Viessmann Vitodens 200-W, Type B2HA, Vitodens 200-W B2HA Installation And Service Instructions Manual

Page 1
Installation and service instructions
for contractors
VIESMANN
Vitodens 200-W Type B2HA, 125 and 150 kW
Wall mounted gas condensing boiler Natural gas and LPG version
For applicability, see the last page
VITODENS 200-W
5623 520 GB 6/2012
Please keep safe.
Page 2
2
Please follow these safety instructions closely to prevent accidents and mate­rial losses.
Safety instructions explained
Danger
This symbol warns against the risk of injury.
!
Please note
This symbol warns against the risk of material losses and envi­ronmental pollution.
Note
Details identified by the word "Note" con­tain additional information.
Target group
These instructions are exclusively designed for qualified personnel.
■ Work on gas equipment must only be carried out by a qualified gas fitter.
■ Work on electrical equipment must only be carried out by a qualified elec­trician.
■ The system must be commissioned by the system installer or a qualified per­son authorised by the installer.
Regulations
Observe the following when working on this system
■ all legal instructions regarding the pre­vention of accidents,
■ all legal instructions regarding envi­ronmental protection,
■ the Code of Practice of relevant trade associations,
■ all current safety regulations as defined by DIN, EN, DVGW, TRGI, TRF, VDE and all locally applicable standards,
■ Gas Safety (Installation & Use) Regu­lations – the appropriate Building Regulation
either the Building regulations, the Building Regulation (Scotland), Building Regulations (Northern Ire­land),
– the Water Fittings Regulation or
Water Bylaws in Scotland,
– the current I.E.E. Wiring Regula-
tions.
If you smell gas
Danger
Escaping gas can lead to explo­sions which may result in serious injury.
■ Never smoke. Prevent naked flames and sparks. Never switch lights or electrical appli­ances ON or OFF.
■ Close the gas shut-off valve.
■ Open windows and doors.
■ Remove all people from the danger zone.
■ Notify your gas or electricity supplier from outside the build­ing.
■ Shut off the electricity supply to the building from a safe place (outside the building).
Safety instructions
Safety instructions
5623 520 GB
Page 3
3
If you smell flue gas
Danger
Flue gas can lead to life-threat­ening poisoning.
■ Shut down the heating system.
■ Ventilate the boiler room.
■ Close all doors leading to the living space.
Working on the system
■ When using gas as fuel, also close the main gas shut-off valve and safeguard against unauthorised reopening.
■ Isolate the system from the power sup­ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a main isolator.
■ Safeguard the system against unau­thorised reconnection.
!
Please note
Electronic modules can be dam­aged by electro-static dis­charges. Touch earthed objects, such as heating or water pipes, to dis­charge static loads.
Repair work
!
Please note
Repairing components which ful­fil a safety function can compro­mise the safe operation of your heating system. Replace faulty components only with original Viessmann spare parts.
Ancillary components, spare and wearing parts
!
Please note
Spare and wearing parts which have not been tested together with the heating system can com­promise its function. Installing non-authorised components and non-approved modifications/con­version can compromise safety and may invalidate our warranty. For replacements, use only orig­inal spare parts from Viessmann or those which are approved by Viessmann.
Safety instructions
Safety instructions
(cont.)
5623 520 GB
Page 4
4
Installation instructions
Preparing for installation
Product information.............................................................................................. 6
Preparing for installation....................................................................................... 7
Installation sequence
Fitting the boiler and making connections............................................................ 9
Heating water side connection............................................................................. 13
Flue gas connection............................................................................................. 13
Condensate connection........................................................................................ 14
Gas connection.................................................................................................... 15
Opening the control unit casing............................................................................ 15
Electrical connections........................................................................................... 17
Closing the control unit casing and inserting the programming unit..................... 27
Service instructions
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance.......................................... 28
Further details regarding the individual steps....................................................... 30
Code 1
Calling up coding level 1...................................................................................... 66
General/group "1"................................................................................................. 67
Boiler/group "2".................................................................................................... 70
DHW/group "3"..................................................................................................... 70
Solar/group "4"..................................................................................................... 71
Heating circuit 1, heating circuit 2, heating circuit 3/group "5"............................. 73
Code 2
Calling up coding level 2...................................................................................... 80
General/group "1"................................................................................................. 81
Boiler/group "2".................................................................................................... 90
DHW/group "3"..................................................................................................... 92
Solar/group "4"..................................................................................................... 94
Heating circuit 1, heating circuit 2, heating circuit 3/group "5"............................. 98
Diagnosis and service scans
Calling up the service level................................................................................... 107
Diagnosis.............................................................................................................. 108
Checking outputs (relay test)................................................................................ 114
Index
Index
5623 520 GB
Page 5
5
Troubleshooting
Fault display......................................................................................................... 117
Fault codes........................................................................................................... 119
Repair................................................................................................................... 135
Function description
Constant temperature control unit........................................................................ 143
Weather-compensated control unit...................................................................... 144
Internal extensions (accessories)......................................................................... 145
External extensions (accessories)........................................................................ 148
Control functions.................................................................................................. 152
Assigning heating circuits to the remote control................................................... 160
Electronic combustion control unit........................................................................ 160
Designs
Connection and wiring diagram – internal connections ....................................... 162
Connection and wiring diagram – external connections....................................... 163
Parts lists
Ordering parts...................................................................................................... 165
Overview of the assemblies................................................................................. 166
Casing assembly.................................................................................................. 167
Heat cell assembly............................................................................................... 168
Burner assembly.................................................................................................. 169
Hydraulic assembly.............................................................................................. 169
Control unit assembly........................................................................................... 170
Miscellaneous....................................................................................................... 171
Commissioning/service reports
............................................................................................................................. 173
Specification....................................................................................................... 174
Certificates
Declaration of conformity...................................................................................... 175
Manufacturer's certificate according to the 1st BImSchV [Germany]................... 175
Keyword index.................................................................................................... 176
Index
Index
(cont.)
5623 520 GB
Page 6
6
Vitodens 200-W, B2HA
Preset for operation with natural gas E and LL. For conversion to LPG P (without conversion kit), see page 37.
Conversion for other countries
The Vitodens 200-W should generally only be delivered to those countries specified on the type plate. For deliveries to alternative countries, an approved contractor, on his own initiative, must arrange individual approval in accordance with the law of the land.
Multi boiler system
In connection with the installation of a multi boiler system observe the installation instructions of the multi boiler system accessories.
Preparing for installation
Product information
5623 520 GB
Page 7
7
Dimensions and connections
!
Please note
To prevent equipment damage,
install all pipework free of load and torque stresses.
165.5
165.5
923
1440
95
689
278
905
600
P
40
200
855
1975
1950
E
L
M
O
K
H
N
A B
C
G
D
F
70 70
195
A
Safety valve
B
Expansion vessel connection G1
C
Boiler flow 7 54 mm
D
Cylinder flow 7 42 mm
E
Gas connection R 1
F
Cylinder return 7 42 mm
Preparing for installation
Preparing for installation
5623 520 GB
Installation
Page 8
8
G
Boiler return 7 54 mm
H
Connection sets (accessories, shown without the thermal insula­tion supplied)
K
Cable entry area at the back
L
Without connection set (accesso­ries)
M
With connection set (accessories)
N
Recommended dimension (single boiler system without mounting frame)
O
Recommended dimension (multi boiler system and single boiler sys­tem with mounting frame)
P
Condensate drain
Preparing for the boiler installation
Note
This boiler (protection IP X4 D) is approved for installation in wet rooms inside safety zone 1 according to DIN VDE 0100 [Germany], if hosed water can be prevented. Observe DIN VDE 0100 [or local regula­tions].
1. Prepare the water connections. Thor­oughly flush the heating system.
2. Prepare gas connection to TRGI [or local regulations].
3. Prepare the electrical connections.
Power cable: NYM-J 3 x 1.5 mm2, max. fuse 16 A, 230 V~.
■ Accessory cables: NYM with the
required number of conductors for the external connections.
Allow all cables in area "K" to pro­trude 1400 mm from the wall.
Preparing for installation
Preparing for installation
(cont.)
5623 520 GB
Page 9
9
Removing boiler from packaging and levelling
2x
3.
1.
2..
4.
1. Remove packing cushions and keep them safe. They are used as a support during levelling.
2. Undo two screws on the underside.
3. Remove front panel.
4. Push packing cushions onto the
underside of the boiler.
Installation sequence
Fitting the boiler and making connections
5623 520 GB
Installation
Page 10
10
A
5.
A
7 9 mm drilled holes for attaching lifting gear
5.
!
Please note
To prevent damage, do not level boiler without packing cushions.
Level boiler with pallet.
Installation sequence
Fitting the boiler and making connections
(cont.)
5623 520 GB
Page 11
11
Fitting the wall mounting bracket
Note
The enclosed screws and rawl plugs are only suitable for concrete. For other con­struction materials, use fixings that are suitable for 145 kg loads.
1975
Ø 12
B
C
D
A
2.
1.
A
Reference point: boiler top edge
B
Installation template (included with the boiler)
C
Top edge finished floor
D
Recommendation
Installation sequence
Fitting the boiler and making connections
(cont.)
5623 520 GB
Installation
Page 12
12
Hooking the boiler into the wall mounting bracket and levelling it
1.
3.
2x
3.
2.
Installation sequence
Fitting the boiler and making connections
(cont.)
5623 520 GB
Page 13
13
A
B
C
D
E
A
Expansion vessel connection
B
Boiler flow
C
Cylinder flow
D
Cylinder return
E
Boiler return
Note
Residual water may escape when undo­ing the locking caps.
Flue gas connection
Note
The labels "System certificate" and "Sko­berne GmbH flue system" enclosed with the technical documentation may only be used in conjunction with the Viessmann flue system made by Skoberne.
Installation sequence
Heating water side connection
5623 520 GB
Installation
Page 14
14
A
1. Only for open flue operation: Remove outer gasket A (ventilation air).
2. Connect flue pipe or flue ventilation air pipe.
Flue system installation instruc­tions.
Condensate connection
Connect the condensate hose with a constant fall and a pipe vent to the public sewage system or to a neutralising sys­tem.
Installation sequence
Flue gas connection
(cont.)
5623 520 GB
Page 15
15
A
Information on operation with LPG
We recommend the installation of an external safety solenoid valve when installing the boiler in rooms below ground level.
1.
Seal in gas shut-off valve A into the gas supply pipe.
2. Carry out a tightness test.
Note
Only use suitable and approved leak detecting agents (EN 14291) and devices for the tightness test. Leak detection agents with unsuitable con­stituents (e.g. nitrites, sulphides) can cause material damage. Remove residues of the leak detec­tion agent after testing.
!
Please note
Excessive test pressure may damage the boiler and the gas valve. Max. test pressure 150 mbar. Where higher pressure is required for tightness tests, disconnect the boiler and the gas valves from the gas sup­ply pipe (undo the fitting).
3. Vent the gas line.
Conversion to other gas types: Service instructions
Opening the control unit casing
!
Please note
Electronic assemblies can be damaged by electrostatic dis­charge. Before beginning work, touch earthed objects, such as heating or water pipes, to discharge static loads.
Installation sequence
Gas connection
5623 520 GB
Installation
Page 16
16
3.
2.
2x
1.
4. 4x
5.
Installation sequence
Opening the control unit casing
(cont.)
5623 520 GB
Page 17
17
L N
230V~ 230V~
5
96
40
40962035100
1LN
X4
2 1
2
1
32 15 4
X3
LN
21
M
1~
X19
X14
A
B
21
20
L 1
C
D
145
145
LN
M
1~
A
Radio clock receiver
B
Heating circuit pump or boiler circuit pump
C
Vitotrol 100 UTDB (only for constant temperature control) When making this connection, remove jumper between "1" and "L".
D
Vitotrol 100 UTA (only for constant temperature control) or Vitotrol 100 UTDB-RF radio clock receiver When making this connection, remove jumper between "1" and "L".
Installation sequence
Electrical connections
5623 520 GB
Installation
Page 18
18
Connections at plug 230 V~
Boiler circuit pump or heating circuit pump, variable speed with 0 - 10 V connection
sA
Circulation pump, optional connec­tion:
■ DHW circulation pump
■ External heating circuit pump
■ Circulation pump for cylinder heating
Power supply
lH
■ Power supply for accessories
■ External demand/blocking
■ Vitotrol 100 UTA
■ Vitotrol 100 UTDB
■ Vitotrol 100 UTDB-RF
Connections at LV plug
!
