Viessmann WB1A Series Installation And Service Instructions Manual

VITODENS 100-W
Installation and Service Instructions
for use by heating contractor
Vitodens 100-W WB1A Series
Wall-mounted, natural gas-fired condensing boiler
For natural gas Heating input 29 to 100 MBH
8.5 to 29.3 kW
Read and save these instructions for future reference.
IMPORTANT
Vitodens 100-W, WB1A (with preinstalled coaxial vent pipe adaptor)
Please file in Service Binder
5581 775 v1.3 08/2009
All manuals and user guides at all-guides.com
all-guides.com
Safety, Installation and Warranty Requirements
2
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
H Licensed professional heating
contractor
The installation, service, and maintenance of this equipment must be performed by a licensed professional heating contractor.
"
Please see section entitled Important Regulatory and Installation Requirements in the Installation Instructions.
H Product documentation
Read all applicable documentation
before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
"
For a listing of applicable literature, please see section entitled Important Regulatory and Installation Requirements in the Installation Instructions.
H Advice to owner
Once the installation work is complete, the heating contractor must familiarize the system operator/ultimate owner with all equipment, as well as safety precautions/requirements, shut-down procedure, and the need for professional service annually before the heating season begins.
H Carbon monoxide
Improper installation, service and/or maintenance can cause flue products to flow into living space. Flue products contain poisonous carbon monoxide gas.
"
For information pertaining to the proper installation, service and maintenance of this equipment to avoid formation of carbon monoxide, please see the Installation Instructions of the Vitodens Venting System.
H Equipment venting
Never operate boiler without an installed venting system. An improper venting system can cause carbon monoxide poisoning.
H Warranty
Information contained in this and related product documentation must be read and followed. Failure
to do so may render warranty null and void.
5581 775 1.3
Installers must follow local regulations with respect to installation of carbon monoxide detectors. Follow manufacturers maintenance schedule of boiler.
WARNING
All manuals and user guides at all-guides.com
Index
3
Page
Safety
Important Regulatory and Installation Requirements 5
. . . .. . . . . . . . . . . . . . . . . . . . . . .
General Information
About these Installation Instructions 8
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . .
Applicability 9
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . .
Product Information 9
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . .
Mechanical Room 10
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .
Set-up
Before Set-up 12
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . .
Minimum Clearances 12
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . .
Boiler Connections
Preparing the Connections 13
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . .
Connections overview 13
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . .
Dimensions overview without bottom connections 13
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . .
Dimensions overview with connections 13
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . ..
Dimensions overview with connections and alternative drain connection 13
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . .
Wall Mounting 16
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . .
Wall mounting bracket installation 16
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . .
Mounting Vitodens 100-W boiler 18
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . .
Connections 18
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . .
Flue gas connection 18
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . .
Proper piping practice 19
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . .
Gas connection and piping 19
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . .
Gas piping pressure test 21
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . .
Heating water connections 22
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . .
Condensate connection 23
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . .
Fill siphon with water 23
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . .
Safety Connections and Pressure Testing 24
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .
Installing safety devices on the boiler 24
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . .
Performing pressure test on the boiler 25
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . .
Installation Examples 26
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . .
Boiler in heating/cooling application 34
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . .
Boiler with low water cut-off (remote mounted, field supplied) 35
. . . .. .
Low-loss header 36
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . .
Venting Connection 37
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . .
Control Connections
Electrical Connections 37
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .
Removing the control unit and opening the power pump module 37
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . .
Electrical connections to the power pump module 38
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . .
Closing the power pump module and reinstalling the control unit 39
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . .
Reinstalling the front cover panel 39
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . .
5581 775 1.3
All manuals and user guides at all-guides.com
4
Initial Start-up, Inspection and Maintenance
Necessary Tools 40
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. .
Overview of Controls and Indicators 41
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . .
Overview of Components 43
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . .
Procedure (Overview) 44
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . .
Steps 45
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting
Troubleshooting Steps 60
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . .
Overview of Controls and Indicators 60
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . .
Changing Room Temperature 61
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . .
Diagnosis 62
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . .
Sequence of operation and potential faults during each start-up cycle 62
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . .
Diagnostics table: Faults with fault display on control unit 63
. . . .. . . . . . . . .
Correction 65
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . .
Remove front cover panel 65
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . .
Check boiler temperature sensor 65
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . .
Check fixed high limit 66
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .
