Viessmann Vitodens 200-W WB2B Series, Vitodens 200-W, WB2B-19, WB2B-26, WB2B-35 Technical Data Manual

...
Page 1
Technical Data Manual
Model Nos. and pricing: see Price List
VITODENS200-W
Gas-fired wall-mounted condensing boiler
31 to 370 MBH / 9 to 105 kW
Multi-boiler installation 320 to 1480 MBH/
Vitodens 200-W
WB2B Series
with modulating MatriX cylinder burner for room air independent operation (using a direct vent system) or room air dependent operation
For Natural Gas and Liquid Propane Gas Heating input 31 to 370 MBH for NG and LPG 9 to 105 kW
5369 295 v1.5 09/2012
This trademark is registered with the U.S. Patent and Trademark Office.
Page 2
Product Information
5
3
6
9
2
9
5
v
1
.
5
VITODENS 200-W
Equipped with the industry’s first intelligent combustion management system and powerful control technology, the new generation Vitodens 200-W gas-fired wall-mount condensing boiler delivers unparalleled performance, reliability and comfort.
The benefits at a glance:
HBest value in its class with new
industry-leading technology and the most standard features.
HHighest Efficiency up to 98% at full
modulation and up to 96.1% A.F.U.E. CSA thermal efficiency rating to ANSI Z.21.13/CSA 4.9 of 94.5% (for model WB2B 105 only). Energy Star and the CSA Energy Performance are not applicable for model WB2B 105.
HLasting performance with industry-leading
Viessmann made SA240 316 Ti stainless steel Inox-Radial heat exchanger constructed to CSA B51 and ASME Section IV.
HLow Emission Combustion with Viessmann
made stainless steel MatriX cylinder burner. Factory calibrated.
HFast Installation and Reduced Maintenance
with Lambda Pro, industry-first intelligent combustion management system: Adjusts automatically to gas type and quality. No fuel conversion kit required.
HPowerful and User-friendly
Viessmann Vitotronic on-board multi-function outdoor reset boiler and system control for multi-temperature space and DHW heating.
HCompact, Esthetic Product Design
and zero clearance to combustibles.
HExtremely Quiet Operation; quieter than
most refrigerators.
HTrue High-Altitude Operation up to
10,000 ft. / 3,000 m with simple electronic adjustment.
HEfficiency up to 98% through intensive
condensation. The flue gas temperature is only approximately 9-27º F (5-15º C) above boiler return temperature (see chart below).
HExpanded Application Range with
increased capacity up to 370 MBH. Multi-boiler installation up to 1480 MBH with up to 4 boilers (models WB2B 45, 60, 80, 105).
HGreater Venting Flexibility with increased
vent length (up to 180 ft. / 55 m) and multiple venting options.
- Horizontal or vertical sealed combustion coaxial venting (factory supplied).
- Horizontal, vertical or hybrid sealed combustion double-pipe venting (field supplied).
- Horizontal or vertical single-wall venting (field supplied).
2
Page 3
Inox-Radial
5
3
6
9
2
9
5
v
1
.
5
heat exchanger
Modulating MatriX cylinder burner
Cross-Section
Vitotronic 200, HO1 on-board outdoor reset control
Boiler may not look exactly as illustrated.
3
Page 4
Technical Data
5
3
6
9
2
9
5
v
1
.
5
Table 1.
Boiler Model Model No. WB2B- 19 26 35 45 60 80 105*
Natural gas / Liquid propane gas
CSA input
CSA output/DOE
*1
heating capacity
Net I=B=R rating
*2
Heat exchanger surface area ft.
Min. gas supply pressure
Natural gas Liquid propane gas
Max. gas supply pressure
*3
Natural gas Liquid propane gas
A.F.U.E. % 96.1 96.1 96.1 96.1 96.1 96.1
CSA thermal efficiency ANSI Z21.13/CSA 4.9 % 94.5
Weight lbs
Boiler water content USG
Boiler max. flow rate
*4
Max. operating pressure
at 210ºF / 99ºC
Boiler water temperature
– Adjustable high limit (AHL)
range
space heating (steady state) DHW production
– Fixed high limit (FHL)
Boiler connections
Boiler heating supply and return NPTM “ Pressure relief valve NPTF “ Drain valve (male
MBH kW MBH kW
31-67
9-20
28-61
8-18
31-93
9-27
28-85
8-25
31-125
9-37
28-114
8-33
60-160
17-47
55-146
16-43
60-212
17-62
55-194
16-57
104-285
30-83
95-260
28-76
104-370
30-108 98-350 29-103
MBH 53 74 99 127 169 226 304
2
2
m
“w.c. “w.c.
“w.c. “w.c.
kg
L
GPM L/h
psig bar
ºF/ ºC ºF/ ºC ºF/ºC
10.23
0.95
10
14 14
102
46
0.87
3.3
6.2
1400
45
¾ ¾ ¾
10.23
0.95
4
4
10
14 14
102
46
0.87
3.30
6.2
1400
45
3
3
¾ ¾ ¾
10.23
0.95
10
14 14
102
46
0.87
3.3
6.2
1400
45
68 to 165 /
20 to 74
165 /
74
210/99
¾ ¾ ¾
15.76
1.46
4
4
10
14 14
155
70
1.9
7.2
15.4
3500
60
3
4
15.76
1.46
10
14 14
155
70
1.9
7.2
15.4
3500
60
28.88
2.68
4
28.88
2.68
4
10
14 14
225 102
225 102
3.4
12.8
35.2
8000
12.8
35.2
8000
60
4
4
68 to 176 /
20 to 80
176 /
80
210/99
¾ ¾
¾ ¾
¾ ¾
thread)
10
14 14
3.4
60
¾ ¾
A
4
4
Boiler supply/return for indirect-fired DHW storage tank NPT” (field supplied) Gas valve connection NPTF
*AFor high altitude installations (5,000 - 10,000 ft.), the input for model WB2B 105 will have an altitude de-ration of 14% for 5,000 ft.
and 28% for 10,000 ft. (average of 2.8% / 1,000 ft.).
*1
Output based on 140ºF / 60ºC, 120ºF / 49ºC system supply/return temperature.
*2
Net I=B=R rating based on piping and pick-up allowance of 1.15.
*3
If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator must be installed upstream of the
heating system.
*4
See “Typical System Flow Rates” on page 11 in this manual.
4
¾
¾
¾
¾
¾
¾
1
1
1
1
Page 5
Technical Data
5
3
6
9
2
9
5
v
1
.
5
Table 1 (continued)
Boiler Model Model No. WB2B- 19 26 35 45 60 80 105*
Dimensions
Overall depth
Overall width
Overall height
Height with flue gas elbow (accessory)
Flue gas
*5
Temperature (at boiler return temperature of 86ºF / 30ºC) – at rated full load – at rated partial load
Temperature (at boiler return temperature of 140ºF / 60ºC)
Average condensate flow rate
*6
with natural gas and
TS/TR=104/86ºF / 40/30ºC USG/day
Condensate connection
*7
Boiler flue gas connection
Combustion air supply connection (coaxial)
*8
inches mm inches mm inches mm inches mm
ºF/ºC ºF/ºC
ºF/ºC
L/day
14
360
17¾
450
33½
850
44
1116
113/45
95/35
154/68
2.6-3.4 10- 12
14
360
17¾
450
33½
850
44
1116
113/45
95/35
158/70
2.9-3.4 11- 13
14
360
17¾
450
33½
850
44
1116
113/45
95/35
158/70
4-4.5
15- 17
15
380
19
480
33½
850
47¼
1200
95/35 91/33
149/65
3.7-5
14- 19
15
380
19
480
33½
850
47¼
1200
104/40
95/35
158/70
6-7.4
23- 28
21
530
19
480
33½
850
47¼
1200
95/35 91/33
149/65
6.6-7.9 25-30
hose nozzle in 1 1 1 1 1 1 1
*8
in/mm
3
2
/
8
/60 2
3
/
/60 2
8
3
/
/60 3¼/80 3¼/80 4
8
3
/
/110 4
8
outer in/mm 4/100 4/100 4/100 5/125 5/125 6/150 6/150
*9
530
480
33½
850
47¼
1200
104/40
95/35
158/70
9.5-10.5 35-40
3
/
/110
8
A
21
19
*9
*AFor high altitude installations (5,000 - 10,000 ft.), the input for model WB2B 105 will have an altitude de-ration of 14% for 5,000 ft.
and 28% for 10,000 ft. (average of 2.8% / 1,000 ft.).
*5
Measured flue gas temperature with a combustion air temperature of 68°F / 20°C.
*6
Based on typical boiler cycles, including partial load conditions.
*7
Requires 1” / 25 mm tubing. See the Installation Instructions of the Vitodens 200-W, WB2B for details.
*8
For side wall vent installations (coaxial system):
Do not exceed max. equivalent length specified in the Installation Instructions of the Vitodens 200-W, WB2B Venting System. A maximum of 5 elbows may be installed in the vent system. Do not attempt to common-vent Vitodens 200-W with any other appliance. Venting material to be supplied by Viessmann only; side wall vent installation must include Viessmann protective screen! For details refer to the Installation Instructions for the Vitodens 200-W, WB2B Venting System.
*9
Add 2½” / 65 mm for coaxial vent pipe transition adaptor.
" For information regarding other Viessmann System Technology componentry, please reference documentation of respective product.
5
Page 6
*1
5
3
6
9
2
9
5
v
1
.
5
Dimensional Information
Models WB2B 19, 26, 35
2½” / 65 mm
7” / 177 mm
2¾” / 70 mm
17¾” / 450 mm
13¾” / 348 mm
2¾” / 70 mm
78” / 1975 mm
for single boiler
4” / 102 mm
4” / 102 mm
87/8” / 225 mm
12” / 300 mm
installation
6¼” / 158 mm
55/8” / 143 mm
33½” / 850 mm
1¾” /
44 mm 141/8” / 360 mm
Fig. 2
Floor line
Fig. 1
Legend
BD Boiler Drain BR Boiler Return BS Boiler Supply AV Air Vent (not shown) GC Gas Connection, ¾” NPT PRV Pressure Relief Valve BF Boiler Fill PG Pressure Gage EXT Extension Adaptors, ¾” NPT DR Boiler heating return for domestic hot
water production ¾” (field supplied)
DS Boiler heating supply for domestic
hot water production ¾” (field supplied)
*
1
See page 38 for alternate DHW connection.
BD
Fig. 3
PRV
DS
EXTEXT
GC
BS
*1DHW Connections
(Field Supplied)
BR
BF
DR
6
Page 7
Models WB2B 45, 60
5
3
6
9
2
9
5
v
1
.
