Viking 823 User Manual

Page 1
TECHNICAL SERVICE MANUAL
MAGNETIC DRIVE PUMPS
SERIES 823 - STEEL
825 - CAST IRON
827 - STAINLESS STEEL
SIZES LQ, LS, Q & QS
SECTION TSM 845.1
PAGE 1 OF 13
CONTENTS
Introduction . . . . . . . . . . . . . . . . . . . . . . . 1
Special Information . . . . . . . . . . . . . . . . . . . 3
Pressure Relief Valves . . . . . . . . . . . . . . . . . 3
Maintenance . . . . . . . . . . . . . . . . . . . . . . 3
Disassembly: Pump. . . . . . . . . . . . . . . . . . . 6
Pump Rotation . . . . . . . . . . . . . . . . . . . . . 7
Port Arrangement . . . . . . . . . . . . . . . . . . . . 7
Disassembly: MD-D Series Coupling . . . . . . . . . . 7
Bearing Housing . . . . . . . . . . . . . . . . . . . . 9
Disassembly of Bearing Housing
Assembly of Bearing Housing . . . . . . . . . . . .
Installation of Bushings . . . . . . . . . . . . . . . . . 9
Pump Assembly. . . . . . . . . . . . . . . . . . . . .10
Adjusting Head Gasket End Clearance . . . . . . . . 11
Assembly: D Series Coupling . . . . . . . . . . . . . 11
Troubleshooting. . . . . . . . . . . . . . . . . . . . 12
Pressure Relief Valves . . . . . . . . . . . . . . . . 12
Pressure Adjustment
Disassembly: Relief Valve. . . . . . . . . . . . .
Assembly: Relief Valve
. . . . . . . . . . . . . . . 12
. . . . . . . . . . . . . . 13
WARNING !
Persons with surgical implants of a metallic or electronic nature should avoid working on pump – especially the inner magnet assembly.
. . . . . . . . . . 9
INTRODUCTION
The illustrations used in this manual are for identification purposes only and should not be used for ordering parts. Secure a parts list from the factory or a Viking® representative. Always give the complete name of the part, model and serial number of the pump when ordering repair parts. The pump model and serial number can be found on the nameplate secured to the pump.
In the Viking model number system, the basic size letters are combined with series number (825, 823, or 827) indicating basic pump construction material (cast iron, steel or stainless
9
steel).
MODEL NUMBER CHART
UNMOUNTED PUMP UNITS
LQ-825, 823, 827
13
LS-825, 823, 827
Q-825, 823, 827
QS-825, 823, 827
This manual deals only with Series 825, 823 and 827 magnetic drive pumps and couplings. Refer to Figures 1 through 21 for general configurations and nomenclature used in this manual. Pump specifications and recommendations are listed in Catalog Section 845.
Units are designated by the un­mounted pump model numbers followed by the magnetic coupling size and a letter indicating drive style:
B – Bracket Mount R – Viking Reducer Drive P = Commercial Reducer Drive (Example: LS-827 MD-D140 R)
FIGURE 1
LS-825 MD-D290 R
Complete Unit on Base with Viking “C” Reducer
VIKING PUMP, INC. A Unit of IDEX Corporation Cedar Falls, IA 50613 USA
FIGURE 2
QS-825 MD-D450 B
Bearing Carrier, Footed Pump and Coupling Bracket
Jacketed Pump Bracket
Page 2
SAFETY INFORMATION AND INSTRUCTIONS
IMPROPER INSTALLATION, OPERATION OR MAINTENANCE OF PUMP MAY CAUSE SERIOUS INJURY OR DEATH AND/OR RESULT IN DAMAGE TO PUMP AND/OR OTHER EQUIPMENT. VIKING’S WARRANTY DOES NOT COVER FAILURE DUE TO IMPROPER INSTALLATION, OPERATION OR MAINTENANCE.
THIS INFORMATION MUST BE FULLY READ BEFORE BEGINNING INSTALLATION, OPERATION OR MAINTENANCE OF PUMP AND MUST BE KEPT WITH PUMP. PUMP MUST BE INSTALLED, OPERATED AND MAINTAINED ONLY BY SUITABLY TRAINED AND QUALIFIED PERSONS.
THE FOLLOWING SAFETY INSTRUCTIONS MUST BE FOLLOWED AND ADHERED TO AT ALL TIMES.
Symbol Legend :
!
!
!
!
!
WARNING
!
WARNING
Danger - Failure to follow the indicated
instruction may result in serious injury
!
or death.
BEFORE opening any liquid chamber (pumping chamber, reservoir, relief valve adjusting cap fitting, etc.) be sure that :
● Any pressure in the chamber has been completely vented through the suction or discharge lines or other appropriate openings or connections.
