Viessmann TectoCell Compact 80, TectoCell Compact 100 Assembly And Operating Manual

Page 1
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 1 GB Right reserved to make technical changes!
Coldroom TectoCell Compact 80 Coldroom and deep-freezing room TectoCell Compact 100
Assembly and Operating Manual
6026901-02 GB
Page 2
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 2 GB Right reserved to make technical changes!
1. Gerneral notes
1.1 Area of validity
1.2 Extract from the conditions of guarantee
1.3 Supplied condition
1.4 Unpacking and Handling
1.5 Assembly of the coldroom
1.6 Disposing of the coldroom
2. Preliminary work
2.1 Compensation for uneven floor
2.2 Coldrooms with flooring ventilation (Coldroom temperature under - 5°C)
2.3 Coldrooms without flooring ventilation
3. Coldroom assembly
3.1 Connecting the coldroom panels
3.2 Assembly of the flooring panels
3.3 Assembly of the wall panels
3.4 Assembly of the door
3.5 Assembly of the ceiling panels
3.6 Assembly of the door threshold
3.7 Removing transportation securing plates
3.8 Adjusting the hinges
3.9 Door lock fastener
3.10 Mechanical works on the door or the hatch
3.11 Coldroom without flooring panels
3.12 Closing the operational openings of the cam locks in the wall and ceiling panels
4. Electrical connections
5. Miscellaneous
5.1 Replacement of cylinder lock on rotary handle lock
5.2 Emergency release
6. Commissioning
6.1 Commissioning the coldroom
6.2 Permissible loads for flooring panels
6.3 Deactivation
6.4 Cleaning the coldroom
7. Energy saving and storage of refrigerated products
7.1 Notes on energy savings
7.2 Storing refrigerated goods
Table of contents
Page 3
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 3 GB Right reserved to make technical changes!
1. Gerneral notes
1.1 Area of validity
This assembly manual is valid for TectoCell coldrooms with the following surfaces:
- Viessmann Standard white powder coating
- stainless steel flooring
1.2 Extract from the conditions of guarantee
No guarantee is assumed for damage resulting from improper use, improper assembly or operation by the buyer or other parties, natural wear, improper or negligent handling, or chemical/electro chemical influence, insofar as this is not our fault, or resulting from inattention to the assembly, operating and maintenance instructions, improper alterations or maintenance done by the buyer or third parties, or as a result of use of parts supplied by other manufacturers.
Caution!
The ceiling panels are not designed for additional loads (i.e. snow or wind pressure). Prior to accessing on the ceiling or installing a ceiling refrigeration unit, or other elements such as hanging rails, pipes, etc., additional support must be provided during assembly.
Attention!
During installation of the refrigeration unit, it must be ensured that the evaporation ventilator does not blow on the door and on the pressure compensation valve.
1.3 Supplied condition
The TectoCell coldroom and deep-freezing room is supplied in individual packing units. The individual panels are designated by labels or numbers.
Door frame heating and extra socket are installed and prewired in the door frame.
The door is already installed in the door frame.
The accessories for assembly are packed separately.
1.4 Unpacking and Handling
- Prior to and during unpacking a visual check of the panels must be made in order to determine if any damage has occurred during transport.
- Any damage must be noted immediately on the freight papers and these must be sent to Viessmann. Please note „Conditions in case of damage“! As a rule, the „General Condtions for Transport Damage and Hidden Transport Damage” apply.
- Before the packing material is disposed of, ensure that it contains no loose parts are in it.
- In order to process the damage claim properly, we request exact details of the damage (pictures) as well as Type Designation and serial number.
Page 4
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 4 GB Right reserved to make technical changes!
1.5 Assembly of the coldroom
Install the coldroom in a well ventilated room to ensure that the heat produced by the refrigeration unit is properly released and the room is not excessively heated. This will reduce the running time of the refrigeration unit, thus reducing running costs and the wear on the refrigeration unit. The distance of the coldroom to the wall, and the space above the coldroom should be a minimum of 50 mm for coldrooms in above zero applications. For coldrooms in below zero applications the space should be at least 100 mm. Please see the assembly instructions for the required clearance above the cell for a refrigeration unit. The assembly height has to be arise according to the potential prop construction. Before starting to install the device, check the dimensions of the intended place of installation. With this, also the right angularity has to be checked by diagonal measurement.
lt should be ensured that the flooring panels are only installed on even and smooth floors (according German VOB regulations). In case of uneven floors (e.g. cement) the difference must be compensated for using flooring inserts.
Coldrooms and deep freezers operated below -5°C must be placed on flooring plates as protection against freezing. An electrical floor heating can be used instead of floor plating.
