Viessmann VITODENS 200, WB2-44/60 Start-up And Service Instructions

Page 1
Start-up/Service Instructions
for use by heating contractor
Vitodens 200 WB2 Series
Wall-mounted, gas-fired condensing boiler
For natural gas and liquid propane Heating input NG 55 to 230 MBH
16 to 67 kW
16 to 63 kW
Please file in Service Binder
VITODENS 200
Vitodens 200, WB2-44/60 (with preinstalled vent pipe adaptor)
Vitodens 200, WB2-44/60 (with preinstalled vent pipe adaptor)
5285 961 v1.3 09/2008
IMPORTANT
Read and save these instructions for future reference.
Page 2
Safety, Installation and Warranty Requirements
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manu al can cause product/property damage, severe personal injury,and/orloss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
HLicensed professional heating
contractor
The installation, service, and maintenance of this equipment must be performed by a licensed professional heating c ontractor.
"
Please see section entitled “Important Regulatory and Installation Requirements” in the Installation Instructions.
HProduct documentation
Read all applicable documentation
before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
"
For a listing of applicable literature, please see section entitled “Important Regulatory and Installation Requirements” in the Installation Instructions.
HCarbon monoxide
Improper installation, service and/or maintenance can cause flue products to flow into living space. Flue products contain poisonous carbon monoxide gas.
"
For information pertaining to the proper installation, service and maintenance of this equipment to avoid formation of carbon monoxide, please see the Installation Instructions of the Vitodens 200 Venting System.
WARNING
Installers must follow local regulations with respect to installation of carbon monoxide detectors. Follow manufacturer’s maintenance schedule of boiler.
HEquipment venting
Never operate boiler without an installed venting system. An improper venting system can cause carbon monoxide poisoning.
HWarranty
Information contained in this and related product documentation must be read and followed. Failure
to do so renders warranty null and void.
HAdvice to owner
Once the installation work is complete, the heating contractor must familiarize the system operator/ultimate owner with all equipment, as well as safety precautions/requirements, shut-down procedure, and the need for professional service annually before the heating season begins.
Operating and Service Documentation
It is recommended that all product documentation such as parts lists, operating and service instructions be handed over to the system user for storage.
2
Documentation is to be stored near boiler in a readily accessible location for reference by service personnel.
5285 961 v1.3
Page 3
Index
Page
General Information
Initial Start-up and Service
Troubleshooting
Safety, Installation and Warranty Requirements 2...................................
Operating and Service Documentation 2......................................................
Important Regulatory and Installation Requirements 4...........................
About these Start-up/Service Instructions 5................................................
Necessary Tools 6...................................................................................................
Removing and Reinstalling Front Enclosure Panel a nd Cover Panel 7
Procedure (Overview) 8........................................................................................
Steps 9........................................................................................................................
Troubleshooting Steps 27......................................................................................
Diagnosis 27................................................................................................................
Correction 39...............................................................................................................
Additional Information
Overview 45................................................................................................................
Technical Data 46.....................................................................................................
Burner Control Unit LGM 29 47..........................................................................
Control Unit for Weather-Responsive Operation
H with programming unit 48.................................................................................
H jumper assignment and codings 59...............................................................
Replacement of Circuit Board VR20 61............................................................
Replacement of Burner Control Unit LGM 29 62..........................................
Wiring Diagram 65....................................................................................................
Parts Lists
H Vitodens 200, WB2 66
H Installation fittings (models WB2 11-44 and 15-60) 68........................
Alphabetical Index 69..............................................................................................
Maintenance Record 70..........................................................................................
Lighting and Operating Instructions 71............................................................
......................................................................................
5285 961 v1.3
3
Page 4
General Information
Important Regulatory and Installation Requirements
Codes
The installation of this unit shall be in accordance with local codes or, in the absence of local codes, use CAN/CSA-B149.1 or .2 Installation Codes for Gas Burning Appliances for Canada. For U.S. installations use the National Fuel Gas Code ANSI Z223.1. Always use latest editions of codes.
In Canada all electrical wiring is to be done in accordance with the latest edition of CSA C22.1 Part 1 and/or local codes. In the U.S. use the National Electrical Code ANSI/NFPA
70. The heating contractor must also comply with both the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, and the Installation Code for Hydronic Heating Systems, CSA B214-01, where required by the authority having jurisdiction.
Instructing the system user
The installer of the system is responsible to ensure the system operator/ultimate owner is made familiar with the system functioning, its activation, and its shut-down.
Initial start-up
Initial start-up m ust be performed by a qualified heating c ontractor. Proper completion of the Maintenance Record by the heating contractor is also required.
Working on the equipment
The installation, adjustment, service, and maintenance of this boiler must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers.
There are no user serviceable parts on the boiler, burners, or control.
The following topics must be covered: Proper system operation sequence. Explain the equipment. Demonstrate an emergency shut-down, what to do and what not. Explain that there is no substitute for proper maintenance to help ensure safe operation.
The Maintenance Record is located on page 70 of this manual.
Please carefully read this manual prior to attempting start-up, maintenance or service. Any warranty is null and void if these instructions are not followed.
For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product.
Ensure main power supply to equipment, the heating system, and all external controls has been deactivated. Close main gas supply valve. Take precautions in all instances to avoid accidental activation of power during service work.
Technical literature
Literature for the Vitodens boiler:
- Technical Data Manual
- Installation Instructions
- Start-up/Service Instructions
- Operating Instructions and User’s I nformation Manual
- System Design Guidelines
- Instructions of other Viessmann products utilized and installed
- Installation codes mentioned in this manual
We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire.
The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, etc.
Leave all literature at the installation site and advise the system operator/ultimate owner where the literature can be found. Contact Viessmann for additional copies.
This product comes with several safety instruction labels attached. Do not remove! Contact Viessmann immediately if replacement labels are required.
4
5285 961 v1.3
Page 5
About these Start-up/Service Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include ”WARNING”, ”CAUTION”, and ”IMPORTANT”. See below.
Warnings draw your attention to the
WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage.
CAUTION
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/property damage.
IMPORTANT
presence of potential hazards or important product information.
Cautions draw your attention to the presence of potential hazards or important product information.
Helpful hints for installation, operation or maintenance which pertain to the product.
This symbol indicates that additional, pertinent information is to be found in column three.
This symbol indicates that other instructions must be referenced.
5285 961 v1.35285 961 v1.3
5
Page 6
General Information
Necessary Tools
Special items
H Approved leak detection fluid for
natural gas and propane gas
H Pipe joint sealant
Testing/analysis equipment
H Multimeter to measure 0 - 230 V,
0 - 12 A AC and 0 - 100 μADC
H Flue gas analyzer to measure % CO
or O2(i.e. Bacharach fluid samplers or suitable electronic analyzer)
H Manometer to measure gas pressure
0 to 11 ”w.c. (accurately) and up to 28 ”w.c. gas pressure (or a non-electric Magnehelic® manometer may also be utilized)
H Stack thermometer 0 to 500 °F /
0 to 260 °C
H Bacharach calculator or suitable
tables to calculate efficiency
H Carbon monoxide measuring
equipment 0 to 400 ppm
Cleaning supplies
H Plastic hand brush H Rags
Use only calibrated equipment.
2
6
5285 961 v1.3
Page 7
General Information
Removing and Reinstalling Front Enclosure Panel and Cover Panel
Some of the following start-up/service steps require the removal of the front enclosure panel and the cover panel. To avoid personal injury and/or product damage of any kind please follow the instructions below carefully when removing or reinstalling the front enclosure panel and cover panel.
To remove front enclosure panel and cover panel proceed as follows:
1. Close main gas supply valve.
5.
2.
1.
3.
2. Open flip-down cover of front enclosure panel (by exerting slight pressure with fingertip). Switch off system on/off switch.
3. Turn off power supply to boiler and ensure that power supply cannot be activated during the duration of the start-up/service work.
5. Unlock enclosure panel by giving cover lock a quarter turn.
6. Remove burner cover panel by unlocking the two pull-down latches located on the bottom of the panel, and slide out panel.
7. Attach front enclosure panel.
8. Secure in place by rotating slotted
screw.
4.
5285 961 v1.3
7
Page 8
Initial Start-up and Service
Procedure (Overview)
Initial start-up steps
Service steps
I I I I I S I S I S I S I S
S I S I S I
S
S
1. Fill heating system with water Page 9................................................................................................................
2. Check power supply connection Page 11..............................................................................................................
3. Select language (if required) Page 12.....................................................................................................................
4. Heating contractor address input Page 12...........................................................................................................
5. Select appropriate gas type Page 13......................................................................................................................
6. Measure static pressure and running pressure Page 13.................................................................................
7. How the Vitodens 200 boiler operates... Page 15............................................................................................
8. Check CO2setting Page 16........................................................................................................................................
9. Clock natural gas meter Page 17..............................................................................................................................
10. Check orifice size Page 17..........................................................................................................................................
11. Check all primary and secondary circuit connections for leaks Page 18................................................
12. Perform c ombustion analysis Page 18...................................................................................................................
13. Check venting system for leaks (circular air gap measurement) Page 18..............................................
14. Disassemble burner and check burner gasket Page 19..................................................................................
15. Visually check exterior of burner mesh assembly Page 19...........................................................................
S
S
S
S
S I S I S I S I S
S I I I
16. Replace burner mesh assembly (if wire mesh is damaged) Page 19........................................................
17. Check and adjust ignition and ionization electrode Page 20........................................................................
18. Check condensate drain Page 20.............................................................................................................................
19. Check neutralization unit (if applicable) Page 21................................................................................................
20. Clean combustion chamber/heat exchanger surfaces, and mount burner Page 21...........................
21. Check diaphragm expansion tank and system pressure Page 22...............................................................
22. Check functioning of safety valves Page 22.......................................................................................................
23. Check electrical connections Page 23....................................................................................................................
24. Check gas pipes and fittings for leaks Page 23.................................................................................................
25. Measure ionization current Page 24........................................................................................................................
26. Verify programming unit system coding addresses Page 24.......................................................................
27. Check extension kit for heating circuit with mixing valve Page 25..........................................................
28. Check Dekamatik-HK Page 26....................................................................................................................................
8
5285 961 v1.3
Page 9
Steps
Initial Start-up and Service
Initial start-up
Air vent
1. Fill heating system with water
1. Open system isolation valves (if
installed).
2. Check inlet pressure of the diaphragm expansion tank.
3. To remove debris and/or sludge ensure that the system piping is flushed out. Failure to do so could cause settlement in the boiler causing overheating and damage not covered by warranty.
4. Optional:
Fill the heating system with w ater at the boiler filling and drain tap and drain air completely from the system at ball valve barb fitting
Max. boiler
operating pressure ......45 psig
Min. boiler
operating pressure ......12 psig
Pressure relief valve ......30 psig
Please note:
Before filling the heating system with water, check that all necessary flow check valves are installed.
If the nitrogen pressure of the precharged expansion tank is less than the static pressure of the system, inflate membrane pressure to slightly exceed pressure of system. The static pressure required at the tank is based upon the static height of the system. The system fill pressure value must be equal to the expansion tank pressure value at approx. 60 ºF/15.6 ºC.
System fill pressure must be approximately 3 psig higher than t he static head when the system is cold.
Water treatment should be considered in areas where it is known that boiler feed water contains a high mineral content and hardness.
.
In areas where freezing might occur, an antifreeze may be added t o the system water to protect the system. Please adhere to the specifications given by the antifreeze m anufacturer. Do not use automotive silicate-based antifreeze. Please observe that an antifreeze/water mixture may require a backflow preventer within the automatic water feed and influence components such as diaphragm expansion t anks, radiation, etc. A 40% antifreeze content will provide freeze-up protection to -10°F/-23°C. Do not use antifreeze other than specifically made for hot water heating systems. System a lso may contain components which might be negatively affected by antifreeze. Check total system frequently when filled with antifreeze.
5285 961 v1.3
9
Page 10
Initial Start-up and Service
Steps (continued)
Initial start-up
1. Fill heating system with water (continued)
5. Check system pressure and open
ball valve
6. Shut off the boiler from the heating system on heating water side (close shutoff valve
7. Connect drain hose to drain valve
or .
8. Open drain valve the boiler with system pressure until noise due to the presence of air is eliminated.
9. Close drain valve open ball valve
10. Check system pressure.
11. Ensure proper/adequate fuel supply
exists. Open gas shutoff valve.
).
or and vent
or and
.
Water flow
Air vent
10
5285 961 v1.3
Page 11
Steps (continued)
Initial Start-up and Service
Initial start-up
2. Check power supply connection
A power module is supplied with the Vitodens 200 boiler, which r equires a 120 VAC power supply from a wall receptacle. The module contains a 120/230 VAC step-up transformer to power the Vitodens 200 with 230 VAC. Refer to the Installation Instructions shipped with the module for wiring details and/or Installation Instructions of the boiler.
Voltage range
The voltage at connector 230 V (see wiring diagram).
Neutral conductor
The electrical power supply must have a neutral conductor.
must be
IMPORTANT
In Canada all electrical wiring is to be done in accordance with the latest edition of CSA C22.1 Part 1 and/or local codes. In the U.S. use the National Electrical Code ANSI/NFPA
70. The heating contractor must also comply with both the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI, ASME CSD-1.