● The pump drive system means (motor, turbine, engine, etc.) has been “locked out” or otherwise been made non-operational so that it cannot be started while work is being done on the pump.
● You know what material the pump has been handling, have obtained a material safety data sheet (MSDS) for the material, and understand and follow all precautions appropriate for the safe handling of the material.
BEFORE
are in place.
DO NOT operate pump if the suction or discharge piping is not connected.
DO NOT place fingers into the pumping chamber or its connection ports or into any part of the drive train if there is any possibility of the pump shafts being rotated.
DO NOT exceed the pumps rated pressure, speed, and temperature, or change the system/duty parameters from those the pump was originally supplied, without confirming its suitability for the new service.
BEFORE
● It is clean and free from debris
● all valves in the suction and discharge pipelines
are fully opened.
● All piping connected to the pump is fully supported
and correctly aligned with the pump.
● Pump rotation is correct for the desired direction
of flow.
operating the pump, be sure all drive guards
operating the pump, be sure that:
WARNING
WARNING
!
WARNING
!
!
!
WARNING
!
WARNING
Warning - In addition to possible serious
injury or death, failure to follow the indicated instruction may cause damage to pump and/or other equipment.
INSTALL pressure gauges/sensors next to the pump suction and discharge connections to monitor pressures.
USE extreme caution when lifting the pump. Suitable lifting devices should be used when appropriate. Lifting eyes installed on the pump must be used only to lift the pump, not the pump with drive and/or base plate. If the pump is mounted on a base plate, the base plate must be used for all lifting purposes. If slings are used for lifting, they must be safely and securely attached. For weight of the pump alone (which does not include the drive and/or base plate) refer to the Viking Pump product catalog.
DO NOT attempt to dismantle a pressure relief valve that has not had the spring pressure relieved or is mounted on a pump that is operating.
AVOID contact with hot areas of the pump and/or drive. Certain operating conditions, temperature control devices (jackets, heat-tracing, etc.), improper installation, improper operation, and improper maintenance can all cause high temperatures on the pump and/or drive.
THE PUMP must be provided with pressure protection. This may be provided through a relief valve mounted directly on the pump, an in-line pressure relief valve, a torque limiting device, or a rupture disk. If pump rotation may be reversed during operation, pressure protection must be provided on both sides of pump. Relief valve adjusting screw caps must always point towards suction side of the pump. If pump rotation is reversed, position of the relief valve must be changed. Pressure relief valves cannot be used to control pump flow or regulate discharge pressure. For additional information, refer to Viking Pump’s Technical Service Manual TSM 000 and Engineering Service Bulletin ESB-31.
THE PUMP must be installed in a matter that allows safe access for routine maintenance and for inspection during operation to check for leakage and monitor pump operation.
SECTION TSM 845.1 ISSUE C PAGE 2 OF 13
Page 3
SPECIAL INFORMATION
DANGER !
Before opening any Viking pump liquid chamber (pumping chamber, reservoir, relief valve adjusting cap fitting etc.) Be sure:
1. That any pressure in the chamber has been completely vented through the suction or discharge lines or other appropriate openings or connections.
2. That the driving means (motor, turbine, engine, etc.) has been “locked out” or made non-operational so that it cannot be started while work is being done on pump.
3. That you know what liquid the pump has been handling and the precautions necessary to safely handle the liquid. Obtain a material safety data sheet (MSDS) for the liquid to be sure these precautions are understood.
Failure to follow above listed precautionary measures may result in serious injury or death.
DISCHARGE
SUCTION
RELIEF VALVE ADJUSTING SCREW CAP
FIGURE 3
For additional information on pressure relief valves, refer to Technical Service Manual TSM000 and Engineering Service Bulletin ESB-31.
MAINTENANCE
ROTATION: Viking Mag Drive® pumps are directional. Shaft rotation determines which port is suction and which is discharge. The port located where pumping elements (gear teeth) come out of mesh is the suction port. Do not attempt to operate the pump in the opposite direction. See PUMP
ROTATION on page 7.
PRESSURE RELIEF VALVES:
1. Viking pumps are positive displacement pumps and must
be provided with some sort of pressure protection. This may be a relief valve mounted directly on the pump, an inline pressure relief valve, a torque limiting device or a rupture disk. Do not rely on decoupling of magnets for protection from over pressure; this may result in damage to the magnets, pump, or other equipment.
2. If pump rotation is to be reversed during operation, pressure protection must be provided on both sides of the pump.
3. The relief valve adjusting screw cap must always point towards the suction side of the pump. Refer to Figure 3. If the pump rotation is reversed, remove the pressure relief valve and turn end for end (see PUMP ROTATION on page 7 first for additional steps required for proper operation.)
CAUTION !
