Viessmann VITOROND 200, VD2-125, VD2-160, VD2-195, VD2-230 Technical Data Manual

...
Page 1
Technical Data Manual
Model Nos. and pricing: see Price List
VITOROND 200
Triple-pass hot water heating boiler
490 to 1096 MBH / 144 to 321 kW
Product may not be exactly as illustrated.
Vitorond 200
Oil-/Gas-fired boiler
5285 661 v1.4 01/2008
144 to 321 kW
Page 2
Product Information
VITOROND 200
The modular sectional cast iron design of the Vitorond 200, VD2 allows for problem-free transport into difficult-to-access boiler rooms and permits easy assembly. The triple-pass design ensures clean, low-emission combustion, while the Eutectoplex heat exchanger surface guarantees economical energy consumption, high operational r eliability and a long service life.
The benefits at a glance:
H Efficient and environmentally friendly
operation due to modulated boiler water temperatures. Combustion efficiency:
- oil 88%.
.......................................................
- gas 85%......................................................
H Eutectoplex heat exchanger surface for high
operational reliability and a long service life. The homogeneous structure of the Eutectoplex special gray cast iron ensures uniform heat transfer, minimizing stress fractures and counteracting the formation of condensate. Shape and geometry of the cast iron sections, excellent water flow characteristics and uniform temperature distribution further increase the level of operational reliability.
H Low-emission combustion through
triple-pass design.
H Problem-free transport into
difficult-to-access boiler rooms due to sectional construction and low we ight of individual sections.
H Simple, quick assembly of the individual
cast iron sections is achieved with a double-groove seal fit system for the flue gas passageways. The gasket seal is secured in place by the double groove, and therefore not subject to mechanical stresses.
H Easy cleaning access facilitated by a
hinged (le ft or right) swing-open combustion chamber door, allowing easy access to all three heat exchanger passes from boile r front, reducing side cleara nce.
H Efficient and safe ope ration of the heating
system with Vitotronic or Dekamatik digital boiler and heating system control. Tailored to s uit every requirement, these controls cover all know n control strategies and applications.
H Economical and hygienic domestic hot
water production with indirect-fired Vitocell 100 steel or Vitocell 300 stainless steel tanks. Tanks may be combined into multiple-tank batteries for a pplications requiring larger quantities of hot water.
2 VITOROND 200, VD2
5285 661 v1.4
Page 3
Product Information
Cut-Away Section
Extremely effective Third Vitotronic 300 control - Burner door 4” / 100 mm thick pass intelligent and easy to install, insulation insulation operate and service.
Product may not be exactly as illustrated.
5285 661 v1.4
VITOROND 200, VD2 3
Second Combustion Eutectoplex heat exchanger Low-emission pass chamber surface constructed from burner
homogeneous special gray cast iron
Page 4
Technical Data
Technical data
Boiler model Input (oil) MBH 490 628 765 902 1059
Input (gas) MBH 508 650 792 934 1096
Output (oil/gas) MBH 432 553 673 794 932
Combustion efficiency (oil) % 88 88 88 88 88 Combustion efficiency (gas) % 85 85 85 85 85
Number of cast iron sections 5 6 7 8 9
Cast ir on block dimensions
Length
Width
Height
Cast ir on section dimensions
Front section (with combustion chamber door)
Intermediate section
Rear section (with flue gas collar)