Outside temperature sensor
?
Flow temperature sensor for low loss header (accessories)
%
Cylinder temperature sensor (part of the DHW cylinder connection set)
aVG
KM BUS subscriber (accessory)
■ Vitotrol 200A or 300A remote control
■ Vitocom 100
■ Extension kit for one heating cir­cuit with mixer
■ Solar control module, type SM1
■ Vitosolic
■ Extension AM1
■ Extension EA1
■ Wireless base station
Information on connecting accessories
When connecting accessories observe the separate installation instructions provided with them.
Circulation pump at plug sÖ:
A
1~
M
L
N
?
x4
B
A
Circulation pump
B
Only with variable speed heating cir­cuit pump: Plug in 0 - 10 V connection at X4.
Rated current 2(1) A~ Rated voltage 230 V~
Installation sequence
Electrical connections
(cont.)
5623 520 GB
Page 19
19
Circulation pump at plug sA:
A
1~
M
sA
L
N
?
A
Circulation pump
Rated current 2(1) A~ Rated voltage 230 V~
Set function of connected component in coding address "39" Function Code
DHW circulation pump 39:0 Heating circuit pump for heating circuit without mixer A1
39:1
Circulation pump for cylinder heating (delivered condi­tion)
39:2
External demand via switching contact
Connection options:
■ Extension EA1 (accessory, see sepa­rate installation instructions).
Plug lH.
Connection
!
Please note
'Live' contacts lead to short cir­cuits or phase failure. The external connection must be floating.
Installation sequence
Electrical connections
(cont.)
5623 520 GB
Installation
Page 20
20
Plug lH
Extension EA1
A
lH
N
?
1
L
A
Floating contact When making this connec­tion, remove jumper be­tween 1 and L.
B
[{S
DE
[{D
DE
[{A
DE
A
A
Floating contact
B
Extension EA1
Burner operation is load-dependent if the contact is closed. The boiler water is heat­ed to the value set in coding address "9b" in group "General"/"1". The boiler water temperature is limited by this set value and the electronic maximum limit (coding address "06" in group "Boiler"/"2").
Codes
Plug lH
Extension EA1
"4b:1" in group "General"/"1" Set "3A" (DE1), "3b" (DE2) or "3C" (DE3) in
group "General"/"1" to 2.
■ Select effect of the function on the relevant heating circuit pump in coding address "d7" in group "Heating circuit"/"5".
■ Select effect of the function on the circulation pump for cylinder heating in coding address "5F" in group "DHW"/"3".
External demand via 0 – 10 V input
Connection at 0 – 10 V input to exten­sion EA1.
Ensure DC separation between the earth conductor and the negative pole of the on-site voltage source.
Installation sequence
Electrical connections
(cont.)
5623 520 GB
Page 21
21
L
?
N
L
?
N
S
P
aBJ
230 V~
Ö
[{{]
0-10V
f-]
A
=
0-10 V
+
1 2
0 – 1 V
no default set boiler water temperature
1 V
Set value 10 °C
10 V
Set value 100 °C
External blocking via switching contact
Connection options:
Plug lH.
■ Extension EA1 (accessory, see sepa­rate installation instructions).
!
Please note
'Live' contacts lead to short cir­cuits or phase failure. The external connection must be floating.
Installation sequence
Electrical connections
(cont.)
5623 520 GB
Installation
Page 22
22
Plug lH
Extension EA1
A
lH
N
?
1
L
A
Floating contact When making this connection, re­move jumper between 1 and L.
B
[{SDE[{D
DE
[{A
DE
A
A
Floating contact
B
Extension EA1
The burner is switched off if this contact is closed. The heating circuit pump and circulation pump for cylinder heating are switched according to the set code (see the following table "Codes").
!
Please note When blocked, there is no frost protection for the
heating system.
Codes
Plug lH
Extension EA1
"4b:2" in group "General"/"1" Set "3A" (DE1), "3b" (DE2) or "3C" (DE3) in
group "General"/"1" to 3 or 4.
■ Select effect of the function on the heating circuit pump in coding address "d6" in group "Heating circuit"/"5".
■ Select effect of the function on the circulation pump for cylinder heating in coding address "5E" in group "DHW"/"3".
Outside temperature sensor
!
Fitting outside temperature sensor RF (wireless accessory):
Wireless base station
Installation sequence
Electrical connections
(cont.)
5623 520 GB
Page 23
23
Fitting location for outside tempera­ture sensor
■ North or north-westerly wall, 2 to
2.5 m above ground level; in multi storey buildings, in the top half of the second floor
■ Not above windows, doors or vents
■ Not immediately below balconies or gutters
■ Never render over
Outside temperature sensor connec­tion
2-core lead, length up to 35 m with a cross-section of 1.5 mm
2
Power supply for accessories at plug
lH
230 V~ Where the boiler is installed in a wet area, the connection of accessories to the power supply must not be carried out at the control unit. The power supply connection for accessories can be made immediately at the control unit, if the boiler is installed outside wet areas. This connection is switched directly with the ON/OFF switch of the control unit.
If the total system current exceeds 6 A, connect one or more extensions via an ON/OFF switch directly to the mains sup­ply (see next chapter).
Installation sequence
Electrical connections
(cont.)
5623 520 GB
Installation
Page 24
24
Connection of accessories
Power supply of all accessories via the boiler control unit
145
145
40 A
40
145
145
40 A
40
B C
145
40
96
A
145
145
40 A
40
D
E
Some accessories with direct power supply
145
145
40 A
40
145
145
40 A
40
B C
145
40
96
A
145
145
40 A
40
D
E
A
Boiler control unit
B
Extension kit for heating circuit with mixer M2
C
Extension kit for heating circuit with mixer M3
D
Extension AM1, EA1 and/or solar control module, type SM1
E
ON/OFF switch
If the current flowing to the connected working parts (e.g. circulation pumps) is higher than the safety level of the acces­sory, the output concerned should only be used to control an on-site relay.
Accessories Internal fuse
protection
Extension kit for heat­ing circuit with mixer
2 A
Extension AM1 4 A Extension EA1 2 A Solar control module, type SM1
2 A
Installation sequence
Electrical connections
(cont.)
5623 520 GB
Page 25
25
Power supply
Danger
Incorrect core allocation can result in serious injury and dam­age to the appliance. Take care not to interchange wires "L1" and "N".
■ Install an isolator in the power cable which simultaneously separates all non-earthed conductors from the mains with contact separation of at least 3 mm. Furthermore, we recommend instal­ling an AC/DC-sensitive RCD (RCD class B ) for DC (fault) currents that can occur with energy efficient equipment.
■ Max. fuse rating 16 A.
Installation sequence
Electrical connections
(cont.)
5623 520 GB
Installation
Page 26
26
Routing the connecting cables
!
Please note
If connecting cables touch hot components they will be damaged. When routing and securing connecting cables on site, ensure that the maxi­mum permissible temperatures for these cables are not exceeded.
5
A
Low voltage connections
B
230 V connections
C
Internal extension
D
Main PCB
E
Communication module
F
Cable grommet for power cable
%
Plugs for connecting the cylinder temperature sensor to the cable har­ness
Remove the existing cable grommet when using larger cross-sections (up to
7
14 mm). Secure the cable with the cable grommet plugged into the lower casing section F (black).
Installation sequence
Electrical connections
(cont.)
5623 520 GB
Page 27
27
1.
3.
2x
2.
4.
4.
6.
Insert programming unit (packed sepa­rately) into the control unit support.
Note
The programming unit can also be housed in a wall mounting base (acces­sory) near the boiler.
Wall mounting base installation instructions
Installation sequence
Closing the control unit casing and inserting the programming unit
5623 520 GB
Installation
Page 28
28
For further information regarding the individual steps, see the page indicated
Commissioning steps
Inspection steps
Maintenance steps Page
1. Opening the boiler.......................................................... 30
2. Filling the heating system.............................................. 31
3. Selecting the language (if necessary) - only for
weather-compensated control units............................. 32
4. Setting the time and date (if required) - only for
weather-compensated control units............................. 33
5. Venting the boiler........................................................... 34
6. Venting the heating system........................................... 35
7. Filling the siphon with water......................................... 35
8. Checking all connections on the heating water side and DHW side for leaks
9. Checking the power supply
10. Designating heating circuits - only for weather-
compensated control units............................................ 36
11. Checking the gas type.................................................... 36
12. Gas type conversion (only for operation with LPG).... 37
13. Function sequence and possible faults....................... 37
14. Checking the static and supply pressure..................... 39
15. Maximum output setting................................................ 41
16. Checking the balanced flue system for tightness
(annular gap check)........................................................ 42
17. Removing the burner and checking the burner gasket 43
18. Checking the burner gauze assembly & replacing if
required........................................................................... 44
19. Checking the flue gas non-return device..................... 45
20. Checking and adjusting the ignition and ionisation
electrodes........................................................................ 46
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance
5623 520 GB
Page 29
29
Commissioning steps
Inspection steps
Maintenance steps Page
21. Cleaning the combustion chamber/heat exchanger
and installing the burner................................................ 47
22. Checking the condensate drain and cleaning the
siphon.............................................................................. 48
23. Checking the neutralising system (if installed)
24. Checking the diaphragm expansion vessel and
system pressure............................................................. 48
25. Checking the function of safety valves
26. Checking firm seating of electrical connections
27. Checking all gas equipment for tightness at operating
pressure .......................................................................... 49
28. Checking combustion quality........................................ 49
29. Checking the flue system for unrestricted flow and tightness
30. Checking the external LPG safety valve (if installed)
31. Matching the control unit to the heating system ........ 51
32. Adjusting the heating curves (only for weather-
compensated control units)........................................... 58
33. Connecting the control unit to the LON....................... 61
34. Calling up and resetting the "Service" display............ 62
35. Fitting the front panel..................................................... 64
36. Instructing the system user........................................... 65
Commissioning, inspection, maintenance
Steps - commissioning, inspection and…
(cont.)
5623 520 GB
Service
Page 30
30
Opening the boiler
2x
2.
1.
4.
3.
Commissioning, inspection, maintenance
Further details regarding the individual steps
5623 520 GB
Page 31
31
Filling the heating system
Fill water
!
Please note
Unsuitable fill water increases the level of deposits and corro­sion and may lead to boiler dam­age.
■ Flush the heating system thor­oughly before filling.
■ Only use fill water of potable quality.
■ An antifreeze additive suitable for heating systems can be added to the fill water. The anti­freeze manufacturer must ver­ify its suitability.
■ Fill and top-up water with a water hardness in excess of the following values must be softened, e.g. with a small soft­ening system for heating water.
Total permissible hardness of the fill and top-up water Total heating output
Specific system volume
kW < 20 l/kW
20 l/kW to < 50 l/kW
50 l/kW
≤ 50
3.0 mol/m
3
(16.8 °dH)
2.0 mol/m
3
(11.2 °dH)
< 0.02 mol/m
3
(0.11 °dH)
> 50 to 200
2.0 mol/m
3
(11.2 °dH)
1.5 mol/m
3
(8.4 °dH)
< 0.02 mol/m
3
(0.11 °dH)
> 200 to 600
1.5 mol/m
3
(8.4 °dH)
0.02 mol/m
3
(0.11 °dH)
< 0.02 mol/m
3
(0.11 °dH)
> 600
< 0.02 mol/m
3
(0.11 °dH)
< 0.02 mol/m
3
(0.11 °dH)
< 0.02 mol/m
3
(0.11 °dH)
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 32
32
A
1. Check the pre-charge pressure of the diaphragm expansion vessel.
2. Close the gas shut-off valve.
3. Connect the supply hose to boiler
drain & fill valve A.
4. Fill the heating system via boiler drain & fill valve A. (minimum system pressure > 1.0 bar). Permiss. operating pressure: 6 bar.
5.
Close boiler drain & fill valve A.
Selecting the language (if necessary) - only for weather-com­pensated control units
At the commissioning stage, the display is in German (factory setting).
Extended menu:
1. å
2. "Settings"
3. "Language"
Sprache
Cesky
CZ
Deutsch
DE
Dansk English
DK GB
Wählen mit
Ø
ç
4. Set the required language with / .
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 33
33
Setting the time and date (if required) - only for weather-com­pensated control units
During commissioning, or after pro­longed time out of use, the time and date need to be reset.