Rare earth magnets used in these couplings have extremely strong magnetic fields capable of changing the performance or damaging items such as the following:
Pacemakers Metal Implants Watches Computers & discs Credit Cards
Completely assembled magnetic couplings will not affect items listed above.
Altered performance or damage can occur only when the coupling halves are separated.
There are no known harmful effects of these magnetic fields on the human body.
4. Pressure relief valves cannot be used to control pump
flow or regulate discharge pressure.
SECTION TSM 845.1 ISSUE C PAGE 3 OF 13
Page 4
TEMPERATURE
MONITOR
(OPTIONAL)
BRACKET BUSHINGS
BALANCE PLATE
CASING
HEAD GASKETS
OUTER
MAGNET
ASSEMBLY
BEARING CARRIER
ASSEMBLY
COUPLING
BRACKET
CANISTER
INNER MAGNET ASSEMBLY
FIGURE 4
CUTAWAY VIEW MAG DRIVE PUMP, MODEL LS-825 MD-D B ILLUSTRATED
Series 825, 823, 827 pumps are designed for long, trouble-free service life under a wide variety of application conditions with a minimum of maintenance. The points listed below will help provide long service life.
CLEANING UNIT: Keep the pump, coupling and motor as clean as possible. This will facilitate inspection, adjustment, and repair work.
STORAGE: If the pump or coupling are to be stored, drain the pump and pour non-detergent SAE 30 weight oil into the pump port. Apply grease to the pump or the coupling shaft extension, if present or accessible. Viking suggests rotating the pump shaft every 30 days to circulate the oil in the pump. The coupling should be stored in a dry area. Note: if the liquid to
be pumped reacts with oil, use an acceptable alternate.
CANISTER O-RING
PUMP
BRACKET
ROTOR
IDLER
4. Snap ring pliers (heavy duty)
EXTERNAL 2-810-029-375
5. Bearing locknut spanner wrench (Source: #471 J.H. Williams & Co. or equal)
6. Arbor press
7. Feeler gauge set
8. Bearing housing jack screws (2 required)
(Supplied with coupling 2-297-022-999)
9. Brass bar
DANGER !
HEAD
IDLER PIN
PRESSURE RELIEF VALVE
SUGGESTED REPAIR TOOLS: The following tools are
required to properly repair a Mag Drive pump. These tools are in addition to standard mechanics tools such as open end wrenches, socket set, pliers, screw drivers, etc. Most items can be obtained from an industrial supply house.
1. Soft headed hammer
2. Allen wrenches
3. Spanner wrench, adjustable pin type for use on end cap
(Source: #482 J.H. Williams & Co. or equal)
SECTION TSM 845.1 ISSUE C PAGE 4 OF 13
Follow recommended procedures to assemble or disassemble magnetic couplings.
Failure to do so may result in serious injury.
Page 5
FIGURE 5
EXPLODED VIEW – LQ & LS SIZE MAG DRIVE PUMPS
ITEM DESCRIPTION ITEM DESCRIPTION ITEM DESCRIPTION
1 Brkt Gasket - Pilot Face 10 Locating Pin 19 Idler & Bushing
2 Brkt Gasket - Pilot O.D. 11 Pipe Plugs 20 Head Gaskets
3 Bracket 12 Casing 21 Idler Pin
4 Capscrews for Bracket 13 Capscrew w/Orifice 22 Head & Idler Pin
5 Capscrews for Casing 14 Lockwasher 23 Pipe Plug
6 Pipe Plug 15 Key 24 Capscrews for Head
7 Casing Gasket 16 External Snap Ring 25 Gaskets for Relief Valve
8 Bracket Bushings 17 Rotor & Shaft 26 Relief Valve
9 Balance Plate 18 Idler Bushing 27 Capscrews for Relief Valve
FIGURE 6
EXPLODED VIEW – Q & QS SIZE MAG DRIVE PUMP (QS SHOWN)
ITEM DESCRIPTION ITEM DESCRIPTION ITEM DESCRIPTION
1 Brkt Gasket - Pilot Face 11 Pipe Plugs 21 Head Gaskets
2 Brkt Gasket - Pilot O.D. 12 Casing 22 Idler Pin
3 Bracket 13 Studs for Flanges 23 Head & Idler Pin
4 Capscrews for Bracket 14 Nuts for Flanges 24 Pipe Plug
5 Capscrews for Casing 15 Capscrew w/Orifice 25 Stud for Head
6 Pipe Plug 16 Lockwasher 26 Nuts for Head
7 Bracket Bushings 17 Key 27 Gaskets for Relief Valve
8 Casing Gasket 18 Rotor & Shaft 28 Relief Valve
9 Balance Plate 19 Idler Bushing 29 Capscrews for Relief Valve
10 Locating Pin 20 Idler & Bushing
SECTION TSM 845.1 ISSUE C PAGE 5 OF 13
Page 6
FIGURE 7
EXPLODED VIEW – D SERIES COUPLING
ITEM DESCRIPTION ITEM DESCRIPTION ITEM DESCRIPTION
1 Locknut 9 Jack Screws 17 Outer Magnet Assembly
2 Lockwasher 10 Set Screws 18 Bracket
3 Endcap 11 Insert 19 Temperature Monitor (Optional)
4 Lip Seals 12 Capscrews, Bearing Housing 20 Pipe Plug
5 Bearing Spacer, Outer 13 Grease Fitting 21 Capscrews for Canister
6 Tapered Roller Bearing, Outer 14 Bearing Housing 22 Canister
7 Bearing Spacer, Inner 15 Gasket, Bearing Housing 23 Washer
8 Tapered Roller Bearing, Inner 16 Key 24 Inner Magnet Assembly
DISASSEMBLY: PUMP
1. See Figure 5 or Figure 6 on page 5 for name of
DANGER !