Please note:
The outer conductor ”L” and the neutral conductor ”N” must not be interchanged. See wiring diagram in section entitled ”Additional Information” in this manual.
5285 961 v1.3
11
Page 12
Initial Start-up and Service
Steps (continued)
Initial start-up
LANGUAGE / LANGUE
>ENGLISH:.................A
>FRANÇAIS:...............B
>BACK / RETOUR: ......D
Initial start-up
HEATING CONTRACTOR INPUT NAME/TEL.:
TEL.: >CHANGE: -/+ >POSITION FORWARD:A
>POSITION BACK: ......B
>INSTALLER SETUP: ...D
3. Select language (if required)
Menu-driven programming unit.
Open cover: Menu option Button
SYSTEM DFACTORY SETTING ALANGUAGE C
Select language.
4. Heating contractor address input
Menu-driven programming unit.
This option allows the system user to access name and telephone number of the heating contractor on the display (see Vitodens 200 Operating I nstructions) almost immediately after a system fault has occurred.
Open the cover: Menu option Button
→ SYSTEM D” → INSTALLER SETUP C” → CODE PLEASE: B-C-C-B” → DIAGNOSIS A” → HEATING
CONTRACTOR C” Position cursor as required using the ”A”and”B” buttons. Select the required characters (number, letter, special character) by turning the ”G” selector knob (turn clockwise or counterclockwise).
Sequence of available characters:
0123456789ABCDEF GHIJKLMNOPQRSTUV WXYZ=<>.:k ?,–i/()
12
Characters already selected can be deleted with the space character ”k”or overwritten with another character.
Upon exiting the input menu (INSTALLER SETUP ”C”), name and telephone number of the heating contractor are automatically stored.
5285 961 v1.3
Page 13
Steps (continued)
Initial Start-up and ServiceInitial Start-up and Service
Initial start-up
The Vitodens 200 boiler is for use with gases whose characteristics fall within the following ranges. Do not use any other types of gas.
Heating value (gross) Btu/ft Specific gravity 0.57 to 0.70 1.522 to 1.574 Ultimate carbon dioxide (CO2) % 11.7 to 12.2 13.73 to 13.82
Service
Initial start-up Service
PE
outlet
5. Select appropriate gas type
1. Ensure that the fuel type listed on
the boiler rating plate is the correct type for the installation being attempted.
2. Record fuel type in Maintenance Record on page 70.
Natural gas Propane gas
3
6. Measure static pressure and running pressure
Static pressure
1. To measure static and/or running
pressure remove burner cover panel as per the removal and reinstallation instructions on page 7 in these instructions.
2. Close gas shutoff valve (field supplied).
3. Loosen screw in test nipple ”PE” A on the gas combination valve, do not remove completely. Connect manometer.
970 to 1100 2466 to 2542
IMPORTANT
A CO measurement (see page 16 must be taken before and after working on gas appliances to eliminate risks to health and to guarantee the satisfactory condition of the system.
A
inlet
Measuring static gas supply pressure, using test nipple “PE”
5285 961 v1.3
4. Open the gas shutoff valve.
5. Measure static pressure. Values
must be:
H 14“w.c.max.forNG H 14“w.c.max.forLP
6. Enter measured value into Maintenance Record on page 70 in this manual.
7. Start up boiler, using the on/off switch on the boiler control.
IMPORTANT
The burner is automatically ignited and starts operation after a safety time has elapsed. During initial start-up, the unit may indicate a fault because of air in the gas supply pipe (especially for propane gas).
After approx. 5 seconds, press the ”EU
button to reset the burner. The ignition procedure is repeated. This boiler employs a direct spark ignition system.
13
Page 14
Initial Start-up and Service
Steps (continued)
Initial start-up Service
6. Measure static pressure and running pressure (continued)
Running pressure
8. Measure the running pressure; value
must be:
Running supply pressure with Corrective action Natural gas Propane gas
Hunder 4 ”w.c. (WB2-44) Hunder 7 ”w.c. (WB2-60)
H4 to 14 “w.c. (WB2-44) H7 to 14 “w.c. (WB2-60)
over 14 ”w.c. over 14 ”w.c. Do not attempt adjustment. Call local
9. Enter gas type into Maintenance Record on page 70 in this manual.
10. Switch off t he heating system on/off switch on the boiler control unit (boiler is shut down), close the gas shutoff valve, remove the manometer and re-tighten the screw in the test nipple ”PE” A.
under 11 ”w.c. Do not attempt adjustment. Call local
11 to 14 ”w.c. Start up boiler.
Use suitable measuring instruments calibrated with a minimum resolution of 0.04 “w.c. for measuring the running pressure.
gas utility to increase pressure.
gas utility to decrease pressure. Boiler valve must not be exposed to pressure over 14 ”w.c.
WARNING
Ensure that there is no open flame in the room.
PE
outlet
A
inlet
Measuring running gas supply pressure, using test nipple “PE”
11. Open gas shutoff valve and check that the test nipple ”PE” and all gas connections are gas-tight.
WARNING
Never purge a gas line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for purpose of checking leakage. Use a soap-and-water solution to check for leakage. A failure to follow this warning could result in fire, explosion, personal injury, or death.
5285 961 v1.3
14
Page 15
Steps (continued)
Initial Start-up and Service
Initial start-up Service
7. How the Vitodens 200 boiler operates...
The MatriX burner blower and the combination gas valve are factory calibrated and pre-adjusted for optimum boiler performance at all firing rates through a non-mechanical, pneumatic modulating link between combustion air and gas flows. Blower speed is automatically increased or decreased based on heat demand and venting system resistances, thereby regulating the amount of combustion air drawn. The pneumatic modulating link between air and gas introduces the required amount of gas for correct combustion to meet the current heat demand, based on a linear relationship between PairandPgas. Optimum combustion air flow rate is recognized and monitored by the differential air pressure sensor (transducer). The output voltage signal of the transducer is analyzed for logic by the LGM 29.XX burner ignition control unit. The LGM 29.XX unit contains pre-programmed performance curves and operational safety parameters unique for every boiler model. See page 47 for sequence of operation.
Flue gas adaptation function
The Vitodens employs a flue gas adaptation function. This unique function records, processes, and reacts in real time to fluctuations in pressure drops in the vent pipe during normal operation caused by partial pipe blockages due to ice formation at the vent termination, debris and/or sudden high winds. Such increase in pressure drop, if not promptly corrected, will reduce the combustion air flow rate, and hence lead to unstable combustion. The differential air pressure sensor (transducer) records such pressure drops and supplies voltage signals to the LGM
29.XX burner ignition control unit which, in turn (based on stored performance curves and safety parameters), initiates prompt adjustment of the blower rotational speed, thus readjusting the combustion air flow rate for optimum combustion. The same automatic adaptation logic applies if combustion air is reduced (or increased) due to slower (or faster) blower speed resulting from line voltage drops (or increases) below (or above) the threshold of 85% (or 110%).
outlet
X
Do not adjust screws X and Y!
5285 961 v1.3
Y
PE
inlet
WARNING
FOR FACTORY CALIBRATING PURPOSES, THE COMBINATION GAS VALVE IS EQUIPPED WITH ADJUSTMENT SCREWS X AND Y. DO NOT ATTEMPT TO ADJUST OR READJUST THESE SCREWS. ANY ATTEMPT TO TAMPER WITH FACTORY PRE-ADJUSTED SETTINGS WILL LEAD TO UNSTABLE OPERATION AND WILL AFFECT BOILER WARRANTY.
15
Page 16
Initial Start-up and Service
Steps (continued)
Initial start-up Service
The Vitodens 200 boiler is factory preset for operation with natural gas or propane. It is recommended t hat a CO check be performed at the boiler vent pipe adaptor as part of the initial start-up/maintenance procedure.
IMPORTANT
The MatriX burner of the Vitodens 200 is preset for the entire gas group. No adjustment or readjustment of the burner is required.
8. Check CO2setting
Depending on the gas type, the CO value lies within the range of H 6.6 to 10.0% for natural gas
2
H approx. 10.0 % for LP
The CO compared with the above CO ranges of the individual gas type.
1. Connect flue gas analyzer to boiler
2. Open the gas shutoff valve and start
3. Trigger a call for heat by adjusting
4. Select lower end of rated input
value measured must be
2
vent pipe adaptor measurement opening).
up the boiler.
the setpoint value.
range and check CO
SYSTEM DINSTALLER
SETUP C”
→ CODE PLEASE B-C-C-B” → DIAGNOSIS A” → RELAY TEST A”
Select menu option CONTINUE ”A” until code
10: MODULATION
10: <PL.90> CLOSED 10: BURNER 10: <PL.41> ON 10: is displayed
(”Flue gas”
content.
2
2
value
If the CO
2
than 1% outside the stated range for NG, or 0.5% outside the stated range for LP, perform the following steps: H Check that correct orifice was used
(see subsection entitled “Check orifice size” on page 17 and section “Technical Data” on page 46 of this manual).
H Check the venting system for leaks
(see subsection entitled “Check venting system f or leaks” on page 18 of this manual).
value measured lies more
2
IMPORTANT
Do not use the emissions test switch
S” to trigger a call for heat.
16
5. Select top end of rated input range
and check CO
If the value differs by more than one percentage point, replace burner. Select menu option CONTINUE ”A”
until code 11: MODULATION
10: <PL.90> OPEN 10: BURNER 10: <PL.41> ON 10: is displayed
6. Exit the setting mode
H Close cover of programming unit. H Enter the measured values into
Maintenance Record on page 70 in this manual.
H Close flue gas measurement
opening
content
2
.
5285 961 v1.3
Page 17
Steps (continued)
Initial Start-up and Service
Initial start-up Service
Clock natural gas meter to verify input
1. Ensure all other gas equipment
served by the meter is turned off during timing of gas input to the Vitodens 200 boiler.
2.Measure the time in seconds it takes for the boiler to use 10 cu. ft. of gas. Divide 3600 x 10 by the number of seconds and you get the number of cu. ft. of gas used per hour. Multiply this number by the heating value of the gas to obtain Btu per hour input.
Service
9. Clock natural gas meter
For example: A Vitodens 200, WB2 11-44 boiler (172 000 Btu/h input) requires 209 seconds to use 10 cu. ft. of natural gas. After contacting the local utility, you will find the heating value is 1000 Btu per cu. ft. Therefore, 3600 x 10/209 x 1000 172 000 Btu/h input. Therefore, the boiler input is correct.
Burner input formulas (for low altitude only):
INPUT=(3600 t=TIME (sec.) f or 1 ft.
INPUT=(3600 x .01 x 1000 x 35.31)÷T where T = TIME (sec.) for .01 m
10. Check orifice size
÷t) x 1000 where
3
3
natural gas
IMPORTANT
A boiler underfired by 5% is acceptable. Do not overfire the boiler.
CAUTION
Always contact your gas utility to obtain the correct heating value before clocking the meter.
E
ACB
Stamped identification code
1. Remove burner cover panel (if still installed) as per the removal and reinstallation instructions on page 7 in this manual, and reinstall panel upon completion of service work.
2. Loosen screws A and take the gas orifice holder C out of the fitting.
3. Read orifice size stamped on the orifice body and cross-reference to table below. If wrong orifice is installed, proceed to next step.
4. Push the gas orifice B sideways out of the gas orifice holder C.Snap new and correct gas orifice into gas orifice holder and push into the gas train.
5. Tighten screws A. Tighten to a torque of 1.1 lb.ft./
6. Check all gas connections for leaks
with an approved leak test solution.
Overview of orifices
Boiler model
Natural gas E44 E60
Liquid propane P44 P60
WB2 11-44 WB2 15-60
See section entitled “Technical Data” on page 46 of this manual for information on gas orifices.
IMPORTANT
Place O-ring E in groove on new gas orifice B.
1.5 Nm.
5285 961 v1.3
17
Page 18
Initial Start-up and Service
Steps (continued)
Initial start-up Service
Initial start-up Service
11. Check all primary and secondary circuit connections for leaks
Check heating system a nd domestic hot water connections (if applicable). Ensure all connections are pressure tight. Correct any leaks found on fittings, pumps, valves, etc.
12. Perform c ombustion analysis
IMPORTANT
A CO measurement (see page 16) must be taken before and after working on gas appliances to eliminate risks to health and to guarantee the satisfactory condition of the system.
Record the measured combustion values in the sequence stated in the Maintenance Record on page 70 in this manual.
Initial start-up
Combustion air measuring point
13. Check venting system for leaks (circular air gap measurement) For sealed combustion, coaxial vent only.
Viessmann strongly recommends that the heating contractor perform a simplified leak test during boiler start-up. For this purpose it is sufficient to measure the CO the combustion air in the coaxial gap of the air intake pipe. The vent pipe is considered sufficiently leak-proof if a
concentration in the combustion
CO
2
airnohigherthan0.2%oranO concentration no lower than 20.6% is measured.
concentration of
2
2
If higher CO are measured, check venting system thoroughly.
Please note!
The vent pipe adaptor comes with two measurement ports, one for combustion air intake measurement and one for flue gas measurement.