Check fuses 67
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . .
Additional Information
Technical Data 68
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . .
Burner Program Sequence of Operation 70
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . ..
Wiring Diagram 71
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . .
Parts List 72
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . .
Maintenance Record 74
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . .
Lighting and Operating Instructions 75
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . .
5581 775 1.3
All manuals and user guides at all-guides.com
Safety
5
Important Regulatory and Installation Requirements
Codes
The installation of this unit shall be in accordance with local codes or, in the absence of local codes, use CAN/CSA-B149.1 or .2 Installation Codes for Gas Burning Appliances for Canada. For U.S. installations use the National Fuel Gas Code ANSI Z223.1. Always use latest editions of codes.
In Canada all electrical wiring is to be done in accordance with the latest edition of CSA C22.1 Part 1 and/or local codes. In the U.S. use the National Electrical Code ANSI/NFPA
70. The heating contractor must also comply with both the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, and the Installation Code for Hydronic Heating Systems, CSA B214-01, where required by the authority having jurisdiction.
Leave all literature at the installation site and advise the system operator/ultimate owner where the literature can be found. Contact Viessmann for additional copies.
This product comes with several safety instruction labels attached. Do not remove! Contact Viessmann immediately if replacement labels are required.
Special Requirements for Side-Wall Vented Appliances In the Commonwealth of Massachusetts
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for installation of side-wall vented gas appliances as follows:
(a) For all side-wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole
or in part for residential purposes, including those owned or operated by the Commonwealth and where the side-wall exhaust vent termination is less than (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side-wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side-wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professional for the installation of hard-wired carbon monoxide detectors.
a. In the event that the side-wall horizontally vented gas fueled equipment is installed in a crawl space or an attic,
the hard-wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Continued on following page.
5581 775 1.3
All manuals and user guides at all-guides.com
Safety
6
Important Regulatory and Installation Requirements
(continued)
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
4. INSPECTION. The state or local gas inspector of the side-wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled Equipment Not Required To Be Vented in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side-wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of
Product Approved side-wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side-wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies special venting systems, the following requirements shall be satisfied by the manufacturer:
1. The referenced special venting system instructions shall be included with the appliance or equipment installation instructions; and
2. The special venting systems shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side-wall horizontally vented gas fueled equipment, all
venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
5581 775 1.3
All manuals and user guides at all-guides.com
all-guides.com
Safety
7
Important Regulatory and Installation Requirements
(continued)
Working on the equipment
The installation, adjustment, service, and maintenance of this boiler must be performed by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burners, or control.
Ensure main power supply to equipment, the heating system, and all external controls has been deactivated. Close main gas supply valve. Take precautions in all instances to avoid accidental activation of power during service work.
The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. This includes low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, etc.
Technical literature
Literature for the Vitodens boiler:
- Technical Data Manual
- Installation and Service Instructions
- Operating Instructions and Users Information Manual
- Vitodens Venting System Installation Instructions
- Instructions of other products utilized and installed
- Installation codes mentioned in this manual and as locally applicable
Leave all literature at the installation site and advise the system operator/ultimate owner where the literature can be found. Contact Viessmann for additional copies.
This product comes with several safety instruction labels attached. Do not remove! Contact Viessmann immediately if replacement labels are required.
5581 775 1.3
All manuals and user guides at all-guides.com
General Information
8
About these Installation Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include WARNING, CAUTION, and IMPORTANT. See below.
Warnings draw your attention to the presence of potential hazards or important product information.
Cautions draw your attention to the presence of potential hazards or important product information.
Helpful hints for installation, operation or maintenance which pertain to the product.
This symbol indicates that additional, pertinent information is to be found in column three.
This symbol indicates that other instructions must be referenced.
5581 775 1.3
Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage.
WARNING
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/property damage.
CAUTION
IMPORTANT
All manuals and user guides at all-guides.com
General Information
9
Applicability
Boiler serial number must be provided when ordering replacement parts. Both the 16-digit serial number bar code paper label and the 12-digit ASME/NB serial number correlate to each other. Providing either serial number is sufficient.
Vitodens 100-W, WB1A 8-24, 8-30
Model No. Serial No.
WB1A 8-24 7246174 and WB1A 8-30 7246175
Product Information
Natural gas-fired wall-mounted hot water heating boiler for space heating.
For operation with constant (set point) boiler water temperatures in closed loop, forced circulation hot water heating circuits. An external controller is required for outdoor responsive control and DHW production.
