Read and save these instructions
for future reference.
Page 2
Safety, Installation and Warranty Requirements
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with theinstructions listed below and details printed in this manu al can cause product/property damage, severe personal injury,and/orloss
of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
HLicensed professional heating
contractor
The installation, service, and
maintenance of this equipment mustbe performed by a licensed
professional heating c ontractor.
"
Please see section
entitled “Important
Regulatory and
Installation
Requirements” in the
Installation Instructions.
HProduct documentation
Read all applicable documentation
before commencing installation. Store
documentation near boiler in a readily
accessible location for reference in
the future by service personnel.
"
For a listing of
applicable literature,
please see section
entitled “Important
Regulatory and
Installation Requirements”
in the Installation Instructions.
HCarbon monoxide
Improper installation, service and/or
maintenance can cause flue products
to flow into living space. Flue
products contain poisonous carbon
monoxide gas.
"
For information
pertaining to the proper
installation, service and
maintenance of this
equipment to avoid
formation of carbon monoxide, please
see the Installation Instructions of the
Vitodens 200 Venting System.
WARNING
Installers must follow local
regulations with respect to
installation of carbon monoxide
detectors. Follow manufacturer’s
maintenance schedule of boiler.
HEquipment venting
Never operate boiler without an
installed venting system. An improper
venting system can cause carbon
monoxide poisoning.
HWarranty
Information contained in
this and related product
documentation must be
read and followed. Failure
to do so renders warranty
null and void.
HAdvice to owner
Once the installation work is
complete, the heating contractor
must familiarize the system
operator/ultimate owner with all
equipment, as well as safety
precautions/requirements, shut-down
procedure, and the need for
professional service annually before
the heating season begins.
Operating and Service Documentation
It is recommended that all product
documentation such as parts lists,
operating and service instructions be
handed over to the system user for
storage.
2
Documentation is to be stored near
boiler in a readily accessible location
for reference by service personnel.
5285 961 v1.3
Page 3
Index
Page
General Information
Initial Start-up
and Service
Troubleshooting
Safety, Installation and Warranty Requirements2...................................
Operating and Service Documentation2......................................................
Important Regulatory and Installation Requirements4...........................
About these Start-up/Service Instructions5................................................
Important Regulatory and Installation Requirements
Codes
The installation of this unit shall be in
accordance with local codes or, in the
absence of local codes, use
CAN/CSA-B149.1 or .2 Installation
Codes for Gas Burning Appliances for
Canada. For U.S. installations use the
National Fuel Gas Code ANSI Z223.1.
Always use latest editions of codes.
In Canada all electrical wiring is to be
done in accordance with the latest
edition of CSA C22.1 Part 1 and/or
local codes. In the U.S. use the
National Electrical Code ANSI/NFPA
70. The heating contractor must also
comply with both the Standard for
Controls and Safety Devices for
Automatically Fired Boilers,
ANSI/ASME CSD-1, and the Installation
Code for Hydronic Heating Systems,
CSA B214-01, where required by the
authority having jurisdiction.
Instructing the system user
The installer of the system is
responsible to ensure the system
operator/ultimate owner is made
familiar with the system functioning,
its activation, and its shut-down.
Initial start-up
Initial start-up m ust be performed by a
qualified heating c ontractor. Proper
completion of the Maintenance Record
by the heating contractor is also
required.
Working on the equipment
The installation, adjustment, service,
and maintenance of this boiler must be
done by a licensed professional heatingcontractor who is qualified and
experienced in the installation, service,
and maintenance of hot water boilers.
There are no user serviceable parts on
the boiler, burners, or control.
The following topics must be
covered:
Proper system operation sequence.
Explain the equipment.
Demonstrate an emergency
shut-down, what to do and what not.
Explain that there is no substitute for
proper maintenance to help ensure
safe operation.
The Maintenance Record is located
on page 70 of this manual.
Please carefully read this manual prior
to attempting start-up, maintenance
or service. Any warranty is null and
void if these instructions are not
followed.
For information regarding other
Viessmann System Technology
componentry, please reference
documentation of the respective
product.
Ensure main power supply to
equipment, the heating system, and all
external controls has been deactivated.
Close main gas supply valve. Take
precautions in all instances to avoid
accidental activation of power during
service work.
Technical literature
Literature for the Vitodens boiler:
- Technical Data Manual
- Installation Instructions
- Start-up/Service Instructions
- Operating Instructions
and User’s I nformation Manual
- System Design Guidelines
- Instructions of other Viessmann
products utilized and installed
- Installation codes mentioned
in this manual
We offer frequent installation and
service seminars to familiarize our
partners with our products. Please
inquire.
The completeness and functionality of
field supplied electrical controls and
components must be verified by the
heating contractor. These include low
water cut-offs, flow switches (if used),
staging controls, pumps, motorized
valves, air vents, thermostats, etc.
Leave all literature at the installation
site and advise the system
operator/ultimate owner where the
literature can be found. Contact
Viessmann for additional copies.
This product comes with several
safety instruction labels attached.
Do not remove!
Contact Viessmann immediately if
replacement labels are required.
4
5285 961 v1.3
Page 5
About these Start-up/Service Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product information.
These include ”WARNING”, ”CAUTION”, and ”IMPORTANT”. See below.
Warnings draw your attention to the
WARNING
Indicates an imminently hazardous
situation which, if not avoided, could
result in death, serious injury or
substantial product/property damage.
CAUTION
Indicates an imminently hazardous
situation which, if not avoided, may
result in minor injury or
product/property damage.
IMPORTANT
presence of potential hazards or
important product information.
Cautions draw your attention to the
presence of potential hazards or
important product information.
Helpful hints for installation,
operation or maintenance which
pertain to the product.
This symbol indicates that additional,
pertinent information is to be found in
column three.
This symbol indicates that other
instructions must be referenced.
5285 961 v1.35285 961 v1.3
5
Page 6
General Information
Necessary Tools
Special items
H Approved leak detection fluid for
natural gas and propane gas
H Pipe joint sealant
Testing/analysis equipment
H Multimeter to measure 0 - 230 V,
0 - 12 A AC and 0 - 100 μADC
H Flue gas analyzer to measure % CO
or O2(i.e. Bacharach fluid samplers
or suitable electronic analyzer)
H Manometer to measure gas pressure
0 to 11 ”w.c. (accurately) and up to
28 ”w.c. gas pressure (or a
non-electric Magnehelic® manometer
may also be utilized)
H Stack thermometer 0 to 500 °F /
0 to 260 °C
H Bacharach calculator or suitable
tables to calculate efficiency
H Carbon monoxide measuring
equipment 0 to 400 ppm
Cleaning supplies
H Plastic hand brush
H Rags
Use only calibrated equipment.
2
6
5285 961 v1.3
Page 7
General Information
Removing and Reinstalling Front Enclosure Panel and Cover Panel
Some of the following start-up/service
steps require the removal of the front
enclosure panel and the cover panel.
To avoid personal injury and/or product
damage of any kind please follow the
instructions below carefully when
removing or reinstalling the front
enclosure panel and cover panel.
To remove front enclosure panel and
cover panel proceed as follows:
1. Close main gas supply valve.
5.
2.
1.
3.
2. Open flip-down cover of front
enclosure panel (by exerting slight
pressure with fingertip). Switch off
system on/off switch.
3. Turn off power supply to boiler and
ensure that power supply cannot be
activated during the duration of the
start-up/service work.
5. Unlock enclosure panel by giving
cover lock a quarter turn.
6. Remove burner cover panel by
unlocking the two pull-down latches
located on the bottom of the panel,
and slide out panel.
7. Attach front enclosure panel.
8. Secure in place by rotating slotted
screw.
4.
5285 961 v1.3
7
Page 8
Initial Start-up and Service
Procedure (Overview)
Initial start-up steps
Service steps
I
I
I
I
IS
IS
IS
IS
IS
S
IS
IS
I
S
S
1. Fill heating system with waterPage9................................................................................................................
2. Check power supply connectionPage11..............................................................................................................
3. Select language (if required)Page12.....................................................................................................................
5. Select appropriate gas typePage13......................................................................................................................
6. Measure static pressure and running pressurePage13.................................................................................
7. How the Vitodens 200 boiler operates...Page15............................................................................................
9. Clock natural gas meterPage17..............................................................................................................................
11. Check all primary and secondary circuit connections for leaksPage18................................................
12. Perform c ombustion analysisPage18...................................................................................................................
13. Check venting system for leaks (circular air gap measurement)Page18..............................................
14. Disassemble burner and check burner gasketPage19..................................................................................
15. Visually check exterior of burner mesh assemblyPage19...........................................................................
S
S
S
S
S
IS
IS
IS
IS
S
I
I
I
16. Replace burner mesh assembly (if wire mesh is damaged)Page19........................................................
17. Check and adjust ignition and ionization electrodePage20........................................................................
2. Check inlet pressure of the
diaphragm expansion tank.
3. To remove debris and/or sludge
ensure that the system piping is
flushed out. Failure to do so could
cause settlement in the boiler
causing overheating and damage
not covered by warranty.
4. Optional:
Fill the heating system with w ater
at the boiler filling and drain tap
and drain air completely from the
system at ball valve barb fitting
Max. boiler
operating pressure......45 psig
Min. boiler
operating pressure......12 psig
Pressure relief valve ......30 psig
Please note:
Before filling the heating system with
water, check that all necessary flow
check valves are installed.
If the nitrogen pressure of the
precharged expansion tank is less
than the static pressure of the
system, inflate membrane pressure to
slightly exceed pressure of system.
The static pressure required at the
tank is based upon the static height
of the system. The system fill
pressure value must be equal to the
expansion tank pressure value at
approx. 60 ºF/15.6 ºC.
System fill pressure must be
approximately 3 psig higher than t he
static head when the system is cold.
Water treatment should be
considered in areas where it is known
that boiler feed water contains a high
mineral content and hardness.
.
In areas where freezing might occur,
an antifreeze may be added t o the
system water to protect the system.
Please adhere to the specifications
given by the antifreeze m anufacturer.
Do not use automotive silicate-based
antifreeze. Please observe that an
antifreeze/water mixture may require
a backflow preventer within the
automatic water feed and influence
components such as diaphragm
expansion t anks, radiation, etc. A
40% antifreeze content will provide
freeze-up protection to -10°F/-23°C.
Do not use antifreeze other than
specifically made for hot water
heating systems. System a lso may
contain components which might be
negatively affected by antifreeze.
Check total system frequently when
filled with antifreeze.
5285 961 v1.3
9
Page 10
Initial Start-up and Service
Steps (continued)
Initial start-up
1. Fill heating system with water (continued)
5. Check system pressure and open
ball valve
6. Shut off the boiler from the heating
system on heating water side (close
shutoff valve
7. Connect drain hose to drain valve
or.
8. Open drain valve
the boiler with system pressure
until noise due to the presence of
air is eliminated.
9. Close drain valve
open ball valve
10. Check system pressure.
11. Ensure proper/adequate fuel supply
exists. Open gas shutoff valve.
).
orand vent
orand
.
Water flow
Air vent
10
5285 961 v1.3
Page 11
Steps (continued)
Initial Start-up and Service
Initial start-up
2. Check power supply connection
A power module is supplied with the
Vitodens 200 boiler, which r equires a
120 VAC power supply from a wall
receptacle.
The module contains a 120/230 VAC
step-up transformer to power the
Vitodens 200 with 230 VAC. Refer to
the Installation Instructions shipped
with the module for wiring details
and/or Installation Instructions of the
boiler.