Extended menu:
1. å
2. "Settings"
3. "Time / Date"
4. Set current time and date.
Note
When time and date have been set, the control unit automatically checks the function of the flue gas temperature sen­sor. The display shows: "Test flue gas temp sensor" and "Active". For further details regarding the flue gas temperature sensor test, see page 139.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 34
34
Venting the boiler
B
A
1. Close the shut-off valves on the heat­ing water side.
2. Connect the supply hose to boiler drain & fill valve A.
3.
Plug the drain hose onto top tap B and connect to a drain.
4.
Open taps A and B and vent at mains pressure (purge) until no sound of escaping air can be heard and no more air bubbles are visible.
5.
Close taps A and B, open the shut- off valves on the heating water side.
6. Remove hoses again.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 35
35
Venting the heating system
1. Close the gas shut-off valve and
switch the control unit ON.
2. Activate venting program (see next steps).
Note
For function and sequence of the venting program, see page 154.
3. Check the system pressure.
Activating the venting function
Weather-compensated control unit Constant temperature control unit
Service menu
1. Press OK and å simultaneously for
approx. 4 s.
2. "Service functions"
3. "Venting"
Venting function is enabled.
4. Ending venting function:
Press OK or ä.
Service menu
1. Press OK and å simultaneously for
approx. 4 s.
2.
Select "5" with Ú and confirm with
OK. "ON" flashes.
3. Activate the venting function with OK. "EL on" is shown constantly.
4. Ending venting function: Press ä.
Filling the siphon with water
E
F
C
D
A
B
1.
Pull off cap A downwards.
2.
Undo hose B.
3.
Undo union nut C and pull off siphon D
downwards.
4.
Fill siphon D with water and refit it.
5.
Refit hose B.
6.
Push on cap A from below.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 36
36
Designating heating circuits - only for weather-compensated control units
In the delivered condition, the heating circuits are designated "Heating circuit 1", "Heating circuit 2" and "Heating cir­cuit 3" (if installed). If the system user prefers, the heating circuits can be designated differently to suit the specific system.
To enter names for heating circuits:
Operating instructions
Checking the gas type
The boiler is equipped with an electronic combustion controller that adjusts the burner for optimum combustion in accordance with the prevailing gas qual­ity.
■ Consequently, for natural gas there is no adjustment required across the entire Wobbe index range. The boiler can be operated in the Wobbe index range 9.5 to
15.2 kWh/m3, (34.2 to 54.7 MJ/m3).
■ Convert the burner for operation with LPG (see "Gas type conversion" on page 37).
1. Determine the gas type and Wobbe index by asking your local gas supply utility or LPG supplier.
2. Convert the burner for operation with LPG (see page 37).
3. Record the gas type in the report on page 173.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 37
37
Gas type conversion (only for operation with LPG)
1
2
A
1.
Set adjusting screw A on the gas train to "2".
2. Switch ON/OFF switch "8" on.
3. Select the gas type in coding address
"82":
■ Call up code 2
■ Call up "General" (weather-com­pensated control unit) or Group "1" (constant temperature control unit)
■ In coding address "11", select value "9"
■ In coding address "82", select value "1" (LPG operation)
In code "11", select value "9".
■ End service functions.
4. Open the gas shut-off valve.
5. Affix label "G 31" (included with the
technical documentation) in a clearly visible position, near the gas train on the cover panel.
Function sequence and possible faults
Display Measures
Control unit is­sues a heat de­mand
no
Increase set value and ensure heat is drawn off
yes
Fan starts
no
After approx. 51 s fault F9
Check the fan, fan connecting cables, power at the fan and fan control
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 38
38
yes
Ignition
no
Fault EE
Check the ignition module (control voltage 230 V across plugs "X2.1" and "X2.2")
yes
Gas train opens
no
Fault EE
Check the gas train (control voltage 230 V); check the gas supply pres­sure
yes
Ionisation current builds Symbol
A
no
Fault EE
Check the ionisa­tion electrode ad­justment and the gas line for air­locks
yes
Burner in opera­tion
no
Stops below the set boiler water temperature and restarts immedi­ately
Check the flue gas system for tight­ness (flue gas re­circulation), check the gas flow pres­sure
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 39
39
yes
Automatic calibra­tion of the com­bustion controller
no
Fault E3
Ensure adequate heat transfer. Press reset button R.
Fault Eb Check gap be-
tween ionisation electrode and burner gauze as­sembly. Check allocation of gas type (coding address 82, gas train setting). Check flue sys­tem; remedy flue gas recirculation if required. Press reset button R.
For further details regarding faults, see page 117.
Checking the static and supply pressure
Danger
CO build-up as a result of incor­rect burner adjustment can have serious health implications. Carry out a CO test before and after work on gas appliances.
Operation with LPG
Flush the LPG tank twice during com­missioning or replacement. Vent the tank and gas supply line thoroughly after flushing.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 40
40
A
1. Close the gas shut-off valve.
2.
Undo screw A inside test nipple "PE" on the gas train, but do not remove it, and connect the pressure gauge.
3. Open the gas shut-off valve.
4. Check the static pressure and record
the value in the report on page 173.
Set value: max. 57.5 mbar.
5. Start the boiler.
Note
During commissioning, the boiler can enter a fault state because of airlocks in the gas line. After approx. 5 s, press R to reset the burner.
6. Check the supply (flow) pressure. Set values:
■ Natural gas 20 mbar
■ LPG 50 mbar
Note
Use a suitable measuring device with a resolution of at least 0.1 mbar to measure the supply pressure.
7. Record the actual value in the service report. Take the action shown in the follow­ing table.
8. Shut down the boiler, close the gas shut-off valve, remove the pressure gauge and close test nipple A with the screw.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 41
41
9. Danger
Gas escaping from the test nipple leads to a risk of explo­sion. Check for gas tightness.
Open the gas shut-off valve, start the boiler and check for tightness at test nipple A.
Supply (flow) pres­sure for natural gas
Supply (flow) pressure for LPG
Action
below 15 mbar below 42.5 mbar Do not start the boiler. Notify your gas
supply utility or LPG supplier. 15 to 25 mbar 42.5 to 57.5 mbar Start the boiler. above 25 mbar above 57.5 mbar Install a separate gas pressure governor
upstream of the system and regulate the
pre-charge pressure to 20 mbar for natu-
ral gas or 50 mbar for LPG. Notify your
gas supply utility or LPG supplier.
Maximum output setting
The maximum output for heating oper­ation can be limited. The limit is set via
the modulation range. The max. adjust­able output is limited upwards by the boiler coding card.
Weather-compensated control unit:
1. Press OK and å simultaneously
for approx. 4 s.
2. "Service functions"
3. "Max. output"
4. "Change?" Select "Yes".
A value appears on the display (e.g. "85"). In the delivered condition, this value represents 100 % of rated heat­ing output.
5. Set the required value.
Constant temperature control unit:
1. Press OK and å simultaneously
for approx. 4 s.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 42
42
2.
Select "3" with Ú and confirm with OK. A value flashes on the display (e.g. "85") and "A" appears. In the deliv­ered condition, this value represents 100 % of rated heating output.
3. Select required value and confirm with OK.
Checking the balanced flue system for tightness (annular gap check)
A
A
Combustion air aperture
For balanced flue systems tested together with the wall mounted gas fired boiler, the requirement for a tightness test during commissioning by the flue gas inspector is not applicable.
We recommend that your heating engi­neer carries out a simple leak/tightness test during the commissioning of your system. For this, it would be sufficient to check the CO2 or O2 concentration in the
combustion air at the annular gap of the balanced flue pipe. The flue pipe is deemed to be gas-tight if the CO2 concentration in the combus-
tion air is no higher than 0.2 % or the O2 concentration is at least 20.6 %.
If actual CO2 values are higher or O2 val­ues are lower, then pressure test the flue
pipe with a static pressure of 200 Pa.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 43
43
Removing the burner and checking the burner gasket
A
B
C
D
E
F
G
H
K
1. Switch OFF the main power supply and the ON/OFF switch at the control unit.
2. Close the gas shut-off valve and safe­guard against reopening.
3.
Unlock control unit A and pivot for­wards.
4.
Remove cover panel B.
5.
Pull cables from fan motor C, gas train D, ignition unit E and ionisa­tion electrode F.
6.
Undo gas supply pipe fitting G.
7.
Undo six screws H and remove the burner.
!
Please note
To prevent damage, never touch the mesh of the burner gauze assembly.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 44
44
8.
Check burner gasket K for damage. Replace gasket if required.
Checking the burner gauze assembly & replacing if required
C
B
6x
E
F
D
4x
A
1.
Remove electrodes A.
2.
Undo six retaining clips B on ther­mal insulation ring C and then remove thermal insulation ring C.
3.
Undo four Torx screws D and remove burner gauze assembly
E
with burner gauze assembly gasket
F
.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 45
45
4. Insert new burner gauze assembly
E
with new gasket F and secure with four Torx screws. Torque: 4.0 Nm
5.
Refit thermal insulation ring C and electrodes A.
Checking the flue gas non-return device
B
A
1. Undo three screws and remove fan
A
.
2. Remove flue gas non-return device
B
.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 46
46
3. Check the damper and gasket for dirt
and damage. Replace as neces­sary.
4.
Refit flue gas non-return device B.
5.
Refit fan A and secure with three screws. Torque: 3.0 Nm.
Checking and adjusting the ignition and ionisation electrodes
14
±1
6
+2
0
4
+0,5
0
A A B
A
Ignition electrodes
B
Ionisation electrode
1. Check the electrodes for wear and contamination.
2. Clean the electrodes with a small brush (not with a wire brush) or sand­paper.
!
Please note
Do not damage the mesh of the burner gauze assembly.
3. Check the electrode gaps. If the gaps are not as specified or the electrodes are damaged, replace the electrodes together with new gaskets and adjust them as required. Tighten the elec­trode fixing screws with 3 Nm.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 47
47
Cleaning the combustion chamber/heat exchanger and installing the burner
A
1.
!
Please note
Scratches on parts that are in contact with flue gas can lead to corrosion.
Never use brushes to clean the heating surface.
Use a vacuum cleaner to remove res­idues from heat exchanger A in the combustion chamber.
2. If necessary, spray slightly acidic, chloride-free cleaning agents based on phosphoric acid onto heat exchanger A and let the solution soak in for at least 20 min.
3.
Thoroughly flush heat exchanger A with water.
4. Install the burner and torque the screws diagonally with 8.5 Nm.
5. Fit the gas supply pipe with a new gasket. Torque fittings with 15 Nm.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 48
48
6. Check the gas connections for tight-
ness.
Danger
Escaping gas leads to a risk of explosion. Check all fittings for gas tight­ness.
7. Connect the electrical cables/leads to the corresponding components.
Checking the condensate drain and cleaning the siphon
Note
If condensate escapes at vent aperture
A
or B, clean or (if necessary) replace
the following drain line.
E
F
C
D
A
B
1.
Pull off cap C downwards.
2.
Undo hose D.
3.
Undo union nut E and pull siphon F
downwards.
4.
Clean siphon F.
5. Check that the condensate can drain freely to the public sewage system.
6.
Fill siphon F with water and reas­semble.
7.
Refit hose D.
8.
Push on cap C from below.
Checking the diaphragm expansion vessel and system pressure
Note
Carry out this test on a cold system.
1. Drain the system or close the cap valve on the diaphragm expansion vessel and reduce the pressure until the pressure gauge indicates "0".
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 49
49
2. If the pre-charge pressure of the dia-
phragm expansion vessel is lower than the static system pressure, top up with nitrogen until the pre-charge pressure is raised by 0.1 to 0.2 bar.
3. Top up with water until the charge pressure of the cooled system is 0.1 to 0.2 bar higher than the pre-charge pressure of the diaphragm expansion vessel. Permiss. operating pressure: 6 bar.
Checking all gas equipment for tightness at operating pressure
Danger
Escaping gas leads to a risk of explosion. Check gas equipment for tight­ness.
Note
Only use suitable and approved leak detecting agents (EN 14291) and devi­ces for the tightness test. Leak detection agents with unsuitable constituents (e.g. nitrites, sulphides) can cause material damage. Remove residues of the leak detection agent after testing.
Checking combustion quality
The electronic combustion controller automatically ensures optimum combus­tion quality. During commissioning/ maintenance, only the combustion val­ues need to be checked. For this, meas­ure the CO content plus the CO2 or O
2
content. For a description of the elec­tronic combustion controller functions, see page 160.
