Viessmann OpenTherm Operating Instructions Manual

Page 1

Operating instructions

for the system user
OpenTherm room temperature controller with digital time switch For Vitodens 100-W, 111-W and 050-W
VIESMANN

Room temperature controller

5837779 GB 12/2018
Please keep safe.
Page 2

Safety instructions

For your safety
Please follow these safety instructions closely to prevent accidents and material losses.
Safety instructions explained
Danger
This symbol warns against the risk of injury.
Please note
This symbol warns against the
!
risk of material losses and envi­ronmental pollution.
Target group
These operating instructions are designed for heating system users. This appliance can also be operated by children 8 years and older, as well as by individuals with reduced physical, sensory or mental faculties or those lacking in experience and knowledge, provided such individuals are being supervised or have been instructed in the safe use of this appliance and any risks arising from it.
Connecting the appliance
■ Connection and commissioning of the appliance may only be carried out by authorised contractors.
■ Only operate the appliance with suit­able fuels.
■ Adhere to the electrical connection requirements.
■ Modifications to the existing installa­tion may only be carried out by authorised contractors.
Note
Details identified by the word "Note" contain additional information.
Please note
Supervise children in the prox-
!
imity of the appliance.
■ Never permit children to play with the appliance.
■ Cleaning and maintenance must not be carried out by unsupervised children.
Danger
Incorrectly executed work on the heating system can lead to life threatening accidents.
■ Work on gas installations must only be carried out by a regis­tered gas fitter.
■ Work on electrical equipment must only be carried out by a qualified electrician.
5837779
Page 3
Safety instructions
For your safety
Working on the appliance
■ When adjusting settings and carrying out work on the appliance always fol­low the guidelines in these operating instructions. Additional work on the appliance may only be carried out by authorised contractors.
■ Never open the appliance.
■ Never remove the cladding.
Damage to the appliance
Danger
Damaged equipment poses a safety hazard.
If you smell gas
Danger
Escaping gas can lead to explo­sions which may result in seri­ous injury.
■ Do not smoke. Prevent naked flames and sparks. Do not switch lights or electrical appli­ances on or off.
■ Close the gas shut-off valve.
■ Open windows and doors.
(cont.)
■ Never remove or change additional parts or installed accessories.
■ Never open or retighten pipe connec­tions.
Danger
Hot surfaces can cause burns.
■ Never open the appliance.
■ Never touch the hot surfaces of uninsulated pipes, fittings or flue pipes.
Check the appliance for external damage. Never start up a dam­aged appliance.
■ Evacuate any people from the danger zone.
■ Notify your gas and power supply utility and your local heating contractor from out­side the building.
■ Have the power supply to the building shut off from a safe place (outside the building).
5837779
Page 4
Safety instructions
For your safety
If you smell flue gas
Danger
Flue gas can lead to life threat­ening poisoning.
■ Shut down the heating sys­tem.
■ Ventilate the installation site.
■ Close all doors in the living space.
In case of fire
Danger
Fire presents a risk of burns and explosion.
What to do if water escapes from the appliance
(cont.)
Emergency contact
If you smell gas or detect a gas leak call the National Gas Emergency serv­ice on 0800 111 999. Notify your gas or electricity supplier and your heating contractor.
■ Shut off the electricity supply to the building from a safe place (outside the building).
■ Shut down the heating sys­tem.
■ Close the shut-off valves in the fuel supply lines.
■ Use a tested fire extinguisher, class ABC.
Danger
If water escapes from the appli­ance there is a risk of electrocu­tion.
What to do if the heating system develops a fault
Danger
Fault messages indicate faults in the heating system. If faults are not rectified, they can have life threatening consequences.
■ Switch OFF the heating sys­tem at the external isolator (e.g. fuse box, domestic distri­bution board).
■ Notify heating contractor.
Do not acknowledge fault mes­sages several times in quick succession. Inform your heating contractor so the cause can be analysed and the fault rectified.
5837779
Page 5
Safety instructions
For your safety
Installation room requirements
Danger
Sealed vents result in a lack of combustion air. This leads to incomplete combustion and the formation of life threatening car­bon monoxide. Never cover or close existing vents. Do not make any subsequent modifications to the building characteristics that could affect safe operation (e.g. cable/pipe­work routing, cladding or parti­tions).
Danger
Easily flammable liquids and materials (e.g. petrol, solvents, cleaning agents, paints or paper) can cause deflagration and fire. Never store or use such materi­als in the boiler room or in direct proximity to the heating system.
(cont.)
Please note
Incorrect ambient conditions can
!
lead to heating system damage and can put safe operation at risk.
■ Ensure ambient temperatures are above 0 °C and below 35 °C.
■ Prevent air contamination by halogenated hydrocarbons (e.g. as contained in paints, solvents or cleaning fluids) and excessive dust (e.g. through grinding/polishing work).
■ Avoid continuously high humidity levels (e.g. through continuous drying of washing).
Extractors
The operation of appliances that extract air to the outside (cooker hoods, extrac­tors, air conditioning units, etc.) can create negative pressure. If the boiler is operated at the same time, this can lead to reverse flow of the flue gas.
5837779
Danger
The simultaneous operation of the boiler and appliances that extract air to the outside can result in life threatening poison­ing due to reverse flow of the flue gas. Take suitable steps to ensure an adequate supply of combustion air. If necessary, contact your contractor.
Page 6
Safety instructions
For your safety
Auxiliary components, spare and wearing parts
Please note
Components not tested with the
!
heating system may damage the system or affect its function.
(cont.)
Only allow qualified contractors to carry out installation or replacement work.
5837779
Page 7