Before opening any Viking pump liquid chamber (pumping chamber, reservoir, relief valve adjusting cap fitting etc.) Be sure:
1. That any pressure in the chamber has been completely vented through suction or discharge lines or other appropriate openings or connections.
2. That the driving means (motor, turbine, engine, etc.) has been “locked out” or made non-operational so that it cannot be started while work is being done on pump.
3. That you know what liquid the pump has been handling and the precautions necessary to safely handle the liquid. Obtain a material safety data sheet (MSDS) for the liquid to be sure these precautions are understood.
Failure to follow above listed precautionary measures may result in serious injury or death.
parts.
2. Mark the head, casing and bracket before dis­assembly to insure proper reassembly. The idler pin, which is offset in pump head, must be positioned toward and equal distance between port connections to allow for proper flow of liquid through pump.
3. Unless there appears to be something wrong with the relief valve (if present), leave assembled and attached to the pump head. If disassembly is required, refer to
PRESSURE RELIEF VALVES on page 12.
the pump head capscrews (LQ & LS) or the nuts (Q & QS).
4. Carefully remove the head from the pump. Make sure the idler does not slide off the idler pin by tilting the pump head back while removing. Avoid damage to the head gasket set or O-ring since all gaskets are required to set end clearance and the O-ring enhances sealing.
5. Remove the idler and bushing assembly from idler pin. If the idler bushing needs replacing, see
INSTALLATION OF BUSHINGS on page 9.
Disassembly and inspection of the pump in this manner is generally sufficient for routine evaluation of the pump’s condition. If the idler pin and bushing are original parts and in good condition, usually the rest of the pump is also in good condition.
Remove
SECTION TSM 845.1 ISSUE C PAGE 6 OF 13
Page 7
Before further disassembly of the pump can occur, the pump must be separated from the coupling. Refer to DISASSEMBLY: MD-D SERIES COUPLING on page 7 before proceeding with step 6.
DISASSEMBLY: MD-D SERIES COUPLING
6. After the inner magnet is removed from pump shaft,
remove the external snap ring from pump shaft (LQ & LS only). The rotor and shaft may now be removed by tapping on the end of shaft with a soft face hammer or, if using a regular hammer, use a piece of hardwood between the shaft and hammer.
7. Because the balance plate is designed to be used in either rotation, mark the balance plate prior to removal. Remove balance plate by pulling out of casing.
Examine the casing for wear, particularly the area between the ports. All parts should be cleaned and checked for wear or damage before pump is assembled.
When making major repairs, such as replacing a rotor and shaft, it is advisable to also install a new head and idler pin, idler and bushing, bracket bushings, balance plate and head gaskets. See INSTALLATION OF BUSHINGS on page 9.
PUMP ROTATION
Viking Mag Drive® pumps are directional. If it is necessary to rotate in the opposite direction, the pump must be disassembled through step 7. Rotate the balance plate 180º and reinstall into the casing. Second, the pipe plug (item 23 for LQ & LS, item 24 for Q & QS) must be on the suction side of the head. Remove the pipe plug and reinstall in the other similar hole in the head Follow the procedure for pump assembly. Reverse the relief valve orientation so the adjusting cap points towards suction port.
PORT ARRANGEMENT
CAUTION !
Magnet sets are extremely powerful.
.
Serious injury may result if proper procedures are not followed.
1. Install the two jackscrews (2-297-022-999) into the bearing housing. See Figure 7 on page 6, and Figure
8. Remove two 0.50” capscrews and thread a 0.50” NC x
8” threaded rod into these holes. Remove other two 0.50” capscrews.
