Installation Instructions
for use by heating contractor
Burner Mixture Damper Replacement, Part No. 7374 870
for Vitodens 100-W, type WB1A boilers
Safety and Installation Requirements
Working on the equipment
Please file in Service Binder
The installation, adjustment, service and maintenance of this product must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burner or control.
Ensure main power supply to equipment, the heating system, and all external controls has been deactivated. Close main gas supply valve. Take precautions in both instances to avoid accidental activation of power during service work.
Ensure that the installation literature of other applicable components is referenced.
Enclosure Removal
1. Remove the screw at the top of
boiler A.
2. Press down on springs at bottom
of boiler B and remove the front enclosure panel C.
3. Flip control console down D.
4. Shut off the secondary side of the boiler and isolate the boiler from the system.
Note:
The boiler is still filled with water.
5730 003 v1.1 02/2009
Page 2
Burner Removal
Mixture Damper Location
5. Disconnect electrical cables from
gas valve E and ignition transformer unit F.
6. Remove connection hose D from
air pressure switch.
7. Loosen the fitting C on the gas
connection pipe.
8. Loosen four screws B, remove
burner and disconnect all electrical cables from blower motor A.
CAUTION
To avoid damage to the burner, do not lay burner on its cylindrical burner tube. Failure to heed this caution may cause damage to the burner tube, which may lead to improper operation.
2
5730 003 v1.1 02/2009
Page 3
Burner Disassembly and Mixture Damper Replacement
5
ATTENTION
Ensure tab of flapper is pointing downward!
1
2
3
9. Remove two screws 2 and remove mixture damper 3 located between burner chassis 1 and
fan motor 5.
10. Remove mixture damper and discard.
11. Install newly supplied mixture
damper. See picture below (rotate 180°).
12. Reassemble the burner in reverse
order with new burner gasket.
IMPORTANT
Ensure that mixture damper 3 is correctly positioned. See Attention below. Check mixture damper for free movement (opens up in the direction of the air flow).
2 44.3 inch-pounds (5 Nm)
For tightening, use a calibrated torque wrench.
IMPORTANT
Perform gas leak testing. Use new gaskets, if needed.
13. Check the gas connections for leaks.
WRONG!! CORRECT!!
5730 003 v1.1 02/2009
3
Page 4
Burner Removal
14. Replace electrical cables from fan
motor A, mount burner, and diagonally tighten 4 torque screws B (approx. 3 ft.lbs/4 Nm using a calibrated torque wrench).
15. Insert new gasket and tighten the
fitting C on the gas connection pipe.
16. Insert air pressure switch
connection pipe D onto the gas valve “OUT” connector (P2 on the switch).
17. Replace electrical cables from gas
valve E, and ignition transformer unit F.
18. Open gas shutoff valve and switch on power supply.
Printed on environmentally friendly
(recycled and recyclable) paper.
Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island • 02886 • USA 1-800-288-0667 • Fax (401) 732-0590 www.viessmann-us.com • info@viessmann-us.com
4
Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario • N2V 2G5 • Canada 1-800-387-7373 • Fax. (519) 885-0887 www.viessmann.com • info@viessmann.ca
5730 003 v1.1 02/2009 Technical information subject to change without notice.
Loading...