Outdoor-reset logic digital cascade control
Panel mount, controls up to 4 Vitodens WB2B boilers
Please file in Service Binder
VITOTRONIC 100, HC1
VITOTRONIC 300-K, MW2S
Certified as a component part
of Viessmann boilers only
Vitotronic 100, HC1
Vitotronic 300-K, MW2S
5727 946 v1.2 11/2011
Page 2
Safety, Installation and Warranty Requirements
5727946v1.2
Please ensure that this manual is read and understood before commencing installation. Failure to comply with the
instructions listed below and details printed in this manual can cause product/property damage, severe personal injury,
and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual
subsections).
Licensed professional heating
contractor
The installation, adjustment, service,
and maintenance of this equipment
must be performed by a licensed
professional heating contractor.
ease see section
Pl
entitled “Important
Regulatory and
Installation
Requirements.”
Product documentation
Read all applicable documentation before commencing installation. Store
documentation near boiler in a readily
accessible location for reference in the
future by service personnel.
For a listing of
applicable literature,
please see section
entitled “Important
Regulatory and
Installation Requirements.”
Advice to owner
Once the installation work is complete,
the heating contractor must familiarize
the system operator/ultimate owner
with all equipment, as well as safety
precautions/requirements, shut-down
procedure, and the need for
professional service annually before
the heating season begins.
Warranty
Information contained in
this and related product
documentation must be
read and followed. Failure
Installing the Cascade Communication Module10
Summary of electrical connections (Power Pump Module)11
Installing modules13
Installing the programming unit13
Summary of electrical connections14
Sensor connection17
Connection of the pumps19
Connection to modulating valve actuators20
Connection of external contacts21
Connection to compiled failure alarm22
Making the LON connection23
Power supply24
Cascade control unit55
Heating circuit control60
DHW tank temperature control63
Components – Vitotronic 300-K
Components from the parts list65
Mixing valve circuit extension kit69
Installation examples70
Remote control71
Room temperature sensor77
Input Module 0 to 10 V78
Coding – Vitotronic 100, HC1
Resetting codes to the factory setting79
Coding Level 179
Coding Level 280
Coding – Vitotronic 300-K
Resetting codings to the factory setting82
Coding Level 182
Coding Level 285
Slab curing function diagram101
Only for integration/installation on Viessmann boilers and for wall mounting.
These application examples are only recommendations, and must therefore be checked on site for completeness and
function.
4
Page 5
Important Regulatory and Safety Requirements
5727946v1.2
General Information
Approvals
Viessmann boilers, burners and
controls are approved for sale in North
America by CSA International.
Codes
The installation of this unit shall be in
accordance with local codes. In the
absence of local codes, use:
CSA C22.1 Part 1 and/or local codes
in Canada
National Electrical Code ANSI/NFPA
70 in the U.S.
Always use latest editions of codes.
Working on the equipment
The installation, adjustment, service,
and maintenance of this product must
be done by a licensed professionalheating contractor who is qualified and
experienced in the installation, service,
and maintenance of hot water boilers.
There are no user serviceable parts on
the boiler, burner, or control.
Please carefully read this manual prior
to attempting installation. Any
warranty is null and void if these
instructions are not followed.
For information regarding other
Viessmann System Technology
componentry, please reference
documentation of the respective
product.
We offer frequent installation and
service seminars to familiarize our
partners with our products. Please
inquire.
The completeness and functionality of
field supplied electrical controls and
components must be verified by the
heating contractor. These include low
water cut-offs, flow switches (if used),
staging controls, pumps, motorized
valves, air vents, thermostats, etc.
Ensure main power supply to
equipment, the heating system, and all
external controls has been deactivated.
Close main oil or gas supply valve.
Take precautions in both instances to
avoid accidental activation of power
during service work.
Technical literature
Literature applicable to all aspects of
the Vitotronic 300-K:
- Installation & Service Instructions
- Operating & User Instructions
- Instructions of other Viessmann
products utilized and installed
- Installation codes mentioned
in this manual
WARNING
Turn off electric power
supply before servicing.
Contact with live
electric components
can cause shock or loss
of life.
Leave all literature at the installation
site and advise the system operator/
ultimate owner where the literature
can be found. Contact Viessmann for
additional copies.
5
Page 6
General Information
5727946v1.2
Important Regulatory and Installation Requirements
Power supply
Install power supply in accordance with
the regulations of the authorities
having jurisdiction or, in the absence of
such requirements, in accordance with
National Codes. Viessmann
recommends the installation of a
disconnect switch to the 120 VAC
power supply outside of the boiler
room. The installer must provide
maximum 15 A overcurrent protection
for the 120 VAC power supply (fuse or
circuit breaker).
Working with an open control
No static discharge to the internal
componentry must ever occur when
working with opened control
equipment.
About these Installation Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product information.
These include ”WARNING”, ”CAUTION”, and ”IMPORTANT”. See below.
Warnings draw your attention to the
WARNING
Indicates an imminently hazardous
situation which, if not avoided, could
result in death, serious injury or
substantial product/property damage.
presence of potential hazards or
important product information.
CAUTION
Indicates an imminently hazardous
situation which, if not avoided, may
result in minor injury or
product/property damage.
IMPORTANT
Cautions draw your attention to the
presence of potential hazards or
important product information.
Helpful hints for installation,
operation or maintenance which
pertain to the product.
This symbol indicates that additional,
pertinent information is to be found in
column three.
This symbol indicates that other
instructions must be referenced.
6
Page 7
System design
5727946v1.2
Heating System Designs
A Vitodens 200-W (models 45 to
105) with the Vitotronic 100, HC1,
with KMK cascade communication
module as part of the standard
delivery
B Vitotronic 300-K with LON
communication module (accessory)
C DHW cylinder
D Vitotronic 200-H with LON
communication module
(accessories)
E Mixing valve on Vitotronic 300-K
F Mixing valve on Viotronic 200-H
G Maximum temperature controller
(underfloor heating)
H Low loss header
K Two-way valve
!Outdoor temperature sensor
?Supply temperature sensor
The codes must be set on every Vitotronic 100.
(see section on coding page 82)
Vitotronic 100, HC1
Required coding
01 : 2
07 : 2
07 : 3
07 : 4
Vitotronic 300-K
Required coding
00 : 3,
00 : 4,
00 : 7,
or
00 : 8
35 : 1
35 : 2
35 : 3
35 : 4
Multi-boiler system with Vitocontrol-S, WB2B
Setting the boiler number at the Vitotronic 100 of the
second boiler
third boiler
fourth boiler
Heating circuit M2 without DHW heating
Heating circuit M2 with DHW heating
Heating circuit M2 and M3 without DHW heating
Heating circuit M2 and M3 with DHW heating
Setting up Vitotronic 300-K with
one Vitotronic 100
two Vitotronic 100
three Vitotronic 100
four Vitotronic 100
Vitotronic 200-H (if installed)
Required coding
97 : 1The outdoor temperature is accepted by the LON BUS
8
Page 9
System design (continued)
5727946v1.2
DHW and Space Heating
Multiple (up to four) Vitodens 200-W, models WB2B 45, 60, 80 and 105 with...
– multiple heating circuits with mixing valves
– low-loss header
Vitotronic 300-K
Heating System Designs
DHW Tank
TPV
PPM
Boiler 1Boiler 2
PRV
PPMPPMPPM
Boiler 3Boiler 4
PRV
PRV
PRV
Common
Supply
Temperature
Sensor
Low-Loss
ader
He
M
Fig. 31
When designing a multiple Vitodens system as shown above, please reference applicable multiple Vitodens technical
documentation, and contact your local Viessmann Sales Representative for further assistance.
M
IMPORTANT
This installation example depicts a
possible piping layout for multiple
Vitodens 200-W, WB2B boilers
equipped with Viessmann system
Technology. Please note that this
example is based on a simplified
conceptual drawing only! Piping and
necessary componentry must be field
verified.
A low water cut-off (LWCO) must be
installed where required by local codes.
Proper installation and functionality in
the field is the responsibility of the
heating contractor.
WARNING
When extending wire, there is the
possibility of exposure to
electromagnetic interference.
Avoid running wires beside or near
high voltage 120/240 VAC
conductors. If proximity to high
voltage conductors cannot be
avoided, use stranded, twisted pair
or shield design wire. Ensure that
only one end of the shielding is
grounded.
9
Page 10
Installation – Vitotronic 300-K
Installing the Cascade Communication Module
A
The cascade communication module
2.
A
3.
Installation Instructions shipped
with boiler.
1.
X7
A
B
C
C
D
A Vitotronic 300-K
B KMK-BUS
C Boiler control with Vitotronic 100
and KMK Module (max 4 boilers)
D 2-core Cable
(cable cross-section 2 x 0.5 mm
2
20 AWG total length 164ft. / 50m)
E Connection to the Vitotronic 300-K
(to terminals X9.3 and X9.4 on
cascade electronic module A2)
F Terminal strip ”KMK1/KMK2” at
the cascade communication module
of the boiler control with
Vitotronic 100
X9
4
3
A2
KMK2KMK1KMK2KMK1
Note:
The total length of BUS cables B
should not exceed 164ft. / 50m.
The wires from the BUS cables are
commutable.