FIGURE 8
Standard configuration (as viewed from the pump shaft) is right angle porting (LQ, LS & Q) – the suction port for clockwise rotation is at 9 o’clock. The top port (at 12:00) is the standard discharge port. If the desired configuration is different and the rotation is still clockwise, mark the suction port, remove the (8) bracket to casing capscrews and carefully rotate the casing on the bracket pilot then reinstall the capscrews. The QS features opposite ports and can not be rotated because the flanged ports will interfere with the pump bracket foot.
FIGURE 9
FIGURE 10
2. Turn in the two jackscrews evenly, backing the bearing
housing away from the bracket. See Figure 8. Install a strap from overhead to support the housing and outer magnet when the housing is approximately 1.50” away from the bracket. See Figure 9. Continue turning the jackscrews until the outer assembly comes out freely. See Figure 10.
SECTION TSM 845.1 ISSUE C PAGE 7 OF 13
Page 8
3. Set the outer assembly with magnets down on a clean, flat surface (preferably not steel) to keep from rolling around. Remove temperature probe (if present).
4. To facilitate disassembly, it may be necessary to slide a block of wood under the pump casing or clamp pump foot as shown, since the pump alone will not balance on foot. See Figure 11. Remove the (4) 0.50” capscrews securing the pump to the coupling bracket. After parting the bracket slightly, it will have a tendency to be drawn to one side due to the inner magnet. Pull the coupling bracket completely away.
FIGURE 11
7. Insert a brass bar through a port between two rotor teeth
and loosen the capscrew holding the inner magnet onto the shaft. See Figure 13. The 0.437” capscrew has right hand threads therefore turn it counterclockwise. THE
INNER MAGNET HAS A VERY STRONG MAGNETIC FIELD AND IS MOST DANGEROUS IN THE UN­ASSEMBLED CONDITION. THE MAGNET IS QUITE HEAVY AND WILL BE DRAWN TO ANY FERROUS OBJECT OR SURFACE CAUSING POTENTIAL PINCHING. BEWARE OF THE CAUTIONS LISTED ON (PAGE 3). USE EXTREME CARE SLIDING THE MAGNET OFF OF THE PUMP SHAFT. SET THE MAGNET DOWN ON EITHER END AWAY FROM ALL OTHER OBJECTS. See Figure 14. Remove the key
and the external snap ring (LQ & LS) and then finish disassembly of the pump.
5. There will probably be some liquid left in the canister so take the necessary safety precautions. The canister drain is located behind the mounting flange and near the underside. Removing plug will drain most of the canister. Once the liquid has drained, replace the plugs.
6. Remove the (8) 0.375” Allen head capscrews holding the canister in place then slide the canister off. See Figure
12.
FIGURE 12
FIGURE 13
FIGURE 14
SECTION TSM 845.1 ISSUE C PAGE 8 OF 13
Page 9
BEARING HOUSING
DISASSEMBLY OF BEARING HOUSING
The bearing housing features two grease packed tapered roller bearings (TRB) along with a one-piece outer magnet assembly with shaft. The unit may be greased externally using the grease fitting. See Figure 15 if further assembly is required and proceed as follows:
1. Cover the open end of the outer magnet with a piece of sheet metal. This will keep foreign material out of magnet area and protect the magnets. Set the assembly face down with the shaft pointing up and remove jackscrews.
2. Bend the lockwasher tab up and gently tap the locknut in a counterclockwise direction with a punch until loose. (If this does not work, place a key into shaft of outer magnet. Use 1.875” wrench to hold outer magnet and a spanner wrench to loosen lock nut. Remove the locknut and lockwasher. Then lift the bearing carrier off the shaft of the outer magnet assembly.
3. Back out the (2) setscrews holding the bearing cap then remove the bearing cap with a spanner wrench. The inner and outer spacers, outer TRB and inner TRB cone should all slide out of the bearing housing.
4. One lip seal is pressed into the bearing cap and the other is pressed into the bearing housing. Do not remove unless replacing.
5. If inner TRB is worn or damaged, remove cup of inner TRB.
END CAP
BEARING HOUSING
LIP SEAL
.75 REF
OUTER
SPACER
LOCK NUT
LOCK WASHER
SET SCREWS (2)
OUTER BEARING
INNER SPACER
GREASE FITTING
INNER BEARING
OUTER MAGNET ASSEMBLY
COVER END OF MAGNET WITH PIECE OF SHEET METAL APPROX. 10” x 10”
FIGURE 15
ASSEMBLY OF BEARING HOUSING
Depending on the condition of the bearings either replace or recondition existing bearings by cleaning and packing with a heavy duty grease. Replace the lip seals if necessary.
1. Place the bearing carrier down with the cast surface up. Install the inner lip seal (if removed). Then install the cup (if removed) of the inner TRB and the cone into the bearing housing bore. Insert the inner bearing spacer (longer one of the two) and the outer TRB into the bore. Place outer spacer on top of the cone of the outer TRB.