Voltage range
The voltage at connector
230 V (see wiring diagram).
Neutral conductor
The electrical power supply must have
a neutral conductor.
must be
IMPORTANT
In Canada all electrical wiring is to be
done in accordance with the latest
edition of CSA C22.1 Part 1 and/or
local codes. In the U.S. use the
National Electrical Code ANSI/NFPA
70. The heating contractor must also
comply with both the Standard for
Controls and Safety Devices for
Automatically Fired Boilers, ANSI,
ASME CSD-1.
Please note:
The outer conductor ”L” and the
neutral conductor ”N” must not be
interchanged.
See wiring diagram in section entitled
”Additional Information” in this
manual.
5285 961 v1.3
11
Page 12
Initial Start-up and Service
Steps (continued)
Initial start-up
LANGUAGE / LANGUE
>ENGLISH:.................A
>FRANÇAIS:...............B
>BACK / RETOUR: ......D
Initial start-up
HEATING CONTRACTOR
INPUT NAME/TEL.:
TEL.:
>CHANGE: -/+
>POSITION FORWARD:A
>POSITION BACK: ......B
>INSTALLER SETUP: ...D
3. Select language (if required)
Menu-driven programming unit.
Open cover:
Menu optionButton
→ SYSTEM”D”
→ FACTORY SETTING”A”
→ LANGUAGE”C”
Select language.
4. Heating contractor address input
Menu-driven programming unit.
This option allows the system user to access name and telephone number of the
heating contractor on the display (see Vitodens 200 Operating I nstructions) almost
immediately after a system fault has occurred.
CONTRACTOR”C”
Position cursor as required using
the ”A”and”B” buttons.
Select the required characters (number,
letter, special character) by turning
the ”G” selector knob (turn
clockwise or counterclockwise).
Characters already selected can be
deleted with the space character ”k”or
overwritten with another character.
Upon exiting the input menu
(INSTALLER SETUP ”C”), name and
telephone number of the heating
contractor are automatically stored.
5285 961 v1.3
Page 13
Steps (continued)
Initial Start-up and ServiceInitial Start-up and Service
Initial start-up
The Vitodens 200 boiler is for use with
gases whose characteristics fall within
the following ranges. Do not use any
other types of gas.
Heating value (gross)Btu/ft
Specific gravity0.57 to 0.701.522 to 1.574
Ultimate carbon dioxide (CO2)%11.7 to 12.213.73 to 13.82
Service
Initial start-upService
PE
outlet
5. Select appropriate gas type
1. Ensure that the fuel type listed on
the boiler rating plate is the correct
type for the installation being
attempted.
2. Record fuel type in Maintenance
Record on page 70.
Natural gasPropane gas
3
6. Measure static pressure and running pressure
Static pressure
1. To measure static and/or running
pressure remove burner cover panel
as per the removal and reinstallation
instructions on page 7 in these
instructions.
2. Close gas shutoff valve (field
supplied).
3. Loosen screw in test nipple ”PE” A
on the gas combination valve, do notremove completely. Connect
manometer.
970 to 11002466 to 2542
IMPORTANT
A CO measurement (see page 16 must
be taken before and after working on
gas appliances to eliminate risks to
health and to guarantee the
satisfactory condition of the system.
A
inlet
Measuring static gas supply pressure,
using test nipple “PE”
5285 961 v1.3
4. Open the gas shutoff valve.
5. Measure static pressure. Values
must be:
H 14“w.c.max.forNG
H 14“w.c.max.forLP
6. Enter measured value into
Maintenance Record on page 70 in
this manual.
7. Start up boiler, using the on/off
switch on the boiler control.
IMPORTANT
The burner is automatically ignited and
starts operation after a safety time has
elapsed.
During initial start-up, the unit may
indicate a fault because of air in the gas
supply pipe (especially for propane gas).
After approx. 5 seconds, press the ”EU”
button to reset the burner. The ignition
procedure is repeated. This boiler
employs a direct spark ignition system.
13
Page 14
Initial Start-up and Service
Steps (continued)
Initial start-upService
6. Measure static pressure and running pressure (continued)
Running pressure
8. Measure the running pressure; value
must be:
Running supply pressure withCorrective action
Natural gasPropane gas
Hunder 4 ”w.c. (WB2-44)
Hunder 7 ”w.c. (WB2-60)
H4 to 14 “w.c. (WB2-44)
H7 to 14 “w.c. (WB2-60)
over 14 ”w.c.over 14 ”w.c.Do not attempt adjustment. Call local
9. Enter gas type into Maintenance
Record on page 70 in this manual.
10. Switch off t he heating system
on/off switch on the boiler control
unit (boiler is shut down), close the
gas shutoff valve, remove the
manometer and re-tighten the
screw in the test nipple ”PE” A.
under 11 ”w.c. Do not attempt adjustment. Call local
11 to 14 ”w.c. Start up boiler.
Use suitable measuring instruments
calibrated with a minimum resolution
of 0.04 “w.c. for measuring the
running pressure.
gas utility to increase pressure.
gas utility to decrease pressure.
Boiler valve must not be exposed to
pressure over 14 ”w.c.
WARNING
Ensure that there is no open flame in
the room.
PE
outlet
A
inlet
Measuring running gas supply pressure,
using test nipple “PE”
11. Open gas shutoff valve and check
that the test nipple ”PE” and all gas
connections are gas-tight.
WARNING
Never purge a gas line into a
combustion chamber. Never use
matches, candles, flame, or other
sources of ignition for purpose of
checking leakage. Use a
soap-and-water solution to check for
leakage. A failure to follow this
warning could result in fire,
explosion, personal injury, or death.
5285 961 v1.3
14
Page 15
Steps (continued)
Initial Start-up and Service
Initial start-upService
7. How the Vitodens 200 boiler operates...
The MatriX burner blower and the combination gas valve are factory calibrated and
pre-adjusted for optimum boiler performance at all firing rates through a
non-mechanical, pneumatic modulating link between combustion air and gas flows.
Blower speed is automatically increased or decreased based on heat demand and
venting system resistances, thereby regulating the amount of combustion air
drawn. The pneumatic modulating link between air and gas introduces the required
amount of gas for correct combustion to meet the current heat demand, based on
a linear relationship between ∆ Pairand∆ Pgas.
Optimum combustion air flow rate is recognized and monitored by the differential
air pressure sensor (transducer). The output voltage signal of the transducer is
analyzed for logic by the LGM 29.XX burner ignition control unit. The LGM 29.XX
unit contains pre-programmed performance curves and operational safety
parameters unique for every boiler model.
See page 47 for sequence of operation.
Flue gas adaptation function
The Vitodens employs a flue gas adaptation function. This unique function
records, processes, and reacts in real time to fluctuations in pressure drops in the
vent pipe during normal operation caused by partial pipe blockages due to ice
formation at the vent termination, debris and/or sudden high winds. Such increase
in pressure drop, if not promptly corrected, will reduce the combustion air flow
rate, and hence lead to unstable combustion. The differential air pressure sensor
(transducer) records such pressure drops and supplies voltage signals to the LGM
29.XX burner ignition control unit which, in turn (based on stored performance
curves and safety parameters), initiates prompt adjustment of the blower rotational
speed, thus readjusting the combustion air flow rate for optimum combustion. The
same automatic adaptation logic applies if combustion air is reduced (or increased)
due to slower (or faster) blower speed resulting from line voltage drops (or
increases) below (or above) the threshold of 85% (or 110%).
outlet
X
Do not adjust screws X and Y!
5285 961 v1.3
Y
PE
inlet
WARNING
FOR FACTORY CALIBRATING
PURPOSES, THE COMBINATION GAS
VALVE IS EQUIPPED WITH
ADJUSTMENT SCREWS X AND Y.
DO NOT ATTEMPT TO ADJUST OR
READJUST THESE SCREWS.
ANY ATTEMPT TO TAMPER WITH
FACTORY PRE-ADJUSTED SETTINGS
WILL LEAD TO UNSTABLE OPERATION
AND WILL AFFECT BOILER
WARRANTY.
15
Page 16
Initial Start-up and Service
Steps (continued)
Initial start-upService
The Vitodens 200 boiler is factory
preset for operation with natural gas or
propane. It is recommended t hat a CO
check be performed at the boiler vent
pipe adaptor as part of the initial
start-up/maintenance procedure.
IMPORTANT
The MatriX burner of the Vitodens 200
is preset for the entire gas group. No
adjustment or readjustment of the
burner is required.
8. Check CO2setting
Depending on the gas type, the CO
value lies within the range of
H 6.6 to 10.0% for natural gas
2
H approx. 10.0 % for LP
The CO
compared with the above CO
ranges of the individual gas type.
10: <PL.90> CLOSED
10: BURNER
10: <PL.41> ON
10: is displayed
(”Flue gas”
content.
2
2
value
If the CO
2
than 1% outside the stated range for
NG, or 0.5% outside the stated range
for LP, perform the following steps:
H Check that correct orifice was used
(see subsection entitled “Check
orifice size” on page 17 and section
“Technical Data” on page 46 of this
manual).
H Check the venting system for leaks
(see subsection entitled “Check
venting system f or leaks” on page 18
of this manual).
value measured lies more
2
IMPORTANT
Do not use the emissions test switch
”S” to trigger a call for heat.
16
5. Select top end of rated input range
and check CO
If the value differs by more than one
percentage point, replace burner.
Select menu option
CONTINUE ”A”
until code
11: MODULATION
10: <PL.90> OPEN
10: BURNER
10: <PL.41> ON
10: is displayed
6. Exit the setting mode
H Close cover of programming unit.
H Enter the measured values into
Maintenance Record on page 70 in
this manual.
H Close flue gas measurement
opening
content
2
.
5285 961 v1.3
Page 17
Steps (continued)
Initial Start-up and Service
Initial start-upService
Clock natural gas meter to verify input
1. Ensure all other gas equipment
served by the meter is turned off
during timing of gas input to the
Vitodens 200 boiler.
2.Measure the time in seconds it takes
for the boiler to use 10 cu. ft. of
gas. Divide 3600 x 10 by the
number of seconds and you get the
number of cu. ft. of gas used per
hour. Multiply this number by the
heating value of the gas to obtain
Btu per hour input.
Service
9. Clock natural gas meter
For example:
A Vitodens 200, WB2 11-44 boiler
(172 000 Btu/h input) requires 209
seconds to use 10 cu. ft. of natural
gas. After contacting the local utility,
you will find the heating value is
1000 Btu per cu. ft.
Therefore,
3600 x 10/209 x 1000 ≅ 172 000
Btu/h input.
Therefore, the boiler input is correct.
Burner input formulas
(for low altitude only):
INPUT=(3600
t=TIME (sec.) f or 1 ft.
INPUT=(3600 x .01 x 1000 x 35.31)÷T
where
T = TIME (sec.) for .01 m
10. Check orifice size
÷t) x 1000 where
3
3
natural gas
IMPORTANT
A boiler underfired by 5% is
acceptable. Do not overfire the boiler.
CAUTION
Always contact your gas utility to
obtain the correct heating value before
clocking the meter.
E
ACB
Stamped identification code
1. Remove burner cover panel (if still
installed) as per the removal and
reinstallation instructions on page 7
in this manual, and reinstall panel
upon completion of service work.
2. Loosen screws A and take the gas
orifice holder C out of the fitting.
3. Read orifice size stamped on the
orifice body and cross-reference to
table below. If wrong orifice is
installed, proceed to next step.