5
Dimensional Information
9½” / 240 mm
6½” / 165 mm
PG
19” / 480 mm
15¾” / 400 mm
9½” / 240 mm
39” / 996 mm
35½” / 902 mm
3” / 80 mm
9½” / 240 mm
51” / 1301 mm
41¾” / 1061 mm
6½” /165 mm
12” / 305 mm
5½” / 146 mm
Ø 5” / 125 mm
33½ “/ 850 mm
78” / 1975 mm for single boiler
installation
4” / 100 mm
15” / 380 mm
Fig. 5
Floor line
Fig. 4
Legend
BD Boiler Drain BR Boiler Return BS Boiler Supply AV Air Vent (not shown) GC Gas Connection, 1” NPT PRV Pressure Relief Valve BF Boiler Fill PG Pressure Gage DR Boiler heating return for domestic hot
water production 1¼” NPT (field supplied)
DS Boiler heating supply for domestic hot
water production 1¼” NPT (field supplied)
*1See page 38 for alternate DHW
connection.
BD
Fig. 6
PRV
DS
GC
BS
*1DHW Connections
(Field Supplied)
BR
BF
DR
7
Page 8
Dimensional Information
5
3
6
9
2
9
5
v
1
.
5
Models WB2B 80, 105
19” / 480mm
4¼” / 108mm
9½” / 240mm
115/8“ / 295mm for WB2B 80-105 using the coaxial vent system
15¾” /
400mm
9½” / 236mm
43” /
33½” /
PG
9½” / 240mm
3” / 80mm
6½” / 165mm
Fig. 7
Legend
BD Boiler Drain BR Boiler Return BS Boiler Supply GC Gas Connection, 1” NPT PRV Pressure Relief Valve BF Boiler Fill PG Pressure Gage DR Boiler heating return for domestic hot water production 1¼” DS Boiler heating supply for domestic hot water production 1¼” *1See page 38 for alternate DHW connection.
15¾” / 400mm
Floor line
9½” / 240mm
1090mm
850mm
78” / 1975 mm
for single boiler
installation
BD
Fig. 8
Fig. 9
PRV
DS
4” / 102mm
21” / 530mm
GC
BS
*1DHW Connections
(Field Supplied)
BR
BF
DR
8
Page 9
Recommended Minimum Service Clearances
5
3
6
9
2
9
5
v
1
.
5
Side
12” / 305 mm
Top 12”/305 mm
Front
28” / 700 mm
Side
Minimum Clearances
Back
0”/mm
Fig. 10
0”/mm
Minimum Clearances to Combustibles
Top Front Rear Left Right Vent pipe
0 0 AL, CL 0 0 0 0
AL= Alcove CL= Closet
*1
Refer to the Installation Instructions of the Vitodens 200-W, WB2B Venting System for details.
Please note: The Vitodens boiler has passed the zero inches vent clearance to combustibles testing requirements dictated by the Harmonized Standard ANSI Z21.13. CSA 4.9.2000 and therefore is listed for zero clearance to combustibles when vented with a single wall special venting system (AL-29-4C material). The zero inches vent clearance to combustibles for the Vitodens boiler supercedes the clearance to combustibles listing that appears on the special venting system label.
*1
9
Page 10
Waterside Flow
5
3
6
9
2
9
5
v
1
.
5
Waterside Flow (primary circuit)
The Vitodens 200-W, WB2B is designed for closed loop, forced circulation hot water heating systems only.
H(ft.)
26
23
19.7
16.4
13.1
9.8
6.6
3.3
Supply head pressure (water)
Fig. 11
H(ft.)
20.1 6.1
16.7
13.4
10.0 3.1
6.7 2.0
H(m)
8
7
6
5
4
3
2
1
0
0
0 500 1000 1500 0 2.2 4.4 6.6 8.8 GPM
H(m)
5.1
4.1
2000 l/h
Pressure drop (primary circuit) for Vitodens 200-W, WB2B 19, 26, 35
For sizing an on-site circulation system. Max. flow rate: 1400 L/h / 6.2 GPM
Pressure drop (primary circuit) for Vitodens 200-W, WB2B 45, 60
For sizing an on-site circulation system. Max. flow rate 3500 L/h / 15.4 USGPM
3.4 1.0
0 0
Supply head pressure (water)
Fig. 12
H(ft.) H(m)
33.5
30.1 9.2
6.7
Supply head pressure (water)
Fig. 13
Use standard friction loss method for pipe sizing. Observe boiler maximum and minimum flow rate limitations. If system flow rate exceeds boiler maximum flow rate (as stated above), falls below the minimum flow rate or if system flow rate is unknown, Viessmann strongly recommends the installation of a low-loss header. An alternative method may be used, such as primary secondary piping using closely spaced tees. A low-loss header offers additional benefits not provided by a pair of closely spaced tees. Viessmann therefore strongly recommends and prefers the use of a low-loss header over closely spaced tees. See page 13 for low-loss header information.
10.2
8.226.8
7.123.4
6.120.1
5.116.7
4.113.4
3.110.0
2.0
1.03.4
0 0
00
500 1000 1500 2000 2500
2.2 4.4 6.6 8.8 11
0
1000
0
4.4
2000 3000
8.8 13.2 17.6 22.0 26.4 30.8 35.2
4000
5000 6000
3000 3500
13.2
7000
15.4
8000 l/h
l/h
GPM
Pressure drop (primary circuit) for Vitodens 200-W, WB2B 80, 105
For sizing an on-site circulation system. Max. flow rate 8000 L/h / 35.2 USGPM
GPM
10
Page 11
Typical System Flow Rates
5
3
6
9
2
9
5
v
1
.
5
System Flow Rates
Table 2.
Model WB2B 19 26 35
∆∆∆∆
t for NG/LPG
Output (NG/LPG)
20ºF rise (GPM) 6.1 8.5 11.4 25ºF rise (GPM) 4.9 6.8 9.1 30ºF rise (GPM) 4.1 5.7 7.6 35ºF rise (GPM) 3.5 4.9 6.5 40ºF rise (GPM) 3.1 4.3 5.7
Table 3.
Model WB2B 45 60
∆∆∆∆
t for NG/LPG
Output (NG/LPG)
20ºF rise (GPM) 14.6 19.4 25ºF rise (GPM) 11.7 15.5 30ºF rise (GPM) 9.7 12.9 35ºF rise (GPM) 8.3 11.1 40ºF rise (GPM) 7.3 9.7
Table 4.
Model WB2B 80 105
∆∆∆∆
t for NG/LPG
Output (NG/LPG)
20ºF rise (GPM) 26.0 35.0 25ºF rise (GPM) 20.8 28.0 30ºF rise (GPM) 17.3 23.3 35ºF rise (GPM) 14.9 20.0 40ºF rise (GPM) 13.0 17.5
Btu/h
61 000 85 000 114 000
Btu/h
Btu/h
146 000 194 000
260 000 350 000
Boiler max. flow rate 1400 L/h (6.2 GPM)
Boiler max. flow rate 3500 L/h (15.4 GPM)
Boiler max. flow rate 8000 L/h (35.2 GPM)
Use standard friction loss method for pipe sizing. Observe boiler maximum and minimum flow rate limitations. If system flow rate exceeds boiler maximum flow rate (as stated above), falls below the minimum flow rate or if system flow rate is unknown, Viessmann strongly recommends the installation of a low-loss header. Once the low-loss header is connected, the built-in low-loss header logic of the Vitodens 200-W boiler ensures the required See page 13 for low-loss header information.
∆∆∆∆
T across the system through the sensory communication between the low-loss header and the boiler.
11
Page 12
Pump Information
5
3
6
9
2
9
5
v
1
.
5
Heating Circuit / Boiler Pumps
Viessmann offers a variety of Grundfos heating circuit / boiler pumps which meet typical Vitodens system installation requirements (see “Heating circuit pump (field supplied)“ or “Boiler pump (field supplied)” in the Installation Examples starting on page 29). See tables below for recommended pumps. Refer to the graphs on page 10 for the proper waterside boiler friction loss calculations.
IMPORTANT
Pump selection must be based on accurate system flow and pressure drop calculations (incl. DHW sizing).
The following pumps have been selected based on boiler heat exchanger head loss and boiler piping to a low-loss header. Before using the following pumps for a DHW tank application, find out the proper pressure drop through the tank, the required temperature difference through the coil and system piping head loss of the domestic hot water.
Table 5.
Model WB2B 19 26 35
Flow rate
20 ºF
∆∆∆∆
t
25 ºF
∆∆∆∆
t
30 ºF
∆∆∆∆
t
35 ºF
∆∆∆∆
t
40 ºF
∆∆∆∆
t
Flow limitation L/h / GPM 1400 / 6.2
Recommended boiler pumps Grundfos 15-58 (3-speed)
6.1 8.5 11.4
4.9 6.8 9.1
4.1 5.7 7.6
3.5 4.9 6.5
3.1 4.3 5.7
Taco 00R
Wilo Star S 21 FX
Table 6.
Model WB2B 45
Flow rate Boiler pressure
20 ºF
∆∆∆∆
t
25 ºF
∆∆∆∆
t
30 ºF
∆∆∆∆
t
35 ºF
∆∆∆∆
t
40 ºF
∆∆∆∆
t
Flow limitation L/h / GPM 3500 / 15.4
Table 7.
Model WB2B 60
20 ºF
∆∆∆∆
t
25 ºF
∆∆∆∆
t
30 ºF
∆∆∆∆
t
35 ºF
∆∆∆∆
t
40 ºF
∆∆∆∆
t
Flow limitation L/h / GPM 3500 / 15.4
14.6 15.8 UPS 26-99FC, 115V, Speed3
11.7 10.0 UPS 26-99FC, 115V, Speed2 UP 26-64F, 115V
9.7 7.5 UPS 26-99FC, 115V, Speed2
8.3 5.8 UPS 26-99FC, 115V, Speed1
7.3 4.2 UPS 26-99FC, 115V, Speed1
Flow rate Boiler pressure
19.4 Not Recommended Not Recommended
15.5 16.7 UPS 26-99FC, 115V, Speed3
12.9 12.6 UPS 26-99FC, 115V, Speed3 UP 26-64F, 115V
11.1 9.2 UPS 26-99FC, 115V, Speed2 UP 26-64F, 115V
9.7 7.5 UPS 26-99FC, 115V, Speed2
drop (ft.)
drop (ft.)
Recommended pump option 1
Grundfos
Recommended pump option 1
Grundfos
Recommended pump option 2
Grundfos
Recommended pump option 2
Grundfos
12
Page 13
Pump and Low-Loss Header Information
5
3
6
9
2
9
5
v
1
.
