Viking VIPR102R Installation Manual

VIKING RANGE, LLC Downdraft Ventilators
!
!
!
MODEL WIDTH BLOWER (purchase separately)
VIPR102 30" VIDV500 Interior or VEDV900 Exterior VIPR102R 30" w/ remote control VIDV500 Interior or VEDV900 Exterior VIPR162 36" VIDV500 Interior or VEDV900 Exterior VIPR162R 36" w/ remote control VIDV500 Interior or VEDV900 Exterior VIPR182 48" VIDV500 Interior, VEDV900 Exterior or VEDV1200 Exterior VIPR182R 48" w/ remote control VIDV500 Interior, VEDV900 Exterior or VEDV1200 Exterior
WARNING - RANGETOPS ONLY: To reduce the risk of burns or ignition of clothing by reaching across burners, an "R" model
downdraft (with remote control) MUST be used with a rangetop. The remote control MUST be mounted in the countertop - at least 4" from the burners. See "INSTALL COOKTOP" section on page 8.
READ AND SAVE THESE INSTRUCTIONS
INTENDED FOR DOMESTIC COOKING ONLY
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number in the warranty.
2. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a qualifi ed person(s) in accordance with all applicable codes and standards, including fi re-rated construction codes and standards.
4. Suffi cient air is needed for proper combustion and exhausting of gases through the fl ue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. To reduce the risk of fi re, use only metal ductwork.
8. Do not install this product with the activating switch directly behind a burner or element. Minimum distance between the switch and the edge of the burner should be 4 inches.
9. Loose-fi tting or hanging clothing should never be worn when operating this appliance. They may be ignited by burners/ elements on cooktop.
10. Children should not be left alone or unattended in the area where this appliance is in use.
11. This unit must be grounded.
TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:
a) Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.
b) Always turn hood ON when cooking at high heat or when
cooking fl aming foods.
c) Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or fi lter.
d) Use proper pan size. Always use cookware appropriate
for the size of the surface element.
WARNING
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING
1. SMOTHER FLAMES with a close-fi tting lid, cookie sheet, or metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. If the fl ames do not go out immedi ately, EVACUATE AND CALL THE FIRE DEPARTMENT.
2.
3. DO NOT USE WATER, including wet dishcloths or towels
- a violent steam explosion will result.
4. Use an extinguisher ONLY if:
A. You know you have a Class ABC extinguisher, and you
already know how to operate it.
B. The fi re is small and contained in the area where it
started.
C. The fi re department is being called. D. You can fi ght the fi re with your back to an exit.
a
Based on “Kitchen Firesafety Tips” published by NFPA.
a
:
NEVER PICK UP A FLAMING PAN - You may be burned.
CAUTION
1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
3. Clean fi lters and grease-laden surfaces frequently.
4. Do not repair or replace any part of this appliance unless specifi cally recommended in this manual. All other servicing should be done by a qualifi ed technician.
5. Please read specification label on product for further information and requirements.
6. DO NOT INSTALL WITH GRILL MODEL RANGETOPS. This will void the warranty.
7. Models VIPR102SS, VIPR162SS, and VIPR182SS (non- remote units): DO NOT INSTALL WITH RANGETOPS. This will void the warranty.
INSTALLER:
Save this manual for Electrical Inspector and
Homeowner to use.
HOMEOWNER:
1
Use and Care Information on Page 11.
Downdraft VentilatorsVIKING RANGE, LLC
PLANNING
Interior Blower Installation Exterior Blower Installation
This downdraft blower system is designed to be used to exhaust airborne contaminants when cooking with a variety of gas or electric cooktops. It can be mounted in island, peninsula, or conventional wall locations.
This unit can be easily installed following these basic steps:
• Cut out the countertop opening.
• Mount the unit in the cabinet.
Install the Model VIDV500
Interior Blower
Connect the ductwork and
• electrical.
Install the cooktop.
Note: the high level of air fl ow of this appliance may effect the gas fl ame on some types of gas cooktops. This is NORMAL and will cause no harm, but can be corrected by lowering the speed of the blower.
TYPICAL INSTALLATION
COUNTER TOP
BLOWER
COOK TOP
GEAR MOTOR COVER
BOX
CHIMNEY TOP
3-1/4" X 10" DUCT CONNECTOR
ELECTRICAL
SPECIFICATIONS
120 VAC • 60 Hz • 4.0 A
AIR VENT
120 VAC GROUNDED OUTLET
This downdraft blower system is designed to be used to ex­haust airborne contaminants when cooking with a variety
TYPICAL INSTALLATION
COUNTER TOP
COOK TOP
CHIMNEY TOP
of gas or electric cooktops. It can be mounted in island, peninsula, or conventional wall locations.
