Viessmann VITOROND 200, VD2-320, VD2-380, VD2-440, VD2-500 Technical Data Manual

...
Page 1
VVVVIIIITTTTOOOORRRROOOONNNNDDDD 222200000000
Triple-pass hot water heating boiler
1255 to 4387 MBH / 368 to 1285 kW
Product may not be exactly as illustrated.
Technical Data Manual
Model Nos. and pricing: see Price List
Vitorond 200
Oil-/Gas-fired boiler
sectional cast iron design with Eutectoplex heat transfer surface, in triple-pass design for operation with modulating water temperatures Heating input: 1255 to 4387 MBH
368 to 1285 kW
5285428v1.607/201
0
Page 2
Product Information
2 VITOROND 200, VD2
VITOROND 200
The modular sectional cast iron design of the Vitorond 200, VD2 allows for problem-free transport into difficult-to-access boiler rooms and permits easy assembly. The triple-pass design ensures clean, low-emission combustion, while the Eutectoplex heat exchanger surface guarantees economical energy consumption, high operational reliability and a long service life.
The benefits at a glance:
H Eutectoplex heat exchanger surface for high
operational reliability and a long service life. The homogeneous structure of the Eutectoplex special gray cast iron ensures uniform heat transfer, minimizing stress fractures and counteracting the formation of condensate. Shape and geometry of the cast iron sections, excellent water flow characteristics and uniform temperature distribution further increase the level of operational reliability.
H Problem-free transport into
difficult-to-access boiler rooms due to sectional construction and low weight of individual sections.
H Efficient and environmentally friendly
operation due to modulated boiler water temperatures. Combustion efficiency up to:
- oil 88.1%
. . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
- gas 85.5%. . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thermal efficiency up to:
- oil 88.0%. . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
- gas 85.4%. . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Low-emission combustion through
triple-pass design.
H Simple, quick assembly of the individual
cast iron sections is achieved with a double-groove seal fit system for the flue gas passageways. The gasket seal is secured in place by the double groove, and therefore not subject to mechanical stresses.
H Problem-free cleaning access facilitated by
a hinged (left or right) swing-open combustion chamber door, allowing easy access to all three heat exchanger passes from boiler front, reducing side clearance.
H Economical and safe operation of the
heating system with Vitotronic or Dekamatik digital boiler and heating system control. Tailored to every requirement, this control covers all known control strategies and applications.
H Economical and hygienic DHW production
with indirect-fired Vitocell 100 steel or Vitocell 300 stainless steel tanks. Tanks may be combined into multiple-tank batteries for applications requiring larger quantities of hot water.
528
542
8
v1.
6
Page 3
Product Information
Cut-Away Section
Product may not be exactly as illustrated.Product may not be exactly as illustrated.
VITOROND 200, VD2 3
Extremely effective Second Combustion Vitotronic 300 control ­4” / 100 mm thick pass chamber intelligent and easy to install, insulation operate and service
Third Eutectoplex heat Wide water Burner door pass exchanger surface passageways insulation
constructed from homogeneous special gray cast iron
5
2
8
5
4
2
8
v
1
.
6
Page 4
Technical Data
4 VITOROND 200, VD2
Technical data
*1
Boiler model VD2- 320 380 440 500 560 630 700 780 860 950 1080
Input (oil)
*1
MBH 1255 1490 1726 1961 2196 2471 2745 3059 3373 3727 4236
kW 368 436 506 574 643 724 804 896 988 1091 1241
Input (gas)
*1
MBH 1300 1544 1787 2031 2275 2559 2843 3168 3493 3860 4387 kW 381 452 523 595 666 750 833 928 1023 1130 1285