5
Heating Circuit / Boiler Pumps
Table 8.
Model WB2B 80
20 ºF
∆∆∆∆
t
25 ºF
∆∆∆∆
t
30 ºF
∆∆∆∆
t
35 ºF
∆∆∆∆
t
40 ºF
∆∆∆∆
t
Flow limitation L/h / GPM 8000 / 35.2
Table 9.
Model WB2B 105
20 ºF
∆∆∆∆
t
25 ºF
∆∆∆∆
t
30 ºF
∆∆∆∆
t
35 ºF
∆∆∆∆
t
40 ºF
∆∆∆∆
t
Flow limitation L/h / GPM 8000 / 35.2
Table 10. Sizing of Low-Loss Header in a Residential Single-Boiler Application
Boiler Model
WB2B 19 1 6.1
WB2B 26 1 6.1
WB2B 35 1 6.1
WB2B 45 1 15.4
WB2B 60 1 15.4
WB2B 80 1 35
WB2B 105 1 35
No. of Boilers
Boiler
Max.
Flow Rate
1385
1385
1385
3498
3498
7949
7949
(continued)
Flow rate Boiler pressure
26.0 16.7 UPS 32-160/2, 115V, Speed1 / UPS 26-150F, 115V, Speed 3
20.8 9.2 UPS 26-99FC, 115V, Speed3
17.3 6.5 UPS 26-99FC, 115V, Speed2
14.9 4.8 UPS 26-99FC, 115V, Speed2
13.0 3.4 UPS 26-99FC, 115V, Speed2
Flow rate Boiler pressure
35.0 30.0 UPS 32-160/2, 115V, Speed3
28.0 20.0 UPS 32-160/2, 115V, Speed2 / UPS 26-150F, 115V, Speed 3
23.3 12.5 UPS 32-160/2, 115V, Speed1
20.0 9.0 UPS 26-99FC, 115V, Speed3
17.5 6.4 UPS 26-99FC, 115V, Speed2
Typical System Flow Rates Viessmann
System
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
∆∆∆∆
t *1
drop (ft.)
drop (ft.)
1385
80/60
1931
80/60
2589
80/60
3316
80/60
4406
80/60
5905
120/80
7949
120/80
20
11.0
6.1
Yes
8.5
Yes
11.4
Yes
14.6
Yes
19.4
Yes
26.0
Yes
35.2
Yes
25
13.9
4.9
1108
Optional
80/60
6.8
1544
Yes
80/60
9.1
2071
Yes
80/60
11.7
2653
Optional
80/60
15.5
3525
Yes
80/60
20.8
4724
Yes
120/80
28.0
6359
Yes
120/80
30
16.8
4.1
924
Optional
80/60
5.7
1287
Optional
80/60
7.6
1726
Yes
80/60
9.7
2211
Optional
80/60
12.9
2937
Optional
80/60
17.3
3937
Optional
120/80
23.3
5300
Yes
120/80
Recommended pump
Grundfos
Recommended pump
Grundfos
35
16.1
3.5
792
Optional
80/60
4.9
1103
Optional
80/60
6.5
1480
Yes
80/60
8.3
1895
Optional
80/60
11.1
2518
Optional
80/60
14.9
3374
Optional
120/80
20.0
4542
Optional
120/80
13.4
Optional
80/60
Optional
80/60
1295
Optional
80/60
1658
Optional
80/60
2203
Optional
80/60
13.0
2953
Optional
120/80
17.5
3975
Optional
120/80
40
3.1
693
4.3
965
5.7
7.3
9.7
°F
°C
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
Temp. Sensor Required
Yes
Yes
Yes
Yes
Yes
Yes
Yes
*1
For system t < 20°F use low-loss header sizes for t 20°F.
13
Page 14
Low-Loss Header Information
5
3
6
9
2
9
5
v
1
.
5
Low-Loss Header Application
Table 11. Sizing of Low-Loss Header in a Commercial Multiple-Boiler Application
Boiler Model
WB2B 45 2 15.4
WB2B 45 3 15.4
WB2B 45 4 15.4
WB2B 60 2 15.4
WB2B 60 3 15.4
WB2B 60 4 15.4
WB2B 80 2 35
WB2B 80 3 35
WB2B 80 4 35
WB2B 105 2 35
WB2B 105 3 35
WB2B 105 4 35
No. of Boilers
Boiler Max. Flow Rate
3498
3498
3498
3498
3498
3498
79497015899
7949
7949
79497015899
7949
7949
Total Flow Rate
30.8 6995
46.2 10493
61.6 13991
30.8 6995
46.2
10493
61.6
13991
105
23848
140
31797
105
23848
140
31797
(continued)
Typical System Flow Rates Viessmann
System
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
System Flow Rate
LLH Required LLH Model
∆∆∆∆
t *1
20
11.0
29.2
6632
Yes
120/80
43.8
9948
Yes
160/80
58.4
13264
Yes
200/120
38.8
8812
Yes
160/80
58.2
13219
Yes
200/120
77.6
17625
Yes
200/120
52.0
11810
Yes
200/120
78.0
17716
Yes
200/120
104.0
23621
Yes
250/150
70
15899
Yes
200/120
105
23848
Yes
250/150
140
31797
Yes
300/200
13.9
23.4
5306
Yes
120/80
35.0
7958
Yes
120/80
46.7
10611
Yes
200/120
31.0
7050
Yes
120/80
46.6
10575
Yes
200/120
62.1
14100
Yes
200/120
41.6
9448
Yes
160/80
62.4
14173
Yes
200/120
83.2
18897
Yes
250/150
12719
Yes
200/120
19078
Yes
250/150
112
25438
Yes
250/150
25
56
84
30
16.8
19.5
4421
Yes
120/80
29.2
6632
Yes
120/80
38.9
8843
Yes
160/80
25.9
5875
Yes
120/80
38.8
8812
Yes
160/80
51.7
11750
Yes
200/120
34.7
7874
Yes
160/80
52.0
11810
Yes
200/120
69.3
15747
Yes
200/120
47
10599
Yes
200/120
70
15899
Yes
200/120
93
21198
Yes
250/150
35
16.1
16.7
3790
Yes
120/80
25.0
5685
Yes
120/80
33.4
7579
Yes
120/80
22.2
5036
Yes
120/80
33.3
7554
Yes
120/80
44.3
10071
Yes
160/80
29.7
6749
Yes
160/80
44.6
10123
Yes
200/120
59.4
13498
Yes
200/120
40
9085
Yes
160/80
60
13627
Yes
200/120
80
18170
Yes
200/120
40
13.4°F°C
14.6
3316
Yes
120/80
21.9
4974
Yes
120/80
29.2
6632
Yes
120/80
19.4
4406
Yes
120/80
29.1
6609
Yes
120/80
38.8
8812
Yes
160/80
26.0
5905
Yes
160/80
39.0
8858
Yes
160/80
52.0
11810
Yes
200/120
35
7949
Yes
160/80
53
11924
Yes
200/120
70
15899
Yes
200/120
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
GPM
L/h
Temp.Sensor Required
*2
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
NOTE: for multiple boiler applications when using the the Vitodens 200-W, WB2B boilers, refer to the multiple boiler low-loss distribution
manifold installation instructions.
*1
For system ∆∆∆t < 20°F use low-loss header sizes for ∆∆∆∆t 20°F.
*
2
Low-Loss sensor - standard equipment of the Vitocontrol-S WB2B: for use in multiple boiler applications.
14
Page 15
DHW Production
5
3
6
9
2
9
5
v
1
.
5
Domestic Hot Water Production
Vitodens 200-W boilers can be used in conjunction with the stand-alone DHW storage tanks offered by Viessmann. All Viessmann DHW storage tanks sold in North America are available in “Vitosilver” finish only.
Size and select the DHW storage tank based on the forecasted DHW consumption of the building in question. For further technical information on DHW storage tanks, see the Vitocell-V Technical Data Manuals.
For the connection of a stand-alone DHW tank, installation fittings (field supplied), an external circulating pump for DHW production (field supplied) and a DHW temperature sensor (optional equipment, see Viessmann Price List for order information) are required.
PRV
GC
DS
DR
Fig. 14
Legend
DR Boiler heating return for domestic
hot water production
DS Boiler heating supply for domestic
hot water production HR Heating Return HS Heating Supply BD Boiler Drain BR Boiler Return BS Boiler Supply GC Gas Connection PRV Pressure Relief Valve BF Boiler Fill PG Pressure Gage (not shown) *
1
See page 38 for alternate DHW connection.
HR
HS
BD
Fig. 15
DS
BS
*1DHW Connections
(Field Supplied)
BF
DR
BR
IMPORTANT
An adequately sized precharged expansion tank must be used. See Installation Examples for details.
15
Page 16
DHW Recirculation
5
3
6
9
2
9
5
v
1
.
5
Domestic Hot Water Recirculation
DHW recirculation lines increase the level of comfort and convenience of the domestic hot water supply and reduce water consumption. These advantages directly derive from the immediate availability of domestic hot water at all draw points.
Poor insulation of the DHW recirculation line, however, can result in considerable heat loss. Viessmann therefore recommends that effective insulation be provided and used for DHW recirculation lines of 23 ft. / 7 m in length or longer.
DHW
R
DCW
Fig. 16
Legend
DCW Domestic Cold Water DHW Domestic Hot Water TPV Temperature and Pressure Relief
R DHW Recirculation Line RP DHW Recirculation Pump
Vitocell-V stand-alone DHW storage tank
Valve (on tank - not shown)
RP
DCW
16
Page 17
Wall Mounting
5
3
6
9
2
9
5
v
1
.
5
Models WB2B 19, 26, 35
The Vitodens 200-W, models WB2B 19 to 35 comes with a template, which allows you to easily mark the location of the screws for the mounting bracket and the location of the flue gas pipe on the wall.
A
Legend
A Reference point top edge Vitodens 200-W B Mounting bracket C Vitodens 200-W mounting template
Fig. 17
B
C
2.
1.
2x
3.
1. Loosen the screws at the bottom of the boiler.
2. Remove front enclosure panel.
3. Mount boiler onto the mounting bracket
and connect boiler to the installation fittings.
Fig. 18
17
Page 18
Wall Mounting
5
3
6
9
2
9
5
v
1
.
5
Models WB2B 45, 60, 80, 105
The Vitodens 200-W, models WB2B 45 to105 comes with a template, which allows you to easily mark the location of the screws for the mounting bracket and the location of the flue gas pipe on the wall.
A
Fig. 19
2.
B
C
3.
