Read and save these instructions
for future reference.
Safety, Installation and Warranty Requirements
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with theinstructions listed below and details printed in this manu al can cause product/property damage, severe personal injury,and/orloss
of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
HLicensed professional heating
contractor
The installation, service, and
maintenance of this equipment mustbe performed by a licensed
professional heating c ontractor.
"
Please see section
entitled “Important
Regulatory and
Installation
Requirements” in the
Installation Instructions.
HProduct documentation
Read all applicable documentation
before commencing installation. Store
documentation near boiler in a readily
accessible location for reference in
the future by service personnel.
"
For a listing of
applicable literature,
please see section
entitled “Important
Regulatory and
Installation Requirements”
in the Installation Instructions.
HCarbon monoxide
Improper installation, service and/or
maintenance can cause flue products
to flow into living space. Flue
products contain poisonous carbon
monoxide gas.
"
For information
pertaining to the proper
installation, service and
maintenance of this
equipment to avoid
formation of carbon monoxide, please
see the Installation Instructions of the
Vitodens 200 Venting System.
WARNING
Installers must follow local
regulations with respect to
installation of carbon monoxide
detectors. Follow manufacturer’s
maintenance schedule of boiler.
HEquipment venting
Never operate boiler without an
installed venting system. An improper
venting system can cause carbon
monoxide poisoning.
HWarranty
Information contained in
this and related product
documentation must be
read and followed. Failure
to do so renders warranty
null and void.
HAdvice to owner
Once the installation work is
complete, the heating contractor
must familiarize the system
operator/ultimate owner with all
equipment, as well as safety
precautions/requirements, shut-down
procedure, and the need for
professional service annually before
the heating season begins.
Operating and Service Documentation
It is recommended that all product
documentation such as parts lists,
operating and service instructions be
handed over to the system user for
storage.
2
Documentation is to be stored near
boiler in a readily accessible location
for reference by service personnel.
5285 961 v1.3
Index
Page
General Information
Initial Start-up
and Service
Troubleshooting
Safety, Installation and Warranty Requirements2...................................
Operating and Service Documentation2......................................................
Important Regulatory and Installation Requirements4...........................
About these Start-up/Service Instructions5................................................
Important Regulatory and Installation Requirements
Codes
The installation of this unit shall be in
accordance with local codes or, in the
absence of local codes, use
CAN/CSA-B149.1 or .2 Installation
Codes for Gas Burning Appliances for
Canada. For U.S. installations use the
National Fuel Gas Code ANSI Z223.1.
Always use latest editions of codes.
In Canada all electrical wiring is to be
done in accordance with the latest
edition of CSA C22.1 Part 1 and/or
local codes. In the U.S. use the
National Electrical Code ANSI/NFPA
70. The heating contractor must also
comply with both the Standard for
Controls and Safety Devices for
Automatically Fired Boilers,
ANSI/ASME CSD-1, and the Installation
Code for Hydronic Heating Systems,
CSA B214-01, where required by the
authority having jurisdiction.
Instructing the system user
The installer of the system is
responsible to ensure the system
operator/ultimate owner is made
familiar with the system functioning,
its activation, and its shut-down.
Initial start-up
Initial start-up m ust be performed by a
qualified heating c ontractor. Proper
completion of the Maintenance Record
by the heating contractor is also
required.
Working on the equipment
The installation, adjustment, service,
and maintenance of this boiler must be
done by a licensed professional heatingcontractor who is qualified and
experienced in the installation, service,
and maintenance of hot water boilers.
There are no user serviceable parts on
the boiler, burners, or control.
The following topics must be
covered:
Proper system operation sequence.
Explain the equipment.
Demonstrate an emergency
shut-down, what to do and what not.
Explain that there is no substitute for
proper maintenance to help ensure
safe operation.
The Maintenance Record is located
on page 70 of this manual.
Please carefully read this manual prior
to attempting start-up, maintenance
or service. Any warranty is null and
void if these instructions are not
followed.
For information regarding other
Viessmann System Technology
componentry, please reference
documentation of the respective
product.
Ensure main power supply to
equipment, the heating system, and all
external controls has been deactivated.
Close main gas supply valve. Take
precautions in all instances to avoid
accidental activation of power during
service work.