This unit can be easily installed following these basic steps:
• Cut out the countertop opening.
Mount the unit in the
GEARMOTOR COVER
10" ROUND DISCHARGE PLATE
AIR VENT
120 VAC GROUNDED OUTLET
cabinet.
Install 10" round dis-
• charge plate
10" ROUND DUCTWORK
• Install Model VEDV900 or VEDV1200 (48" Model ONLY) External Blower
• Connect the ductwork and electrical.
Install the cooktop.
ELECTRICAL
SPECIFICATIONS
120 VAC • 60 Hz • 6.0 A
(max.)
Note: the high level of air fl ow of this appliance may effect the
gas fl ame on some types of gas cooktops. This is NORMAL and will cause no harm, but can be corrected by lowering the speed of the blower.
TAKE MEASUREMENTS
All Units
1. Refer to the cooktop installation instructions for dimensions of cooktop, countertop cut-out, and cabinet requirements. The Models VIPR102SS and VIPR102RSS will fi t in most 30" wide cabinets the Models VIPR162SS and VIPR162RSS will fi t in most 36" wide cabinets and the Models VIPR182SS and VIPR182RSS will fi t most 48" wide cabinets. However, it is recommended that oversized cabinets be used for easier installation.
2. Cooktop depth can vary greatly from one to another. This may cause the fi t of these two appliances to be rather tight.
Pay special attention to the areas of potential interference highlighted above. A countertop with (A) a raised lip and/or (B) a backsplash may not allow enough fl at countertop for a proper installation. Note that 2" of fl at countertop is required behind cooktop and that 1-3/4" is necessary between the back edge of the cooktop and the inside of cabinet back.
2
VIKING RANGE, LLC Downdraft Ventilators
29
"
5
16
2
"
1 8
VIDV500
INTERNAL
BLOWER
5"
2"
1"
3
"
1 4
3
"
5 8
1 4
7
"
11 16
18"
FROM
COUNTERTOP
TO BOTTOM OF AIR BOX
"
29
"
5
16
2
"
1 8
2"
1"
3
"
1 4
3
"
5
8
1 4
7
"
11 16
FROM
COUNTERTOP
TO BOTTOM OF AIR BOX
"
3
"
3
16
1 4
"
13
1 4
"
13
1
"
9
16
10" ROUND
ELBOW
TAKE MEASUREMENTS (CONTINUED)
Interior Blower Installation Exterior Blower Installation
SIDE VIEW
OF DOWNDRAFT
WITH
VIDV500
INTERIOR
BLOWER
SIDE VIEW
OF DOWNDRAFT
WITH
10" ROUND ELBOW
(for connection to VEDV900 or
VEDV1200 Exterior
VIDV500
INTERIOR
BLOWER
Blower)
PLAN THE DUCTWORK
Interior Blower Installation Exterior Blower Installation
1. The interior down­draft blower system is designed for use with 3-1/4" x 10" duct­work (can be transi­tioned to 6" round). Three different dis­charge directions are available with side-to­side adjustment for accurate alignment of ductwork.
2. For best perfor­mance: Choose the ducting option which allows the shortest length of ductwork and a minimum number of elbows and transitions. Check location of fl oor joists, wall studs, electrical wiring or plumbing for possible interference.
6" ROUND
ELBOW
3-1/4" X 10" TO 6" RD. TRANSITION
LEFT
DISCHARGE
RIGHT
DISCHARGE
DOWN DISCHARGE
3-1/4" X 10"
90O ELBOW
1. The exterior downdraft blower system is designed for use with 10" round ductwork.
2. For best performance: Plan ducting which has the shortest length of ductwork and a minimum number of elbows. Check location of fl oor joists, wall studs, elec­trical wiring or plumbing for possible interference.
10" ROUND
ELBOW
10" ROUND DISCHARGE
PLATE
EQUALS 6 FT. OF
STRAIGHT DUCT
3. The system will operate most effi ciently when the ductwork
EQUALS 6 FT. OF
3. The system will operate most effi ciently when the ductwork
NOTE: The equivalent feet of various roof and wall caps has been taken into consideration. Do not include them in this calculation.