1 2 3 41 2 3 4
5727 946 v1.2
10
Page 11
Summary of electrical connections (Power Pump Module)
Power/Pump module
MAIN POWER SUPPLY
120V, 60HZ, 12A
L
N
G
MAIN
DISCONNECT
L2
L1
P1
P2
A
-TYPICAL
SAFETY DEVICE
LOW WATER CUT-OFF
SWITCH
120VAC
WALL
RECEPTACLE
120/230
Transformer
NL
202120A40
L2
L1 G N
40
202120A
M
120VAC
BOILER
PUMP
Installation – Vitotronic 300-K
Installation
Instructions,
Power Pump
31 2
143
NL
NLNLNL
50
50
120VAC
FAULT
ALARM
OUTPUT
1 2 3 1 2 3 1 2 3
28
L G N
144
31 2
31 2
145
145144143
Module
KMK1KMK2
X1
4321
KMK
Module
L
145
X
7
X
8
X
9
X11
LON
KMK
X4
Boiler Control Board
1234567
X3
2040
N
230 VAC
40962035100
5727 946 v1.2
11
Page 12
Installation – Vitotronic 300-K
Summary of electrical connections (Power Pump Module) (continued)
305
1.
318
2.
129
X10
139
4.
X2
X1
12
5727 946 v1.2
Page 13
Installing modules
5727946v1.2
A4A3
A1A2
A1 Power supply module
2 Cascade electronic module
A
A3 Power module
A4 Extension module, mixing valves
Installing the programming unit
Installation – Vitotronic 300-K
1. Install the modules in accordance
with the layout indicated on DIN
rail inside the control panel.
2. Connect the modules in accordance
with the overview
on page 14 and 15, using the
connecting cables provided.
1. Make a cutout with the dimensions
305 × 129 mm in the front door of
the control panel.
When installing two programming
units, maintain a distance between
both of 20 mm.
2. Snap the frame into place.
3. Insert the programming unit.
4. Plug the connecting cable into the
back of the programming unit and
into the cascade electronic module
(A2).
13
Page 14
Installation – Vitotronic 300-K
5727946v1.2
Summary of electrical connections
14
F1 4A
(slow)
Page 15
Summary of electrical connections (continued)
5727946v1.2
Installation – Vitotronic 300-K
15
Page 16
Installation – Vitotronic 300-K
5727946v1.2
Summary of electrical connections (continued)
A1 Power supply module
fÖPower supply connection
A2 Cascade electronic module
!Outdoor temperature sensor
(accessories)
?Common supply temperature
sensor
%DHW tank temperature sensor
(accessories)
%B 2nd tank temperature sensor
(accessories)
aJA Temperature sensor T1
aJB Temperature sensor T2
or
temperature sensor - DHW tank
loading system
aVDExternal connections
aVGKM BUS users (accessories) link
to Vitotronic 100 and remote
controls Vitocontrol
aVHExternal connections
LONConnecting cable for data
transfer between the control
units
S1Emissions test switch S
(optional)
A3 Power module
sÖA1 Heating circuit pump or
DHW tank loading system
sADHW tank pump (accessories)
sKDHW re-circulation pump
sLShunt or supply pump
gÖCompiled failure alarm
gSA1 Three-way return elevation valve
Remove both jumpers when connecting the emissions test circuit.
16
Page 17
Sensor connection
Outdoor temperature sensor
Installation – Vitotronic 300-K
The outdoor temperature sensor should be mounted 6.5 to 8ft / 2 to 2.5m above
ground level on the north or north-west facing wall of the building. In the case of
multi-storey buildings, it should be mounted in the upper half of the second storey.
Make sure that the sensor is not located over windows, doors and air vents, nor
immediately beneath a balcony or guttering.
Do not paint over the outdoor temperature sensor housing.
1. Remove the cap.
2. Mount the bottom part of the sensor
housing.
1.
4.
2.
WARNING
When extending wire, there is the
possibility of exposure to
electromagnetic interference.
Avoid running wires beside or near
high voltage 120/240 VAC
conductors. If proximity to high
voltage conductors cannot be avoided,
use stranded, twisted pair or shield
design wire. Ensure that only one end
of the shielding is grounded.
5.
3.
3. Pull the sensor wire through the
opening in the terminal compartment
and through the strain relief
provided.
4. Connect the wires to the terminals.
5. Place the cap over the outdoor
temperature sensor.
600
580
560
540
520
500
480
460
440
5727 946 v1.2
420
Resistance in
400
-40-30-20-100102030
-40-22-41432506886
Outdoor temperature in °C / °F
17
Page 18
Installation – Vitotronic 300-K
Sensor connection (continued)
DHW tank temperature sensor
The sensor measures the domestic hot
water tank temperature.
720
700
680
Heating systems with domestic hot
water heating (single-boiler systems
only)
1. Install the DHW tank temperature
sensor.
See installation instructions
for domestic hot water tank
Note:
When installing the sensor in DHW
tanks of other makes, make sure
that the sensor is pressed against
the sensor well of the DHW tank by
means of a suitable device.
2. Ensure that the maximum
permissible domestic hot water
temperature is not exceeded. If
necessary, install a suitable safety
device for this purpose.
Check the sensor
1. Disconnect wires from terminals
X2.7 and 2.1 of module A2.
2. Measure resistance of sensor at
terminals ”1” and ”2” of the plug.
DHW tank
temperature
Resistance
in ΩΩΩΩ
in °F / °C /
104 / 40
122 / 50
140 / 60
578
597
616
3. Compare the value measured with
the current temperature. If the value
differs significantly, check
installation and, if necessary, replace
sensor.
Technical data
Degree of protection: IP 32
Ambient temperature
During operation:
32 to + 194°F
0 to + 90°C
During storage and transport:
- 4 to + 158°F
-20 to + 170°C
660
640
620
600
580
560
Resistance in
540
020406080100
3268104140176212
DHW tank temperature in °C / °F
18
ctrical connection
Ele
The sensors are ready to connect.
Insert the DHW temperature sensor lead
wires to terminals X2.7 and 2.1 of the
A2 Module.
Heating systems without domestic hot
water heating
Do not connect the DHW tank
temperature sensor.
5727 946 v1.2
Page 19
Connection of the pumps
Available pump connections
sÖHeating circuit high temperature
(without mixing valve)
sÖM2 Heating circuit M2 pump
Terminals 2 - L, - G , - N
sÖM3 Heating circuit M3 pump
Terminals 1 - L, - G , - N
sADHW pump for heating up the
domestic hot water tank Terminals 4 - L, - G , - N
sKDHW recirulation pump
Terminals 3 - L, - G, - N.
Installation – Vitotronic 300-K
TERMINAL
4 or 3
A
B
Install pumps: see
manufacturer’s
instructions.
120 VAC pumps
Note:
The maximum power consumption of
all pumps is 4A .
Rated current: max. 2 FLA
Recommended connection
cable: AWG 14
Connect the 3-wire cable from the
pump to the corresponding terminals.
240 VAC or 3 PH pumps
Note:
Use contactor to switch pump.
For activating the contactor:
Rated current: max. 2 FLA
Recommended connection
cable: AWG 14
Please ensure that all connections and
cable gauge comply with local and
national codes.
1.Select the contactor and the
connecting cable in accordance with
the rating of the pump that is to be
connected.
2.Connect the pump and power supply
to the contactor.
3.Connect contactor coil to the
corresponding terminals.
2. Install 120V or 24V valve adaptor
on DIN rail inside connection
enclosure.
3. Insert the plug gS into socket gS on
the control.
4. Fasten cable with tie.
5. Connect black wire of the adaptor to
connection aBH on the DIN rail
- Terminal 8, 9 or 10.
6. Connect valve actuator wires to the
adaptor terminals as shown on
figures.
20
5727 946 v1.2
Page 21
Connection of external contacts
Implement connection a
A2 in accordance with the overview on
pages 15 and 16 and the control panel
wiring diagram.
VD / aVH on
A External heating program
changeover or “Mixing valve open”
Contact closed:
The manually pre-selected heating
program can be changed via this
contact, (see table below) enabling the
mixing valves to be opened.
The mixing valve open function can be
allocated via coding address “9A”, and
the heating program changeover can be
allocated to the heating circuits via
address “91”.
Installation – Vitotronic 300-K
WARNING
Heating circuits are no longer frost
protected during mixing valve closed.
A minimum boiler return temperature
is not maintained during external
disabling.
Via coding address “99”, you can
pre-select what input aVD should
affect.
A External heating program
changeover/external “Mixing valve
open”.
B External disable/external “Mixing
valve closed”
C External demand
Manually pre-selected
heating program
(with open contact)
9
Room heating OFF/
DHW OFF
or
worRoom heating OFF/
DHW ON
rw Room heating ON/
DHW ON
Coding 2Changed heating program
d5: 0
(factory
default)
d5: 1<–> Continuous operation with normal room temperature/DHW in
B External disable/external “Mixing
valve closed”
Closing the dry contact causes the
burner to shut down or the mixing
valve to be closed.
Allocated boiler or pumps are switched
OFF, and isolation valves are closed.
No frost protection!
(with closed contact)
<–> Continuous operation with reduced room temperature/DHW OFF
accordance with coding address “64”
C External demand
Closing the dry contact starts the boiler
burners, subject to load via a set
supply temperature (coding address
“9b”) on Vitotronic 300-K.
The supply temperature is limited via
the set min. and max. supply
temperature.
5727 946 v1.2
21
Page 22
Installation – Vitotronic 300-K
Connection of the compiled failure alarm
Implement connection gÖ on A3 in
accordance with overview on page 104
and control panel wiring.