Please note!
This test is not applicable for single ­wall venting system (non-sealed combustion).
values or lower O2values
2
18
5285 961 v1.3
Page 19
Steps (continued)
Initial Start-up and Service
Service
14. Disassemble burner and check burner gasket
1. Remove burner cover panel (if still
installed) as per the removal and reinstallation instructions on page 7 in this manual, and reinstall panel upon completion of service work.
2. Switch off the heating system switch on the control unit and the power supply.
3. Close gas shutoff valve and secure.
4. Disconnect electrical cables from fan
motor sensor
transformer
5. Remove two screws disconnect gas line from gas valve.
6. Loosen six hexagon socket head cap screws
7. Check burner gaskets for damage and replace if required (see Parts List).
, differential a ir pressure
, combination gas valve
, ionization electrode , ignition
and grounding .
to
and remove burner.
Do not lay burner on burner mesh assembly (wire mesh)!
CAUTION
5285 961 v1.3
Service
Service
15. Visually check exterior of burner mesh assembly
To check the exterior of the burner mesh assembly for physical damages, such as dents, corrosion and/or abnormally large holes:
1. Remove burner cover panel, if still installed (see page 7). Reinstall panel upon completion of service work.
16. Replace burner mesh assembly (if wire mesh is damaged)
1. Remove electrodes .
3. Turn thermal insulation ring
clockwise and remove.
2. Unsrew the eight Torx screws and remove burner mesh assembly
and assembly gasket .
3. Remove existing burner mesh assembly gasket .
4. Fit new burner mesh assembly with the new gasket and tighten with the eight Torx screws.
IMPORTANT
Do not replace gasket inspecting the exterior of the mesh assembly.
Tighten to a torque of 3.3 lb.ft. /
4.5 Nm
when visually
19
Page 20
Initial Start-up and Service
Steps (continued)
Service
17. Check and adjust ignition and ionization electrode
1. Remove burner cover panel (if still
installed) as per the removal and reinstallation instructions on page 7 in this manual, and reinstall panel upon completion of service work.
2. Check electrodes for wear and contamination.
3. Clean electrodes with small brush or emery paper.
4. Check clearances. If clearances are
CAUTION
Do not damage wire mesh when cleaning.
not satisfactory or the electrodes are damaged, replace electrodes and gasket A and align. Tighten fastening screws for the electrodes to a torque of 1.5 lb.ft. / 2Nm.
+4
8
-0
+3
5
-0
3
+0.5
-0
+0
7
-1
Service
20
18. Check condensate drain
Ensure condensate drains freely (e.g. at siphon trap
).
If necessary, clean siphon trap.
Discharge tubing Flexible discharge tubing Siphon trap
IMPORTANT
If the condensate does not drain freely, condensate will accumulate in bottom part of boiler resulting in a burner shut-down (fault message).
Installation Instructions Neutralization Unit (if applicable)
5285 961 v1.3
Page 21
Steps (continued)
Initial Start-up and Service
Service
Service
19. Check neutralization unit (if applicable) Accessory
1. Check the pH value of the
condensate with pH measuring strip. If the pH value is less than 6.5, replace granulate.
2. If contaminated: Rinse neutralization unit with tap water.
3. Add granulate as marked.
IMPORTANT
pH measuring strip must be field supplied.
IMPORTANT
The granulate is consumed as it neutralizes the condensate. The red marking indicates the min. filling level.
Installation Instructions Neutralization Unit
20. Clean combustion chamber/heat exchanger surfaces, and mount burner
1. Remove burner cover panel (if still
installed) as per the removal and reinstallation instructions on page 7 in this manual, and reinstall panel upon completion of service work.
2. If necessary, clean the combustion chamber surfaces with water. Use solvent-free cleaning agents to remove residues: H Remove deposits of soot with
alkaline agents containing tenside.
H Remove coatings and (yellowish
brown) surface discoloration with phosphoric acid-based “Antox 75 E Plus”, or citric acid-based CitriSurft 3050 by Stellar Solutions Inc.
H Rinse thoroughly with water.
3. Mount burner and tighten diagonally to a torque of 3.3 lb.ft. / 4.5 Nm (six hexagon socket head cap screws).
4. Fasten threaded connection for the gas connection hose with a new O-ring.
5. Connect electrical cables to corresponding parts.
and heat exchanger with a brush and/or rinse
Please note:
Be careful not to scratch parts which are in contact with flue gas. Use plastic brushes, not wire brushes!
The cleaning agents must not contain hydrocarbon-based solvents or potassium.
WARNING
Follow cleaning agent manufacturer’s safety instructions and wear appropriate protective equipment.
IMPORTANT
Perform leak test.
5285 961 v1.3
21
Page 22
Initial Start-up and Service
Steps (continued)
Initial start-up Service
21. Check diaphragm expansion tank and system pressure
Perform check with the system cold.
1. Drain boiler/system and reduce pressure until the manometer reading is ”0”.
2. If the nitrogen pressure of the precharged expansion tank is less than the static pressure of the system, inflate membrane pressure to slightly exceed pressure of system. The static pressure required at the tank is based upon the static height of the system. The system fill pressure value must be equal to the expansion tank pressure value at approx. 60 ºF/15.6 ºC.
3. Top up with water until filling pressure is higher than the inlet pressure of the diaphragm expansion tank.
Example
Static head of 33 ft./10 m (distance between boiler and topmost heat emitter surface) corresponds to a static pressure of 1 bar/15 psig.
With the system cold, the filling pressure must be approx. 3 psig higher than the static pressure. Max. operating pressure:
........................................
Min. operating pressure:
........................................
45 psig
12 psig
Initial start-up Service
4. When starting up the system for the
first time, mark this value as the minimum filling pressure on the manometer.
22. Check functioning of safety valves
Ensure proper operation of low water cut-off(s) (if applicable), pressure relief valve, and pump(s).
Check pressure gage, air vent and pressure relief valve. Ensure that pressure relief valve does not leak and that it operates in accordance with information provided by the manufacturer.
Refer to maintenance instructions supplied with low water cut-offs, pumps, etc.
Flush float water type low water cut-offs (if used).
A lower manometer reading usually indicates loss of water due to leakage. All leaks must be repaired.
Follow local regulations with respect to backflow preventers.
If oil-lubricated pumps are used, ensure proper lubrication.
If motorized zone valves are used, refer to maintenance instructions provided with zone valves.
22
5285 961 v1.3
Page 23
Steps (continued)
Initial Start-up and Service
Initial start-up Service
Initial start-up Service
23. Check electrical connections
Ensure all plug-in connectors and strain reliefs make positive contact and are seated properly.
24. Check gas pipes and fittings for leaks
WARNING
The gas supply piping must be leak tested before placing the boiler in operation.
Installation Instructions Power/Pump Module
CAUTION
Ensure all joints of gas line are pressure tight and that gas valves do not leak when under normal operating pressure (use approved leak detection liquid).
5285 961 v1.3
23
Page 24
Initial Start-up and Service
Steps (continued)
Service
B
D
25. Measure ionization current
IMPORTANT
Switch off heating system on the control unit before connecting the measuring instrument.
1. Remove burner cover panel (if still
installed) as per the removal and reinstallation instructions on page 7 in this manual, and reinstall panel upon completion of service work.
2. Connect a DC μA multimeter in series with the ionization cable as follows: a)Disconnect the socket of the
ionization cable ionization electrode connect to the plug of the multimeter via adaptor
b)Connect additional ionization
measuring cable ionization electrode socket of the multimeter.
3. Start up boiler to its maximum input: Turn emissions test switch ”S”on the control unit to ”h”.
from the
and
.
to the
and the
Please note:
The m easurement can be made with a multimeter (measuring range 0 to 100 μA).
A C
Initial start-up
4. If the ionization current is less than
5 μA H check the electrode clearance (see
page 20).
H check the power supply
connection of the control unit.
5. After completing the measurement, turn emissions test switch to ”a”.
6. Enter the value measured in the Maintenance Record on page 70 in this manual.
26. Verify programming unit system coding addresses
The control unit must be adjusted according to the system equipment. See H page 48 onwards for programming unit. For details on coding procedure and for an overview of the coding addresses, see H page 50 onwards for programming unit.
Please note:
The minimum ionization current must be at least 5 μA when the flame is formed (approx. 2- 3 seconds after opening the gas combination valve).
24
5285 961 v1.3
Page 25
Steps (continued)
Initial Start-up and Service
Initial start-up
A
B
DC
27. Check extension kit for heating circuit with mixing valve Accessory
1. Check via Scan 1 on the
programming unit whether the connected extension kit is recognized.
Please note:
The third and fourth-placed digits from the left have the following meaning:
(__ 02 _ _ = with burner control unit
5
4
6
3
7
8
2
9
1
0
10
5
4
6
3
+
-
i
7
8
2
1
S
9
10
Calling up Scan 1
Open the cover: Menu option Button
SYSTEM DOPERATING
STATUS B”
CONTINUE A”
until ”Scan 1” is displayed
(__12 _ _)= additionally with Vitocom
100
(__ 03 _ _ = with burner control unit
and variable speed heat circuit pump
(__13 _ _)= additionally with Vitocom
100
(__ 06 _ _ = with burner control unit
and extension kit for heating circuit with mixing valve
(__16 _ _)= additionally with Vitocom
100
(__ 07 _ _ = with burner control unit,
extension kit for heating circuit with mixing valve and variable speed heating circuit pump
(__17 _ _)= additionally with Vitocom
100
2. If the extension kit is not recog­nized, check the coding of the heating system type (see page 49).
Please note:
The extension kit is only recog­nized when connected via the KM-BUS, not when connected via the Viessmann 2-wire BUS.
Rotational direction switch Power supply switch ” ”
5285 961 v1.3
I II
Check mixing valve motor
1. Select rotational direction of the
mixing valve motor. H Switch setting I for boiler return
from left (factory default setting).
Please note:
Please reference Installation Instructions of Mixing Valve Actuator.
H Switch setting II for boiler return
from right.
2. Relay test Switch power supply switch on the motor off and on again. The unit will
1
0
perform the following self-test:
H Close mixing valve (150 sec) H Pump ON ( 10 sec) H Open mixing valve ( 10 sec) H Close mixing valve ( 10 sec)
After that normal control mode is resumed.
3. Observe the rotational direction of the mixing valve motor during the automatic relay test of the extension kit. Afterwards, position the mixing valve by hand in t he ”Open” setting.
The supply temperature sensor must now measure a higher temperature. If the temperature is lower, either the rotational direction of t he motor is incorrect or the mixing valve insert is incorrectly fitted.
25
Page 26
Initial Start-up and Service
Steps (continued)
Initial start-up
141
WHBNGN
21 23
22 24
141
X5
2341
28. Check Dekamatik-HK Accessory
1. Check via Scan 2 on the
programming unit whether the connected expansion module is recognized.
Expansion module
The last-placed digit has the following meaning: 2____0 =Viessmann 2-wire BUS
expansion module not
Calling up Scan 2
YE
Open the cover:
2____1 =Viessmann 2-wire BUS
Menu option Button SYSTEM D”
recognized
expansion module is recognized
OPERATING
STATUS B”
CONTINUE A”
until ”Scan 2” is displayed
Dekamatik-HK
The second-placed digit from the left has the following meaning: _2____ =Extension kit for a heating
circuit with mixing valve or Dekamatik-HK1/-HK 2 recognized
_3____ =Dekamatik-HK4 recognized
2. If the expansion module or the Dekamatik is not recognized, check that they were installed correctly.
Please note:
A green LED will flash on the expansion module if the data BUS is intact. If the LED is not lit, the data line ”X5.3”- ”X 5.4” may be incorrectly connected.
Check setting of rotary switch
H Dekamatik-HK1:
The rotary switch on the communication module must be set to ”4”.
H Dekamatik-HK2:
The rotary switch on the circuit board E4 must be set to ”4”.
H Dekamatik-HK 4:
The rotary switch on circuit board E4.1 must be set to ”4” and the rotary switch on circuit board E4.2 to ”5”.
See wiring diagram in section entitled ”Additional Information”.
Please note:
Please reference corresponding installation documentation for Dekamatik-HK.
26
5285 961 v1.3
Page 27
Troubleshooting Steps
Diagnosis 1. Establish fault message or diagnose behavior of system.
2. Look for corresponding cause of fault in the diagnostics table. Diagnosis H for faults with fault display on control unit (see below).
Please note:
See page 28 for retrieval of fault codes from the fault memory.
H for faults without fault display on control unit (page 38).
3. Find corrective action in the table.
Correction 4. Perform corrective action (page 39).
Diagnosis
Faults with fault display on control unit
When a fault message is detected, ––––FAULT–––– flashes in the display of the programming unit with the cover closed.
Troubleshooting
FAULT SEARCH
FAULT:
OUTDOOR TEMP. SENSOR
>HEATG. CONTRACTOR: >ACKNOWLEDGE: A
DIAGNOSIS/SENSORS
01: OUTDOOR TEMP.
HC A 01: OPEN CIRCUIT
>CONTINUE:..............A
>BACK: ...................B
>INSTALLER SETUP: ..D
To trace the fault
1. Open cover:
FAULT SEARCH A”. Fault code is displayed.