Index

Index
Information
Symbols................................................................................................................ 9
Intended use......................................................................................................... 10
Introductory information
Control unit function modes.................................................................................. 11
Where to find the controls
Summary of controls and indicators..................................................................... 12
■ Controls and display elements.......................................................................... 12
■ Symbols on the display..................................................................................... 13
Commissioning
Heating system operating mode........................................................................... 15
Time program or operating mode......................................................................... 16
■ Selecting the time program or operating mode................................................. 16
■ Preset time programs........................................................................................ 16
■ Constant operating modes................................................................................ 17
■ Changing the selected time program and set temperatures............................. 18
Central heating
Selecting the operating mode............................................................................... 20
Temporarily changing the room temperature........................................................ 20
■ Temporarily changing the set room temperature.............................................. 20
■ Comfort mode................................................................................................... 20
■ Reduced mode.................................................................................................. 21
Permanently changing the room temperature...................................................... 21
■ Changing the heating curve for weather-compensated operation.................... 22
Changing the room temperature for a few days (holiday mode).......................... 24
■ Stopping or interrupting the holiday program.................................................... 25
DHW heating
Setting the time program and DHW temperature................................................. 26
■ Changing or deleting switching times............................................................... 26
■ Temporarily changing the DHW temperature.................................................... 26
Further adjustments
Time and date...................................................................................................... 27
Summer/wintertime.............................................................................................. 27
Further settings.................................................................................................... 27
Setting the language............................................................................................ 28
Changing the default display................................................................................ 28
Setting the contrast.............................................................................................. 29
5837779
Page 8
Index
(cont.)
Index
Locking out controls (key lock)............................................................................. 29
■ Temporarily interrupting or unlocking key lock.................................................. 29
Changing the display format of fault messages................................................... 29
Returning all settings to their delivered condition................................................. 29
Checks
Checking information............................................................................................ 30
What to do if...
Rooms are too cold.............................................................................................. 31
Rooms are too hot................................................................................................ 31
Carrying out a reset.............................................................................................. 32
Maintenance
Cleaning............................................................................................................... 33
Appendix
Menu structure in setting mode (MODE).............................................................. 34
Menu structure in settings.................................................................................... 34
Keyword index.................................................................................................... 36
5837779
Page 9
1.