Dimensions (with insul. jacket)
Total length
Total width with NR2 control (side-mounted)
Total width with Dekamatik (side-mounted)
Total width with KR control (side-mounted)
Weight
Front section (with combustion chamber door)
Intermediate section
Rear section (with flue gas collar) Cast iron heat exchanger block
Overall weight
complete with insulation
Boiler water content USG
Max. boiler temperature
(= fixed high limit)
*1
*2
VD2- 125 160 195 230 270
kW 144 184 224 264 310
kW 149 190 232 274 321
kW 127 162 197 233 273
inches mm inches mm inches mm
inches mm inches mm inches mm
inches mm
inches mm
inches mm
inches mm
lbs kg lbs kg lbs kg lbs kg
lbs kg
ltr °F
°C
35¼
893
29¼
743
40
1015
41½
1056
39
990
42¾
1090
44¾
1140
309 140 203
92 256 116
1347
611
1424
646
20.6 78
248 120
40¼
1024
29¼
743
40
1015
32 x 29¼ x 10¼ 810 x 743 x 261
810 x 628 x 130
810 x 628 x 238
46¾
1187
39
990
42¾
1090
44¾
1140
309 140 203
92 256 116
1556
706
1624
745
24.0 91
248 120
45½
1155
29¼
743
1015
32 x 24¾ x 5
32 x 24¾ x 9¼
1318
990
42¾
1090
44¾
1140
309 140 203
256 116
1750
794
1845
837
27.5 104
248 120
40
52
39
92
49½
1256
29¼
743
40
1015
57
1449
39
990
42¾
1090
44¾
1140
309 140 203
92 256 116
1940
880
2044
927
30.9 117
248 120
55¾
1417
29¼
743
40
1015
62¼
1580
39
990
42¾
1090
44¾
1140
309 140 203
92 256 116
2052
931
2196
996
34.3 130
248 120
4 VITOROND 200, VD2
5285 661 v1.4
Page 5
Technical Data
Technical data
Boiler model VD2- 125 160 195 230 270
Max. allow. operating pressure
Boiler connections
Boiler supply and return Safety supply Safety return Drain valve
Heating surface area
Flue gas side
Water side ft.
Flue gas
– Temperature (gross)
– Flue gas mass flow rate
With minimum heating input and a 2-stage burne r (operation of stage 1) – Temperature
– Flue gas mass flow rate at
Boiler standby loss based on max. hea ting input and hot water supply and return temperatures of 167 / 140°F
Vent pipe collar outer
Flue gas re sistance “w.c. 0.20 0.35 0.51 0.67 0.75
- at upper end of rated input mbar 0.5 0.9 1.3 1.7 1.9
*3
*4
*4
*5
minimum input rate
75 / 60 °C
*6
psig 75 75 75 75 75
inches inches inches inches
2
ft.
2
m
2
2
m
°F °C lbs/h kg/h
°F °C lbs/h kg/h
2½ 1½ 1½
40
3.7
32
3.0
374 190 470 213
266 130 282 128
2½ 1½ 1½
¾
¾
49.5
4.6
37.5
3.5
374 190 602 273
266 130 362 164
2½ 1½ 1½
60
5.6
43
4.0
374 190 732 332
266 130 439 199
2½ 1½ 1½
¾
¾
70
6.5
49.5
4.6
374 190 864 390
266 130 516 234
%0.300.27 0.24 0.20 0.18
*7
in mm
200
8
200
8
200
8
8
200
2½ 1½ 1½
79.5
7.4
55
5.1
374 190
1014
457
266 130 604 274
200
¾
8
*1
Inch dime nsions are rounded to the neares t ¼”.
*2
The maximum supply operating temperature (= max. adjustable high limit) lies approx. 27°F / 15°C below the fixed high limit setting.
*3
May be less in some Canadian provinces.
*4
Connections for boiler connection kit (standard equipment).
*5
Combustion r esults are based on 13.0% CO2with fuel oil #2 and 10% CO2with natural gas, as well as a system supply temper ature of 167 °F / 75 °C, and a system return temperature of 140 °F / 60 °C.
*6
Measured flue gas temperature with a c ombustion air tempe rature of 68 °F / 20 °C and a boiler water temperature of 176 °F / 80 °C.
*7
Vent pipe collar diameter does not automatically indicate vent/chimney s ize. See page 13 for details.
"
The combustion burner head material must be suitable for temperatur es of at least 932 °F / 50 0 °C.
"
For informa tion regarding other Viessmann System Technology componentry, please reference documentation of respective product.