2. Close the cover.
To reset the burner
If red light is on or flashing:
1. Press the ”EU” button once to reset
the burner.
Display window Reset button Burner fault indicator
Find nature of sensor fault in plain language
Open the cover: Menu option Button
→ MAIN MENU D” → SYSTEM D” → INSTALLER SETUP C” → CODE PLEASE: B-C-C-B → DIAGNOSIS A” → SCAN SENSORS B”
Please note:
The fault message is cleared when ”ACKNOWLEDGE” is selected. If an acknowledged fault is not corrected by 24:00 hrs on the same day, the fault message will reappear. The acoustic alarm system (only with optional expansion board installed), is not reactivated. The meaning of the fault codes is explained in the table starting on page 30.
Please note:
Please refer to the diagnostics table starting on page 30 for details on required action.
5285 961 v1.35285 961 v1.3
Select defective sensor with the menu option CONTINUE ”A”.
27
Page 28
Troubleshooting
Diagnosis (continued)
Retrieval of fault codes from the fault memory
1. Open the cover:
Menu option Button
5
4
6
3
7
8
2
9
1
0
10
5
4
6
3
+
--
A
B
DC
7
i
8
2
S
9
1
10
→ SYSTEM D” → INSTALLER SETUP C” → CODE PLEASE: B-C-C-B” → CODING 2 C”
2. H Select coding address ”0B2” by pressing button ”A” (CONTINUE) or ”B”(BACK).
H With the ”G” selector knob
Please note:
All settings are made in the ”Installer Setup” menu, containing ”Coding 1” (the main coding addresses in plain language) and ”Coding 2” (all coding addresses).
Changes which are made and confirmed in Coding 1 are automatically transferred t o Coding 2 and vice versa.
(CHANGE), set the value of the coding address to ”001”.
H Confirm the change with
button ”D”.
3. Select coding address ”0B3”. The value which appears is the most
recent fault code (value in brackets () in the diagnostics table).
4. Repeat step 2, but set value of
“0B2” coding address to ”002”. The
Please note:
10 fault codes can be scanned.
new value which appears under coding address ”0B3” is the next fault code.
Fault code displayed on programming unit
Fault history code displayed
Fault: F9 249
Fault: FD 253
Fault: FE 254
Fault: 02 002
Fault: 04 004
Fault: 05 005
Fault: 06 006
Fault: 07 007
Fault: 08 008
Fault: 14 020
Fault: 15 021
Fault: 0A 010
Fault: 0B 011
Fault: 0C 012
Fault: 0D 013
Fault: 0E 014
Fault: 0F 015
Fault: CC 204
28
5285 961 v1.3
Page 29
Diagnosis (continued)
Sequence of operation and potential faults during each start-up cycle
Check water flow switch. Replace
if necessary.
Check cabling and plug-in connectors of the
blower , as well as blower itself.
Check differential air pressure sensor.
Seepage34.
Troubleshooting
Fault 06
Display message
no
5285 961 v1.3
no
Water flow switch activates
plug 33.
no
after approx. 70 seconds
no
Fault 94
see page 34
29
Page 30
Troubleshooting
Diagnosis (continued)
Display window
Reset button
Burner fault indicator
Control unit for weather-responsive operation with programming unit
Diagnostics table: Faults with fault display on control unit
Fault message in display window
Control unit for weather-responsive operation with programming unit
FAULT: OUTDOOR TEMP. SENSOR
FAULT: OUTDOOR TEMP. SENSOR
FAULT: SUPPLY TEMP. SENSOR
FAULT: SUPPLY TEMP. SENSOR
FAULT: BOILER TEMP. SENSOR
FAULT: BOILER TEMP. SENSOR
FAULT: SUPPLY TEMP. SENSOR
FAULT: SUPPLY TEMP. SENSOR
FAULT: TANK TEMP. SENSOR
Burner System behavior fault indicator (red)
OFF Boiler operates based on 32 ºF/0 ºC outdoor temperature.
OFF Boiler operates based on 32 ºF/0 ºC outdoor temperature.
OFF Supply temperature of heating circuits too low.
OFF Supply temperature of heating circuits too low.
OFF Boiler cools down.
OFF Boiler cools down.
OFF Mixing valve is opened.
OFF Mixing valve is closed.
OFF DHW tank cools down.
FAULT: TANK TEMP. SENSOR
FAULT: EXT.PROG.2
30
OFF DHW tank cools down.
ON Boiler cools down
5285 961 v1.35285 961 v1.3
Page 31
Cause of fault Corrective action
Troubleshooting
Short circuit – outdoor temperature sensor Check outdoor temperature sensor (see page 40).
Open circuit – outdoor temperature sensor Check outdoor temperature sensor (see page 40).
Short circuit – low-loss header temperature sensor Check supply temperature sensor (see page 40).
Open circuit – low-loss header temperature sensor Check supply temperature sensor (see page 40).
Short circuit – boiler temperature sensor Check boiler temperature sensor (see page 40).
Open circuit – boiler temperature sensor Check boiler temperature sensor (see page 40).
Short circuit – supply temperature sensor See Installation Instructions Mix. Valve Actuator.
Open circuit – supply temperature sensor See Installation Instructions Mix. Valve Actuator.
Short circuit – tank temperature sensor Check tank temperature sensor (see page 41).
See coding address “000” (see page 49). See coding address “0B8” (see page 56).
Open circuit – tank temperature sensor Check tank temperature sensor (see page 41).
See coding address “000” (see page 49). See coding address “0B8” (see page 56).
Internal BUS fault Replace VR20 (see page 61).
Replace LGM 29 (see page 62). Replace entire control console.
See coding address “000” (see page 49). See coding address “0B8” (see page 56).
See coding address “000” (see page 49). See coding address “0B8” (see page 56).
5285 961 v1.3
31
Page 32
Troubleshooting
CONTROLUNIT
Diagnosis (continued)
Diagnostics table: Faults with fault display on control unit (continued)
Fault message in display window
Burner fault
System behavior
indicator (red)
FAULT: 70 RS
/WS REMOTE
CONTROL FAULT: 78
RS
/WS REMOTE
CONTROL FAULT: A1
KM-BUS BURNER CONTROL UNIT
OFF Operates based on 68 ºF/20 ºC desired daytime
temperature, 58 ºF/14 ºC desired nighttime temperature.
OFF Operates based on 68 ºF/20 ºC desired daytime
temperature, 58 ºF/14 ºC desired nighttime temperature.
Flashes Boiler operates in emergency mode
(after approx. 30 min. BUS fault).
OFF Boiler cools down.
FAULT: A2 OFF –– FAULT: A5
KM-BUS MIXING VALVE
OFF ––
FAULT: B1 OFF DIP switches A and B on back of are switched
(e.g. A-A or B-B).
FAULT: B2 OFF Boiler cools down.
FAULT: B3 OFF Setting via service level not possible. FAULT: B6
BURNER CONTROL UNIT DEFECTIVE
FAULT: CC
*1
(204
)
OFF Boiler cools down.
ON Burner control unit switches to lockout
(due to large line voltage fluctuations). FAULT: C8 OFF Boiler does not activate. FAULT: C0 OFF Boiler does not activate. FAULT: E4 or E... OFF ––
FAULT: F2 OFF –– FAULT: F5 OFF ––
FAULT: F9
*1
(249
)
FAULT: FB Flashes ––
FAULT: FD
*1
(253
)
*1
Displayed when fault codes retrieved from fault memory.
32
OFF/ON Burner control switches to lockout.
ON Burner control switches to lockout.
5285 961 v1.3
Page 33
Troubleshooting
p
p
y
p
fieldsuppliedconnections(byprocessofeliminationif
Cause of fault Corrective action
Short circuit – WS/RS remote control unit Check WS/RS remote control unit (see page 44).
Open circuit – WS/RS r emote control unit or wrong coding
Internal BUS fault
Open circuit – internal BUS connection
Check WS/RS remote control unit (see page 44).
Check proper system coding.
Verify connections X5.3 and X5.4 for mixing valve (if applicable). Check that circuit board VR20 is inserted properly and check field su required). Check coding of LGM 29 c omponent part. Replace circuit board VR20 or circuit board of burner control unit LGM 29 (see page 61).
lied connections (b
rocess of elimination if
KM-BUS fault to Vitocom Check connection to Vitocom or Vitocom defective. Short circuit/open circuit – BUS connection to extension
kit for heating circuit with mixing valve
Check connection of extension kit for heating circuit with mixing valve (see page 25). Check coding for system with a mixing valve. Mixing valve might be defective.
Set DIP switches to factory default setting. See symbols on back of programming unit.
Sensor inputs are not read correctly. Check correct connection of sensors.
Data points are not stored; internal fault VR20. Replace circuit board VR20 AD-converter of burner control unit defective;
internal fault LGM 29
Check for damage on wiring harnesses. Check whether circuit board VR20 is defective. If required, replace circuit board VR20
*1
.
Replace burner control unit LGM 29
*1
*1
.
.
Differential air pressure sensor / open circuit Check wiring, replace sensor.
Differential air pressure sensor / short circuit Check wiring, replace sensor. Internal fault or fault with internal data protection Reset burner control unit. Fault in Dekamatik-HK heating circuit control unit
connected downstream
Check Dekamatik-HK heating circuit control unit connected downstream and data transmission circuit. Check wiring con-
nections. Error message to Vitocom communication unit Check Vitocom communication unit. Error message extension kit for heating circuit with mixing
valve
Check coding for extension kit and the extension kit itself.
Check sensor of mixing valve.
Parameterization of burner control defective Replace circuit board of burner control unit LGM 29
*1
.
Emergency operation LGM 29 Check plug-in connection and circuit board VR20.
Parameterization of burner control defective Replace circuit board of burner control unit LGM 29
5285 961 v1.3
Replace circuit board VR20 if necessary.
*1
.
33
Page 34
Troubleshooting
Diagnosis (continued)
Diagnostics table: Faults with fault display on control unit (continued)
Fault message in display window
FAULT: FE
*1
(254
)
FAULT: 02
*1
(002
)
FAULT: 04
*1
)
(004
FAULT: 05
*1
)
(005 FAULT: 06
*1
)
(006
FAULT: 07
*1
)
(007 FAULT: 08
*1
)
(008 FAULT: 09
*1
)
(008 FAULT: 14
*1
)
(020
Burner fault
System behavior
indicator (red)
ON Burner control switches to lockout
ON Burner control switches to lockout.
ON Burner control switches to lockout.
ON Burner control switches to lockout.
ON Burner control switches to lockout.
ON Burner control switches to lockout.
ON Burner control switches to lockout.
ON Burner control switches to lockout.
ON Burner control switches to lockout.
FAULT: 0A
*1
)
(010 FAULT: 0B
*1
)
(011 FAULT: 0C
*1
)
(012 FAULT: 0D
*1
)
(013
*1
Displayed when fault codes retrieved from fault memory.
34
ON Burner control switches to lockout.
ON Burner control switches to lockout.
Fan does not idle after auto reset (incorrect fan rpm).
ON Burner control switches to lockout.
ON Burner control switches to lockout.
5285 961 v1.3
Page 35
Cause of fault Corrective action
Troubleshooting
Internal fault burner control unit or interference Check electrode settings.
Safety chain w as activated (fixed high limit) Check fixed high limit (see page 43). Bleed air from the
Fan speed too high at start (maximum fan rpm exceeded). Fan or fan electronics defective.
Fan speed too low at start (incorrect fan rpm). Check fan and flue gas system.
Air pressure threshold for ignition level is not reached. Feedback voltage signal to LGM 29 not available.
Fan speed incorrect. Check fan and flue gas system.
Fan speed too high prior to ignition (incorrect fan rpm). Check fan and flue gas system.
Fault fan speed Check fan and flue gas system.
No flame signal Check electrical connections (see page 11).
Basic level of air pressure threshold in standby mode not correct.
Severe wind conditions in vent system. Protect outside wall vent termination from severe winds.
Check wiring harness plug X13 for proper connection or
damage.
Check whether flue gas system is leak-tight.
If after corrective action fault “FE” still appears on display
replace LGM 29.
heating system.
Replace RLS 154 electric fan control.
Replace LGM 29 and/or burner assembly.
Check fan plug, fan, differential pressure sensor (see page 41)
and inlet air damper (flapper).
Check flue gas system for proper sizing and functioning.
Purge air from gas line (for LP gas, purge air several times).
Measure ionization current (see page 24).
Check gas pressure (see page 13).
Check gas combination valve (see page 13).
Check ignition transformer.
Check ignition electrodes (see page 20).
Check condensate drain (see page 20).
Check power supply polarity (L,N,G).
Check proper grounding.
Check #158 plug on (replacement) LGM 29 is installed
Check differential air pressure sensor (see page 41).
Check wiring harness and connection to air pressure sensor.
Flame signal still present after switching off. Check gas combination valve (see page 13).
Reset button “EU“ pressed repeatedly or while burner is running.
5285 961 v1.3
Check electrode block (see page 20).
Power ON/OFF boiler / acknowledge fault.
Press reset button ”EU” once.