Symbols

Information

Sym­bol
Meaning
Reference to other document containing further information
Step in a diagram: The numbers correspond to the order in which the steps are carried out.
Warning of material losses and environmental pollution
Live electrical area
Pay particular attention.
■ Component must audibly click into place. or
■ Acoustic signal
■ Fit new component. or
■ In conjunction with a tool: Clean the surface.
Dispose of component correct­ly.
Dispose of component at a suitable collection point. Do not dispose of component in domestic waste.
5837779
Page 10
Information

Intended use

The appliance is intended solely for installation and operation in sealed unvented heating systems that comply with EN 12828, with due attention paid to the associated installation, service and operating instructions. It is only designed for heating up heating water that is of potable water quality.
Intended use presupposes that a fixed installation in conjunction with permissi­ble, system-specific components has been carried out.
Commercial or industrial usage for a purpose other than heating the building or DHW shall be deemed inappropriate.
Any usage beyond this must be approved by the manufacturer in each individual case.
Incorrect usage or operation of the appliance (e.g. the appliance being opened by the system user) is prohibi­ted and will result in an exclusion of lia­bility. Incorrect usage also occurs if the components in the heating system are modified from their intended use (e.g. if the flue gas and ventilation air paths are sealed).
10
5837779
Page 11

Control unit function modes

Introductory information

Your heating contractor set the function mode during commissioning.
Two function modes are possible:
■ Room temperature-dependent opera­tion: If no outside temperature sensor and no heating circuit with mixer is connected, function mode "ROOM- CONTROL" must be selected.
■ Weather-compensated operation: If an outside temperature sensor and a heating circuit with mixer are connec­ted, function mode "OT CONTROL" must be selected.
The settings you can make vary depending on the function mode selec­ted.
Note
DHW heating is active continuously or in accordance with the set switching times, regardless of the function mode set.
Function mode set by the heating contractor
"ROOM-CONTROL" (room tem-
=
perature-dependent operation) "OT CONTROL" (weather-com-
=
pensated operation)
Note
You will have to select the function mode again following a reset.
5837779
11
Page 12
08:26
21 3
A B
D C
ROOM TEMP
MODE PARTY ECO INFO
°
c

Where to find the controls

Summary of controls and indicators

Controls and display elements

Display
A
Rotary selector for changing the
B
temperature/value
12
Keys
C
Reset (see page 32)
D
5837779
Page 13
AK
H
B C
E
F
G
08:26
21 3
ROOM TEMP
MODE PARTY ECO INFO
°
c
D
A B C
ESC OK
Where to find the controls
Summary of controls and indicators

Symbols on the display

These symbols are not always dis­played, but appear subject to operating conditions.
Time
A
Text line
B
Temperature display
C
Weather-compensated mode
D
Operating display
E
F G H K
(cont.)
Function display Keys Weekday Time program (set switching times)
Controls
Step back in the menu/exit menu
A
(Esc)
5837779
13
Page 14
08:26
°
C
21 3
Where to find the controls
Summary of controls and indicators
+/-: Change value
B
/ : Scroll through menu
Confirm selection
C
Save value
Default display
When idle, the screen always shows the room temperature, time and (sub­ject to settings) selected time phases as the default display. Press INFO to access control mode.
Information on operation
You can perform most setting and selection procedures using the +/- keys or the rotary selector. The following only describes how to control the device using the keys.
(cont.)
14
5837779
Page 15

Heating system operating mode

Depending on the installation and set­tings, your heating system is either room temperature-dependent or weather-compensated in conjunction with an outside temperature sensor.
■ In room temperature-dependent mode, the set room temperature is controlled via the flow temperature.
■ In weather-compensated mode with room influence, the set room temperature is controlled via the selected heating curve and room influence factor. The room influence factor can be set by your local heat­ing contractor.
■ In weather-compensated mode without room influence, the room temperature is controlled via thermo­static valves. At the temperature lev­els Comfort 1 to 3 and Party, the flow temperature is controlled according to the selected heating curve. In reduced mode (setback mode and eco mode), the flow temperature is reduced by a parallel shift of the heating curve. The setting of the heating curve and the height of the parallel shift can be changed by your heating contractor.