Note
Operate the appliance with uncontami­nated combustion air to prevent operat­ing faults and damage.
CO content
■ The CO content must be < 1000 ppm for all gas types.
CO2 or O2 content
■ The CO2 content must be within the following limits (upper and lower out-
put): – 7.5 to 9.6 % for natural gas E and LL – 9.0 to 11.3 % for LPG P
■ For all gas types, the O2 content must be between 3.8 and 7.3 %.
If the actual CO2 or O2 values lie outside their respective ranges, check the bal-
anced flue system for tightness, see page 42.
Note
During commissioning, the combustion controller carries out an automatic cali­bration. Only test the emissions approx. 30 s after the burner has started.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 50
50
A
1. Connect a flue gas analyser at flue gas port A on the boiler flue con­nection.
2. Open the gas shut-off valve, start the boiler and create a heat demand.
3. Set the lower heating output (see page 50).
4. Check the CO2 content. Should the actual value deviate from the afore-
mentioned ranges by more than 1 %, implement steps from page 49.
5. Enter actual values into the report.
6. Select the upper output (see
page 50).
7. Check the CO2 content. Should the actual value deviate from the afore-
mentioned ranges by more than 1 %, implement steps from page 49.
8. After testing, press OK.
9. Enter actual values into the report.
Select higher/lower heating output
Weather-compensated control unit Constant temperature control unit
Service menu
1. Press OK and å simultaneously for
approx. 4 s.
2. "Actuator test"
3. Select the lower heating output: Select "Base load OFF". Then "Base load ON" appears and the burner op­erates at its lower heating output.
4. Select the upper heating output: Select "Full load OFF". Then "Full load ON" appears and the burner op­erates at its upper heating output.
5. Ending output selection: Press ä.
Service menu
1. Press OK and å simultaneously for
approx. 4 s.
2. Select " " with Ú and confirm with
OK. The display shows "I" and "ON" flash­es.
3. Select the lower heating output: Press OK, "ON" will be displayed con- stantly.
4. Select the upper heating output: Press ä.
5. Select "2" with Ú, "ON" flashes.
6. Press OK, "ON" will be displayed con­stantly.
7. Ending output selection: Press ä.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 51
51
Matching the control unit to the heating system
The control unit must be matched to the equipment level of the system. Various system components are recognised automatically by the control unit and the relevant codes are adjusted automati­cally.
■ For the selection of an appropriate scheme, see the following diagrams.
■ For coding steps, see page 66.
System version 1
One heating circuit without mixer A1, with/without DHW heating, with low loss header
1
2
34
6
5
9
qP
8
7
ID: 4605139_1103_02
1
Vitodens 200-W
2
Outside temperature sensor (only for weather-compensated control units) or Vitotrol 100 (only for constant tem­perature control units)
3
Boiler circuit pump
4
Circulation pump for cylinder heat­ing
5
DHW cylinder
6
Cylinder temperature sensor
7
Heating circuit without mixer A1 (heating circuit 1)
8
Heating circuit pump A1
9
Low loss header
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 52
52
qP
Flow temperature sensor, low loss header
Function/system components Code
Adjust Group
Operation with LPG 82:1 "General"/1 System with low loss header and without DHW circu­lation pump: Heating circuit pump A1 connection at internal exten­sion H1 or H2
53:2 "General"/1
System with low loss header and with DHW circula­tion pump: Heating circuit pump A1 connection at extension AM1, terminal A1
"General"/1
DHW circulation pump connection at internal exten­sion H1 or H2
"General"/1
System with low loss header 04:0 "Boiler"/1
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 53
53
System version 2
One heating circuit with mixer M2, with/without DHW heating, with low loss header
1
2
4
qW
qE
3
M
7
8
qP
qQ
9
6
5
ID: 4605140_1103_02
1
Vitodens 200-W
2
Outside temperature sensor
3
Boiler circuit pump
4
Circulation pump for cylinder heat­ing
5
DHW cylinder
6
Cylinder temperature sensor
7
Heating circuit with mixer M2 (heat­ing circuit 2)
8
Temperature limiter to restrict the maximum temperature of underfloor heating systems
9
Flow temperature sensor M2
qP
Heating circuit pump M2
qQ
Extension kit for one heating circuit with mixer M2
qW
Low loss header
qE
Flow temperature sensor, low loss header
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 54
54
Function/system components Code
Adjust Group
Operation with LPG 82:1 "General" System only with one heating circuit with mixer with extension kit for mixer (without unregulated heating circuit)
■ with DHW cylinder 00:4 "General"
■ without DHW cylinder 00:3 "General" System with DHW circulation pump DHW circulation pump connection at internal exten­sion H1 or H2
"General"
System with low loss header 04:0 "Boiler"
System version 3
One heating circuit with mixer M2, with system separation, with/without DHW heating
1
6
5
2
4
M
7
8
qP
qQ
qP
qW
9
3
ID: 4605141_1103_02
1
Vitodens 200-W
2
Outside temperature sensor
3
Boiler circuit pump
4
Circulation pump for cylinder heat­ing
5
DHW cylinder
6
Cylinder temperature sensor
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 55
55
7
Heating circuit with mixer M2 (heat­ing circuit 2)
8
Temperature limiter to restrict the maximum temperature of underfloor heating systems
9
Flow temperature sensor M2
qP
Heating circuit pump M2
qQ
Heat exchanger for system separa­tion
qW
Extension kit for one heating circuit with mixer M2
Function/system components Code
Adjust Group
Operation with LPG 82:1 "General" System only with one heating circuit with mixer with extension kit for mixer (without unregulated heating circuit)
■ with DHW cylinder 00:4 "General"
■ without DHW cylinder 00:3 "General" System with DHW circulation pump DHW circulation pump connection at internal exten­sion H1 or H2
"General"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 56
56
System version 4
One heating circuit without mixer, one heating circuit with mixer M2 (with extension kit), one heating circuit with mixer M3 (with extension kit) and low loss header (with/without DHW heating)
1
6
5
M
qI
qO
8
7
qE
qZ
qU
2
34
qT
M
qW
qQ
qP
9
qR
ID: 4605142_1103_02
1
Vitodens 200-W
2
Outside temperature sensor
3
Boiler circuit pump
4
Circulation pump for cylinder heat­ing
5
DHW cylinder
6
Cylinder temperature sensor
7
Heating circuit without mixer A1 (heating circuit 1)
8
Heating circuit pump A1
9
Heating circuit with mixer M2 (heat­ing circuit 2)
qP
Flow temperature sensor M2
qQ
Heating circuit pump M2
qW
Extension kit for one heating circuit with mixer M2
qE
Heating circuit with mixer M3 (heat­ing circuit 3)
qR
Temperature limiter to restrict the maximum temperature of underfloor heating systems
qT
Flow temperature sensor M3
qZ
Heating circuit pump M3
qU
Extension kit for one heating circuit with mixer M3
qI
Low loss header
qO
Flow temperature sensor, low loss header
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 57
57
Function/system components Code
Adjust Group
Operation with LPG 82:1 "General" System only with two heating circuits with mixer, with extension kit for heating circuit with mixer (without unregulated heating circuit)
■ with DHW cylinder 00:8 "General"
■ without DHW cylinder 00:7 "General" System without DHW circulation pump Heating circuit pump A1 connection at internal exten­sion H1 or H2
53:2 "General"
System with DHW circulation pump Heating circuit pump A1 connection at extension AM1, terminal A1
"General"
DHW circulation pump connection at extension AM1, terminal A2
"General"
System with low loss header 04:0 "Boiler"
System version 5
Multi boiler system with several heating circuits with mixer and low loss header (with/without DHW heating)
1
4
6
5
M M
1
4
7
qU
qI
qQ
qP
9
8
32 qW
qE qR
qT
qZ
ID: 4605016_1103_04
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 58
58
1
Vitodens 200-W
2
Vitotronic 300-K
3
Outside temperature sensor
4
Boiler circuit pump
5
DHW cylinder
6
Cylinder temperature sensor
7
Circulation pump for cylinder heat­ing
8
Heating circuit with mixer M2 (heat­ing circuit 2)
9
Flow temperature sensor M2
qP
Heating circuit pump M2
qQ
Extension kit for one heating circuit with mixer M2
qW
Heating circuit with mixer M3 (heat­ing circuit 3)
qE
Temperature limiter to restrict the maximum temperature of underfloor heating systems
qR
Flow temperature sensor M3
qT
Heating circuit pump M3
qZ
Extension kit for one heating circuit with mixer M3
qU
Low loss header
qI
Flow temperature sensor, low loss header
Required codes Address
Multi boiler system with Vitotronic 300-K 01:2
Note
Codes for multi boiler system, see Vitotronic 300-K installation and service instructions
Adjusting the heating curves (only for weather-compensated control units)
The heating curves illustrate the relation­ship between the outside temperature and the boiler water or flow tempera­ture. To put it simply: The lower the outside temperature, the higher the boiler water or flow temperature. The room temperature, in turn, depends on the boiler water or flow temperature.
Settings in the delivered condition:
■ Slope = 1.4
■ Level = 0
Note
If the heating system includes heating circuits with mixers, then the flow tem­perature of the heating circuit without mixer is higher by a selected differential (8 K in the delivered condition) than the flow temperature of the heating circuits with mixers. The differential temperature is adjusta­ble via coding address "9F" in the "Gen- eral" group.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 59
59
0.2
Outside temperature in °C
Boiler water or
Flow temperature in °C
Slope
2.4
2.6
2.8
3.0
3.2
3.4
90
80
70
60
50
40
30
0 -5 -10 -15 -20510
2.0
2.2
Set room temperature in °C
35
30
25
20
15
10
5
0.4
0.6
0.8
1.0
1.2
1.4
-30-25
1.8
1.6
Slope setting ranges:
■ Underfloor heating systems: 0.2 to 0.8
■ Low temperature heating systems: 0.8 to 1.6
Selecting the set room temperature
Individually adjustable for each heating circuit. The heating curve is offset along the axis of the set room temperature. When the heating circuit pump logic function has been enabled, the curve modifies the starting and stopping characteristics of the heating circuit pump.
Standard set room temperature
90
-20
26 + 20
A
C
D
E
B
Example 1: Change in the standard set room temperature from 20 to 26 °C
A
Boiler water temperature or flow temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 60
60
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Changing the standard set room temper­ature
Operating instructions
Reduced set room temperature
+20 14 5
90
-20
D E
A
C
B
Example 2: Change in the reduced set room temperature from 5 °C to 14 °C
A
Boiler water temperature or flow temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Changing the reduced set room temper­ature
Operating instructions
Changing the slope and level
Individually adjustable for each heating circuit.
A
B
Boiler water or
flow temperature in °C
90
+20 -20
Outside temperature in °C
3.5
1.4
0.2
A
Changing the slope
B
Changing the level (vertical parallel offset of the heating curve)
Extended menu:
1. å
2. "Heating"
3. Select heating circuit.
4. "Heating curve"
5. "Slope" or "Level"
6. Select heating curve according to the
system requirements.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 61
61
Connecting the control unit to the LON
The LON communication module must be plugged in.
Note
The data transfer via the LON can take several minutes.
Single boiler system with Vitotronic 200-H and Vitocom 300 (example)
Set the LON subscriber numbers and further functions via code 2 in group "General" (see following table).
Note
In the LON system, the same subscriber number cannot be allocated twice. Only one Vitotronic may be program­med as fault manager.
Boiler control unit Vitotronic 200-H Vitotronic 200-H Vitocom
LON LON LON
Subscriber no. 1 Code "77:1"
Subscriber no. 10 Code "77:10"
Subscriber no. 11 Set code "77:11"
Subscriber no.
99 Control unit is fault manager Code "79:1"
Control unit is not fault manager Code "79:0"
Control unit is not fault manager Code "79:0"
Device is fault
manager
Control unit transmits the time Code "7b:1"
The control unit re­ceives the time Set code "81:3"
The control unit re­ceives the time Set code "81:3"
Device re-
ceives the
time Control unit transmits outside temperature Set code "97:2"
Control unit receives outside temperature Set code "97:1"
Control unit receives outside temperature Set code "97:1"
LON subscriber fault monitoring Code "9C:20"
LON subscriber fault monitoring Code "9C:20"
LON subscriber fault monitoring Code "9C:20"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 62
62
Carrying out a LON subscriber check
The subscriber check is used to test communication with the system devices connected to the fault manager.