4. Push the gas orifice B sideways out
of the gas orifice holder C.Snap
new and correct gas orifice into gas
orifice holder and push into the gas
train.
5. Tighten screws A.Tighten to a torque of 1.1 lb.ft./
6. Check all gas connections for leaks
with an approved leak test solution.
Overview of orifices
Boiler model
Natural gasE44E60
Liquid propaneP44P60
WB2 11-44WB2 15-60
See section entitled “Technical Data”
on page 46 of this manual for
information on gas orifices.
IMPORTANT
Place O-ring E in groove on new gas
orifice B.
1.5 Nm.
5285 961 v1.3
17
Page 18
Initial Start-up and Service
Steps (continued)
Initial start-upService
Initial start-upService
11. Check all primary and secondary circuit connections for leaks
Check heating system a nd domestic
hot water connections (if applicable).
Ensure all connections are pressure
tight.
Correct any leaks found on fittings,
pumps, valves, etc.
12. Perform c ombustion analysis
IMPORTANT
A CO measurement (see page 16) must
be taken before and after working on gas
appliances to eliminate risks to health
and to guarantee the satisfactory condition
of the system.
Record the measured combustion
values in the sequence stated in the
Maintenance Record on page 70 in this
manual.
Initial start-up
Combustion air measuring point
13. Check venting system for leaks (circular air gap measurement)
For sealed combustion, coaxial vent only.
Viessmann strongly recommends that
the heating contractor perform a
simplified leak test during boiler
start-up. For this purpose it is sufficient
to measure the CO
the combustion air in the coaxial gap of
the air intake pipe. The vent pipe is
considered sufficiently leak-proof if a
concentration in the combustion
CO
2
airnohigherthan0.2%oranO
concentration no lower than 20.6% is
measured.
concentration of
2
2
If higher CO
are measured, check venting system
thoroughly.
Please note!
The vent pipe adaptor comes with two
measurement ports, one for
combustion air intake measurement
and one for flue gas measurement.
Please note!
This test is not applicable for single wall venting system (non-sealed
combustion).
values or lower O2values
2
18
5285 961 v1.3
Page 19
Steps (continued)
Initial Start-up and Service
Service
14. Disassemble burner and check burner gasket
1. Remove burner cover panel (if still
installed) as per the removal and
reinstallation instructions on page 7
in this manual, and reinstall panel
upon completion of service work.
2. Switch off the heating system
switch on the control unit and the
power supply.
3. Close gas shutoff valve and secure.
4. Disconnect electrical cables from fan
motor
sensor
transformer
5. Remove two screws
disconnect gas line from gas valve.
6. Loosen six hexagon socket head cap
screws
7. Check burner gaskets for damage
and replace if required (see Parts
List).
, differential a ir pressure
, combination gas valve
, ionization electrode, ignition
and grounding.
to
and remove burner.
Do not lay burner on burner mesh
assembly (wire mesh)!
CAUTION
5285 961 v1.3
Service
Service
15. Visually check exterior of burner mesh assembly
To check the exterior of the burner
mesh assembly for physical damages,
such as dents, corrosion and/or
abnormally large holes:
1. Remove burner cover panel, if still
installed (see page 7). Reinstall
panel upon completion of service
work.
16. Replace burner mesh assembly (if wire mesh is damaged)
1. Remove electrodes.
3. Turn thermal insulation ring
clockwise and remove.
2. Unsrew the eight Torx screws
and remove burner mesh assembly
and assembly gasket.
3. Remove existing burner mesh
assembly gasket.
4. Fit new burner mesh assembly with
the new gasket and tighten with the
eight Torx screws.
IMPORTANT
Do not replace gasket
inspecting the exterior of the mesh
assembly.
Tighten to a torque of 3.3 lb.ft. /
4.5 Nm
when visually
19
Page 20
Initial Start-up and Service
Steps (continued)
Service
17. Check and adjust ignition and ionization electrode
1. Remove burner cover panel (if still
installed) as per the removal and
reinstallation instructions on page 7
in this manual, and reinstall panel
upon completion of service work.
2. Check electrodes for wear and
contamination.
3. Clean electrodes with small brush or
emery paper.
4. Check clearances. If clearances are
CAUTION
Do not damage wire mesh when
cleaning.
not satisfactory or the electrodes are
damaged, replace electrodes and
gasket A and align.
Tighten fastening screws for the
electrodes to a torque of 1.5 lb.ft. /
2Nm.
+4
8
-0
+3
5
-0
3
+0.5
-0
+0
7
-1
Service
20
18. Check condensate drain
Ensure condensate drains freely (e.g. at
siphon trap
21. Check diaphragm expansion tank and system pressure
Perform check with the system cold.
1. Drain boiler/system and reduce
pressure until the manometer reading
is ”0”.
2. If the nitrogen pressure of the
precharged expansion tank is less
than the static pressure of the
system, inflate membrane pressure
to slightly exceed pressure of
system.
The static pressure required at the
tank is based upon the static height
of the system. The system fill
pressure value must be equal to the
expansion tank pressure value at
approx. 60 ºF/15.6 ºC.
3. Top up with water until filling
pressure is higher than the inlet
pressure of the diaphragm expansion
tank.
Example
Static head of 33 ft./10 m
(distance between boiler and
topmost heat emitter surface)
corresponds to a static
pressure of 1 bar/15 psig.
With the system cold, the filling
pressure must be approx. 3 psig
higher than the static pressure.
Max. operating pressure:
........................................
Min. operating pressure:
........................................
45 psig
12 psig
Initial start-upService
4. When starting up the system for the
first time, mark this value as the
minimum filling pressure on the
manometer.
22. Check functioning of safety valves
Ensure proper operation of low water
cut-off(s) (if applicable), pressure relief
valve, and pump(s).
Check pressure gage, air vent and
pressure relief valve. Ensure that
pressure relief valve does not leak and
that it operates in accordance with
information provided by the
manufacturer.
Refer to maintenance instructions
supplied with low water cut-offs,
pumps, etc.
Flush float water type low water
cut-offs (if used).
A lower manometer reading usually
indicates loss of water due to
leakage. All leaks must be repaired.
Follow local regulations with respect to
backflow preventers.
If oil-lubricated pumps are used, ensure
proper lubrication.
If motorized zone valves are used, refer
to maintenance instructions provided
with zone valves.
22
5285 961 v1.3
Page 23
Steps (continued)
Initial Start-up and Service
Initial start-upService
Initial start-upService
23. Check electrical connections
Ensure all plug-in connectors and strain
reliefs make positive contact and are
seated properly.
24. Check gas pipes and fittings for leaks
WARNING
The gas supply piping must be leak
tested before placing the boiler in
operation.
Installation Instructions
Power/Pump Module
CAUTION
Ensure all joints of gas line are
pressure tight and that gas valves do
not leak when under normal
operating pressure (use approved
leak detection liquid).
5285 961 v1.3
23
Page 24
Initial Start-up and Service
Steps (continued)
Service
B
D
25. Measure ionization current
IMPORTANT
Switch off heating system on
the control unit before connecting the
measuring instrument.
1. Remove burner cover panel (if still
installed) as per the removal and
reinstallation instructions on page 7
in this manual, and reinstall panel
upon completion of service work.
2. Connect a DC μA multimeter in
series with the ionization cable as
follows:
a)Disconnect the socket of the
ionization cable
ionization electrode
connect to the plug of the
multimeter via adaptor
b)Connect additional ionization
measuring cable
ionization electrode
socket of the multimeter.
3. Start up boiler to its maximum input:
Turn emissions test switch ”S”on
the control unit to ”h”.
from the
and
.
to the
and the
Please note:
The m easurement can be made with
a multimeter (measuring range 0 to
100 μA).
A C
Initial start-up
4. If the ionization current is less than
5 μA
H check the electrode clearance (see
page 20).
H check the power supply
connection of the control unit.
5. After completing the measurement,
turn emissions test switch to ”a”.
6. Enter the value measured in the
Maintenance Record on page 70 in
this manual.
26. Verify programming unit system coding addresses
The control unit must be adjusted according to the system equipment. See
H page 48 onwards for programming unit.
For details on coding procedure and for an overview of the coding addresses, see
H page 50 onwards for programming unit.
Please note:
The minimum ionization current must
be at least 5 μA when the flame is
formed (approx. 2- 3 seconds after
opening the gas combination valve).
24
5285 961 v1.3
Page 25
Steps (continued)
Initial Start-up and Service
Initial start-up
A
B
DC
27. Check extension kit for heating circuit with mixing valveAccessory
1. Check via Scan 1 on the
programming unit whether the
connected extension kit is
recognized.
Please note:
The third and fourth-placed digits
from the left have the following
meaning:
(__ 02 _ _ = with burner control unit
5
4
6
3
7
8
2
9
1
0
10
5
4
6
3
+
-
i
7
8
2
1
S
9
10
Calling up Scan 1
Open the cover:
Menu optionButton
→ SYSTEM”D”
→ OPERATING
STATUS”B”
→ CONTINUE”A”
until
”Scan 1”
is
displayed
(__12 _ _)= additionally with Vitocom
100
(__ 03 _ _ = with burner control unit
and variable speed heat
circuit pump
(__13 _ _)= additionally with Vitocom
100
(__ 06 _ _ = with burner control unit
and extension kit for
heating circuit with mixing
valve
(__16 _ _)= additionally with Vitocom
100
(__ 07 _ _ = with burner control unit,
extension kit for heating
circuit with mixing valve
and variable speed heating
circuit pump
(__17 _ _)= additionally with Vitocom
100
2. If the extension kit is not recognized, check the coding of the
heating system type (see page 49).
Please note:
The extension kit is only recognized when connected via the
KM-BUS, not when connected via the
Viessmann 2-wire BUS.
Rotational direction switch
Power supply switch ” ”
5285 961 v1.3
III
Check mixing valve motor
1. Select rotational direction of the
mixing valve motor.
H Switch setting I for boiler return
from left (factory default setting).
Please note:
Please reference Installation
Instructions of Mixing Valve
Actuator.
H Switch setting II for boiler return
from right.
2. Relay test
Switch power supply switch on the
motor off and on again. The unit will
1
0
perform the following self-test:
H Close mixing valve (150 sec)
H Pump ON( 10 sec)
H Open mixing valve ( 10 sec)
H Close mixing valve ( 10 sec)
After that normal control mode is
resumed.
3. Observe the rotational direction of
the mixing valve motor during the
automatic relay test of the extension
kit.
Afterwards, position the mixing
valve by hand in t he ”Open” setting.
The supply temperature sensor must
now measure a higher temperature.
If the temperature is lower, either the
rotational direction of t he motor is
incorrect or the mixing valve insert is
incorrectly fitted.
25
Page 26
Initial Start-up and Service
Steps (continued)
Initial start-up
141
WHBNGN
21 23
22 24
141
X5
2341
28. Check Dekamatik-HKAccessory
1. Check via Scan 2 on the
programming unit whether the
connected expansion module is
recognized.
Expansion module
The last-placed digit has the following
meaning:
2____0 =Viessmann 2-wire BUS
expansion module not
Calling up Scan 2
YE
Open the cover:
2____1 =Viessmann 2-wire BUS
Menu optionButton
→ SYSTEM”D”
recognized
expansion module is
recognized
→ OPERATING
STATUS”B”
→ CONTINUE”A”
until
”Scan 2”
is
displayed
Dekamatik-HK
The second-placed digit from the left
has the following meaning:
_2____ =Extension kit for a heating
circuit with mixing valve or
Dekamatik-HK1/-HK 2
recognized
_3____ =Dekamatik-HK4 recognized
2. If the expansion module or the
Dekamatik is not recognized, check
that they were installed correctly.