Commissioning

Note
In weather-compensated mode with­out room influence, choosing temper­ature levels Comfort 1 to 3 or Party does not result in different room tem­peratures.
5837779
15
Page 16
Commissioning

Time program or operating mode

You can choose between 3 preset time programs (P1 to P3) or select a perma­nent operating mode. You can change the switching times of the time pro­grams individually. See page 18.
For each time phase, you can choose between the following preselected set room temperatures (temperature level):
"COMFORT 1"
"COMFORT 2"
"COMFORT 3"
"REDUCED TEMP"
"FROST PROTECTION"
See page 18 for how to permanently change the set room temperatures.
If your room temperature controller acts on 2 heating circuits:
The set time program affects both heat­ing circuits.

Selecting the time program or operating mode

Press the following keys:
1. Press INFO.
2. Press MODE.
3. Select the required time program
with / . In the delivered condition, time pro­gram P1 is set.
4. OK to confirm

Preset time programs

Time program P1
Central heating in accordance with the following time program:
Monday to Friday
■ 06:00 to 22:00 h: Central heating with standard room temperature (Comfort 1)
■ 22:00 to 06:00 h: Central heating with reduced room temperature
Saturday and Sunday
■ 07:00 to 23:00 h: Central heating with standard room temperature (Comfort 1)
■ 23:00 to 07:00 h: Central heating with reduced room temperature
Time program P2
Central heating in accordance with the following time program:
16
5837779
Page 17
Commissioning
Time program or operating mode
Monday to Friday
■ 06:00 to 08:00 h and 16:00 to 22:00 h: Central heating with standard room temperature (Comfort 1)
■ 08:00 to 16:00 h and 22:00 to 06:00 h: Central heating with reduced room temperature
Saturday and Sunday
■ 07:00 to 23:00 h: Central heating with standard room temperature (Comfort 1)
■ 23:00 to 07:00 h: Central heating with reduced room temperature

Constant operating modes

You can set the following operating modes:
"PERM COMFORT": Continuous operation with standard room temper­ature
"PERM REDUCED": Continuous operation with reduced room temper­ature
"FROST PROTECTION":
(cont.)
Time program P3
Central heating in accordance with the following time program:
Monday to Friday
■ 12:00 to 20:00 h: Central heating with standard room temperature (Comfort 1)
■ 20:00 to 12:00 h: Central heating with reduced room temperature
Saturday and Sunday
■ 07:00 to 22:00 h: Central heating with standard room temperature (Comfort 1)
■ 22:00 to 07:00 h: Central heating with reduced room temperature
Frost protection mode: – For room temperature-dependent
operation: At room temperatures below + 6 °C.
– For weather-compensated opera-
tion: At outside temperatures below + 3 °C.
5837779
17
Page 18
Commissioning
Time program or operating mode
(cont.)