2. The outer end cap houses the second lip seal. If the seal is in good condition, slide the endcap over the outer spacer then thread into bearing housing. Center the inner spacer so the shaft will slide through the two bearings. Thread in the end cap until it makes contact with the outer TRB. Tighten the endcap by hand until tight and secure in position with the (2) setscrews.
3. Insert the outer magnet shaft through the bearings and the spacers. When the shaft is in the proper position there should be approximately 0.75” between the magnet and the housing. See Figure 15.
4. Place the lock washer onto the shaft then thread the locknut onto the shaft. Tighten locknut to 50 Ft-Lbs then bend over a lockwasher tab.
5. Tighten the endcap to 75 Ft-lbs and rotate bearing housing 2-3 turns. Back off the end cap and then retighten to 75 Ft-Lbs. Tighten the two .31” setscrews onto the endcap.
Use the grease fitting to fill the bearing chamber with additional grease.
INSTALLATION OF BUSHINGS
CARBON GRAPHITE:
When installing carbon graphite bushings, extreme care must be taken to prevent breaking. Carbon graphite is a brittle material and easily cracked. If cracked, the bushing will quickly disintegrate. Using a lubricant on the bushing and mating part will help in installation. The additional precautions listed below must be followed for installation:
1. An arbor press must be used for installation.
2. Be certain bushing is started straight.
3. Do not stop pressing operation until bushing is in proper
position, starting and stopping will result in cracking bushing.
4. Check bushing for cracks after installation.
SILICON CARBIDE:
When installing silicon carbide bushings into a metal part the mating part must be heated to 600ºF (preferably in an oven). Bushing must be quickly put into the proper position before the mating part cools down and the bushing heats up.
FAILURE TO FOLLOW THIS PROCEDURE WILL RESULT IN CRACKED BUSHINGS.
SECTION TSM 845.1 ISSUE C PAGE 9 OF 13
Page 10
PUMP ASSEMBLY
Use a lubricant compatible with the fluid being handled when reassembling the pump.
Inspect all parts, replacing any worn parts. Polish out any nicks or burrs and clean all parts thoroughly. Make sure drilled holes in rotor, shaft, orifice, balance plate and bracket are clear. Plugged areas will cause heat buildup and destroy the magnets. Also check the drilled passageways in the head and idler pin to be sure they are clear.
1. If the casing was removed from the bracket, place the O-ring into the groove on back mounting face of casing (side closest to the hole for the locating pin), and carefully slide the casing onto the pilot of the bracket and install capscrews. Install the locating pin into the casing.
2. Place the balance plate into the casing bore with grooved side out. Orient the groove toward the discharge port. Push to the bottom of the casing. Line up the notch in plate with the pin projecting through the casing bore.
3. Insert the shaft gently into the inner bushing bore and push through until rotor is up against the balance plate.
4. If the old head gaskets are not reusable, refer to Gasket Table Figure 18. Otherwise, place all head gaskets on the head. Proper placement of the head is achieved by the correct number of gaskets. Improper placement will adversely affect the operation of the pump. The Gasket Table shows the recommended end clearance and itemizes the content of gaskets in a set. The O-ring is the primary seal and should be installed onto the head pilot after the proper gaskets have been put in place.
FIGURE 16
FIGURE 17
5. Coat the idler pin with suitable lubricant and place the
idler on the idler pin in head.
6. The head can now be assembled on the pump. Tilt the top of the head away from the pump slightly until the crescent enters the inside diameter of the rotor and rotate the idler until its teeth mesh with the rotor teeth. Line up mark on head and casing, which were previously marked to insure proper reassembly. Be sure idler pin, which is offset in pump head, is positioned toward and equal distance between port connections to allow for proper flow of liquid through pump. Tighten the head capscrews (or nuts onto studs in the Q size). Check the end clearance using a feeler gage as illustrated. See Figure 20 on page
11. If end clearance is not correct, refer to section on ADJUSTING HEAD GASKET END CLEARANCE on page 11.
7. Install relief valve if provided and removed.
8. Install the snap ring onto the shaft (not required on Q
size). Apply a lubricant to the canister O-ring and place into the face groove in the bracket.
GASKET TABLE
NORMAL
END
PUMP MODEL
LQ & LS-825 .008
Q & QS-825 .010
End clearances are adequate for viscosities up to 750 SSU
(SAE 20-lube oil at room temperature). Higher viscosity liquids require additional end clearances.
As a general guideline, for viscosities between 750 and 7500 SSU (heavier lube oils) add an additional 50% of the end clearance listed, for viscosities between 7500 and 25,000 SSU (e.g., resins) double the amount indicated.
