Viking Range Designer Series, DCH3042SS Installation Instructions Manual

1
INSTALLATION INSTRUCTIONS
Designer Series BUILT-IN chimney-style HOODS
VIKING RANGE CORPORATION
111 FRONT STREET
GREENWOOD, MISSISSIPPI 38930 USA
(662) 455-1200
IMPORTANT - PLEASE READ AND FOLLOW
•Before beginning, please read these instructions completely and carefully.
•Do not remove permanently affixed labels, warnings, or plates from the product. This may void the warranty.
•Please observe all local and national codes and ordinances. If no local codes are applicable, wire in accordance with the National Electrical Code, ANSI/NFPA 70-latest edition.
CChheecckk wwiitthh aa qquuaalliiffiieedd aanndd ttrraaiinneedd iinnssttaalllleerr oorr llooccaall ccooddeess ffoorr mmaakkeeuupp aaiirr rreeqquuiirreemmeenntt,, iiff aannyy..
The installer should leave these instructions with the consumer who should retain for local inspector’s use and for future reference.
This hood is for residential installation only and is not designed for installation over a commercial product. Make sure power is off at the main circuit breaker or fuse box before making connections. To avoid risk of fire, electric shock, or injury to persons,
turn off the electricity to the hood from the power supply before servicing or cleaning.
Viking hoods are equipped with variable speed controls for blowers. These units will not function with a single speed ventilator. All Viking Range ventilator kits are designed specifically for use with Viking Range hoods. Use of any non-Viking Range ventilator kit will void the hood warranty.
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction.
2. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
3. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
4. Ducted fans must always be vented to the outdoors.
5. WARNING
!!::
To reduce the risk of fire, use only metal ductwork.
6. CAUTION
!!::
To reduce risk of fire and to properly exhaust air, be sure to duct air outside. Do not vent exhaust
air into spaces within walls or ceilings, or into attics, crawl spaces, or garages.
CAUTION
For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS, RANGEHOODS MUST BE INSTALLED WITH THE VENTILATORS THAT ARE SPECIFIED ON THEIR CARTON INDICATING SUITABILITY WITH THIS MODEL. OTHER VENTILATORS CANNOT BE SUBSTITUTED.
WARNING
TO REDUCE THE RISK OF A RANGETOP GREASE FIRE:
1. Never leave surface units unattended at high setting. Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.
2. Always turn hoon ON when cooking at high heat or when cooking flaming foods.
3. Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or filter.
4. Use proper pan size. Always use cookware appropriate for the size of the surface element.
BASIC SPECIFICATIONS INTERIOR AND EXTERIOR POWER HOODS
RREECCOOMMMMEENNDDEEDD MMAAXX.. DDUUCCTT
MMOODDEELL NNUUMMBBEERR CCFFMM
11
DDUUCCTT SSIIZZEE RRUUNN
22
((fftt..))
FFoorr UUssee wwiitthh hhooooddss::
DIV300 (interior) 300 7” round 50
DIV440 (interior) 440 7” round 50
DIV600 (interior) 600 7” round 50
DIV1200 (interior) 1200 10” round 50
DEV900 (exterior) 900 10” round 50
DEV1200 (exterior) 1200 10” round 50
DEV1500 (exterior) 1500 10” round 75
PROPER INSTALLATION/DUCTING IS EXTREMELY IMPORTANT TO ENSURE MAXIMUM PERFORMANCE FROM ANY VENTILATION PRODUCT
1. •All CFMs stated are based on tests at .1 static pressure: without applying static pressure, CFM would be greatly overstated.
2. •Duct run length is for general reference only; for longer duct runs, increase duct size and contact a qualified and trained installer.
•Straight runs and gradual turns are best; for example, each 90
o
elbow is equivalent to 5-10 feet (1.52 - 3.05 cm) of
straight run.
•Never use flexible duct; it creates back pressure/air turbulence and greatly reduces performance.
•Proper performance is dependent upon proper ducting; make sure that a qualified and trained installer is used.
CChheecckk wwiitthh aa qquuaalliiffiieedd aanndd ttrraaiinneedd iinnssttaalllleerr oorr llooccaall ccooddeess ffoorr mmaakkeeuupp aaiirr rreeqquuiirreemmeenntt,, iiff aannyy..
3. •Max. amp rating for hoods includes recommended ventilator kit rating; all products must be hard wired direct with 2­wire with ground.
**11220000 CCFFMM ((oorr 11550000 CCFFMM iiff aapppplliiccaabbllee)) eexxtteerriioorr vveennttiillaattoorr sshhoouulldd bbee uusseedd wwhheenn iinnssttaalllleedd oovveerr rraannggeess//rraannggeettooppss wwiitthh ggaass ggrriillll..
