series solar charge controller
1. Overview
Thank you for selecting the ViewStar A series
controller. The VS-A controller is a
PWM charge controller with built in LCD
adopts the most advanced digital technique. The m
ultiple load control modes
can be widely used on solar home system, traffic
signal, solar street light, solar garden
lamp, etc. The features are listed below:
3-Stage intelligent PWM charging:
Bulk, Boost/Equalize, Float
Support 3 charging options: Sealed, Gel, and Flooded
LCD display design, dynamically displaying device
’s operating data and working
condition
Multiple load control modes
Battery temperature compensation function
Extensive Electronic protection
2. Product Features
①
LCD
⑤
PV
③
Mounting hole size Φ4.5
⑦
Remote Temperature Sensor (Model: RTS300R47K3.81A)
Acquisition of battery temperature for undertaking temperature compensation of control
parameters, the standard length of the cable is 3m (length can be customized). The
RTS300R47K3.81A connects to the port (4th) on the controller.
Note: Unplug the RTS, the temperature of battery will be set to a fixed value 25ºC.
(1) Connect components to the charge controller in the sequence as shown above and
pay much attention to the “+” and “-”. Please don’t insert the fuse
during the installation. When disconnecting the
system, the order will be reserved.
(2)After power on the controller, check the LCD on. Otherwise
the battery first, in order to allow the controller to recognize the
The battery fuse should be installed as close to battery as possible.
distance is within 150mm.
(4) The VS-A series
is a positive ground controller. Any positive connection of solar
or battery can be earth grounded as required.
NOTE: Please connect the inverter
or other load that it has the large start current
to the battery rather than to the controller, if the inverter
necessary.
Figure 3 Connection diagram
Figure 1 Characteristic
②
or other load is
4. Operation
4.1 Button Function
MENU button
SET button
4.2 LCD Display
Status Description
Item Icon
PV array
PV Voltage, Current ,Power
Battery voltage. current, temperature
Load Voltage, Current, Load mode
Browse interface
NOTE:
1)
When no operation,
the interface will be automatic cycle
interfaces not be display.
2)
Accumulative power zero clearing: Under PV power interface, press
then the value blink, press
3) Setting temperature unit: U
nder battery temperature interface, press
and hold on 5s to switch.
Fault Indication
Battery level shows empty, battery frame blink,
Battery level shows current value, battery frame
①
When load current reaches1.02-1.0
times more than nominal value, controller will automatically
30s,10s and 2s respectively.
Browse interface
Setting parameter
Load ON/OFF
Clear error
Enter into Set Mode
Save data
Status
attery capacity, In Charging
SET button again to clear the value.
full, battery frame blink, fault
-1.25 times, 1.25-1.35 times and
turn off loads in 50s,
4.3 Load mode setting
Operating Steps:
Under load mode setting interface, press SET button
begin flashing, then press MENU button
to set the parameter, press
101
Load will be on for 1 hour
since sunset
201
Load will be on for 1 hour
102
Load will be on for 2 hours
since sunset
202
Load will be on for 2 hour
Load will be on for 3~13
hours since sunset
203~213
114
Load will be on for 14 hours
since sunset
214
115
Load will be on for 15 hours
since sunset
215
117
Manual mode(Default load
ON)
2 n
Please set Light ON/OFF, Test mode and Manual mode via Timer1.
will be disabled and display "2 n".
4.4 Battery Type
Operating Steps
Under Battery Voltage interface, press SET button
interface of Battery type setting. After choosing the battery type by pressing
button, waiting for 5s or pressing SET
button again to modify successfully.
Battery Type
①
Sealed (Default) ②Gel
③
NOTE: Please refer to the battery voltage parameters table
battery type.
5. Protections
PV Short Circuit
When PV short circuit occurs, the controller will stop charging. Clear it to resume normal
operation.
PV Reverse Polarity
Fully protection against PV reverse polarity, c
orrect the wire connection to resume
normal operation.
Battery Reverse Polarity
Fully protection against battery reverse polarity, c
orrect the wire connection to resume
normal operation.
Warning:Shock Hazard!
When the battery is reverse, the load will app
polarity voltage to battery.
Battery Over Voltage
When the battery voltage reaches to the set point of Over Voltage
charging the battery to protect the battery from being over
charged to break down.