Output (oil/gas)
*2
MBH 1110 1319 1526 1732 1941 2183 2425 2699 2976 3288 3738
kW 325 387 447 508 569 640 711 791 872 963 1095
Combustion efficiency (oil) % 88.1 88.0 88.0 87.9 87.8 87.8 87.7 87.6 87.5 87.4 87.3 Combustion efficiency (gas) % 85.5 85.4 85.4 85.3 85.2 85.1 85.1 85.0 84.9 84.8 84.6
Thermal efficiency (oil) % 88.0 88.0 88.0 88.0 88.0 87.9 87.9 87.9 87.9 87.8 87.8 Thermal efficiency (gas) % 85.4 85.4 85.4 85.3 85.3 85.3 85.3 85.2 85.2 85.2 85.2 Number of cast iron sections 9 10 11 12 13 14 15 16 17 18 19
Cast iron block dimensions
Length
Width
Height
inches mm inches mm inches mm
57
1450
40½
1030
45¼
1150
62
1580
40½
1030
45¼
1150
67
1710
40½
1030
45¼
1150
72
1840
40½
1030
45¼
1150
77½
1970
40½
1030
45¼
1150
82½
2100
40½
1030
45¼
1150
88
2230
40½
1030
45¼
1150
93
2360
40½
1030
45¼
1150
98
2490
40½
1030
45¼
1150
103
2620
40½
1030
45¼
1150
108
2750
40½
1030
45¼
1150
Cast iron section dimensions
Front section (with combustion chamber door)
Intermediate section
Rear section (with flue gas collar)
inches mm inches mm inches mm
45¼ x 40½ x 10¾ 1150 x 1030 x 270
45¼ x 36¼ x 5
1150 x 920 x 125
45¼ x 36¼ x 9
1150 x 920 x 290
Dimensions (with insul. jacket)
Total length
Total width with NR2 control (side-mounted)
Total width with Dekamatik (side-mounted)
Total width with KR control (side-mounted)
Total height
inches mm
inches mm
inches mm
inches mm
inches mm
58¾
1490
49¼
1250
52¾
1340
54¾
1390
50¾
1290
63¾
1620
49¼
1250
52¾
1340
54¾
1390
50¾
1290
68¾
1750
49¼
1250
52¾
1340
54¾
1390
50¾
1290
73¾
1870
49¼
1250
52¾
1340
54¾
1390
50¾
1290
78¾
2000
49¼
1250
52¾
1340
54¾
1390
50¾
1290
83¾
2130
49¼
1250
52¾
1340
54¾
1390
50¾
1290
89
2260
49¼
1250
52¾
1340
54¾
1390
50¾
1290
93¾
2380
49¼
1250
52¾
1340
54¾
1390
50¾
1290
98¾
2510
49¼
1250
52¾
1340
54¾
1390
50¾
1290
104
2640
49¼
1250
52¾
1340
54¾
1390
50¾
1290
108¾
2760
49¼
1250
52¾
1340
54¾
1390
50¾
1290
Weight
Front section (with combustion chamber door)
Intermediate section
Rear section (with flue gas collar) Cast iron heat exchanger block
Overall weight
complete with insulation
lbs kg lbs kg lbs kg lbs kg
lbs kg
529 240 353 160 507
230 3748 1700
3924 1780
529 240 353 160 507
230 4100 1860
4299 1950
529 240 353 160 507
230 4453 2020
4652 2110
529 240 353 160 507
230 4762 2160
4982 2260
529 240 353 160 507
230 5115 2320
5335 2420
529 240 353 160 507
230 5423 2460
5666 2570
529 240 353 160 507
230 5776 2620
6019 2730
529 240 353 160 507
230 6085 2760
6349 2880
529 240 353 160 507
230 6437 2920
6702 3040
529 240 353 160 507
230 6790 3080
7070 3210
529 240 353 160 507
230 7143 3240
7429 3370
*1
Input ratings are based on ANSI Z21.13a*CSA 4.9a-2005 - Gas Fired Steam and Hot Water Boilers; CSA B140.7-05 - Oil Burning Equipment - Steam and Hot Water Boilers; CSA B140.0-03 - Oil Burning Equipment - General Requirements; UL 726 - 7th ed. - Oil-Fired Boiler Assemblies; and UL 795 - Commercial Industrial Gas Heating Equipment.
*2
Output ratings are based on the IBR BTS-2000
method to determine efficiency of commercial space heating boilers”.
528
542
8
v1.
6
Page 5
Technical Data
VITOROND 200, VD2 5
Technical data
Boiler model VD2- 320 380 440 500 560 630 700 780 860 950 1080
Boiler water content USG
ltr
65
24773275803038733195359
102 387
110 415
117 443
124 471
132 499
139 527
Max. boiler temperature
*2
(= fixed high limit)
°F °C
248 120
248 120
248 120
248 120
248 120
248 120
248 120
248 120
248 120
248 120
248 120
Max. allow. operating pressure
*3
psig 75 75 75 75 75 75 75 75 75 75 75
Boiler connections
Boiler supply and return Safety supply
*4
Safety return
*4
Drain valve
inches inches inches inches
4 2½ 2½
¾
4 2½ 2½
¾
4 2½ 2½
¾
4 2½ 2½
¾
4 2½ 2½
¾
4 2½ 2½
¾
4 2½ 2½
¾
4 2½ 2½
¾
4 2½ 2½
¾
4 2½ 2½
¾
4 2½ 2½
¾
Heating surface area
Flue gas side ft.
