Viessmann VITODENSd 100-W, Vitodens 100-W, WB1B Series, WB1B 26, WB1B 35 Technical Data Manual

Technical Data Manual
Model Nos. and pricing: see Price List
Vitodens 100-W WB1B Series
Wall-Mounted, gas-fired condensing boiler with optional on demand hot water CombiPLUS Kit
Heating input: 37 to 118 MBH
10.8 to 34.5 kW
VITODENSd 100-W
Vitodens 100-W, WB1B (with pre-installed coaxial vent pipe adaptor)
Gas-Fired Wall-Mounted Condensing Boiler with modulating stainless steel MatriX cylinder burner, stainless steel Inox­Radial heat exchanger for room air independent operation (using a direct vent system) or room air dependent operation. Optional CombiPLUS Kit providing reliable on demand hot water without a DHW tank is available.
5601 189 v1.1 09/2011
CombiPLUS Kit
General
Product Information
Vitodens 100-W, WB1B Technical Data
Equipped with a Viessmann stainless steel heat exchanger for lasting performance and reliability and a modulating MatriX cylinder gas burner, the Vitodens 100-W wall­mounted condensing boiler is the perfect combination of value, quality and Viessmann technology.
The benefits at a glance:
Outstanding efficiency
of 94.0 % A.F.U.E. on all models.
Lasting performance
with Viessmann-made SA240 316Ti stainless steel Inox-Radial heat exchanger constructed to ASME Section IV and CSA B51.
Low-emission
with fully-modulating stainless steel MatriX cylinder burner. Factory calibration eliminates adjustments in the field. < 29 ppm NOx (at 3% O2) < 40 ppm CO (at 3% O2)
Control variety
Integrated boiler control interfaces with any level of external control - from room thermostat to outdoor reset and more.
Compact, lightweight wall mount design
and zero clearance to combustibles make it a great choice for limited-space installations.
Extremely quiet operation
quieter than most refrigerators. < 50 dBA [at 3.3 ft. (1 meter)]
Multiple venting options
- Horizontal or vertical sealed combustion coaxial, PP(s) vent system (Viessmann supplied).
- Horizontal, vertical or hybrid sealed combustion double-pipe CPVC vent system (field supplied).
- Horizontal or vertical single pipe CPVC vent system (field supplied).
- Horizontal or vertical single or double pipe PP(s), flexible vent system (Viessmann supplied).
Suitable for high altitude levels
of up to 10,000 ft. (3,000 m) without deration.
Built-in automatic frost protection
allows boiler to be shut off for an extended period of time while protecting it against freeze-up.
Reliable on demand hot water
with an optional CombiPLUS kit (no DHW tank required).
- Plate type heat exchanger
- Built-in diverting valve
- Built-in Grundfos 3-speed pump
- Built-in pressure bypass valve
- Built-in water hammer arrester
- Built-in flow sensor
- Built-in temperature sensor
- Supplied with a pressure relief valve rated at 150 psi
Note: Check the boiler rating plate on the Vitodens 100-W, models WB1B-26 or WB1B-35 to ensure it states compatibility with the CombiPLUS kit.
Limited lifetime warranty
in residential applications.
Easy installation, service and maintenance
with all pipe connections located at the bottom and serviceable components (including electrical connections) easily accessible from the front.
2
5601 189 v1.1
Vitodens 100-W, WB1B Technical Data
Product Information
General
Boiler cross-section
Legend
A Stainless steel MatriX cylinder burner
B
Inox-Radial stainless steel heat exchanger
C Burner blower D Gas and hydronic connections E Boiler control
Standard Equipment:
Wall-mount boiler and installation fittings c/w 30 psi pressure relief valve, pressure gage, gas shut-off valve, two fill/drain valves, all mounting hardware, outdoor temperature sensor, and LP conversion kit.
J I
Note: Products may not look exactly as illustrated.