Changing the selected time program and set temperatures

You can set the following days and groups of days:
■ Entire week (1 to 7)
■ Monday to Friday (1 to 5)
■ Saturday and Sunday (6 and 7)
■ Individual days (1, 2, 3, ...7)
Changing existing time phases
Press the following keys:
01. INFO
02. MODE
03.
Select "SETTINGS" with / .
04. OK to confirm
05. Select "PROGRAMMING" with
/ .
06. OK to confirm
07. Select the required program with
/ .
12. OK to confirm
13. +/- for the required temperature
level (e.g. Comfort 1)
14. OK to confirm
15. +/- for hour (start time)
16. OK to confirm
17. +/- for minute (start time)
18. OK to confirm
19. OK to change further switching
times.
ESC to exit programming.
Creating new time phases
Press the following keys:
01. INFO
02. MODE
08. OK to confirm
09. EDIT, "CHANGE" appears.
10. OK to confirm, to change the
switching time. Days flash.
/ for "CLEAR" and OK, to
delete the switching time.
11. +/- for the required group of days or single day
18
03.
Select "SETTINGS" with / .
04. OK to confirm
05. Select "PROGRAMMING" with
/ .
06. OK to confirm
07. Select the required program with
/ .
08. OK to confirm
5837779
Page 19
Commissioning
Time program or operating mode
09. NEW
Days flash.
10. +/- for the required group of days or single day
11. OK to confirm
12. +/- for the required temperature
level (e.g. Comfort 1)
13. OK to confirm
14. +/- for hour (start time)
15. OK to confirm
16. +/- for minute (start time)
17. OK to confirm
18. OK to change further switching
times.
ESC to exit programming.
(cont.)
07. Select the required program with
/ .
08. OK to confirm
09. Press NEXT to call up the set
switching times one after another.
10. ESC to exit programming.
Deleting the time program
Press the following keys:
01. INFO
02. MODE
03.
Select "SETTINGS" with / .
04. OK to confirm
05. Select "PROGRAMMING" with
/ .
Calling up switching times
Press the following keys:
01. INFO
02. MODE
03.
Select "SETTINGS" with / .
04. OK to confirm
05. Select "PROGRAMMING" with
/ .
06. OK to confirm
5837779
06. OK to confirm
07. Select the required program with
/ "CLEAR P...".
08. OK to confirm
09.
Select "CLEAR PROG" with / .
10. OK to confirm
Confirm appears.
11. OK to confirm
12. ESC to exit programming.
19
Page 20

Central heating

Selecting the operating mode

You can choose between the following time programs and operating modes:
"P 1" to "P 3" Alternating operation with standard and reduced room temperature according to the set switching times.
"PERM COMFORT" Continuous comfort mode
"PERM REDUCED" Continuous reduced mode
"FROST PROTECTION" Continuous frost protection mode
See page 16 for how to select the oper­ating mode.

Temporarily changing the room temperature

Temporarily changing the set room temperature

You can change the room temperature for a short time, regardless of the selec­ted operating program. The change remains in force until the next operating program changeover.
1. Press INFO to access control mode.
2. ■ Room temperature-dependent mode or weather-compensated mode with room influence: Use the rotary selector to set the required increase or decrease in the set room temperature in °C.
■ Weather-compensated mode without room influence: Use the rotary selector to set a value from -5 to +5 for the required increase or decrease in the flow temperature. Value 1 means increasing or decreasing the flow temperature by 5 °C. This temporarily changes the room temperature.

Comfort mode

In comfort mode, the room temperature is regulated to a preselected set value (delivered condition: 23 °C). You can change the preselected set value. The setting remains in force until the next operating program changeover.
1. Press INFO to access control mode.
20
2. Press PARTY. The selected set
room temperature appears.
3. Use the rotary selector to set the required increase or reduction of the set room temperature. PARTY is displayed.
5837779
Page 21
Central heating
Temporarily changing the room temperature
Ending comfort mode early
1. Press PARTY. "PARTY OFF"
appears.
2. Press OK to end comfort mode.

Reduced mode

In reduced mode, the room tempera­ture is regulated to a preselected set value (delivered condition: 17 °C). You can change the preselected set value. The setting remains in force until the next operating program changeover.
1. Press INFO to access control mode.
2. Press ECO. The selected set room temperature appears.
3. Use the rotary selector to set the required increase or reduction of the set room temperature.
Ending reduced mode early
1. Press ECO. "ECO OFF" appears.
2. Press OK to end reduced mode.