2
m
2
170
15.8
196
18.2
212
19.7
232
21.5
254
23.6
274
25.5
296
27.5
317
29.5
339
31.5
358
33.3
380
35.3
Water side ft.
2
m
2
98
9.1
109
10.1
120½
11.2
131
12.2
142
13.2
153
14.2
165
15.3
175
16.3
187
17.4
198
18.4
209
19.4
Flue gas
*5
– Temperature (gross)
*6
– Flue gas mass flow rate
With minimum heating input and a 2-stage burner (operation of stage 1) – Temperature
– Flue gas mass flow rate at
minimum input rate
°F °C lbs/h kg/h
°F °C lbs/h kg/h
374 190
1301
590
266 130 710 322
374 190
1598
725
266 130 842 382
374 190
1854
841
266 130 974 442
374 190
2081
944
266 130
1109
503
374
190 2337 1060
266
130 1241
563
374
190 2601 1180
266
130 1398
634
374
190 2897 1314
266
130 1552
704
374
190 3196 1450
266
130 1730
785
374
190 3527 1600
266
130 1907
865
383
195 3825 1735
275
135 2110
957
383
195 4277 1940
275
135 2394 1086
Boiler standby loss based on max. heating input and hot water supply and return temperatures of 167 / 140°F
75 / 60 °C
% 0.40 0.38 0.35 0.32 0.31 0.29 0.28 0.27 0.26 0.25 0.24
Vent pipe collar outer
*7
in mm
12
30012300123001230012300123001230012300123001230012300
Flue gas resistance “w.c. 0.20 0.35 0.51 0.67 0.75 0.83 1.10 1.54 1.93 1.77 2.28
- at upper end of rated input mbar 0.5 0.9 1.3 1.7 1.9 2.1 2.8 3.9 4.9 4.5 5.8
Required flue draft
Category I
Pa “w.c.
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
Positive pressure
Category III
Pa “w.c.200.08200.08200.08200.08200.08200.08200.08200.08200.08200.08200.08
*1
Inch dimensions are rounded to the nearest ¼”.
*2
The maximum supply operating temperature (= max. adjustable high limit) lies approx. 27°F / 15°C below the fixed high limit setting.
*3
May be less in some Canadian provinces.
*4
Connections for boiler connection kit (standard equipment).
*5
Combustion results are based on 13.0% CO2with fuel oil #2 and 10% CO2with natural gas, as well as a system supply temperature of 167 °F / 75 °C, and a system return temperature of 140 °F / 60 °C.
*6
Measured flue gas temperature with a combustion air temperature of 68 °F / 20 °C and a boiler water temperature of 176 °F / 80 °C.
*7
Vent pipe collar diameter does not automatically indicate vent/chimney size. See page 13 for details.
"
The combustion burner head material must be suitable for temperatures of at least 932 °F / 500 °C.
"
Vitorond 200, VD2-950 and VD2-1080 boiler sizes have unique characteristics, including differences in insulation jacket and dimensions.
"
For information regarding other Viessmann System Technology componentry, please reference documentation of respective product.
5
2
8
5
4
2
8
v
1
.
6
Page 6
Technical Data
6 VITOROND 200, VD2
Legend
BD Boiler drain ¾” BWR Boiler water return BWS Boiler water supply CO Clean-out opening FGC Flue gas collar SG Sight glass
a 10½” / 270 mm b 5” / 125 mm c 11½” / 290 mm d 5½” / 140 mm e 4” / 100 mm
Burner Installation
The burner must be fitted to the burner plate; installations direct to the boiler door are not feasible. Viessmann supplies a pre-drilled end burner plate in accordance with the supplied burner dimensions.
Note
For mounting burners with blast tube diameters of 180 mm / 7” to 280 mm / 11”, the door insulation (refractory material) can be cut to the required size. The blast tube must protrude from the thermal insulation on the boiler door.
528
542
8
v1.
6
CO
FGC
BWS
SG
Total length
Length
Total width
Width
Total height
BD BWR CO
50¾”/1290 mm
41”/1040 mm
33¼”/845 mm
22¾”/580 mm
22¾”/580 mm
a
e
d
a
b
c
Viessmann North America offers the side-mounted control option only. Refer to the side-mounted control dimension on page 4.