The Vitodens 100-W comes factory set for operation with natural gas, with no option of conversion to liquid propane.
Boiler model must be selected based on an accurate heat loss calculation of the building. Ensure boiler model is compatible with connected radiation.
Vitodens 100 boilers are 100% factory tested and calibrated. No further adjustments are required during field start-up.
To vent this boiler, follow the Vitodens Venting System Installation Instructions.
5581 775 1.3
IMPORTANT
Serial No. location (16-digit barcode white paper label located on the left or right side of the boiler)
ASME/NB stamp serial number location (12-digit metallic plate riveted on the heat exchanger)
All manuals and user guides at all-guides.com
General Information
10
Mechanical Room
During the early stages of new home design, we recommend that proper consideration be given to constructing a separate mechanical room dedicated to gas- or oil-fired equipment including domestic hot water storage tanks.
The boiler must be located in a heated indoor space, near a floor drain, and as close as possible to the wall.
Whenever possible, install boiler near an outside wall so that it is easy to duct the venting system to the boiler.
Locate boiler on walls capable of supporting the weight of the boiler filled with water (see section entitled Technical Data on page 68 for information required for total boiler weight calculation). Ensure that boiler location does not interfere with proper circulation of combustion and ventilation air of other fuel burning equipment (if applicable) within the mechanical room.
The maximum room temperature of the mechanical room where the boiler is located must not exceed 104°F/40°C.
Boiler operation in marine environments (damp, salty coastal areas):
The service life of the boilers exposed metallic surfaces, such as the casing and fan housing, is directly influenced by proximity to damp and salty marine environments. In such areas, higher concentration levels of chlorides from sea spray, coupled with relative humidity, can lead to degradation of the exposed metallic surfaces mentioned above. Therefore, it is imperative that boilers installed in such environments not be installed using direct vent systems which draw outdoor air for combustion. Such boilers must be installed using room air dependent vent systems; i.e. using room air for combustion. The indoor air will have a much lower relative humidity and, hence, potential corrosion will be minimized.
5581 775 1.3
IMPORTANT
All manuals and user guides at all-guides.com
General Information
11
Mechanical Room
(continued)
Installation area conditions
H Ensure ambient temperatures are
higher than 32°F / 0°C and lower than 104°F / 40°C.
H Prevent the air from becoming
contaminated by halogenated hydrocarbons (e.g. as contained in paints solvents or cleaning fluids) and excessive dust (e.g. through grinding or polishing work). Combustion air for the heating process, and ventilation of the boiler room must be free of corrosive contaminants. To that end, any boiler must be installed in an area that has no chemical exposure. The list to the right indicates the main, currently known sources.
H Avoid continuously high levels of
humidity (e.g. through frequent drying of laundry).
H Never close existing ventilation
openings.
Sources of combustion and ventilation air contaminants
Areas likely to contain contaminants:
H New building construction H Swimming pools H Remodelling areas, hobby rooms H Garages with workshops H Furniture refinishing areas H Dry cleaning/laundry areas and
establishments
H Auto body shops H Refrigeration repair shops H Metal fabrication plants H Plastic manufacturing plants H Photo processing plants H Beauty salons
Products containing contaminants:
H Chlorine-type bleaches, detergents
and cleaning solvents found in household laundry rooms
H Paint and varnish removers H Hydrochloric acid, muriatic acid H Chlorine-based swimming pool
chemicals
H Spray cans containing
chlorofluorocarbons
H Chlorinated waxes and cleaners H Cements and glues H Refrigerant leaks H Calcium chloride used for thawing H Sodium chloride used for water
softening salt
H Permanent wave solutions H Adhesives used to fasten building
products and other similar items
H Antistatic fabric softeners used in
clothes dryers
If you notice fire coming from the appliance, call the fire department immediately! Do not attempt to extinguish the fire unless qualified to do so.
WARNING
Fire causes a risk of burns and explosion!
HHHH Shut down the boiler HHHH Close fuel shut-off valves HHHH Use a tested fire extinguisher,
class ABC.
WARNING
Incorrect ambient conditions can lead to damage to the heating system and put safe operation at risk.
WARNING
All manuals and user guides at all-guides.com
all-guides.com
General Information/Set-up
12
Before Set-up
Before placing boiler in its installation location, ensure all necessary accessories are installed.