Commissioning of all Vitodens 200-W, WB2B with Vitotronic 100, HC1
Service Instructions Vitodens 200-W, WB2B
A
ºC
A Heating programs
B No function
C Information
+
OK
i
–
BD CEFGHK
D Fact0ory default setting
E Confirmation
F Value setting
G No function
H Emissions test function
K Boiler water temperature
26
5727 946 v1.2
Page 27
Further step-by-step instructions (continued)
Boiler sequence
Initial start-up
A Heating circuit selection
B Reduced room temperature
C DHW temperature
D Normal room temperature
E Standby mode
F DHW only
G Heating and DHW
H Economy mode
K Party mode
L Information
M Standard settings
N Confirmation
Checking the heating circuit allocation (Vitotronic 300-K)
heck that the label for heating
H C
circuit allocation has been affixed to
the corresponding fields of the
programming unit.
H Press the corresponding key before
commencing all adjustments.
Changing the display language (Vitotronic 300-K)
1. Press i.
2. Select the required language
with.
3. Confirm with.
O Adjusting values
P Time programs
R Holiday program
S Time/date
T Heating curve level shift
U Heating curve slope
5727 946 v1.2
27
Page 28
Initial start-up
Further step-by-step instructions (continued)
Configuring a multi-boiler system
The cascade communication module must be fitted into all Vitotronic 100 boiler control.
Setting codes, see page 80 and 86.
Example of a multi-boiler system
Vitotronic 300-K
145
Vitotronic 300-K
––
––
Number of connected boilers
< 5 boilers
Set code ”35:2”, ”35:3” or
”35:4”
Vitotronic 100Vitotronic 100
KMK1KMK2
Vitotronic 100, HC1
Multi-boiler system
Set code ”01:2”
Boiler number 1
Coding ”07:1”
––––
Connecting control units into the LON system
The LON communication module (accessories) must be fitted.
ote:
N
The data transfer via the LON system can take several minutes.
Vitotronic 200-H
– – – –
– – – –
KMK1
Vitotronic 300-K
Multi-boiler system
Set code ”01:2”
Boiler number 4
Set code ”07:4”
Setting up LON participant numbers
In coding 1, set the LON participant
number via coding address “77”.
Vitotronic 300-K
1. Set the number of boilers
In coding 1, set coding address “35”.
Coding 1 see page 82.
Note:
In one LON system, each number
must only be allocated once.
Only one Vitotronic may be
programmed as fault manager.
28
Installation and service
instructions, Vitotronic 200-H.
Note:
In one LON system, each number
must only be allocated once.
5727 946 v1.2
Page 29
Initial start-up
Further step-by-step instructions (continued)
Update the LON participant list on Vitotronic 300-K
Only possible if all users are connected and the control unit is encoded as fault manager (coding 79 : 1 factory default setting)
Note: In each heating system, only one Vitotronic may be encoded as fault manager.
1. Press w and
for approx. 2 s.
The participant check is initiated.
simultaneously
2. Press D.
The participant list is updated
after approx. 2 min.
Participant check completed.
Example of a LON system
Vitotronic 300-K
Participant no. 5
Code ”77:5”
Send time via LON
Code ”7b:1”
Transmit outdoor temperature
via LON
Set code ”97:2”
”79:1” Fault Manager”79:0” Control is not fault
”9C:20” Monitoring LON
Participant
Vitotronic 200-H
LONLON
Participant no. 10
Set code ”77:10”
Accept time via LON
Set code ”81:3”
Receive outdoor temperature
via LON
Set code ”97:1”
manager
”9C:20” Monitoring LON
Participant
Vitotronic 200-H
LON
Participant no. 11
Set code ”77:11”
Accept time via LON
Set code ”81:3”
Device receives the time
”79:0” Control is not fault
manager
”9C:20” Monitoring LON
Participant
Vitocom
Participant no. 99
Time received via LON
Carrying out a participant check (300-K)
The communication with the system devices connected to the fault manager is tested by means of a participant check.
Preconditions:
H The control unit must be programmed as fault manager (code 79:1).
H The LON participant number must be programmed in all control units
(see page 28).
H The fault manager participant list must be up to date.
Participant check
F01 : 01
1
Participant
Consecutive
number in the
participant list
5727 946 v1.2
number
1. Press w andsimultaneously for
approx. 2 seconds.
2. Select the required participant with
and.
3. Activate check with.
”Check” flashes until its completion.
The display and all key illuminations
of the selected participant flash for
approx. 60 seconds.
H During communication between
both devices ”Check OK” is
displayed.
H ”Check not OK” is displayed, if no
communication is established.
Check the LON connection and
coding.
4. To check further participants
proceed as described under points 2
and 3.
5. Press w and
approx. 1 second.
simultaneously for
29
Page 30
Initial start-up
Further step-by-step instructions (continued)
Reducing the maximum burner output (Vitotronic 100)
Vitodens 200 service instructions
Matching the coding addresses to respective system version (Vitotronic 100)
In code 1, set the following coding
ddresses:
a
01Multi-boiler system
06Maximum boiler temperature
In code 2, set the following coding
addresses:
76:2 With cascade communication
module KMK
07Boiler number
2FAir bleed function
Matching coding addresses to respective system version (Vitotronic 300-K)
In code 1, set the following coding
addresses:
00System design
35Number of boilers in cascade
36Minimum limit of the cascade
supply temperature
37Maximum limit of the cascade
supply temperature
*1
3bControl type
3CControl strategy
77LON participant number
*2
A2DHW priority
A5Heating circuit pump logic
function (economy control)
C5Minimum supply temperature
limit, heating circuits
C6Maximum supply temperature
limit, heating circuits
In code 2, set the following coding
addresses:
38Lead boiler rotation
39Permanent lead boiler
3APermanent last boiler
55Function DHW temperature
control
78LON communication enabled
7ACentral control
7FDetached house or apartment
building (management system)
98Viessmann system number
*1
9CMonitoring LON participants
*1
Not higher than (Vitotronic 100 Coding Level 1 - 06:)
*2
Only in conjunction with LON system
30
5727 946 v1.2
Page 31
Further step-by-step instructions (continued)
Checking outputs (actuators) and sensors
Vitotronic 100
Relay test
Initial start-up
1. Press 9 and
approx. two seconds.
The following relay outputs may be selected:
Display
indication
11
12
13
14
Check sensors
1. Press.
Scanning operating conditions is
active, see page 38.
Relay function
Burner modulation lower output
Burner modulation upper output
Internal pump/ output 20 ON (Power Pump module)
Output 50 ON/ fault indicator in Power Pump Module
simultaneously for
2. Select the relay outputs
2. Scan the actual temperature with
withor.
or.
3. Press.
3. Press
Scanning is completed.
.
5727 946 v1.2
31
Page 32
Initial start-up
Further step-by-step instructions (continued)
Vitotronic 300-K
Relay test
1. Press 9 andsimultaneously for
approx. two seconds.
The following relay outputs may be selected:
Output 20M1 ON
Output 52A1 open
Output 52A1 ntr.
Output 52A1 close
DHW tank heating pump ON
DHW recirculation pump ON
Heating pump (M2) ON
Heating pump (M3) ON
Check sensors
1. Press
Scanning operating conditions is
active, see page 43.
.
2. Select the relay outputs
with
Mixing valve (M2) open
Mixing valve (M2) close
Mixing valve (M3) open
Mixing valve (M3) close
Central fault display ON
2. Scan the actual temperature with
or.
or.
Selecting the boiler sequence (Vitotronic 300-K)
f required:
1. I
In coding 2, set coding addresses 39
(permanent lead boiler) and 3A
(permanent last boiler).
2. Pressandsimultaneously for
approx. two seconds.
3. Select the required boiler sequence
withor.
By pressingand
simultaneously, you can exit the
adjustment without saving any
modifications made.
3. Press
Note:
The illuminated heating circuit selector
button indicates the corresponding
heating circuit.
3. Press.
Scanning is completed.
4. Press.
The adjustment has been
transferred.
5. In coding 2, set the coding
addresses 38, 41, 42, 43 and 44;
see also the function description
from page 59.
.
32
5727 946 v1.2
Page 33
Initial start-up
Further step-by-step instructions (continued)
Adjusting the heating curve (Vitotronic 300-K)
The heating curves illustrate the relationship between the outdoor temperature and the boiler water or the supply
temperature. To put it simply: the lower the outdoor temperature, the higher the boiler water or supply temperature.
The room temperature again depends on the boiler water or the supply temperature.
Factory default settings:
Slope:
Shift:= 0
Generally, the heating curve is set:
In range A for underfloor heating systems,
In range B for low temperature heating systems (according to the Energy Savings Order),
= 1.4
Slope
3.4
3.2
3.0
2.8
2.6
2.4
90/194
80/176
70/158
60/140
50/122
Supply tempertaure in ºC / ºF
40/104
30/86
35
95
30
86
25
77
20
68
15
59
Set room temperature in ºC / ºF
10
50
10
50
5
-1014-15
41032-523
Outdoor temperature in ºC / ºF
5
41
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
-20
-4
5
5727 946 v1.2
33
Page 34
Initial start-up
Further step-by-step instructions (continued)
Changing slope and shift
(for every heating circuit separately)
1. Call up slope with,
adjustable value 0.2 to 3.5;
call up shift with
;
adjustable value 8.6 to 104°F / –13
to +40°C.
110
230
A
Supply temperature in °C / °F
3.5
2. Change the value with
3. Confirm the set value with
B
1.4
0.2
or.
.