5601 189 v1.1
H
CombiPLUS cross-section
Legend
F Plate-type heat exchanger G Boiler / DHW pump H Flow sensor I Pressure by-pass valve J Diverting valve
GF
3
Technical Data
Vitodens 100-W, WB1B Technical Data
Specifications
Standard heating boiler
Boiler Mo
Natural gas and LPG CSA input
CSA output/DOE 1 heating capacity Net I=B=R rating 2
Heat exchanger surface area
Min. gas supply pressure
Natural gas LPG
Max. gas supply pressure
3
Natural gas and LPG “w.c. 14 14
A.F.U.E. % 94.0 94.0
Weight
Shipping weight
Boiler water content USG
Boiler max. flow rate 4
Max. operating pressure
(max. allowable working pressure) at 210º F (99º C)
Boiler water temperature
- Adjustable high limit (AHL) range
- space heating (steady state)
- DHW production (set-point)
del No. WB1B 26 WB1B 35
MBH
kW
MBH
kW
MBH
ft.
m
“w.c. “w.c.
lbs
kg
lbs
kg
GPM
L/hr.
psig
bar
ºF (ºC) ºF (ºC)
2 2
L
37-91
10.8-26.7 34-83
9.9-24.3 72
10.23
0.95
4
10
78
34.1 95
43
0.87
3.3
6.2
1400
45
3
86 to 176 (30 to 80)
176 (80)
37-118
10.8-34.6 34-108
9.9-31.6
10.23
0.95
34.1
0.87
1400
94
4
10
78
95 43
3.3
6.2
45
3
- Fixed high limit (FHL)
Boiler connections
Boiler heating supply and return Pressure relief valve Drain valve
NPTM (male) “
NPTF (female) “
(male thread) “
ºF (ºC)
Dimensions
Overall depth
inches
mm
Overall width
inches
15 c
mm
Overall height
inches
28 b
mm
1
Output based on 140º F (60º C), 120º F (49º C) system supply / return temperature.
2
Net I=B=R rating based on piping and pick-up allowance of 1.15.
3
If the gas supply pressure exceeds the maximum gas supply pressure value,
a separate gas pressure regulator must be installed upstream of the heating system.
4
See “System Flow Rates” on pages 20 to 25 in this manual.
4
210 (99)
c c c
14d
360
400
725
c c c
14d
360
15 c
400
28b
725
5601 189 v1.1
Vitodens 100-W, WB1B Technical Data
Specifications (continued)
Standard heating boiler (continued)
Boil Gas supply connection
Flue gas
Temperature at boiler return temperature of 86º F (30º C)
- at rated full load
- at rated partial load Temperature at boiler return temperature of 140º F (60º C)
Flue gas value
Mass flow rate (of flue gas)
5
Technical Data
er Model No. WB1B 26 WB1B 35
NPTF
(female)”
ºF (ºC) ºF (ºC)
ºF (ºC)
127 (53)
c c
90 (32)
167 (75)
131 (55)
90 (32)
172 (78)
- at rated full load
- at rated partial load
Available draught
lbs/h
kg/h
lbs/h
kg/h
Pa
mbar
79.2
36.0
33.0
15.0
100
1.0
100.1
45.5
33.0
15.0
100
1.0
Flue gas temperature sensor limit ºF (ºC) 230 (110) 230 (110)
Average condensate flow rate
6
with natural gas
- TS/TR =122 / 86º F (50 / 30º C) USG/day L/day
Condensate connection
7
hose
nozzle
1.95-2.3 8-9
2.5-2.8
9.4-10.5
Ø in 1 1
Boiler flue gas connection
8
Combustion air supply connection
8 single
coaxial
outer Ø in (mm) 4 (100)
Ø
in (mm) 2e
2e (60)
(60) 2e (60)
4 (100)
2e (60)
Noise level (at 1 meter)
- at full load
- at partial load High altitude (factory set)
9
(dB) (dB)
47 40
49 42
ft. (m) 0-5,000 (0-1,500) 0-5,000 (0-1,500)
5
Measured flue gas temperature with a combustion air temperature of 68° F (20° C).
6
Based on typical boiler cycles, including partial load conditions.
7
Requires 1”(25) mm tubing. See Vitodens 100-W Installation Instructions for details.
8
For detailed information refer to the Vitodens Venting System Installation Instructions.
9
For 5,000 to 10,000 ft. (1,500 to 3,048 m) operation, a control programming change is required.
Refer to the Installation and Service Instructions for details. u For information regarding other Viessmann System Technology componentry,
please reference documentation of respective product.