RREECCOOMM.. NNUUMMBBEERR OOFF 112200VVAACC//6600HHzz
DDEESSCCRRIIPPTTIIOONN CCFFMM
11
HHAALLOOGGEENN FFIILLTTEERRSS SSPPAACCEERRSS MMAAXX.. AAMMPPSS
33
((iinntt..--iinntteerriioorr;; eexxtt--eexxtteerriioorr
LLIIGGHHTTSS
((IInntteerriioorr//EExxtteerriioorr))
30”W. 300 int,/440 int./900 ext./1200 ext. 2 2 0 1.7/3.2/6.6/3.9 36”W.* 300 int./600 int./900 ext./1200 ext. 2 2 1 1.7/3.9/6.6/3.9 42”W.* 600 int./900 ext./1200 ext. 2 3 0 3.9/6.6/3.9 48”W.
1200 int./1200 ext./1500 ext.
3 3 0 7.3/4.3/5.1
WWaallll HHooooddss
RREECCOOMM.. NNUUMMBBEERR OOFF 112200VVAACC//6600HHzz
DDEESSCCRRIIPPTTIIOONN CCFFMM
11
HHAALLOOGGEENN FFIILLTTEERRSS SSPPAACCEERRSS MMAAXX.. AAMMPPSS
33
((iinntt..--iinntteerriioorr;; eexxtt--eexxtteerriioorr
LLIIGGHHTTSS
((IInntteerriioorr//EExxtteerriioorr))
36”W.* 600 int./900 ext./1200 ext. 4 2 1 3.9/6.6/3.9
42”W.* 600 int./900 ext./1200 ext./1500 ext. 4 2 1 4.7/7.4/4.8/5.5
54”W.
1200 int./1200 ext./1500 ext. 6 3 2 8.6/5.6/6.4
IIssllaanndd HHooooddss
2
3
HEIGHT OF HOOD
The bottom of the hood to should be 30” (76.2 cm) min. to 36” (91.4 cm) max above the countertop. This would typically result in the bottom of the hood being 66” (167.6 cm) to 72” (182.9 cm) above the floor. For best performance, it is recommended that the bottom of the hood be 30” (76.2 cm) to 33” (83.8 cm) above the countertop. These dimensions provide for safe and efficient operation of the hood.
ISLAND INSTALLATION
WALL INSTALLATION
Cooking
Surface
Cooking
Surface
30” W. Models-
12” (30.5 cm)
All other models-
14” (35.6 cm)
14” (35.6 cm)
30” (76.2 cm) min
36” (91.4 cm) max
30” (76.2 cm) min
36” (91.4 cm) max
36”
(91.4 cm)
36”
(91.4 cm)
INSTALLING HOOD CANOPY
(Before installing island hood canopy - skip to page 5)
Center the canopy and attach to wall. Secure the hood to wall with mounting screws provided. Make sure that the mounting screws are driven into the framing and not just the drywall. Use additional mounting screws (and wall anchors if necessary) in the other holes.
NOTE: BECAUSE OF THE WEIGHT OF THE HOOD - MAKE SURE THAT THE MOUNTING SCREWS ARE DRIVEN INTO THE FRAMING AND NOT JUST THE DRYWALL. IT MAY BE NECESSARY TO DRILL ADDITIONAL HOLES IN THE CANOPY FOR PROPER ALIGNMENT.
4
PREPARING FOR HOOD INSTALLATION
Plan where the ductwork will be located. See pages 11-14 for rough-in dimensions. Install proper-sized duct work, and roof or wall cap for the type of blower you are using. Recommended hood locations for the most common installations are shown on page 2. Adjust your measurements for various heights of ceilings, soffits, cabinets, or ranges/rangetops.
Roof Cap
10” Round
Duct
1200 CFM Single
Blower
Interior-Power -
Typical Ductwork
Exterior Blower
10” Round
Duct
12” Duct
Cover
or Soffit
900, 1200, or
1500 CFM Exterior-Power ­Typical Ductwork
ELECTRICAL SUPPLY
Run 120 VAC electrical power cable from service panel to installation location. See “Basic Specifications” on page 15 for the maximum amp requirements.
Top Mounting Holes (Soffit or duct cover)
12” Duct Cover
or Soffit
Roof Cap
7” Round
Duct
600 CFM Single
Blower
Interior-Power -
Typical Ductwork
Duct Cover or Soffit
Roof Cap
7” Round
Duct
300 or 440 CFM
Single Blower
Interior-Power -
Typical Ductwork
Duct Cover or Soffit
5
INSTALLING THE DUCT COVER (wall hoods only)
1. Measure from top of the canopy to ceiling and subtract 1/8” (0.3 cm) for clearance.
2. Place the duct cover top inside the duct cover base and lower until desired height is found. (To eliminate scratches, make a mark on the duct cover top for the desired lowering point by subtracting 18” (45.7 cm) from the total height needed.)