+20 / 68
Outdoor temperature in °C / °F
A Change slope
B Change shift
-20 / -4
34
5727 946 v1.2
Page 35
Further step-by-step instructions (continued)
Adjusting the normal room temperature
(for every heating circuit separately)
Initial start-up
D
1
Standard roomtemp.
2
3
1
2
3
20
Reduced roomtemp.
14
Select the normal day temperature with
the set value adjuster.
Reduced room temperature:
1. Call up the reduced night
temperature with tm.
Normal room temperature:
The value will be automatically
transferred after approx. 2 seconds.
2. Change the value with
or.
3. Confirm the set value with.
Temperature conversion:
˚F˚C
-4-20
415
5714
6820
7926
230110
E
DE
Example 1:
Adjustment of the normal room
temperature from 68 to 79˚F / 20 to
26˚C.
A Boiler water temperature or supply
temperature in ˚F / ˚C
B Outdoor temperature in ˚F / ˚C
C Set room temperature in ˚F / ˚C
D Heating circuit pump OFF
E Heating circuit pump ON
5727 946 v1.2
Example 2:
Adjustment of the reduced room
temperature from 41 to 57˚F / 5 to
14˚C.
Accordingly, the heating curve is
adjusted along the set room temperature
axis, resulting in modified start/shutdown
characteristics for the heating circuit
pumps, if the heating circuit pump logic
is active.
35
Page 36
Service scanning – Vitotronic 100, HC1
Service level summary
FunctionEntryExitPage
Reducing the max.
burner output
Relay testPress 9 and “OK”
Temperatures,
boiler coding card
and brief scans
Operating
conditions
TroubleshootingPress “OK”44
Fault historyPress rw and “OK”
Resetting codes
to the factory
default setting
Coding Level 1Press 9 and w
Coding Level 2Press w and rw
Press 9 and tw
simultaneously for
approx. 2 seconds
simultaneously for
approx. 2 seconds
Press 9 and rw
simultaneously for
approx. 2 seconds
Press 8Press 843
simultaneously for
approx. 2 seconds
Press w and rw
simultaneously for
approx. 2 seconds
press D
simultaneously for
approx. 2 seconds
simultaneously for approx.
2 seconds
Press “OK”29
Press “OK”32
Press “OK”32
Press “OK”44
––82
Press 9 and w
simultaneously for
approx. 1 second
Press w and rw
simultaneously for
approx. 1 second
79
80
Vitodens 200-W Service Instructions
36
5727 946 v1.2
Page 37
Temperatures, boiler coding card and quick scans
Service scanning – Vitotronic 100, HC1
1. Press 9 and rw simultaneously
for approx. two seconds.
Brief scans
8
0System
1Burner control unit software
ENo function
3Set boiler temperature
AHighest demand temperature
4Burner control unit typeBoiler type
5No function
bMaximum heating output in %
CBoiler coding card (hexadecimal)
cEquipment version (EEPROM)Burner control unit version
dVariable speed
88888
2. Select the required scan
withor.
Control unit software versionProgramming
design 1
version
(EEPROM)
pump
0 without
1 Wilo
2 Grundfos
unit software
version
Cascade
module
software
version
Variable speed
pump software
version
0: No variable
speed pump
5727 946 v1.2
37
Page 38
Service scanning – Vitotronic 100, HC1
Scanning operating conditions
1. Press 8.2. Select the required operating
condition scan withor.
Scans
Display
indication
001
3__65
263572
030417
ExplanationNotes
Boiler number––
°CBoiler temperature––
hBurner hours runThe hours run can be reset to 0 with D.
The hours run displayed are only
approximate values.
Burner startsThe burner starts can be reset to 0
with D.
3. Press.
38
5727 946 v1.2
Page 39
Service scanning – Vitotronic 100, HC1
Scanning and resetting service displays
After the limits set up via coding addresses 21 and 23 (see page 80) have been reached, the programming unit display
flashes one of the following messages.
Note:
Set code 24:1 and then code 24:0, if maintenance is implemented before a maintenance message is displayed; the set
maintenance parameters for hours run and maintenance intervals are then reset to 0.
Display
indication
35510
___12
After maintenance has been carried out
1. Reset coding 24: 1 (see page 80) to
24: 0.
Note:
If coding address 24 is not reset, a
new maintenance message will be
displayed on Monday morning.
2. If required:
Press
Reset burner run hours and burner
starts with D select the value to 0
(see page 80)
Pressorfor further queries
Pressquery is complete
Explanation
Burner run hours have
h
been reached
Time interval
u
(e.g. 12 months)
has been reached
1. Scan maintenance messages with
or.
2. Press.
The maintenance indication in the
display is cleared.
Note:
An acknowledged maintenance
message can be redisplayed by
pressing(approx. three seconds).
5727 946 v1.2
39
Page 40
Service scanning – Vitotronic 300-K
Service level summary
FunctionEntryExitPage
Adjusting display
contrast
Participant checkPress the w and “OK” buttons
Relay testPress the 9 and “OK” buttons
Boiler sequencePress the g and û buttons
Temperatures and
quick scans
Operating statusPress the buttonPress the button43
TroubleshootingPress the buttonPress the “OK” button48
Error historyPress the rw and “OK”
Resetting codings
to factory default
settings
Coding Level 1Press 9 and w simultaneously
Coding Level 2Press the w and rw buttons
Press the “OK” and “+”
buttons simultaneously;
the display will darken
Press the “OK” and “-” buttons
simultaneously;
the display will get lighter
simultaneously for approx.
2 seconds
simultaneously for approx. 2
seconds
simultaneously for approx. 2
seconds
Press 9 and rw
simultaneously for approx. 2
seconds
buttons simultaneously for
approx. 2 seconds
Press the w and rw buttons
simultaneously for approx.
2 seconds; press the D button;
confirm by pressing the “OK”
button
for approx. 2 seconds
simultaneously for approx. 2
seconds; confirm by pressing the
“OK” button
––––
––––
Press the w and “OK” buttons simultaneously for approx. 1 sec29
Press the “OK” button32
Press the “OK” button32
Press the “OK” button41
Press the “OK” button48
––79
Press the 9 and w buttons simultaneously for approx. 1 sec79
Press the w and rw buttons simultaneously for approx. 1 sec80
40
5727 946 v1.2
Page 41
Temperatures and quick scans
Service scanning – Vitotronic 300-K
1. Press 9 and rw simultaneously
for approx. 2 seconds.
2. Select the required scan
withor.
The following values can be scanned subject to the actual equipment level:
Outdoor temperature adjusted
Outdoor temperature actual
Boiler sequence
P-actual % boiler 1 to 4
Output red. %
Integral
Boiler temperature actual boiler . . . .
1 to 4
Sensor 17B actual (not used)
Set DHW temperature
Actual DHW temperature
Supply temperature set
Supply temperature actual
Room temperature set
Roomtemperature actual
Quick scan 1 to quick scan 8
3. Press “OK”.
The adjusted outdoor temperature
can be reset to the current outdoor
temperature with D.
Boiler output - actual value.
No function.
at - 1 to - 100 start-up integral in
percent; at 1 to 100 shutdown
integral in percent (Y - arrow above
ord, when integral grows).
w
Display only if a sensor is connected.
Display only if a system design with
a DHW tankhas been encoded . . . . .
(code 00).
Display only if a remote control unit
is installed
Quick scans 1 to 7, see page
NO TAG.
5727 946 v1.2
41
Page 42
42
Service scans – Vitotronic 300-K
Temperatures and quick scans (continued)
8
N/A
Software version
remote control
mixing valve
circuit M3
N/A
re
8
N/A
Software version
mixing valve
extension M3
Printed Circuit
Board
Actual value boilers 1 to 4
Display only if a sensor is connected
Display only if a DHW tank sensor is
connected
Display only in conjunction with
mixing valve circuits
Display only if a remote control unit
is installed
Position detail in %
Position detail in %.
Each language can be selected as
permanent display language
with
A fault can be acknowledged with
“OK”. The fault message in the display
will be hidden, but the red fault
indicator U continues to flash.
The fault message will be redisplayed,
if an acknowledged fault message has
not been removed by the following
morning.
Calling up acknowledged fault
messages
Press “OK” for approximately 2
seconds.
Select the acknowledged fault with
or.
E in the display indicates that the
burner control unit is locked out. After
the fault has been removed,
acknowledge by pressing reset E.
Note:
After acknowledging the fault, E will
be displayed until the burner control
unit lockout has been lifted.
5727 946 v1.2
43
Page 44
Troubleshooting – Vitotronic 100, HC1
Retrieving fault codes from the fault memory (fault history)
The most recent 10 faults are saved and may be called up.
Faults are sorted by date. The most recent fault is fault number 1.
1. Press rw and
for approx. 2 seconds.
2. Pressorfor individual fault
codes.
Note:
All saved fault codes can be deleted
with D.
3. Pressto finish scan.
Faults displayed at the programming unit
The red faults indicator U flashes for
every fault.
A fault code flashes in the display if a
fault message has been issued.
iConsecutive fault number
38 Fault code
UFault symbol
Call up further fault codes with
.
A fault can be acknowledged with
“OK”. The fault message in the display
will be hidden, but the red fault
indicator U continues to flash.
The fault message will be redisplayed,
if an acknowledged fault message has
not been removed by the following
morning.
Calling up acknowledged fault
messages
Press “OK” for approximately 2
seconds.
Select the acknowledged fault with
or.
or
E in the display indicates that the
burner control unit is locked out. After
the fault has been removed,
acknowledge by pressing reset E.
simultaneously
44
Note:
After acknowledging the fault, E will
be displayed until the burner control
unit lockout has been lifted.