STRAIGHT DUCT
does not exceed 40 feet of equivalent duct. The chart, above, shows equivalent feet of elbows and transitions. The number of feet of straight duct plus the equivalent feet of transitions and/or elbows to be used should equal 40 feet or less.
EQUALS 2 FT. OF STRAIGHT DUCT
EQUALS 8 FT. OF
STRAIGHT DUCT
3
does not exceed 40 feet of equivalent duct. The illustration, above, shows equivalent feet of a 10" round elbow. The number of feet of straight duct plus the equivalent feet of elbows to be used should equal 40 feet or less.
NOTE: The equivalent feet of various roof and wall caps has been taken into consideration. Do not include them in this calculation.
Downdraft VentilatorsVIKING RANGE, LLC
CENTER LINE OF COUNTER
CUTOUT
CENTER LINE
OF DUCT CUTOUT
1" to 8"
5½"
10¼" x 3½"
CUTOUT
(TYP.)
CENTER LINE OF COUNTER
CUTOUT
CENTER
LINES OF
DUCT
CUTOUT
16
3
/
8
"
5½"
10¼" x 3½"
CUTOUT
(TYP.)
CENTER LINE OF COUNTER
CUTOUT
CENTER LINES
OF DUCT
CUTOUT
19¾"
10" ROUND
CUTOUT
(TYP.)
10¼"
CENTER LINE OF COUNTER
CUTOUT
CENTER
LINE
OF DUCT
CUTOUT
2¾"
10¼"
10" ROUND
DIA. CUTOUT
(TYP.)
3½"
6¼"
CENTER LINE OF DUCT CUTOUT (can be located within this area)
CENTER LINE OF COUNTER
CUTOUT
19¾"
10¼"
10" ROUND
CUTOUT
(TYP.)
CENTER
LINES OF
DUCT
CUTOUT
CENTER LINE OF COUNTER
CUTOUT
CENTER
LINES OF
DUCT CUTOUT
24
1
/
8
"
10¼" x 3½"
CUTOUT
(TYP.)
5½"
!
PLAN THE CABINET CUTOUTS
Interior Blower Installation Exterior Blower Installation
LEFT SIDE
DISCHARGE
RIGHT SIDE
DISCHARGE
LEFT SIDE
DISCHARGE
CAUTION: BEFORE CUTTING HOLE IN CABINET FOR DUCTWORK,
check for interference with fl oor
joists, wall studs, electrical
wiring, or plumbing.
RIGHT SIDE
DISCHARGE
BOTTOM
DISCHARGE
BOTTOM
DISCHARGE
4
VIKING RANGE, LLC Downdraft Ventilators
PLAN THE WIRING
Interior Blower Installation Exterior Blower Installation
1. The Interior Downdraft Blower system draws 4 AMPS and requires a 120 VAC, 60 Hz circuit.
2. The downdraft has a 2 ft. long power cord with a 3-pronged plug. Plan to provide a grounded outlet in a location which will allow the unit’s power cord to reach.
IMPORTANT - LOCATION OF ELECTRICAL OUTLET: If Models VIPR102SS or VIPR102RSS are being installed
in a 30" wide cabinet...
or Models VIPR162SS or VIPR162RSS are being
installed in a 36" wide cabinet...
or Models VIPR182SS or VIPR182RSS are being
installed in a 48" wide cabinet...
...the outlet cannot be located on the back wall of
cabinet.
In these cases, the width of the downdraft covers nearly
the entire width of the back wall of the cabinet. So you must either:
• mount the electrical box to a side wall or cabinet fl oor
- at least 12 inches from the back wall.
• mount the electrical box to a wall stud behind the cabinet - where it will not be covered by the downdraft. Then provide a clearance hole in the back wall of the cabinet.
PREPARE THE DOWNDRAFT
1. The Exterior Downdraft Blower system draws 6 AMPS and requires a 120 VAC, 60 Hz circuit.
2. The downdraft has a 2 ft. long power cord with a 3-pronged plug. Plan to provide a grounded outlet in a location which will allow the unit’s power cord to reach.
IMPORTANT - LOCATION OF ELECTRICAL OUTLET: If Models VIPR102SS or VIPR102RSS are being installed
in a 30" wide cabinet...
or Models VIPR162SS or VIPR162RSS are being
installed in a 36" wide cabinet...
or Models VIPR182SS or VIPR182RSS are being
installed in a 48" wide cabinet...
...the outlet cannot be located on the back wall of
cabinet.
In these cases, the width of the downdraft covers nearly
the entire width of the back wall of the cabinet. So you must either:
• mount the electrical box to a side wall or cabinet fl oor
- at least 12 inches from the back wall.