Minimum Clearances
Recommended minimum service clearances
Refer to the illustrations on the left hand side.
Note: The Vitodens 100-W boiler has passed the zero inches vent clearance to combustibles testing requirements dictated by the boiler Harmonized Standard ANSI Z21.13. CSA 4.9.2005 and therefore is listed for zero clearance to combustibles when vented with a single wall special venting system (AL-29-4C material) or UL/ULC-listed CPVC gas vent material. The zero inches vent clearance to combustibles for the Vitodens 100-W boiler supercedes the clearance to combustibles listing that appears on the special venting system label.
Clearances to combustibles
Top Front Rear Left Right Vent pipe
*1
0 0 AL, CL 0 0 0 0
AL = Alcove CL = Closet
*1
Refer to the Installation Instructions of the Vitodens
Venting System for details.
The boiler must be installed in such a way that gas ignition system components are protected from water (spraying, splashing, etc.) during boiler operation and service.
CAUTION
Top clearance - 12. See Vitodens Venting System Installation Instructions.
12/300 mm
*
4/100 mm
28/ 700 mm
¼/5 mm ¼/5 mm¼/5 mm
Front
12/305 mm
Top
*
12/305 mm
0/mm
28/700 mm
Side
0/mm
Back
Sid
e
All manuals and user guides at all-guides.com
Boiler Connections
13
Preparing the Connections
Use an approved pipe sealant or teflon tape when connecting the following installation fittings.
Connections overview
This section constitutes an overview only! Refer to subsequent sections for detailed information on individual piping connections.
Piping connections for Vitodens 100-W, WB1A 8-24 and 8-30 (factory supplied)
Legend
BWR Boiler water return, ¾ BWS Boiler water supply, ¾ BD Boiler drain BF Boiler fill GC Gas connection, ¾ NPTM
(male thread) PRV Pressure relief valve NPT National Pipe Thread PG Pressure gage VC Vent connection
5581 775 1.3
BWS
BWR
NPT
GC
PRV
BD
PG
BF
VC
NPT
NPT
All manuals and user guides at all-guides.com
Boiler Connections
14
Preparing the Connections
(continued)
Dimensions overview without bottom connections
Connections Vitodens 100-W, WB1A 8-24, 8-30
Legend
Boiler water supply, NPT ¾ (male thread) Condensate drain, plastic hose Ø 0.87 / 22mm Gas connection, NPT ¾ (male thread) Boiler water return, NPT ¾ (male
thread) a 7 / 180 mm b 15¾ / 400 mm c 2¼ or 27/16 / 58 mm or 62 mm d 27½ / 700 mm e 47/8 / 123 mm f 7¼ / 183 mm g 133/8 / 340 mm h 5 / 125 mm
Vitodens 100-W, WB1A side view
When preparing gas, water and electrical connections in the field, see section entitled Wall Mounting on page 16 of this manual for information regarding the installation of the wall mounting bracket.
The maximum ambient temperature must not exceed 104 ºF/40 ºC.
H Heating water connections and gas
connection to be made in the field. See illustration to the left and connection-specific section for details.
H See subsection entitled Power
supply connection for details regarding power supply to the Vitodens 100-W boiler.
5581 775 1.3
d
c
h
e
g
a f
b
e
IMPORTANT
All manuals and user guides at all-guides.com
Boiler Connections
15
Preparing the Connections
(continued)
Dimensions overview with connections
This section constitutes an overview only! Refer to subsequent sections for detailed information on individual piping connections.
Piping connections for Vitodens 100-W, WB1A 8-24 and 8-30 (factory supplied)
Legend
BWR Boiler water return, ¾ BWS Boiler water supply, ¾ BD Boiler drain BF Boiler fill GC Gas connection, ¾ NPTM
(male thread) PRV Pressure relief valve PG Pressure gage VC Venting connection
5581 775 1.3
14 / 355mm
15¾ / 400mm
27/8 / 73mm
5
3
/
8
/ 137mm
27½ / 700mm
33 / 838mm
12 / 300mm
2¼ or
27/16
/ 58mm or 62 mm
6 / 152mm
47/8 / 123mm
47/8 / 123mm
VC
PRV
BD
GC
PG
BF
BWS
BWR
All manuals and user guides at all-guides.com
Boiler Connections
16
Wall Mounting
Wall mounting bracket installation
Legend
Mounting template Finished floor level
Dimensions
a 12 / 300mm b min. 45 / 1143mm
The Vitodens 100-W can be wall-mounted on
H a brick/concrete wall H wood studs H metal studs
Following are the installation instructions for the mounting bracket on each material. Skip to the installation instructions applicable to your installation requirements.