3. Use the retaining nuts and bolts to fasten in place.
4. Slide the duct cover in place and fasten from inside canopy using the sheet metal screws provided.
5. Note: For installations with ceilings above 9’ (22.9 cm), use optional duct extensions. See product literature for
details
Item 1
C
12” (30.5 cm)
Duct
Cover Top
Duct Cover
Base
Item 2
A
Min
B
Max
Item 4
Item 3
Canopy Top
Model “A” Min. “B” Max “C”
DCWH3042 18” (45.7 cm) 30” (76.2 cm) 10” (25.4 cm) DCWH3644 16” (40.6 cm) 28” (71.1 cm) 12” (30.5 cm) DCWH4244 16” (40.6 cm) 28” (71.1 cm) 12” (30.5 cm) DCWH4844 16” (40.6 cm) 28” (71.1 cm) 18” (45.7 cm)
DCWL3342 18” (45.7 cm) 30” (76.2 cm) 10” (25.4 cm) DCWL3944 16” (40.6 cm) 28” (71.1 cm) 12” (30.5 cm) DCWL4544 16” (40.6 cm) 28” (71.1 cm) 12” (30.5 cm) DCWL5144 16” (40.6 cm) 28” (71.1 cm) 18” (45.7 cm)
DCWN3042 18” (45.7 cm) 30” (76.2 cm) 10” (25.4 cm) DCWN3644 16” (40.6 cm) 28” (71.1 cm) 12” (30.5 cm) DCWN4244 16” (40.6 cm) 28” (71.1 cm) 12” (30.5 cm) DCWN4844 16” (40.6 cm) 28” (71.1 cm) 18” (45.7 cm)
6
INSTALLING THE optional DUCT COVER (island hoods only)
1. Cut hole in ceiling for correct diameter duct.
2. Attach duct cover/soffit to ceiling. Make sure there is enough support in the ceiling to support at least 200 lbs. (Center duct cover/soffit with duct opening)
3. Run duct work down to bottom edge of duct cover/soffit and secure in place. (Make sure the duct does not stick down past the cover/soffit.)
4. Attach duct cover/soffit to the top of the canopy with nuts and bolts provided. (Additional support can be added by running threaded rod from the ceiling to the top of the canopy at all four corners using the holes provided.)
5. Install blower (see ventilator kit installation).
A
B
12”
(30.5 cm)
6”
(15.3 cm)
C
2
1
4
3
Holes for threaded rod (4)
Canopy
To p
36”W. / 42”W. 54”W. A 12” (30.5 cm) 18” (45.7 cm) B 6” (15.3 cm) 9” (22.7 cm) C 16” (40.6 cm), 16” (40.6 cm),
28” (71.1 cm), or 28” (71.1 cm), or
40” (101.6 cm) 40” (101.6 cm)
Duct Cover/Soffit
7
ventilator kit installation DiV300
(Also see instructions supplied with ventilator kit)
1. Attach DAMPER to VENTILATOR, as shown, using three (3) HEX SCREWS (provided). Note: Damper flange to be captured by screw heads.
2. Attach VENTILATOR to (4) THREADED STUDS on MOUNTING PLATE using (4) HEX NUTS (provided).
3. Lift ventilator into position inside the hood.
4. Fasten ventilator to four (4) THREADED STUDS, using four (4) HEX NUTS (provided).
5. Plug ventilator's POWER CORD into RECEPTACLE inside the hood.
ventilator kit installation DiV440
(Also see instructions supplied with ventilator kit)
1. Attach DAMPER to VENTILATOR, as shown, using three (3) HEX SCREWS (provided). Note: Damper flange to be captured by screw heads.
2. Lift ventilator into position inside the hood.
3. Fasten ventilator to four (4) THREADED STUDS, using four (4) HEX NUTS (provided).
4. Plug ventilator's POWER CORD into RECEPTACLE inside the hood.
5. NOTE: This installation does not use the mounting
plate and (4) additional hex nuts. They may be discarded.
8
ventilator kit installation DiV600
(Also see instructions supplied with ventilator kit)
1. Choose the correct VENTILATOR MOUNTING PLATE for your hood series.
2. Attach DAMPER to VENTILATOR, as shown, using three (3) HEX SCREWS (provided). Note: Damper FLANGE to be captured by screw heads.
3. Slide mounting plate/damper assembly into hood and onto four (4) THREADED STUDS, as shown. Slide four (4) NEOPRENE WASHERS onto threaded studs to temporarily hold plate to hood.
4. Rotate ventilator 90oand lift into position inside hood.
5. Roatate ventilator back to orientation shown.
6. Fasten ventilator to four (4) threaded studs, using four (4) HEX NUTS.
7. Plug ventilator's POWER CORD into RECEPTACLE inside the hood.
TThhrreeaaddeedd SSttuuddss
NNeeoopprreennee WWaasshheerrss
DDCCWW//DDCCII SSeerriieess VVeennttiillaattoorr MMoouunnttiinngg PPllaattee
FFllaannggee
TToopp ooff hhoooodd
HHeexx SSccrreewwss
DDaammppeerr
RReecceeppttaaccllee
PPoowweerr CCoorrdd
VVeennttiillaattoorr
HHeexx NNuuttss
ventilator kit installation DiV1200
(Also see instructions supplied with ventilator kit)
1. Remove REAR FILTER RAIL from hood.
2. Lift VENTILATOR into position inside the hood.
3. Engage two (2) TABS on ventilator into two (2) SLOTS in TOP OF HOOD. Secure ventilator to THREADED STUDS with two (2) HEX NUTS (provided).