For specific recommendations for end clearances for viscosity or for operating temperatures above 225ºF, check with your Viking representative or consult the factory.
CLEARANCE
FIGURE 18
ONE SET OF
GASKETS CONSISTS
OF THE FOLLOWING
(1) .015
(2) .007
(2) .005
(1) .015
(2) .007
(3) .005
SECTION TSM 845.1 ISSUE C PAGE 10 OF 13
Page 11
ADJUSTING HEAD GASKET END CLEARANCE
Use either of the following procedures to properly adjust the end clearance, when replacing gaskets.
PROCEDURE A:
With the casing secured to the bracket and balance plate in position, slide the rotor and shaft into the casing. Insert the feeler gage of the proper thickness into the port and between two rotor teeth. Install one .015” and .007” gasket onto the head. With the idler on idler pin, place head into the pump casing. With capscrews tight, the feeler gage should fit snugly; otherwise gaskets should be added or removed until the proper clearance is attained. See Figure 19.
ASSEMBLY: D SERIES COUPLING
1. Remove any foreign material attached to the magnets.
Place key in pump shaft and slide inner magnet on shaft until it comes to rest against shoulder on shaft. Insert washer, lockwasher and capscrew into end of magnet and tighten. May require inserting brass bar into port to block rotor from turning. Install O-ring into face of pump bracket then slide canister over inner magnet and secure with the capscrews.
DANGER !
Follow these directions exactly to avoid injury to self or damage to pumping unit, be extremely careful to keep inner & outer magnets at least (1) foot apart until step
3. Do not allow magnets to engage in any other fashion. Be aware of health hazards listed on (page 2).
2. Place a spacer under pump so the foot sits flat and clamp
foot to the table. Install one of the secondary O-Ring seals onto the pump pilot then slide the coupling bracket up to pump and bolt together.
FIGURE 19
PROCEDURE B:
If the pump is in the pipeline and not accessible through ports, remove the head and remove gaskets. Put the head back on and measure the gap as shown. See Figure 20. After determining the gap between head and casing, select a combination of gaskets with approximately 25% more total thickness than the feeler gage plus required end clearance. See Figure 18 on page 10. Note: gaskets will compress when head is tightened down. Remove head, install all gaskets and the O-ring, and then install head. Tighten the head capscrews and then check the pump by making sure the pump turns over freely by hand.
3. Install two threaded rods into the bracket on the other end. Insert the (2) jackscrews into their holes of the bearing housing and thread in completely. Install other secondary O-ring onto the bearing housing pilot. Support the bearing housing assembly from over head then slide onto the (2) threaded rods. Balance the assembly and glide outer magnet onto canister until jackscrews come to rest in the two counter bored holes on the bracket. BE
CAREFUL TO CENTER THE OUTER MAGNET WHILE STARTING TO ENGAGE CANISTER. Depending
on lengths of magnets the unit may be drawn in as the jackscrews are removed or may require pushing in. Evenly back off the jack screws until the housing is approximately 1” from the bracket then remove the over head support and finish backing off the jack screws. The housing may require a slight lift to get into the pilot of the bracket. Secure with (2) capscrews then remove the rods and install final (2) capscrews.
DANGER !
Before starting pump, be sure all drive equipment guards are in place.
Failure to properly mount guards may result in serious injury or death.
FIGURE 20
SECTION TSM 845.1 ISSUE C PAGE 11 OF 13
Page 12
TROUBLESHOOTING
PRESSURE RELIEF VALVES
Some of the following may help pinpoint the problem:
Pump does not pump:
Pump has lost its prime from air leak or low level in tank.
Suction lift is too high
Pump is rotating in the wrong direction
Suction and/or discharge valves not open.
The strainer may be clogged.
The bypass valve is open, the pressure relief valve is set too low or the pressure relief valve poppet stuck open.
Improper end clearance
The pump is worn out.
Are there any changes in liquid, system or operation that would influence pump or coupling performance, e.g. new liquid, additional lines or process changes?
Temperature changes either in the liquid or the environment.
The magnetic coupling is decoupling. Changes in application (temperature, pressure, viscosity, etc.) may require torque beyond coupling capabilities.
Pump starts, then loses its prime:
The supply tank is empty
Liquid vaporizing in the suction line
An air leak or air pocket in the suction line.
Pump is noisy:
Pump is being starved (heavy liquid cannot get to pump fast enough). Increase suction pipe size, reduce its length or slow down the pump.
Pump is cavitating (liquid vaporizing in suction line). Increase suction pipe size or reduce its length.
Check alignment.
The magnetic coupling has decoupled. Shut off and restart.
Pump is not delivering up to capacity:
The pump is starving or cavitating – increase suction pipe size or reduce length or reduce pump speed.