Installation of mounting bracket on brick/concrete wall:
1. Drill holes (Ø3/8/10 mm), using
mounting template supplied with the boiler.
2. Align wall mounting bracket and attach to wall with the screws and plastic anchors supplied.
5581 775 1.3
Ø3/8 / 10mm
2x
1.
2.
a
b
Whichever mounting method is used, ensure that the bracket is tightly and securely fastened to wall. Failure to secure boiler properly could cause boiler to loosen, posing a severe safety hazard.
CAUTION
All manuals and user guides at all-guides.com
all-guides.com
Boiler Connections
Installation of mounting bracket
a
a = 16/407 mm
Installation of mounting bracket on wood studs
16/407 mm
3/16
2x
Installation of mounting bracket on metal studs
5/8
2x
16/407 mm
17
Wall Mounting
(continued)
Mounting bracket installation (continued)
Installation of mounting bracket on wood and metal studs
To mount the Vitodens 100-W boiler on wood or metal studs, install mounting bracket on wall as shown on previous page. Refer to drawings on the left and below for more detailed installation information.
Install mounting bracket on wood studs as per illustration. Drill3/16 pilot holes to insert mounting bolts. Ensure that holes are located in the center of each wood stud.
Install mounting bracket on metal studs as per illustration. Drill5/8 pilot holes to insert mounting bolts. Ensure that holes are located in the center of each metal stud. Secure mounting bracket with bolts to metal studs as shown.
5581 775 1.3
All manuals and user guides at all-guides.com
Boiler Connections
Boiler Connections
18
Wall Mounting
(continued)
Mounting Vitodens 100-W boiler
1. Remove the screw at the top of
boiler.
2. Press down on springs at bottom of boiler and remove the front enclosure panel.
3. Remove front enclosure panel.
4. Mount boiler onto the mounting
bracket.
For installation of the mounting bracket, see subsection entitled Wall mounting bracket installation on page 16 of this manual.
Connections
Flue gas connection
Combustion air Flue gases
The Vitodens 100-W boiler comes with a preinstalled vent pipe adaptor (as shown). Run venting system, single-pipe, double-pipe or coaxial, through the side wall or the roof, taking the shortest possible route and at a rising angle (min. 3º).
Read and follow the Installation Instructions Vitodens Venting System for details.
5581 775 1.35581 775 1.3
All manuals and user guides at all-guides.com
Boiler Connections
19
Connections
(continued)
Proper piping practice
Support piping by proper suspension method. Piping must not rest on or be supported by boiler.
Gas connection and piping
Legend
Water supply connection Condensate drain connection Gas connection Water return connection
1. Make gas connection in accordance with codes CAN/CSA B149.1 or National Fuel Gas Code ANSI Z223.1/NFPA 54, as well as local codes where applicable.
2. Close gas shutoff valve on boiler.
3. Perform leak test.
4. Bleed air from gas supply pipe.
See following page for details on gas connection and piping.
5581 775 1.3
Usemoderateamountofdope
Leave 2 end threads bare
hread pipe right length
2imperfectthreads
¨
zz
All manuals and user guides at all-guides.com
Boiler Connections
20
Connections
(continued)
Gas connection and piping (continued)
Legend
Gas connection Accessible manual gas shutoff (factory supplied) Drip leg
Max. gas supply pressure: 14 w.c.
1. Refer to current CAN/CSA B149.1 or
National Fuel Gas Code ANSI Z223.1/NFPA 54, as well as local codes for gas piping requirements and sizing. Pipe size to the boiler must be determined based on: pipe length number of fittings maximum input requirements of all
gas appliances in the residence.
Design piping layout in such a way that piping does not interfere with serviceable components.
2. Before connecting boiler to gas line,
install ground joint union, capped drip leg and a manual equipment shutoff valve. Valves must be listed by a nationally recognized testing agency. Make boiler gas connection as shown on the left.
Gas connection (NPT) ¾
. . . .. . . . . . . . . . . . . . .
3. Perform gas piping pressure test as described in the following subsection.
4. Identify shutoff valves as such with a tab and familiarize operator/ultimate owner of boiler with these valves.
5581 775 1.35581 775 1.3
IMPORTANT
The gas supply piping must be leak tested before placing the boiler in operation.