4. Plug ventilator's POWER CORDS into RECEPTACLES inside the hood.
5. Replace rear filter rail.
6. Fasten the provided plate with #10 x 1/2” sheet metal
screws to cover electrical box opening.
TThhrreeaaddeedd SSttuuddss
TToopp ooff hhoooodd
RReecceeppttaacclleess
PPoowweerr CCoorrddss
VVeennttiillaattoorr
HHeexx NNuuttss
RReeaarr FFiilltteerr
RRaaiill
SSlloott
TTaabb
9
CONNECTING DUCTWORK -EXTERNAL POWER DEV900/DEV1200 /DEV1500
(Also see instructions supplied with ventilator kit)
1. Run 10” (25.4 cm) round steel ductwork from external blower to the installation location. For best performance, use the straighest possible duct run and the fewest number of elbows. Tape all joints.
2. Run 120 VAC electrical power cable from service panel and remote blower to installation location.
3. Remove wiring box cover. Feed 6” (15.2 cm) of power cable (from service and remote blower) through the openings. See illustration below.
4. Wire black to black, white to white, and green or bare (ground) to green ground screw (provided). Replace wiring box cover. Make sure to connect remote wires to 2-prong male cord and service to 3-prong female cord.
5. Connect duct work to top of hood (no tranistion required). Tape all joints.
Ventilator Kit Contents
Supply Cord with strain relief and rough in cover (1) #10 x 1/2 S.M.S Green grounding screw
10” (25.4 cm) damper mounts inside ductwork at least 3” (7.6 cm) above canopy outlet
10” (25.4 cm) round duct
House wiring
Top of hood
Female receptacle blower supply (power to blower)
Rough in cover
Blower supply cord to female receptacle on back of control panel
Rough in box
Power supply cord
Male plug on back of control panel
ROOF INSTALLATION EXTERIOR-POWER VENTILATOR
DEV900-Exterior Power Ventilator Kit (900CFM)
(also see instructions supplied with ventilator kit)
1. Locate the blower on the rear slope of the roof. Place it in a location to minimize duct run. The location should be free of obstacles (T.V. leads, electrical lines, etc.). Bear in mind, if the blower top is level with the roof peak, it will not be seen from the street. Keep this approximate location in mind as you work from within the attic.
2. Mark a point halfway between rafters.
3. Drill a guide hole through the roof at this point.
4. From the outside, use the guide hole as a starting point.
A. Use a T-square to measure 8
1
/2
” (21.6 cm) to the
left
of the guide hole, then down 10
3
/8”
(26.4 cm)
to locate the bottom left corner of the layout.
B. Mark the rectangular cutout and r
emove only the
shingles
in this area.
5. Mark an 11” (27.9 cm) diameter circle centered on the guide hole and mark the center of the 1
1
/4” (3.2 cm)
diameter electrical wiring hole.
6. Cut out the roof board(s) along the 11” (27.9 cm) diameter circle and drill a 1
1
/4” hole as marked.
7. For flat roof installations, build a curb that will mount the blower at a minimum pitch of 2/12. Discharge end of the blower should be pointed away from prevailing winds.
8. Remove roofing nails from the upper two-thirds of the shingles around the cutout area. Carefully lift the shingles to allow the back flashing sheet on the blower housing to fit under them.
9. Center the blower ring in the 11” (27.9 cm) diameter hole, making sure that the 1
1
/4” (3.2 cm) diameter
electrical wiring hold aligns with the hole in the wiring box.
10. Attach the blower to the roof with the six screws provided. It is recommende that the screws be located inside the blower housing. All six holes in the back panel must be filled, or any moisture that may get inside the housing could leak into the house.
11. Using a good grade of roofing cement, seal all of the
shingles around the housing and flashing sheet as well as the mounting screw heads.
12. Bring electrical wiring through the hole in the wiring
box and secure it according to local codes.
13. Make the electrical connections with the proper
connector for the type of wiring being used. Connect white to white, black to black, and the green or bare wire to green.
14. Replace wiring box cover and screws. Do not pinch
wiring under the cover.
15. Check for free movement of the damper before
installing housing cover and screws.