Legend
A Reference point top edge Vitodens 200-W B Mounting bracket C Vitodens 200-W mounting template
1. Loosen the screws at the bottom of the boiler.
2. Remove front enclosure panel.
3. Mount boiler onto the mounting bracket
and connect boiler to the installation fittings.
1.
2x
Fig. 20
18
Page 19
Condensate Connection/Neutralization Unit
(effluent
)
5
3
6
9
2
9
5
v
1
.
5
Condensate Connection
Install the condensate drain pipe with a suitable gradient. Discharge condensate from the boiler into the drainage system, either directly or (if required) via a neutralization unit (accessory).
IMPORTANT
Pipe ventilation must take place between the siphon trap and the neutralization unit (if applicable).
Condensate Connection for Vitodens 200-W, models WB2B 19, 26, 35
Fig. 21
Condensate Drainage and Neutralization
The condensate formed both in the condensing boiler and in the flue gas pipe must be discharged into the public sewage system in accordance with all applicable local regulations. The condensate produced by a gas-fired heating system has a pH value between 3 and 4.
Some local codes may require the use of a separate neutralization unit to treat the aggressive and corrosive nature of the condensate. With a neutralization unit installed, all condensate from the boiler and the flue gas pipe enters into the neutralization unit where it is treated and released into the public sewage system with a safe pH value of above 6.5.
The use of neutralization granulate (performing the neutralizing process) is dependent on the operation of the heating system. To determine the required refill amount, check granulate level several times during the first year of operation. In some cases one granulate fill may last an entire year.
Condensate Connection for Vitodens 200-W, models WB2B 45, 60
Fig. 22
The condensate discharge outlet to the drainage system connection must be clearly visible. It must be installed with a suitable gradient and provided with a stench trap.
If the condensate outlet of the Vitodens 200-W boiler is lower than the drain, a condensate pump must be used.
Only corrosion-resistant materials must be used for condensate drainage purposes (e.g. braided hose). Do not use galvanized materials or materials containing copper for piping, couplings etc. The condensate drain must have a trap to prevent flue gas leakage.
Please note that other requirements might apply depending on local regulations and/or project-specific details.
Condensate Connection for Vitodens 200-W, models WB2B 80, 105
Fig. 23
It is advisable to contact your local waterworks office (authority responsible for waste water regulations) well before commencing with the installation of the neutralization unit in order to establish details of local regulations that apply.
The following table shows the concentration of (effluent) substances (e.g. heavy metals) contained in the waste water from the Vitodens 200-W condensing boiler.
Table 12.
Condensate (effluent) substances
Lead Cadmium Chromium Copper Nickel Zinc Tin
Values measured
in mg/L
Vitodens 200-W
< 0.01 < 0.005 < 0.01 < 0.01 < 0.01 < 0.05 < 0.05
Contact Viessmann to order a neutralization unit for the Vitodens 200-W boiler. See Viessmann Price List for order information.
19
Page 20
Venting Options / Electrical Connection / Boiler Control
5
3
6
9
2
9
5
v
1
.
5
Venting Options
For an overview of venting options refer to the appendix starting on page NO TAG. For detailed information refer to the Installation Instructions for the Vitodens 200-W, WB2B Venting System.
Fig. 24
Vent Connection, models WB2B 19, 26, 35
Fig. 25
Vent Connection, models WB2B 45, 60, 80,105
(with optional air intake openings on sides)
Electrical Connection
For an overview of the required wiring refer to pages 39 (for WB2B 19 to 60) and 40 (for WB2B 80 and 105).
Power Supply
The Vitodens 200-W is shipped with a Power / Pump Module. The module requires a 120 VAC power supply from a wall receptacle. The module contains a 120/230 VAC step-up transformer to power the Vitodens 200-W with 230 VAC. Refer to the Installation Instructions shipped with the module for wiring details, or reference the “Overview of Electrical Connections” on pages 39 and 40 of this manual.
Power Supply Connection of Accessories
The power supply connection of accessories can be made directly at the boiler control. The connection is activated and deactivated with the system on/off switch. The mixing valve accessory kit and the Vitosolic control (if used) will require a separate 120 VAC power supply from the wall receptacle.
Wire cabling required for:
H outdoor temperature sensor H Vitotronic 200-H, HK1M mixing valve
control
H accessory kit for heating circuit with
mixing valve
H Vitotrol 200 remote control H Vitotrol 300 remote control H remote switching of operating mode H remote disable H alarm output
On-Board Vitotronic 200, HO1 Outdoor Reset Control
The on-board Vitodens menu-driven Vitotronic 200, HO1 control provides the following:
2
1
3
0
0
4
RESET
Boiler temp.
M o
s
140
?F
A
+
Fig. 26
20
+
OK
?
Page 21
Design and Functions
5
3
6
9
2
9
5
v
1
.
5
Boiler Control
Modular Structure
The control unit contains: System on/off switch, override/emission test switch, fixed high limit, adjustable high limit, digital display, micro-computer, adjustment options for switching times, for temperatures during normal and reduced operation, domestic hot water temperature, adjustment options for heating curves, temperature scanning options, built-in diagnostic system and fuses, reset button, analogue pressure display.
Programming Unit
H Illuminated display with plain text support H Adjustment and display of temperatures
and codes
H All settings, main codings and fault
messages shown in plain text
H Holiday program H Party button for switching to ”normal
operation” whenever required
H Energy savings button for lowering the
desired room temperature by approx.
3.6°F / 2°C in normal operation
H Rotary selector for the temperature in
standard mode
H Keys:
- Program selection
- Holiday program
- Party and economy mode
- Temperature for reduced mode
- DHW temperature
- Emissions test function
- Time/date
Boiler-Specific Functions
The control unit adjusts the boiler water temperature (= supply temperature of a direct-connected heating circuit and/or a heating circuit with mixing valve in conjunction with the accessory kit for a heating circuit with mixing valve) automatically and on a continuous basis to individual outdoor temperatures. The control has a DHW temperature controller with DHW priority switching (heating circuit pump off).
Functions
H Outdoor reset control of boiler water
and/or supply temperature
H Electronic maximum temperature limit H Demand-dependent heating circuit pump
and burner OFF control
H Anti-seizing pump protection H Maintenance display H Heating system frost protection H Integral diagnostic system H DHW temperature control with priority
control
H
H Auxiliary function for DHW heating
(short-term heating to a higher temperature, gas fired central heating boiler)
H Adjusting switching times for the DHW
recirculation pump
H 0-10 V external signal input H Boiler pump contol output H Alarm output H Heating circuit pump control output H DHW pump control output H DHW recirculation pump control output
Control Characteristics
PI characteristics with modulating output.
Time Switch
Digital time switch.
H Individual and 7-day program H Automatic daylight savings time
changeover
H Automatic function for DHW heating and
DHW recirculation pump
H Time, day and standard switching times
for space heating, DHW heating and the DHW circulation pump are factory-set
H Switching times are individually
programmable, i.e. up to four switching
periods per day Shortest switching interval: 10 minutes Power backup: 14 days.
Setting the Heating Programs
The heating system frost protection (see frost protection function) applies to all heating programs. You can select the following heating programs wiyh the program keys:
H Heating and DHW H DHW only H Standby mode
External heating program changeover.
Summer Operation
Heating program “ The burner is only activated upon a call for domestic hot water from the DHW storage tank (controlled by DHW tank temperature sensor).
Frost protection
H The frost protection function will be
started when the ouside temperature drops below approx. 34°F / +1°C. With the frost protection function, the heating circuit pump will be switched ON and the boiler water is maintained at a lower temperature of approx. 68°F / 20° C. The DHW tank will be heated to approx. 68°F / +20°C.
H The frost protection function will be
stopped when the outside temperature rises above approx. 37°F / +3°C (default settings).
Technical Data
Rated supply voltage: 120 VAC Rated frequency: 60 Hz Rated current: 12 A Max. ambient temperature
H at operation: 32 to 104ºF
H when storing or
transporting: –4 to +158ºF
Max. operating temp. setting (space heating): Models WB2B 19-60 165ºF / 74ºC Models WB2B 80-105 176ºF / 80ºC DHW production: Models WB2B 19-60 165ºF / 74ºC Models WB2B 80-105 176ºF / 80ºC Setting fixed high limit: 210ºF / 99ºC
Adjustment range of DHW tank set-point temperature: 50 to 154ºF
Adjustment range heating curves
H Heating curve
H slope 0.2 to 3.5
H Heating curve
H shift: –12 to +33ºC
w
0 to 40ºC Installation in living spaces or boiler rooms (standard ambient conditions)
–20 to +70ºC
(not adjustable)
10 to 68ºC
–13 to 40 K
21
Page 22
Boiler Control
5
3
6
9
2
9
5
v
1
.
5
Heating Curve Adjustment (slope and shift)
The control unit regulates the boiler water temperature (= supply temperature of heating circuit without mixing valve) and the supply temperature of the heating circuit with mixing valve (in conjunction with the accessory kit for a heating circuit with mixing valve) according to the outdoor temperature. The boiler water temperature is automatically raised by 0 to 72 F / 0 to 40 K higher than the currently required set supply termperature (in the factory default setting the differential temperature is
14.4 F / 8 K). See Start-up/Service Instructions for coding address “9F” in coding level 2. The supply temperature that is required to achieve a given room temperature depends on the heating system and the thermal insulation of the building that is being heated. The adjustment of the two heating curves is used to match the boiler water temperature and the supply temperature to these conditions. The boiler water temperature is limited upwards by the fixed high limit and the temperature set for the electronic high limit. The supply temperature cannot rise above the boiler water temperature.
Boiler water or
95 35
Fig. 27
ºF / ºC
194
176
158
140
122
104
flow temperature
86
86 30
77 25
Room ­set-point temperature
90
80
70
60
50
40
30
68 20
3,4
50 41 32 23 14 5 -4 -13 -22
60 15
50 10
41 5
ºF ºC
Boiler Temperature Sensor
The boiler temperature sensor is connected at the control unit for weather-responsive operation and is built into the boiler. Max. ambient temperature
H at operation: 32 to 266ºF
H when storing or
transporting: – 4 to+158ºF
DHW Tank Temperature Sensor
Part No. 7179 114
Supplied with: H Cable length approx. 13 ft. / 3.75 m,
ready to plug in
H All pipe connections are field supplied.