Please note:
A green LED will flash on the
expansion module if the data BUS is
intact. If the LED is not lit, the data
line ”X5.3”- ”X 5.4” may be
incorrectly connected.
Check setting of rotary switch
H Dekamatik-HK1:
The rotary switch on the
communication module must be set
to ”4”.
H Dekamatik-HK2:
The rotary switch on the circuit board
E4 must be set to ”4”.
H Dekamatik-HK 4:
The rotary switch on circuit
board E4.1 must be set to ”4” and
the rotary switch on circuit
board E4.2 to ”5”.
See wiring diagram in section entitled
”Additional Information”.
Please note:
Please reference
corresponding installation
documentation for
Dekamatik-HK.
26
5285 961 v1.3
Page 27
Troubleshooting Steps
Diagnosis1. Establish fault message or diagnose behavior of system.
2. Look for corresponding cause of fault in the diagnostics table.
Diagnosis
H for faults with fault display on control unit (see below).
Please note:
See page 28 for retrieval of fault codes from the fault memory.
H for faults without fault display on control unit (page 38).
3. Find corrective action in the table.
Correction4. Perform corrective action (page 39).
Diagnosis
Faults with fault display on control unit
When a fault message is detected, ––––FAULT–––– flashes in the display of
the programming unit with the cover closed.
The fault message is cleared when
”ACKNOWLEDGE” is selected.
If an acknowledged fault is not
corrected by 24:00 hrs on the same
day, the fault message will reappear.
The acoustic alarm system (only with
optional expansion board installed), is
not reactivated.
The meaning of the fault codes is
explained in the table starting on
page 30.
Please note:
Please refer to the diagnostics table
starting on page 30 for details on
required action.
5285 961 v1.35285 961 v1.3
Select defective sensor with the menu
option CONTINUE ”A”.
2. H Select coding address ”0B2” by
pressing button ”A” (CONTINUE)
or ”B”(BACK).
H With the ”G” selector knob
Please note:
All settings are made in the ”Installer
Setup” menu, containing ”Coding 1”
(the main coding addresses in plain
language) and ”Coding 2” (all coding
addresses).
Changes which are made and
confirmed in Coding 1 are
automatically transferred t o Coding 2
and vice versa.
(CHANGE), set the value of the
coding address to ”001”.
H Confirm the change with
button ”D”.
3. Select coding address ”0B3”.The value which appears is the most
recent fault code (value in brackets ()
in the diagnostics table).
4. Repeat step 2, but set value of
“0B2” coding address to ”002”. The
Please note:
10 fault codes can be scanned.
new value which appears under
coding address ”0B3” is the next
fault code.
Fault code displayed on
programming unit
Fault history
code displayed
Fault: F9249
Fault: FD253
Fault: FE254
Fault: 02002
Fault: 04004
Fault: 05005
Fault: 06006
Fault: 07007
Fault: 08008
Fault: 14020
Fault: 15021
Fault: 0A010
Fault: 0B011
Fault: 0C012
Fault: 0D013
Fault: 0E014
Fault: 0F015
Fault: CC204
28
5285 961 v1.3
Page 29
Diagnosis (continued)
Sequence of operation and potential faults during each start-up cycle
Check water flow switch. Replace
if necessary.
Check cabling and plug-in connectors of the
blower , as well as blower itself.
Check differential air pressure sensor.
Seepage34.
Troubleshooting
Fault 06
Display message
no
5285 961 v1.3
no
Water flow switch activates
plug 33.
no
after approx. 70 seconds
no
Fault 94
see page 34
29
Page 30
Troubleshooting
Diagnosis (continued)
Display window
Reset button
Burner
fault indicator
Control unit for weather-responsive operation
with programming unit
Diagnostics table: Faults with fault display on control unit
Fault message in display window
Control unit for
weather-responsive operation with
programming unit
FAULT:
OUTDOOR TEMP. SENSOR
FAULT:
OUTDOOR TEMP. SENSOR
FAULT:
SUPPLY TEMP. SENSOR
FAULT:
SUPPLY TEMP. SENSOR
FAULT:
BOILER TEMP. SENSOR
FAULT:
BOILER TEMP. SENSOR
FAULT:
SUPPLY TEMP. SENSOR
FAULT:
SUPPLY TEMP. SENSOR
FAULT:
TANK TEMP. SENSOR
BurnerSystem behavior
fault indicator (red)
OFFBoiler operates based on 32 ºF/0 ºC outdoor temperature.
OFFBoiler operates based on 32 ºF/0 ºC outdoor temperature.
OFFSupply temperature of heating circuits too low.
OFFSupply temperature of heating circuits too low.
OFFBoiler cools down.
OFFBoiler cools down.
OFFMixing valve is opened.
OFFMixing valve is closed.
OFFDHW tank cools down.
FAULT:
TANK TEMP. SENSOR
FAULT:
EXT.PROG.2
30
OFFDHW tank cools down.
ONBoiler cools down
5285 961 v1.35285 961 v1.3
Page 31
Cause of faultCorrective action
Troubleshooting
Short circuit – outdoor temperature sensorCheck outdoor temperature sensor (see page 40).
Open circuit – outdoor temperature sensorCheck outdoor temperature sensor (see page 40).
Short circuit – low-loss header temperature sensorCheck supply temperature sensor (see page 40).
Open circuit – low-loss header temperature sensorCheck supply temperature sensor (see page 40).
Short circuit – boiler temperature sensorCheck boiler temperature sensor (see page 40).
Open circuit – boiler temperature sensorCheck boiler temperature sensor (see page 40).
Short circuit – supply temperature sensorSee Installation Instructions Mix. Valve Actuator.
Open circuit – supply temperature sensorSee Installation Instructions Mix. Valve Actuator.
Short circuit – tank temperature sensorCheck tank temperature sensor (see page 41).
See coding address “000” (see page 49).
See coding address “0B8” (see page 56).
Open circuit – tank temperature sensorCheck tank temperature sensor (see page 41).
See coding address “000” (see page 49).
See coding address “0B8” (see page 56).
Internal BUS faultReplace VR20 (see page 61).
Replace LGM 29 (see page 62).
Replace entire control console.
See coding address “000” (see page 49).
See coding address “0B8” (see page 56).
See coding address “000” (see page 49).
See coding address “0B8” (see page 56).
5285 961 v1.3
31
Page 32
Troubleshooting
CONTROLUNIT
Diagnosis (continued)
Diagnostics table: Faults with fault display on control unit (continued)
FAULT: B1OFFDIP switches A and B on back of are switched
(e.g. A-A or B-B).
FAULT: B2OFFBoiler cools down.
FAULT: B3OFFSetting via service level not possible.
FAULT: B6
BURNER
CONTROL
UNIT DEFECTIVE
FAULT: CC
*1
(204
)
OFFBoiler cools down.
ONBurner control unit switches to lockout
(due to large line voltage fluctuations).
FAULT: C8OFFBoiler does not activate.
FAULT: C0OFFBoiler does not activate.
FAULT: E4 or E...OFF––
FAULT: F2OFF––
FAULT: F5OFF––
FAULT: F9
*1
(249
)
FAULT: FBFlashes––
FAULT: FD
*1
(253
)
*1
Displayed when fault codes retrieved from fault memory.
32
OFF/ONBurner control switches to lockout.
ONBurner control switches to lockout.
5285 961 v1.3
Page 33
Troubleshooting
p
p
y
p
fieldsuppliedconnections(byprocessofeliminationif
Cause of faultCorrective action
Short circuit – WS/RS remote control unitCheck WS/RS remote control unit (see page 44).
Open circuit – WS/RS r emote control unit or wrong
coding
Internal BUS fault
Open circuit – internal BUS connection
Check WS/RS remote control unit (see page 44).
Check proper system coding.
Verify connections X5.3 and X5.4 for mixing valve
(if applicable).
Check that circuit board VR20 is inserted properly and check
field su
required).
Check coding of LGM 29 c omponent part.
Replace circuit board VR20 or circuit board of burner control
unit LGM 29 (see page 61).
lied connections (b
rocess of elimination if
KM-BUS fault to VitocomCheck connection to Vitocom or Vitocom defective.
Short circuit/open circuit – BUS connection to extension
kit for heating circuit with mixing valve
Check connection of extension kit for heating circuit with
mixing valve (see page 25). Check coding for system
with a mixing valve. Mixing valve might be defective.
Set DIP switches to factory default setting. See symbols on
back of programming unit.
Sensor inputs are not read correctly.Check correct connection of sensors.
Data points are not stored; internal fault VR20.Replace circuit board VR20
AD-converter of burner control unit defective;
internal fault LGM 29
Check for damage on wiring harnesses.
Check whether circuit board VR20 is defective.
If required, replace circuit board VR20
*1
.
Replace burner control unit LGM 29
*1
*1
.
.
Differential air pressure sensor / open circuitCheck wiring, replace sensor.
Differential air pressure sensor / short circuitCheck wiring, replace sensor.
Internal fault or fault with internal data protectionReset burner control unit.
Fault in Dekamatik-HK heating circuit control unit
connected downstream
Check Dekamatik-HK heating circuit control unit connected
downstream and data transmission circuit. Check wiring con-
nections.
Error message to Vitocom communication unitCheck Vitocom communication unit.
Error message extension kit for heating circuit with mixing
valve
Check coding for extension kit and the extension kit itself.
Check sensorof mixing valve.
Parameterization of burner control defectiveReplace circuit board of burner control unit LGM 29
*1
.
Emergency operation LGM 29Check plug-in connection and circuit board VR20.
Parameterization of burner control defectiveReplace circuit board of burner control unit LGM 29
5285 961 v1.3
Replace circuit board VR20 if necessary.
*1
.
33
Page 34
Troubleshooting
Diagnosis (continued)
Diagnostics table: Faults with fault display on control unit (continued)
Fault message in display window
FAULT: FE
*1
(254
)
FAULT: 02
*1
(002
)
FAULT: 04
*1
)
(004
FAULT: 05
*1
)
(005
FAULT: 06
*1
)
(006
FAULT: 07
*1
)
(007
FAULT: 08
*1
)
(008
FAULT: 09
*1
)
(008
FAULT: 14
*1
)
(020
Burner fault
System behavior
indicator (red)
ONBurner control switches to lockout
ONBurner control switches to lockout.
ONBurner control switches to lockout.
ONBurner control switches to lockout.
ONBurner control switches to lockout.
ONBurner control switches to lockout.
ONBurner control switches to lockout.
ONBurner control switches to lockout.
ONBurner control switches to lockout.
FAULT: 0A
*1
)
(010
FAULT: 0B
*1
)
(011
FAULT: 0C
*1
)
(012
FAULT: 0D
*1
)
(013
*1
Displayed when fault codes retrieved from fault memory.
34
ONBurner control switches to lockout.
ONBurner control switches to lockout.
Fan does not idle after auto reset (incorrect fan rpm).
ONBurner control switches to lockout.
ONBurner control switches to lockout.
5285 961 v1.3
Page 35
Cause of faultCorrective action
Troubleshooting
Internal fault burner control unit or interferenceCheck electrode settings.
Safety chain w as activated (fixed high limit)Check fixed high limit (see page 43). Bleed air from the
Fan speed too high at start (maximum fan rpm exceeded).Fan or fan electronics defective.