Installation outdoor
The Viessmann coldrooms are suitable for installation outdoor - but this must be done under a protective roof. (local construction measures)
lf coldrooms are installed outdoor, discolouring of the paint may occur as a result of UV radiation.
In addition to these assembly instructions, the
applicable national and local rules on work safety must be observed when carrying out assembly work and the proper measures to prevent accidents must be taken!
1.6 Disposing of the coldroom
Any waste materials must be disposed of in
accordance with the local and international laws.
Page 5
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 5 GB Right reserved to make technical changes!
2.1 Compensation for uneven floor
(Please note accompanying coldroom drawing)
Mark shape of coldroom on floor with chalk.
2.2 Coldrooms with flooring ventilation (Coldroom temperature under - 5°C)
The flooring gratings are laid loosely at a distance of 200 to 300 mm from each other. Ensure that the joins (B) and the exterior edges (A) are placed exactly on the flooring gratings. lf there is unevenness in the flooring, the flooring gratings must be adjusted for height. The adjustment for height may be done using damp cement, fast setting adhesives or compensation plating. The adjustment should begin at the highest point.
2.3 Coldrooms without flooring ventilation
In case of uneven or non horizontal flooring, compensate
using floor underlays.
2. Preliminary work
a
a
aa
a
a
aa
a
a
a
a
a
a
a
aa
a
a
aa
a
a
a
a
a
aa
aa
a
a
a
a
aa
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
aa
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
aa
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
aa
a
a
a
a
a
aaa
a
aa
a
a
a
a
aa
a
a
a
a
a
200 - 300 mm
200 - 300 mm
B
A
051-4-0/1
Page 6
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 6 GB Right reserved to make technical changes!
3. Coldroom assembly
Important!
The panels are provided with seal at the plant
- do not damage!
When transporting or moving the elements, do not grasp them by the overlap of the spring side or in their groove. Always hold the elements at the bot tom, to prevent the sheets from coming loose.
All joining work is to be done carefully to prevent any and all penetration by water or contamination.
The individual coldroom elements are labelled. The respec­tive position of each coldroom element can be ascertained by comparing the label on the coldroom, the provided drawing and BOM.
3.1 Connecting the coldroom panels
The coldroom panels are connected using foamed in eccentric cam locks. These are activated from the interior of the coldroom. Prior to assembly check that all the cam locks are open by turning them to the left. The cam locks have a pulling distance of 12 mm. lf the distance between the coldroom panels is greater than 12 mm during assembly, the eccentric locks will not clamp in place. In this case, open the cam locks again and push the panels together, and then clamp the locks shut again.
Page 7
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 7 GB Right reserved to make technical changes!
3.2 Assembly of the flooring panels
Flooring panels with stainless steel covering plate: The flooring panels are equipped with a sealing gasket (R) on
the tongue side at the underlapping point. Ensure that this seal is not damaged.
For flooring panels with one or two sided connections, fill the points marked on the drawing with sealant.
Do not place weight on the panel to be assembled. Push the flooring panels together and tighten the external cam lock on one side. Push the opposite sides together, using a crow bar if necessary, taking care not to damage the part. Using the drill hole (S) provided in the surface of the top section, drill a hole in the end of the plate (T) and rivet the overlapping section.
Drilling lubricants: e.g. Jokisch HDS 400, Chesterton 380
Closing the holes on cam locks (See picture next page). Use PU sealant.
1000 N flooring: Plug ø 15 mm stainless steel
Attention: Using a steel hammer may cfrome rusting.
- pound in with rubber hammer
T
S
R
Page 8
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 8 GB Right reserved to make technical changes!
3.3 Assembly of the wall panels
Clean the interior flooring panel in the area of the interior
wall plating C with isopropanol. Adhere the enclosed sealing gasket (D) to the cleaned edge of the interior flooring plate. Remove the protective foil from the sealing gasket.
Begin the wall assembly with the corner panels. Connect the panels using the cam locks.
3.4 Assembly of the door
The one piece door is supplied complete with the door
frame.
During assembly ensure that the doorframe is installed
perfectly horizontally and vertically (plumb Iine).
3.5 Assembly of the ceiling panels
When installing a wall-hanging unit, it must be hung on the
side section of the door frame or on the wall before installing the ceiling elements. During installation ensure that the evaporator fan does not blow onto the door leaf and the pressure compensation valve.
Place the ceiling panels in position and tighten the cam locks.
Note!
lf the panels are uneven, release the cam locks and adjust
the panels. Tighten all cam locks (wall/ceiling, wall/wall, wall/floor) again.