Permanently changing the room temperature

(cont.)
You can permanently change the fol­lowing preselected set room tempera­tures:
"COMFORT 1" (delivered condition 21 °C)
"COMFORT 2" (delivered condition 22 °C)
"COMFORT 3" (delivered condition 23 °C)
"REDUCED TEMP" (delivered condi­tion 17 °C)
"FROST PROTECTION" (delivered condition 6 °C)
Choose the preselected set room tem­peratures for the time phases in the time programs, for example.
5837779
Press the following keys:
1. INFO
2. MODE
3.
Select "SETTINGS" with / .
4. OK to confirm
5. Select "TARGET TEMP" with
/ .
6. OK to confirm "COMFORT 3" is displayed and
the value flashes.
21
Page 22
Outside temperature in °C
Flow temperature in °C
90
80
70
60
50
40
30
0 -5 -10 -15510
20
152025 -20
A
B
Central heating
Permanently changing the room temperature
7. Use +/- to change or press OK to
move to the next setting (e.g.
"COMFORT 1").
8. OK to confirm
The next setting appears.
9. Change with +/- or press ESC to exit programming.
(cont.)
Changing the heating curve for weather-compensated opera­tion
In weather-compensated operation, the room temperature is controlled accord­ing to a preset heating curve. If your room temperature controller acts on 2 heating circuits, a heating curve is preset for each heating circuit.
The heating curves show the relation­ship between the outside temperature and the boiler water temperature or flow temperature. The lower the outside temperature, the higher the boiler water or flow temperature. The heating curve is limited upwards by the maximum set flow temperature. The maximum set flow temperature can only be changed by your heating contractor.
Low end
A
22
End point
B
5837779
Page 23
Central heating
Permanently changing the room temperature
The line shows the curve for the stand­ard room temperature. The delivered condition is shown. The heating curve is changed with
"LOW END", "END POINT" and "SHIFT", which influences the room
temperature.
Changing the heating characteristics to change the room temperature Heating characteristics Measure The living space is too cold during the heating season The living space is too hot during the heating season The living space is too cold during spring/autumn and during the heating season The living space is too hot during spring/autumn and during the heating season The living space is too cold during spring/autumn The living space is too hot during spring/autumn, but warm enough the
heating season The living space is too cold in reduced
mode The living space is too hot in reduced mode
Shifting the heating curve means reducing the flow temperature for reduced mode. The value of "SHIFT" acts on both heating circuits.
Set the "END POINT" to a higher val­ue (e.g. 80 °C) Set the "END POINT" to a lower value (e.g. 70 °C) Set the "END POINT" and "LOW END" to a higher value (low end e.g. 30 °C; end point e.g. 80 °C) Set the "END POINT" and "LOW END" to a lower value (low end e.g. 20 °C; end point e.g. 70 °C) Set the "LOW END" to a higher value (e.g. 30 °C) Set the "LOW END" to a lower value (e.g. 20 °C)
Set the "SHIFT" to a lower value (e.g. 20 °C) Set the "SHIFT" to a higher value (e.g. 30 °C)
(cont.)
Setting a heating curve
Press the following keys:
01. INFO
02. MODE
03.
Select "SETTINGS" with / .
04. OK to confirm
5837779
05.
Select "CONTROL" with / .
06. OK to confirm
07.
Use / to select "OT CON­TROL".
23
Page 24
Central heating
Permanently changing the room temperature
08.
Use / to select the required setting:
■ – "LOW END" for heating circuit without mixer
"LOW END 2" for heating cir-
cuit with mixer
■ – "END POINT" for heating cir­cuit without mixer
"END POINT 2" for heating
circuit with mixer
■ – "SHIFT" for heating circuit without mixer
"SHIFT 2" for heating circuit
with mixer
09. OK to confirm
10. Use +/- or the rotary selector to
change the setting.
11. OK to confirm
12. ESC to exit the settings.
(cont.)

Changing the room temperature for a few days (holiday mode)

The holiday program starts on the set leaving day and ends on the set return day. The set time program is then active again.
07. Change with +/-.
08. OK to confirm
The month flashes.
Press the following keys:
01. INFO
02. MODE
03.
Select "SETTINGS" with / .
04. OK to confirm
05.
Select "HOLIDAY" with / .
06. OK to confirm
START HOLIDAY appears briefly, then the year flashes.
24
09. Change with +/-.
10. OK to confirm
The day flashes.
11. Set the day and hour in the same way, and press OK to confirm. END HOLIDAY appears.
12. Set END HOLIDAY the same way.
13. "FROST PROTECTION" appears.
Set the required set temperature.
14. OK to confirm
5837779
Page 25
Central heating
Changing the room temperature for a few days…