35
Page 36
Troubleshooting
Diagnosis (continued)
Diagnostics table: Faults with fault display on control unit (continued)
Fault message in display window
FAULT: 25 OFF Boiler operates with high boiler water temperature.
FAULT: 26 OFF Boiler operates with continuous relay test.
FAULT: 35 OFF Boiler does not activate.
FAULT: 94 OFF Boiler does not activate.
FAULT: 95 OFF Boiler does not activate. FAULT: 51 OFF No DHW function.
FAULT: 59 OFF No DHW function.
Burner fault indicator (red)
System behavior
36
5285 961 v1.3
Page 37
Cause of fault Corrective action
Troubleshooting
Emissions test switch ”S” turned to ”h” f or 30 minutes already.
Setting mode for maximum or minimum rated input active for 30 minutes already.
Reset button ”EU” pressed while burner is off with emis­sions test switch ”S” turned to ”h”.
Basic level of air pressure threshold in standby mode not correct.
Start-up prevented. Check wiring, water and gas pressures. DHW outlet sensor / short circuit Check sensor/wiring.
DHW outlet sensor / open circuit Check sensor/wiring.
Turn emissions test switch ”S”to”a”.
Set heating program selector switch to required operating
mode or close cover on programming unit.
Turn emissions test switch ”S”to”a” and press reset
button ”EU” once.
Check differential air pressure sensor (see page 41).
Check wiring harness and connection to air pressure sensor.
Fault will clear if output signal of air pressure sensor is
correct.
See coding address “000” (page 49).
See coding address “0B8” (page 54).
See coding address “000” (page 49).
See coding address “0B8” (page 54).
5285 961 v1.3
37
Page 38
Troubleshooting
Diagnosis (continued)
Diagnostics table: Faults without fault display on control unit
System behavior
Supply temperature too cold or too warm. Fuse Check fuse (see page 43).
Room temperature too cold or too warm. Thermostatic radiator valves Check thermostatic radiator
Domestic hot water temperature too cold or too warm.
Boiler constantly switches on and off. Flue gas system leaking Check flue gas system for leaks
Diagnostics table: Faults on power module
System behavior
Boiler has no power Main power on/off switch Check switch position
(main power on/off switch on boiler is in ”ON” position)
Heating pump does not operate
Cause of fault Corrective action
Variable speed heating circuit pump
Heating system type incorrectly coded
Circulating pump Check circulating pump.
Cause of fault Corrective action
Power supply or boiler is not electrically connected
Fuse F1 (located in the Power/Pump Module)
Electrical connection(s) has/have been made incorrectly.
Check coding of heating circuit pump (see page 52).
Check coding of heating system type (see page 49).
valves (see page 43).
and perform leak test.
Ensure that power cord and power supply cable to the boiler are plugged in properly.
Replace fuse with same type and of same rating (T2A/250 V, slow blow)
Ensure that – connections , , and on the mother board – connections ..., , and in the boiler junction box are made correctly.
20A
20A
38
Fuse F2A (located in the Power/Pump Module)
Replace fuse with the same type and of same rating (T10A/250 V, slow blow)
5285 961 v1.3
Page 39
Correction
Troubleshooting
Page
Sensors
Check outdoor temperature sensor 40
Check boiler temperature sensor 40.................................................................
Check DHW tank temperature sensor or low-loss header temperature sensor 41
.............................................................................................
Check and replace differential air pressure sensor 41...............................
Control components
Relay test 42
...............................................................................................................
Check safety fixed high limits 43........................................................................
Check fuse 43.............................................................................................................
Check thermostatic radiator valves 43............................................................
Accessories
Control unit for weather-responsive operation
H Check WS remote control unit (Accessory) 44
H Check RS remote control (Accessory) 44...................................................
.............................................................
..........................................
5285 961 v1.3
39
Page 40
Troubleshooting
Correction (continued)
Scanning the actual and desired t emperatures
Check outdoor temperature sensor
X6
1 2 43
Outdoor temperature sensor
600
580
560
540
520
500
480
460
440
420
400
Resistance in
-40 -22 -04 +50+68+86
-40 Outdoor temperature in ºF/ºC
+14
-10 0 +10+20+30-30 -20
+32
Check boiler temperature sensor
1. Disconnect connector ”X6” from the
control unit.
2. Measure resistance of outdoor temperature sensor at the disconnected connector between ”X6.3” and ”X6.4”, and compare with resistance/outdoor temperature curve shown on the left.
3. If the value measured differs significantly from the curve, disconnect wires from the sensor and repeat the measurement directly on the sensor.
4. Depending on the result, replace cable or the outdoor temperature sensor.
A
40
20
10
8 6
4
2
1
0.8
0.6
0.4
0.2
Resistance in k
50 86 122 158 194 230
68 104 140 176 212 248
10 30 50
20 40 60
Boiler water temperature in ºF/ºC
70 90 110
80 100 120
1. Disconnect cables from boiler temperature sensor A.
2. Measure resistance of the boiler temperature sensor and compare with resistance/boiler water temperature curve shown on the left.
3. If the value measured differs significantly, replace the sensor.
IMPORTANT
As the sensor is in direct contact with the boiler water, the boiler must be drained before changing the sensor.
5285 961 v1.3
40
Page 41
Correction (continued)
Troubleshooting
Check DHW tank temperature sensor or low-loss header temperature sensor
A
B
X7
3 421
A DHW tank temperature sensor B Low-loss header temperature sensor
40
1. Disconnect connector ”X7” from the control unit.
20
10
8 6
4
2
2. Measure resistance of the tank temperature sensor and compare with the curve.
3. If the value measured differs significantly, replace the sensor.
4. Repeat above steps 1 - 3 for checking the low-loss header
1
0.8
0.6
0.4
0.2
Resistance in k
50 86 122 158 194 230
68 104 140 176 212 248
10 30 50 70 110
20 40 60
Tank temperature in ºF/ºC
80 100 120
temperature sensor.
Check and replace differential air pressure sensor
B D
5285 961 v1.3
B
C D
C D
A
In case of fault messages regarding the differential a ir pressure sensor, check that
H the sensor was installed correctly. H the electrical connections were made correctly. H the O-rings in the adaptor are correctly positioned. H the test nipples have been sealed with plugs.
If the error message persists, replace sensor.
To check O-rings:
Transducer power supply
X14.3 Red................
1. Disconnect electrical plug-in
164
connection
A.
2. Remove sensor B by pulling off in
an upward direction.
3. Check that the two O-rings C are
correctly located in the m ountings D of the adaptor.
X14.4 Yellow................
X14.5 Black................
Between red and black:
24VDC.......................
Between black and yellow:
at standby 0.2 to 0.3VDC........
at ignition 0.7 to 1.0VDC.........
at low fire 0.5 to 0.6 VDC........
4. Insert connection nipples of the
at high fire 3.5VDC........
sensor in the adaptor of the gas combination valve and snap into place.
5. Reconnect the electrical plug-in connection on the sensor.
41
Page 42
Troubleshooting
Correction (continued)
Relay test
DIAGNOSIS/RELAYS
02: HEATING C IRCUIT PUMP A
02: <PL. 20> ON
>CONTINUE:................. A
>BACK:........................ B
>INSTALLER SETUP:...... C
Open cover: Menu option Button
→ SYSTEM D” → INSTALLER SETUP C” → CODE PLEASE: B-C-C-B” → DIAGNOSIS A” → RELAY TEST A”
Select required relay to check its function with the menu option CONTINUE ”A”(seebelow).
Please note:
Those relays which are not mentioned have no significance. When the relay is selected, only the corresponding unit is addressed. If no call for heat is present, the burner is omitted from the relay test.
For installations with Dekamatik-HK mixing valve control, refer to the Dekamatik-HK control manual.
Display Meaning
01 – 1st stage burner Without function
<PL41> ON (Burner on, pump not running)
02 – Heating circuit pump A Circulating pump
<PL20> ON
03 – Heating circuit pump B Heating circuit pump
<PL20B> ON with extension kit with mixing valve
04 – DHW pump DHW heating pump
<PL21> ON
05 – Not assigned
06 – Not assigned
07 – Mixing valve HC B Mixing valve CLOSED
*1
<PL52B> CLOSED
08 – Mixing valve HC B Mixing valve OPEN
*1
<PL52B> OPEN
10 – Modulation Burner (min. input)
<PL90> CLOSED Circulating pump Burner <PL41> ON
11 – Modulation Burner (max. input)
<PL90> OPEN Circulating pump Burner <PL41> ON
13 – Additional heating pump Additional heating pump or
<PL28> ON DHW recirculation pump
14 – Alarm output Alarm output
*3
*2
<PL56> ON
*1
Only in conjunction with mixing valve extension kit
*2
If no low-loss header is installed, pump will be operated as a DHW recirculating pump (see coding addresses “099” and “0B8”). If a low-loss header is installed, the pump will operate as a boiler pump (see coding address “0B8”).
*3
Only in conjunction with expansion board (optional)
5285 961 v1.35285 961 v1.3
42
Page 43
Correction (continued)
A
Troubleshooting
Check safety fixed high limits (FHL)
If the safety fixed high limits cannot be reset after an automatic lockout of the burner control unit, even though the boiler water temperature is below approx. 194 ºF/90 ºC, perform the following steps: H Disconnect the cables from the fixed
high limit switch A.
H Check continuity of the fixed high
limit switch with a multimeter.
H Remove defective limit switch. H Coat new limit switch with heat
conductive paste and install.
H After start-up, press the reset button
EU” on the control unit.
5285 961 v1.3
AB
Check fuse
1. Disconnect connector A in the
control unit.
2. Remove fuse F 3 (6.3 A) B by holding its grip and pulling out of the base.
3. Check continuity of fuse with a multimeter.
Check thermostatic radiator valves
Check operation and setting.
IMPORTANT
The thermostatic radiator valves must not be activated in a room in which the room temperature sensor is installed for room temperature dependent operation. In case of a weather-responsive control, with a room temperature sensor via the RS remote control unit, keep the thermostatic radiator valves fully open.
43
Page 44
Troubleshooting
Correction (continued)
Check WS remote control unit (Accessory) Check RS remote control unit (Accessory)
The WS remote control unit is used for setting the desired room temperature values from any room in the building. The RS remote control unit is used f or setting the desired room temperature values from the main living room (with room temperature dependent control).
Functionality check
IMPORTANT
Resistance measurement and control unit response test. If the presence of a fault is suspected in the customer’s connecting cable, temporarily connect the remote control directly to the control unit and perform test.
To calculate total r esistance (NTC), add the actual value and the current resistance setpoint value.
In most cases, faulty behavior of the control unit is due to the installation of the RS remote control unit in an unsuitable location. This can lead to draft phenomena caused by cavities behind the remote control or by the stack effect of empty pipes.
Wiring diagram: see section e ntitled ”Additional Information”.
310
300
290
280
280
Resistance in
54 61 68 75 82
46
12 20 24 2816
8
Setpoint value
ºF ºC
WS remote control s– Setpoint value between terminal
”9” and ”10”
m – Setpoint value between terminal
”9” and ”11”
240
220
200
180
160
140
Resistance in
46
8 1216202428
Actual value
61
54 68 75 82
ºF ºC
RS remote control Room temperature sensor (NTC) curve between terminal ”9” and ”13”
172 152 145
138 119 108
84 59
Resistance in
46 54 61 68 75
50 57
812
10
Setpoint value
64 72 79
16 20 24
14 18 22
26
ºF
ºC
RS remote control s– Setpoint value between terminal
”10” and ”14”
m – Setpoint value between terminal
”11” and ”14”
44
5285 961 v1.3
Page 45
Overview
Additional Information
Page
Technical Data 46.....................................................................................................
Burner Control Unit LGM 29.XX 47..................................................................
Control Unit for Weather-Responsive Operation with Programming Unit 48
Functional description 48...................................................................................
Heating system types 49....................................................................................
Accessing coding addresses 50......................................................................
Heating curve 51....................................................................................................
Overview of coding addresses 52..................................................................
Accessing temperature settings 58................................................................
Jumper Assignment and Codings 59................................................................
Assignment of plug-in jumper on circuit board VR20 59.....................
External switching of the heating program 59..........................................
External heat demand 59.....................................................................................
External disable 60.................................................................................................
....................................................................................
Replacement of Circuit Board VR20 61............................................................
Replacement of Burner Control Unit LGM 29 62..........................................
Wiring Diagram 64....................................................................................................
Parts Lists 66...............................................................................................................
Vitodens 200, WB2 66...................................................................................
Installation fittings (models WB2 11-44 and 15-60) 68.....................
Alphabetical Index 69..............................................................................................
Maintenance Record 70..........................................................................................
Lighting and Operating Instructions 71............................................................
5285 961 v1.3
45
Page 46
Additional Information
Technical Data
Rated voltage: 230 VAC Rated frequency: 60 Hz Rated current: 2.5 A~
Max. ambient temperature H at operation: 32 to 104 ºF
Setting of fixed high limit safety cut-out: 210 ºF (fixed setting) 99 ºC
–0 to +40 ºC
H when storing
Main fuse: max. 16 A
and transporting: –4 to +149 ºF
–20 to +65 ºC Setting of adjustable electronic high limit 167 ºF
Power consumption
H Burner: max. 105 W H Control unit: max. 10 VA
75 ºC
WARNING
Always ensure the correct orifices are installed in the boiler. See table below. The boiler must achieve the output stated on the rating plate. Do not overfire the boiler.