Preconditions:
■ The control unit must be programmed as fault manager (code "79:1")
■ The LON subscriber number must be programmed in all control units (see page 61)
■ The LON subscriber list in the fault manager must be up to date (see page 61)
Carry out subscriber check:
1. Press OK and å simultaneously
for approx. 4 s.
2. "Service functions"
3. "Subscriber check"
4. Select subscriber (e.g. subscriber
10). The subscriber check for the selected subscriber is initiated.
■ Successfully tested subscribers are designated with "OK".
■ Unsuccessfully tested subscribers are designated with "Not OK".
Note
To carry out a new subscriber check, create a new subscriber list with menu item "Delete list?"
Note
If the subscriber check is carried out by another control unit, the sub­scriber number and "Wink" appear on the display for approx. 1 min.
Calling up and resetting the "Service" display
The red fault indicator flashes when the limits set in coding address "21" and "23" in group "Boiler" have been reached.
The following appears on the program­ming unit display:
■ On a constant temperature control unit: The specified hours run or the speci­fied interval with calendar symbol "ý" (subject to setting) and "¸"
■ On a weather-compensated control unit: "Service" and "¸"
Acknowledging and resetting service
Press OK to acknowledge a service message.
Note
An acknowledged service message that was not reset reappears:
■ On a weather-compensated control unit, on the following Monday.
■ On a constant temperature control unit, after seven days.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 63
63
After a service has been carried out (resetting service)
Weather-compensated control unit
1. Press OK and å simultaneously
for approx. 4 s.
2. "Service functions"
3. "Service reset"
Note
The selected service parameters for hours run and interval restart at 0.
Constant temperature control unit
Reset code 24:1 in group "2" to 24:0.
Note
The selected service parameters for hours run and interval restart at 0.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 64
64
Fitting the front panel
2x
1.
2.
Note
Ensure the locking screws are fitted before operating.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Page 65
65
Instructing the system user
The system installer should hand the operating instructions to the system user and instruct the user in operating the system.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service
Page 66
66
Calling up coding level 1
Note
■ On weather-compensated control units, codes are displayed as plain text.
■ Codes that have not been assigned due to the heating system equipment level or the setting of other codes are not displayed.
■ Heating systems with one heating cir­cuit without mixer and one or two heat­ing circuits with mixer: The heating circuit without mixer is designated "Heating circuit 1" and the heating circuits with mixer as
"Heating circuit 2" or "Heating cir­cuit 3".
If the heating circuits were given indi­vidual designations, the selected des­ignation and "HC1", "HC2" or "HC3" appear instead.
Weather-compensated control unit:
1. Press OK and å simultaneously
for approx. 4 s.
2. "Coding level 1"
3. Select group of required coding
address:
"General"
"Boiler"
"DHW"
"Solar"
"Heating circuit 1/2/3"
"All codes std device" In this group, all coding addresses from coding level 1 (except the cod­ing addresses from the "Solar" group) are displayed in ascending order.
4. Select coding address.
5. Select value according to the follow- ing tables and confirm with OK.
6. If you want to reset all codes to their delivered condition: Select "Standard setting" in "Cod­ing level 1".
Note
This also resets codes at coding level
2.
Constant temperature control unit:
1. Press OK and å simultaneously
for approx. 4 s.
2.
Select "1" with Ú for coding level 1 and confirm with OK. "I" flashes on the display for the cod­ing addresses in group 1.
3. Select the group for the required cod­ing address with V/v:
1: "General" 2: "Boiler" 3: "DHW" 4: "Solar" 5: "Heating circuit 1" 6: "All codes std device"
In this group, all coding addresses are displayed in ascending order.
Confirm selected category with OK.
4. Select coding address with V/v.
Code 1
Calling up coding level 1
5623 520 GB
Page 67
67
5. Set value according to the following
tables with V/v and confirm with
OK.
6. If you want to reset all codes to their delivered condition: Select "7" with Ú and confirm with OK. When " " flashes, confirm with OK.
Note
This also resets codes at coding level
2.
General/group "1"
Select "General" for weather-compensated control units (see page 66). Select "1" for constant temperature control units (see page 66).
Coding
Coding in the delivered condition Possible change System design
00:1 System version 1:
One heating circuit with­out mixer A1 (heating cir­cuit 1), without DHW heating
00:2 to 00:10
For system schemes, see the following table:
Value address 00: ...
System version
Description
2 1 One heating circuit without mixer A1 (heating circuit 1), with
DHW heating (code is adjusted automatically)
3 2.3 One heating circuit with mixer M2 (heating circuit 2), without
DHW heating
4 2.3 One heating circuit with mixer (heating circuit 2), with DHW
heating
5 4 One heating circuit without mixer A1 (heating circuit 1) and
one heating circuit with mixer M2 (heating circuit 2), without DHW heating (code is adjusted automatically)
6 4 One heating circuit without mixer A1 (heating circuit 1) and
one heating circuit with mixer M2 (heating circuit 2), with DHW heating (code is adjusted automatically)
Code 1
Calling up coding level 1
(cont.)
5623 520 GB
Service
Page 68
68
Value address 00: ...
System version
Description
7 4 One heating circuit with mixer M2 (heating circuit 2) and one
heating circuit with mixer M3 (heating circuit 3), without DHW heating
8 4 One heating circuit with mixer M2 (heating circuit 2) and one
heating circuit with mixer M3 (heating circuit 3), with DHW heating
9 4 One heating circuit without mixer A1 (heating circuit 1), one
heating circuit with mixer M2 (heating circuit 2) and one heat­ing circuit with mixer M3 (heating circuit 3), without DHW heating (code is adjusted automatically)
10 4 One heating circuit without mixer A1 (heating circuit 1), one
heating circuit with mixer M2 (heating circuit 2) and one heat­ing circuit with mixer M3 (heating circuit 3), with DHW heating (code is adjusted automatically)
Coding in the delivered condition Possible change Internal circulation pump function
51:0 System with low loss
header: Internal circulation pump always starts when there is a heat demand
51:1 System with low loss head-
er: When there is a heat de­mand, the internal circula­tion pump is only started if the burner is operational. Circulation pump is switch­ed off when run-on time ex­pires.
51:2 System with heating water
buffer cylinder: When there is a heat de­mand, the internal circula­tion pump is only started if the burner is operational. Circulation pump is switch­ed off when run-on time ex­pires.
Code 1
General/group "1"
(cont.)
5623 520 GB
Page 69
69
Coding in the delivered condition Possible change Subscriber no.
77:1 LON subscriber number
(only for weather-com­pensated control units)
77:2 to 77:99
LON subscriber number, adjustable from 1 to 99: 1 - 4 = Boiler 5 = Cascade 10 - 97 = Vitotronic 200-H 98 = Vitogate 99 = Vitocom
Note
Allocate each number only once.
Detached house/apartment building
7F:1 Detached house (only for
weather-compensated control units)
7F:0 Apartment building
Separate adjustment of holiday program and time program for DHW heating possible.
Lock out controls
8F:0 Operation in the standard
menu and extended menu enabled.
Note
The respective code is only activated when you exit the service menu.
8F:1 Operation in standard
menu and extended menu blocked. Emissions test mode can be enabled.
8F:2 Operation enabled in the
standard menu and blocked in the extended menu. Emissions test mode can be enabled.
Set flow temperature for external demand
9b:70 Set flow temperature for
external demand 70 °C
9b:0 to 9b:127
Set flow temperature for external demand adjusta­ble from 0 to 127 °C (limited by boiler-specific parame­ters)
Code 1
General/group "1"
(cont.)
5623 520 GB
Service
Page 70
70
Select "Boiler" for weather-compensated control units (see page 66). Select "2" for constant temperature control units (see page 66).
Coding
Coding in the delivered condition Possible change Single/multi boiler system
01:1 Single boiler system (only
for constant temperature control units)
01:2 Multi boiler system with
Vitotronic 300-K
Boiler number
07:1 Boiler number in multi
boiler systems (only for constant temperature control units)
07:2 to 07:8
Boiler number 2 to 8 in mul­ti boiler systems
Burner service in 100 hours
21:0 No service interval (hours
run) selected
21:1 to 21:100
Number of hours run be­fore the burner should be serviced is adjustable from 100 to 10,000 h One adjusting step
100 h
Service interval in months
23:0 No time interval for burn-
er service
23:1 to 23:24
Interval adjustable from 1 to 24 months
Service status
24:0 No "Service" display 24:1 "Service" display (the ad-
dress is automatically set and must be manually re­set after a service has been carried out)
Filling/Venting
2F:0 Venting program/fill pro-
gram disabled
2F:1 Venting program enabled 2F:2 Fill program enabled
DHW/group "3"
Select "DHW" for weather-compensated control units (see page 66). Select "3" for constant temperature control units (see page 66).
Code 1
Boiler/group "2"
5623 520 GB
Page 71
71
Coding
Coding in the delivered condition Possible change Set DHW temperature reheating suppression
67:40 For solar DHW heating:
Set DHW temperature 40 °C. Reheating is sup­pressed above the selec­ted set temperature (boil­er is only connected as backup if the rise in cylin­der temperature is too low). Cannot be adjusted on gas condensing combi boilers.
67:0 to 67:95
Set DHW temperature ad­justable from 0 to 95 °C (limited by boiler-specific parameters)
Enable DHW circulation pump
73:0 DHW circulation pump:
"ON" in accordance with the time program (only for weather-compensated control units)
73:1 to 73:6
"ON" from once per hour for 5 min up to 6 times per hour for 5 min during the time program
73:7 Constantly "ON"
Solar/group "4"
Select "Solar" for weather-compensated control units (see page 66). Select "4" for constant temperature control units (see page 66).
Note
The solar group is only displayed if a solar control module, type SM1, is connected.
Code 1
DHW/group "3"
(cont.)
5623 520 GB
Service
Page 72
72
Coding
Coding in the delivered condition Possible change Speed control solar circuit pump
02:0 Solar circuit pump is not
speed-controlled.
02:1 Solar circuit pump is
speed-controlled with wave packet control.
02:2 Solar circuit pump is
speed-controlled with PWM control.
Cylinder maximum temperature
08:60 Set DHW temperature
(maximum cylinder tem­perature) 60 °C.
08:10 to 08:90
Set DHW temperature ad­justable from 10 to 90 °C.
Stagnation time reduction
0A:5 Temperature differential
for stagnation time reduc­tion (reduction in the speed of the solar circuit pump to protect system components and heat transfer medium) 5 K.
0A:0 Stagnation time reduction
disabled. 0A:1 to 0A:40
Temperature differential
adjustable from 1 to 40 K.
Flow rate solar circuit
0F:70 Solar circuit flow rate at
the maximum pump speed 7 l/min.
0F:1 to 0F:255
Flow rate adjustable from
0.1 to 25.5 l/min;
1 step ≙ 0.1 l/min.
Code 1
Solar/group "4"
(cont.)
5623 520 GB
Page 73
73
Coding in the delivered condition Possible change Extended solar control functions
20:0 No extended control func-
tion enabled.
20:1 Additional function for
DHW heating.
20:2 Differential temperature
control 2.
20:3 Differential temperature
control 2 and auxiliary func­tion.
20:4 Differential temperature
control 2 for central heating
backup. 20:5 Thermostat function. 20:6 Thermostat function and
auxiliary function. 20:7 Solar heating via external
heat exchanger without ad-
ditional temperature sen-
sor. 20:8 Solar heating via external
heat exchanger with addi-
tional temperature sensor. 20:9 Solar heating of two DHW
cylinders.
Heating circuit 1, heating circuit 2, heating circuit 3/group "5"
Select "Heating circuit ..." for weather-compensated control units (see page 66). Select "5" for constant temperature control units (see page 66).
Code 1
Solar/group "4"
(cont.)
5623 520 GB
Service
Page 74
74
Coding
Coding in the delivered condition Possible change Priority DHW heating
A2:2 Cylinder priority applica-
ble to heating circuit pump and mixer
A2:0 Without cylinder priority ap-
plied to heating circuit pump and mixer
A2:1 Cylinder priority only appli-
cable to mixer A2:3 to A2:15
Reduced priority applied to
mixer (the heating circuit
receives a reduced amount
of energy)
Economy function outside temperature
A5:5 With heating circuit pump
logic function (economy mode): Heating circuit pump "OFF" when the outside temperature (AT) is 1 K higher than the set room temperature (RT
set
)
AT > RT
set
+ 1 K (only for
weather-compensated control units)
A5:0 Without heating circuit
pump logic function A5:1 to A5:15
With heating circuit pump
logic function: Heating cir-
cuit pump "OFF"; see fol-
lowing table
Parameter address A5:...