Attention
580 mm/22 7/8”
845 mm/33 1/4”
450 mm/17 3/4”
130 mm/5”
180 mm/7”
Page 7
Technical Data
Legend
TCP Additional temperature control port, ½” AQW Aquastat well tapping, ½” BWR Boiler water return BWS Boiler water supply ACP Additional control port, ½” (pressure gage) S
1
Return temperature sensor port
S
2
Boiler pump temperature sensor, ½”
R
WE Return water elevation, 2½”
SR Safety return - connection to precharged
membrane expansion tank
SS Safety supply - connection to pressure relief valve
Air Vent
BWS
AQW
ACP
TCP
BWS
SS/RWE
LWCO SS/RWE
BWR
SR/RWE
SR/RWE
BWR
S
1
S
2
31½” / 800 mm
1
5¾” / 400 mm
25¼” / 640 mm
9½” / 240 mm
15¾” / 400 mm
2
6
/
6
6
0
m
m
8¼” / 210 mm
3
1
½
/
8
0
0
m
m
15¾” / 400 mm
VITOROND 200, VD2 7
Boiler Connection Kit (Standard Equipment)
consisting of boiler supply and return header
Boiler supply header
Boiler return header (top view)
Low Temperature Protection
Boiler model
VD2- 320 380 440 500 560 630 700 780 860 950 1080
30% Boiler Flow Package Ø” not applicable
100% Boiler Flow Package Ø” 3 4 4 5 5 6
Low temperature protection packages from Viessmann are required for Vitorond 200 boilers. A 30% Boiler Flow Package is typically utilized in single-boiler installations. 100% Boiler Flow Packages are utilized in single- and multiple-boiler installations.
Selection of the correct package depends on the characteristics of the heating system and the degree of control necessary to protect the boiler. Contact Viessmann for assistance.
5
2
8
5
4
2
8
v
1
.
6
Page 8
Technical Data
Boiler supply header
Boiler return header
Boiler supply connection
Boiler return connection
Boiler supply header
Boiler return header
Boiler supply connection
Boiler return connection
8 VITOROND 200, VD2
30% Boiler Flow Package
The 30% boiler flow package consists of:
H 1 boiler pump H 2 ball valves H 1 flow check valve
Low water cut-off (standard equipment) Boiler shunt pump for return water temperature elevation Flow check valve Location of Honeywell aquastat (to control boiler pump) Location of sensor (installed in stainless steel well)
All boiler piping field supplied.
100% Boiler Flow Package
The 100% boiler flow package consists of:
H 1 3-way mixing valve H 1 actuator H 1 boiler pump
Boiler pump 3-way mixing valve Low water cut-off (standard equipment) Location of sensor (installed in stainless steel well)
All boiler piping field supplied.
It is essential that the heating system designer review the sizing of all pumps including the boiler pump normally supplied with the 100% Boiler Flow Package to verify that all pumps in the system will operate correctly. The responsibility for the distribution system design, including all circulation pumps, remains with the system designer.
528
542
8
v1.
6
IMPORTANT
Page 9
Technical Data
35½” / 900 mm
43¼” / 1100 mm
4” / 100 mm
2” / 50 mm
>=4” / 100 mm
4” /
100 mm
5½” /
140 mm
a
b
39½” /
19¾” / 500 mm
19¾” / 500 mm
8” / 200 mm
d
c
1000 mm
VITOROND 200, VD2 9
Boiler Base
The boiler must be installed on a levelled base or foundation, which must be designed to carry the entire weight of the boiler, water fill, burner and attached piping. To ease the installation of the individual sections, angle-iron or flat steel may be incorporated into the concrete foundation. Surface width of steel strips should be 4” / 100 mm.
Boiler model
VD2-
320
VD2-
380
VD2-
440
VD2-
500
VD2-
560
VD2-
630
VD2-
700
VD2-
780
VD2-
860
VD2-
950
VD2-
1080
a inchesmm45
1140
49¾
1265
54¾
1390
59¾
1515
64½
1640
69½
1765
74½
1890
79¼
2015
84¼
2140872205942390
b inchesmm52¼
1330
57¼
1455
62¼
1580671705721830771955822080
86¾
2205
91¾
2330
96½
2460
101½
2580
Inch dimensions rounded to the nearest ¼”.
Recommended Minimum Clearances
The combustion chamber door is factory assembled to hinge on the left-hand side. A right-hand hinge is feasible by rebuilding the door hinge hardware.
Boiler model
VD2-
320
VD2-
380
VD2-
440
VD2-
500
VD2-
560
VD2-
630
VD2-
700
VD2-
780
VD2-
860
VD2-
950
VD2-
1080
c inchesmm65¼
1660
70½
1790
75½
1920
80¾
2050
85¾
2180912310962440
101¼
2570
106¼
2700
111½
2830
116½
2960
d inchesmmDependent on burner model size
Inch dimensions rounded to the nearest ¼”.