5285 661 v1.4
VITOROND 200, VD2 5
Page 6
Technical Data
Height
Total height
SG
Width
Total width
Legend
BD Boiler drain ¾” BWR Boiler water return BWS Boiler wa ter s upply CO Clean-out opening FGC Flue gas collar SG Sight glass
a 10½” / 270 mm b 5” / 125 mm c 11½” / 290 mm d 5½” / 140 mm e 4” / 100 mm
Attention
Viessmann North America offers the side-mounted control option only. Refer to the side-mounted control dimension on page 4.
28¾” / 730 mm
BWS
FGC
Burner Installation
The burner must be fitted to the bur ner plate; installations direct to the boiler door are not feasible. Viessmann supplies a pre-drilled end burner plate in accordance with the
20½”
520 mm
a
Total length
Length
8”
205 mm
b
23½”
600 mm
33½” / 850 mm
c
42¼” / 1075 mm
supplied burner dimensions.
Note
For mounting burners with blast tube diameters of 150 mm / 6” to 240 mm / 9½”, the door insulation (refractory material) can be cut to the required size. The blast tube must protrude from the thermal insulation on the boiler door.
730 mm / 28 3/4”
520 mm / 20 1/2”
320 mm / 12 5/8”
150 mm / 6”
110 mm / 4 3/8”
CO
BWR
CO
BD
6 VITOROND 200, VD2
5285 661 v1.4
Page 7
Boiler Connection Kit (Standard Equipment)
consisting of boiler supply and return header
Boiler supply header
BWS
Technical Data
SS/RWE
”/
16
21” / 535 mm
/
3
132 mm
5
AQW
Boiler return header
SEN 2
29½” / 750 mm
14¾” / 375 mm
BWR
190 mm
ACP
29½” / 750 mm
SR/RWE
SEN 1
SR/RWE
7½”
20¼” / 515 mm
Air vent
BWR
SS/RWE
TCP
BWS
12¾” / 325 mm
Legend
TCP Additional temperature control port ½” AQW Aquastat well tapping ½” BWR Boiler water return BWS Boiler water supply ACP Additional control port ½” (pressure gage) SEN 1 Return temperature sensor port SEN 2 Boiler pump temperature sensor ½” RWE Return water elevation 1½” SR Safety return - connection to precharged
membrane expansion tank
SS Safety supply - connec tion to pressure relief valve
Low Temperature Protection
Boiler model VD2- 125 160 195 230 270 30% Boiler Flow Package Ø” 100% Boiler Flow Package Ø” 2 3 3
Low temperature protection packages from Viessmann are required for Rondomat boilers. A 30% Boiler Flow Package is typically utilized in single-boiler installations. 100% Boiler Flow Packages are utilized in single- and multiple-boiler installations. Selection of the correct package depends on the characteristics of the heating system, and the degree of control necessary to protect the boiler. Contact Viessmann for assistance.
5285 661 v1.4
VITOROND 200, VD2 7
30% Boiler Flow Package: H 1 Boiler pump, 2 ball valves,
1 flow check valve
100% Boiler Flow Package: H 1 3-Way return water mixing valve,
1 actuator, 1 circula ting pump
Page 8
Technical Data
30% Boiler Flow Package
Boiler return header
Boiler supply header
Boiler supply connection
Boiler return connection
The 30% boiler flow package consists of:
H 1 Boiler pump, 2 ball valves,
1 flow check valve
Low water cut-off (standard equipment) Boiler shunt pum p for return water temperature elevation or bypass pump Flow check valve Location of Honeywell aquastat (to control boiler pump) Location of sensor (installed in s tainless steel well)
All boiler piping field supplied.
100% Boiler Flow Package
Boiler supply header
Boiler supply connection
Boiler return connection
The 100% boiler flow package consists of:
H 1 3-Way return water mixing valve,
1 actuator, 1 circ ulating pump
Boiler pump 3-Way return water mixing valve Low water cut-off (standard equipment) Location of sensor (installed in s tainless steel well)
All boiler piping field supplied.
IMPORTANT
It is ess ential that the designer review the sizing of all pumps including the boiler pump normally supplied with the 100% Boiler Flow Package to verify that all pumps in the system operate correctly. The responsibility for the distribution system design, including all c irculation pum ps, r emains with the system designer.