Battery Over Discharge
When the battery voltage reaches to the set point of Low Voltage Disconnect
the controller will stop discharging the battery to protect the
discharged.
Battery Overheating
The controller detect the battery temperature through the external temperature sensor. If
the battery temperature exceeds 65ºC, the controller will automatically start the
overheating protection to stop working and recover below 50 ºC.
Load Overload
Load will be switched off when 1.05 times rated current overload happens. Controller
ill automatically attempt to reconnect load for 5 times. If overload protection still exist
after controller’s 5 times attempts, user have to
reduce load appliance, then
SET button or repower the controller or wait for one night-
hours).
Load Short Circuit
Load will be switched off when load short circuit (≥
4 times rated current) happens.
Controller will automatically attempt to reconnect load for 5 times. If short circuit
protection still exist after controller’s 5 times attempts, user have to
circuit ,then press the SET button or disconnect and restart the
controller or wait for one
night-day cycle (night time>3 hours).
Damaged Remote Temperature Sensor
If the temperature sensor is short-
circuited or damaged, the controller will be charging or
discharging at the default temperature 25 to preven℃
t the battery damaged from
overcharging or over discharged.
Controller Overheating
If the temperature of the controller heat sinks exceeds 85
automatically start the overheating protection and recover below 75
High Voltage Transients
PV is protected against small high voltage surge. In lightning prone areas, additional
external suppression is recommended.
till the number
SET button to
6. Troubleshooting
Faults
The LCD is off
during daytime when
sunshine falls on PV
modules properly
Wire connection is
correct, LCD not
display
circuit
7. Technical Specifications
Nominal system voltage
Battery input voltage
range
Rated charge current 10A
Max. PV open circuit
voltage
Temperature
compensation coefficient
Self-consumption
Charge circuit voltage drop
Discharge circuit voltage
drop
LCD temperature range
Working environment
temperature
Humidity range
Enclosure
Grounding
Mounting hole size
Terminals 4mm
is working under high temperature environment,
capacity in service
Battery Voltage Parameters
(parameters is in 12V system at 25
value in 24V.)
Battery charging setting
Over Voltage Disconnect Voltage
Charging Limit Voltage
Over Voltage Reconnect Voltage
Equalize Charging Voltage
Boost Charging Voltage
Float Charging Voltage
Boost Reconnect Charging Voltage
Low Voltage Reconnect Voltage
Under Voltage Warning Reconnect Voltage
Under Volt. Warning Volt.
Low Volt. Disconnect Volt.
Discharging Limit Voltage
Equalize Duration
Boost Duration
8. Disclaimer
1)
Damage from improper use or use in an
PV or load current, voltage or power exceeding the rated value of controller.
User disassembly or attempted repair the controller without permission.
The controller is damaged due to natural elements such as lighting.
The controller is damaged during transportation and shipment.
Any changes without prior notice!
Confirm that PV wire connections
are correct and tight
1. Please check the voltage of
battery. At least 9V voltage to
activate the controller
2. Check the PV input voltage
which should be higher than
battery’s
Check if the battery voltage is
higher than OVD point (over
voltage disconnect voltage), and
disconnect the PV.
When the battery voltage is
restored to or above LVR point
(low voltage reconnect voltage),
the load will recover
The controller will automatically
turn the system off. But while the
temperature decline to be below
50 ºC, the controller will resume.
Short
Please reduce the number of
electric equipments or check
carefully loads connection.
VS2024A VS3024A
12/24VDC Auto
9~32V
20A
30A
50V
-3mV/℃/2V(25℃)
≤8.1mA(12V);≤6.5mA(24V)
≤0.29V
≤0.16V
-20℃~+55℃
-25℃~+55℃*
≤95% (N.C.)
IP30
Common Positive
149x94.1
x46.1mm
177.5x106.6
x46.2mm
137x60mm
165.5x70mm
Φ4.5mm
℃, please use double
Sealed Gel Flooded
16.0V 16.0V 16.0V
15.0V 15.0V 15.0V
15.0V 15.0V 15.0V
14.6V —— 14.8V
14.4V 14.2V 14.6V
13.8V 13.8V 13.8V
13.2V 13.2V 13.2V
12.6V 12.6V 12.6V
12.2V 12.2V 12.2V
12.0V 12.0V 12.0V
11.1V 11.1V 11.1V
10.6V 10.6V 10.6V
120min —— 120min
120min 120min 120min