5727 946 v1.25727 946 v1.2
Page 45
Faults displayed at the programming unit (continued)
Troubleshooting – Vitotronic 100, HC1
Fault
code
0000ffff
33330000
33338888
bbbb0000
bbbb1111
bbbb4444
bbbb5555
bbbb7777
bbbb8888
e4444
System characteristics
Control modeService “0F” is only displayed in the
Burner blocked
Control mode (stays in factory
default setting)
regulates as if the outdoor
temperature was 32°F / 0°C
Control mode
(factory default setting)
Burner blocked
CauseRemedy
fault history
Boiler water temperature sensor
shorted out
Boiler water temperature sensor
cable broken
Flue gas temperature sensor
shorted out.
Communication fault programming unit (internal)
Internal faultReplace the control unit.
Boiler coding card missing, faulty or
incorrect boiler coding card.
Flue gas temperature sensor cable
broken.
Fault, supply voltage 24VReplace the control unit.
Service the equipment.
Note:
After the service, reset coding
address “24” to “0”.
Check the boiler water temperature
sensor
Check the flue gas temperature
sensor (see Vitodens 200-W
Start-up/Service Instructions).
Check connections and replace
programming unit, if required.
Plug in boiler coding card or replace,
if faulty.
Check the flue gas temperature
sensor (see Vitodens 200-W
Start-up/Service Instructions)
5727 946 v1.2
e5555
e8
e9
ea
Burner in fault mode
Internal faultCheck ionization electrode and
connecting cables, check tightness
of flue gas system.
Press “E RESET”.
The ionization current lies outside
the permiss. range.
The ionization current lies outside
the permiss. range during
calibration.
The ionization current lies outside
the permiss. range during
calibration.
Check ionization electrode and
cable. Press “E RESET”.
Check ionization electrode and
cable. Press “E RESET”.
Check ionization electrode and
cable. Press “E RESET”.
45
Page 46
Troubleshooting – Vitotronic 100, HC1
Faults displayed at the programming unit (continued)
Fault
code
ebbbb
ec
ed
ee
effff
ffff0000
ffff1111
ffff2222
ffff3333
System characteristics
Burner blockedBoiler control initiated a combustion
Burner in fault mode
Burner blockedInternal fault.Replace control unit.
Burner in a fault modeMaximum flue gas temperature
CauseRemedy
- Heat generated by boiler must be
calibration but could not complete
the process
The ionization current lies outside
the permiss. range during
calibration.
Internal fault.Replace the control unit.
At burner start, flame signal is
missing or too week.
Flame is lost immediately after it
has built (during the safety time).
exceeded (230ºF / 110ºC).
Fixed high limit switch open
(activated).
Flame signal is already present at
burner start.
removed (boiler is cycling on
temperature limits, before
calibration process is complete)
- Check the connecting cable and
the ionization electrode, check the
flue gas system (flue gas
recirculation).
- Verify pump operation
- Switching points of flow switch
marginal (not enough flow)
- Check coding card
- Check gas valve
- Check coding address 82
- Also see address 12:_
Press “E RESET”.
Check ionization electrode and
cable. Press “E RESET”.
Check ionization electrode and
cable, test ionization current, check
gas supply, check ignition and
ignition module, check condensate
drain. Press “E RESET”.
Check gas supply, check flue
gas/exhaust pipe/air intake for flue
gas recirculation, check ionization
electrode (replace if necessary)
Press “E RESET”.
Check the heating system fill level.
Bleed air from system. Press “E
RESET” after vent system has
cooled down.
Check heating system fill level.
Check the circulation pump. Bleed
air from the system. Check fixed
high limit switch and connecting
cables. Press “E RESET”.
Check the ionization electrode and
connecting cable. Press “E RESET”.
46
5727 946 v1.2
Page 47
Faults displayed at the programming unit (continued)
controlunitiftheequipmentwillno
t
Troubleshooting – Vitotronic 100, HC1
Fault
code
ffff4444
ffff8888
ffff9999
ffffaaaa
ffffcccc
ffffdddd
ffffeeee
ffffffff
No fault
code
System characteristics
Burner in a fault mode
Burner blockedBurner control unit fault.Check ignition electrodes and
Burner blocked or in a fault mode
Boiler/burner in standstillFlow switch openCheck pump operation and flow
*1
CauseRemedy
No flame signal is present.Check ionization electrode and
cable, measure the ionization
current, check the gas pressure,
check the gas valve, ignition,
ignition module, ignition electrodes
and condensate drain. Press “E
RESET”.
The gas valve closes too late.Check gas valve and both control
wiring and connections. Press “E
RESET”.
Fan speed too low at burner start.Check fan, fan supply cables, fan
power supply and control. Press “E
RESET”.
Fan not at standstill.Check the fan, the fan connecting
cables and fan control. Press “E
RESET”.
Gas valve faulty or faulty
modulation valve control; or vent
system blocked.
Strong interference (EMC) field
nearby, or faulty main PCB.
Strong interference (EMC) field
nearby, or internal fault.
Check the gas valve. check the vent
system. Press “E RESET”.
connecting cables. Check the boiler
coding card. Check whether a
strong interference (EMC) field
exists near the equipment; press
“E RESET”. Replace control unit if
the fault persists.
Restart the equipment. Replace the
control unit if the equipment will not
restart.
switch.
displayed
*1
Control mode: Boiler/burner fully operational (fault code must be verified and reset).
Burner in fault mode: Boiler control requires manual reset before burner can resume operation.
Burner blocked: If fault cause is corrected, burner resumes operation.
5727 946 v1.2
47
Page 48
Troubleshooting – Vitotronic 300-K
Retrieving fault codes from the fault memory (fault history)
The most recent 10 faults are saved and may be called up.
Faults are sorted by date. The most recent fault is fault number 1.
Fault history
1
1
18
1. Press rw andsimultaneously
for approx. 2 seconds.
2. Call up the individual fault codes
with
Note:
All saved fault codes can be deleted
with D.
3. Press.
Faults displayed at the programming unit
Red fault indicator U flashes for all faults.
The display flashes “Fault” if a fault message is issued.
Troubleshooting
1. Press.
Outdoor temp. sensor
2. Call up further fault codes
DBG-
1
101
Fault
DBG-
1
UFault symbol
2Consecutive number (1 to 10)
d5 Fault code (for explanations see
page 49)
d52
withor.
The fault can be acknowledged with
. The fault message in the display
will be hidden, but the red fault
lindicator U continues to flash. A
new fault message will be displayed
if an acknowledged fault is not
removed by the following morning.
A central fault messaging device
connected to plug gÖ will be
activated.
or
Fault display in plain text
Ext. fault
Outdoor temperature sensor
Supply sensor
DHW tank sensor (1 or 2; display
only, if a second DHW tank
temperature sensor is connected)
Return sensor
Room temperature sensor
Flue gas sensor
Collector sensor
Solar DHW sensor
Participant number
Participant fault (display only if
control unit is programmed as fault
manager)
48
Calling up acknowledged fault
messages
Press
fault will then be displayed.
Select the acknowledged fault
withor.
for approx. 2 seconds. The
5727 946 v1.2
5727 946 v1.2
Page 49
Faults displayed at the programming unit (continued)
temperaturewas3
2˚F/0˚C
temperaturesensor(suppl
y
Troubleshooting – Vitotronic 300-K
Fault display in plain text
Ext. fault
Outdoor temperature sensor
Supply sensor
DHW tank sensor (1 or 2; display
only, if a second DHW tank
temperature sensor is connected)
Room temperature sensor
Participant fault (display only if
control unit is programmed as fault
manager)
Fault
code
0000ffff
11110000
System characteristics
Control modeService “0F” is only displayed in the
Controls as if the outdoor
temperature was 32˚F / 0˚C
11118888
22220000
Vitocontrol-S, WB2B controls in a
stand-alone manner w/o supply
Calling up acknowledged fault
messages
Pressfor approx. 2 seconds. The
fault will then be displayed.
Select the acknowledged fault
with
or.
CauseRemedy
fault history
Outdoor temperature sensor shorted
out
Outdoor temperature sensor cable
broken
Common supply temperature sensor
shorted out
Service the equipment.
Note:
After the service, reset coding
address “24” to “0”.
Check outdoor temperature sensor
(see page 67)
Check common supply temperature
sensor (see page 66)
22228888
44440000
44444444
44448888
4444cccc
temperature may not be high
enough)
Mixing valve closesSupply temperature sensor of
Common supply temperature sensor
cable broken
mixing valve circuit M2 shorted out
Supply temperature sensor of
mixing valve circuit M3 shorted out
Supply temperature sensor cable of
mixing valve circuit M2 broken
Supply temperature sensor cable of
mixing valve circuit M3 broken
Check supply temperature sensor
(see page 66)
5727 946 v1.2
49
Page 50
Troubleshooting – Vitotronic 300-K
returncontrolopen
returncontrolopen
Mixingvalveprimarycircuitclosed
,
Withouttemperaturesensor:
100ofboiler1to4
codeontherespectiveVitotronic
100ofboiler1to4codeontherespectiveVitotroni
c
ofboiler1to
4
communicationmoduleofth
e
ofboiler1to
4
8D-BoilerNo.2
communicationmoduleofth
e
cable,ifrequire
d
8D-BoilerNo.2
8F-BoilerNo.4
cable,ifrequire
d
(seeaddress07:onpage9and80)
8F-BoilerNo.4(seeaddress07:onpage9and80
)
Faults displayed at the programming unit (continued)
Fault
code
55550000
55551111
55558888
55559999
66660000
System characteristics
DHW tank primary pump ON:
Set DHW temp.= set boiler water
temp., priority controls are cancelled
or
ith DHW tank primary system:
W
DHW heating is started and stopped
by DHW tank temp. sensor 2 (not
used)
With DHW tank primary system:
DHW heating is started and stopped
by DHW tank temp. sensor
DHW tank primary pump ON:
Set DHW temp.= set boiler water
temp., priority controls are cancelled
or
With DHW tank primary system:
DHW heating is started and stopped
by DHW tank temp. sensor 2 (not
used)
With DHW tank primary system:
DHW heating is started and stopped
by DHW tank temp. sensor
Boiler with maximum temp.,
CauseRemedy
DHW tank temperature sensor 1
shorted out
DHW tank temperature sensor 2
(not used) shorted out
DHW tank temperature sensor cable
broken
DHW tank temperature sensor 2
(not used) cable broken
With DHW tank primary system:
Mixing valve primary circuit closed,
no DHW heating (not used).