Technical literature
Literature for the Vitodens boiler:
- Technical Data Manual
- Installation Instructions
- Start-up/Service Instructions
- Operating Instructions
and User’s I nformation Manual
- System Design Guidelines
- Instructions of other Viessmann
products utilized and installed
- Installation codes mentioned
in this manual
We offer frequent installation and
service seminars to familiarize our
partners with our products. Please
inquire.
The completeness and functionality of
field supplied electrical controls and
components must be verified by the
heating contractor. These include low
water cut-offs, flow switches (if used),
staging controls, pumps, motorized
valves, air vents, thermostats, etc.
Leave all literature at the installation
site and advise the system
operator/ultimate owner where the
literature can be found. Contact
Viessmann for additional copies.
This product comes with several
safety instruction labels attached.
Do not remove!
Contact Viessmann immediately if
replacement labels are required.
4
5285 961 v1.3
About these Start-up/Service Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product information.
These include ”WARNING”, ”CAUTION”, and ”IMPORTANT”. See below.
Warnings draw your attention to the
WARNING
Indicates an imminently hazardous
situation which, if not avoided, could
result in death, serious injury or
substantial product/property damage.
CAUTION
Indicates an imminently hazardous
situation which, if not avoided, may
result in minor injury or
product/property damage.
IMPORTANT
presence of potential hazards or
important product information.
Cautions draw your attention to the
presence of potential hazards or
important product information.
Helpful hints for installation,
operation or maintenance which
pertain to the product.
This symbol indicates that additional,
pertinent information is to be found in
column three.
This symbol indicates that other
instructions must be referenced.
5285 961 v1.35285 961 v1.3
5
General Information
Necessary Tools
Special items
H Approved leak detection fluid for
natural gas and propane gas
H Pipe joint sealant
Testing/analysis equipment
H Multimeter to measure 0 - 230 V,
0 - 12 A AC and 0 - 100 μADC
H Flue gas analyzer to measure % CO
or O2(i.e. Bacharach fluid samplers
or suitable electronic analyzer)
H Manometer to measure gas pressure
0 to 11 ”w.c. (accurately) and up to
28 ”w.c. gas pressure (or a
non-electric Magnehelic® manometer
may also be utilized)
H Stack thermometer 0 to 500 °F /
0 to 260 °C
H Bacharach calculator or suitable
tables to calculate efficiency
H Carbon monoxide measuring
equipment 0 to 400 ppm
Cleaning supplies
H Plastic hand brush
H Rags
Use only calibrated equipment.
2
6
5285 961 v1.3
General Information
Removing and Reinstalling Front Enclosure Panel and Cover Panel
Some of the following start-up/service
steps require the removal of the front
enclosure panel and the cover panel.
To avoid personal injury and/or product
damage of any kind please follow the
instructions below carefully when
removing or reinstalling the front
enclosure panel and cover panel.
To remove front enclosure panel and
cover panel proceed as follows:
1. Close main gas supply valve.
5.
2.
1.
3.
2. Open flip-down cover of front
enclosure panel (by exerting slight
pressure with fingertip). Switch off
system on/off switch.
3. Turn off power supply to boiler and
ensure that power supply cannot be
activated during the duration of the
start-up/service work.
5. Unlock enclosure panel by giving
cover lock a quarter turn.
6. Remove burner cover panel by
unlocking the two pull-down latches
located on the bottom of the panel,
and slide out panel.
7. Attach front enclosure panel.
8. Secure in place by rotating slotted
screw.
4.
5285 961 v1.3
7
Initial Start-up and Service
Procedure (Overview)
Initial start-up steps
Service steps
I
I
I
I
IS
IS
IS
IS
IS
S
IS
IS
I
S
S
1. Fill heating system with waterPage9................................................................................................................
2. Check power supply connectionPage11..............................................................................................................
3. Select language (if required)Page12.....................................................................................................................
5. Select appropriate gas typePage13......................................................................................................................
6. Measure static pressure and running pressurePage13.................................................................................
7. How the Vitodens 200 boiler operates...Page15............................................................................................
9. Clock natural gas meterPage17..............................................................................................................................
11. Check all primary and secondary circuit connections for leaksPage18................................................
12. Perform c ombustion analysisPage18...................................................................................................................