With heating circuit pump logic function: Heating cir­cuit pump "OFF"
1 AT > RT
set
+ 5 K
2 AT > RT
set
+ 4 K
3 AT > RT
set
+ 3 K
4 AT > RT
set
+ 2 K
5 AT > RT
set
+ 1 K
6 AT > RT
set
7 to
AT > RT
set
- 1 K
15 AT > RT
set
- 9 K
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5623 520 GB
Page 75
75
Coding in the delivered condition Possible change Extended economy function adjusted outside temperature
A6:36 Extended economy func-
tion disabled (only for weather-compensated control units)
A6:5 to A6:35
Extended economy func­tion enabled, i.e. the burner and heating circuit pump will stop and the mixer close at a variable value, adjustable between 5 and 35 °C plus 1 °C. The base value is the adjusted out­side temperature. This val­ue is based on the actual outside temperature and a time constant, which takes the cooling down of an average building into con­sideration.
Extended economy function mixer
A7:0 Without mixer economy
function (only for a weath­er-compensated control unit and heating circuit with mixer)
A7:1 With mixer economy func-
tion (extended heating cir­cuit pump logic): Heating circuit pump also "OFF":
■ If the mixer has been at­tempting to close for lon­ger than 20 min.
Heating circuit pump "ON":
■ If the mixer changes to control function
■ If there is a risk of frost
Pump idle time, transition reduced mode
A9:7 With pump idle time:
Heating circuit pump "OFF" if the set value is altered through a change in operating mode or through a change in the set room temperature (only for weather-com­pensated control units)
A9:0 Without pump idle time A9:1 to A9:15
With pump idle time, ad­justable from 1 to 15. The higher the value, the longer the pump idle time.
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5623 520 GB
Service
Page 76
76
Coding in the delivered condition Possible change Weather-compensated/room temperature hook-up
b0:0 With remote control:
Heating mode/reduced mode: weather-compen­sated (only for weather­compensated control units; only change the code for the heating cir­cuit with mixer)
b0:1 Heating mode: weather-
compensated Reduced mode: with room temperature hook-up
b0:2 Heating mode: with room
temperature hook-up Reduced mode: weather­compensated
b0:3 Heating mode/reduced
mode: with room tempera­ture hook-up
Economy function room temperature
b5:0 With remote control: No
room temperature-de­pendent heating circuit pump logic function (only for weather-compensa­ted control units; only change the code for the heating circuit with mix­er)
b5:1 to b5:8
Heating circuit pump logic function, see the following table:
Parameter ad­dress b5:...
With heating circuit pump logic function: Heating circuit pump "OFF" Heating circuit pump "ON"
1 RT
actual
> RT
set
+ 5 K RT
actual
< RT
set
+ 4 K
2 RT
actual
> RT
set
+ 4 K RT
actual
< RT
set
+ 3 K
3 RT
actual
> RT
set
+ 3 K RT
actual
< RT
set
+ 2 K
4 RT
actual
> RT
set
+ 2 K RT
actual
< RT
set
+ 1 K
5 RT
actual
> RT
set
+ 1 K RT
actual
< RT
set
6 RT
actual
> RT
set
RT
actual
< RT
set
- 1 K
7 RT
actual
> RT
set
- 1 K RT
actual
< RT
set
- 2 K
8 RT
actual
> RT
set
- 2 K RT
actual
< RT
set
- 3 K
Coding in the delivered condition Possible change Min. flow temperature heating circuit
C5:20 Electronic minimum flow
temperature limit 20 °C (only for weather-com­pensated control units)
C5:1 to C5:127
Minimum limit adjustable from 1 to 127 °C (limited by boiler-specific parameters)
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5623 520 GB
Page 77
77
Coding in the delivered condition Possible change Max. flow temperature heating circuit
C6:74 Electronic maximum flow
temperature limit 74 °C (only for weather-com­pensated control units)
C6:10 to C6:127
Maximum limit adjustable from 10 to 127 °C (limited by boiler-specific parame­ters)
Heating program - changeover
d5:0 The external heating pro-
gram changeover changes the heating pro­gram to "Constant opera­tion with reduced room temperature" or "Standby mode" (only for weather­compensated control units)
d5:1 The external heating pro-
gram changeover changes to "Constant operation with standard room tempera­ture" (subject to coding ad­dress 3A, 3b and 3C)
Ext. heating program changeover to heating circuit
d8:0 No heating program
changeover via extension EA1
d8:1 Heating program change-
over via input DE1 at ex­tension EA1
d8:2 Heating program change-
over via input DE2 at ex­tension EA1
d8:3 Heating program change-
over via input DE3 at ex­tension EA1
Screed drying
F1:0 Screed drying function
disabled (only for weath­er-compensated control units).
F1:1 to F1:6
Screed drying adjustable in accordance with 6 selecta­ble temperature/time pro­files (see page 154)
F1:15 Constant flow temperature
20 °C
Party mode time limit
F2:8 Time limit for party mode
or external heating pro­gram changeover via pushbutton: 8 h (only for weather-compensated control units)
*1
F2:0 No time limit for party
mode
*1
F2:1 to F2:12
Time limit adjustable from 1 to 12 h
*1
*1
Party mode ends automatically in the "Heating and DHW" program, when the system changes over to operation with standard room temperature.
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5623 520 GB
Service
Page 78
78
Coding in the delivered condition Possible change Pump control in only DHW mode
F6:25 In the "Only DHW" oper-
ating mode, the circula­tion pump in the heating circuit connection set is permanently on (only for constant temperature control units)
F6:0 In the "Only DHW" operat-
ing mode, the circulation pump in the heating circuit connection set is perma-
nently off F6:1 to F6:24
In the "Only DHW" operat-
ing mode, the circulation
pump in the heating circuit
connection set will be star-
ted 1 to 24 times per day for
10 min each time.
Pump control in standby mode
F7:25 In the "Standby" operat-
ing mode, the circulation pump in the heating cir­cuit connection set is per­manently on (only for constant temperature control units)
F7:0 In the "Standby" operating
mode, the circulation pump
in the heating circuit con-
nection set is permanently
off F7:1 to F7:24
In the "Standby" operating
mode, the circulation pump
in the heating circuit con-
nection set will be started 1
to 24 times per day for
10 min each time.
Start temperature raising
F8:-5 Temperature limit for ter-
minating the reduced mode -5 ºC; see example on page 157. Observe the setting of coding address "A3". (on­ly for weather-compensa­ted control units)
F8:+10 to F8:-60
Temperature limit adjusta-
ble from
+10 to -60 °C F8:-61 Function disabled
End temperature raising
F9:-14 Temperature limit for rais-
ing the reduced set room temperature -14 ºC; see example on page 157. (only for weather-com­pensated control units)
F9:+10 to F9:-60
Temperature limit for rais-
ing the set room tempera-
ture to the value selected
for standard mode adjusta-
ble from
+10 to -60 °C
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5623 520 GB
Page 79
79
Coding in the delivered condition Possible change Set flow temperature increase
FA:20 Raising the set boiler wa-
ter temperature or the set flow temperature when changing from operation with reduced room tem­perature to operation with standard room tempera­ture, by 20 %. See exam­ple on page 158 (only for weather-compensated control units).
FA:0 to FA:50
Temperature rise adjusta­ble from 0 to 50 %
Duration set flow temperature increase
Fb:30 Duration for raising the
set boiler water tempera­ture or the set flow tem­perature (see coding ad­dress "FA") 60 min. See example on page 158 (only for weather-com­pensated control units).
Fb:0 to Fb:150
Duration adjustable from 0 to 300 min; 1 step ≙ 2 min
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5623 520 GB
Service
Page 80
80
Calling up coding level 2
Note
■ At coding level 2, all codes are acces­sible, including the codes at coding level 1.
■ Codes that have not been assigned due to the heating system equipment level or the setting of other codes are not displayed.
■ Heating systems with one heating cir­cuit without mixer and one or two heat­ing circuits with mixer: The heating circuit without mixer is designated "Heating circuit 1" and the heating circuits with mixer as
"Heating circuit 2" or "Heating cir­cuit 3".
If the heating circuits were given indi­vidual designations, the selected des­ignation and "HC1", "HC2" or "HC3" appear instead.
Weather-compensated control unit:
1. Press OK and å simultaneously
for approx. 4 s.
2. Press OK and ä simultaneously for
approx. 4 s.
3. "Coding level 2"
4. Select group of required coding
address:
"General"
"Boiler"
"DHW"
"Solar"
"Heating circuit 1/2/3"
"All codes std device" In this group, all coding addresses (except the coding addresses from the "Solar" group) are displayed in ascending order.
5. Select coding address.
6. Select value according to the follow- ing tables and confirm with "OK".
7. If you want to reset all codes to their delivered condition: Select "Standard setting" in "Cod­ing level 2".
Note
This also resets codes at coding level
1.
Constant temperature control unit:
1. Press OK and å simultaneously
for approx. 4 s.
2. Press OK and ä simultaneously for approx. 4 s.
3.
Select "2" with Ú for coding level 2 and confirm with OK. "I" flashes on the display for the cod­ing addresses in category 1.
Code 2
Calling up coding level 2
5623 520 GB
Page 81
81
4. Select the group for the required cod-
ing address with V/v:
1: "General" 2: "Boiler" 3: "DHW" 4: "Solar" 5: "Heating circuit 1" 6: "All codes std device"
In this group, all coding addresses are displayed in ascending order.
Confirm selected category with OK.
5. Select coding address with V/v.
6. Set value according to the following
tables with V/v and confirm with
OK.
7. If you want to reset all codes to their delivered condition: Select "7" with Ú and confirm with OK. When " " flashes, confirm with OK.
Note
This also resets codes at coding level
1.
General/group "1"
Select "General" for weather-compensated control units (see page 80). Select "1" for constant temperature control units (see page 80).
Coding
Coding in the delivered condition Possible change
00:1 System version 1:
One heating circuit with­out mixer A1 (heating cir­cuit 1), without DHW heating
00:2 to 00:10
For system schemes, see the following table:
Value address 00: ...
System version
Description
2 1 One heating circuit without mixer A1 (heating circuit 1), with
DHW heating (code is adjusted automatically)
3 2.3 One heating circuit with mixer M2 (heating circuit 2), without
DHW heating
4 2.3 One heating circuit with mixer (heating circuit 2), with DHW
heating
5 4 One heating circuit without mixer A1 (heating circuit 1) and
one heating circuit with mixer M2 (heating circuit 2), without DHW heating (code is adjusted automatically)
Code 2
Calling up coding level 2
(cont.)
5623 520 GB
Service
Page 82
82
Value address 00: ...
System version
Description
6 4 One heating circuit without mixer A1 (heating circuit 1) and
one heating circuit with mixer M2 (heating circuit 2), with DHW heating (code is adjusted automatically)
7 4 One heating circuit with mixer M2 (heating circuit 2) and one
heating circuit with mixer M3 (heating circuit 3), without DHW heating
8 4 One heating circuit with mixer M2 (heating circuit 2) and one
heating circuit with mixer M3 (heating circuit 3), with DHW heating
9 4 One heating circuit without mixer A1 (heating circuit 1), one
heating circuit with mixer M2 (heating circuit 2) and one heat­ing circuit with mixer M3 (heating circuit 3), without DHW heating (code is adjusted automatically)
10 4 One heating circuit without mixer A1 (heating circuit 1), one
heating circuit with mixer M2 (heating circuit 2) and one heat­ing circuit with mixer M3 (heating circuit 3), with DHW heating (code is adjusted automatically)
Coding in the delivered condition Possible change
11:9
No access to the coding addresses for the com­bustion controller param­eters
11:9 Access open to the coding
addresses for the combus­tion controller parameters
25:0 Without outside tempera-
ture sensor (for constant temperature control units)
25:1 With outside temperature
sensor (automatic recogni­tion)
2A:0 Without wireless outside
temperature sensor
2A:1 With wireless outside tem-
perature sensor (automatic recognition)
2A:2 Wireless outside tempera-
ture sensor not used
2d:1 With flow sensors (do not
adjust)
32:0 Without extension AM1 32:1 With extension AM1 (auto-
matic recognition)
33:1 Function output A1 at ex-
tension AM1: Heating cir­cuit pump
33:0 Function output A1: DHW
circulation pump
Code 2
General/group "1"
(cont.)