Stopping or interrupting the holiday program

Stopping the holiday program
1. Press OFF. "HOLIDAY OFF" appears.
2. OK to confirm
The holiday program is interrupted.
Reactivating the holiday program
1. INFO
2. MODE
3.
Select "SETTINGS" with / .
4. OK to confirm
5.
Select "HOLIDAY" with / .
6. OK to confirm "REACTIVATE" appears.
7. OK to confirm
HOLIDAY appears.
(cont.)
5837779
25
Page 26

DHW heating

Setting the time program and DHW temperature

You can set time phases for DHW heat­ing:
■ The DHW cylinder is heated during the set time phases when using a boiler with a DHW cylinder connected to it.
■ If using a boiler with an integral instantaneous water heater, the DHW is kept at the set temperature during the set time phases.
Press the following keys:
01. INFO
02. MODE
03.
Select "SETTINGS" with / .
04. OK to confirm
05. Select "PROGRAMMING" with
/ .
06. OK to confirm
07.
Select "HOT WATER" with / .
08. OK to confirm
09. NEW
Days flash.
10. +/- for the required group of days or single day
11. OK to confirm
12. +/- for the required set DHW tem-
perature
13. OK to confirm
14. +/- for hour
15. OK to confirm
16. +/- for minute
17. OK to confirm
18. OK to set further switching
times.
ESC to exit programming.

Changing or deleting switching times

See page 18.

Temporarily changing the DHW temperature

You can change the DHW temperature for one hour.
1. Press INFO repeatedly until "HW SETPOINT TEMP" appears.
26
2. Select the required set DHW tem-
perature with the rotary selector.
5837779
Page 27

Time and date

Further adjustments

Press the following keys:
1. INFO
2. MODE
3.
Select "SETTINGS" with / .
4. OK to confirm
5.
Select "TIME/DATE" with / .

Summer/wintertime

Press the following keys:
1. INFO
2. MODE
3.
Select "SETTINGS" with / .
4. OK to confirm
5.
Select "TIME/DATE" with / .
6. OK to confirm
7. Press +/- to make the required set-
ting.
8. OK to confirm and to move to the next setting.
9. ESC to exit programming.
6. Press OK repeatedly until "SU/WI RULE" appears.
7.
Press / to select the required setting.
8. OK to confirm
9. ESC to exit programming.

Further settings

You can make further settings under "OPTIONS". For further information on settings, see the following chapters.
Press the following keys:
1. INFO
2. MODE
3.
Select "SETTINGS" with / .
5837779
4. OK to confirm
5.
Select "OPTIONS" with / .
6. OK to confirm
7.
Press / to select the required setting. See following chapter.
8. ESC to exit programming.
27
Page 28
08:26
°
C
21 3
c
°
21.3
12:00
ROOM TEMP
08:26
21.3
°
c
Further adjustments

Setting the language

1. Confirm "LANGUAGE" with OK.
2. +/- for the required language

Changing the default display

1. Confirm "DISPLAY" with OK. 2. +/- for the required display version
Setting Display version
3. OK to confirm
3. OK to confirm
28
5837779
Page 29

Setting the contrast

Further adjustments
You can change the display contrast in stages.
1. Confirm "CONTRAST" with OK.
2. Use +/- to set the required value (0
to 15).
3. OK to confirm

Locking out controls (key lock)

You can lock out the controls by switch­ing on key lock.
1. Confirm "KEY LOCK" with OK.
2. Press +/- to select "WITH KEY­LOCK" or "NO KEYLOCK".
3. OK to confirm The display then shows only "KEY LOCK" and a key symbol.

Temporarily interrupting or unlocking key lock

Press and hold INFO for longer than 3 seconds. You can then temporarily operate the device or unlock the key lock. See above.