The strainer is partially clogged.
An air leak somewhere in suction line.
The pump may be running too slow. Is motor the correct speed and wired up correctly?
The pressure relief valve is set too low, stuck open or has a damaged poppet or seat.
The bypass line around the pump is partially open.
The pump is worn out or has too many gaskets.
PRESSURE ADJUSTMENT
If a new spring is installed or if pressure setting of pressure relief valve is to be changed from that which the factory has set, the following instructions must be carefully followed.
1. Carefully remove the valve cap, which covers adjusting screw. Loosen locknut, which locks adjusting screw so pressure setting will not change during operation of pump.
2. Install a pressure gauge in discharge line for actual operating adjustment.
3. Turn adjusting screw in to increase pressure and out to decrease pressure.
4. With discharge line closed at a point beyond pressure gauge, gauge will show maximum pressure valve will allow while pump is in operation.
FIGURE 21
LIST OF PARTS
1. Valve Cap 6. Valve Body
2. Adjusting Screw 7. Valve Spring
3. Lock Nut 8. Poppet
4. Spring Guide 9. Cap Gasket
5. Bonnet 10. Bonnet Gasket
Pump takes too much power (stalls motor):
The liquid is more viscous than the unit is sized to handle.
The system pressure relief valve is set too high.
The coupling is misaligned.
The bushings have frozen up or the liquid has set up in the coupling.
SECTION TSM 845.1 ISSUE C PAGE 12 OF 13
IMPORTANT: In ordering parts for pressure relief valve, always give model number and serial number of pump as it appears on nameplate and name of part wanted. When ordering springs, be sure to give pressure setting desired.
Page 13
TECHNICAL SERVICE MANUAL
DISASSEMBLY: RELIEF VALVE
DANGER !
SECTION TSM 845.1
PAGE 13 OF 13
ISSUE C
Before opening any Viking pump liquid chamber (pumping chamber, reservoir, relief valve adjusting cap fitting, etc.) be sure:
1. That any pressure in the chamber has been completely vented through the suction or discharge lines or other appropriate openings or connections.
2. That the driving means (motor, turbine, engine, etc.) has been “locked out” or made non-operational so that it cannot be started while work is being done on pump.
3. That you know what liquid the pump has been handling and the precautions necessary to safely handle the liquid. Obtain a material safety data sheet (MSDS) for the liquid to be sure these precautions are understood.
Failure to follow above listed precautionary measures may result in serious injury or death.
Mark valve and head before disassembly to insure proper reassembly.
1. Remove valve cap.
2. Measure and record length of extension of adjusting screw. Refer to “A” on Figure 21 on page 12.
WARRANTY
Viking warrants all products manufactured by it to be free from defects in workmanship or material for a period of one (1) year from date of startup, provided that in no event shall this warranty extend more than eighteen (18) months from the date of shipment from Viking. If, during said warranty period, any products sold by Viking prove to be defective in workmanship or material under normal use and service, and if such products are returned to Viking’s factory at Cedar Falls, Iowa, transportation charges prepaid, and if the products are found by Viking to be defective in workmanship or material, they will be replaced or repaired free of charge, FOB. Cedar Falls, Iowa.
Viking assumes no liability for consequential damages of any kind and the purchaser by acceptance of delivery assumes all liability for the consequences of the use or misuse of Viking products by the purchaser, his employees or others. Viking will assume no field expense for service or parts unless authorized by it in advance.
Equipment and accessories purchased by Viking from outside sources which are incorporated into any Viking product are warranted only to the extent of and by the original manufacturer’s warranty or guarantee, if any.
THIS IS VIKING’S SOLE WARRANTY AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, WHICH ARE HEREBY EXCLUDED, INCLUDING IN PARTICULAR ALL WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. No officer or employee of IDEX Corporation or Viking Pump, Inc. is authorized to alter this warranty.
3. Loosen locknut and back out adjusting screw until spring pressure is released.
4.
Remove bonnet, spring guide, spring and poppet from valve body. Clean and inspect all parts for wear or damage and replace as necessary.
ASSEMBLY: RELIEF VALVE
Reverse procedures outlined under Disassembly. If valve is removed for repairs, be sure to replace in original position. Relief valve adjusting screw cap must always point toward suction side of pump. If pump rotation is reversed, remove relief valve and turn end for end. See Figure 3 on page 3. Also refer to PUMP ROTATION on page 7.
VIKING PUMP, INC. A Unit of IDEX Corporation Cedar Falls, IA 50613 USA
DANGER !
Before starting pump, be sure all drive equipment guards are in place.
Failure to properly mount guards may result in serious injury or death.
© 5/2007 Viking Pump Inc. All rights reserved
Loading...