Control modeMaintenance or error on Vitotronic
Temperature sensor aJB shorted
out
Temperature sensor aJB cable
broken
Communication fault Vitotronic 100
8C - Boiler No. 1
8E - Boiler No. 3
Check temperature sensor
Without temperature sensor:
Set code “4b:0”
Check maintenance display or fault
100
Check and replace cascade
Vitotronic 100 and connecting
- check for assigned participant no.
- if problem persists, replace all 4
modules with part no. 7441 586.
50
5727 946 v1.2
Page 51
Faults displayed at the programming unit (continued)
Onlysolarcontrolunitfaultcode
s
ifrequired.
ifrequired.
control
codingaddress“A0”andremot
e
Troubleshooting – Vitotronic 300-K
Fault
code
99992222
99993333
99994444
9999aaaa
9999bbbb
9999cccc
9999ffff
aaaabbbb
bbbb1111
bbbb4444
System characteristics
Control mode
Only solar control unit fault codes
will be displayed
Control operation perhaps DHW
tank cold
Control modeCommunication error
Emmissions test mode
CauseRemedy
Collector temp. sensor shorted out,
connects to S1 at the Vitosolic
DHW tank temp. sensor shorted
out, connects to S3 at the Vitosolic
Temp. sensor shorted out, connects
to S2 at the Vitosolic
Collector temp. sensor cable
broken, connects to S1 at the
Vitosolic
DHW tank temp. sensor cable
broken, connects to S3 at the
Vitosolic
Temp. sensor cable broken,
connects to S2 at the Vitosolic
Fault
Solar control unit; displayed if a
fault without fault code occurs at
the solar control unit
DHW tank primary system
configuration error:
Code “55:3” has been set, but plug
aJB is not plugged in (not used)
and/or
Codes “4C:1” and “4E:1” have not
been set
Programming unit
Internal electronics faultCheck electronics PCB and replace,
Check solar control unit sensor
Check solar control unit
Insert plug aJB and check the
code (not used).
Check connections and replace
programming unit if required.
bbbb5555
bbbb6666
bbbbaaaa
bbbbcccc
Control mode
Constant modeInvalid hardware recognizedCheck the control software circuit
Communication error Vitotrol
remote control, heating circuit A1
Communication error Vitotrol
remote control, heating circuit M2
Communication error Vitotrol
remote control, heating circuit M3
module
board and confirm the coding address:
- Enter coding 2 (see page 80 for
instructions).
- Change code 8A to 176.
- Confirm coding 92:186
Check PCB and replace, if required.
Check connections, lead/cable,
coding address “A0” and remote
control DIP switches.
Replace the communication module.
51
Page 52
Troubleshooting – Vitotronic 300-K
Faults displayed at the programming unit (continued)
Fault
code
cccc2222
cccc4444
CCCCcccc5555
cccceeee
ccccffff
dddd6666
dddd7777
dddd8888
ddddaaaa
ddddbbbb
ddddcccc
dddddddd
ddddeeee
ddddffff
System characteristics
Control mode
Control mode, max. pump speed
(Not used)
Control mode
Control mode without room
influence
CauseRemedy
Cable break KM BUS to solar
control unit.
Communication error with function
extension 0 to 10 V
Communication fault, variable
speed circulation pump, heating
circuit connection set
Communication error Plug-in
adaptor for external safety
equipment
Error
LON communication module
Fault at DE1 in plug-in adaptor for
external safety equipment (not
used)
Fault at DE2 in plug-in adaptor for
external safety equipment (not
used)
Fault at DE3 in plug-in adaptor for
external safety equipment (not
used)
Room temperature sensor shorted
out,
Heating circuit A1
Room temperature sensor shorted
out,
Heating circuit M2
Room temperature sensor shorted
out,
Heating circuit M3
Room temperature sensor cable
broken,
Heating circuit A1
Room temperature sensor able
broken,
Heating circuit M2
Room temperature sensor cable
broken,
Heating circuit M3
Check KM BUS cable and the solar
control unit
Without solar control unit:
Set code “54: 0”
Check connections and
cables/leads; replace the function
extension, if required
Without function extension:
Set code “9d: 0”
Check setting of coding
address ”30” Set to “0” 30:”0”
Check plug-in adaptor for external
safety equipment and cables/leads
Without plug-in adaptor:
Set coding “94: 0”
Replace communication module
Check connections at “DE1” to
“DE3”
Check room temperature sensor
Check the room temperature sensor
and the DIP switch on the Vitotrol
52
5727 946 v1.2
Page 53
Faults displayed at the programming unit (continued)
Troubleshooting – Vitotronic 300-K
LON participants fault messages
Preconditions:
The control unit must be programmed
as fault manager (code “79:1”)
Fault
code
00001111
to
System characteristics
Control modeA participant, e.g. 12
99998888
99999999
Participant
11112222
CauseRemedy
Download fault code to participant
(Vitotronic 200-H), has
developed a fault
or
There is no connection to the
participant
Fault message active at
Vitocom 300
or
Fault at the Vitocom 300
or
No connection to the Vitocom
300
See the Installation and Service instructions
of the relevant control unit.
- Check coding
- Check LON communication module
- Update participant list
- Carry out a participant check
Check external connections at Vitocom 300
See separate Installation and Service
instructions
- Check coding
- Check LON connection cable
- Update participant list
- Carry out a participant check
5727 946 v1.2
53
Page 54
Function description – Vitotronic 100, HC1
Boiler temperature control
Brief description
The boiler water temperature is
regulated by controlling a modulating
burner.
The set boiler water temperature
set-point is controlled by Vitotronic
300-K.
Functions
The boiler water temperature is
ecorded separately:
r
Fixed high limit (FHL)
Boiler temperature sensor KTS
(changes in resistance NTC)
Control sequence
Boiler goes cold
(set value 4ºC below set point)
The burner start signal is set to the set
boiler water temperature less (=less
7.2ºF or 4ºC) and the burner starts its
own monitoring program.
Coding addresses which influence the
boiler temperature control
06 (see page 80).
For a description, see the coding
overview.
Upper control limit.
Electronic maximum limit
Setting range: 20 to boiler coding card
default
The maximum boiler water temperature
limit can be adjusted via coding
address 06.
Boiler heats up.
The burner shutdown point is
determined by the switch-off
differential of (=less 14.4ºF or 8ºC)
above set point.
Note:
Value on display shown in K (Kelvin).
1 K = 1.8 Fahrenheit degrees or 1
Celsius degree.
Air bleed program
Note:
lose the gas shut-off valve when
C
operating the air bleed program.
The air bleed program is activated via
coding address 2F:1 (the display shows
EL).
During the air bleed program, the
circulation pump will be alternately
switched ON and OFF for 30 seconds
respectively over a period of 20
minutes.
The burner is switched OFF during the
air bleed program.
The program is automatically
deactivated after 20 minutes, and the
coding address is set to 0.
5727 946 v1.2
54
Page 55
Cascade control unit
Brief description
Function description – Vitotronic 300-K
The supply temperature is regulated by
starting or stopping the burner or by
starting/stopping individual burners.
The boilers will be controlled to the set
boiler water temperature determined by
the cascade control (stand-alone type
of control).
Subject to the system design, you may
select between one gross calorific
strategy and two net calorific
strategies.
Set supply temperature
The set supply temperature is
termined from
de
the set supply temperature set-point
values of system circuit A1 and
mixing valve circuits M2 and M3,
the set DHW temperature and
external demands (e.g. the set
supply temperature defaulted by
coding address 9b or via the Input
Module 0 to 10 V).
The boiler sequence (see page 59) can
be determined via coding 2 and the
boiler sequence selection.
Coding addresses which influence the
cascade control
35 to 3F, 41 to 4F.
For a description, see the coding
overview.
Upper control limit
Electronic maximum system supply
temperature limit.
Setting range: 68 to 26˚ F / 20 to
127˚C.
The maximum supply temperature limit
can be adjusted via coding address 37.
This value must be set no higher than
the lowest value of coding address 06
of all connected Vitotronic 100, HC1.
Lower control range limit
Electronic minimum system supply
temperature limit.
Setting range: 68 to 261˚ F / 20 to
127˚ C.
The minimum supply temperature limit
can be adjusted via coding address 36.
5727 946 v1.2
55
Page 56
Function description – Vitotronic 300-K
Cascade control (continued)
Control sequence
Stand-alone type of control: Parallel boiler control
(coding 3b : 0 without supply temperature sensor or
coding 3b : 1 with supply temperature sensor)
The cascade control unit defaults the
set boiler water temperature to all
currently active boilers.