Boiler return header
8 VITOROND 200, VD2
5285 661 v1.4
Page 9
Recommended Minimum Service Clearances
39½” / 19¾” /
1000 mm
500 mm
c
Technical Data
The combustion chamber door is factory assembled to hinge on the left-hand side. A right-hand hinge is feasible by rebuilding the door hinge hardwar e.
19¾” / 500 mm
8” / 200 mm
Boiler model
c inc hes
mm
d inches
mm
Inch dime nsions rounded to the nearest ¼”.
Front clearances (dimension “c” above) will allow for easy removal of flue gas
d
turbulator inserts, as well as for full insertion of bristle brush for heat exchanger cleaning.
VD2-125 VD2-160 VD2-195 VD2-230 VD2-270
47¼
1200
Dependent on burner model
53
1350
59
1500
65
1650
71
1800
IMPORTANT
Minimum side clearance of 19¾” / 500 mm must be ma intained for side-mounted KR or Dekamatik controls.
Recommended Clearances to Combustibles
Boiler model VD2- 125 160 195 230 270
Top 6” / 150 mm
Sides 6” / 150 mm Flue (oil) 9” / 229 mm Flue (gas) 6” / 150 mm
Front 6” / 150 mm Floor non-combustible
IMPORTANT
Maintain 1” air clearance from uninsulated hot water pipes to combustible material.
IMPORTANT
Boiler must not be installed on carpet.
5285 661 v1.4
VITOROND 200, VD2 9
Page 10
Technical Data
Waterside Flow
The Vitorond 200 boiler is designed for closed loop, forced circulation, hot water heating systems only.
The recommended water flow rate through the Vitorond 200 is based on a temperature difference of between 20°F and
40°F / 11°C and 22°C (see table below). When a balancing valve is used for proper balancing and water flow through the boiler, the valve should be installed 5 pipe dia meters from any fittings and 10 pipe diameters from circulation pumps to allow for laminar flow.
The consulting engineer or c ontractor should review the system design if more balancing valves are required to properly balance the system.
Viessmann can supply TA (Victaulic) balancing valves upon request. The balancing should be carried out by a certified balancing firm prior to boiler start-up. Please contact Viessmann for your closest certified balancing firm.
VD2-125 and VD2-160 VD2-195 VD2-230 and VD2-270
”W.C.
320 280
200
Pressure drop
400
160 140 120
100
80
60
40
32
28
24
20 16
14
12 10
8
6
mbar
1000
800 700 600240
500
400 350
300 250
200
150
100
80 70
60 50
40
35
30 25
20
15
A
B
C
10
4
3.2
8
2
5
345
18
810
35
2213 110886644
15 20 25
132
30
3
m
/h
USG/min
Flow rate
Recommended Flow Rates
Boiler model VD2- 125 160 195 230 270
*1
20°F ∆t 40°F ∆t
11°C ∆t 22°C ∆t
*1
t = temperature difference
GPM GPM
ltrs/s ltrs/s
43 21
2.7
1.3
55 27
3.4
1.7
67 33
4.2
2.1
79 39
5.0
2.5
92 46
5.8
2.9
10 VITOROND 200, VD2
5285 661 v1.4
Page 11
Operational Details
Operational Details
Requirements are fulfilled via...