WARNING
Ensure that gas piping is large enough for all appliances in the residence. No noticeable gas pressure drop in the gas line must occur when any unit (or combination of units) lights or runs.
CAUTION
IMPORTANT
All manuals and user guides at all-guides.com
Boiler Connections
21
Connections
(continued)
Gas piping pressure test
When performing the gas piping pressure test, ensure the following requirements are met.
½ psig = 14 w.c.
1. Isolate the boiler from the gas supply
piping system using the individual manual shutoff valve during pressure tests equal to or less than ½ psig/ 14 w.c.
2. The boiler and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psig/14 w.c.
3. Perform leak test. Use approved liquid spray solution for bubble test. Ensure that no liquid is sprayed on any electrical components, wires or connectors. Do not allow leak detection fluid to contact gas valve regulator or regulator vent opening.
4. Correct any and all deficiencies.
5. Remove air from gas line.
5581 775 1.3
Never check for gas leaks with an open flame.
WARNING
Exposing boiler gas pressure regulator and gas valve to extreme pressures renders warranty null and void.
WARNING
IMPORTANT
All manuals and user guides at all-guides.com
all-guides.com
Boiler Connections
22
Connections
(continued)
Heating water connections
Legend
BWR Boiler water return, ¾ BWS Boiler water supply, ¾ BD Boiler drain BF Boiler fill GC Gas connection, ¾ NPTM PRV Pressure relief valve NPT National Pipe Thread PG Pressure gage
1. Thoroughly flush heating system (particularly before connecting the boiler to an existing system).
2. Connect boiler to the heating system.
Max. operating pressure 3 bar/
. . . ..
45 psig
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . .
Test pressure 4 bar/
. . . .. . . . . . . . . . . . . . . . . . . . . . .
60 psig
. . . .. . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . .. . . .
Damage resulting from pressure exceeding those values stated is not covered by Viessmann warranty.
H Use a two-hand wrench method
when tightening fittings or piping onto the boiler connectors. Use one wrench to prevent the boiler pipes from twisting and the second wrench to tighten the fitting or piping. Failure to support the boiler connection could damage the boiler and its internal piping.
H All plumbing must meet or exceed all
local state and national plumbing codes.
SUPPORT ALL PIPING USING HANGERS. DO NOT support piping by the unit or its components.
H Use isolation valves to isolate system
components.
5581 775 1.35581 775 1.3
BWS
BWR
NPT
GC
PRV
BD
PG
BF
IMPORTANT
IMPORTANT
All manuals and user guides at all-guides.com
Boiler Connections
23
Connections
(continued)
Condensate connection
Flexible discharge tubing Discharge tubing
The Vitodens 100-W boiler comes with a built-in condensate trap. An external trap is not required when connecting the field drain to flexible discharge tubing. Discharge tubing (field supplied) must be of 1 diameter. Use CPVC, PVC or other material approved by codes listed below. In the U.S. the drain pipe and fittings must conform to ANSI standards and ASTM D1785 or D2846. CPVC or PVC cement and primer must conform to ASTM D2564 or F493. In Canada use CSA or ULC listed schedule 40 CPVC or PVC drain pipe, fittings and cement. If the condensate outlet of the Vitodens 100-W boiler is lower than the drain, a condensate pump must be installed. Select a pump which is approved for condensing boiler applications. To avoid condensate spillage, select a pump with an overflow switch. The drain connection must terminate into an open or vented drain as close to the boiler as possible to prevent siphoning of the boiler drain.
1. Install the condensate drain pipe with a suitable gradient.
2. Discharge condensate from the boiler into the drainage system, either directly or (if required) via a neutralization unit (accessory).
Installation Instructions of Neutralization Unit (if applicable)
Pipe ventilation must take place between the siphon trap and the neutralization unit (if applicable).
Do not connect the drain pipe from any other appliance, such as water softener backwash pipe, to Vitodens condensate drain pipe.
Fill Siphon with water
Fill a minimum of 10 fl.oz. / 0.3 liters of water into the boiler adaptor.
5581 775 1.3
IMPORTANT
IMPORTANT
At initial start-up, flue gases may be emitted from the condensate drain. Fill the siphon with water before start-up.
WARNING
All manuals and user guides at all-guides.com
Loading...
+ 53 hidden pages