16. Turn on power and check operation of the blower.
Guide Hole
11” (27.9 cm)
dia. hole
7
1
/4” (18.4 cm)
1
1
/
4” (3.2 cm) dia. hole
8
1
/2” (21.6 cm)
10
3
/8”
(26.4 cm)
20
1
/2”
(52.1 cm)
9
1
/8”
(23.2 cm)
20
3
/4” (52.7 cm)
2”(5.1 cm)
2”(5.1 cm)
7” (17.8 cm)
29
1
/2”
(74.9 cm)
25” (63.5 cm)
RROOOOFF CCUUTTOOUUTT
RREEMMOOVVEE SSHHIINNGGLLEESS
Green to Green
White to White
Black to Black
120 VAC Line In
10
11
WALL INSTALLATION EXTERIOR-POWER VENTILATOR
DEV900-Exterior-Power Ventilator Kit (900CFM)
1. Choose a position on the outside wall. Min. 24” (61.0 cm from ground may vary depending on local codes or location. Make sure that no wall studs, pipes or wires run through the opening area.
2. Drill a guide hole at the center of the opening area.
3. From the outside, use the guide hole as a starting point to lay out the installation.
A. Use a T-square to measure 10
3
/4” (27.3 cm) to the
left of the guide hole, then 12
7/
8” (32.7 cm) to
locate the top-left corner of the layout.
B. Starting from the top -left corner, mark a 25”
(63.5 cm) by 28
1
/2” (72.4 cm) rectangle on wall
located from guide hole.
4. Cut a r
ectangular hole in the siding only. Do not cut
the sheathing. Nail down all siding ends.
5. Mark an 11” (27.9 cm) diameter circle centered on the guide hole and mark the center of the 1
1
/4” diameter
electrical wiring hole.
6. Cut the 11” (27.9 cm) hole in the sheathing and drill the 1
1
/4”(3.2 cm) as marked.
7. Place a large bead of caulk on the back side of the housing along the outer edge.
8. Center the blower ring in the 11” (27.9 cm) diameter hole, making sure that the 1
1
/4
” (3.2 cm) diameter electrical wiring hole aligns with the hole in the wiring box.
9. Attach blower to the wall with the six screws provided. It is recommended that the screws be located inside the blower housing. All six holes in the back panel must be filled, or any moisture that may get inside the housing could leak into the house.
10. Using a good grade of caulk, seal all around the mounting screw heads.
11. Bring electrical wiring through the hole in the wiring box and secure it according to local codes.
12. Make the electrical connections with the proper connector for the type of wire being used. Connect white to white, black to black, and green or bare wire to green.
13. Replace wiring box cover and screws. Do not pinch wiring under cover.
14. Check for free movement of the damper before installing housing cover and screws.
15. Turn on power and check operation of the blower.
16. Top and side flanges of the back plate may be covered with trim strips. Do not block grill opening at bottom with trim. It will adversely affect performance of the blower.
Black to Black
120 VAC Line In
White to White
Green to Green
11” (27.9 cm) dia. hole
Guide Hole
9
1
/8”
(23.2 cm)
7
1
/
4” (18.4 cm)
1
1
/4” (3.2 cm)
Dia. Hole
127/8”
(32.7 cm)
28 1/4” (71.8 cm)
25” (63.5 cm)
10
3
/4”
(27.3 cm)
WALL CUTOUT
ROOF INSTALLATION EXTERIOR-POWER VENTILATOR
Exterior Power Ventilator
(also see instructions supplied with ventilator kit)
1. Locate the blower on the rear slope of the roof. Place it in a location to minimize duct run. The location should be free of obstacles (T.V. leads, electrical lines, etc.). Bear in mind, if the blower top is level with the roof peak, it will not be seen from the street. Keep this approximate location in mind as you work from within the attic.
2. Mark a point halfway between rafters.
3. Drill a guide hole through the roof at this point.
4. From the outside, use the guide hole as a starting point to lay out the installation.
A. Use a T-square to measure 9
13
/16” (24.9 cm) to
the left of the guide hole, then 12
11
/16” (32.2 cm)
to locate the top-left corner of the layout.
B. Starting from the top-left corner, mark the
rectangular cutout and r
emove only the shingles in
this area.
5. Mark an 11” (27.9 cm) diameter hole centered on the guide hole. Mark the center of the 1
1
/4” (3.2 cm)
diameter electrical wiring hole.
6. Cut out the roof board(s) along the 11” (27.9 cm) diameter circle and drill a 1
1
/4” hole as marked.
7. For flat roof installations, build a curb that will mount the blower at a minimum pitch of 2/12. Discharge end of the blower should be pointed away from prevailing winds.
8. Remove roofing nails from the shingles around the top and sides of the cutout area only. Carefully lift the shingles to allow the back flashing sheet on the blower housing to fit under them.
9. Center the blower ring in the 11” (27.9 cm) diameter hole, making sure that the 1 ¼” (3.2 cm) diameter electrical wiring hold aligns with the hole in the wiring box.
10. Attach the blower to the roof with the six screws provided. It is recommended that the screws be located inside the blower housing. All six holes in the back panel must be filled, or any moisture that may get inside the housing could leak into the house.
11. Using a good grade of roofing cement, seal all of the
shingles around the housing and flashing sheet as well as the mounting screw heads.