13. Check venting system for leaks (circular air gap measurement)Page18..............................................
14. Disassemble burner and check burner gasketPage19..................................................................................
15. Visually check exterior of burner mesh assemblyPage19...........................................................................
S
S
S
S
S
IS
IS
IS
IS
S
I
I
I
16. Replace burner mesh assembly (if wire mesh is damaged)Page19........................................................
17. Check and adjust ignition and ionization electrodePage20........................................................................
2. Check inlet pressure of the
diaphragm expansion tank.
3. To remove debris and/or sludge
ensure that the system piping is
flushed out. Failure to do so could
cause settlement in the boiler
causing overheating and damage
not covered by warranty.
4. Optional:
Fill the heating system with w ater
at the boiler filling and drain tap
and drain air completely from the
system at ball valve barb fitting
Max. boiler
operating pressure......45 psig
Min. boiler
operating pressure......12 psig
Pressure relief valve ......30 psig
Please note:
Before filling the heating system with
water, check that all necessary flow
check valves are installed.
If the nitrogen pressure of the
precharged expansion tank is less
than the static pressure of the
system, inflate membrane pressure to
slightly exceed pressure of system.
The static pressure required at the
tank is based upon the static height
of the system. The system fill
pressure value must be equal to the
expansion tank pressure value at
approx. 60 ºF/15.6 ºC.
System fill pressure must be
approximately 3 psig higher than t he
static head when the system is cold.
Water treatment should be
considered in areas where it is known
that boiler feed water contains a high
mineral content and hardness.
.
In areas where freezing might occur,
an antifreeze may be added t o the
system water to protect the system.
Please adhere to the specifications
given by the antifreeze m anufacturer.
Do not use automotive silicate-based
antifreeze. Please observe that an
antifreeze/water mixture may require
a backflow preventer within the
automatic water feed and influence
components such as diaphragm
expansion t anks, radiation, etc. A
40% antifreeze content will provide
freeze-up protection to -10°F/-23°C.
Do not use antifreeze other than
specifically made for hot water
heating systems. System a lso may
contain components which might be
negatively affected by antifreeze.
Check total system frequently when
filled with antifreeze.
5285 961 v1.3
9
Initial Start-up and Service
Steps (continued)
Initial start-up
1. Fill heating system with water (continued)
5. Check system pressure and open
ball valve
6. Shut off the boiler from the heating
system on heating water side (close
shutoff valve
7. Connect drain hose to drain valve
or.
8. Open drain valve
the boiler with system pressure
until noise due to the presence of
air is eliminated.
9. Close drain valve
open ball valve
10. Check system pressure.
11. Ensure proper/adequate fuel supply
exists. Open gas shutoff valve.
).
orand vent
orand
.
Water flow
Air vent
10
5285 961 v1.3
Steps (continued)
Initial Start-up and Service
Initial start-up
2. Check power supply connection
A power module is supplied with the
Vitodens 200 boiler, which r equires a
120 VAC power supply from a wall
receptacle.
The module contains a 120/230 VAC
step-up transformer to power the
Vitodens 200 with 230 VAC. Refer to
the Installation Instructions shipped
with the module for wiring details
and/or Installation Instructions of the
boiler.
Voltage range
The voltage at connector
230 V (see wiring diagram).
Neutral conductor
The electrical power supply must have
a neutral conductor.
must be
IMPORTANT
In Canada all electrical wiring is to be
done in accordance with the latest
edition of CSA C22.1 Part 1 and/or
local codes. In the U.S. use the
National Electrical Code ANSI/NFPA
70. The heating contractor must also
comply with both the Standard for
Controls and Safety Devices for
Automatically Fired Boilers, ANSI,
ASME CSD-1.
Please note:
The outer conductor ”L” and the
neutral conductor ”N” must not be
interchanged.
See wiring diagram in section entitled
”Additional Information” in this
manual.
5285 961 v1.3
11
Initial Start-up and Service
Steps (continued)
Initial start-up
LANGUAGE / LANGUE
>ENGLISH:.................A
>FRANÇAIS:...............B
>BACK / RETOUR: ......D
Initial start-up
HEATING CONTRACTOR
INPUT NAME/TEL.:
TEL.:
>CHANGE: -/+
>POSITION FORWARD:A
>POSITION BACK: ......B
>INSTALLER SETUP: ...D
3. Select language (if required)
Menu-driven programming unit.