Standard heating boiler
Boiler Model Model No. WB2 11-44 WB2 15-60
Natural gas
CSA input
CSA output/DOE heating capacity
Net I=B=R rating
Propane gas
CSA input
CSA output/DOE heating capacity
Net I=B=R rating
Min. gas supply pressure
Natural gas Propane gas
Max. gas supply pressure
Natural gas Propane gas
Flue gas
Temperature (at boiler return water temp. of 86 ºF/30 ºC) – at rated full load – at rated partial load
Temperature (at boiler water return temp. of 140 ºF/60 ºC)
Max. natural gas flow rate ft3/h
Max. propane gas flow rate ft3/h
Burner orifices diameter
Natural gas Propane gas
*1
*2
*3
*3
Net I=B=R rating based on piping and pick-up allowance of 1.15. If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator must be installed upstream of the
heating system.
Measured flue gas temperature with combustion air temperature of 68 °F/20 °C.
*1
*1
MBH kW MBH kW
MBH 133 178
MBH kW MBH kW
MBH 120 166
“w.c. “w.c.
*2
“w.c. “w.c.
ºF/ºC ºF/ºC
ºF/ºC
3
/h
m
3
/h
m
Ømm Ømm
55-172
16-50
49-153
14-44
55-155
16-45
49-138
14-40
4
11
14 14
95/35 91/33
149/65
172
4.87
62
1.75
(E44) 8.40 (P44) 6.10
80-230
23-67
71-205
21-60
37-112
11-33
33-101
10-30
11
14 14
104/40
95/35
158/70
230
6.51
85.6
2.42
(E60) 9.00 (P60) 6.70
7
46
5285 961 v1.3
Page 47
Burner Control Unit LGM 29.XX
Program sequence
Standby
Initial boiler run
time with
internal tests Call for heat Ionization Safety chain (FHL)
Gas combi valve
Ignition transformer Combustion air modulation
Speed
Time in sec. <71 2 0.2 <5 5 Heating mode
signal required signal invalid
signal required for transition to next phase
Pre-purge time
Pre-ignition time
Safety time
Flame
recognition
Operation
Modulation range
Shutdown and
auto reset with
max. 51
Additional Information
internal tests
Standby
Waiting time until next call for heat start. Differential air pressure sensor must be reset and the speed feedback signal (HALL) must record that fan is stationary.
Start-up and initial boiler run time
Start takes place when a call f or heat is received f rom the temperature controller, provided no air pressure is detected. The fan motor receives voltage. The speed signal (HALL) and the differential air pressure voltage signal must be received by the burner control unit LGM 29.XX within approx. 70 seconds, otherwise a fault message is transmitted. During the initial boiler run time, self-tests take place within the burner control unit LGM 29.XX.
Pre-purge time
The combustion chamber is flushed out by the fan.
Pre-ignition time
Ignition spark is initiated.
Safety time
The gas combination valve coils receive voltage (energized), flame monitoring is activated. Ignition is switched off after approx. 4 seconds. If the flame is not recognized during ignition after three trials, automatic lockout takes place.
5285 961 v1.3
Burner operation (green LED is lit)
Burner operation begins after the safety time has e lapsed, and flame recognition has taken place successfully. The burner control unit modulates from its ignition load according to the currently selected setpoint value. After controlled shutdown (heat demand is satisfied), a uto reset to the standby mode takes place.
Shutdown
The gas valve is de-energized. Internal tests are performed.
Test time
Auto reset is the end of the shutdown phase after controlled switch-off. Auto reset also takes place after resetting, failure of the flame during operation or after a call for heat is terminated before the start of the safety time.
Safety chain (FHL)
The fixed high limits must be closed at all times during the entire period of operation, otherwise automatic lockout takes place immediately.
Burner control unit LGM 29.XX The burner control unit LGM 29.XX performs self-tests in the following instances: H when the burner has been in
continuous operation for more than 24 hours,
H before each time the burner is
switched on,
H after each time the burner is
switched off.
Behavior in the event of malfunctions
If faults are detected, e ither no start-up takes place or automatic lockout is triggered. In case of all safety­relevant malfunctions, the gas supply is cut off. Automatic lockout takes place H when flame establishment fails
before the end of the flame recognition time,
H in the event of an uninterrupted delay
of the flame signal for more than 3 seconds,
H in the event of an incorrect differential
air pressure sensor signal longer than 70 seconds,
H in the event of internal faults.
In the event of a line voltage drop, the burner control unit either operates without a fault indication function or goes into reset position (gas valve closed). When the line voltage reaches its normal level again, burner c ontrol is ready for another start-up.
47
Page 48
Additional Information
Control Unit for Weather-Responsive Operation with programming unit
Functional description
Space heating mode
The control unit calculates a boiler water setpoint temperature based on the outdoor or room temperature (where a room temperature dependent remote control is connected) and on the slope/shift of the heating curve. The computed boiler water setpoint temperature is transmitted to t he burner control unit. From the boiler water setpoint and the actual temperature the burner control calculates the degree of modulation required, and regulates the burner accordingly. The maximum operating boiler water temperature is limited in the burner control unit to 167ºF / 75ºC by the electronic temperature control. The maximum adjustable high limit of the boiler is 180ºF / 82ºC. The fixed high limits of the safety chain interlock the burner control unit at 210 ºF/99 ºC boiler water temperature.
Programming Unit (removable)
Domestic hot water supply with gas-fired space heating boiler
Domestic hot water heating is activated when the tank temperature is
4.5 ºF/2.5 ºC below the tank temperature setpoint value. The burner and the tank DHW pump are switched on. In the f actory default setting, the desired boiler water temperature is set at 36 ºF/20 ºC above the tank temperature setpoint value. When the actual tank temperature rises 4.5 ºF/2.5 ºC above the tank temperature setpoint value, the burner is switched off and the time delay function of the tank DHW pump is activated.
Additional heating function (anti ­legionnaire-function) for domestic hot water production
The additional heating function is activated when an activation period of 10 minutes is selected (e.g. 22.10 to
22.20 hrs). This period must lie outside the switching times for normal domestic hot water heating so that the signal is recognized by t he control unit.
The temperature setpoint value for additional heating is set in coding address ”0A7”.
Pressure gage
Display window
Heating program selector switch
30
2
15
1
45
3
0
0
60
0
+
A
-
B
DC
i
5
4
6
3
7
8
2
9
1
0
10
5
4
6
3
7
8
2
9
1
10
Burner fault reset button
Emission test switch (override switch)
Selector knob for ”normal room temperature”
Burner operating status indicator
Burner fault indicator
Boiler on/off switch
Party button
Energy savings button
Selector knob for ”reduced room temperature”
Information button
”Factory default settings” button
Selector knob
Flip-down cover
Selector buttons
DHW comfort function switch (only available on Combi heating boiler)
5285 961 v1.3
48
Page 49
Additional Information
Control Unit for Weather-Responsive Operation
with programming unit (continued)
Heating system types
The control unit is adjusted to the system equipment. In the factory default setting, the heating system type is coded ”000:000”.
H The coding is set automatically when a tank temperature sensor is connected (for operation with a DHW tank). H The control unit must be r e-coded m anually if a heating circuit with mixing valve is connected:
For this purpose the corresponding heating system type is coded in the coding address ”000”. For other settings please note numbers of system types.
See page 50 for information of how to access t he required coding level.
Please note:
If only heating circuit B with mixing valve is connected (i.e. there is no direct-connected heating circuit), coding address ”008” must be set to value ”001”.
Refer to the Vitodens 200 Installation Instructions for piping layout details.
System type ”000:000”
Heating system with one heating circuit without mixing valve, without DHW heating
*1
*1
M
M
*1
Circulating pump and check valve are external to the boiler and not internal as illustrated.
5285 961 v1.3
*1
*1
MM
MM
or Heating system with low-loss header and heating circuits connected downstream with separate heating circuit control unit (Dekamatik-HK), without DHW heating.
System type ”000:001”
Heating system with one heating circuit without mixing valve, with DHW heating or Heating system with low-loss header and heating circuits connected downstream with separate heating circuit control unit (Dekamatik-HK), with DHW heating.
System type ”000:002”
Heating system with one heating circuit with mixing valve, without DHW heating (with or without low-loss header) or Heating system with one heating circuit with mixing valve and one heating circuit without mixing valve, without DHW heating (with or without low-loss header).
System type ”000:003”
Heating system with one heating circuit with mixing valve, with DHW heating (with or without low­loss header) or Heating system with one heating circuit with mixing valve and one heating circuit without mixing valve, with DHW heating (with or without low-loss header).
49
Page 50
Additional Information
Control Unit for Weather-Responsive Operation
Accessing coding addresses
The coding of the programming unit is performed by using the ”A”, ”B”, ”C” and ”D” buttons and t he ”G” selector knob.
5
4
6
3
7
8
2
9
1
0
10
5
4
6
3
+
A
-
B
DC
i
7
8
2
9
1
10
Open cover: Menu option Button
SYSTEM DINSTALLER SETUP C
S
→ CODE PLEASE: B-C-C-B” → CODING 1 B”
or CODING 2 C”
The desired coding address is selected by pressing button ”A” (CONTINUE) or ”B”(BACK). The respective coding address is changed with the ”G” selector knob (CHANGE). The change is confirmed with button ”D” (change is stored).
with programming unit (continued)
Please note:
All the settings are performed in the ”Installer Setup” menu which contains ”Coding 1” (main coding addresses in plain language) and ”Coding 2” (all coding addresses).
Changes made and confirmed in Coding Level 1 are automatically adopted in Coding Level 2 and vice versa.
50
5285 961 v1.3
Page 51
Additional Information
Control Unit for Weather-Responsive Operation
Heating curve
Slope
Boiler water temperature or
230
212
194
176
158
140
122
supply temperature in ºF/ºC
104
ºF ºC
86
110
100
90
80
70
60
50
40
30
3.2
3.4
10 5 0 -5 -10
50 41 32 23
Outdoor temperature
3.0
14
2.8
-15
2.4
2.6
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
ºC
-20
-4
ºF
5
with programming unit (continued)
The heating curves represent the relationship between the outdoor temperature and the boiler water or supply temperature. Put simply: The lower the outdoor temperature, the higher the boiler water or supply temperature. In turn, the room temperature is dependent on the boiler water or supply temperature. If a different room temperature is set, the curves are shifted parallel to the desired room temperature axis.
Factory settings:
H slope ”n”=1.4 H shift ”N”=0
230/ 110
Boiler water temperature or
supply temperature in ºF/ºC
+68/20 -4/20
Outdoor temperature in ºF/ºC
230/ 110
Boiler water temperature or
supply temperature in ºF/ºC
+68/20 -4/20
5285 961 v1.3
Outdoor temperature in ºF/ºC
3.5
-13
+40
1.4
0.2
1.4
1. To change the slope
Open cover on programming unit a nd go through menu as follows: Menu option Button HEATING CIRCUIT A ”A
or HEATING CIRCUIT B ”B
HEATING CURVE BCHANGE A
2. To change the shift
Open cover on programming unit a nd go through the menu as follows: HEATING CIRCUIT A ”A
or HEATING CIRCUIT B ”B
HEATING CURVE BCHANGE 2 × ”A
51
Page 52
Additional Information
Control Unit for Weather-Responsive Operation
Overview of coding addresses
Coding addresses not discussed in this section must not be changed. See page 50 for information of how to access coding addresses.
Coding (factory default setting) Address: Value
000:000 One heating circuit without mixing valve,
001:000 Do not change 003:001 DHW
004:000 Do not change 005:001 Heating
006:001 Heating
007:000 DHW
Function mode Coding
change Address: Value
000:001 system without domestic hot water heat­ing
000:002
000:003
tank
circuit
With priority switching over heating circuit pump(s)
With heating circuit pump logic function
003:000 Without priority switching over heating circuit
005:000 Without heating circuit pump logic function
pump
circuit pump
tank
Heating circuit pump speed in reduced range as per coding address ”044:...”
Setting range of domestic hot water temperature
006:000 Heating circuit pump speed in reduced range
007:001 Setting range of domestic hot water tempera-
50 to 140 ºF/10 to 60 ºC
*1
*2
*1, 2
with programming unit (continued)
Possible change
One heating circuit without mixing valve, system with domestic hot water heating One heating circuit with mixing valve, system without domestic hot water heating One heating circuit with mixing valve, system with domestic hot water heating
pump(s)
as per coding address ”046:...”
ture 50 to 158 ºF/10 to 70 ºC
IMPORTANT
Note max. tank water temperature.
008:000 Do not change 009:000 Program-
ming unit
Display of boiler water temperature
010:000 Do not change 011:000 External call for heat or external
switching of heating program blocked
012:000 Do not change 013:000 Heating
circuit pump
Heating circuit pump without variable speed operation (e.g. as temporary m easure f or servicing)
014:000
*3
Heating circuit
Party button ”g” effective for heating circuit B
015:001 Do not change
*1
Coding for systems with domestic hot water heating is automatically recognized.