Changing the display format of fault messages

1. Press OK to confirm the "ERROR FORMAT".
2. Press +/- to select "HEXADECI­MAL". Do not adjust "DECIMAL".
3. OK to confirm

Returning all settings to their delivered condition

All settings made after commissioning will be lost.
5837779
1. Confirm "FACTORY SET" with OK. "CONFIRM" appears.
2. OK to confirm
29
Page 30

Checks

Checking information

You can check the following information with INFO:
■ Current outside temperature
■ Active time program
■ Fault messages
■ Set flow temperature
■ Actual flow temperature
■ Date and time
Press INFO repeatedly until the required information appears.
30
5837779
Page 31

Rooms are too cold

Cause Remedy
The room temperature controller is in­correctly set.
Note
For further causes, see the boiler oper­ating instructions
Check the settings and correct if re­quired:
■ Program
■ Room temperature
■ Time

Rooms are too hot

Cause Remedy
The room temperature controller is in­correctly set.
Check the settings and correct if re­quired:
■ Program
■ Room temperature
■ Time

What to do if...

Note
For further causes, see the boiler oper­ating instructions
5837779
31
Page 32
What to do if...

Carrying out a reset

Press the reset button with a suitable instrument.
32
5837779
Page 33

Cleaning

This device can be cleaned with a com­mercially available domestic cleaning agent. Never use any scouring agents.

Maintenance

5837779
33
Page 34

Appendix

Menu structure in setting mode (MODE)

MODE
P1 ACTIVE ACTIVATE P2 P2 ACTIVE ACTIVATE P3

Menu structure in settings

SETTINGS
TARGET TEMP
COMFORT 3
COMFORT 2 COMFORT 1 REDUCED TEMP FROST PROTECTION
TIME/DATE
HOUR
MINUTE YEAR MONTH DAY SU/WI RULE
PROGRAMMING
PROG P1
PROG P2 PROG P3 HOT WATER CLEAR PROG
PERM COMFORT PERM REDUCED FROST PROTECTION SETTINGS
HOLIDAY
START HOLIDAY
YEAR MONTH DAY HOUR END HOLIDAY FROST PROTECTION
OPTIONS
LANGUAGE
DISPLAY LCD BACKLIGHT CONTRAST KEY LOCK ERROR FORMAT FACTORY SET
SERVICE
WALL COMP
OPTIMISE EXT INPUT DEVICE TYPE CONTROL SERVICE CHIMNEY SWEEP INFO TSP-PARAMETER
34
5837779
Page 35
Appendix
Menu structure in settings
Note
Menu point TSP-PARAMETER only appears if the room temperature con­troller acts on heating circuits (mixer extension kit).
(cont.)
5837779
35
Page 36

Keyword index

Keyword index
C
Checks............................................... 30
Cleaning.............................................33
Contrast, setting.................................29
Controls..............................................13
– Locking out..................................... 29
Controls and display elements...........12
D
Default display, changing...................28
DHW.................................................. 26
DHW temperature
– Changing........................................ 26
Display............................................... 13
Display screen................................... 13
H
Heating characteristics.......................23
Heating curve
– Explanation.....................................22
Holiday mode..................................... 24
K
Key lock............................................. 29
L
Language, setting.............................. 28
O
Operating mode........................... 16, 20
Operating mode, selecting................. 20
R
Reset..................................................32
Room temperature
– Changing.................................. 20, 21
– Changing for a few days.................24
– Permanently changing....................21
– Temporarily changing..................... 20
S
Summer/wintertime............................ 27
Switching times.................................. 16
– Changing........................................ 18
T
Temperatures
– Changing........................................ 18
Temperatures, checking.....................30
Time and date.................................... 27
Time program.....................................16
Troubleshooting................................. 31
36
5837779
Page 37
5837779
37
Page 38
38
5837779
Page 39
5837779
39
Page 40
Your contact
Contact your local contractor if you have any questions about your system or wish to arrange maintenance or repair work. You can find local contractors on the inter­net at www.viessmann.de.
Viessmann Werke GmbH & Co. KG D-35107 Allendorf Telephone: +49 6452 70-0 Fax: +49 6452 70-2780 www.viessmann.com
40
Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: +44 1952 675000 Fax: +44 1952 675040 E-mail: info-uk@viessmann.com
5837779 Subject to technical modifications.
Loading...