Open cover:
Menu optionButton
→ SYSTEM”D”
→ FACTORY SETTING”A”
→ LANGUAGE”C”
Select language.
4. Heating contractor address input
Menu-driven programming unit.
This option allows the system user to access name and telephone number of the
heating contractor on the display (see Vitodens 200 Operating I nstructions) almost
immediately after a system fault has occurred.
CONTRACTOR”C”
Position cursor as required using
the ”A”and”B” buttons.
Select the required characters (number,
letter, special character) by turning
the ”G” selector knob (turn
clockwise or counterclockwise).
Characters already selected can be
deleted with the space character ”k”or
overwritten with another character.
Upon exiting the input menu
(INSTALLER SETUP ”C”), name and
telephone number of the heating
contractor are automatically stored.
5285 961 v1.3
Steps (continued)
Initial Start-up and ServiceInitial Start-up and Service
Initial start-up
The Vitodens 200 boiler is for use with
gases whose characteristics fall within
the following ranges. Do not use any
other types of gas.
Heating value (gross)Btu/ft
Specific gravity0.57 to 0.701.522 to 1.574
Ultimate carbon dioxide (CO2)%11.7 to 12.213.73 to 13.82
Service
Initial start-upService
PE
outlet
5. Select appropriate gas type
1. Ensure that the fuel type listed on
the boiler rating plate is the correct
type for the installation being
attempted.
2. Record fuel type in Maintenance
Record on page 70.
Natural gasPropane gas
3
6. Measure static pressure and running pressure
Static pressure
1. To measure static and/or running
pressure remove burner cover panel
as per the removal and reinstallation
instructions on page 7 in these
instructions.
2. Close gas shutoff valve (field
supplied).
3. Loosen screw in test nipple ”PE” A
on the gas combination valve, do notremove completely. Connect
manometer.
970 to 11002466 to 2542
IMPORTANT
A CO measurement (see page 16 must
be taken before and after working on
gas appliances to eliminate risks to
health and to guarantee the
satisfactory condition of the system.
A
inlet
Measuring static gas supply pressure,
using test nipple “PE”
5285 961 v1.3
4. Open the gas shutoff valve.
5. Measure static pressure. Values
must be:
H 14“w.c.max.forNG
H 14“w.c.max.forLP
6. Enter measured value into
Maintenance Record on page 70 in
this manual.
7. Start up boiler, using the on/off
switch on the boiler control.
IMPORTANT
The burner is automatically ignited and
starts operation after a safety time has
elapsed.
During initial start-up, the unit may
indicate a fault because of air in the gas
supply pipe (especially for propane gas).
After approx. 5 seconds, press the ”EU”
button to reset the burner. The ignition
procedure is repeated. This boiler
employs a direct spark ignition system.
13
Initial Start-up and Service
Steps (continued)
Initial start-upService
6. Measure static pressure and running pressure (continued)
Running pressure
8. Measure the running pressure; value
must be:
Running supply pressure withCorrective action
Natural gasPropane gas
Hunder 4 ”w.c. (WB2-44)
Hunder 7 ”w.c. (WB2-60)
H4 to 14 “w.c. (WB2-44)
H7 to 14 “w.c. (WB2-60)
over 14 ”w.c.over 14 ”w.c.Do not attempt adjustment. Call local
9. Enter gas type into Maintenance
Record on page 70 in this manual.
10. Switch off t he heating system
on/off switch on the boiler control
unit (boiler is shut down), close the
gas shutoff valve, remove the
manometer and re-tighten the
screw in the test nipple ”PE” A.
under 11 ”w.c. Do not attempt adjustment. Call local
11 to 14 ”w.c. Start up boiler.
Use suitable measuring instruments
calibrated with a minimum resolution
of 0.04 “w.c. for measuring the
running pressure.
gas utility to increase pressure.
gas utility to decrease pressure.
Boiler valve must not be exposed to
pressure over 14 ”w.c.
WARNING
Ensure that there is no open flame in
the room.
PE
outlet
A
inlet
Measuring running gas supply pressure,
using test nipple “PE”
11. Open gas shutoff valve and check
that the test nipple ”PE” and all gas
connections are gas-tight.