Heating water volume flow 30% at heating output a bypass pump / shunt pump or
Boiler return water temperature (minimum)
Minimum boiler water temperature
2-Stage burne r operation For operation with modulating boiler water temperatures:
Modulating burner ope ration For elevated boiler water temperatures only:
Setback ope ration Minimum boiler water temperature:
Weekend setback See Setback ope ration See Setback operation
For operation with modulating boiler water temperatures:
- Oil-fired 104°F / 40°C
- Gas-fired 127°F / 53°C
For operation with elevated boiler water temperatures:
- Oil-fired 127°F / 53°C
- Gas-fired 127°F / 53°C For operation with modulating boiler water temperatures:
- Oil-fired 122°F / 50°C
- Gas-fired 140°F / 60°C
For operation with elevated boiler water temperatures:
- Oil-fired 140°F / 60°C
- Gas-fired 149°F / 65°C
first stage 60% of heating output
For operation with elevated boiler water temperatures: No minimum heating input applies
- Oil-fired 140°F / 60°C
- Gas-fired 149°F / 65°C
- min. return water temperature 127°F / 53°C
- Oil-fired 122°F / 50°C
- Gas-fired 140°F / 60°C
For multiple-boiler installations:
- Lead boiler as above
- Lag boiler(s) is/are deactivated
boiler circulation pump
an effective system of return tempera­ture elevation
The Viessmann Dekamatik or Vitotronic control system
Burner calibration (site)
The Viessmann Dekamatik or Vitotronic control system
The Viessmann control included in the standard equipment
5285 661 v1.4
VITOROND 200, VD2 11
Page 12
Standard Equipment Boiler Control Alternatives
Standard Equipment
Note: Boiler controls and burners are purchased separately. Please see Price List for details.
H The cast iron sections are delivered as
individual units on skids.
H The combustion chamber door is mounted
on the front section.
H The flue gas collector, with two
inspection opening c overs (fastened with screws), is mounted on the re ar section.
Boiler Control Alternatives
For single-boiler installations:
Dekamatik-D1,-E Vitotronic 100, GC1 Vitotronic 300, GW2
Digital boiler control systems for modulating boiler water temperature or boiler setpoint control.
*1
*1
1 skid c ontaining supply and return headers 1 carton containing insulation panels 1 carton containing the boiler control
Standard equipment includes: – Boiler base with leveling bolts – Connection piping with counter flanges and
seals
– Supply piping, sight glass, turbulators and
cleaning brush are packed in a carton and placed inside the combustion chamber
When cast iron sections are delivered as individual units: – Push nipples, sight glass, glass fiber rope
seals, adhesive and oil graphite are packed in a carton and placed inside the combustion chamber
For multiple-boiler installations:
Dekamatik-D1,-D2 Vitotronic 100, GC1
Digital boiler control systems for modulating boiler and common supply tempera tur e control.
Vitocontrol
Master control for up to four boilers in conjunction with Vitotronic 100, GC1.
*1
*1
IMPORTANT
Ensure
specific regional, provincial, or state requirements, such as fuel train and additional safety control requirements etc., are known before the product order is placed, to determine proper burner selection and pricing.
For single- or multiple-boiler installations :
Custom contr ol panels
Custom contr ol panels for residential or commercial applications are designed and manufactured by Vies smann to suit any customer’s specific requirements. Custom control panels can have features such as pool hea ting, hot tub heating, s now melting, telephone tie-in, integration with Building Management Systems, as well as several other functions. Please inquire.
1*
Limited application only. Please inquire .
The control of the Vitorond 200, VD2 boiler can be mounted either on the left- or r ight-hand side of the boiler. Please specify control location a t the time of order.
12 VITOROND 200, VD2
5285 661 v1.4
Page 13
System Design Considerations
System Design Considerations
Burner calibration
With 2-stage and fully modulating burners, ensure that the chimney is compatible with the lower flue gas temperatures associated with partial load conditions set on the burner.
2-Stage burne r
When used with the Dekamatik or Vitotronic control, the following minimum heating outputs ar e applicable to protect the boiler:
- 60% of outputs stated in the Technical Data table on page 4.
Fully modulating burner
The minimum boiler water temperature is: – 140°F / 60°C with oil, – 149°F / 65°C with natural gas. Set the return temperature elevation system to maintain a minimum value of 127°F / 53°C.
Venting
The Vitorond 200, VD2 boiler is approved as a Category I appliance and must be vented accordingly.
CAUTION
The Vitorond 200, VD2 boiler is not approved for side wall venting.
Chimney
For proper operation of the Vitorond 200, VD2 boiler, all products of combustion must be safely vented to the outdoors, while ensuring that flue gases do not cool prematurely. It is critical that the chimney s ystem be properly designed to handle the relatively cool flue gas temperatures produced by the Vitorond 200, VD2 boiler. If the chimney system lacks sufficient insulation and/or the chimney diameter is too large, corrosive and damaging condensation will result due to flue gases cooling too quickly. If a calculated chimney diameter lies between two values, the larger diameter should be selected.