Every Vitotronic 100 individually
regulates the dafaulted set
temperature.
The control sequence is subject to the
start-up and shutdown criteria selected
with control strategy (coding address
3C):
The contro deviation is calculated from
the set supply temperature and the
actual supply temperature to determine
the start-up and shutdown criteria.
Gross calorific strategy (Condensing strategy)
It is the aim of the gross calorific
strategy to operate as many boilers as
possible at the lowest output
(modulation) level.
Start-up criterion
Boilers are started via an output
statement (coding 3d : 1).
An additional boiler will be started
when the currently required output can
also be achieved by the currently active
boiler plus the next boiler in the boiler
sequence (see page 66).
Without supply temperature sensor:
The control deviation is calculated from
the set boiler water temperature and
the estimated average actual boiler
water temperture of the active boiler to
determine the start-up and shutdown
criteria. Only those boilers are taken
into consideration whose boiler circuit
pumps are not switched OFF.
Advantages
Optimum utilization of the
Long burner operating times
Shutdown criterion
The boiler is shut down via a shutdown
integral. The shutdown criterion is met
when the shutdown integral exceeds a
limit set via coding address 46, and the
boiler started last will be shut down.
condensing effect (as many boilers
active as possible)
56
5727 946 v1.2
Page 57
Cascade control (continued)
Net calorific strategy 1
Function description – Vitotronic 300-K
Conventional boilers are preferably
operated at their upper output range, to
reliably prevent the formation of
condensate due to low return
temperatures.
With net calorific strategy 1, an
additional boiler will only be started if
the maximum output of all currently
active burners is insufficient to achieve
the set supply temperature.
A boiler will be shut down, when the
remaining boiler(s) can achieve the
required output on its/their own.
Start-up criteria
The boiler is started via a start-up
integral.
The start-up criteria is met when the
start-up integral exceeds a limit set via
coding address 45, and the next boiler
in the sequence will be started (see
page 59).
Benefit:
As few boilers as possible are active.
Shutdown criteria
The boiler is shut down via an output
statement (coding 3d: 1).
A boiler is shut down when the
currently required output can be
achieved without the boiler which was
started last.
Net calorific strategy 2
With the net calorific strategy 2, an
additional boiler will only be started if
the maximum output of all currently
active burners is insufficient to achieve
the set supply temperature.
A boiler will be shut down if the burner
was returned to its minimum output
because of a large negative control
deviation, and the output is then still
too high.
Start-up criteria
The boiler is started via a start-up
integral.
The start-up criteria is met when the
start-up integral exceeds a limit set via
coding address 45, and the next boiler
in the sequence will be started (see
page 59).
Benefit:
Long burner operating times
Shutdown criteria
The boiler is shut down via a shutdown
integral. The shutdown criteria is met
when the shutdown integral exceeds a
limit set via coding 46, and the boiler
started last will be shut down.
5727 946 v1.2
57
Page 58
Function description – Vitotronic 300-K
Cascade control (continued)
Control strategy example
Two boiler system with modulating burners and separate flue gas systems:
Boiler 1: 100% rated output (basic load set to 25%)
Boiler 2: 100% rated output (basic load set to 25%)
Gross calorific strategy (coding 3C: 0)
Start-upSwitching OFF
Rated output in %
100
100
200
150
100
TotalBoiler 2Boiler 1
66
25
25
25
0
0
0
Time
Rated output in %
100
66
25
100
25
200
150
100
TotalBoiler 2Boiler 1
25
0
0
0
Net calorific strategy 1 (coding 3C: 1)
Start-upSwitching OFF
Rated output in %
100
100
200
150
100
TotalBoiler 2Boiler 1
50
25
50
25
0
0
0
Time
Rated output in %
100
50
25
100
50
200
150
100
TotalBoiler 2Boiler 1
25
0
0
0
Time
Time
58
5727 946 v1.2
Page 59
Cascade control (continued)
Net calorific strategy 2 (coding 3C: 2)
Start-upSwitching OFF
Function description – Vitotronic 300-K
100
50
25
0
100
50
0
200
150
100
Rated output in %
TotalBoiler 2Boiler 1
25
0
Time
Boiler sequence
The boiler sequence is determined by
he boiler sequence selection and the
t
following coding addresses (see also
page 86):
38Changing the lead boiler and the
boiler sequence.
38: 1 Every 1
month, the boiler with the
burner which has
operated for the shortest
number of hours becomes
lead boiler.
38: 2After 200 to 20,000 run
hours, the boiler with the
next higher number
(coding address 07 of
Vitotronic 100) becomes
lead boiler.
Via the ECO threshold, every boiler can
be disabled or enabled subject to the
outdoor temperature. The ECO control
becomes disabled, if the boiler is
required to achieve the set supply
temperature, when enabled boilers
have failed. At least the lead boiler
remains active if all boilers in a system
are disabled by the ECO control.
5727 946 v1.2
59
Page 60
Function description – Vitotronic 300-K
Heating circuit control
Brief description
The control unit provides control
circuits for one high temperature
(boiler) circuit and two mixing valve
circuits.
The set supply temperature of every
heating circuit results from the outdoor
temperature, the set room temperature,
the operating mode and the heating
curve.
The supply temperature of the system
circuit corresponds to the common
system supply temperature.
The supply temperature of the mixing
valve circuits is regulated by the
stepped opening or closing of the
mixing valves.
The mixing motor control changes the
actuating and pause times subject to
the control difference
(control deviation).
Coding addresses which influence the
heating circuit control
9F,A2 to A7, A9, C3 to C8, F1, F2
For a description, see the coding
overview (see page 86).
Time program
The control unit timer changes in
accordance with the times programmed
in the room heating and DHW heating
program between the heating with
normal room temperature and heating
with reduced room temperature
operating modes.
Every operating mode has its own set
level.
Outdoor temperature
A heating curve must be set up for
matching the control unit to the
building and the heating system.
The heating curve characteristics
determine the set boiler water
temperature subject to outdoor
temperature. An average outdoor
temperature (dampened) is used for
control purposes. This comprises the
actual and the adjusted outdoor
temperature.
Functions
The high temperature (boiler) circuit is
subject to the boiler water temperature
and its control range limits.
The heating circuit pump is the
controlling element. The mixing valve
circuit supply temperature is recorded
by the supply temperature sensor.
5727 946 v1.2
60
Page 61
Heating circuit control (continued)
Function description – Vitotronic 300-K
Domestic hot water temperature
With priority control:
The set supply temperature will be
set to 32˚F / 0˚C during DHW
heating.
The mixing valve closes, and the
heating circuit pumps are switched
OFF.
Without priority control:
The heating circuit control unit
continues to operate with the same
set value.
Room temperature
In conjunction with remote control and
room temperature input (observe
coding address b0).
Compared to the outdoor temperature,
the room temperature has a greater
influence on the common set supply
temperature. This influence may be
adjusted via coding address b2.
In conjunction with the mixing valve
circuit:
For control differences (actual value
deviation) above 3.6˚F / 2˚C room
temperature, the influence can be
increased again (via coding address b6,
quick heat-up/quick setback).
Quick heat-up:
The set room temperature must be
raised by a minimum of 3.6˚F / 2˚C
by:
Pressing party button
Changing from heating with reduced
temperature to heating with normal
temperature.
Start-up optimisation.
Quick heat-up will stop when the set
room temperature has been reached.
.
Heating circuit pump logic
(economy circuit)
The heating circuit pump is switched
OFF (set supply temperature set to 0˚C /
32˚F), when the outdoor temperature
exceeds the value selected via coding
address A5.
Extended economy circuit
The heating circuit pump is switched
OFF, and the set supply temperature is
set to 32˚F / 0˚C, if:
The outdoor temperature exceeds the
value selected via coding address A6.
The set room temperature is reduced
via coding address A9.
In conjunction with the mixing valve
circuit:
The mixing valve has been closed for
12 minutes (mixing valve economy
function, coding address A7).
Slab curing function
(only in conjunction with a mixing valve
circuit).
Please note:
Four different temperature profiles can
be selected for drying the slab. These
profiles are activated via coding
address F1.
When the slab curing function is
activated, the heating circuit pump of
the mixing valve circuit is switched
ON, and the supply temperature will be
held at the selected profile. After
completion (30 days), the mixing valve
circuit will be regulated automatically
via the set parameters.
System dynamics – mixing valve circuit
(only in conjunction with a mixing valve
circuit)
You can influence the control
characteristics of the mixing valve via
coding address C4.
Central operation
Central operation for all downstream
heating circuits can be programmed via
coding address 7A.
The heating and holiday program then
applies to all heating circuits in the
system.
The programming unit of the other
heating circuits displays central control
when the heating program and holiday
program buttons are activated.
Any set holiday programs in the
heating circuit programming units will
be deleted.
Party and economy buttons on all
control units are without effect.
Frost protection
When the outdoor temperature falls
below 34˚F / 1˚C, a supply
temperature of at least 50˚F / 10˚C
will be safeguarded.
For changes, see coding address A3,
variable frost limit.
Quick setback:
The set room temperature must be
reduced by a minimum of 3.6˚F / 2˚C
by:
Pressing economy button.
Changing from room heating with
normal temperature to heating with
reduced temperature.
Shutdown optimisation.
Quick setback will stop when the set
room temperature has been reached.