Front clearances (dimension “c” above) will allow for easy removal of flue gas turbulator inserts, as well as for full insertion of bristle brush for heat exchanger cleaning.
Minimum side clearance of 19¾” / 500 mm must be maintained for side-mounted KR or Dekamatik controls.
528
542
8
v1.
6
IMPORTANT
Page 10
10 VITOROND 200, VD2
Waterside Flow
The Vitorond 200 is designed for closed loop, forced circulation, hot water heating systems only.
The recommended water flow rate through the Vitorond 200 is based on a temperature difference of between 20°F and 40°F / 11°C and 22°C. When a balancing valve is used for proper balancing and water flow through the boiler, the valve should be installed 5 pipe diameters from any fittings and 10 pipe diameters from circulation pumps to allow for laminar flow.
The consulting engineer or contractor should review the system design if more balancing valves are required to properly balance the system.
Viessmann can supply TA (Victaulic) balancing valves upon request. The balancing should be carried out by a certified balancing firm prior to boiler start-up. Please contact Viessmann for your closest certified balancing firm.
VD2-320, VD2-380 and VD2-440 VD2-500, VD2-560 and VD2-630 VD2-700, VD2-780 and VD2-860 VD2-950 and VD2-1080
Recommended Flow Rates
Boiler model VD2- 320 380 440 500 560 630 700 780 860 950 1080
20°F t 40°F t
11°C t 2
2°C t
GPM GPM
ltrs/s ltrs/s
109
55
6.9
3.4
130
65
8.2
4.1
150
75
9.5
4.7
171
85
10.8
5.4
191
96
12.1
6.0
215 108
13.6
6.8
239 119
15.1
7.5
266 133
16.8
8.4
293 147
18.5
9.3
324 162
20
10.2
369 184
23.2
11.6
"
t = temperature difference
Note: This boiler does not require a flow switch.
528
542
8
v1.
6
500 400
300
200
100
50 40
30 25
20
15
10
10 15 20 30 10050 806040
Pressure Drop
Flow Rate
200 160
120
80
40
20 16
12 10
8
6
4
44
66 88 132 176 220 264 352 440
”w.c.
mbar
GPM
m3/h
Page 11
Operational Details
VITOROND 200, VD2 11
Operational Details
Requirements are fulfilled via...
Heating water volume flow 30% at heating output a bypass pump / shunt pump or
boiler circulation pump
Boiler return water temperature (minimum)
For operation with modulating boiler water temperatures:
- Oil-fired 104°F / 40°C
- Gas-fired 127°F / 53°C
For operation with elevated boiler water temperatures:
- Oil-fired 127°F / 53°C
- Gas-fired 127°F / 53°C
an effective system of return tempera­ture elevation
Minimum boiler water temperature
For operation with modulating boiler water temperatures:
- Oil-fired 122°F / 50°C
- Gas-fired 140°F / 60°C
For operation with elevated boiler water temperatures:
- Oil-fired 140°F / 60°C
- Gas-fired 149°F / 65°C
The Viessmann Dekamatik or Vitotronic control system
2-Stage burner operation For operation with modulating boiler water temperatures:
first stage 60% of heating output
For operation with elevated boiler water temperatures: No minimum heating input applies
Burner calibration (site)
Modulating burner operation For elevated boiler water temperatures only:
- Oil-fired 140°F / 60°C
- Gas-fired 149°F / 65°C
- min. return water temperature 127°F / 53°C
The Viessmann Dekamatik or Vitotronic control system
Setback operation Minimum boiler water temperature:
- Oil-fired 122°F / 50°C
- Gas-fired 140°F / 60°C
For multiple-boiler installations:
- Lead boiler as above
- Lag boiler(s) is/are deactivated
The Viessmann control included in the standard equipment
Weekend setback See Setback operation See Setback operation
5
2
8
5
4
2
8
v
1
.
6
Page 12
Standard Equipment Boiler Control Alternatives
12 VITOROND 200, VD2
Standard Equipment
Note: Boiler controls and burners are purchased separately. Please see Price List for details.
H The cast iron sections are delivered as
individual units on skids.
H The combustion chamber door (with
burner plate) is mounted on the front section.
H The flue gas collector, with two
inspection opening covers (fastened with screws), is mounted on the rear section.