12. Bring electrical wiring through the hole in the wiring
box and secure it according to local codes.
13. Make the electrical connections with the proper
connector for the type of wiring being used. Connect white to white, black to black, and the green or bare wire to green.
14. Replace wiring box cover and screws. Do not pinch
wiring under the cover.
15. Check for free movement of the damper before
installing housing cover and screws.
16. Turn on power and check operation of the blower.
20 1/2”
(52.1 cm)
BB
12 11/16” (32.2 cm)
AA
CC
1
1
/4” (3.2
cm) dia. hole
11” (27.9 cm)
dia. hole
RREEMMOOVVEE SSHHIINNGGLLEESS
29
1
/2
(74.9 cm)
DD
2” (5.1 cm)
2” (5.1 cm)
7”
(17.8 cm)
RROOOOFF CCUUTTOOUUTT
Black to Black
Ground to grounding
screw
120 VAC Line In
12
White to Blue
ABCD
DEV1200 18” 15” 9 13/16’ 22”
(45.7 cm) (38.1 cm) (24.9 cm) (55.9 cm)
DEV1500 21” 18” 12 5/8” 25”
(53.3 cm) (45.7 cm) (32.1 cm) (63.5 cm)
13
WALL INSTALLATION EXTERIOR-POWER VENTILATOR
Exterior Power Ventilator Kit
1. Choose a position on the outside wall. Min. 24” (61.0 cm from ground may vary depending on local codes or location. Make sure that no wall studs, pipes or wires run through the opening area.
2. From inside, mark and drill a guide hole at the center of the opening area.
3. From the outside, use the guide hoel as a starting point to lay out the installation.
A. Use a T-square to measure 11
13
/16” (30.0 cm) to the left
of the guide hole, then 14
11/
16” (37.3 cm) tolocate the
top-left corner of the layout.
B. Starting from the top-left corner, mark a 22” (55.9 cm) by
29
1
/2
” (74.9 cm) rectangle on wall located from guide
hole.
4. Cut a r
ectangular hole in the siding only. Do not cut the
sheathing.
Nail down all siding ends.
5. Mark an 11” (27.9 cm) diameter circle centered on the guide hole and mark the center of the 1
1
/4
” diameter electrical
wiring hole.
6. Cut the 11” (27.9 cm) hole in the sheathing and drill the 1
1
/4
”(3.2 cm) as marked.
7. Place a large bead of caulk on the back side of the housing along the outer edge.
8. Center the blower ring in the 11” (27.9 cm) diameter hole, making sure that the 1
1
/4” (3.2 cm) diameter electrical wiring
hole aligns with the hole in the wiring box.
9. Attach blower to the wall with the six screws provided. All six holes in the back panel must be filled, or any moisture that may get inside the housing could leak into the house.
10. Using a good grade of caulk, seal all around the mounting screw heads.
11. Bring electrical wiring through the hole in the wiring box and secure it according to local codes.
12. Make the electrical connections with the proper connector for the type of wire being used. Connect white to blue, black to black, and green or bare wire to grounding screw.
13. Replace wiring box cover and screws. Do not pinch wiring under cover.
14. Check for free movement of the damper before installing housing cover and screws.
15. Turn on power and check operation of the blower.
16. Top and side flanges of the back plate may be covered with trim strips. Do not block grill opening at bottom with trim. It will adversely affect performance of the blower.
WALL CUTOUT
BB
3”
(7.6 cm)
14
11/
16
(37.3 cm)
CC
AA
11” (27.9 cm) dia. hole
1
1
/4” (3.2 cm)
dia. hole
Black to Black
120 VAC Line In
Ground to grounding
screw
FILTER INSTALLATION
Number of mesh filters will vary by model. Only the 36"W. model has one spacer located between the mesh filters W
all Hoods - 30”W., 36”W., . - 2 filters per unit
42” W, 48”W. - 3 filters per unit
Island Hoods
- 36”W., 42”W. - 4 filters per unit 54”W. - 6 filters per unit
29
1/
2”
(74.9 cm)
Mesh Filters
Spacer
White to Blue
ABC
DEV1200 22” 17” 11 13/16”
(55.9 cm) (43.2 cm) (30.0 cm)
DEV1500 25” 20” 14 5/8”
(63.5 cm) (50.8 cm) (37.2 cm)
WIRING DIAGRAM
EXTERIOR VENTILATOR
14
EXTERIOR VENTILATOR DIMENSIONS
10” Dia.
20
3
/4” (52.7 cm)
24
1
/2
(62.2 cm)
4
3
/4
(12.1 cm)
14”
(35.6 cm)
24
3
/4
(62.9 cm)
15
1
/2
(39.4 cm)
28
1
/4
(71.8 cm)
DEV900
DEV1200 DEV1500
221/8
(56.2 cm)
BB
101/8
25.7 cm
AA
291/2
(74.9 cm)
10”
(25.4 cm)
Dia.