3.6 Assembly of the door threshold
Place the stainless steel door threshold (G) in the middle of
the door opening and adjust. Drill holes for fastening of the door threshold (ø 3.3 mm)
Do not drill extra holes due to possible heating
cable underneath. Danger to life!
In order to seal the threshold securely against penetrating damp, apply a bead of polyurethane sealant (L) to the front of the door sill at the bottom, on the inside and on the sides.
Place door threshold plate on the flooring panel, adjust and rivet in place using enclosed rivets.
Seal the threshold with PU sealant on the sides of the door opening and to the floor.
Smooth off excessive sealant.
D
C
Montage Wand - Ceiling
Montage Türschwelle
Page 9
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 9 GB Right reserved to make technical changes!
3.7 Removing transportation securing plates
The magnetic gasket seal on the door is protected from
mechanical damage by means of the securing plates (M). Prior to adjusting the door and/or activation of the coldroom, these must be removed.
3.8 Adjusting the hinges
Important!
lf the magnetic gasket profile does not fit properly around the whole periphery of the door and the sealing profile does not lie flush on the threshold or the flooring on the inside, deviations can be adjusted for in three ways on the door hinges.
Remove covering caps (N) from the door hinges. Open the
door and insert a nail, a small screwdriver or something (M) similar diagonally into the opening (K) with the cap in order to release the cap locking.
After releasing the screw (P) or (R), the door can be adjusted horizontally or depthwise.
For vertical adjustment, turn the screws of the rising hinges (T) so that the door reaches the wanted height (see image).
The non-rising hinge can be mounted on the left or on the right side. It has the same screw (T) at the top and at the bottom. For vertical adjustment, turn the screw (T) so that the door is in the wanted height. For that, first release the upper screw (T) and then adjust the hinge turning the lower screw (T). Finally, fasten the upper screw (T) so that the hinge can still be moved easily.
3.9 Door lock fastener
The door lock fastener (V) of the hairpin lock has been
factory-fitted at the plant. After assembly and adjustment of the door, the fit of the lock behind the door lock fastener should be tested. lf adjustment is necessary, loosen screws (U), and insert support (W) if necessary, adjust door lock fastener and tighten screws again.
Check that see if the door has a tight seal. After that, drill holes with a 3.7 mm drill and fix the fastener additionally with the screws provided (X).
M
P
U
N
R
P
M
K
M
N
R
T
K
W
X
U
V
Page 10
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 10 GB Right reserved to make technical changes!
3.10 Mechanical works on the door or the hatch
Important!
For door and view hatch panels, mechanical work in the marked area (e.g. drilling, sawing) is prohibited. This applies both for the exterior and for the interior. Electrical components have been foamed in here. Danger to life may result from damaging the integrated electrical wires!
3.11 Coldroom without flooring panels
The wall panels are placed in plastic U-channels which are screwed onto the floor of the room in which the coldroom is assembled. These are constructed such that they form a seal with the floor of the building. During assembly the wall panels are either riveted to the U channels or screwed onto them.
Caution!
To avoid damage to the floor of the building, ensure prior to drilling in the floor that the cement coating does not contain an damp proof layer which might be damaged. In addition, the drill holes must be placed such that they are not under the cam locks of the panels.
The door panel without flooring is supplied with transport securing plates and without door frame heating. Remove transport securing plates for assembly of the door.
3.12 Closing the operational openings of the cam locks in the wall and ceiling panels
Fill the openings with the insulating foam fillers supplied (D)
and seal with plastic plugs (E).
12 mm
a
a
a
a
a
D
E
Page 11
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 11 GB Right reserved to make technical changes!
4. Electrical connections
Attention!
Work on the electrical network and protective measures (FI-safety switch) is to be done by a specialist electrician according to the current regulations (EN, ISO, VDE...) and conditions of the local energy supply company.
The specialist electrical installation company will ensure professional installation and is responsible for checking the operation and the safety of the sytem.
The electrical work must be done by a qualified electrician!
In the lead going into the electrical distributor, there is a
facility to ensure that all non grounded leads are separated from the electrical power supply by at least 3 mm (plug or 2 pole switch).
The lead type of at least H05VV-F3G1,5 or NYM-J 3x1.5 must be used as long as no additional requirements for a higher type exist.
Check that the cross section of the lead to the power supply is secured.
Design is according to the Standard Door Panel Protective Class II.
Attention!
While preparing of the connection to the power supply, it must be ensured that the power supply is switched off and secured against switching on!