Fan speed too low at start (incorrect fan rpm).Check fan and flue gas system.
Air pressure threshold for ignition level is not reached.
Feedback voltage signal to LGM 29 not available.
Fan speed incorrect.Check fan and flue gas system.
Fan speed too high prior to ignition (incorrect fan rpm).Check fan and flue gas system.
Fault fan speedCheck fan and flue gas system.
No flame signalCheck electrical connections (see page 11).
Basic level of air pressure threshold in standby mode not
correct.
Severe wind conditions in vent system.Protect outside wall vent termination from severe winds.
Check wiring harness plug X13 for proper connection or
damage.
Check whether flue gas system is leak-tight.
If after corrective action fault “FE” still appears on display
replace LGM 29.
heating system.
Replace RLS 154 electric fan control.
Replace LGM 29 and/or burner assembly.
Check fan plug, fan, differential pressure sensor (see page 41)
and inlet air damper (flapper).
Check flue gas system for proper sizing and functioning.
Purge air from gas line (for LP gas, purge air several times).
Measure ionization current (see page 24).
Check gas pressure (see page 13).
Check gas combination valve (see page 13).
Check ignition transformer.
Check ignition electrodes (see page 20).
Check condensate drain (see page 20).
Check power supply polarity (L,N,G).
Check proper grounding.
Check #158 plug on (replacement) LGM 29 is installed
Check differential air pressure sensor (see page 41).
Check wiring harness and connection to air pressure sensor.
Flame signal still present after switching off.Check gas combination valve (see page 13).
Reset button “EU“ pressed repeatedly or while burner is
running.
5285 961 v1.3
Check electrode block (see page 20).
Power ON/OFF boiler / acknowledge fault.
Press reset button ”EU” once.
35
Page 36
Troubleshooting
Diagnosis (continued)
Diagnostics table: Faults with fault display on control unit (continued)
Fault message in display window
FAULT: 25OFFBoiler operates with high boiler water temperature.
FAULT: 26OFFBoiler operates with continuous relay test.
FAULT: 35OFFBoiler does not activate.
FAULT: 94OFFBoiler does not activate.
FAULT: 95OFFBoiler does not activate.
FAULT: 51OFFNo DHW function.
FAULT: 59OFFNo DHW function.
Burner fault
indicator (red)
System behavior
36
5285 961 v1.3
Page 37
Cause of faultCorrective action
Troubleshooting
Emissions test switch ”S” turned to ”h” f or 30 minutes
already.
Setting mode for maximum or minimum rated input active
for 30 minutes already.
Reset button ”EU” pressed while burner is off with emissions test switch ”S” turned to ”h”.
Basic level of air pressure threshold in standby mode not
correct.
Start-up prevented.Check wiring, water and gas pressures.
DHW outlet sensor / short circuitCheck sensor/wiring.
DHW outlet sensor / open circuitCheck sensor/wiring.
Turn emissions test switch ”S”to”a”.
Set heating program selector switch to required operating
mode or close cover on programming unit.
Turn emissions test switch ”S”to”a” and press reset
button ”EU” once.
Check differential air pressure sensor (see page 41).
Check wiring harness and connection to air pressure sensor.
Fault will clear if output signal of air pressure sensor is
correct.
See coding address “000” (page 49).
See coding address “0B8” (page 54).
See coding address “000” (page 49).
See coding address “0B8” (page 54).
5285 961 v1.3
37
Page 38
Troubleshooting
Diagnosis (continued)
Diagnostics table: Faults without fault display on control unit
System behavior
Supply temperature too cold or too warm.FuseCheck fuse (see page 43).
Room temperature too cold or too warm.Thermostatic radiator valvesCheck thermostatic radiator
Domestic hot water temperature too cold or too
warm.
Boiler constantly switches on and off.Flue gas system leakingCheck flue gas system for leaks
Diagnostics table: Faults on power module
System behavior
Boiler has no powerMain power on/off switchCheck switch position
(main power on/off switch on boiler is in ”ON”
position)
Heating pump does not operate
Cause of faultCorrective action
Variable speed heating circuit
pump
Heating system type incorrectly
coded
Circulating pumpCheck circulating pump.
Cause of faultCorrective action
Power supply or boiler is not
electrically connected
Fuse F1
(located in the Power/Pump
Module)
Electrical connection(s) has/have
been made incorrectly.
Check coding of heating circuit
pump (see page 52).
Check coding of heating
system type (see page 49).
valves (see page 43).
and perform leak test.
Ensure that power cord and
power supply cable to the boiler
are plugged in properly.
Replace fuse with same type and
of same rating (T2A/250 V, slow
blow)
Ensure that
– connections,, and
on the mother board
– connections ...,, and
in the boiler junction box
are made correctly.
20A
20A
38
Fuse F2A
(located in the Power/Pump
Module)
Replace fuse with the same type
and of same rating (T10A/250 V,
slow blow)
5285 961 v1.3
Page 39
Correction
Troubleshooting
Page
Sensors
Check outdoor temperature sensor40
Check boiler temperature sensor40.................................................................
Check DHW tank temperature sensor or low-loss header
temperature sensor41
2. Measure resistance of outdoor
temperature sensor at the
disconnected connector between
”X6.3” and ”X6.4”, and compare
with resistance/outdoor temperature
curve shown on the left.
3. If the value measured differs
significantly from the curve,
disconnect wires from the sensor
and repeat the measurement directly
on the sensor.
4. Depending on the result, replace
cable or the outdoor temperature
sensor.
A
40
20
10
8
6
4
2
1
Ω
0.8
0.6
0.4
0.2
Resistance in k
5086122 158 194 230
68104 140 176 212 248
103050
204060
Boiler water temperature in ºF/ºC
7090 110
80100 120
1. Disconnect cables from boiler
temperature sensor A.
2. Measure resistance of the boiler
temperature sensor and compare
with resistance/boiler water
temperature curve shown on the
left.
3. If the value measured differs
significantly, replace the sensor.
IMPORTANT
As the sensor is in direct contact
with the boiler water, the boiler must
be drained before changing the
sensor.
5285 961 v1.3
40
Page 41
Correction (continued)
Troubleshooting
Check DHW tank temperature sensor or low-loss header temperature sensor
A
B
X7
3 421
A DHW tank temperature sensor
B Low-loss header temperature sensor
40
1. Disconnect connector ”X7” from the
control unit.
20
10
8
6
4
2
2. Measure resistance of the tank
temperature sensor and compare
with the curve.
3. If the value measured differs
significantly, replace the sensor.
4. Repeat above steps 1 - 3 for
checking the low-loss header
Ω
1
0.8
0.6
0.4
0.2
Resistance in k
5086122 158 194 230
68104 140 176 212 248
10305070110
204060
Tank temperature in ºF/ºC
80100 120
temperature sensor.
Check and replace differential air pressure sensor
B
D
5285 961 v1.3
B
C
D
C
D
A
In case of fault messages regarding the differential a ir pressure sensor, check that
H the sensor was installed correctly.
H the electrical connections were made correctly.
H the O-rings in the adaptor are correctly positioned.
H the test nipples have been sealed with plugs.
If the error message persists, replace sensor.
To check O-rings:
Transducer power supply
X14.3Red................
1. Disconnect electrical plug-in
164
connection
A.
2. Remove sensor B by pulling off in
an upward direction.
3. Check that the two O-rings C are
correctly located in the m ountings
D of the adaptor.
X14.4Yellow................
X14.5Black................
Between red and black:
24VDC.......................
Between black and yellow:
at standby0.2 to 0.3VDC........
at ignition0.7 to 1.0VDC.........
at low fire0.5 to 0.6 VDC........
4. Insert connection nipples of the
at high fire3.5VDC........
sensor in the adaptor of the gas
combination valve and snap into
place.
5. Reconnect the electrical plug-in
connection on the sensor.
Select required relay to check its
function with the menu option
CONTINUE ”A”(seebelow).
Please note:
Those relays which are not
mentioned have no significance.
When the relay is selected, only the
corresponding unit is addressed. If no
call for heat is present, the burner is
omitted from the relay test.
For installations with Dekamatik-HK
mixing valve control, refer to the
Dekamatik-HK control manual.
DisplayMeaning
01– 1st stage burnerWithout function
<PL41> ON(Burner on, pump not running)
02– Heating circuit pump ACirculating pump
<PL20> ON
03– Heating circuit pump BHeating circuit pump
<PL20B> ONwith extension kit with mixing valve
04– DHW pumpDHW heating pump
<PL21> ON
05– Not assigned
06– Not assigned
07– Mixing valve HC BMixing valve CLOSED
*1
<PL52B> CLOSED
08– Mixing valve HC BMixing valve OPEN
*1
<PL52B> OPEN
10– ModulationBurner (min. input)
<PL90> CLOSEDCirculating pump
Burner
<PL41> ON
11– ModulationBurner (max. input)
<PL90> OPENCirculating pump
Burner
<PL41> ON
13– Additional heating pumpAdditional heating pump or
<PL28> ONDHW recirculation pump
14– Alarm outputAlarm output
*3
*2
<PL56> ON
*1
Only in conjunction with mixing valve extension kit
*2
If no low-loss header is installed, pump will be operated as a DHW recirculating pump
(see coding addresses “099” and “0B8”).
If a low-loss header is installed, the pump will operate as a boiler pump
(see coding address “0B8”).
*3
Only in conjunction with expansion board (optional)
5285 961 v1.35285 961 v1.3
42
Page 43
Correction (continued)
A
Troubleshooting
Check safety fixed high limits (FHL)
If the safety fixed high limits cannot be
reset after an automatic lockout of the
burner control unit, even though the
boiler water temperature is below
approx. 194 ºF/90 ºC, perform the
following steps:
H Disconnect the cables from the fixed
high limit switch A.
H Check continuity of the fixed high
limit switch with a multimeter.
H Remove defective limit switch.
H Coat new limit switch with heat
conductive paste and install.
H After start-up, press the reset button
”EU” on the control unit.
5285 961 v1.3
AB
Check fuse
1. Disconnect connector fÖ A in the
control unit.
2. Remove fuse F 3 (6.3 A) B by
holding its grip and pulling out of the
base.
3. Check continuity of fuse with a
multimeter.
Check thermostatic radiator valves
Check operation and setting.
IMPORTANT
The thermostatic radiator valves must
not be activated in a room in which the
room temperature sensor is installed for
room temperature dependent operation.
In case of a weather-responsive control,
with a room temperature sensor via the
RS remote control unit, keep the
thermostatic radiator valves fully open.
43
Page 44
Troubleshooting
Correction (continued)
Check WS remote control unit(Accessory)
Check RS remote control unit(Accessory)
The WS remote control unit is used for setting the desired room temperature
values from any room in the building.
The RS remote control unit is used f or setting the desired room temperature values
from the main living room (with room temperature dependent control).
Functionality check
IMPORTANT
Resistance measurement and control
unit response test.
If the presence of a fault is suspected
in the customer’s connecting cable,
temporarily connect the remote control
directly to the control unit and perform
test.
To calculate total r esistance (NTC), add
the actual value and the current
resistance setpoint value.
In most cases, faulty behavior of the
control unit is due to the installation of
the RS remote control unit in an
unsuitable location.
This can lead to draft phenomena
caused by cavities behind the remote
control or by the stack effect of empty
pipes.
Wiring diagram: see section e ntitled
”Additional Information”.