5285 661 v1.4
VITOROND 200, VD2 13
Chimney (continued)
The chimney connection length between the boiler vent pipe collar and the chimney must be installed w ith insulation. Vent pipe collar diameter does not automatically indicate vent/chimney size. We recommend consulting a reputable chimney installer for advice in project-specific circumstances.
When installing the Vitorond 200, VD2 boiler, it is necessary to install a barometric draft regulator in the chimney/vent for proper operation of the boiler.
Install the barome tr ic dra ft regulator within 5 to 7 ft. / 1½ to 2 m from the breeching outlet located at the rear of the boiler.
Barometric draft regulator type
For natura l gas or propane applications, use a double -acting type.
For #2 fuel oil applications, use a single-acting type.
Barometric draft r egulator diameter
The barometric draft regulator must be the same diameter opening as the chimney for
which the vent is sized. For example , a 14” chimney would require a 14” barometric draft regulator. Do not size the barometric draft regulator to the breeching outlet of the boiler, unless the chimney is also intended to be of that diameter.
IMPORTANT
The size of the flue gas outlet on the boiler does not automatically determine the horizontal breeching, or the actual chimney diameter. The chimney size must be designed for the actual boiler model and its input.
Barometric draft regulator
Combustion air supply
The boiler must not be located in areas or rooms where chemicals containing chlorine, bromine, fluorine, or other corrosive chemicals are stored. Examples include refrigerants, bleach, paint, paint thinner, hair spray, cleaning solvents, water softener salt, etc. The combus tion air must not be contaminated with any amount of the above mentioned chemicals.
Boiler should never be installe d in areas where excessive dust, high humidity, or risk of frost exist. Ensure adequate ventilation and supply of fresh combustion air.
Consult Viessmann with unc ertainties in regard to a suitable boiler installation location.
This boiler/burner unit needs clean fresh air for safe operation. Provisions for combustion and ventilation air must be made at time of installation. For oil-fired boilers, use the “Installation Code for Oil Burning Equipment CAN/CSA-B139” (Canada), or NFPA 31 (USA). For gas or propane installations, use the “Natural Gas Installation Code CAN/CSA-B149.1 or B149.2” (Canada), or “National Fuel Gas Code ANSI Z223.1” (USA), and/or provisions of local codes.
The sizing methods outlined in the above codes should be used w hen ins talling a round duct to supply combustion air from the outside.
Warranty
Our warranty does not cover damages resulting from the following: – Corrosion caused by flue gas condensation
due to low boiler water and/or return water temperatures.
– Operation with contaminated fill and
supplementary feed water.
System layout
The boiler water temperature limit is factory set to 167°F / 75°C. The boiler water temperature limit can be increased by altering the adjus table high limit to increas e the supply water temperature. To minimize piping losses of the system, however, Viessmann recommends that the radiation and domestic hot water production in the system be designed for a 158°F / 70°C boiler supply water temperature.
Page 14
System Design Considerations/Burner Alternatives
System Design Considerations (continued)/Burner Alternatives
Water quality
Treatment for boile r feed water should be considered in areas of known problems, such as where a high mineral content and hardness exist. In areas where freezing might occur, an antifreeze may be added to the system water to protect the system. Please adhere to the specifications given by the antifreez e manufacturer. Do not use automotive silicate-based antifreeze. Please observe that an antifreeze/water mixture may require a backflow preventer within the automatic water feed and influence components such as diaphragm expansion tanks, radiation, etc. A 40% antifreeze content will provide freeze-up protection to
-10°F / -23°C. Do not use antifreeze other than specifically made for hot water heating systems. System also may contain components which might be negatively affected by antifreeze. Check total s ystem frequently when filled with antifreeze. Follow the instructions of antifreeze manufacturer.
Oxygen diffusion barrier underfloor tubing
The boiler warranty does not cover leaks resulting from corrosion caused by the use of underfloor plastic tubing without an oxygen diffusion barrier. Such systems must have the tubing without oxygen diffusion barrier separated from the boiler with a heat exchanger. Viessmann recommends the use of underfloor plastic tubing with an oxygen diffusion bar rier.