5601 189 v1.1
5
Technical Data
Vitodens 100-W, WB1B Technical Data
Specifications (continued)
CombiPLUS (Integrated with the Boiler)
Boiler Model No. WB1B 26 WB1B 35
DHW supply temperature ºF (ºC) 140 (60) 140 (60)
Continuous draw rate
with DCW temp. of 56º F (13º C)
Continuous draw rate
at t= 63º F (35K)
Maximum allowable working pressure (potable water) psi 150 150
Test pressure psi 300 300
Connections, DHW and DCW NPTM (male) “
Connections to boiler supply/return and to heating supply/return
Dimensions
Overall depth
Overall width
Overall height
Height with pipe connector
Integrated pump flow rate DHW production @ 23 ft. (9.8 m) Head pressure
Heating system operation with system side additional drop in pressure of max. 6 ft. of water (1.8 m)
Weight lbs
1
2
NPTM (male) “
USG/h
L/h
USG/h
L/h
inches
mm
inches
mm
inches
mm
inches
mm
USG/min.
L/h
USG/min.
L/h
kg
99
374
156 589
b b c
c
9.8
250
17
432
8.7
223
13
331
5.63
1278
6.2
1408
25 11
147 556
216 800
250
432
223
331
5.63
1278
1408
9.8
17
8.7
13
6.2
25 11
1
Based on boiler max. output and boiler supply temperature of 176º F (80º C).
2
DCW and DHW temperature rise would be proportional. Maximum DHW supply temperature is 140º F (60º C).
6
5601 189 v1.1
Vitodens 100-W, WB1B Technical Data
Boiler dimensions without bottom piping connections
Dimensions
Front view Side view Top view
Connections Vitodens 100-W, WB1B 26, 35
Legend Connections
A Condensate drain, plastic hose Ø 0.87” (22 mm) B
Boiler water supply, NPT ¾” (male thread)
C Gas connection, NPT ¾” (male thread) D Boiler water return, NPT ¾” (male thread) E Combustion air opening for double pipe system F Combustion air opening for coaxial system
Note: If using the optional CombiPLUS see page 9.
Dimensions
a See illustration for dimensions b 15¾” (400 mm) c 2f” (68 mm) d 28½” (725 mm) e 47/8” (123 mm) f 6d” (156 mm) g 14d” (360 mm) h 5” (125 mm) j 12” (305 mm) k 1a” (31 mm) m 77/8” (200 mm) n 3d” (80 mm)
5601 189 v1.1
7
Dimensions
Boiler dimensions with piping connections
Piping connections for Vitodens 100-W, WB1B 26 and 35 (factory supplied)
Vitodens 100-W, WB1B Technical Data
Note: If using the optional CombiPLUS see page 9.
Legend
BWR Boiler water return, ¾” BWS Boiler water supply, ¾” BD BF Boiler fill GC Gas connection, ¾” NPTM (male thread) PRV Pressure relief valve PG Pressure gage VC Venting connection CAI Combustion air inlet connection (optional)
Boiler drain
8
5601 189 v1.1
Vitodens 100-W, WB1B Technical Data
CombiPLUS dimensions and piping connections
CombiPLUS Connections
Dimensions
Front view
Top view
Legend
A Boiler water supply, NPTM ¾” (male thread) B
Boiler water return, NPTM ¾” (male thread)
C System water supply, NPTM ¾” (male thread) D System water return, NPTM ¾” (male thread) E DHW, NPTM ½” (male thread) F DCW, NPTM ½” (male thread)
Side view
with 7”
flex pipes
A B
C DE F
Front view
5601 189 v1.1
9
Dimensions
Boiler minimum clearances
Vitodens 100-W, WB1B Technical Data
Recommended minimum boiler service clearances
Side
Top
Front
Side
5
7”/178mm
Back
Recommended minimum boiler and CombiPLUS Kit clearances to combustibles
Top Front Rear Left Right Vent
0 0 AL,
CL
AL = Alcove CL = Closet
1
*
Re
fer to the Installation Instructions of the Vitodens Venting System for details.
Note: The Vitodens 100-W boiler has passed the zero inches vent clearance to combustibles testing requirements dictated by the boiler latest Harmonized Standard ANSI Z21.13. CSA 4.9.2007 and therefore is listed for zero clearance to combustibles when vented with a single-wall special venting system (AL-29-4C material) or UL/ULC-listed CPVC/PP(s) gas vent material. The zero inches vent clearance to combustibles for the Vitodens 100-W boiler supercedes the clearance to combustibles listing that appears on the special venting system label.
0
0 0 0
pipe*
1
CombiPLUS installation options
Min. distance between the boiler and CombiPLUS with Viessmann supplied 7” flex piping connection fittings.
Note: The maximum distance between the boiler and the CombiPLUS is restricted by the cable to 36” (915 mm).
10
communication
Shown is the maximum distance between the boiler and CombiPLUS using field supplied fittings and pipes.
5601 189 v1.1