310
Ω
300
290
280
280
Resistance in
54 61 68 75 82
46
1220 24 2816
8
Setpoint value
ºF
ºC
WS remote control
s– Setpoint value between terminal
”9” and ”10”
m – Setpoint value between terminal
”9” and ”11”
240
220
200
Ω
180
160
140
Resistance in
46
8 1216202428
Actual value
61
5468 75 82
ºF
ºC
RS remote control
Room temperature sensor (NTC) curve
between terminal ”9” and ”13”
172
152
145
Ω
138
119
108
84
59
Resistance in
46 54 61 68 75
50 57
812
10
Setpoint value
64 7279
16 20 24
14 18 22
26
ºF
ºC
RS remote control
s– Setpoint value between terminal
Max. ambient
temperature
H at operation:32 to 104 ºF
Setting of fixed high limit
safety cut-out:210 ºF
(fixed setting)99 ºC
–0 to +40 ºC
H when storing
Main fuse:max. 16 A
and transporting: –4 to +149 ºF
–20 to +65 ºC
Setting of adjustable
electronic high limit 167 ºF
Power consumption
H Burner:max. 105 W
H Control unit:max. 10 VA
75 ºC
WARNING
Always ensure the correct orifices
are installed in the boiler. See table
below.
The boiler must achieve the output
stated on the rating plate. Do not
overfire the boiler.
Standard heating boiler
Boiler ModelModel No.WB2 11-44WB2 15-60
Natural gas
CSA input
CSA output/DOE
heating capacity
Net I=B=R rating
Propane gas
CSA input
CSA output/DOE
heating capacity
Net I=B=R rating
Min. gas supply pressure
Natural gas
Propane gas
Max. gas supply pressure
Natural gas
Propane gas
Flue gas
Temperature (at boiler return
water temp. of 86 ºF/30 ºC)
– at rated full load
– at rated partial load
Temperature (at boiler water
return temp. of 140 ºF/60 ºC)
Max. natural gas flow rateft3/h
Max. propane gas flow rateft3/h
Burner orifices diameter
Natural gas
Propane gas
*1
*2
*3
*3
Net I=B=R rating based on piping and pick-up allowance of 1.15.
If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator must be installed upstream of the
heating system.
Measured flue gas temperature with combustion air temperature of 68 °F/20 °C.
*1
*1
MBH
kW
MBH
kW
MBH133178
MBH
kW
MBH
kW
MBH120166
“w.c.
“w.c.
*2
“w.c.
“w.c.
ºF/ºC
ºF/ºC
ºF/ºC
3
/h
m
3
/h
m
Ømm
Ømm
55-172
16-50
49-153
14-44
55-155
16-45
49-138
14-40
4
11
14
14
95/35
91/33
149/65
172
4.87
62
1.75
(E44) 8.40
(P44) 6.10
80-230
23-67
71-205
21-60
37-112
11-33
33-101
10-30
11
14
14
104/40
95/35
158/70
230
6.51
85.6
2.42
(E60) 9.00
(P60) 6.70
7
46
5285 961 v1.3
Page 47
Burner Control Unit LGM 29.XX
Program sequence
Standby
Initial boiler run
time with
internal tests
Call for heat
Ionization
Safety chain (FHL)
Gas combi valve
Ignition transformer
Combustion air modulation
Speed
Time in sec.<71 20.2<55Heating mode
signal required
signal invalid
signal required for transition to next phase
Pre-purge time
Pre-ignition time
Safety time
Flame
recognition
Operation
Modulation range
Shutdown and
auto reset with
max. 51
Additional Information
internal tests
Standby
Waiting time until next call for heat
start. Differential air pressure sensor
must be reset and the speed feedback
signal (HALL) must record that fan is
stationary.
Start-up and initial boiler run time
Start takes place when a call f or heat
is received f rom the temperature
controller, provided no air pressure is
detected. The fan motor receives
voltage. The speed signal (HALL) and
the differential air pressure voltage
signal must be received by the burner
control unit LGM 29.XX within approx.
70 seconds, otherwise a fault message
is transmitted. During the initial boiler
run time, self-tests take place within
the burner control unit LGM 29.XX.
Pre-purge time
The combustion chamber is flushed out
by the fan.
Pre-ignition time
Ignition spark is initiated.
Safety time
The gas combination valve coils receive
voltage (energized), flame monitoring is
activated. Ignition is switched off after
approx. 4 seconds.
If the flame is not recognized during
ignition after three trials, automatic
lockout takes place.
5285 961 v1.3
Burner operation (green LED is lit)
Burner operation begins after the safety
time has e lapsed, and flame recognition
has taken place successfully. The
burner control unit modulates from its
ignition load according to the currently
selected setpoint value.
After controlled shutdown (heat
demand is satisfied), a uto reset to the
standby mode takes place.
Shutdown
The gas valve is de-energized.
Internal tests are performed.
Test time
Auto reset is the end of the shutdown
phase after controlled switch-off.
Auto reset also takes place after
resetting, failure of the flame during
operation or after a call for heat is
terminated before the start of the safety
time.
Safety chain (FHL)
The fixed high limits must be closed at
all times during the entire period of
operation, otherwise automatic lockout
takes place immediately.
Burner control unit LGM 29.XX
The burner control unit LGM 29.XX
performs self-tests in the following
instances:
H when the burner has been in
continuous operation for more than
24 hours,
H before each time the burner is
switched on,
H after each time the burner is
switched off.
Behavior in the event of malfunctions
If faults are detected, e ither no start-up
takes place or automatic lockout is
triggered. In case of all safetyrelevant malfunctions, the gas supply is
cut off. Automatic lockout takes place
H when flame establishment fails
before the end of the flame
recognition time,
H in the event of an uninterrupted delay
of the flame signal for more than 3
seconds,
H in the event of an incorrect differential
air pressure sensor signal longer than
70 seconds,
H in the event of internal faults.
In the event of a line voltage drop, the
burner control unit either operates
without a fault indication function or
goes into reset position (gas valve
closed).
When the line voltage reaches its
normal level again, burner c ontrol is
ready for another start-up.
47
Page 48
Additional Information
Control Unit for Weather-Responsive Operation with programming unit
Functional description
Space heating mode
The control unit calculates a boiler
water setpoint temperature based on
the outdoor or room temperature
(where a room temperature dependent
remote control is connected) and on
the slope/shift of the heating curve.
The computed boiler water setpoint
temperature is transmitted to t he
burner control unit.
From the boiler water setpoint and the
actual temperature the burner control
calculates the degree of modulation
required, and regulates the burner
accordingly.
The maximum operating boiler water
temperature is limited in the burner
control unit to 167ºF / 75ºC by the
electronic temperature control.
The maximum adjustable high limit of
the boiler is 180ºF / 82ºC.
The fixed high limits of the safety chain
interlock the burner control unit at
210 ºF/99 ºC boiler water temperature.
Programming Unit (removable)
Domestic hot water supply
with gas-fired space heating boiler
Domestic hot water heating is
activated when the tank temperature is
4.5 ºF/2.5 ºC below the tank
temperature setpoint value.
The burner and the tank DHW pump
are switched on. In the f actory default
setting, the desired boiler water
temperature is set at 36 ºF/20 ºC
above the tank temperature setpoint
value. When the actual tank
temperature rises 4.5 ºF/2.5 ºC above
the tank temperature setpoint value,
the burner is switched off and the time
delay function of the tank DHW pump
is activated.
Additional heating function (anti legionnaire-function) for domestic hot
water production
The additional heating function is
activated when an activation period of
10 minutes is selected (e.g. 22.10 to
22.20 hrs).
This period must lie outside the
switching times for normal domestic
hot water heating so that the signal is
recognized by t he control unit.
The temperature setpoint value for
additional heating is set in coding
address ”0A7”.
Pressure gage
Display window
Heating program selector switch
30
2
15
1
45
3
0
0
60
0
+
A
-
B
DC
i
5
4
6
3
7
8
2
9
1
0
10
5
4
6
3
7
8
2
9
1
10
Burner fault reset button
Emission test switch (override switch)
Selector knob for ”normal room temperature”
Burner operating status indicator
Burner fault indicator
Boiler on/off switch
Party button
Energy savings button
Selector knob for ”reduced room temperature”
Information button
”Factory default settings” button
Selector knob
Flip-down cover
Selector buttons
DHW comfort function switch (only available
on Combi heating boiler)
5285 961 v1.3
48
Page 49
Additional Information
Control Unit for Weather-Responsive Operation
with programming unit (continued)
Heating system types
The control unit is adjusted to the system equipment.
In the factory default setting, the heating system type is coded ”000:000”.
H The coding is set automatically when a tank temperature sensor is connected (for operation with a DHW tank).
H The control unit must be r e-coded m anually if a heating circuit with mixing valve is connected:
For this purpose the corresponding heating system type is coded in the coding address ”000”.
For other settings please note numbers of system types.
See page 50 for information of how to access t he required coding level.
Please note:
If only heating circuit B with mixing valve is connected (i.e. there is no direct-connected heating circuit), coding address
”008” must be set to value ”001”.
Refer to the Vitodens 200 Installation Instructions for piping layout details.
System type ”000:000”
Heating system with
one heating circuit without mixing valve,
without DHW heating
*1
*1
M
M
*1
Circulating pump and check valve are external to the boiler and not internal as illustrated.
5285 961 v1.3
*1
*1
MM
MM
or
Heating system with low-loss header and
heating circuits connected downstream
with separate heating circuit control unit
(Dekamatik-HK), without DHW heating.
System type ”000:001”
Heating system with
one heating circuit without mixing valve,
with DHW heating
or
Heating system with low-loss header and
heating circuits connected downstream
with separate heating circuit control unit
(Dekamatik-HK), with DHW heating.
System type ”000:002”
Heating system with one heating
circuit with mixing valve,
without DHW heating (with or without
low-loss header)
or
Heating system with one heating
circuit with mixing valve and one heating
circuit without mixing valve, without
DHW heating (with or without low-loss
header).
System type ”000:003”
Heating system with one heating
circuit with mixing valve,
with DHW heating (with or without lowloss header)
or
Heating system with one heating
circuit with mixing valve and one heating
circuit without mixing valve, with DHW
heating (with or without low-loss
header).
49
Page 50
Additional Information
Control Unit for Weather-Responsive Operation
Accessing coding addresses
The coding of the programming unit is
performed by using the ”A”, ”B”, ”C”
and ”D” buttons and t he ”G”
selector knob.
5
4
6
3
7
8
2
9
1
0
10
5
4
6
3
+
A
-
B
DC
i
7
8
2
9
1
10
Open cover:
Menu optionButton
→ SYSTEM”D”
→ INSTALLER SETUP”C”
S
→ CODE PLEASE:”B-C-C-B”
→ CODING 1”B”
or
CODING 2”C”
The desired coding address is selected
by pressing button ”A” (CONTINUE) or
”B”(BACK).
The respective coding address is
changed with the ”G” selector knob
(CHANGE). The change is confirmed
with button ”D” (change is stored).
with programming unit
(continued)
Please note:
All the settings are performed in the
”Installer Setup” menu which
contains ”Coding 1” (main coding
addresses in plain language) and
”Coding 2” (all coding addresses).
Changes made and confirmed in
Coding Level 1 are automatically
adopted in Coding Level 2 and vice
versa.