Specification
Max. ambient temperature
H at operation: 32 to 194ºF
H when storing or transporting:
3,0
2,8
3,2
0 -5 -10 -15 -20510
2,4
2,6
2,2
Outdoor temperature
–20 to +70ºC
0 to 90ºC
– 4 to+158ºF –20 to+ 70ºC
2,0
1,8
0 to 130ºC
1,6
1,4
1,2
1,0
0,8
0,6
0,4
0,2
-30-25
Outdoor Temperature Sensor
Fig. 28 (dimensions in mm)
Sensor location:
H North or northwest wall of building H 6.6 to 8.2 ft. / 2 to 2.5 m above ground
or in case of a multi-storey building
approx. halfway up the second floor Electrical connection: H 2-wire cable, max. cable length 115 ft. /
35 m with a wire size of min. AWG 16
copper H Cable to the outdoor sensor must not be
laid near line voltage wiring
(120/240 V) Max. ambient temperature at operation, when storing or transporting: –40 to+158ºF
–40 to +70ºC
C
B
A
ºC ºF
Legend
Low temperature heating system, e.g. radiant floor heating Medium temperature heating system, e.g. cast iron radiation, staple-up radiant floor heating High temperature heating system, e.g. fintube radiation, fan coils
22
Page 23
Vitotronic Control Accessories
5
3
6
9
2
9
5
v
1
.
5
Control Accessories
Mixing Valve Actuator Accessory Kit,
Part No. 7133 392
Fig. 29 (dimensions in mm)
Rated voltage: 120 VAC Rated frequency: 60 Hz Rated current: 4 (2) A Power consumption: 4 W Max. ambient temperature
H at operation: 32 to 104ºF
H when storing
H or transporting: –4 to +149ºF
Relay output for heating circuit pump: 4(2) A, 120 VAC Actuator torque: 3 Nm Time of 90 º: 2 minutes
(old version)
0 to 40ºC
–20 to +65ºC
Supply Temperature Sensor
(strap-on sensor,
included with mixing valve actuator accessory kit), Part No. 7133 895
H when storing or transporting: –20 to+70ºC
(old version)
Mixing Valve Actuator Accessory Kit,
Part No. 7837 524 (new version)
Fig. 31 (mm)
The mixing valve actuator is mounted directly on the Viessmann ¾ to 2½“ mixing valve. The mixing valve actuator is a motor-driven control unit. The rotational direction is reversible. The mixing valve actuator comes with a plug-in connector for a heating circuit pump, supply temperature sensor (strap-on sensor with 7 ft. / 2.1 m connecting cable),
supply connecting cable (9 ft. / 2.7 m)
connecting cable ( KM-BUS Expansion Module.
Rated voltage: 120 VAC Rated frequency: 60 Hz Rated current: 4 A
Power consumption: 5W max. ambient temperature
- at operation: 32ºF to 104ºF (0ºC to 40ºC) application in living areas and installation
sites (normal ambient conditions)
-
storage & shipping: -4ºF to 149ºF (-20ºC to 65ºC) Max. relay outputs at 120 VAC for:
- Heating circuit pump 1.0 A
- Mixing valve 0.2 A
9 ft. / 2.7
m) for the
power
and a
Supply Temperature Sensor
Part No. 7183 288 (new version)
LON Communication Module
Part No. 7179 113 Electronic PCB for data exchange with the Vitotronic 200-H, Vitocom 200 and for connecting to a higher level building management system.
LON Connecting Cable
(for data exchange between control units)
Cable length 23 ft / 7m, fully wired
Fig. 33
LON Terminal End Resistor
Part No. 7143 497 To terminate the LON BUS at the first and the last control unit.
KM BUS Expansion Module
Part No. 7133 393 To connect 2 to 9 devices (mixing valve actuator, Vitotrol, input module, etc.) to the single KM BUS connection of the boiler.
Fig. 34 (dimensions in mm)
Specification
Lead lenght 10 ft / 3.0 m,
fully wired
Permissable ambient temperature
- during operation 32 to 104°F 0 to 40°C
- during storage and
transport - 4 to+149°F
-20 to +65°C
Fig. 30 (dimensions in mm)
Installed with a strapping band.
Cable length 19.7 ft. / 6 m, ready to plug in.
Max. ambient temperature
H at operation: 32 to 212ºF
H when storing or transporting:
–4 to+149ºF (–20 to+70ºC)
0 to 100ºC
Fig. 32 (mm)
Immersion temperature sensor
Part No. 7173 488 To capture the low loss temperature
Specification
Lead length 12 ft / 3.75 m,
fully wired
Permissable ambient temperature
- during operation 32 to 194°F
0 to 90°C
- during storage and
transport - 4 to+158°F
-20 to +70°C
23
Page 24
Vitotronic Control Accessories
5
3
6
9
2
9
5
v
1
.
5
Vitotrol 200
Part No. 7450 017
Fig. 35 (dimensions in mm)
KM BUS subscriber The Vitotrol 200 remote control regulates the heating program for one heating circuit and the required set room temperature in standard mode, from any room in the house. The Vitotrol 200 is equipped with backlit heating program selection keys as well as a party and economy key. The fault display shows faults on the control unit. WS function: Installation anywhere in the building. RS function: Installation in the main living room on an internal wall opposite radiators. Never install inside shelf units, recesses, immediately by a door or heat source (e.g. direct sunlight, fireplace, TV set, etc.). The integral room tempearutre sensor captures the actual room temperature and effects any necessary corrections of the supply temperature as well as a rapid heat-up at the start of the heating operation (if appropriately programmed). Connection:
H
2-core lead, length max. 164 ft / 50 m (even if connecting several remote control units)
H Never route this lead immediately next to
230/400 V cables
H LV plug part of the standard delivery
Specification
Power supply via KM BUS Power consumption 0.2 W Protection class III Max. ambient temperature
H at operation: 32 to 104ºF
H when storing
H or transporting: –4 to+149ºF
Set room temp. range 50 to 86ºF
The set room temperature for reduced mode is adjusted at the control unit.
0 to 40ºC
–20 to +65 ºC
10 to 30ºC adjustable from 37 to 74ºF
3 to 23ºC or 63 to 99ºF 17 to 37ºC
Vitotrol 300
Part No. 7248 907
Fig. 36 (dimensions in mm)
KM BUS subscriber The Vitotrol 300 remote control regulates the required set room temperature for one heating circuit in standard and reduced mode, the heating program and the switching times for central heating, DHW heating and the DHW circulation pump. The Vitotrol 300 provides a backlit display as well as backlit heating program keys, a party and economy key, automatic summer/winter time changeover, keys for holiday program, day and time. WS function: Installation at any point in the building. RS function: Installation in the main living room on an internal wall opposite radiators. Never install inside shelf units, niches, immediately by a door or heat source (e.g. direct sunlight, fireplace, TV set, etc.) The integral room temperature sensor captures the actual room tempeture and affects any necessary correction of the supply temperature as well as a rapid heat-up at the start of the heating operation (if suitable encoded). Connection:
H
2-core lead, length max. 164 ft / 50 m (even if connecting several remote control units)
H Never route this lead immediately next to
230/400 V cables
H LV plug part of the standard delivery
Specification
Power supply via KM BUS Power consumption 0.5 W Protection class III Max. ambient temperature
H at operation: 32 to 104ºF
H when storing
H or transporting: –4 to+149ºF
Set room temp. range for standard mode 50 to 86ºF
for reduced mode 37 to 99ºF
0 to 40ºC
–20 to +65ºC
10 to30ºC adjustable from 37 to 74ºF
3 to 23ºC or 63 to 99ºF 17 to 37ºC
3 to 37ºC
Room Temperature Sensor,
Part No. 7133 379
Fig. 37 (dimensions in mm)
Separate room temperature sensor as supplement to the Vitotrol 200 and 300; to be used if the the Vitotrol 200 or 300 cannot be installed inside the main living room or in a suitable position where the unit can capture and adjust the temperature. Installation in the main living room on an internal wall opposite radiators. Never install inside shelf units, recesses, immediately by a door or heat source (e.g. direct sunlight, fireplace, TV set, etc.). Connect the room temperature sensor to the Vitotrol 200 or 300. Electrical connection: H 2-wire cable with a wire size of min. AWG
18 copper
H The cable length between the control unit,
remote control unit and room temperature
sensor must not exceed 98 ft./30 m Max. ambient temperature H at operation: 32 to 104ºF
0 to 40ºC
H when storing
H or transporting: –4 to+149ºF
–20 to +65ºC
24
Page 25
Accessories for Vitodens 200-W
5
3
6
9
2
9
5
v
1
.
5
Boiler Accessories
Neutralization Unit for Single-Boiler Applications
with neutralizing granulate
for models WB2B 19, 26, 35 Part No. 7134 231
310
Fig. 38 (dimensions in mm)
for models WB2B 45, 60 Part No. 7134 232
400
Fig. 39 (dimensions in mm)
for models WB2B 80, 105 Part No. 7264 769
50
DN 40
Ø 145
DN 40
400
476
300
Ø 145
Fuel Conversion Label Kit (NG>LPG)
Part No. 7428 427 (included in boiler technical literature set) The Vitodens 200-W, WB2B boiler comes factory set for operation with natural gas. All WB2B models can be field converted to operate with liquid propane gas (as well as back to natural gas as required). The kit includes instructions and labels for field conversion.
185
90
Low-Loss Header
–Type 80/50 Part No. 7134 230 (max. flow rate 17.6 GPM / 4 m3/h) –Type 120/80 Part No. 7134 244 (max. flow rate 35.2 GPM / 8 m3/h) –Type 160/80 Part No. 7134 293 (max. flow rate 44 GPM / 10 m3/h ) –Type 200/120 Part No. 7134 294 (max. flow rate 80 GPM / 18 m3/h )
Fig. 41
When used in conjunction with the Vitodens 200-W boiler, the low-loss header acts as hydraulic break, decoupling boiler and system circuits from each other. It is recommended to use the low-loss header in applications in which the total system flow rate exceeds the maximum (or minimum) boiler flow rate. For maximum boiler flow rates, see pages 10 and 11 in this manual. Viessmann strongly recommends the use of a low-loss header in cases where the system head and flow rates are unknown.
*1
*1
Fig. 40 (dimensions in mm)
Neutralization Pellets
for models WB2B 19, 26, 35, 45, 60 Part No. 9524 670 2 x 1.3 kg for refill or replacement purposes
for models WB2B 80, 105 Part No. 9521 702 8 kg for refill or replacement purposes
*1
Floor-mounted version (typically used for multiple-boiler installations).
25
Page 26
Boiler Accessories
5
3
6
9
2
9
5
v
1
.
5
Accessories for Vitodens 200-W
(continued)
Low-Loss Header (continued)
The temperature sensor connection [TS] typically located at the top of the low-loss header ensures low return temperatures to the Vitodens 200-W boiler at all times, increasing operational efficiency. In addition, the low-loss header helps eliminate air and debris [D] from the heating system. See figures on the right for an illustration of the principle of operation.