• mount the electrical box to a wall stud behind the cabinet - where it will not be covered by the downdraft. Then provide a clearance hole in the back wall of the cabinet.
PLEASE NOTE: External blowers must be hard-wired using locally-supplied wire and connected to the downdraft plug (included).
Interior Blower Installation
The downdraft is shipped without a blower. Purchase a Model VIDV500 Interior Blower and mount it to the downdraft as follows:
1. Place the downdraft on its back on a table of fl at work surface.
2. Remove the 4 nuts and 2 clamp channels.
3. Remove 2 screws and the gear motor cover.
4. Carefully position the blower under the bottom fl ange of the downdraft with the 3¼" x 10" discharge pointed in the desired direction.
5. Connect motor plug.
6. Replace the gear motor cover and 2 sheet metal screws.
7. Replace the 2 clamp channels and start the 4 nuts, do not tighten.
8. Slide blower left of right to desired position. Use cover plate (supplied) to close up any open space.
9. Tighten 4 nuts to secure top of blower. Use additional screws (supplied) through bottom fl ange to secure bottom in blower.
CLAMP
CHANNELS
SCREWS
GEARMOTOR
COVER
5
NUTS
BLOWER
MOTOR
PLUG
BOTTOM
FLANGE
3¼" X 10"
DISCHARGE
COVER
PLATE
ADDITIONAL
SCREWS
PREPARE THE DOWNDRAFT
Exterior Blower Installation
The downdraft is shipped without a blower. Purchase a Model VEDV900 or VEDV1200 Exterior Blower and mount the 10" discharge plate to the downdraft as follows:
1.
Place the downdraft on its back on a table of fl at work surface.
2. Remove the 4 nuts and 2 clamp channels.
3. Remove 2 screws and the gear motor cover.
4. Carefully position the10" discharge plate under the bottom fl ange of the downdraft.
5. Connect motor plug.
6. Replace the gear motor cover and 2 sheet metal screws.
7. Replace the 2 clamp channels and start the 4 nuts, do not tighten.
8. Slide blower left of right to desired position. Use cover plate (supplied) to close up any open space.
9. Tighten 4 nuts to secure top of blower. Use additional screws (supplied) through bottom fl ange to secure bottom of dis­charge plate.
CLAMP
CHANNELS
SCREWS
GEARMOTOR
COVER
NUTS
Downdraft VentilatorsVIKING RANGE, LLC
MOTOR
PLUG
10" ROUND DISCHARGE
PLATE
COVER
PLATE
ADDITIONAL
SCREWS
BOTTOM
FLANGE
6
CUT COUNTERTOP OPENING
Downdraft VentilatorsVIKING RANGE, LLC
All Units
Cooktop Width & Model 30" VECU 36" VECU VGSU102 VGSU162 30" VGRT * 36" VGRT * 48" VGRT *
For use with Downdraft Models
VIPR102RSS VIPR162RSS VIPR102RSS VIPR162RSS
Cutout Dimensions A 28-3/4" 34-3/4" 28-1/16" 34-1/4" 30" 36" 48" B 20-1/4" 20-1/4" 18-3/4" 18-3/4" 24" 24" 24" C 27" 33" 27" 33" 27" 33" 45" D 2-1/4" 2-1/4" 3" 3" 2-3/4" 2-3/4" 2-3/4" E 7/8" 7/8" --- --- 1-1/2" 1-1/2" 1-1/2" F 7/8" 7/8" 1-1/16" 1-1/4" 1-1/2" 1-1/2" 1-1/2"
VIPR102SS VIPR162SS VIPR102SS VIPR162SS VIPR102RSS VIPR162RSS VIPR182RSS
1. Measure and cut the countertop opening for your width of cooktop and downdraft.
* Must use island trim. Rear countertop trim (supplied with island trim) will be used in this installation.
E
C
Cutout for:
VECU Cooktops &
VGRT Rangetops
F
B
C
D
Cutout for:
VGSU102 & VGSU162
Cooktops
F
D
B
A
Cooktop Width & Model 30" VEC 36" VEC 30" VGC 36" VGC
For use with Downdraft Models
VIPR102RSS VIPR162RSS VIPR102RSS VIPR162RSS
Cutout Dimensions A 28-7/8" 34-7/8" 27-3/4" 33-3/4" B 19-1/4" 19-1/4" 18-3/4" 18-3/4" C 27" 33" 27" 33" D 2-11/16" 2-11/16" 2-15/16" 2-15/16"" E 15/16" 15/16" 3/8" 3/8" F 15/16" 15/16" 3/8" 3/8""
E
VIPR102SS VIPR162SS VIPR102SS VIPR162SS
F
E
C
D
Cutout for:
VEC Cooktops
B
A
C
Cutout for:
VGC Cooktops
F
D
B
A
7
A
VIKING RANGE, LLC Downdraft Ventilators
!