1 skid containing supply and return
headers 3 cartons containing insulation panels 1 carton containing the boiler control 1 carton with miscellaneous boiler assembly
components
Standard equipment includes: – Supply/Return header (c/w left/right
connections) – Low water cut-off – Thermometer, pressure gage, air vent,
pressure relief valve, and boiler drain valve
Ensure specific regional, provincial, or
state requirements, such as fuel train and additional safety control requirements etc., are known before the product order is placed, to determine proper burner selection and pricing.
Boiler Control Alternatives
For single boiler systems:
H without Vitocontrol control panel
Vitotronic 100 (type GC1) for constant boiler water temperature or outdoor reset mode in conjunction with an external control unit (BMS).
Vitotronic 300 (type GW2) for modulating boiler water temperature with mixing valve control for a maximum of two heating circuits with mixing valve.
H with Vitocontrol control panel
Vitotronic 100 (type GC1) and
Vitocontrol-S, VD2 control panel
with Vitotronic 333 for outdoor reset mode and mixing valve control for a maximum of 2 heating circuits with mixing valve and additional Vitotronic 050, type HK1S or HK3S for 1 or up to 3 heating circuits with mixing valve.
For multi-boiler system (up to 4 boilers):
Hwithout Vitocontrol control panel
Vitotronic 100 (typeGC1) and LON module for modulating boiler water temperature in conjunction with an extrnal control unit (BMS).
H with Vitocontrol control panel
Vitotronic 100 (typeGC1) and LON module for modulating boiler water temperature for each boiler of the multi-boiler system and
Vitocontrol-S, VD2 control panel
with Vitotronic 333 for multi-boiler system, outdoor reset mode and mixing valve control for a maximum of 2 heating circuits with mixing valve and additional Vitotronic 050, type HK1S or HK3S for 1 or up to 3 heating circuits with mixing valve.
For single- or multiple-boiler installations:
Custom control panels
Custom control panels for residential or commercial applications are designed and manufactured by Viessmann to suit any customer’s specific requirements. Custom control panels can have features such as pool heating, hot tub heating, snow melting, telephone tie-in, integration with Building Management Systems, as well as several other functions. Please inquire.
The control of the Vitorond 200, VD2 boiler can be mounted either on the left- or right-hand side of the boiler. Please specify control location at the time of order.
528
542
8
v1.
6
IMPORTANT
Page 13
System Design Considerations
VITOROND 200, VD2 13
System Design Considerations
Burner calibration
With 2-stage and fully modulating burners, ensure that the chimney is compatible with the lower flue gas temperatures associated with partial load conditions set on the burner.
2-Stage burner
When used with the Dekamatik or Vitotronic control, the following minimum heating outputs are applicable to protect the boiler:
- 60% of outputs stated in the Technical Data table on page 4.
Fully modulating burner
The minimum boiler water temperature is: – 140°F / 60°C with oil, – 149°F / 65°C with natural gas. Set the return temperature elevation system to maintain a minimum value of 127°F / 53°C.
Venting
The Vitorond 200, VD2 boiler is approved a
s a Category I and III appliance and must
be vented accordingly.
Chimney
For proper operation of the Vitorond 200, V
D2 boiler, all products of combustion must be safely vented to the outdoors, while ensuring that flue gases do not cool prematurely. It is critical that the chimney system be properly designed to handle the relatively cool flue gas temperatures produced by the Vitorond 200, VD2 boiler. If the chimney system lacks sufficient insulation and/or the chimney diameter is too large, corrosive and damaging condensation will result due to flue gases cooling too quickly. If a calculated chimney diameter lies between two values, the larger diameter should be selected. The chimney connection length between the boiler vent pipe collar and the chimney must be installed with insulation. Vent pipe collar diameter does not automatically indicate vent/chimney size. We recommend consulting a reputable chimney installer for advice in project-specific circumstances.
Chimney (continued)
W
hen installing the Vitorond 200, VD2 boiler, it is necessary to install a barometric draft regulator in the chimney/vent for proper operation of the boiler.
Install the barometric draft regulator within 5 to 7 ft. / 1½ to 2 m from the breeching outlet located at the rear of the boiler.
Barometric draft regulator type
For natural gas or propane applications, use a double-acting type.
For #2 fuel oil applications, use a single-acting type.
Barometric draft regulator diameter
The barometric draft regulator must be the same diameter opening as the chimney for
which the vent is sized. For example, a 14” chimney would require a 14” barometric draft regulator. Do not size the barometric draft regulator to the breeching outlet of the boiler, unless the chimney is also intended to be of that diameter.
