threshold value sent by the communication object is used. If a threshold is set once using the parameter or a communication object, the last set threshold value remains until a new threshold value is transmitted by a communication object. The last threshold values set by the communication objects are saved in EEPROM memory, so as to preserve the values during a power failure that are then available when power is restored.
Page 15
15
VIMAR group
ETS parameters and communication objects
COMMUNICATION OBJECTS
KNX weather station
Brightness
Brightness
ETS text
Available values
Comment
[
Default value
]
Measured value
Do not send
Send cyclically
Send with change
Send with change or cyclically
[
Send cyclically
]
Starting from a change in %
1 ... 50
It is displayed when selecting "Send with change" and "Send with change and cyclically" for the measured value
[10]
Limit value 1
off
on
[
off
]
Limit value 2
off
on
[
off
]
Limit value 1,2,3
When the above parameter Limit Value is selected as on it is necessary to set its characteristics and those of the Control output too.
Limit value on
ETS text
Available values
Comment
[
Default value
]
The limit value will be set by the
Parameter
Communication object
Communication object saving the last value
[
Parameter
]
Limit value in klux
1 ...99
[5]
Hysteresis of the limit value in klux
0..99 See par. Hysteresis
on page 20
[2]
On delay
none, 1s, 1min...2h
[none]
Off delay
none, 1s, 1min...2h
[none]
Output activates with
LV upper = ON | LV - lower hyst. = OFF
LV lower = ON | LV + lower hyst. = OFF
[LV upper = ON | LV - lower hyst. = OFF]
Continues
ETS text
Available values
Comment
[
Default value
]
Limit value 3
off
on
[
off
]
Continues
Continued
Page 16
16
ETS parameters and communication objects
KNX weather station
ETS text
Available values
Comment
[
Default value
]
Control output communica­tion object LV 1 brightness
Do not send
Send with change
Send reversed with change
Send with change and cyclically
Send reversed with change and cyclically
[Do not send]
Continued
Note: If the threshold value is set by a communication object, the threshold value must be specified during configuration because this value remains valid until the 1st object is sent with the new threshold value. In the case of weather stations that have already been put into service, the last threshold value sent by the communication object is used. If a threshold is set once using the parameter or a communication object, the last set threshold value remains until a new threshold value is transmitted by a communication object. The last threshold values set by the communication objects are saved in EEPROM memory, so as to preserve the values during a power failure that are then available when power is restored.
Twilight
ETS text
Available values
Comment
[
Default value
]
Limit value 1
off
on
[
off
]
Limit value 2
off
on
[
off
]
Limit value 2
off
on
[
off
]
Twilight
Limit value 1,2,3
When the above parameter Limit Value is selected as on it is necessary to set its characteristics and those of the Control output too.
Limit value on
ETS text
Available values
Comment
[
Default value
]
The limit value will be set by the
Parameter
Communication object
Communication object saving the last value
[
Parameter
]
Limit value in lux
1 ...1000
[200]
Hysteresis of the limit value in lux
0..1000
See par. Hysteresis on page 20
[50]
On delay
none, 1s, 1min...2h
[none]
Off delay
none, 1s, 1min...2h
[none]
Page 17
17
VIMAR group
COMMUNICATION OBJECTS
ETS parameters and communication objects
KNX weather station
ETS text
Available values
Comment
[
Default value
]
Output activates with
LV upper = ON | LV - lower hyst. = OFF
LV lower = ON | LV + lower hyst. = OFF
[LV upper = ON | LV - lower hyst. = OFF]
Control output communica­tion object LV 1 twilight
Do not send
Send with change
Send reversed with change
Send with change and cyclically
Send reversed with change and cyclically
[Do not send]
Note: If the threshold value is set by a communication object,
the threshold value must be specified during configuration because this value remains valid until the 1st object is sent with the new threshold value. In the case of weather stations that have already been put into service, the last threshold value sent by the communication object is used. If a threshold is set once using the parameter or a communication object, the last set threshold value remains until a new threshold value is transmitted by a communication object. The last threshold values set by the communication objects are saved in EEPROM memory, so as to preserve the values during a power failure that are then available when power is restored.
Logics
ETS text
Available values
Comment
[
Default value
]
Logic 1
off
on
[
off
]
Logic 2
off
on
[
off
]
Logic 3
off
on
[
off
]
Logic 4
off
on
[
off
]
Logic 5
off
on
[
off
]
Logic 6
off
on
[
off
]
Logic 7
off
on
[
off
]
Logic 8
off
on
[
off
]
Logics
Page 18
18
ETS parameters and communication objects
KNX weather station
ETS text
Available values
Comment
[
Default value
]
1. Input
Do not use
Communication ob­jects can be selected as an input for the logic function.
Night = 1
Night = 0
Limit value twilight 1
Limit value twilight 1 reversed
Limit value twilight 2
Limit value twilight 2 reversed
Limit value twilight 3
Limit value twilight 3 reversed
Limit value brightness 1
Limit value brightness 1 reversed
Limit value brightness 2
Limit value brightness 2 reversed
Limit value brightness 3
Limit value brightness 3 reversed
Logic input 1 communi­cation object
Logic input 1 rev. com­munication object
Logic input 2 communi­cation object
Logic input 2 rev. com­munication object
Logic input 3 communi­cation object
Logic input 3 rev. com­munication object
Logic input 4 communi­cation object
Logic input 4 rev. com­munication object
Logic input 5 communi­cation object
Logic input 5 rev. com­munication object
Logic input 6 communi­cation object
Logic input 6 rev. com­munication object
Logic input 7 communi­cation object
Logic input 7 rev. com­munication object
Logic input 8 communi­cation object
Logic input 8 rev. com­munication object
Logic AND
ETS text
Available values
Comment
[
Default value
]
1. Input
Rain Yes
Communication ob­jects can be selected as an input for the logic function.
Rain No
Temperature error
Temperature error reversed
Wind error
Reversed wind error
Temperature 1 LV
Temperature 1 LV reversed
Temperature 2 LV
Temperature 2 LV reversed
Temperature 3 LV
Temperature 3 LV reversed
Temperature 4 LV
Temperature 4 LV reversed
Wind 1 LV
Wind 1 LV reversed
Wind 2 LV
Wind 2 LV reversed
Wind 3 LV
Wind 3 LV reversed
[
Do not use
]
2. Input As 1. Input As 1. Input
3. Input As 1. Input As 1. Input
4. Input As 1. Input As 1. Input
Logic output transmits
no
one 1-bit object
two 8-bit objects
[no]
Continues
Continued
Page 19
19
VIMAR group
COMMUNICATION OBJECTS
ETS parameters and communication objects
KNX weather station
Logic AND
Logic AND with Logic output transmits "one 1-bit object" Logic AND with Logic output transmits "two 8-bit objects"
Logic OR
Logic OR
The parameters with which the OR logic gates are configured are similar to those previously illustrated for the AND logic gates. Therefore please refer to the information on the previous pages.
Page 20
20
ETS parameters and communication objects
KNX weather station
Hysteresis of the limit value.
This section graphically illustrates the meaning of the Hysteresis parameter for the object with Limit Value 1,2,3 for Temperature, Wind, Brightness and Twilight.