Viessmann WB2B 80, WB2B 105, B2HA 80, B2HA 88, B2HA 100 Installation Instructions Manual

...
Installation Instructions
Heat Exchanger Assembly
for use by heating contractor for Vitodens 200-W WB2B / B2HA
Part Number: 7831454 WB2B 80, 105 Part Number: 7843753 B2HA 80, 88, 100, 285, 311, 352
Safety and Installation Requirements
Please ensure that these instructions are read and understood before starting any service work. Failure to comply with these instructions may cause product/property damage, severe personal injury and/or loss of life.
Working on the equipment
The installation, adjustment, service and maintenance of this product must be performed by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burner or control.
Ensure that main power to the equipment being serviced is off.
Ensure that the main fuel supply valve to the boiler is closed.
Take precautions to avoid accidental activation of power or fuel during service work.
Do not perform service work on any component part without ensuring safe operation of the heating system. When replacing parts, use original Viessmann or Viessmann approved replacement parts.
Refer to the Installation and Service Instructions applicable to this boiler.
5698 072 - 02 08/2017
Accessing the Heat Exchanger
Heat Exchanger Assembly Installation
For more details refer to the Installation and Service Instructions applicable to this boiler.
1. With the electrical power and fuel supply off, open the control cover and switch the ON/OFF control switch to OFF.
2. Remove the front enclosure panel.
3. Close the boiler isolation valve or drain the system.
4. Remove the burner assembly.
Replacing Supply Pipe/Sensors/Refractory
1. Remove the Torx screw G (T-25) with the washer and pull the refractory H straight out.
2. Disconnect electrical connectors from the heating supply pipe A.
3. To replace the following:
- Remove connecting clip for boiler temperature sensor B.
- Remove 2 Phillips screws for high limit sensor C.
4. Pull off the connecting clip E to disconnect the pressure gauge hose from the heating supply pipe A.
boiler
Legend
Tighten the following fasteners on assembly:
C 8.9 lb.in. (1 Nm) D 70.8 lb.in. (8 Nm) G 35 lb.in. (4 Nm)
5. Remove the two Torx screws (T-40) D at the top and loosen the compression fitting at the bottom on the heating supply pipe A and remove pipe with top O-ring F.
6. Replace parts as required and reassemble as per steps 5 through 1 respectively and torque fasteners per legend.