WARNING
Never purge a gas line into a
combustion chamber. Never use
matches, candles, flame, or other
sources of ignition for purpose of
checking leakage. Use a
soap-and-water solution to check for
leakage. A failure to follow this
warning could result in fire,
explosion, personal injury, or death.
5285 961 v1.3
14
Steps (continued)
Initial Start-up and Service
Initial start-upService
7. How the Vitodens 200 boiler operates...
The MatriX burner blower and the combination gas valve are factory calibrated and
pre-adjusted for optimum boiler performance at all firing rates through a
non-mechanical, pneumatic modulating link between combustion air and gas flows.
Blower speed is automatically increased or decreased based on heat demand and
venting system resistances, thereby regulating the amount of combustion air
drawn. The pneumatic modulating link between air and gas introduces the required
amount of gas for correct combustion to meet the current heat demand, based on
a linear relationship between ∆ Pairand∆ Pgas.
Optimum combustion air flow rate is recognized and monitored by the differential
air pressure sensor (transducer). The output voltage signal of the transducer is
analyzed for logic by the LGM 29.XX burner ignition control unit. The LGM 29.XX
unit contains pre-programmed performance curves and operational safety
parameters unique for every boiler model.
See page 47 for sequence of operation.
Flue gas adaptation function
The Vitodens employs a flue gas adaptation function. This unique function
records, processes, and reacts in real time to fluctuations in pressure drops in the
vent pipe during normal operation caused by partial pipe blockages due to ice
formation at the vent termination, debris and/or sudden high winds. Such increase
in pressure drop, if not promptly corrected, will reduce the combustion air flow
rate, and hence lead to unstable combustion. The differential air pressure sensor
(transducer) records such pressure drops and supplies voltage signals to the LGM
29.XX burner ignition control unit which, in turn (based on stored performance
curves and safety parameters), initiates prompt adjustment of the blower rotational
speed, thus readjusting the combustion air flow rate for optimum combustion. The
same automatic adaptation logic applies if combustion air is reduced (or increased)
due to slower (or faster) blower speed resulting from line voltage drops (or
increases) below (or above) the threshold of 85% (or 110%).
outlet
X
Do not adjust screws X and Y!
5285 961 v1.3
Y
PE
inlet
WARNING
FOR FACTORY CALIBRATING
PURPOSES, THE COMBINATION GAS
VALVE IS EQUIPPED WITH
ADJUSTMENT SCREWS X AND Y.
DO NOT ATTEMPT TO ADJUST OR
READJUST THESE SCREWS.
ANY ATTEMPT TO TAMPER WITH
FACTORY PRE-ADJUSTED SETTINGS
WILL LEAD TO UNSTABLE OPERATION
AND WILL AFFECT BOILER
WARRANTY.
15
Initial Start-up and Service
Steps (continued)
Initial start-upService
The Vitodens 200 boiler is factory
preset for operation with natural gas or
propane. It is recommended t hat a CO
check be performed at the boiler vent
pipe adaptor as part of the initial
start-up/maintenance procedure.
IMPORTANT
The MatriX burner of the Vitodens 200
is preset for the entire gas group. No
adjustment or readjustment of the
burner is required.
8. Check CO2setting
Depending on the gas type, the CO
value lies within the range of
H 6.6 to 10.0% for natural gas
2
H approx. 10.0 % for LP
The CO
compared with the above CO
ranges of the individual gas type.
10: <PL.90> CLOSED
10: BURNER
10: <PL.41> ON
10: is displayed
(”Flue gas”
content.
2
2
value
If the CO
2
than 1% outside the stated range for
NG, or 0.5% outside the stated range
for LP, perform the following steps:
H Check that correct orifice was used
(see subsection entitled “Check
orifice size” on page 17 and section
“Technical Data” on page 46 of this
manual).
H Check the venting system for leaks
(see subsection entitled “Check
venting system f or leaks” on page 18
of this manual).
value measured lies more
2
IMPORTANT
Do not use the emissions test switch
”S” to trigger a call for heat.
16
5. Select top end of rated input range
and check CO
If the value differs by more than one
percentage point, replace burner.