Opening for wiring
Flashing
Flashing
Opening for
wiring
3 1/2” (8.9 cm)
6 1/4”
(15.9 cm)
5” (12.7 cm)
3” (7.6 cm)
14 13/16” (37.6 cm)
11 13/16”
(30.0 cm)
AB
DEV1200 18” 22”
(45.7 cm) (55.9 cm)
DEV1500 21” 25”
(53.3 cm) (55.9 cm)
15
WALL HOOD DIMENSIONS 30”W. Classic Chimney, Classic Chimney w/Ledge, and classic chimney ledgeless
12”
(30.5 cm)
12”
(30.5 cm)
6”
(15.2 cm)
7 7/8”
(20.0 cm)
12”
(30.5 cm)
6 7/8”
(17.5 cm)
1” (2.5 cm)
12”
(30.5 cm)
1” (2.5 cm)
24” (61.0 cm)
25 1/2” (64.8 cm) Ledge model only
24” (61.0 cm)
25 1/2” (64.8 cm) Ledge model only
900 or 1200 CFM
External Ventilation Installation
300 or 440 CFM
Internal Ventilation Installation
10”
(25.4 cm)
14 15/16”
(37.9 cm)
10”
(25.4 cm)
14 15/16”
(37.9 cm)
6”
(15.2 cm)
6”
(15.2 cm)
1 1/2” (3.8 cm)
1 1/2” (3.8 cm)
1 1/2” (3.8 cm)
1 1/2” (3.8 cm)
120V Power Supply
Classic
Chimney
Classic Chimney w/Ledge
8” round for external vent ducting*
29 7/8” (75.9 cm)
32 7/8” (83.5 cm) Ledge model only
29 7/8” (75.9 cm)
32 7/8” (83.5 cm) Ledge model only
900 or 1200 CFM
External Ventilation Installation
300 or 440 CFM
Internal Ventilation Installation
*Must purchase 8” dia. to 10” dia. transition locally. Transition should be installed past the duct cover.
120V Power Supply
7” round for vent ducting
2”(5.1 cm)
2”(5.1 cm)
Classic Chimney Ledgeless
Classic Chimney Ledgeless
1 1/2”
(3.8 cm)
1 1/2”
(3.8 cm)
6”
(15.2 cm)
16
WALL HOOD DIMENSIONS 36”W./42”W. Classic Chimney, Classic Chimney w/Ledge, and Classic chimney ledgeless
990000 oorr 11220000 CCFFMM
EExxtteerrnnaall VVeennttiillaattiioonn IInnssttaallllaattiioonn
330000 oorr 660000 CCFFMM****
IInntteerrnnaall VVeennttiillaattiioonn IInnssttaallllaattiioonn
990000 oorr 11220000 CCFFMM
EExxtteerrnnaall VVeennttiillaattiioonn IInnssttaallllaattiioonn
330000 oorr 660000 CCFFMM****
IInntteerrnnaall VVeennttiillaattiioonn IInnssttaallllaattiioonn
12”
(30.5 cm)
9 7/8”
(25.1 cm)
6 7/8”
(17.5 cm)
12”
(30.5 cm)
14”
(35.6 cm)
14”
(35.6 cm)
24” (61.0 cm)
25 1/2” (64.8 cm) Ledge model only
24” (61.0 cm)
25 1/2” (64.8 cm) Ledge model only
1” (2.5 cm)
1” (2.5 cm)
2” (5.1 cm)
2” (5.1 cm)
Classic Chimney
Classic Chimney
Classic Chimney w/Ledge
Classic Chimney w/Ledge
6”
(15.2 cm)
6”
(15.2 cm)
A
B
A B
1 1/2” (3.8 cm)
1 1/2” (3.8 cm)
1 1/2” (3.8 cm)
C
1 1/2” (3.8 cm)
1 1/2” (3.8 cm)
C
12”
(38.0 cm)
12”
(38.0 cm)
120V Power Supply
120V Power Supply
36”W. 42”W.
A 35 7/8” 41 7/8”
(91.1 cm) (103.4 cm)
B* 38 7/8” 44 7/8”
(98.4 cm) (114.0 cm)
C 17 15/16” 20 15/16”
(45.6 cm) (53.2 cm)
7” (17.8 cm) round for vent ducting
*Ledge models only.