Burner manufacturer
Weishaupt or Riello
Burner/Gas train approval
Standard approvals are CSA (for Canada) and U L (for U.S.). IRI and FM approved equipment is also a vailable - please inquire.
Electrical requirements
Weishaupt W Series bur ners are available in 120 VAC, single-phase, in a 60 Hz configuration. L, G, and GL Series burners listed below are available in 120 VAC single phase, 208 VAC three-phase, 460 VAC three-phase, or 575 VAC three-phase, all in 60 Hz configuration. It is generally acceptable to use voltages within ten percent of the supply voltage. Available voltage inside boiler room must be provided at time of order. Ensure appropriate disconnect means and overcurrent protection.
Natural gas pressure
Natural gas pressures and heating values as provided by the gas utilities vary greatly across North America. Select the appropriate gas train accordingly. Low pressure gas trains have a maximum input of 14 ”w.c .; high pressure gas trains have a maximum pressure of 5 psig. Minimum gas pressures apply - please inquire. Gas pressures and heating values at site must be provided at time of order.
Factory prewired components
Custom factory prewiring by Viessmann ensures optimal functionality, compliance with regional r equirements, and ease of installation in the field. Pricing provided by Viessmann includes all necessary hardware items such as junction pane l, burner power supply, boiler door safety switch (where necessary), and all essential pressure switches, as well as interconnection with conduit between control and burner.
Electrical drawings provided upon product delivery.
Boiler/Burner start-up
Vitorond 200, VD2 boilers with Weishaupt burners require start-up by Viessmann. Please inquire to obtain details rega rding the necessary prerequisites of boiler/burner start-up procedures.
IMPORTANT
To minimize delivery lead times, please ensure that critical technical information is provided at time of order. Viessmann will not process an order without site-specific information regarding available voltage and gas pressure. In addition Vie ssmann recommends that gas pressure information be provided in writing by the loca l gas utility.
14 VITOROND 200, VD2
5285 661 v1.4
Page 15
System Design Considerations/Burner Alternatives
Weishaupt Burners
Boiler model VD2- 125 160 195 230 270
No. 2 oil-fired
2-stage
Natural gas-fired
2-stage
Natural gas-fired
fully modulating
Propane gas-fired
2-stage
Propane gas-fired
fully modulating
Combination
fully modulating NG, 2-stage oil
Riello Burners
Boiler model VD2- 125 160 195 230 270
No. 2 oil-fired
1-stage
No. 2 oil-fired
2-stage
Natural gas-fired
1-stage with assembled gas train
Propane gas-fired
1-stage with assembled gas train
Natural gas-fired
2-stage with assembled gas train
Propane gas-fired
2-stage with assembled gas train
Natural gas-fired
fully modulating
Propane gas-fired
fully modulating
Combination
2-stage NG, 2-stage oil
Natural gas-fired
fully modulating low NO
x
Model WL30 L1Z
Model WG30 G1 G3
Model WG30 G1 G3
Model WG30 G1 G3
Model WG30 G1 G3
Model WGL30 GL1
Model F15 F20 n.a.
Model n.a. RL28/2
Model G750 n.a.
Model G750 n.a.
Model n.a. G900 n.a.
Model n.a. G900 n.a.
Model n.a. RS28/M
Model n.a. RS28/M
Model n.a. RLS28/M
Model n.a. RS45/M LN
5285 661 v1.4
VITOROND 200, VD2 15
Page 16
Printed on environmentally friendly
Printed on environmentally friendly
(recycled and recyclable) paper.
(recycled and recyclable) paper.
Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island 02886 USA Tel. (401) 732-0667 Fax (401) 732-0590 www.viessmann-us.com info@viessmann-us.com
16 VITOROND 200, VD2
Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario N2V 2G5 Canada Tel. (519) 885-6300 Fax (519) 885-0887 www.viessmann.ca info@viessmann.ca
Technical information subject to change without notice.