Select menu option
CONTINUE ”A”
until code
11: MODULATION
10: <PL.90> OPEN
10: BURNER
10: <PL.41> ON
10: is displayed
6. Exit the setting mode
H Close cover of programming unit.
H Enter the measured values into
Maintenance Record on page 70 in
this manual.
H Close flue gas measurement
opening
content
2
.
5285 961 v1.3
Steps (continued)
Initial Start-up and Service
Initial start-upService
Clock natural gas meter to verify input
1. Ensure all other gas equipment
served by the meter is turned off
during timing of gas input to the
Vitodens 200 boiler.
2.Measure the time in seconds it takes
for the boiler to use 10 cu. ft. of
gas. Divide 3600 x 10 by the
number of seconds and you get the
number of cu. ft. of gas used per
hour. Multiply this number by the
heating value of the gas to obtain
Btu per hour input.
Service
9. Clock natural gas meter
For example:
A Vitodens 200, WB2 11-44 boiler
(172 000 Btu/h input) requires 209
seconds to use 10 cu. ft. of natural
gas. After contacting the local utility,
you will find the heating value is
1000 Btu per cu. ft.
Therefore,
3600 x 10/209 x 1000 ≅ 172 000
Btu/h input.
Therefore, the boiler input is correct.
Burner input formulas
(for low altitude only):
INPUT=(3600
t=TIME (sec.) f or 1 ft.
INPUT=(3600 x .01 x 1000 x 35.31)÷T
where
T = TIME (sec.) for .01 m
10. Check orifice size
÷t) x 1000 where
3
3
natural gas
IMPORTANT
A boiler underfired by 5% is
acceptable. Do not overfire the boiler.
CAUTION
Always contact your gas utility to
obtain the correct heating value before
clocking the meter.
E
ACB
Stamped identification code
1. Remove burner cover panel (if still
installed) as per the removal and
reinstallation instructions on page 7
in this manual, and reinstall panel
upon completion of service work.
2. Loosen screws A and take the gas
orifice holder C out of the fitting.
3. Read orifice size stamped on the
orifice body and cross-reference to
table below. If wrong orifice is
installed, proceed to next step.
4. Push the gas orifice B sideways out
of the gas orifice holder C.Snap
new and correct gas orifice into gas
orifice holder and push into the gas
train.
5. Tighten screws A.Tighten to a torque of 1.1 lb.ft./
6. Check all gas connections for leaks
with an approved leak test solution.
Overview of orifices
Boiler model
Natural gasE44E60
Liquid propaneP44P60
WB2 11-44WB2 15-60
See section entitled “Technical Data”
on page 46 of this manual for
information on gas orifices.
IMPORTANT
Place O-ring E in groove on new gas
orifice B.
1.5 Nm.
5285 961 v1.3
17
Initial Start-up and Service
Steps (continued)
Initial start-upService
Initial start-upService
11. Check all primary and secondary circuit connections for leaks
Check heating system a nd domestic
hot water connections (if applicable).
Ensure all connections are pressure
tight.
Correct any leaks found on fittings,
pumps, valves, etc.
12. Perform c ombustion analysis
IMPORTANT
A CO measurement (see page 16) must
be taken before and after working on gas
appliances to eliminate risks to health
and to guarantee the satisfactory condition
of the system.
Record the measured combustion
values in the sequence stated in the
Maintenance Record on page 70 in this
manual.
Initial start-up
Combustion air measuring point
13. Check venting system for leaks (circular air gap measurement)
For sealed combustion, coaxial vent only.
Viessmann strongly recommends that
the heating contractor perform a
simplified leak test during boiler
start-up. For this purpose it is sufficient
to measure the CO
the combustion air in the coaxial gap of
the air intake pipe. The vent pipe is
considered sufficiently leak-proof if a
concentration in the combustion
CO
2
airnohigherthan0.2%oranO
concentration no lower than 20.6% is
measured.
concentration of
2
2
If higher CO
are measured, check venting system
thoroughly.
Please note!
The vent pipe adaptor comes with two
measurement ports, one for
combustion air intake measurement
and one for flue gas measurement.
Please note!