The low-loss header is available in the following sizes. Select the size based on the maximum system flow rate of your application.
Table 13.
Model No. Max. system flow rate
Type 80/50 17.6 GPM / 4 m3/h
Type 120/80 35.2 GPM / 8 m3/h
*
Type 160/80
1
44 GPM / 10 m3/h
Type 200/120*180 GPM / 18 m3/h
*1
Floor-mounted version (typically used for multiple-boiler installations).
BS
BR
Fig. 42
SC
TS
BY
Low-loss header design (Type 80/50 or 120/80)
AB
SW
SS
SR
DV
Legend
AB Air Bleed BR Boiler Return BS Boiler Supply BY Bypass (with laminar flow) D Debris and/or air DV Drain Valve SC Sensor Cable SR System Return SS System Supply TS Viessmann Temperature Sensor SW Sensor Well
IMPORTANT
Use only a Viessmann supplied temperature sensor. Do not use any other manufacturer’s temperature sensor.
D
T1
V
T2
Fig. 43
primary
bypass
Principle of Operation
Legend
T1 Boiler supply temperature T2 Boiler return temperature T3 System supply temperature T4 System return temperature V
primary
V
secondary
V
bypass
T3
Q
primary
Q
secondary
V
V
T4V
secondary
primary
T1 > T3
Boiler circuit flow rate Heating circuit flow rate Bypass flow rate Heat supplied by boiler Heat consumed by system
< V
secondary
T2 = T4 Q
primary
= Q
secondary
T1 ± 167°F / 75°C V
secondary=Vprimary+Vbypass
T4
IMPORTANT
When installing a low-loss header, the system mixed supply temperature (T3) must be calculated as follows:
T3=
T1 × V
primary
V
secondary
+T4 V
bypass
26
Page 27
Standard Equipment
5
3
6
9
2
9
5
v
1
.
5
Boiler Standard Equipment / Combustion Management System
The Vitodens 200-W gas-fired condensing boiler with Inox-Radial heat exchanger, modulating MatriX cylinder burner for liquid propane gas and natural gas (available on all models), comes standard with:
H pressure gage H installation fittings with 30 psig pressure
relief valve and air vent (no air vent for models WB2B 80 and 105)
H boiler control unit with outdoor
temperature sensor, power/pump module
The boiler comes prewired and fully piped internally for field connections and
Venting material (coaxial) is to be supplied
by Viessmann only. Side wall vent installations must include Viessmann protective screen!
– Enclosure finish:
black steel, powder-coated white
– The Vitodens 200-W comes ready for use
with natural gas and can be fuel
converted to liquid propane gas in the field.
- Power/Pump module
Lambda Pro Combustion Management System
The combustion management system utilizes the physical correlation between the level of the ionization current and the air factor λ. For all gas qualities, the maximum ionization current results with air factor 1. The ionization signal is evaluated by the combustion management system, and the air factor is adjusted to between λ=1.24 and 1.44. This range provides for an optimum combustion quality. Thereafter, the electronic gas valve regulates the required gas volume based on the prevailing gas quality. To check the combustion quality, the CO content or the O2content of the flue gas is measured. The actual values enable the prevailing air factor to be determined. The relationship between the CO2or O2content and air factor λ is illustrated in the table below.
prewired.
2
Wall mounting componentry
The following wall mounting components are supplied with the Vitodens 200-W boiler:
H Mounting bracket H Mounting bolts H Installation fittings H Screws for mounting bracket on
– wood studs (2” x 4”) – metal studs – brick/concrete wall
To achieve an optimum combustion control, the system regularly performs an automatic self-calibration; also after a power failure (shutdown). For this, the combustion is briefly regulated to max. ionization current (equals air factor λ=1). The automatic calibration is performed shortly after the burner starts and lasts approx. 5 s. During the calibration, higher than normal CO emissions may occur briefly. The combustion management system can also be calibrated manually, e.g. after maintenance or service work (coding address “85”, see Start-up/Service Instructions).
Table 14. Air factor λ - CO2/O2content
Air factor λ O2content (%) CO2content (%) for natural gas CO2content (%) for liquid propane gas
1.24 4.4 9.2 10.9
1.27 4.9 9.0 10.6
1.30 5.3 8.7 10.3
1.34 5.7 8.5 10.0
1.37 6.1 8.3 9.8
1.40 6.5 8.1 9.6
1.44 6.9 7.8 9.3
The Vitodens 200-W, WB2B boilers come equipped with Lambda Pro, the industry’s first intelligent combustion management system. The boiler adjusts automatically to any gas type and quality without the need for a fuel conversion kit.
27
Page 28
Installation Examples
5
3
6
9
2
9
5
v
1
.
5
Installation Examples
Please note that in the following piping layout examples all pumps are field supplied.
IMPORTANT
The examples on the following pages depict possible piping layouts of the Vitodens 200-W boiler equipped with Viessmann System Technology. For boiler and tank combinations, please install only feasible combinations listed in the Viessmann Price List.
Please note that the following examples are simplified conceptual drawings only! Piping and necessary componentry must be field verified. A low water cut-off (LWCO) must be installed where required by local codes. Proper installation and functionality in the field is the responsibility of the heating contractor.
WARNING IMPORTANT
If a DHW storage tank other than a Viessmann Vitocell 100 or 300 tank is used, the installer must verify proper operation of the Viessmann DHW tank temperature sensor with the original manufacturer of the tank. Viessmann strongly recommends the installation of a temperature tempering valve in the DHW supply line.
DHW supply and return piping between boiler DHW connections and the Viessmann DHW tank connections, shall be a minimum of 1” nominal pipe diameter (for models WB2B 19 to 35) or 1¼(for models WB2B 45 to105) DHW connection outlet sizes provided on the boiler and the DHW tank). This will ensure the residual head of the field supplied pump is fully utilized to overcome the resistance of the DHW heat exchanger coil and to provide sufficient water flow to the boiler heat exchanger. In non-Viessmann DHW tank applications, perform, in addition to the above, accurate calculations for DHW tank coil pressure drop versus boiler pump (field supplied) residual head to ensure sufficient water flow to the boiler heat exchanger. Failure to heed the above instructions may cause boiler short-cycling and inadequate DHW supply.
28
Page 29
System Layout 1
I
J
5
3
6
9
2
9
5
v
1
.
5
Vitodens 200-W, WB2B with a direct-connected heating circuit
1
Installation Examples
B
G
L
TPV
A
AV
PRV
H
5
M
K
J
C
D
E
F
Fig. 44
Legend AV Air vent (models WB2B 19 to 60 only) PRV Pressure relief valve TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with Vitotronic 200, HO1 outdoor reset control Outdoor temperature sensor Remote control Vitotrol 300 (optional) Heating circuit Heating circuit pump DHW circulating pump sA DHW storage tank DHW tank temperature sensor Expansion tank Flow check valve DHW recirculation pump sK Power/Pump module
M Optional purge tee (field supplied)
I
Installation of ...
H radiator heating circuit (high-temp. circuit) H DHW production
... with the following flow conditions:
The flow rate of the heating circuit is less than the maximum possible water flow rate of the Vitodens 200-W WB2B boiler (see page 10 for maximum water flow rate of boiler).
The use of a low-loss header is strongly recommended if the maximum water flow rate in the application concerned exceeds the values shown in the applicable table on page 11, or if the system flow rates are unknown. The low-loss header is available as accessory part.
See following pages for installation examples with a low-loss header.
IMPORTANT
DHW circulating pump must pump into the Vitodens 200-W boiler (as illustrated).
29
Page 30
Installation Examples
I
J
I
5
3
6
9
2
9
5
v
1
.
5
System Layout 2
Vitodens 200-W, WB2B with a direct-connected heating circuit and low-loss header
1
B
L
A
C
G
PRV
TPV
H
5
N
K
F
Fig. 45
Legend AV Air vent (models WB2B 19 to 60 only) PRV Pressure relief valve TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with Vitotronic 200, HO1 outdoor reset control Outdoor temperature sensor Remote control Vitotrol 300 (optional) Heating circuit Boiler pump DHW circulating pump sA DHW storage tank DHW tank temperature sensor Expansion tank Flow check valve DHW recirculation pump sK Power/Pump Module
M Low-loss header N Optional purge tee (field supplied) O Viessmann temperature sensor for
low-loss header
AV
J
E
5
O
M
P
I
P Heating circuit pump
Installation of ...
H radiator heating circuit (high-temp. circuit) H DHW production
... with the following flow conditions: The flow rate of the heating circuit is greater than the maximum possible water flow rate of the Vitodens 200-W WB2B boiler (see page 10 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended if the maximum water flow rate in the application concerned exceeds the values shown on page 11, or if the system flow rates are unknown. The low-loss header is available as accessory part.
20A
D
IMPORTANT
Please note location of expansion tank and flow check valveJ.
IMPORTANT
DHW circulating pump must pump into the Vitodens 200-W WB2B boiler (as illustrated).
IMPORTANT
DHW circulating pump must pump into the Vitodens 200 boiler (as illustrated).
30
Page 31
System Layout 3
I
J
5
3
6
9
2
9
5
v
1
.
5
Vitodens 200-W, WB2B with...
– DHW storage tank – one heating circuit with mixing valve and system separation
Installation Examples
Fig. 46
AV
N
1
2
PRV
Y
F1
J
PRV
TPV
F2
5
M
Y
O
I
P
Y
Legend AV Air vent (WB2B models 19 to 60 only) PRV Pressure relief valve TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with Vitotronic 200, HO1 outdoor reset control Outdoor temperature Remote control Vitotrol 300 (optional) Underfloor heating circuit Mixing valve temperature sensor
F1
Heating circuit pump
F2
Heating circuit pump located upstream of heat exchanger (see IMPORTANT note to the right) Plate heat exchanger for system separation Accessory kit for heating circuit with mixing valve DHW circulating pump sA DHW storage tank DHW tank temperature sensor Expansion tank
M DHW recirculation pump sK N Power/Pump module O Optional purge tee (field supplied) P Flow check valve
Installation of ...
H underfloor heating circuit with 3-way
mixing valve and system separation
(low-temp. circuit) H DHW production ... with the following flow conditions: The flow rate of the heating circuit is less than the maximum possible water flow rate of the Vitodens 200-W WB2B boiler. See page 10 for maximum water flow rate of the Vitodens 200-W WB2B boilers. The use of a low-loss header is recommended if the system water flow rate is unknown. The low-loss header is available as accessory part.
See following pages for installation examples with a low-loss header.
IMPORTANT
System separation is required of underfloor heating systems employing non-oxygen diffusion barrier tubing. All components on the secondary side of the heat exchanger must be made of corrosion-resistant materials.