Push the lead through the coldroom ceiling. Protect from
sharp edges. Remove cover of distributor cap. Open the distributor‘s lead-through opening and insert enclosed grommet. Insert the power supply lead into the grommet and secure to L1, N and PE in the distributor. Connect to power supply.
The power lead must be firmly installed in the area of the coldroom.
Seal the grommet in the distributor box and the lid through-put opening with cold-setting putty.
Switch on the power supply and check the working of the working of the electrical system.
Note!
If the temperature drops and reaches a level of approx. 0°C, the thermal actuator in the distributor box of heated doors switches on the window and valve heating and switches this off again if the temperature rises and reaches approx. 7°C. The hysteresis range and the tolerance of the thermal actuator must be taken into account here.
If the junction box is located on the warm side, the
small thermostat will not switch the heating on. In this case, the heating must be connected directly without the small thermostat. If the system is shut down or for coldroom operation in the positive range, the heating must be disconnected.
Standflügelheizung
Fensterheizung Standflügel
Fensterheizung Gehflügel
zusätzl. DA-Ventil
Schwellenheizung
00048841-04
Bedientableau
Netzanschluß 230 V AC 50 Hz - bauseits
Schalter (2-polig) mit Leuchtmelder für Kühlzellen­beleuchtung
Abzweig­dose
Türrahmen­heizung (optional)
Netzanschluß 230V AC über mehrpoligen Stecker
Türkontakt­schalter (optional)
Kühlzellen­beleuchtung (optional)
4
N
Druckaus­gleichsventil mit Beheizung (optional)
3
N
L1
BK3
BK2
BK1
2
3
1
L1
N
N
3
Thermostat L1-4 nur bei Heizung
T
N
3
1
2
4
L1
BK1
BK2
BK3
BK4
BK5
5
6
N N
L1L1
PE PE
GNYE
PE
PE
Wiring diagram, coldroom door
Page 12
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 12 GB Right reserved to make technical changes!
5. Miscellaneous
5.1 Replacement of cylinder lock on rotary handle lock
Unscrew the stud bolt (K) from the side of the outside handle
using a 2.5 mm hexagon key (L).
Insert key (H) into the cylinder (F), turn to the horizontal position with ¼ turn and remove cylinder lock with key.
Install in reverse sequence.
The key no. (G) is embossed at the front of the cylinder.
5.2 Emergency release
Check function of rotary handle lock, cylinder lock and
emergency opening while the door is open.
The revolving doors can be opened with the emergency opener from the inside while the door is locked.
The door lock remains thereby in the locked condition.
Check the emergency opener regularly.
L
K
G
F
H
Page 13
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 13 GB Right reserved to make technical changes!
6.1 Commissioning the coldroom
- only for the intended or agreed purpse
After assembly, clean and ventilate the coldroom.
(See section „Cleaning the Coldroom“).
The coldroom is ready to operate. The refrigeration unit can be activated according to the separate Operating Manual.
Allow the temperature in the coldroom to reach the desired value. Place refrigerated goods in the coldroom only when this value has been reached.
Have the pressure compensation valve checked by a refri geration specialist. Do not exceed the allowed pressure differential in the coldroom of 100 Pa (1 mbar). Check the function of the pressure compensation valve regularly. The opening of the valve must not be blocked internally or externally (e.g. by refrigerated goods).
6.2 Permissible loads for flooring panels
Wheel load N Wheel load N Wheel load > 1 cm2 > 4 cm2 in N/m
2
hard rubber wheel bakery wheel
1. 250 1000 30.000
6.3 Deactivation
When the coldroom is to be deactivated for a long period,
the power supply plug must be disconnected or the power supply must be switched off. Provide sufficient ventilation!
6.4 Cleaning the coldroom
During cleaning the refrigeration unit and the coldroom should be cut off from the power supply.
Remove the plug from the power supply during such
work and secure against the plug being reinserted, or switch off the power supply at source and secure against switching on.
Elements with powder-coated steel plate surfaces or stainless steel surfaces: do not spray water onto walls, ceilings, elements with electrical components (e.g. door frame) or the refrigeration units inside or outside. Wipe out the inside of the coldroom, dry well and allow ventilation. Do not use scouring agents or cleaning agents containing solvents. Wipe the outside of the coldroom with a damp cloth.
Standard floor:
Only wipe with a moist cloth Not suited for stagnant water or jet water!
Wash the door seals regularly with soapy water and wipe dry. Do not clean the seals with Aceton or solventcontaining detergent.