The size of the flue gas outlet on the boiler does not automatically determine the horizontal breeching, or the actual chimney diameter. The chimney size must be designed for the actual boiler model and its input.
Venting option #2 (Category III)
The Vitorond 200 boiler is a C
ategory III
positive pressure non-condensing boiler. Each boiler must be vented individually. The vent system must be properly designed and suitable materials must be selected. The chimney must be gas tight.
Combustion air supply
The boiler must not be located in areas or r
ooms where chemicals containing chlorine, bromine, fluorine, or other corrosive chemicals are stored. Examples include refrigerants, bleach, paint, paint thinner, hair spray, cleaning solvents, water softener salt, etc. The combustion air must not be contaminated with any amount of the above mentioned chemicals.
Boiler should never be installed in areas where excessive dust, high humidity, or risk of frost exist. Ensure adequate ventilation and supply of fresh combustion air.
Consult Viessmann with uncertainties in regard to a suitable boiler installation location.
This boiler/burner unit needs clean fresh air for safe operation. Provisions for combustion and ventilation air must be made at time of installation. For oil-fired boilers, use the “Installation Code for Oil Burning Equipment CAN/CSA-B139” (Canada), or NFPA 31 (USA). For gas or propane installations, use the “Natural Gas Installation Code CAN/CSA-B149.1 or B149.2” (Canada), or “National Fuel Gas Code ANSI Z223.1” (USA), and/or provisions of local codes.
The sizing methods outlined in the above codes should be used when installing a round duct to supply combustion air from the outside.
Warranty
Our warranty does not cover damages r
esulting from the following: – Corrosion caused by flue gas condensation
due to low boiler water and/or return water temperatures.
– Operation with contaminated fill and
supplementary feed water.
System layout
The boiler water temperature limit is factory set to 167°F / 75°C. The boiler water temperature limit can be increased by altering the adjustable high limit to increase the supply water temperature. To minimize piping losses of the system, however, Viessmann recommends that the radiation and domestic hot water production in the system be designed for a 158°F / 70°C boiler supply water temperature.
5
2
8
5
4
2
8
v
1
.
6
The Vitorond 200, VD2 boiler is not approved for side wall venting.
CAUTION
IMPORTANT
Barometric draft regulator
Page 14
System Design Considerations/Burner Alternatives
14 VITOROND 200, VD2
System Design Considerations (continued)/Burner Alternatives
Water quality
Treatment for boiler feed water should be considered in areas of known problems, such as where a high mineral content and hardness exist. In areas where freezing might occur, an antifreeze may be added to the system water to protect the system. Please adhere to the specifications given by the antifreeze manufacturer. Do not use automotive silicate-based antifreeze. Please observe that an antifreeze/water mixture may require a backflow preventer within the automatic water feed and influence components such as diaphragm expansion tanks, radiation, etc. A 40% antifreeze content will provide freeze-up protection to
-10°F / -23°C. Do not exceed 50% antifreeze mix ratio and do not use antifreeze other than specifically made for hot water heating systems. System also may contain components which might be negatively affected by antifreeze. Check total system frequently when filled with antifreeze. Follow the instructions of antifreeze manufacturer.
Oxygen diffusion barrier underfloor tubing
The boiler warranty does not cover leaks resulting from corrosion caused by the use of underfloor plastic tubing without an oxygen diffusion barrier. Such systems must have the non-oxygen diffusion barrier tubing separated from the boiler with a heat exchanger. Viessmann recommends the use of underfloor plastic tubing with an oxygen diffusion barrier.
Burner manufacturer
Weishaupt or Riello.
Burner/Gas train approval
Standard approvals are CSA (for Canada) and UL (for U.S.). IRI and FM approved equipment is also available - please inquire.
Electrical requirements
Weishaupt WG, WL, L, RL, G, GL and WM-G(L) RGL Series burners listed on page 15 are available in 120 VAC single-phase, 208 VAC three-phase, 460 VAC three-phase, or 575 VAC three-phase, all in 60 Hz configuration. Size 7 burners are not available in 120 VAC single-phase configuration. It is generally acceptable to use voltages within ten percent of the supply voltage. Available voltage inside boiler room must be provided at time of order. Ensure appropriate disconnect means and overcurrent protection.
Natural gas pressure
Natural gas pressures and heating values as provided by the gas utilities vary greatly across North America. Select the appropriate gas train accordingly. Low pressure gas trains have a maximum input of 14 ”w.c.; high pressure gas trains have a maximum pressure of 5 psig. Minimum gas pressures apply - please inquire. Gas pressures and heating values at site must be provided at time of order.