5623 520 GB
Page 83
83
Coding in the delivered condition Possible change
33:2 Function output A1: Circu-
lation pump for cylinder heating
34:0 Function output A2 at ex-
tension AM1: DHW circu­lation pump
34:1 Function output A2: Heat-
ing circuit pump
34:2 Function output A2: Circu-
lation pump for cylinder heating
35:0 Without extension EA1 35:1 With extension EA1 (auto-
matic recognition)
36:0
Function, output aBJ at extension EA1: Fault message
36:1
Function output aBJ: Feed pump
36:2
Function output aBJ: DHW circulation pump
39:2
Function output sA: Cir­culation pump for cylinder heating
39:0
Function output sA: DHW circulation pump
39:1
Function output sA: Heat­ing circuit pump
3A:0 Function input DE1 at ex-
tension EA1: Not as­signed
3A:1 Function input DE1: Heat-
ing program - changeover
3A:2 Function input DE1: Exter-
nal demand with set flow temperature. Flow temperature setting: Coding address 9b. Internal circulation pump function: Coding address 3F
3A:3 Function input DE1: Exter-
nal blocking. Internal circulation pump function: Coding address 3E
3A:4 Function input DE1: Exter-
nal blocking with fault mes­sage input Internal circulation pump function: Coding address 3E
3A:5 Function input DE1: Fault
message input
Code 2
General/group "1"
(cont.)
5623 520 GB
Service
Page 84
84
Coding in the delivered condition Possible change
3A:6 Function input DE1: Brief
operation, DHW circulation pump (pushbutton func­tion). DHW circulation pump run­time adjustment: Coding address 3d
3b:0 Function input DE2 at ex-
tension EA1: Not as­signed
3b:1 Function input DE2: Heat-
ing program - changeover
3b:2 Function input DE2: Exter-
nal demand with set flow temperature. Flow temperature setting: Coding address 9b. Internal circulation pump function: Coding address 3F
3b:3 Function input DE2: Exter-
nal blocking. Internal circulation pump function: Coding address 3E
3b:4 Function input DE2: Exter-
nal blocking with fault mes­sage input Internal circulation pump function: Coding address 3E
3b:5 Function input DE2: Fault
message input
3b:6 Function input DE2: Brief
operation, DHW circulation pump (pushbutton func­tion). DHW circulation pump run­time adjustment: Coding address 3d
3C:0 Function input DE3 at ex-
tension EA1: Not as­signed
3C:1 Function input DE3: Heat-
ing program - changeover
Code 2
General/group "1"
(cont.)
5623 520 GB
Page 85
85
Coding in the delivered condition Possible change
3C:2 Function input DE3: Exter-
nal demand with set flow temperature. Flow temperature setting: Coding address 9b. Internal circulation pump function: Coding address 3F
3C:3 Function input DE3: Exter-
nal blocking. Internal circulation pump function: Coding address 3E
3C:4 Function input DE3: Exter-
nal blocking with fault mes­sage input Internal circulation pump function: Coding address 3E
3C:5 Function input DE3: Fault
message input
3C:6 Function input DE3: Brief
operation, DHW circulation pump (pushbutton func­tion). DHW circulation pump run­time adjustment: Coding address 3d
3d:5 DHW circulation pump
runtime for brief opera­tion: 5 min
3d:1 to 3d:60
DHW circulation pump run­time adjustable from 1 to 60 min
3E:0 Boiler circuit pump stays
in control mode on "Ex­ternal blocking" signal
3E:1 Boiler circuit pump is stop-
ped on "External blocking" signal
3E:2 Boiler circuit pump is star-
ted on "External blocking" signal
3F:0 Boiler circuit pump stays
in control mode on "Ex­ternal demand" signal
3F:1 Boiler circuit pump is stop-
ped on "External demand" signal
Code 2
General/group "1"
(cont.)
5623 520 GB
Service
Page 86
86
Coding in the delivered condition Possible change
3F:2 Boiler circuit pump is star-
ted on "External demand" signal
4b:0
Function input lH: Room thermostat (Vitotrol 100) for constant temperature control
4b:1 External demand 4b:2 External blocking
51:0 System with low loss
header: Boiler circuit pump is al­ways started when there is a heat demand
51:1 System with low loss head-
er: When there is heat de­mand, the boiler circuit pump will only be started if the burner is running. Circulation pump is switch­ed off when run-on time ex­pires.
51:2 System with heating water
buffer cylinder: When there is heat de­mand, the boiler circuit pump will only be started if the burner is running. Circulation pump is switch­ed off when run-on time ex­pires.
52:0 Without flow temperature
sensor for low loss head­er
52:1 With flow temperature sen-
sor for low loss header (au­tomatic recognition)
53:1
Function connection sK of the internal extension: DHW circulation pump
53:0
Function connection sK: Central fault message
53:2
Function connection sK: External heating circuit pump (heating circuit 1)
53:3
Function connection sK: External circulation pump for cylinder heating
54:0 Without solar thermal
system
54:1 With Vitosolic 100 (auto-
matic recognition)
54:2 With Vitosolic 200 (auto-
matic recognition)
Code 2
General/group "1"
(cont.)
5623 520 GB
Page 87
87
Coding in the delivered condition Possible change
54:3 With solar control module
SM1 without auxiliary func­tion (automatic recogni­tion)
54:4 With solar control module
SM1 with auxiliary function, e.g. central heating backup (automatic recognition)
6E:50 No correction of meas-
ured outside tempera­ture
6E:0 to 6E:100
Outside temperature cor­rection in 0.1 K steps 0 to 49 = -5 K to -0.1 K 51 to 100 = 0.1 K to 5 K
76:0 Without communication
module
76:1 With LON communication
module (recognised auto­matically; only for weather­compensated control units)
76:2 With cascade communica-
tion module (recognised automatically; only for con­stant temperature control units)
77:1 LON subscriber number
(only for weather-com­pensated control units)
77:2 to 77:99
LON subscriber number, adjustable from 1 to 99: 1 - 4 = Boiler 5 = Cascade 10 - 97 = Vitotronic 200-H 98 = Vitogate 99 = Vitocom
Note
Allocate each number only once.
79:1 With LON communication
module: Control unit is fault manager (only for weather-compensated control units)
79:0 Control unit is not fault
manager
Code 2
General/group "1"
(cont.)
5623 520 GB
Service
Page 88
88
Coding in the delivered condition Possible change
7b:1 With LON communication
module: Control unit transmits the time (only for weather-compensa­ted control units)
7b:0 Does not transmit time
7F:1 Detached house (only for
weather-compensated control units)
7F:0 Apartment building
Separate adjustment of holiday program and time program for DHW heating possible.
80:6 If a fault occurs for at least
30 s, a fault message is displayed
80:0 Immediate fault message 80:2 to 80:199
Minimum fault duration un­til fault message occurs, adjustable from 10 s to 995 s; 1 step ≙ 5 s
81:1 Automatic summer/win-
tertime changeover
81:0 Manual summer/winter-
time changeover
81:2 Use of the radio clock re-
ceiver (automatic recogni­tion)
81:3 With LON communication
module: The control unit re­ceives the time
82:0 Operation with natural
gas
82:1 Operation with LPG (only
adjustable if coding ad­dress 11:9 has been set)
88:0 Temperature display in
°C (Celsius)
88:1 Temperature display in °F
(Fahrenheit) 8A:175 Do not adjust. 8F:0 Operation in the standard
menu and extended menu enabled.
Note
The respective code is only activated when you exit the service menu.
8F:1 Operation in the standard
menu and extended menu
blocked.
Emissions test mode can
be enabled.
8F:2 Operation enabled in the
standard menu; blocked in
the extended menu.
Emissions test mode can
be enabled.
Code 2
General/group "1"
(cont.)
5623 520 GB
Page 89
89
Coding in the delivered condition Possible change
90:128 Time constant for calcu-
lating the adjusted out­side temperature 21.3 h
90:1 to 90:199
Fast (low values) or slow (high values) matching of the flow temperature, sub­ject to the set value when the outside temperature changes; 1 step ≙ 10 min
94:0 Without Open Therm ex-
tension
94:1 With Open Therm exten-
sion (automatic recogni­tion)
95:0 Without Vitocom 100
communication interface
95:1 With Vitocom 100 commu-
nication interface (auto­matic recognition)
97:0 With LON communication
module: The outside tem­perature of the sensor connected to the control unit is utilised internally (only for weather-com­pensated control units)
97:1 Control unit receives out-
side temperature
97:2 Control unit transmits the
outside temperature to the Vitotronic 200-H
98:1 Viessmann system num-
ber (in conjunction with monitoring several sys­tems via Vitocom 300)
98:1 to 98:5
System number adjustable from 1 to 5
99:0 Do not adjust 9A:0 Do not adjust 9b:70 Set flow temperature for
external demand 70 °C
9b:0 to 9b:127
Set flow temperature for external demand adjusta­ble from 0 to 127 °C (limited by boiler-specific parame­ters)
9C:20 Monitoring LON subscrib-
ers.
9C:0 No monitoring 9C:5 to
Time adjustable from 5 to 60 min
Code 2
General/group "1"
(cont.)
5623 520 GB
Service
Page 90
90
Coding in the delivered condition Possible change
If a subscriber fails to re­spond, the values speci­fied inside the control unit will be used after 20 min. Only then will a fault mes­sage be issued. (only for weather-compensated control units)
9C:60
9F:8 Differential temperature
8 K; only in conjunction with mixer circuit (only for weather-compensated control units)
9F:0 to 9F:40
Differential temperature
adjustable from 0 to 40 K
Boiler/group "2"
Select "Boiler" for weather-compensated control units (see page 80). Select "2" for constant temperature control units (see page 80).
Coding
Coding in the delivered condition Possible change
01:1 Single boiler system (only
for constant temperature control units)
01:2 Multi boiler system with
Vitotronic 300-K
04:1 Minimum burner pause
subject to the boiler load (specified by boiler cod­ing card)
04:0 Minimum burner pause set
permanently (specified by
boiler coding card)
06:... Maximum limit of the boil-
er water temperature, specified in °C by the boil­er coding card
06:20 to 06:127
Maximum limit of the boiler
water temperature within
the ranges specified by the
boiler 07:1 Boiler number in multi
boiler systems (only for constant temperature control units)
07:2 to 07:8
Boiler number 2 to 8 in mul-
ti boiler systems
Code 2
General/group "1"
(cont.)
5623 520 GB
Page 91
91
Coding in the delivered condition Possible change
08:... Maximum burner heating
output in kW in the case of a multi boiler system
08:0 to 08:199
Maximum burner heating output adjustable from 0 to 199 kW (limited by boiler­specific parameters) in
steps of 1 kW 0d:0 Do not adjust 0E:0 Do not adjust 13:1 Do not adjust 14:1 Do not adjust 15:1 Do not adjust 21:0 No service interval (hours
run) selected
21:1 to 21:100
Number of hours run be-
fore the burner should be
serviced is adjustable from
100 to 10,000 h
One adjusting step
100 h 23:0 No time interval for burn-
er service
23:1 to 23:24
Interval adjustable from 1
to 24 months
24:0 No "Service" display 24:1 "Service" display (the ad-
dress is automatically set
and must be manually re-
set after a service has been
carried out) 28:0 No burner interval igni-
tion
28:1 to 28:24
Interval adjustable from 1 h
to 24 h. The burner is force-
started once every 30 s
(only when operating with
LPG). 2E:0 Do not adjust 2F:0 Venting program/fill pro-
gram disabled
2F:1 Venting program enabled 2F:2 Fill program enabled
30:3 Boiler circuit pump speed
controlled via 0-10 V in­terface (do not adjust)
38:0 Status burner control unit:
Operational (no fault)
38:0
Status burner control unit:
Faults
Code 2
Boiler/group "2"
(cont.)
5623 520 GB
Service
Page 92
92
Select "DHW" for weather-compensated control units (see page 80). Select "3" for constant temperature control units (see page 80).
Coding
Coding in the delivered condition Possible change
56:0 Set DHW temperature
adjustable from 10 to 60 °C
56:1 Set DHW temperature ad-
justable from 10 to over 60 °C
Note
Maximum value subject to boiler coding card. Observe the max. permis­sible DHW temperature.