The walls, shelves, containers and packing materials can be washed off with potassium sorbate solution (1 tablespoon of potassium sorbate dissolved in
0.1 litre of water. Potassium sorbate is produced by Merck and available at the local chemist‘s.) Wipe the walls, shelves, etc., with a linen towel dampened by the solution. The solution should dry onto the parts cleaned, leaving a light coat of residue.
The stainless steel coldroom flooring can be treated with normal stainless steel cleaners (e.g. ETOLIT, Fa. Viessmann). Seal the stainless steel surface with an appropriate material for stainless steel (e.g. Chromadur, Fa. Assindia-Chemie or Inox Top, Fa. Viessmann).
Pay attention to the product information!
6. Commissioning
Page 14
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 14 GB Right reserved to make technical changes!
7.1 Notes on energy savings
Do not install coldrooms or refrigeration units near heating
sources; if the ambient temperature is too high, this will cfrome the refrigeration unit to run to activate too often.
- Direct radiation from the sun will increase power use.
- Allow warm food to cool down to room temperature before placing it the coldroom.
- Avoid keeping the door open for longer than necessary.
- Monitor temperature of storage
Caution!
Do not store substances with aggressive vapours (marinades, vinegar, etc.) in open containers, but rather in closed or covered containers.
7. Energy saving and storage of refrigerated products
7.2 Storing refrigerated goods
When the desired temperature of storage is achieved
in the coldroom, the refrigerated goods can be brought in. After this, the temperature in the coldroom should be checked again, and corrections in the regulation of the refrigeration unit made, if required.
Page 15
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 15 GB Right reserved to make technical changes!
Page 16
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 16 GB Right reserved to make technical changes!
Latvia Viessmann Refrigeration Systems Latvia fi liále Telephone +371 6782 8449 info.lv@viessmann.com
www.viessmann.com
Netherlands Viessmann Nederland B.V. Telephone +31 10 45844 44 info-ref-nl@viessmann.com
www.viessmann.nl
Norway Viessmann Refrigeration Systems AS Telephone +47 3336 3500 post@viessmann.no
www.viessmann.no
Poland Viessmann Systemy Chłodnicze Sp. z o.o. Telephone +48 22 882 0020 info.pl@viessmann.com
www.viessmann.pl
Russia Viessmann Group – Refrigeration Systems Moscow, St. Petersburg Telephone +7 499 277 1260
www.viessmann.ru
Slovakia Viessmann, s.r.o. Telephone +421 32 23 01 00 viessmann@viessmann.sk
www.viessmann.sk
Sweden Viessmann Refrigeration Systems AB Telephone +46 8 5941 1200 info.refrigeration@viessmann.se
www.viessmann.se
Switzerland Viessmann (Schweiz) AG Telephone +41 56 418 67 11 info@viessmann.ch
www.viessmann.ch
United Arabian Emirates Viessmann Middle East FZE Telephone +971 43724247 refrigeration@viessmann.ae
www.viessmann.ae
United Kingdom Viessmann Refrigeration Systems Limited Telephone +44 1952 457157 sales@viessmann-coldtech.co.uk
www.viessmann.co.uk
Austria Viessmann Kühlsysteme Austria GmbH Telephone +43 72 35 66367- 0 o ce_vk_at@viessmann.com
www.viessmann.at
Belgium Viessmann Nederland B.V. Telephone +31 10 45844 44 info-ref-be@viessmann.com
www.viessmann.be
Czech Republic Viessmann, spol. s r.o. Telephone + 420 257 090 900 viessmann@viessmann.cz
www.viessmann.cz
Denmark Viessmann Refrigeration Systems ApS Telephone +45 4120 5420 info.dk@viessmann.com
www.viessmann.dk
Estonia Viessmann Külmasüsteemid OÜ Telephone +372 675 5150 info.ee@viessmann.com
www.viessmann.ee
Finland Viessmann Refrigeration Systems Oy Telephone +358 19 537 8000 info.fi @viessmann.com
www.viessmann.com
Viessmann Kylmäjärjestelmät Oy Telephone +358 19 537 8000 info.fi @viessmann.com
www.viessmann.fi
France Viessmann Technique du Froid S.à.r.l. Telephone +33 3 87 13 08 13 france@viessmann-refrigeration.com
www.viessmann.fr
Germany Viessmann Kühlsysteme GmbH, Hof Telephone +49 9281 814- 0 Viessmann Kühlsysteme GmbH, Mainz Telephone +49 61315 7046-17 kuehlsysteme@viessmann.de
www.viessmann.de
Ireland Viessmann Refrigeration Systems Limited Telephone +353 1 617 7930 sales@viessmann-coldtech.ie
www.viessmann-coldtech.ie
Loading...