This test is not applicable for single wall venting system (non-sealed
combustion).
values or lower O2values
2
18
5285 961 v1.3
Steps (continued)
Initial Start-up and Service
Service
14. Disassemble burner and check burner gasket
1. Remove burner cover panel (if still
installed) as per the removal and
reinstallation instructions on page 7
in this manual, and reinstall panel
upon completion of service work.
2. Switch off the heating system
switch on the control unit and the
power supply.
3. Close gas shutoff valve and secure.
4. Disconnect electrical cables from fan
motor
sensor
transformer
5. Remove two screws
disconnect gas line from gas valve.
6. Loosen six hexagon socket head cap
screws
7. Check burner gaskets for damage
and replace if required (see Parts
List).
, differential a ir pressure
, combination gas valve
, ionization electrode, ignition
and grounding.
to
and remove burner.
Do not lay burner on burner mesh
assembly (wire mesh)!
CAUTION
5285 961 v1.3
Service
Service
15. Visually check exterior of burner mesh assembly
To check the exterior of the burner
mesh assembly for physical damages,
such as dents, corrosion and/or
abnormally large holes:
1. Remove burner cover panel, if still
installed (see page 7). Reinstall
panel upon completion of service
work.
16. Replace burner mesh assembly (if wire mesh is damaged)
1. Remove electrodes.
3. Turn thermal insulation ring
clockwise and remove.
2. Unsrew the eight Torx screws
and remove burner mesh assembly
and assembly gasket.
3. Remove existing burner mesh
assembly gasket.
4. Fit new burner mesh assembly with
the new gasket and tighten with the
eight Torx screws.
IMPORTANT
Do not replace gasket
inspecting the exterior of the mesh
assembly.
Tighten to a torque of 3.3 lb.ft. /
4.5 Nm
when visually
19
Initial Start-up and Service
Steps (continued)
Service
17. Check and adjust ignition and ionization electrode
1. Remove burner cover panel (if still
installed) as per the removal and
reinstallation instructions on page 7
in this manual, and reinstall panel
upon completion of service work.
2. Check electrodes for wear and
contamination.
3. Clean electrodes with small brush or
emery paper.
4. Check clearances. If clearances are
CAUTION
Do not damage wire mesh when
cleaning.
not satisfactory or the electrodes are
damaged, replace electrodes and
gasket A and align.
Tighten fastening screws for the
electrodes to a torque of 1.5 lb.ft. /
2Nm.
+4
8
-0
+3
5
-0
3
+0.5
-0
+0
7
-1
Service
20
18. Check condensate drain
Ensure condensate drains freely (e.g. at
siphon trap
21. Check diaphragm expansion tank and system pressure
Perform check with the system cold.
1. Drain boiler/system and reduce
pressure until the manometer reading
is ”0”.
2. If the nitrogen pressure of the
precharged expansion tank is less
than the static pressure of the
system, inflate membrane pressure
to slightly exceed pressure of
system.
The static pressure required at the
tank is based upon the static height
of the system. The system fill
pressure value must be equal to the
expansion tank pressure value at
approx. 60 ºF/15.6 ºC.
3. Top up with water until filling
pressure is higher than the inlet
pressure of the diaphragm expansion
tank.
Example
Static head of 33 ft./10 m
(distance between boiler and
topmost heat emitter surface)
corresponds to a static
pressure of 1 bar/15 psig.
With the system cold, the filling
pressure must be approx. 3 psig
higher than the static pressure.
Max. operating pressure:
........................................
Min. operating pressure:
........................................
45 psig
12 psig
Initial start-upService
4. When starting up the system for the
first time, mark this value as the
minimum filling pressure on the
manometer.
22. Check functioning of safety valves
Ensure proper operation of low water
cut-off(s) (if applicable), pressure relief
valve, and pump(s).
Check pressure gage, air vent and
pressure relief valve. Ensure that
pressure relief valve does not leak and
that it operates in accordance with
information provided by the
manufacturer.
Refer to maintenance instructions
supplied with low water cut-offs,
pumps, etc.
Flush float water type low water
cut-offs (if used).
A lower manometer reading usually
indicates loss of water due to
leakage. All leaks must be repaired.
Follow local regulations with respect to
backflow preventers.
If oil-lubricated pumps are used, ensure
proper lubrication.
If motorized zone valves are used, refer
to maintenance instructions provided
with zone valves.
22
5285 961 v1.3
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.