50
5285 961 v1.3
Page 51
Additional Information
Control Unit for Weather-Responsive Operation
Heating curve
Slope
Boiler water temperature or
230
212
194
176
158
140
122
supply temperature in ºF/ºC
104
ºF ºC
86
110
100
90
80
70
60
50
40
30
3.2
3.4
1050-5-10
5041 32 23
Outdoor temperature
3.0
14
2.8
-15
2.4
2.6
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
ºC
-20
-4
ºF
5
with programming unit
(continued)
The heating curves represent the
relationship between the outdoor
temperature and the boiler water or
supply temperature.
Put simply: The lower the outdoor
temperature, the higher the boiler water
or supply temperature.
In turn, the room temperature is
dependent on the boiler water or supply
temperature.
If a different room temperature is set, the
curves are shifted parallel to the desired
room temperature axis.
Factory settings:
H slope ”n”=1.4
H shift ”N”=0
230/
110
Boiler water temperature or
supply temperature in ºF/ºC
+68/20-4/20
Outdoor temperature in ºF/ºC
230/
110
Boiler water temperature or
supply temperature in ºF/ºC
+68/20-4/20
5285 961 v1.3
Outdoor temperature in ºF/ºC
3.5
-13
+40
1.4
0.2
1.4
1. To change the slope
Open cover on programming unit a nd
go through menu as follows:
Menu optionButton
→ HEATING CIRCUIT A ”A”
or
HEATING CIRCUIT B ”B”
→ HEATING CURVE”B”
→ CHANGE”A”
2. To change the shift
Open cover on programming unit a nd
go through the menu as follows:
→ HEATING CIRCUIT A ”A”
or
HEATING CIRCUIT B ”B”
→ HEATING CURVE”B”
→ CHANGE2 × ”A”
51
Page 52
Additional Information
Control Unit for Weather-Responsive Operation
Overview of coding addresses
Coding addresses not discussed in this section must not be
changed.
See page 50 for information of how to access coding addresses.
Coding (factory
default setting)
Address: Value
000:000One heating circuit without mixing valve,
001:000Do not change
003:001DHW
004:000Do not change
005:001Heating
006:001Heating
007:000DHW
Function modeCoding
change
Address: Value
000:001
system without domestic hot water heating
000:002
000:003
tank
circuit
With priority switching over
heating circuit pump(s)
With heating circuit pump
logic function
003:000Without priority switching over heating circuit
005:000Without heating circuit pump logic function
pump
circuit
pump
tank
Heating circuit pump speed in
reduced range as per
coding address ”044:...”
Setting range of domestic hot
water temperature
006:000Heating circuit pump speed in reduced range
007:001Setting range of domestic hot water tempera-
50 to 140 ºF/10 to 60 ºC
*1
*2
*1, 2
with programming unit
(continued)
Possible change
One heating circuit without mixing valve,
system with domestic hot water heating
One heating circuit with mixing valve,
system without domestic hot water heating
One heating circuit with mixing valve,
system with domestic hot water heating
pump(s)
as per coding address ”046:...”
ture 50 to 158 ºF/10 to 70 ºC
IMPORTANT
Note max. tank water temperature.
008:000Do not change
009:000Program-
ming unit
Display of boiler water
temperature
010:000Do not change
011:000External call for heat or external
switching of heating program blocked
012:000Do not change
013:000Heating
circuit
pump
Heating circuit pump without
variable speed operation (e.g.
as temporary m easure f or
servicing)
014:000
*3
Heating
circuit
Party button ”g” effective
for heating circuit B
015:001Do not change
*1
Coding for systems with domestic hot water heating is automatically recognized.
*2
These codings also apply on systems with one heating circuit without mixing valve and one heating circuit with mixing valve.
*3
Only on heating system types ”000:002” and ”000:003” (heating systems with one heating circuit with mixing valve).
52
IMPORTANT
Do not adjust domestic hot water
temperature more than 140 ºF/
60 ºC.
009:001Display of outdoor temperature
011:001External call for heat or external switching of
Party button ”g” effective for heating circuit
A and heating circuit B
5285 961 v1.3
Page 53
Additional Information
Control Unit for Weather-Responsive Operation
with programming unit
(continued)
Overview of coding addresses (continued)
Coding (factory
default setting)
Address: Value
Function modeCoding
change
Address: Value
Possible change
016:000Do not change
017:001Do not change
018:000DHW
tank
019:000Program-
ming
unit or
remote
control
Circulating pump with time
delay function
Weather-responsive operation
(WS function) for all connected heating circuits
018:001Circulating pump without time delay function
019:001
*1
H On systems with one heating circuit
without mixing valve or one heating
circuit with mixing valve:
Operation with room temperature
dependent control (RS function)
H On systems with one heating circuit
without mixing valve and one heating circuit
with mixing valve:
Weather-responsive operation (WS function)
for heating circuit with mixing valve and operation with room temperature dependent
control (RS function) for heating circuit with
mixing valve
H On systems with one heating circuit
019:002
*1
without mixing valve or one heating
circuit with mixing valve:
Weather-responsive operation (WS function)
in normal heating mode and operation with
room temperature dependent control (RS
function) in reduced operation
H On systems with one heating circuit
without mixing valve and one heating circuit
with mixing valve:
Weather-responsive operation (WS function)
for heating circuit without mixing valve and
on weather-responsive basis in normal heating mode and operation with room temperature dependent control in reduced operation
(WS/RS function) for heating c ircuit with
mixing valve
020:000Heating
circuits
Without WS or RS remote
control unit
020:001With WS or RS remote control unit
027:000External switching of heating program027:001External call for heat
028:000BoilerDuring DHW production, the
boiler water temp. is max. 36
ºF / 20 ºC higher than the
028:001During domestic hot water production, the
boiler water temperature is limited to
172 ºF/78 ºC by the limit thermostat
desired tank water temp.
029:001Do not change
033:000Do not change
034:000Do not change
036:000Do not change
038:020Minimum supply temperature in heating mode 020 to 127Min. possible supply temperature
68 to 261 ºF / 20 to 127 ºC
*1
Change only feasible if programming unit is mounted on a wall-mount base.
*2
Address set automatically, must be reset manually.
*2
5285 961 v1.3
53
Page 54
Additional Information
Control Unit for Weather-Responsive Operation
with programming unit
(continued)
Overview of coding addresses (continued)
Coding (factory
default setting)
Address: Value
Function modeCoding
change
Address: Value
Possible changes
042:070Boiler water temperature in heating mode000 to 82Max. adjustable temperature limit setting
180ºF / 82ºC
044:030Heating
circuit
pump
Minimum rotational speed of
heating circuit pump; approx.
1100 rpm
044:001
to
044:100
*1
Lowest value for minimum rotational speed of
heating circuit pump; approx. 700 rpm
Highest value for minimum rotational speed of
heating circuit pump; approx. 2700 rpm
045:065Heating
circuit
pump
Maximum rotational speed of
heating circuit pump; approx.
1750 rpm
045:001
to
045:100
*1
Lowest value for maximum rotational speed of
heating circuit pump; approx. 700 rpm
Highest value for maximum rotational speed of
heating circuit pump; approx. 2700 rpm
046:045Heating
circuit
pump
Rotational speed of heating
circuit pump in reduced operation; approx. 1200 rpm
046:001
to
046:100
*1
Lowest value for rotational speed of heating circuit pump in reduced operation; approx. 700 rpm
Highest value for rotational speed of heating cir-
cuit pump in reduced operation; approx. 2700 rpm
049:___Hours run (”hundreds”) at 3rd place from left049:000Reset hours run
050:___Hours run (”units”) at 3rd place and
050:000Reset hours run
”tens” at 2nd place from left
055:040Do not change
085:032Do not change
086:032Do not change
088:007Do not change
089:008Do not change
099:000Possibility for connecting a DHW
recirculating pump (on timer schedule)
099:001Output signal for domestic hot water
production active (ON), whenever there is a call
for DHW only
0A0:020
*2
Differential temperature between desired
boiler water temperature and desired
tank temperature with domestic hot water
0A0:10
to
0A0:50
heating
0A1:000Do not change
0A2:075BoilerDesired boiler temperature
with external request
167 ºF/75 ºC
0A2:032
to
0A2:127
Setting range of desired boiler water temperature 90 to 261 ºF/32 to 127 ºC (max. possible
boiler water temperature 180 ºF/82 ºC)
0A3:___Do not change
*1
One increment corresponds to approx. 20 rpm.
*2
Only effective with coding 028:000.
54
5285 961 v1.3
Page 55
Additional Information
g
Control Unit for Weather-Responsive Operation
Overview of coding addresses (continued)
Coding (factory
default setting)
Address: Value
0A4:255Do not change
0A5:255Do not change
0A6:255Do not change
0A7:060DHW
0A8:000BoilerSee table below for effect of
Function modeCoding
change
Address: Value
tank
Setpoint value for ”Additional
function for domestic hot
water heating”
(“Anti-Legionnaire-Function”
– domestic hot water heated
briefly to 140 ºF/60 ºC)
external disable signal
(also see page 59)
A07:061
to
A07:070
0A8:001
to
0A8:007
with programming unit
(continued)
Possible changes
Setting range between 142 to 158 ºF/
61 and 70 ºC.
IMPORTANT
Do not adjust domestic hot water
temperature more than 158 ºF/
70 ºC.
See table below for effect of external disable
signal
Possible coding changes for coding address 0A8 ”external disable”
Max. rotational speed of circulating pump for DHW production
0A9:001
to
0A9:100
*1
Possible changes
Lowest value for rotational speed of
circulating pump for DHW production
Highest value for rotational speed of
circulating pump for DHW production
0B2:___Fault memory (see page 28)
0B3:___Fault memory (see page 28)
0B4:___Do not change
0B8:000Space heating only - no DHW0B8:001
0B8:002
With DHW heating
Optimum DHW heating (with anti legionnaire
function) (see page 48).
0B8:005
0B8:006
Combi boiler only
Not assigned. Must be changed to one of the
other coding addresses.
0C1:011Freeze-up protection threshold
+34/+37ºFor+1/+3ºC
0C1:000
0C1:015
+50/+18ºFor+10/–8ºC
+41/+45ºFor+5/+7ºC
0C2:008Do not change
0C5:000BoilerSee table below for effect of
external heat demand signal
(also see page 59)
0C5:001
to
0C5:011
Possible coding changes for coding address 0C5 ”external heat demand”
This is set automatically when a tank temperature sensor is connected; can be reset to ”001” manually if required.
*3
Once this function has ended, the program changes automatically to the ”Space heating and DHW heating” mode.