Factory prewired components
Custom factory prewiring by Viessmann ensures optimal functionality, compliance with regional requirements, and ease of installation in the field. Pricing provided by Viessmann includes all necessary hardware items such as junction panel, burner power supply, boiler door safety switch (where necessary), and all essential pressure switches, as well as interconnection with conduit between control and burner.
Electrical drawings provided upon product delivery.
Boiler/Burner start-up
Vitorond 200, VD2 boilers with Weishaupt burners require start-up by Viessmann. Please inquire to obtain details regarding the necessary prerequisites of boiler/burner start-up procedures.
To minimize delivery lead times, please ensure that critical technical information is provided at time of order. Viessmann will not process an order without site-specific information regarding available voltage and gas pressure. In addition Viessmann recommends that gas pressure information be provided in writing by the local gas utility.
528
542
8
v1.
6
IMPORTANT
Page 15
System Design Considerations/Burner Alternatives
VITOROND 200, VD2 15
Weishaupt Burners
Boiler model VD2- 320 380 440 500 560 630 700 780 860 950 1080
No. 2 oil-fired
2-stage
Model L1Z L3Z L5Z L7Z
No. 2 oil-fired
fully modulating
Model RL3 RL5 RL7
Natural gas-fired
2-stage
Model G3 G5 G7
Natural gas-fired
fully modulating
Model G3 G5 G7
Propane gas-fired
2-stage
Model G3 G5 G7
Propane gas-fired
fully modulating
Model G3 G5 G7
Combination
fully modulating NG, 2-stage oil
Model GL3 GL5 GL7
Combination
fully modulating NG, fully modulating oil
Model RGL3 RGL5 RGL7
Weishaupt Burners, Linkageless
1
Boiler model VD2- 320 380 440 500 560 630 700 780 860 950 1080
No. 2 oil-fired
2-stage
Model WL40 WM-L10/3 WM-L10/4 L7
No. 2 oil-fired
fully modulating
Model WM-L10/2 WM-L10/3 RL5 RL7
Natural gas-fired
2-stage
Model WG40-LN WM-G10/2 G10/3-LN WM-G10/4 G7-LN
Natural gas-fired
fully modulating
Model WG40-LN WM-G10/2 G10/3-LN WM-G10/4 G7-LN
Propane gas-fired
2
2-stage
Model WG40-LN WM-G10/2 WM-G10/3 WM-G10/4 G7
Propane gas-fired
2
fully modulating
Model WG40-LN WM-G10/2 WM-G10/3 WM-G10/4 G7
Combination
fully modulating NG, 2 stage oil
Model WM-GL10/1- WM-GL10/2 WM-GL10/3 WM-GL20/2
Combination
fully modulating NG, fully modulating oil
Model WM-GL10/2 WM-GL10/3 WM-GL20/2
Combination
fully modulating NG, fully modulating L.P.
Model WM-GL10/1 WM-GL10/2 WM-GL10/3 WM-G10/4 WM-GL20/2
1
LN behind burner model no. indicates low NOxburner head is standard equipment.
2
Please contact Viessmann to quote a propane burner gas train, where less than 14” w.c. gas pressure exists.
Riello Burners
Boiler model VD2- 320 380 440 500 560 630 700 780 860 950 1080
No. 2 oil-fired
2-stage
Model RL28/2 RL38/2 RL50/2 RL70/2 RL100/2
No. 2 oil-fired
fully modulating
Model RL28/M RL38/M RL50/M RL70/M RL100/M
Natural gas-fired
fully modulating
Model RS38/M RS50/M RS70/M RS100/M
Propane gas-fired
fully modulating
Model RS38/M RS50/M RS70/M RS100/M
Combination
2-stage NG/2-stage oil
Model RLS38 RLS50 --- --- ---
full mod. NG/2-stage oil --- --- RLS70 RLS100 RLS130
Natural gas-fired
fully modulating, low NO
x
Model RS45/M LN RS68/M LN RS120/M LN
5
2
8
5
4
2
8
v
1
.
6
Page 16
Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario N2V 2G5 Canada Tel. (519) 885-6300 Fax (519) 885-0887 www.viessmann.ca info@viessmann.ca
Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island 02886 USA Tel. (401) 732-0667 Fax (401) 732-0590 www.viessmann-us.com info@viessmann-us.com
16 VITOROND 200, VD2
Printed on environmentally friendly
(recycled and recyclable) paper.
Printed on environmentally friendly
(recycled and recyclable) paper.
528
542
8
v1.
6
Technical information subject to change without notice.
Loading...