MOUNT THE UNIT
MOUNTING SCREWS
All Units
LEVELING BRACKET -
FLANGE FACING OUT
1. Set downdraft into opening. Extend leveling brackets to fl oor
of cabinet so downdraft sits straight. (Note: Leveling brackets can be removed and re-attached in other positions. Bottom fl ange may have to face inward in tight cabinet installations.)
2. Secure the downdraft to the countertop as follows: Hold the downdraft against the back of countertop cut-out and tightening the two mounting screws (one on each end of unit) on underside of countertop. Use a wood shim between screw and underside of granite countertops.
3. Screw leveling brackets to bottom of cabinet. Tighten screws holding leveling bracket to unit on each side.
LEVELING BRACKET -
FLANGE FACING IN
INSTALL DUCTWORK
Interior Blower Installation Exterior Blower Installation
BEFORE CUTTING HOLE IN CABINET FOR DUCTWORK,
check for interference with fl oor
joists, wall studs, electrical
BLOWER
3-1/4" X 10"
COLLAR
SCREWS
1.
Cut hole in cabinet as well as holes in wall or fl oor as necessary.
2. Mount the roof or wall cap and work back towards the cabinet, attaching all ductwork, elbows and transitions as previously planned. Tape all ductwork connections to make them secure and air tight.
3. Connect ductwork (and transition, if required) to downdraft. If necessary, LOOSEN nuts and screws that hold the blower in place, and slide blower left or right to meet ductwork. Re-tighten screws and nuts.
Note: A 3-1/4" x 10" collar is provided for installers who prefer to rivet the ductwork to the unit. This will allow blower to be removed and replaced easily in service situations without disturbing ductwork.
TO 6" RD.
TRANSITION
6" RD. ELBOW & DUCTWORK
CAUTION:
wiring, or plumbing.
ELBOW
1.
Cut hole in cabinet as well as holes in wall or fl oor as necessary.
2. Mount the exterior blower and work back towards the cabinet,
attaching all ductwork, elbows and transitions as previously planned. Tape all ductwork connections to make them secure and air tight.
3. Connect ductwork to downdraft. If necessary, LOOSEN nuts and screws that hold remote blower adapter plate in place, and slide outlet assembly left or right to meet ductwork. Re-tighten screws and nuts.
10" ROUND DUCT
ELBOW
8
VIKING RANGE, LLC Downdraft Ventilators
INSTALLATION OF REMOTE CONTROL SWITCH
WARNING: To reduce the risk of burns or ignition of clothing by reaching across burners, the remote control must be mounted at least 4" away from any cook top burner.
Keep in mind you do not want to place the control where it will be in the way for cooking, or where hot pans could be set, or hot liquids spilled on the control.
1. Using the template below, lay out the 3-hole pattern on the counter top. Mark the centers of the three holes to be drilled.
2. Carefully drill the three holes through the counter top. Be careful not to damage or chip the counter top surface when drilling the holes.
3. Remove the control from the plastic bag. Remove the paper from the adhesive back of the control, line the control up with the three holes and position the control so it is parallel with the front of the counter top. Press down fi rmly for 60 seconds.
4. Remove the two nylon thumbnuts from the plastic bag and thread onto the two studs on the control from below the counter top. Hand tighten only. The thumbnuts just need to be snugged by hand. They are there to hold the control in place until the adhesive sets up.
5. Remove cable from the plastic bag and plug into back of control from below counter top. Route cable through cabinet to lower right hand corner of downdraft. Plug other end of cable into the downdraft unit. (Receptacle hole for cabinet is on the lower right hand side of the downdraft.)
6. Stuff excess cable out of the way and secure the cable so it is not damaged from items stored in the cabinet.
1/4" DIA.
HOLE
TOP EDGE
1/4" DIA.
HOLE
1" DIA.
HOLE
CUT OUT ON DOTTED LINE
9
This page has been left
blank intentionally.
Downdraft VentilatorsVIKING RANGE, LLC
BACKSIDE OF
REMOTE SWITCH
TEMPLATE
10
INSTALL ELECTRICAL WIRING
!