58:0 Without auxiliary function
for DHW heating
58:10 to 58:60
Input of a second set DHW temperature, adjustable from 10 to 60 °C (observe coding addresses "56" and "63")
59:0 Cylinder heating:
Starting point -2.5 K Stopping point +2.5 K
59:1 to 59:10
Starting point adjustable from 1 to 10 K below the set value
5b:0 DHW cylinder directly
connected to the boiler
5b:1 DHW cylinder connected
downstream of the low loss header
5E:0 Circulation pump for cyl-
inder heating stays in control mode at signal "External blocking"
5E:1 Circulation pump for cylin-
der heating stops at signal "External blocking"
5E:2 Circulation pump for cylin-
der heating starts at signal "External blocking"
5F:0 Circulation pump for cyl-
inder heating stays in control mode at signal "External demand"
5F:1 Circulation pump for cylin-
der heating stops at signal "External demand"
5F:2 Circulation pump for cylin-
der heating starts at signal "External demand"
Code 2
DHW/group "3"
5623 520 GB
Page 93
93
Coding in the delivered condition Possible change
60:20 During DHW heating, the
boiler water temperature is max. 20 K higher than the set DHW tempera­ture
60:5 to 60:25
The differential between
the boiler water tempera-
ture and the set DHW tem-
perature is adjustable from
5 to 25 K 62:2 Circulation pump with
2 min run-on time after cylinder heating
62:0 Circulation pump without
run-on
62:1 to 62:15
Run-on time adjustable
from 1 to 15 min
63:0 Without auxiliary function
for DHW heating (only for constant temperature control units)
63:1 Auxiliary function: 1 x daily 63:2 to 63:14
Every 2 days to every 14
days
63:15 2 x daily 65:0 Do not adjust. 67:40 For solar DHW heating:
Set DHW temperature 40 °C. Reheating is sup­pressed above the selec­ted set temperature (boil­er is only connected as backup if the rise in cylin­der temperature is too low).
67:0
to
67:95
Set DHW temperature ad­justable from 0 to 95 °C (limited by boiler-specific parameters)
6F:... Maximum output for
DHW heating in %, speci­fied by the boiler coding card
6F:0
to
6F:100
Max. output for DHW heat­ing adjustable from min. output to 100 %
71:0 DHW circulation pump:
"ON" in accordance with the time program (only for weather-compensated control units)
71:1 "OFF" during DHW heating
to set value 1
71:2 "ON" during DHW heating
to set value 1
72:0 DHW circulation pump:
"ON" in accordance with the time program (only for weather-compensated control units)
72:1 "OFF" during DHW heating
to set value 2
72:2 "ON" during DHW heating
to set value 2
Code 2
DHW/group "3"
(cont.)
5623 520 GB
Service
Page 94
94
Coding in the delivered condition Possible change
73:0 DHW circulation pump:
"ON" in accordance with the time program (only for weather-compensated control units)
73:1 to 73:6
"ON" from once per hour for 5 min up to 6 times per hour for 5 min during the time program
73:7 Constantly "ON"
Solar/group "4"
Select "Solar" for weather-compensated control units (see page 80). Select "4" for constant temperature control units (see page 80).
Note
The solar group is only displayed if a solar control module, type SM1, is connected.
Coding
Coding in the delivered condition Possible change
00:8 Start temperature differ-
ential for solar circuit pump 8 K .
00:2 to 00:30
Start temperature differen­tial adjustable from 2 to 30 K.
01:4 Stop temperature differ-
ential for solar circuit pump 4 K.
01:1 to 01:29
Stop temperature differen­tial adjustable from 1 to 29 K.
02:0 Solar circuit pump is not
speed-controlled.
02:1 Solar circuit pump is
speed-controlled with wave packet control.
02:2 Solar circuit pump is
speed-controlled with PWM control.
03:10 Temperature differential
for the start of the speed control 10 K.
03:5 to 03:20
Temperature differential adjustable from 5 to 20 K.
04:4 Controller amplification of
the speed control 4 %/K.
04:1 to 04:10
Controller amplification ad­justable from 1 to 10 %/K.
05:10 Minimum speed of the so-
lar circuit pump 10 % of the maximum speed.
05:2 to 05:100
Minimum speed of the so­lar circuit pump is adjusta­ble from 2 to 100 %.
Code 2
DHW/group "3"
(cont.)
5623 520 GB
Page 95
95
Coding in the delivered condition Possible change
06:75 Maximum speed of the
solar circuit pump 75 % of the maximum possible speed.
06:1
to
06:100
Maximum speed of the so­lar circuit pump is adjusta­ble from 1 to 100 %.
07:0 Interval function of the so-
lar circuit pump switched off.
07:1 Interval function of the so-
lar circuit pump switched on. To capture the collector temperature more accu­rately, the solar circuit pump starts for short cy­cles.
08:60 Set DHW temperature
(maximum cylinder tem­perature) 60 °C.
08:10
to
08:90
Set DHW temperature ad­justable from 10 to 90 °C.
09:130 Maximum collector tem-
perature (to protect the system components) 130 °C.
09:20
to
09:200
Temperature adjustable from 20 to 200 °C.
0A:5 Temperature differential
for stagnation time reduc­tion (reduction in the speed of the solar circuit pump to protect system components and heat transfer medium) 5 K.
0A:0 Stagnation time reduction
is disabled. 0A:1 to 0A:40
Temperature differential
adjustable from 1 to 40 K.
0b:0 Frost protection function
for solar circuit switched off.
0b:1 Frost protection function
for solar circuit switched on
(not required with
Viessmann heat transfer
medium).
0C:1 Delta T monitoring
switched on. No flow rate captured in the solar circuit, or flow rate too low.
0C:0 Delta T monitoring switch-
ed off.
0d:1 Night circulation monitor-
ing switched on. Unintentional flow rate is captured in the solar cir­cuit (e.g. at night).
0d:0 Night circulation monitor-
ing switched off.
Code 2
Solar/group "4"
(cont.)
5623 520 GB
Service
Page 96
96
Coding in the delivered condition Possible change
0E:1 Heat statement in con-
junction with Viessmann heat transfer medium.
0E:2 Never adjust. 0E:0 No heat statement.
0F:70 Solar circuit flow rate at
the maximum pump speed 7 l/min.
0F:1 to 0F:255
Flow rate adjustable from
0.1 to 25.5 l/min. 1 step ≙ 0.1 l/min
10:0 Target temperature con-
trol switched off (see cod­ing address "11").
10:1 Target temperature control
switched on.
11:50 Set solar DHW tempera-
ture 50 °C.
■ Target temperature control switched on (code "10:1"): Temperature at which the solar heated water in the DHW cylinder is to be stratified.
■ Code "20:9" (heating of two DHW cylinders) is selected: When one DHW cylin­der reaches its set DHW temperature, the second DHW cylinder is heated.
11:10 to 11:90
The set solar DHW temper­ature is adjustable from 10 to 90 °C.
12:20 Minimum collector tem-
perature (minimum start temperature for the solar circuit pump) 20 °C.
12:0 No minimum limit enabled. 12:1 to 12:90
Minimum collector temper­ature adjustable from 1 to 90 °C.
20:0 No extended control func-
tions enabled.
20:1 Additional function for
DHW heating.
20:2 Differential temperature
control 2.
20:3 Differential temperature
control 2 and auxiliary func­tion.
20:4 Differential temperature
control 2 for central heating backup.
20:5 Thermostat function.
Code 2
Solar/group "4"
(cont.)
5623 520 GB
Page 97
97
Coding in the delivered condition Possible change
20:6 Thermostat function and
auxiliary function.
20:7 Solar heating via external
heat exchanger without ad­ditional temperature sen­sor.
20:8 Solar heating via external
heat exchanger with addi­tional temperature sensor.
20:9 Solar heating of two DHW
cylinders.
22:8 Start temperature differ-
ential with central heating backup (code "20:4" must be selected) 8 K.
22:2 to 22:30
Start temperature differen­tial adjustable from 2 to 30 K.
23:4 Shutdown temperature
differential with central heating backup (code "20:4" must be selected) 4 K.
23:2 to 23:30
Shutdown temperature dif­ferential adjustable from 1 to 29 K.
24:40 Start temperature for
thermostat function (code "20:5" or "20:6" must be selected) 40 °C.
24:0 to 24:100
Start temperature for ther­mostat function adjustable from 0 to 100 K.
25:50 Shutdown temperature
for thermostat function (code "20:5" or "20:6" must be selected) 50 °C.
25:0 to 25:100
Shutdown temperature for thermostat function adjust­able from 0 to 100 K.
26:1 Priority for DHW cylinder
1 with alternate heating. (Code "20:9" must be se­lected).
26:0 Priority for DHW cylinder 1
without alternate heating.
26:2 Priority for DHW cylinder 2
without alternate heating.
26:3 Priority for DHW cylinder 2
with alternate heating.
26:4 Alternate heating without
priority for either DHW cyl­inder.
27:15 Alternate heating time
15 min.
27:5 to 27:60
The alternate heating time is adjustable from 5 to 60 min.
Code 2
Solar/group "4"
(cont.)
5623 520 GB
Service
Page 98
98
Coding in the delivered condition Possible change
The DHW cylinder with­out priority is heated at most for the duration of the set alternate heating time if the DHW cylinder with priority is heated up.
28:3 Alternate pause time
3 min. After the selected alter­nate heating time for the DHW cylinder without pri­ority has expired, the rise in collector temperature is captured during the alter­nate pause time.
28:1 to 28:60
The alternate pause time is adjustable from 1 to 60 min.
Heating circuit 1, heating circuit 2, heating circuit 3/group "5"
Select "Heating circuit ..." for weather-compensated control units (see page 80). Select "5" for constant temperature control units (see page 80).
Coding
Coding in the delivered condition Possible change
A0:0 Without remote control A0:1 With Vitotrol 200A/200RF
(automatic recognition)
A0:2 With Vitotrol 300A/300RF
or Vitohome 300 (automat­ic recognition)
A1:0 All possible settings at
the remote control can be accessed
A1:1 Only party mode can be set
at the remote control (only for Vitotrol 200 and 200 RF)
A2:2 Cylinder priority applica-
ble to heating circuit pump and mixer
A2:0 Without cylinder priority ap-
plied to heating circuit pump and mixer
A2:1 Cylinder priority only appli-
cable to mixer
Code 2
Solar/group "4"
(cont.)
5623 520 GB
Page 99
99
Coding in the delivered condition Possible change
A2:3 to A2:15
Reduced priority applied to mixer (the heating circuit receives a reduced amount of energy)
A3:2 Outside temperature be-
low 1 °C: Heating circuit pump "ON" Outside temperature above 3 °C: Heating cir­cuit pump "OFF"
A3:-9 to A3:15
Heating circuit pump "ON/ OFF" (see following table)
!
Please note
When selecting a value below 1 °C, there is a risk of pipes outside the thermal envelope of the building freezing up. The standby mode in particular should be taken into consideration, e.g. during holidays.
Parameter Heating circuit pump address A3:... "On" "Off"
-9 -10 °C -8 °C
-8 -9 °C -7 °C
-7 -8 °C -6 °C
-6 -7 °C -5 °C
-5 -6 °C -4 °C
-4 -5 °C -3 °C
-3 -4 °C -2 °C
-2 -3 °C -1 °C
-1 -2 °C 0 °C 0 -1 °C 1 °C 1 0 °C 2 °C 2 to
1 °C to
3 °C to
15 14 °C 16 °C
Coding in the delivered condition Possible change
A4:0 With frost protection (only
for weather-compensa­ted control units).
A4:1 No frost protection; this set-
ting is only possible if code "A3:-9" has been selected.
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5623 520 GB
Service
Page 100
100
Coding in the delivered condition Possible change
Note
"Important" observe for code "A3".
A5:5 With heating circuit pump
logic function (economy mode): Heating circuit pump "OFF" when the outside temperature (AT) is 1 K higher than the set room temperature (RT
set
)
AT > RT
set
+ 1 K (only for
weather-compensated control units)
A5:0 Without heating circuit
pump logic function A5:1 to A5:15
With heating circuit pump
logic function: Heating cir-
cuit pump "OFF"; see fol-
lowing table
Parameter address A5:...
With heating circuit pump logic function: Heating cir­cuit pump "OFF"
1 AT > RT
set
+ 5 K
2 AT > RT
set
+ 4 K
3 AT > RT
set
+ 3 K
4 AT > RT
set
+ 2 K
5 AT > RT
set
+ 1 K
6 AT > RT
set
7 to
AT > RT
set
- 1 K
15 AT > RT
set
- 9 K
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5623 520 GB
Loading...