IMPORTANT
DHW circulating pumpImust pump into the Vitodens 200-W WB2B boiler (as illustrated).
IMPORTANT
Sizing of field-supplied pumpF2is critical for proper boiler operation in this system layout. See page 10 for the supply head pressure drop of the boiler. An undersized pump may cause short-cycling and/or improper operation of the boiler. Viessmann STRONGLY recommends using a low-loss header and a boiler pump in this system layout.
31
Page 32
Installation Examples
I
J
5
3
6
9
2
9
5
v
1
.
5
System Layout 4
Vitodens 200-W, WB2B with...
– DHW storage tank – one direct-connected heating circuit – one heating circuit with a mixing valve
O
A
B
1
C
G
2
D
E
I
TPV
J
5
M
N
Q
M
Fig. 47
Legend AV Air vent (WB2B models 19 to 60 only) PRV Pressure relief valve TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with Vitotronic 200, HO1 outdoor reset control Outdoor temperature sensor Remote control Vitotrol 300 (optional) Under floor heating circuit Radiator heating circuit Heating circuit pump Mixing valve temperature sensor Accessory kit for heating circuit with mixing valve Domestic hot water storage tank DHW tank temperature sensor Expansion tank Optional purge tee (field supplied) DHW supply and return piping DHW recirculation pump sK
O Power/Pump module P Boiler pump Q DHW circulating pump sA R Flow check valve
AV
PRV
V
L
K
Installation of different heating circuits...
H radiator heating circuit (high-temp. circuit) H under floor heating circuit with 3-way
mixing valve (low-temp. circuit) H DHW production ... with the following flow conditions:
1. The water flow rate (output) of the radiator heating circuit is at least 30% greater than that of the under floor heating circuit.
2. The total flow rate of the two heating circuits is less than the maximum possible water flow rate of the Vitodens 200-W WB2B boiler (see page 10 for max. water flow rate). The use of a low-loss header is strongly recommended if the maximum water flow rate in the application concerned exceeds the values shown on page 11, or if the system flow rates are unknown. The low-loss header is available as accessory part.
R
P
H
F
See following pages for additional installation examples with a low-loss header.
The 3-way mixing valve, built-in to achieve the low-temperature level of the under floor heating circuit, is controlled by an accessory
kit for a heating circuit with mixing valve.
IMPORTANT
DHW circulating pump Q must pump into the Vitodens 200-W WB2B boiler (as illustrated).
32
Page 33
System Layout 5
I
J
5
3
6
9
2
9
5
v
1
.
5
Vitodens 200-W, WB2B with...
– DHW storage tank – one heating circuit with mixing valve – one heating circuit without mixing valve and low-loss header
O
A
B
Installation Examples
1
C
G
2
D
E
I
TPV
J
5
M
N
Q
M
Fig. 48
Legend AV Air vent (WB2B models 19 to 60 only) PRV Pressure relief valve TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with Vitotronic 200, HO1 outdoor reset control Outdoor temperature sensor Remote control Vitotrol 300 (optional) Under floor heating circuit Radiator heating circuit Heating circuit pump
F1
Heating circuit pump Mixing valve temperature sensor Kit for heating circuit with mixing valve Domestic hot water storage tank DHW tank temperature sensor Expansion tank Optional purge tee (field supplied) DHW supply and return piping DHW circulating pump sK
20A
AV
PRV
T
L
K
Q DHW circulating pump sA R Low-loss header S Viessmann temperature sensor for
low-loss header
T Flow check valve
Installation of different heating circuits...
H radiator heating circuit (high-temp. circuit) H under floor heating circuit with 3-way
mixing valve (low-temp. circuit) H DHW production ... with the following flow conditions: The total flow rate of the two heating circuits is greater than the maximum possible water flow rate of the Vitodens 200-W WB2B boiler (see page 11 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended. The low-loss header is available as accessory part.
P
5
S
R
H
F
The 3-way mixing valve, built-in to achieve the low-temperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with mixing valve.
F1
IMPORTANT
Please note location of expansion tank and flow check valve T.
IMPORTANT
DHW circulating pump Q must pump into the Vitodens 200-W WB2B boiler (as illustrated).
33
Page 34
Installation Examples
I
J
5
3
6
9
2
9
5
v
1
.
5
System Layout 6
Vitodens 200-W, WB2B with...
– DHW storage tank – two heating circuits with a mixing valve and low-loss header
1
B
F
2
C
G
I
Q
TPV
5
O
P
A
AV
PRV
J
T R
L
5
N
E
D
H
F
2
D
E
S
O
Fig. 49
Legend AV Air vent (WB2B models 19 to 60 only) PRV Pressure relief valve TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with Vitotronic 200, HO1 outdoor reset control Outdoor temperature sensor Remote control Vitotrol 300 (optional) Under floor heating circuit Heating circuit pumps Mixing valve temperature sensor Accessory kit for heating circuit with mixing valve Vitotronic 200-H, HK1M with LON communication module DHW storage tank DHW tank temperature sensor Expansion tank Optional purge tee (field supplied) for easier air removal Low-loss header Viessmann temperature sensor for low-loss header
O DHW supply and return piping P DHW circulating pump sK Q Power/Pump Module R Boiler pump
K
*1
M
S DHW circulating pump sA T Flow check valve
Installation of different heating circuits...
H two heating circuits with 3-way mixing
valve (low-temp. circuit) H DHW production ... with the following flow conditions: The total flow rate of the two heating circuits is greater than the maximum possible water flow rate of the Vitodens 200-W WB2B boiler (see page 11 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended. The low-loss header is available as accessory part.
The 3-way mixing valve, built-in to achieve the low-temperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with mixing valve
. The second under floor heating circuit is supplied by a field supplied circulation controlled by an accessory kit or a Vitotronic 200-H, HK1M mixing valve
control . If more than two heating circuits with mixing valves are to be connected, they can be controlled by a Vitocontrol multi-boiler control. Contact your local Viessmann Technical Sales Representative for details.
*1
Requires...
-
LON communication module 200-H HK1M
- Boiler LON communication module
- LON cable
- End resistors
IMPORTANT
Please note location of expansion tank and flow check valve T.
IMPORTANT
DHW circulating pump S must pump into the Vitodens 200-W WB2B boiler (as illustrated).
34
Page 35
System Layout 7
I
J
I
5
3
6
9
2
9
5
v
1
.
5
Vitodens 200-W, WB2B with...
– direct-connected heating circuit – one heating circuit with system separation
R
J
TPV
K
5
N
O
Q
PRV
V
M
A
AV
S
P
B
Installation Examples
1
C
2
G
I
D
E
N
Fig. 50
Legend
AV Air vent (WB2B models 19 to 60 only) PRV Pressure relief valve TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with Vitotronic 200, HO1 outdoor reset control Outdoor temperature sensor Remote control Vitotrol 300 (optional) Under floor heating circuit Heating circuit pump Plate heat exchanger for system separation Heating circuit pump Mixing valve temperature sensor Accessory kit for heating circuit with mixing valve DHW storage tank DHW tank temperature sensor Expansion tanks Optional purge tee (field supplied) DHW supply and return piping
O DHW recirculation pump sK P Boiler pump Q DHW circulating pump sA R Power/pump module S Flow check valve
L
Installation of different heating circuits...
H radiator heating circuit (high-temp. circuit) H under floor heating circuit with 3-way
mixing valve (low-temp. circuit) H DHW production ... with the following flow conditions: The total flow rate of the two heating circuits is less than the maximum possible water flow rate of the Vitodens 200-W WB2B boiler (see page 11 for maximum water flow rate of boiler). The use of a low-loss header is strongly recommended if the maximum water flow rate in the application concerned exceeds the max. boiler flow rate, or if the system flow rates are unknown. The low-loss header is available as accessory part.
The 3-way mixing valve, built-in to achieve the low-temperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with mixing valve
. The boiler pump supplies the
radiator heating circuit and the plate heat exchanger for system separation.
F
IMPORTANT
The pressure drop (secondary circuit) of the plate heat exchanger must be less/equal to the pressure drop of the 3-way mixing valve. This must be taken into account when sizing the plate heat exchanger.
IMPORTANT
DHW circulating pump Q must pump into the Vitodens 200-W WB2B boiler (as illustrated).
35
Page 36
Installation Examples
I
J
O
P
5
3
6
9
2
9
5
v
1
.
5
System Layout 8
Vitodens 200-W, WB2B with...
– DHW storage tank – low-loss header – multiple heating circuits with mixing valves
1
B
P
A
AV
M
PRV
TPV
L
5
Q
O
C
5
I
D
H H H
2 2
E E E
F F
G
2
G
F
G
J
K
Fig. 51
When designing a system as illustrated above, please contact your local Viessmann Sales Representative for assistance.
Legend AV Air vent (WB2B models 19 to 60 only) PRV Pressure relief valve TPV Temperature and pressure relief valve
Vitodens 200-W WB2B boiler with Vitotronic 200, HO1 outdoor reset control Outdoor temperature Boiler pump Vitocontrol or Vitotronic 200-H,
*1
HK1S Mixing valve temperature sensor Heating circuit pumps Accessory kit for heating circuit with mixing valve Heating circuits with mixing valves Viessmann temperature sensor for low-loss header Low-loss header DHW circulating pump sA DHW tank temperature sensor
*2
Q Flow check valve
*1
*2
N
DHW storage tank Expansion tank DHW recirculation pump sK Power/Pump module
Contact your local Sales Representative
for details.
Vitotronic 200-H, HK1M mixing valve control with LON communication module can be used instead of the accessory kit and Vitocontrol.
IMPORTANT
Please note location of expansion tank and flow check valve Q.
IMPORTANT
Pumps and must pump into the Vitodens 200-W WB2B boiler (as illustrated).
36
Page 37
System Layout 9
5
3
6
9
2
9
5
v
1
.
5
Multiple (up to four) Vitodens 200-W, models WB2B 45 to 105 with...
– multiple heating circuits with mixing valves – low-loss header
Vitocontrol-S
Installation Examples
Boiler 1 Boiler 2
PRV
TPV
5
DHW Tank
Fig. 52
When designing a multiple Vitodens system as shown above, please reference applicable multiple Vitodens technical documentation, and contact your local Viessmann Sales Representative for further assistance.
PRV
Boiler 3 Boiler 4
PRV
PRV
Common
Supply Temperature Sensor
5
Low-Loss Header
M
M
IMPORTANT
This installation example depicts a possible piping layout for multiple Vitodens 200-W, WB2B boilers equipped with Viessmann System Technology. Please note that this example is based on a simplified conceptual drawing only! Piping and necessary componentry must be field verified. A low water cut-off (LWCO) must be installed where required by local codes. Proper installation and functionality in the field is the responsibility of the heating
contractor.