10” (25.4 cm) round for vent ducting
Classic Chimney Ledgeless
Classic Chimney Ledgeless
6”
(15.2 cm)
6”
(15.2 cm)
1 1/2” (3.8 cm)
****330000 CCFFMM vveennttiillaattoorr kkiittss ffoorr uussee wwiitthh 3366 WW.. hhooooddss oonnllyy..
17
island hood dimensions 36”w. and 42”w. classic chimney island hood
14”
(35.6 cm)
14”
(35.6 cm)
30” (76.2 cm)
30” (76.2 cm)
1” (2.5 cm)
2” (5.1 cm)
1” (2.5 cm)
2” (5.1 cm)
9 7/8”
(25.0 cm)
6 7/8”
(17.5 cm)
6” (15.2 cm)
6” (15.2 cm)
990000 oorr 11220000 CCFFMM
EExxtteerriioorr VVeennttiillaattiioonn IInnssttaallllaattiioonn
660000 CCFFMM
IInntteerriioorr VVeennttiillaattiioonn IInnssttaallllaattiioonn
990000 oorr 11220000 CCFFMM
EExxtteerriioorr VVeennttiillaattiioonn IInnssttaallllaattiioonn
660000 CCFFMM
IInntteerriioorr VVeennttiillaattiioonn IInnssttaallllaattiioonn
B
A
B
A
15”
(38.1 cm)
12”
(30.5 cm)
15”
(38.1 cm)
12”
(30.5 cm)
12”
(30.5 cm)
4 3/4” (12.1 cm)
4 3/4”(12.1 cm)
12”
(30.5 cm)
4 3/4” (12.1 cm)
4 3/4”(12.1 cm)
120 V Power Supply
120 V Power Supply
10” Round for Ventilation Duct
7” Round for Ventilation Duct
10” Round not used with DIV600
3366 WW.. MMooddeellss 4422 WW.. MMooddeellss AA 3355 77//88 ((9911..11 ccmm)) 4411 77//88 ((110066..44 ccmm)) BB 1177 1155//1166 ((4455..66 ccmm)) 2200 1155//1166 ((5533..22 ccmm))
18
island hood dimensions 54”w. classic chimney island hood
9 7/8”
(25.0 cm)
14”
(35.6 cm)
1” (2.5 cm)
2” (5.1 cm)
30” (76.2 cm)
11220000 CCFFMM IInntteerriioorr oorr EExxtteerriioorr
11550000 CCFFMM EExxtteerriioorr
VVeennttiillaattiioonn IInnssttaallllaattiioonn
11220000 CCFFMM IInntteerriioorr oorr EExxtteerriioorr
11550000 CCFFMM EExxtteerriioorr
VVeennttiillaattiioonn IInnssttaallllaattiioonn
120 V Power Supply
10” Round for Ventilation Duct
26 15/16”
(68.4 cm)
18”
(45.7 cm)
15”
(38.1 cm)
12”
(30.5 cm)
53 7/8” (136.8 cm)
6” (15.2 cm)
7”
(17.8 cm)
19
11220000 oorr 11550000 CCFFMM
EExxtteerrnnaall VVeennttiillaattiioonn IInnssttaallllaattiioonn
12”
(30.5 cm)
6”
(15.2 cm)
6”
(15.2 cm)
97/8”
(25.1 cm)
14”
(35.6 cm)
24” (61.0 cm)
25 1/2” (64.8 cm) Ledge model only
1” (2.5 cm)
WALL HOOD DIMENSIONS 48”W. Classic Chimney, Classic Chimney w/Ledge, and classic chimney ledgeless
11220000 CCFFMM
IInntteerrnnaall VVeennttiillaattiioonn IInnssttaallllaattiioonn
12”
(30.5 cm)
14”
(35.6 cm)
24” (61.0 cm)
25 1/2” (64.8 cm) Ledge model only
1” (2.5 cm)
2” (5.1 cm)
2”
(5.1 cm)
11220000 oorr 11550000 CCFFMM
EExxtteerrnnaall VVeennttiillaattiioonn IInnssttaallllaattiioonn
Classic Chimney
Classic Chimney w/Ledge
Classic Chimney
6”
(15.2 cm)
47 7/8” (121.6 cm)
50 7/8” (129.2 cm) Ledge model only
1 1/2” (3.8 cm)
1 1/2” (3.8 cm)
23 15/16”
(60.8 cm)
18”
(45.8 cm)
120V Power Supply
6”
(15.2 cm)
1 1/2” (3.8 cm)
1 1/2” (3.8 cm)
18”
(45.8 cm)
120V Power Supply
11220000 CCFFMM
IInntteerrnnaall VVeennttiillaattiioonn IInnssttaallllaattiioonn
47 7/8” (121.6 cm)
50 7/8” (129.2 cm) Ledge model only
23 15/16”
(60.8 cm)
10” (25.4 cm) round
Vent Duct
10” (25.4 cm) round
Vent Duct
Classic Chimney Ledgeless
Classic Chimney Ledgeless
9 7/8”
(25.1 cm)
1 1/2” (3.8 cm)
1 1/2” (3.8 cm)
Classic Chimney w/Ledge
WIRING DIAGRAM
BUILT-IN CHIMNEY HOODS
REFER ONLY TO FEATURES EQUIPPED WITH THIS UNIT.
VIKING RANGE CORPORATION
111 Front Street • Greenwood, Mississippi 38930 USA • (662) 455-1200
Specifications subject to change without notice.
For more product information, call 1-888-VIKING1 (845-4641), or visit our web site at http://www.vikingrange.com
F20042L
(PS1104VR)
Loading...