Viessmann TectoCell Compact 80, TectoCell Compact 100 Assembly And Operating Manual

GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 1 GB Right reserved to make technical changes!
Coldroom TectoCell Compact 80 Coldroom and deep-freezing room TectoCell Compact 100
Assembly and Operating Manual
6026901-02 GB
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 2 GB Right reserved to make technical changes!
1. Gerneral notes
1.1 Area of validity
1.2 Extract from the conditions of guarantee
1.3 Supplied condition
1.4 Unpacking and Handling
1.5 Assembly of the coldroom
1.6 Disposing of the coldroom
2. Preliminary work
2.1 Compensation for uneven floor
2.2 Coldrooms with flooring ventilation (Coldroom temperature under - 5°C)
2.3 Coldrooms without flooring ventilation
3. Coldroom assembly
3.1 Connecting the coldroom panels
3.2 Assembly of the flooring panels
3.3 Assembly of the wall panels
3.4 Assembly of the door
3.5 Assembly of the ceiling panels
3.6 Assembly of the door threshold
3.7 Removing transportation securing plates
3.8 Adjusting the hinges
3.9 Door lock fastener
3.10 Mechanical works on the door or the hatch
3.11 Coldroom without flooring panels
3.12 Closing the operational openings of the cam locks in the wall and ceiling panels
4. Electrical connections
5. Miscellaneous
5.1 Replacement of cylinder lock on rotary handle lock
5.2 Emergency release
6. Commissioning
6.1 Commissioning the coldroom
6.2 Permissible loads for flooring panels
6.3 Deactivation
6.4 Cleaning the coldroom
7. Energy saving and storage of refrigerated products
7.1 Notes on energy savings
7.2 Storing refrigerated goods
Table of contents
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 3 GB Right reserved to make technical changes!
1. Gerneral notes
1.1 Area of validity
This assembly manual is valid for TectoCell coldrooms with the following surfaces:
- Viessmann Standard white powder coating
- stainless steel flooring
1.2 Extract from the conditions of guarantee
No guarantee is assumed for damage resulting from improper use, improper assembly or operation by the buyer or other parties, natural wear, improper or negligent handling, or chemical/electro chemical influence, insofar as this is not our fault, or resulting from inattention to the assembly, operating and maintenance instructions, improper alterations or maintenance done by the buyer or third parties, or as a result of use of parts supplied by other manufacturers.
Caution!
The ceiling panels are not designed for additional loads (i.e. snow or wind pressure). Prior to accessing on the ceiling or installing a ceiling refrigeration unit, or other elements such as hanging rails, pipes, etc., additional support must be provided during assembly.
Attention!
During installation of the refrigeration unit, it must be ensured that the evaporation ventilator does not blow on the door and on the pressure compensation valve.
1.3 Supplied condition
The TectoCell coldroom and deep-freezing room is supplied in individual packing units. The individual panels are designated by labels or numbers.
Door frame heating and extra socket are installed and prewired in the door frame.
The door is already installed in the door frame.
The accessories for assembly are packed separately.
1.4 Unpacking and Handling
- Prior to and during unpacking a visual check of the panels must be made in order to determine if any damage has occurred during transport.
- Any damage must be noted immediately on the freight papers and these must be sent to Viessmann. Please note „Conditions in case of damage“! As a rule, the „General Condtions for Transport Damage and Hidden Transport Damage” apply.
- Before the packing material is disposed of, ensure that it contains no loose parts are in it.
- In order to process the damage claim properly, we request exact details of the damage (pictures) as well as Type Designation and serial number.
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 4 GB Right reserved to make technical changes!
1.5 Assembly of the coldroom
Install the coldroom in a well ventilated room to ensure that the heat produced by the refrigeration unit is properly released and the room is not excessively heated. This will reduce the running time of the refrigeration unit, thus reducing running costs and the wear on the refrigeration unit. The distance of the coldroom to the wall, and the space above the coldroom should be a minimum of 50 mm for coldrooms in above zero applications. For coldrooms in below zero applications the space should be at least 100 mm. Please see the assembly instructions for the required clearance above the cell for a refrigeration unit. The assembly height has to be arise according to the potential prop construction. Before starting to install the device, check the dimensions of the intended place of installation. With this, also the right angularity has to be checked by diagonal measurement.
lt should be ensured that the flooring panels are only installed on even and smooth floors (according German VOB regulations). In case of uneven floors (e.g. cement) the difference must be compensated for using flooring inserts.
Coldrooms and deep freezers operated below -5°C must be placed on flooring plates as protection against freezing. An electrical floor heating can be used instead of floor plating.
Installation outdoor
The Viessmann coldrooms are suitable for installation outdoor - but this must be done under a protective roof. (local construction measures)
lf coldrooms are installed outdoor, discolouring of the paint may occur as a result of UV radiation.
In addition to these assembly instructions, the
applicable national and local rules on work safety must be observed when carrying out assembly work and the proper measures to prevent accidents must be taken!
1.6 Disposing of the coldroom
Any waste materials must be disposed of in
accordance with the local and international laws.
GB
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or regarding a certain purpose always require a special written agreement.
Page 5 GB Right reserved to make technical changes!
2.1 Compensation for uneven floor
(Please note accompanying coldroom drawing)
Mark shape of coldroom on floor with chalk.
2.2 Coldrooms with flooring ventilation (Coldroom temperature under - 5°C)
The flooring gratings are laid loosely at a distance of 200 to 300 mm from each other. Ensure that the joins (B) and the exterior edges (A) are placed exactly on the flooring gratings. lf there is unevenness in the flooring, the flooring gratings must be adjusted for height. The adjustment for height may be done using damp cement, fast setting adhesives or compensation plating. The adjustment should begin at the highest point.
2.3 Coldrooms without flooring ventilation
In case of uneven or non horizontal flooring, compensate
using floor underlays.
2. Preliminary work
a
a
aa
a
a
aa
a
a
a
a
a
a
a
aa
a
a
aa
a
a
a
a
a
aa
aa
a
a
a
a
aa
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
aa
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
aa
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
aa
a
a
a
a
a
aaa
a
aa
a
a
a
a
aa
a
a
a
a
a
200 - 300 mm
200 - 300 mm
B
A
051-4-0/1
Loading...
+ 11 hidden pages