WARNING
If a DHW storage tank other than a Viessmann Vitocell 100 or 300 tank is used, the installer must verify proper operation of the Viessmann DHW tank temperature sensor with the original manufacturer of the tank. Viessmann strongly recommends the installation of a temperature tempering valve in the DHW supply line.
37
Page 38
Installation Examples
5
3
6
9
2
9
5
v
1
.
5
The following piping diagram reflects an alternative connection for the DHW tank only and applies to system layouts 2, 5, 6 and 8. The boiler control pump logic function must be programmed in the Start-up/Service Instructions.
1
2
TPV
.
Fig. 53
5
PRV
M
5
*
Alternative location of the expansion tank
*
*Note:
When using a low loss header in the system, the DHW connections can be made downstream of the low loss header. See Vitodens 200-W WB2B Start-up/Service Instructions for applicable system coding information (see coding level 2): 00: ... A2: ... 5b: ...
38
Page 39
Overview of Electrical Connections, Models WB2B 19, 26, 35, 45 and 60
5
3
6
9
2
9
5
v
1
.
5
Wiring Diagram
MAIN POWER SUPPLY
120V,60HZ, 12A
L2 L1 P1 P2
A
--TYPICAL
SAFETY DEVICE
LOW WATER CUT--OFF
N
G
LON
L
MAIN DISCONNECT SWITCH
120VAC WALL RECEPTACLE
120/230 Transformer
Vitotronic 050
HK1M
Power/Pump module
NL
L2
L1 G N
40
M M
M
120VAC
120VAC
DHW
SYSTEM
PUMP
PUMP
2
145 145
1 20 40
202120A40
202120A
120VAC
BOILER
PUMP
31 2
31 2
143
NL
NLNLNL
50
50
120VAC
FAULT
ALARM
OUTPUT
145
1 2 3 1 2 3 1 2 3
28
L G N
M
120VAC
DHW
RE--CIRC.
PUMP
EXTERNAL
DEMAND
L
N
144
-- +
EXTERNAL
SIGNAL
0--10V
31 2
31 2
145
145144143
230 VAC
LON
X1
KMK1KMK2
X1
A8
Fig. 54
Legend
! Outdoor Temperature Sensor ? Flow Temp. Sensor/Low-Loss
Header
% DHW Temperature SensorBoiler Pump
20A
System Pump
sA DHW Pump sK DHW Recirculation PumpPower Suppl
LON
X2
5
X 7
4321
X 8
X9.3
X9.4
X 9
X11 LON KMK
X4
Boiler Control Board GC130
Fault Alarm Output aVD External Blocking Terminals 2-3
External Demand Terminals 1-2 External Heating Program Changeover Terminals 1-2 (Allocation of this function is set via Coding Address 91.)
aVF External 0-10 V Signal
X3
1234567
40962035100
L Low water cut-off (field supplied) M Power/Pump Module
A1 Main PCB (GC130 Ignition Module) A6 Coding Card A7 Connection Adaptor A8 LON/Cascade Communication
Module(Accessory)
X Electrical Interfaces
aVG KM BUS to Power/Pump Module /
Accessories
39
Page 40
Wiring Diagram
5
3
6
9
2
9
5
v
1
.
5
Overview of Electrical Connections, Models WB2B 80 and 105
MAIN POWER SUPPLY
L2 L1 P1 P2
A
--TYPICAL
SAFETY DEVICE
LOW WATER CUT--OFF
120V,60HZ, 12A
N
L
G
LON
MAIN DISCONNECT SWITCH
120VAC WALL RECEPTACLE
120/230 Transformer
Vitotronic 200--H
HK1M
Power/Pump module
NL
L2
L1 G N
40
M M
M
120VAC
120VAC
DHW
SYSTEM
PUMP
PUMP
2
145 145
1 20 40
202120A40
202120A
120VAC
BOILER
PUMP
31 2
31 2
143
NL
NLNLNL
145
50
50
120VAC
FAULT ALARM OUTPUT
1 2 3 1 2 3 1 2 3
28
L G N
M
120VAC
DHW
RE--CIRC.
PUMP
EXTERNAL
DEMAND
L
N
144
-- +
EXTERNAL
SIGNAL
0--10V
31 2
31 2
145
145144143
230 VAC
LON
X1
X1
LON
X2
KMK1KMK2
1
432
X 7
A8
Fig. 55
Legend
! Outdoor Temperature Sensor ? Flow Temp. Sensor/Low-Loss Header % DHW Temperature SensorBoiler Pump
20A
System Pump
sA DHW Pump sK DHW Recirculation PumpPower Supply
5
X4
X8.10
X8.11
X 8
X 9
X11
LON
KMK
Boiler Control Board GC131
X3
Fault Alarm Output aVD External Blocking Terminals 2-3
External Demand Terminals 1-2 External Heating Program Changeover Terminals 1-2 (Allocation of this function is set via Coding Address 91.)
aVF External 0-10 V Signal aVG KM BUS to Power/Pump Module /
Accessories
1234567
40962035100
L Low water cut-off (field supplied) M Power/Pump Module
A1 Main PCB (GC131 Ignition Module) A6 Coding Card A7 Connection Adaptor A8 LON/Cascade Communication
Module (Accessory)
X Electrical Interfaces
40
Page 41
System Design Considerations
5
3
6
9
2
9
5
v
1
.
5
IN THE COMMONWEALTH OF MASSACHUSETTS...
-this product shall be installed by a licensed plumber or gas fitter.
-the flexible connector (if used) cannot exceed 36”.
-any level type shutoff used must be of tee handle type.
Installation Examples
Boiler location
As a direct vent appliance, the Vitodens 200-W can be installed for room air independent operation (sealed combustion) regardless of size and ventilation method of the room in which it is located. The Vitodens 200-W can be installed, for example, in the main living area of a house, in non-ventilated utility rooms, cupboards, closets and alcoves with no clearance required from combustible materials, as well as in attics with a direct outlet for the flue gas/fresh air system. Follow all local and national codes.
Flue gas system
Viessmann PPS (Polypropylene) concentric flue gas/fresh air systems for room air independent operation (sealed combustion) and side wall venting are tested to ANSI Z21.13 - CSA 4.9 - 2000 standards and are certified together with the Vitodens 200-W boiler as a constructional unit. The Vitodens 200-W boiler may also be vented vertically, using an AL29-4C® special stainless steel, single-wall, room air dependent venting system (UL listed for category IV). For a more detailed description of the direct vent and single-wall vent system, please refer to the Vitodens 200-W Venting System Installation Instructions.
Flue gas temperature protection
Flue pipes used for the Vitodens 200-W are suitable for max. flue gas temperatures of up to 230°F / 110°C.
No flue gas temperature protection is required as the maximum permissible flue gas temperature is not exceeded in any operating condition or in the event of malfunctioning.
Low water cut-off
A low water cut-off may be required by local codes. If the boiler is installed above the radiation level, a low water cut-off device of approved type must be installed in all instances. An approved type low water cut-off device must be provided by the heating contractor. Do not install an isolation valve between the boiler and the low water cut-off.
System layout
H The max. boiler water temperature for
space heating and DHW production is –165°F / 74°C for models WB2B 19 to 60 or –176°F / 80°C for models WB2B 80 and105. To minimize distribution losses, Viessmann recommends that the heating and domestic hot water systems be based on a maximum boiler supply temperature of 158°F / 70°C.
H Due to the low return temperatures
required for gas condensing, no mixing valves should be used in the heating circuit whenever possible. If mixing valves are required, e.g. for multi-circuit systems or underfloor heating systems, only 3-way mixing valves must be used.
Do not use 4-way mixing valves with condensing boilers.
Water connections
Vitodens 200-W boilers can be used in any fully pumped hot water heating system. Minimum system pressure is 0.8 bar/12 psig.
Chemical corrosion protection products
Corrosion does not typically occur in sealed heating systems which have been correctly installed and are correctly operated. Many manufacturers of plastic pipes recommend the use of chemical additives. In this case, only those commercially available corrosion protection products approved for boilers with domestic hot water heating via single-wall heat exchangers (instantaneous plate heat exchangers or DHW tanks) must be used.
Underfloor heating systems
For underfloor heating systems Viessmann recommends the use of plastic tubing with an oxygen diffusion barrier in order to prevent the diffusion of oxygen through tubing. If plastic tubing without an oxygen diffusion barrier is used in underfloor heating systems, Viessmann recommends that such systems be separated from the boiler with a heat exchanger.
Underfloor heating systems and heating circuits containing a very large volume of water must be connected to the boiler via a 3-way mixing valve; please refer to the applicable installation example in this manual.
Oxygen diffusion barrier underfloor tubing
The boiler warranty does not cover leaks resulting from corrosion caused by the use of underfloor plastic tubing without an oxygen diffusion barrier. Such systems must have the non-oxygen diffusion barrier tubing separated from the boiler with a heat exchanger. Viessmann recommends the use of underfloor plastic tubing with an oxygen
diffusion barrier.
Water quality
Treatment for boiler feed water should be considered in areas of known problems, such as where a high mineral content and hardness exist. In areas where freezing might occur, an antifreeze may be added to the system water to protect the system. Please adhere to the specifications given by the antifreeze manufacturer. Do not use automotive silicate based antifreeze. Please observe that an antifreeze/water mixture may require a backflow preventer within the automatic water feed and influence components such as diaphragm expansion tanks, radiation, etc. Maximum antifreeze content is 50% for the Vitodens 200-W boiler. Do not use antifreeze other than specifically made for hot water heating systems. System also may contain components which might be negatively affected by antifreeze. Check total system frequently when filled with antifreeze. Advise system operator/ultimate owner that system is filled with a glycol mix. The heating contractor must provide a MSDS (Material Safety Data Sheet) for the antifreeze used to the system operator/ultimate owner.
Warranty
Our warranty does not cover damages resulting from the following: – installation or service by unqualified and
unlicensed personnel.
– attempting to perform any repair work on
the boiler other than that mentioned in the boiler literature.
– tampering with or attempting, without
Viessmann permission, to readjust the factory settings of the
–combination gas valve –combustion air opening of the
burner blower Leaks resulting from corrosion caused by the use of underfloor plastic tubing without an oxygen diffusion barrier.For detailed warranty information, please read warranty sheet supplied with product.
41
Page 42
42
5369295v1.5
Page 43
43
5369295v1.5
Page 44
44
5369295v1.5
Technical information subject to change without notic
e
Printed on environmentally friendly (recycled and recyclable) paper.
Loading...