*2
These codings also apply on systems with one heating circuit without mixing valve and one heating circuit with mixing valve.
*3
Only on heating system types ”000:002” and ”000:003” (heating systems with one heating circuit with mixing valve).
52
IMPORTANT
Do not adjust domestic hot water temperature more than 140 ºF/ 60 ºC.
009:001 Display of outdoor temperature
011:001 External call for heat or external switching of
heating program active at X4.1 - X4.2
013:001 With variable speed heating circuit pump (au-
tomatic recognition)
014:001
*3
Party button ”g” effective for heating circuit A and heating circuit B
5285 961 v1.3
Page 53
Additional Information
Control Unit for Weather-Responsive Operation
with programming unit (continued)
Overview of coding addresses (continued)
Coding (factory default setting) Address: Value
Function mode Coding
change Address: Value
Possible change
016:000 Do not change 017:001 Do not change 018:000 DHW
tank
019:000 Program-
ming unit or remote control
Circulating pump with time delay function
Weather-responsive operation (WS function) for all con­nected heating circuits
018:001 Circulating pump without time delay function
019:001
*1
H On systems with one heating circuit
without mixing valve or one heating circuit with mixing valve: Operation with room temperature dependent control (RS function)
H On systems with one heating circuit
without mixing valve and one heating circuit with mixing valve: Weather-responsive operation (WS function) for heating circuit with mixing valve and op­eration with room temperature dependent control (RS function) for heating circuit with mixing valve
H On systems with one heating circuit
019:002
*1
without mixing valve or one heating circuit with mixing valve: Weather-responsive operation (WS function) in normal heating mode and operation with room temperature dependent control (RS function) in reduced operation
H On systems with one heating circuit
without mixing valve and one heating circuit with mixing valve: Weather-responsive operation (WS function) for heating circuit without mixing valve and on weather-responsive basis in normal heat­ing mode and operation with room tempera­ture dependent control in reduced operation (WS/RS function) for heating c ircuit with mixing valve
020:000 Heating
circuits
Without WS or RS remote control unit
020:001 With WS or RS remote control unit
027:000 External switching of heating program 027:001 External call for heat 028:000 Boiler During DHW production, the
boiler water temp. is max. 36 ºF / 20 ºC higher than the
028:001 During domestic hot water production, the
boiler water temperature is limited to 172 ºF/78 ºC by the limit thermostat
desired tank water temp. 029:001 Do not change 033:000 Do not change 034:000 Do not change 036:000 Do not change 038:020 Minimum supply temperature in heating mode 020 to 127 Min. possible supply temperature
68 to 261 ºF / 20 to 127 ºC
*1
Change only feasible if programming unit is mounted on a wall-mount base.
*2
Address set automatically, must be reset manually.
*2
5285 961 v1.3
53
Page 54
Additional Information
Control Unit for Weather-Responsive Operation
with programming unit (continued)
Overview of coding addresses (continued)
Coding (factory default setting) Address: Value
Function mode Coding
change Address: Value
Possible changes
042:070 Boiler water temperature in heating mode 000 to 82 Max. adjustable temperature limit setting
180ºF / 82ºC
044:030 Heating
circuit pump
Minimum rotational speed of heating circuit pump; approx. 1100 rpm
044:001 to 044:100
*1
Lowest value for minimum rotational speed of heating circuit pump; approx. 700 rpm Highest value for minimum rotational speed of heating circuit pump; approx. 2700 rpm
045:065 Heating
circuit pump
Maximum rotational speed of heating circuit pump; approx. 1750 rpm
045:001 to 045:100
*1
Lowest value for maximum rotational speed of heating circuit pump; approx. 700 rpm Highest value for maximum rotational speed of heating circuit pump; approx. 2700 rpm
046:045 Heating
circuit pump
Rotational speed of heating circuit pump in reduced ope­ration; approx. 1200 rpm
046:001 to 046:100
*1
Lowest value for rotational speed of heating cir­cuit pump in reduced operation; approx. 700 rpm Highest value for rotational speed of heating cir-
cuit pump in reduced operation; approx. 2700 rpm 049:___ Hours run (”hundreds”) at 3rd place from left 049:000 Reset hours run 050:___ Hours run (”units”) at 3rd place and
050:000 Reset hours run
”tens” at 2nd place from left 055:040 Do not change 085:032 Do not change 086:032 Do not change 088:007 Do not change 089:008 Do not change 099:000 Possibility for connecting a DHW
recirculating pump (on timer schedule)
099:001 Output signal for domestic hot water
production active (ON), whenever there is a call for DHW only
0A0:020
*2
Differential temperature between desired
boiler water temperature and desired
tank temperature with domestic hot water
0A0:10 to 0A0:50
heating 0A1:000 Do not change 0A2:075 Boiler Desired boiler temperature
with external request 167 ºF/75 ºC
0A2:032 to 0A2:127
Setting range of desired boiler water tempera­ture 90 to 261 ºF/32 to 127 ºC (max. possible boiler water temperature 180 ºF/82 ºC)
0A3:___ Do not change
*1
One increment corresponds to approx. 20 rpm.
*2
Only effective with coding 028:000.
54
5285 961 v1.3
Page 55
Additional Information
g
Control Unit for Weather-Responsive Operation
Overview of coding addresses (continued)
Coding (factory default setting) Address: Value
0A4:255 Do not change 0A5:255 Do not change 0A6:255 Do not change 0A7:060 DHW
0A8:000 Boiler See table below for effect of
Function mode Coding
change Address: Value
tank
Setpoint value for ”Additional function for domestic hot water heating” (“Anti-Legionnaire-Function” – domestic hot water heated briefly to 140 ºF/60 ºC)
external disable signal (also see page 59)
A07:061 to A07:070
0A8:001 to 0A8:007
with programming unit (continued)
Possible changes
Setting range between 142 to 158 ºF/ 61 and 70 ºC.
IMPORTANT
Do not adjust domestic hot water temperature more than 158 ºF/ 70 ºC.
See table below for effect of external disable signal
Possible coding changes for coding address 0A8 ”external disable”
Coding
0A8:000 × × × × Blocked 0A8:001 OFF OFF CLOSED OFF Blocked 0A8:002 × × × OFF Blocked 0A8:003 × OFF CLOSED × Blocked 0A8:004 OFF × × × Blocked 0A8:005 OFF × × OFF Blocked 0A8:006 OFF × × × Blocked 0A8:007 OFF OFF CLOSED × Blocked
× = in normal control mode
Heating circuit pump
Heating circuit with mixing valve (extension kit)
Heating circuit pump Mixing valve
Tank (Circulating pump for tank heating)
Burner
5285 961 v1.3
55
Page 56
Additional Information
pum
p
fortankheatingtemperature
accordingto
g
Control Unit for Weather-Responsive Operation
with programming unit (continued)
Overview of coding addresses (continued)
Coding (factory default setting) Address: Value
0A9:098 Circulating
Function mode Coding
change Address: Value
pump
Max. rotational speed of cir­culating pump for DHW pro­duction
0A9:001 to 0A9:100
*1
Possible changes
Lowest value for rotational speed of circulating pump for DHW production Highest value for rotational speed of
circulating pump for DHW production 0B2:___ Fault memory (see page 28) 0B3:___ Fault memory (see page 28) 0B4:___ Do not change 0B8:000 Space heating only - no DHW 0B8:001
0B8:002
With DHW heating
Optimum DHW heating (with anti legionnaire
function) (see page 48).
0B8:005 0B8:006
Combi boiler only
Not assigned. Must be changed to one of the
other coding addresses. 0C1:011 Freeze-up protection threshold
+34/+37ºFor+1/+3ºC
0C1:000 0C1:015
+50/+18ºFor+10/–8ºC
+41/+45ºFor+5/+7ºC 0C2:008 Do not change 0C5:000 Boiler See table below for effect of
external heat demand signal (also see page 59)
0C5:001 to 0C5:011
Possible coding changes for coding address 0C5 ”external heat demand”
Coding Heating circuit
pump
Heating circuit with mixing valve (extension kit)
*3
See table below for effect of external
heat demand signal
*3
Circulating pump for tank heating
Heating circuit pump Mixing valve
0C5:000 ON OFF CLOSED OFF 0C5:001 OFF OFF CLOSED OFF 0C5:002 × OFF CLOSED OFF 0C5:003 OFF × × OFF 0C5:004 ON × × OFF 0C5:005 × × × OFF 0C5:006 OFF OFF CLOSED × 0C5:007 ON OFF CLOSED × 0C5:008 × OFF CLOSED × 0C5:009 OFF × × × 0C5:010 ON × × × 0C5:011 × × × ×
× = in normal control mode
*1
One increment corresponds to approx. 20 rpm.
*2
This is set automatically when a tank temperature sensor is connected; can be reset to ”001” manually if required.
*3
Once this function has ended, the program changes automatically to the ”Space heating and DHW heating” mode.
Boiler water temperature
Maintained at desired value
coding address ”0A2”
56
5285 961 v1.3
Page 57
Additional Information
Control Unit for Weather-Responsive Operation
Overview of coding addresses (continued)
Coding (factory default setting) Address: Value
0C6:000 Do not change 0C7:003 Resetting
0C8:001 External
0C9:003 Startofsummertime:March 0C9:001
0D0:005 Start of summer time: Last week of
0D1:007 Start of summer time: Last day of week
0D2:010 Startofwintertime: October 0D2:001
0D3:005 Start of winter time: Last week of
0D4:007 Start of winter time: Last day of week
0D5:000 Program-
0D6:000 Program-
0D7:000 Do not change
Function mode Coding
change Address: Value
Automatic 0C7:000
to summer/ winter time
switching of heating program
ming unit
ming unit
Contact open: Space heating ON/domestic hot water heating ON (ac­cordingtotimeprogram) Contact closed: Central heating OFF/domestic hot water heating OFF.
month
(Sunday)
month
(Sunday)
Normal display format with cover closed
Temperatures displayed in ”ºC” (º Celsius)
0C7:001 0C7:002
0C8:000 Contact open:
to 0C9:012
0D0:001 to 0D0:005
0D1:001 to 0D1:007
to 0D2:012
0D3:001 to 0D3:005
0D4:001 to 0D4:007
0D5:001 Large display format for time and outdoor
0D6:001 Temperatures displayed in ”ºF” (º Fahrenheit)
with programming unit (continued)
Possible change
Manual resetting to s/w / date change blocked Automatic resetting to s/w Manual resetting to s/w / date change released
Central heating ON/domestic hot water heating ON (according to time program) Contact closed: Continuous space heating ON/domestic hot water heating ON (independent of preset time program)
January to December
Week 1 to Week 5 of selected month
Monday to Sunday
January to December
Week 1 to Week 5 of selected month
Monday to Sunday
temperature with cover closed
5285 961 v1.3
57
Page 58
Additional Information
Control Unit for Weather-Responsive Operation
Accessing temperature settings
The following desired and actual temperature values can be accessed and shown on the display of the programming unit:
5
4
6
3
7
8
2
9
1
0
10
5
4
6
3
+
A
-
B
DC
i
7
8
2
9
1
10
H Outdoor temperature H Boiler water temperature H Supply temperature of the extension
S
kit for the heating circuit with mixing valve
H Room temperature (if programming
unit is mounted on a wall-mount base andusedasaremotecontrol).
Open the cover: Menu option Button HEATING
CIRCUIT A or A” HEATING CIRCUIT B or B” SYSTEM D”
OPERATING STATUS”C”or”BCONTINUE A
with programming unit (continued)
Depending on the coding, the boiler water temperature or the outdoor temperature is shown in the first menu on the display.
H Domestic hot water temperature
Open cover: Menu option Button
DHW CDHW TANK AOPERATING STATUS”C
58
5285 961 v1.3
Page 59
Jumper Assignment and Codings
Assignment of plug-in jumper on circuit board VR20
Additional Information
Plug-in jumper ”X6”
Factory default setting without ”External burner disable” function.
With ”External burner disable” function.
Plug-in jumpers ”X2” - ”X 4”
Factory default setting without Viessmann 2-wire BUS expansion module: Two plug-in jumpers connected as shown.
With Viessmann 2-wire BUS expansion module: Both plug-in jumpers r emoved.
External switching of the heating program (telephone contact)
With programming unit
Change coding address ”011:000” to ”011:001”.
External heat demand field supplied
With programming unit
Change coding address ”011:000” to ”011:001” and ”027:000” to ”027:001”.
Boiler start-up takes place in accordance with the settings of coding address ”0C5”. Boiler water temperature is maintained at the value selected in coding address ”0A2”.
5285 961 v1.3
59
Page 60
Additional Information
Jumper Assignment and Codings (continued)
External disable field supplied
B
A
1. Remove circuit board VR 20 A.
2. Reverse plug-in jumper ”X6” B.
3. Insert circuit board A again.
Boiler shutdown takes place in accordance with the settings selected in coding address ”0A8”.
60
5285 961 v1.3
Page 61
Additional Information
000:000(withoutDHW;factorydefaultsetting)Setaccordingtosystemla
y
001(withDHWstoragetank)
indicated
.