Boiler water
temperature
Maintained at
desired value
coding address
”0A2”
56
5285 961 v1.3
Page 57
Additional Information
Control Unit for Weather-Responsive Operation
Overview of coding addresses (continued)
Coding (factory
default setting)
Address: Value
0C6:000Do not change
0C7:003Resetting
0C8:001External
0C9:003Startofsummertime:March0C9:001
0D0:005Start of summer time: Last week of
0D1:007Start of summer time: Last day of week
0D2:010Startofwintertime: October0D2:001
0D3:005Start of winter time: Last week of
0D4:007Start of winter time: Last day of week
0D5:000Program-
0D6:000Program-
0D7:000Do not change
Function modeCoding
change
Address: Value
Automatic0C7:000
to
summer/
winter time
switching
of heating
program
ming unit
ming unit
Contact open:
Space heating ON/domestic
hot water heating ON (accordingtotimeprogram)
Contact closed:
Central heating OFF/domestic
hot water heating OFF.
month
(Sunday)
month
(Sunday)
Normal display format with
cover closed
Temperatures displayed in
”ºC” (º Celsius)
0C7:001
0C7:002
0C8:000Contact open:
to
0C9:012
0D0:001
to
0D0:005
0D1:001
to
0D1:007
to
0D2:012
0D3:001
to
0D3:005
0D4:001
to
0D4:007
0D5:001Large display format for time and outdoor
0D6:001Temperatures displayed in ”ºF” (º Fahrenheit)
with programming unit
(continued)
Possible change
Manual resetting to s/w / date change blocked
Automatic resetting to s/w
Manual resetting to s/w / date change
released
Central heating ON/domestic hot water
heating ON (according to time program)
Contact closed:
Continuous space heating ON/domestic hot
water heating ON (independent of preset time
program)
January
to
December
Week 1
to
Week 5 of selected month
Monday
to
Sunday
January
to
December
Week 1
to
Week 5 of selected month
Monday
to
Sunday
temperature with cover closed
5285 961 v1.3
57
Page 58
Additional Information
Control Unit for Weather-Responsive Operation
Accessing temperature settings
The following desired and actual
temperature values can be accessed
and shown on the display of the
programming unit:
5
4
6
3
7
8
2
9
1
0
10
5
4
6
3
+
A
-
B
DC
i
7
8
2
9
1
10
H Outdoor temperature
H Boiler water temperature
H Supply temperature of the extension
S
kit for the heating circuit with mixing
valve
H Room temperature (if programming
unit is mounted on a wall-mount base
andusedasaremotecontrol).
Open the cover:
Menu optionButton
→ HEATING
CIRCUIT A or”A”
HEATING
CIRCUIT B or”B”
SYSTEM”D”
→ OPERATING STATUS”C”or”B”
→ CONTINUE”A”
with programming unit
(continued)
Depending on the coding, the boiler
water temperature or the outdoor
temperature is shown in the first
menu on the display.
H Domestic hot water temperature
Open cover:
Menu optionButton
→ DHW”C”
→ DHW TANK”A”
→ OPERATING STATUS”C”
58
5285 961 v1.3
Page 59
Jumper Assignment and Codings
Assignment of plug-in jumper on circuit board VR20
Additional Information
Plug-in jumper ”X6”
Factory default setting without
”External burner disable” function.
With ”External burner disable”
function.
Plug-in jumpers ”X2” - ”X 4”
Factory default setting without
Viessmann 2-wire BUS expansion
module: Two plug-in jumpers connected
as shown.
With Viessmann 2-wire BUS expansion
module: Both plug-in jumpers r emoved.
External switching of the heating program (telephone contact)
With programming unit
Change coding address ”011:000” to
”011:001”.
External heat demandfield supplied
With programming unit
Change coding address ”011:000” to
”011:001” and ”027:000” to
”027:001”.
Boiler start-up takes place in
accordance with the settings of
coding address ”0C5”.
Boiler water temperature is
maintained at the value selected in
coding address ”0A2”.
5285 961 v1.3
59
Page 60
Additional Information
Jumper Assignment and Codings (continued)
External disablefield supplied
B
A
1. Remove circuit board VR 20 A.
2. Reverse plug-in jumper ”X6” B.
3. Insert circuit board A again.
Boiler shutdown takes place in
accordance with the settings selected
in coding address ”0A8”.
Before replacing circuit board VR20, record actual system addresses (in particular coding addresses 000, 0B8, 042, 045,
015, 017, 0A2) and their corresponding values, heating curves and DHW settings.
Removing circuit board VR20
Coding information
1. Loosen the two screws located
underneath the control
carefully fold down t he control.
2. Unscrew and remove cover
3. Slide out circuit board VR20
using supplied handle.
Installing the replacement circuit board
1. Slide circuit board VR20
back into the control.
Ensure that circuit board is fully
plugged in and makes positive
contact.
2. Reinstall front enclosure panel and
cosmetic piping cover.
3. Verify that all coding addresses and
their values a re programmed t o
recorded actual/required values.
See table below.
4. Turn on power supply to boiler and
start up boiler.
and
.
Please note!
This table does not reflect all necessary coding cha nges required for proper operation of the boiler.
See subsection “Overview of coding addresses” in this manual for other coding changes required.
Coding address
000:000 (without DHW; factory default setting)Set according to system lay-
015:001(factory default setting)Do not change!
017:001(factory default setting)Do not change!
0B8:000 (no DHW storage tank)
5285 961 v1.3
Possible coding valuesRequired action
001 (with DHW storage tank)
002 (with DHW storage tank optimized)
006 not assigned
out. See page 52 for details.
Set to (one of) the value(s)
indicated.
61
Page 62
Additional Information
Replacement of Burner Control Unit LGM 29
Removing the circuit board
1. Unlock hooks
located on both
sides of the control unit and remove
the control housing
of the control
unit.
2. Remove pressure gage.
3. Loosen the two screws located
underneath the control unit
and
carefully fold down t he control unit.
4. Remove covers,,and.
5. Remove all plug-in connectors and
the grounding wire, including #158
plug.
6. Slide off circuit board VR20
using
the supplied handle.
7. Loosen screws holding installed
circuit board LGM 29.22in place
and remove carefully.
Setting the dip switch (applicable only t o replacement boards)
qQ
ON
2
345678
1
S2
62
1. Set dip switch
setting of the new
circuit board according to the table
on the following page.
IMPORTANT
To ensure the boiler is operated in
accordance with its certification (see
boiler rating plate), the dip switch must
be set according to the table on the
following page.
Note that in the factory default setting
all switches are set to “OFF”.
2. Remove fuse holder from fuse F3 of
the removed circuit board LGM 29.22
and install on fuse F3 on replacement
circuit board LGM 29.55.
5285 961 v1.3
Page 63
Replacement of Burner Control Unit LGM 29 (continued)
Setting the dip switch
Additional Information
Boiler model no.
WB2 11-44
WB2 15-60
Installing the replacement circuit board
Dip switch setting
ON
2
345678
1
ON
2
345678
1
1. Install new circuit board LGM
29.55
.
IMPORTANT
Do not remove clear covers on the
circuit board. These provide protection
against static discharge.
2. Connect all plug-in connectors to
circuit board LGM 29.55
including #158 plug.
,
IMPORTANT
Do not interchange plug-in connectors
“X6” and “X7”. None of the other
connectors are interchangeable.
3. Install covers
4. Plug in grounding wire.
5. Insert circuit board VR20
6. Install covers
7.Fold up control unit
using screws.
8.Insert pressure gage
capillaries).
9. Mount control housing
into place with hooks
both sides of the control unit.
and.
.
and.
and secure,
(do not kink
and lock
located on
5285 961 v1.3
63
Page 64
Additional InformationAdditional Information
Replacement of Burner Control Unit LGM 29 (continued)
Installing the replacement circuit board (continued)
10. Reinstall front enclosure panel.
11. Start up boiler a nd check for proper
functioning of the circuit board and
the heating system.
Vitodens 200
Start-up/Service
Instructions
IMPORTANT
If “FAULT : FE“ appears in the display
of the control unit during the
functionality check, check dip switch
settings against table on previous page
and adjust if required.
Wiring Diagram
See following page.
64
5285 961 v1.3
Page 65
5285 961 v1.3
65
Page 66
Additional Information
Parts List
Model No.Serial No.
WB2 11-44 7188578
and
WB2 15-60 7188577
Ordering Replacement Parts:
Please provide boiler Model and Serial
Number from rating plate when
ordering replacement parts. Order
replacement components from your
Viessmann distributor.
Parts
001 Profile gasket
016 Air vent without shut-off, R 3/8”
017 Matrix burner assembly (with Pos.
018, 026, 027, 056, 088,
094, 096, 100 and 120)
018 Matrix burner mesh (with Pos.
096 and 100)
020 Radial fan, RLS154 (without
electrode)
026 Ignition electrode
027 Ionization electrode
028 Flex gas pipe, 90x1½x1½cm
030 Conversion kit, NG
032 Conversion kit, LP
043 Connecting pipe extension (return)
044 Flow sensor
050 Condensate hose
055 Differential pressure sensor
056 Gas valve without orifice
057 Sealing grommet
058 Spring clip (set)
059 P-trap
086 Fixed high limit, 210°F / 99°C
087 Temperature sensor (with Pos.
unit LGM 29, 47
Outdoor temperature sensor, 40
Overview of coding addresses, 52
P
Parts list, 66
Power supply connection, 11
Program sequence, 47
R
Relay test, 42
RS remote control unit, 44
Running pressure, 13
Selecting the language, 12
Static pressure, 13
T
Tank temperature sensor, 41
Technical data, 46
Thermostatic radiator valves, 43
Troubleshooting, 27
V
Viessmann 2-wire BUS expansion
module, 25, 59
H with programming unit, 26
W
Weather-responsive operation, 48
Wiring diagram, 64
WS remote control unit, 44
5285 961 v1.3
G
S
Safety instructions, 2
Safety valves, 22
69
Page 70
Additional Information
S
i
Maintenance Record
Setpoint value
Service
date:
Service
date:
Service
date:
ce
erv
date:
by:
by:
by:
by:
max.
14 ”w.c.
4-14 ”w.c.17-10 ”w.c.211-14 “w.c.
Never exceed
50 ppm air-free
min. 5 μA
Setpoint value running pressure WB2-44
Setpoint value running pressure WB2-60
*1
*2
Service
date:
by:
Service
date:
by:
“w.c.
Measurements
Static pressure
unning pressure (supply pressure)
“w.c.
j Natural gas
“w.c.
j LP
ppm
at lower end of rated input range
ppm
at upper end of rated input range
vol.-%
vol.-%
2
2
j Check gas type
Carbon dioxide content CO
H at lower end of rated input range
H at upper end of rated input range
Oxygen content O
vol.-%
at lower end of rated input range
vol.-%
at upper end of rated input range
Carbon monoxide content CO
μA
Ionization current
5285 961 v1.3
70
Page 71
Lighting and Operating Instructions
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING:Ifyoudonotfollowtheseinstructionsexactly, a fire or
explosion may result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped
with an ignition device which automatically lights
the burner. Do not
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the
floor because some gas is heavier than air and will
settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fire
department.
try to light the burner by hand.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this
label.
2. Set thermostat or other operating control to lowest
setting.
3. Turn off all electric power to the appliance.
4. This device is equipped with an ignition device
which automatically lights the burner. Do not
light the burner by hand.
try to
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not
push in or turn by hand, don’t try to repair it, call a
qualified service technician. Force or attempted
repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to replace
any part of the control system and any gas control
which has been under water.
5. Close main gas shutoff valve.
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you smell
gas, STOP! Follow ”B” in the safety information
above on this label. If you don’t smell gas, go to the
next step.
7. Open main gas shutoff valve.
8. Turn on all electric power to the appliance.
Manual gas shutoff
Open
Closed
1. Set thermostat or other operating control to lowest
setting.
2. Turn off all electric power to the appliance if service
is to be performed.
3. Close main gas shutoff valve.
5285 961 v1.3
9. Set thermostat or other operating control to
desired setting.
10. If the appliance will not operate, follow the
instructions ”To Turn Off Gas To Appliance” and
call your service technician or gas supplier.
TO TURN OFF GAS TO BOILER
71
Page 72
Printed on environmentally friendly
(recycled and recyclable) paper.
Viessmann Manufacturing Company (U.S.) Inc.
45 Access Road
Warwick, Rhode Island • 02886 • USA
Tel. (401) 732-0667 • Fax (401) 732-0590
www.viessmann-us.com • info@viessmann-us.com