!
FIL
TER
R
ES
ET
1234
UP/DOWN
TO
1
2
3
4
FILTER
UP
DOWN
MIN.
Downdraft VentilatorsVIKING RANGE, LLC
Interior Blower Installation
CAUTION: All electrical wiring should be done by a qualifi ed person(s) in accordance with all applicable codes and standards.
1. Mount a standard wiring box, with 3-pronged receptacle, inside the cabinet. Make sure the downdraft's power cord can easily reach it.
2. Run appropriate power cable into cabinet and connect it to receptacle.
3. Plug the downdraft's power cord into the outlet. Make sure that the power cord is routed away from the heat generated by the cooktop.
INSTALL COOKTOP
All Units
1. Align the cooktop with the downdraft and fasten cooktop in place.
Note: Accurate alignment of cooktop and downdraft is neces­sary to ensure that there is no interference when air vent is raised and lowered. There should be a gap of 1/32" - 1/16" between the back of the cooktop and the front of the downdraft cover.
Exterior Blower Installation
CAUTION: All electrical wiring should be done by a qualifi ed person(s) in accordance with all applicable codes and standards.
1. Mount a standard wiring box, with 3-pronged grounded recepta­cle, inside the kitchen cabinet. Make sure the downdraft's power cord can easily reach it.
2. Run appropriate power cabinet into cabinet and connect it to electrical box and receptacle.
3. Exterior blower may not exceed 6.0 Amp rating.
4. Run 2-wire plus ground power cable from the remote blower to wiring box on 10" round discharge plate.
5. Connect downdraft wiring to power cable from remote blower. Wire black to black, white to white, and green to green or bare wire.
6. Replace wiring box cover.
7. Plug the downdraft's power cord into outlet. Make sure that the power cord is routed away from the heat generated by the cooktop.
"R" MODEL
DOWNDRAFT
REMOTE
CONTROL
RANGETOP
Note: Rangetops and Designer Cooktops must be used with an "R"
model downdraft (with remote control) - mounted into the countertop, at least 4" from the burners.
11
COUNTERTOP
VIKING RANGE, LLC Downdraft Ventilators
1
2
3
4
FILTER
RESET
UP/DOWN
OPERATION
UP / DOWN --- Raises and lowers
Turns blower ON
Note: The UP/DOWN switch for models VIPR102SS, VIPR162SS, and VIPR182SS is on the right hand end of the top cover.
DELAY ------------ Allows blower to run for 10 min. after button is
BLOWER SPEEDS --------Blower operates at 4 different speed
FILTER LIGHT ---------------Comes ON after 30 hours of opera-
vent.
when vent is UP and OFF when vent is DOWN.
pressed. Delay is activated by holding down any speed control button until the LED indicator fl ashes. Blower will run for 10 min. - then shut OFF. VENT WILL NOT LOWER. You must press UP / DOWN to lower vent. When DELAY is activated, the speed level light will blink.
levels. Press button ONCE to turn blower ON to desired speed. Press button AGAIN to turn blower OFF.
tion to remind you to clean fi lters. Press button to reset.
All Units
USE AND CARE
Always turn the downdraft blower on before you begin cooking to es­tablish an air fl ow in the kitchen. Let the blower run for a few minutes to clean the air after you turn the cooktop off. This will keep the whole kitchen cleaner and brighter. The activating switch is pressed and the air vent rises.
WARNING: Always disconnect electric power supply before cleaning and/or servicing unit.
Cleaning
Use a mild detergent suitable for painted surfaces. DO NOT USE ABRASIVE CLOTH, STEEL WOOL PADS, OR SCOURING POW­DERS. Vacuum blower to clean. Do not immerse blower in water.
All Units
REMOTE CONTROL
FOR MODELS
VIPR102RSS VIPR162RSS VIPR182RSS
TOP COVER CONTROL FOR MODELS VIPR102SS VIPR162SS VIPR182SS
Wash the 2 aluminum/stainless steel grease fi lters in a mild de­tergent solution or a dishwasher. Remove them from the air vent by grasping the tab at the top of each fi lter.
Servicing
It may be necessary to remove the downdraft blower system from the cabinet in order to service components such as the blower motor or air vent mechanism.
Disconnect power to the cooktop and remove it fi rst. Reverse the steps under “MOUNT THE UNIT” to remove the downdraft from the cabinet.
12
Loading...
+ 28 hidden pages