Replacement of Circuit Board VR20
IMPORTANT
Before replacing circuit board VR20, record actual system addresses (in particular coding addresses 000, 0B8, 042, 045, 015, 017, 0A2) and their corresponding values, heating curves and DHW settings.
Removing circuit board VR20
Coding information
1. Loosen the two screws located
underneath the control carefully fold down t he control.
2. Unscrew and remove cover
3. Slide out circuit board VR20
using supplied handle.
Installing the replacement circuit board
1. Slide circuit board VR20
back into the control. Ensure that circuit board is fully plugged in and makes positive contact.
2. Reinstall front enclosure panel and cosmetic piping cover.
3. Verify that all coding addresses and their values a re programmed t o recorded actual/required values. See table below.
4. Turn on power supply to boiler and start up boiler.
and
.
Please note! This table does not reflect all necessary coding cha nges required for proper operation of the boiler. See subsection “Overview of coding addresses” in this manual for other coding changes required.
Coding address
000: 000 (without DHW; factory default setting) Set according to system lay-
015: 001(factory default setting) Do not change! 017: 001(factory default setting) Do not change! 0B8: 000 (no DHW storage tank)
5285 961 v1.3
Possible coding values Required action
001 (with DHW storage tank) 002 (with DHW storage tank optimized) 006 not assigned
out. See page 52 for details.
Set to (one of) the value(s) indicated.
61
Page 62
Additional Information
Replacement of Burner Control Unit LGM 29
Removing the circuit board
1. Unlock hooks
located on both sides of the control unit and remove the control housing
of the control
unit.
2. Remove pressure gage .
3. Loosen the two screws located
underneath the control unit
and
carefully fold down t he control unit.
4. Remove covers , , and .
5. Remove all plug-in connectors and
the grounding wire, including #158 plug.
6. Slide off circuit board VR20
using
the supplied handle.
7. Loosen screws holding installed circuit board LGM 29.22 in place and remove carefully.
Setting the dip switch (applicable only t o replacement boards)
qQ
ON
2
345678
1
S2
62
1. Set dip switch
setting of the new circuit board according to the table on the following page.
IMPORTANT
To ensure the boiler is operated in accordance with its certification (see boiler rating plate), the dip switch must be set according to the table on the following page.
Note that in the factory default setting all switches are set to “OFF”.
2. Remove fuse holder from fuse F3 of
the removed circuit board LGM 29.22 and install on fuse F3 on replacement circuit board LGM 29.55.
5285 961 v1.3
Page 63
Replacement of Burner Control Unit LGM 29 (continued)
Setting the dip switch
Additional Information
Boiler model no.
WB2 11-44
WB2 15-60
Installing the replacement circuit board
Dip switch setting
ON
2
345678
1
ON
2
345678
1
1. Install new circuit board LGM
29.55
.
IMPORTANT
Do not remove clear covers on the circuit board. These provide protection against static discharge.
2. Connect all plug-in connectors to
circuit board LGM 29.55 including #158 plug.
,
IMPORTANT
Do not interchange plug-in connectors “X6” and “X7”. None of the other connectors are interchangeable.
3. Install covers
4. Plug in grounding wire.
5. Insert circuit board VR20
6. Install covers
7.Fold up control unit
using screws.
8.Insert pressure gage capillaries).
9. Mount control housing into place with hooks both sides of the control unit.
and .
.
and .
and secure,
(do not kink
and lock
located on
5285 961 v1.3
63
Page 64
Additional InformationAdditional Information
Replacement of Burner Control Unit LGM 29 (continued)
Installing the replacement circuit board (continued)
10. Reinstall front enclosure panel.
11. Start up boiler a nd check for proper
functioning of the circuit board and the heating system.
Vitodens 200 Start-up/Service Instructions
IMPORTANT
If “FAULT : FE“ appears in the display of the control unit during the functionality check, check dip switch settings against table on previous page and adjust if required.
Wiring Diagram
See following page.
64
5285 961 v1.3
Page 65
5285 961 v1.3
65
Page 66
Additional Information
Parts List
Model No. Serial No.
WB2 11-44 7188578 and WB2 15-60 7188577
Ordering Replacement Parts:
Please provide boiler Model and Serial Number from rating plate when ordering replacement parts. Order replacement components from your Viessmann distributor.
Parts
001 Profile gasket 016 Air vent without shut-off, R 3/8” 017 Matrix burner assembly (with Pos.
018, 026, 027, 056, 088, 094, 096, 100 and 120)
018 Matrix burner mesh (with Pos.
096 and 100)
020 Radial fan, RLS154 (without
electrode) 026 Ignition electrode 027 Ionization electrode 028 Flex gas pipe, 90x1½x1½cm 030 Conversion kit, NG 032 Conversion kit, LP
043 Connecting pipe extension (return) 044 Flow sensor 050 Condensate hose 055 Differential pressure sensor 056 Gas valve without orifice 057 Sealing grommet 058 Spring clip (set) 059 P-trap 086 Fixed high limit, 210°F / 99°C 087 Temperature sensor (with Pos.
049)
088 Ignition transformer
093 Heat exchanger assembly ASME 094 Insulation ring 096 Burner gasket (secondary) 100 Burner gasket 120 Burner gasket (primary)
Other Parts (not illustrated)
004 Operating Instructions
and User’s Information Manual 005 Start-up/Service Instructions 006 Parts List 007 Installation Instructions 049 Heat conductive paste
66
028
055
028
5285 961 v1.3
Page 67
Parts List (continued)
Additional Information
Parts
008 Front panel
(with Pos. 046, 060 and 061) 010 Wall-mount bracket 011 Fuse 6.3 amp (10 pack) 013 Programming unit 015 Ball valve, ½” with handle 019 Electronics box, RLS154 021 Burner control, LGM29.55 022 Circuit board, VR20 025 Hood (internal) for control unit 033 Harness for pump output 035 Circuit board, connection box 037 Vent pipe adaptor 039 Base panel 040 Cover panel 041 Gasket DN110 045 Seal d=150mm 046 Nameplate (set) “Vitodens 200” 047 Seal d=100mm 048 Pressure gage (psi) 060 Cover (flip-down) 060 Cover (flip-down)
061 Accessory pack, front panel hardware 062 Transformer 230V 063 Pressure gage insert 064 Connection module cover 065 Connection module 066 Switch (pair, Reset/Override) 070 Cover (blank) 071 Mounting bracket 072 Cable entry strip 073 Cable entry cover 074 Cover (poti) 075 Circuit board cover for VR20 076 Cable entry plug (pair) 079 Mounting plate 080 Control console (empty) 081 Switch (on/off)
(mechanism only-no switch) 082 Flat cable, 26-pole 084 Circuit board, adaptor 085 Circuit board, Optolink 089 Cap for vent pipe adaptor 200 Fastening bracket (10 pack) 205 Cap G 3/4 SW30
Other Parts (not illustrated)
023 Wiring harness, X 14 024 Wiring harness, X 11 034 Wiring harness, X 13 051 Touch-up paint stick, pure white 052 Touch-up spray paint, pure white 053 Pressure relief valve 054 Lubricating grease (6g) 068 Jumper plug, ionization 077 Counter plug (set) 078 Accessory pack (control unit) 090 Gasket (set) 092 Wiring harness, X 12 095 Accessory pack (burner parts) 097 Accessory pack,
enclosure hardware 10 pack 099 Connection assembly DEV 167 Wiring harness, ION/PE 201 Sensor #1 (outdoor) 202 Power/pump control module 203 Gasket assortment ½”, ¾” 204 Maintenance kit 210 Flow check valve DN25 305 Drain valve kit, ¾” 306 Power conditioner 307 Accessory pack (strain reliefs) 400 Service tool set ”Vitodens 200”
5285 961 v1.3
67
Page 68
Additional Information
Parts List (continued)
Installation fittings
Parts
110 Gasket, 32 x 44 x 2mm 111 Adaptor (pair with gasket)
1½ - 1¼” 113 Tee, 1¼” x 1¼” x ¾” 114 Nipple, 1¼ NPTM x 2½” 115 Full port ball valve, 1¼” FBV (T) 116 Nipple, ¾” x 3½ 117 Brass tee, ¾” 118 Sediment faucet, ¾” 119 Nipple, ¾ x 2” 120 Pressure relief valve 122 Shut-Off Valve (pair with gasket)
Parts not illustrated
130 Accessory pack
(metal stud mounting k it) 131 Loctite sealant, 6ml Tube 132 Keychain with air bleed key 133 Parts List
*1
Included in DHW Production Kit.
120
110
119
113
118
117
116
114
122
111
*1
110
111
115
*1
115
68
5285 961 v1.3
Page 69
Alphabetical Index
Additional Information
A
Accessing coding addresses (with
programming unit), 50
Accessing temperature settings
with programming unit, 58
Accessing the boiler water
temperature, 58 Accessing the outdoor temperature, 58 Accessing the tank water temperature,
58 Additional information, 45 Adjusting the CO Assembly of burner, 21
B
Boiler temperature sensor, 40 Burner control unit LGM 29, 47 Burner mesh assembly, 19
C
Checking the Dekamatik-HK, 26 Circuit board VR20, 59, Cleaning agents, 21 Cleaning the combustion chamber, 21 Cleaning the heat exchanger surfaces,
21 Coding addresses (general), 24 Condensate drain, 20
D
Diagnosis with the control unit, 27 Diaphragm expansion tank, 22 Differential pressure sensor, 41 Disassembly of burner, 19
E
Electrode block, 20 Expansion tank, 22 Extension kit for a heating circuit with
mixing valve, 25 External burner disable, 60 External switching of the heating
program, 59 External call for heat, 59
F
Fault memory, 28 Fault message, 27 Fixed high limit, 43 Fuse, 43
value, 16
2
Gas combination valve, 13 Gas orifices, 46 Gas manifold pressure, 13 Gas type, 13
H
Heating contractor address input, Heating curve H with programming unit, 51 Heating system types H with programming unit, 49
I
Ignition, 20 Important Regulatory and Installation
Requirements, 4 Initial start-up, 9 Ionization current, 24
L
Low-loss header, 49
M
Maintenance Record, 70
N
Neutralization unit, 21
O
Operating sequence of burner control
unit LGM 29, 47 Outdoor temperature sensor, 40 Overview of coding addresses, 52
P
Parts list, 66 Power supply connection, 11 Program sequence, 47
R
Relay test, 42 RS remote control unit, 44 Running pressure, 13
Selecting the language, 12 Static pressure, 13
T
Tank temperature sensor, 41 Technical data, 46 Thermostatic radiator valves, 43 Troubleshooting, 27
V
Viessmann 2-wire BUS expansion
module, 25, 59
H with programming unit, 26
W
Weather-responsive operation, 48 Wiring diagram, 64 WS remote control unit, 44
5285 961 v1.3
G
S
Safety instructions, 2 Safety valves, 22
69
Page 70
Additional Information
S
i
Maintenance Record
Setpoint value
Service
date:
Service
date:
Service
date:
ce
erv
date:
by:
by:
by:
by:
max.
14 ”w.c.
4-14 ”w.c.17-10 ”w.c.211-14 “w.c.
Never exceed
50 ppm air-free
min. 5 μA
Setpoint value running pressure WB2-44
Setpoint value running pressure WB2-60
*1
*2
Service
date:
by:
Service
date:
by:
“w.c.
Measurements
Static pressure
unning pressure (supply pressure)
“w.c.
j Natural gas
“w.c.
j LP
ppm
at lower end of rated input range
ppm
at upper end of rated input range
vol.-%
vol.-%
2
2
j Check gas type
Carbon dioxide content CO
H at lower end of rated input range
H at upper end of rated input range
Oxygen content O
vol.-%
at lower end of rated input range
vol.-%
at upper end of rated input range
Carbon monoxide content CO
μA
Ionization current
5285 961 v1.3
70
Page 71
Lighting and Operating Instructions
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING:Ifyoudonotfollowtheseinstructionsexactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped
with an ignition device which automatically lights the burner. Do not
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
try to light the burner by hand.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. Set thermostat or other operating control to lowest setting.
3. Turn off all electric power to the appliance.
4. This device is equipped with an ignition device which automatically lights the burner. Do not light the burner by hand.
try to
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
5. Close main gas shutoff valve.
6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow ”B” in the safety information above on this label. If you don’t smell gas, go to the next step.
7. Open main gas shutoff valve.
8. Turn on all electric power to the appliance.
Manual gas shutoff
Open
Closed
1. Set thermostat or other operating control to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Close main gas shutoff valve.
5285 961 v1.3
9. Set thermostat or other operating control to desired setting.
10. If the appliance will not operate, follow the instructions ”To Turn Off Gas To Appliance” and call your service technician or gas supplier.
TO TURN OFF GAS TO BOILER
71
Page 72
Printed on environmentally friendly
(recycled and recyclable) paper.
Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island 02886 USA Tel. (401) 732-0667 Fax (401) 732-0590 www.viessmann-us.com info@viessmann-us.com
72
Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario N2V 2G5 Canada Tel. (519) 885-6300 Fax (519) 885-0887 www.viessmann.ca info@viessmann.ca
Technical information subject to change without notice.
5285 961 v1.3
5285 961 v1.3
Loading...