5727 946 v1.2
61
Page 62
Function description – Vitotronic 300-K
Heating circuit control (continued)
Supply temperature control
Differential temperature:
The differential temperature may be
adjusted via coding address 9F; factory
supplied setting 15˚F / 8˚C.
110
230
The differential temperature is that
minimum temperature differential by
which the common supply temperature
should be higher than the currently
required supply temperature of the
mixing valve circuit.
System with only one mixing valve
circuit:
The common set supply temperature
will be automatically held 15˚F / 8˚C
above the set supply temperature of
the mixing valve circuits.
System with high temperature
(boiler) circuits and mixing valve
circuits:
The common set supply temperature
operates in accordance with its own
heating curve. The differential
temperature of 15˚F / 8˚C towards
the set supply temperature of the
mixing valve circuits is set up at the
factory.
Upper control limit
Electronic maximum limit:
Setting range: 34 to 261˚F / 1 to
127˚C.
Changes via coding address C6.
Please note:
The maximum limit is no replacement
for the underfloor heating system
temperature limiter.
87
189
8K
+8K
+20/ 68-20/-4
Supply temperature °C / °F
Outdoor temperature in °C / °F
A Max. common supply temperature
B Slope = 1.8 high temperature
(boiler) circuit
C Slope = 1.2 mixing valve circuit
D Common supply temperature (at a
differential temperature = 15˚F /
8˚C)
E Minimum common supply
temperature
Lower control range limit
Electronic minimum limit:
Setting range: 34 to 261˚F / 1 to
127˚C.
Changes via coding address C5 (only
effective in standard mode).
Control sequence
Mixing valve circuit
he mixing valve motor will not be
T
activated within the neutral zone
(±2˚F / 1˚C).
62
Supply temperature falls
(set value -2˚F / –1˚C)
The mixing valve motor receives the
open signal.
The signal duration lengthens with an
increasing control differential. The
duration of pauses reduces with an
increasing control differential.
Supply temperature rises
(set value +2˚F / 1˚C)
The mixing valve motor receives the
close signal.
The signal duration lengthens with an
increasing control differential. The
duration of pauses reduces with an
increasing control differential.
5727 946 v1.2
Page 63
DHW tank temperature control
Brief description
Function description – Vitotronic 300-K
The DHW tank control logic is a
set-point control. It is the result of
starting and stopping the DHW pump.
The switching differential is ±4.5˚F /
2.5˚C.
Functions
Time program
n automatic program or an individual
A
time program may be selected for DHW
heating and the control of the DHW
recirculation pump.
Compared with the space heating
circuit’s heat-up phase, DHW heating
in automatic mode starts 30 minutes
earlier.
The individual time program enables up
to four switching periods per day to be
set via the time switch to control the
DHW heating/heating and the DHW
recirculation pump.
Any DHW tank heating sequence will
be completed, independent of the time
program.
During DHW tank heating, a constant
boiler supply temperature will be set
(36˚F / 20˚C higher than the set DHW
tank temperature, adjustable via coding
address 60) and space heating is
switched OFF (optional DHW tank
priority).
In conjunction with coding address 7F
7F: 1 Detached house:
Automatic mode:
For systems with two or three space
heating circuits, the heating times for
the first of the existing heating
circuits will be applied.
Individual time program:
The switching times for DHW heating
and the DHW recirculation pump
have the same effect on all heating
circuits.
Coding addresses which influence the
DHW tank control
54 to 75, 7F, A2.
For a description, see the coding
overview.
7F : 0 Apartment building:
Automatic mode:
For systems with two or three
heating circuits, the heating times
for the respective heating circuit
will be applied.
Individual time program:
The switching times for DHW heating
can be adjusted separately for each
heating circuit.
DHW priority
With DHW priority (coding A2: 2):
The set supply temperature will be
set to 32˚F / 0˚C while the DHW
tank is being heated.
The mixing valve closes, and the
heating circuit pumps are switched
OFF.
With DHW priority:
The heating circuit control unit
continues to operate with the same
set value.
Frost protection
The DHW tank will be heated to 68˚F /
20˚C, if the DHW temperature falls
below 41˚F / 5˚C.
5727 946 v1.2
Auxiliary functions – DHW heating
This function is activated by providing
a second set DHW temperature via
coding address 58 and activating the
th
DHW phase for DHW heating.
4
Set DHW temperature
The set DHW temperature can be
adjusted between 50 and 140˚F / 10
and 60˚C. The set range can be
expanded to 203˚F / 95˚C via coding
address 56.
You can select the set DHW
temperature at the programming unit of
the control and at every Vitotrol 300
remote control unit (if installed).
You can determine the allocation to
individual heating circuits via coding
address 66.
DHW recirculation pump
It delivers hot water to the draw-off
points at adjustable times. Up to four
control periods can be set at the timer.
Auxiliary circuits
The DHW heating can be disabled or
enabled by changing over the heating
program.
System with DHW tank heating system
The above functions also apply in
conjunction with calorifiers.
Set the following codings:
4C: 1, 4E: 1, 55: 3.
For a description, see the coding
overview.
Systems with Vitosolic
A third DHW temperature set-point can
be programmed via coding address 67.
Reloading suppression will be active
below the set temperature. The DHW
tank is heated only by the solar heating
system.
63
Page 64
Function description – Vitotronic 300-K
DHW tank temperature control (continued)
Control sequence
Pump delay
The DHW pump continuous operation
(coding 62: 10) after the DHW tank
heating, until:
– the actual temperature is 9˚F / 5˚C
higher than the set DHW
temperature or
– the maximum time delay (adjustable
via coding address 62) has been
reached.
Without the pump time-delay for
DHW tank heating (coding 62: 0).
Coding 55: 0:
DHW heating
The DHW tank goes cold
(set value 4.5˚F / –2.5 ˚C, adjustable
via coding address 59)
The common supply temperature is
adjusted 36˚F / 20˚C higher than the
set DHW (adjustable via coding address
60).
The DHW tank is hot
(set value +4.5˚F / 2.5˚C)
The common set supply temperature is
returned to the weather-compensated
value.
Coding 55: 1:
Adaptive DHW tank heating
With adaptive DHW tank heating, the
speed of the temperature rise during
DHW heating is taken into account.
Also taken into account is the question
of whether the boiler will be required to
supply heat after the DHW tank has
been heated or whether residual boiler
heat should be transferred to the DHW
tank.
Accordingly, the control unit
determines the burner and DHW
recirculation pump shutdown point to
prevent the set DHW temperature
being substantially exceeded after the
DHW tank has been heated.
Coding 55: 2:
DHW tank temperature control with
2 DHW tank temperature sensors
st
The 1
DHW tank temperature sensor
enables the DHW pump, and is
evaluated for stop conditions during
nd
the pump run-on time. The 2
DHW
tank temperature sensor (inside the
cold water inlet) is designed to
prematurely start DHW tank heating
when large quantities of DHW are
drawn off as well as to prematurely
stop DHW tank heating if no DHW is
drawn.
Coding 55: 3:
DHW tank control – DHW heating (for
DHW loading systems only)
The DHW tank goes cold
(set value -4.5˚F / –2.5˚C, adjustable
via coding address 59),
The common set supply temperature
is adjusted 36˚F / 20˚C higher than
the set DHW temperature (adjustable
via coding address 60).
The primary DHW pump is switched
ON.
The three-way mixing valve opens
and then regulates to the defaulted
set value.
The DHW pump cycles (short term
ON and OFF) until the set supply
temperature has been reached, then
it runs constantly. If, during DHW
tank heating, the actual value stays
below the required set supply
temperature, then the DHW pump
will temporarily cycle again.
The DHW tank is hot
(1stDHW tank temperature sensor:
Actual value ≥ set value
and
2ndDHW tank temperature sensor:
Actual value > set value -2.7˚F /
–1.5˚C)
The common set supply temperature
is returned to the weathercompensated value;
The DHW pump:
– is immediately switched OFF, if the
three-way mixing valve is open
or
– is switched OFF after run-on time
adjustable via coding 62.
64
5727 946 v1.2
Page 65
Components from the parts list
Components – Vitotronic 300-K
The main PCB comprises:
Relays and outputs for controlling .
pumps and actuators.
Slot for power supply unit.
Main PCB low voltage
The main PCB comprises:
onnection plug for sensors,
C
communication connections and
external connections.
Slot for PCB, LON communication
module, programming unit and
Optolink PCB.
Supplementary PCB
When replacing the PCB:
1. Record the coding and adjustments
made at the control unit.
2. Replace the PCB.
3. Set coding 8A: 176, and coding
address 92 to 92: 186.
Mixing valve extension PCB
Mixing valve extension
s
upplementary PCB
This is plugged into the mixing valve
extension PCB.
All data is processed and outputs
(relay) are selected.
Power supply unit PCB
The power supply unit PCB comprises
he low voltage supply for all electronic
t
equipment.
Programming unit
Setting the:
Heating program
Set values
Switching times
Heating curve (slope and shift)
Date
Time
Economy and party mode
Coding
Override switch for testing flue gas
with briefly raised boiler water
temperature.
The following functions are triggered in
position h:
Starting all pumps.
Mixing valve in control function.
Front panel with heating circuit
elector keys
s
Display and selection of the heating
circuit.
Programming unit ON / OFF
switch
The programming unit comprises:
Fuse
Mains ON / OFF switch.
The PCB comprises the relay for the
ontrolling the mixing valve motor and
c
the heating circuit pump of the mixing
valve circuits.
5727 946 v1.2
Fuses
F1: 6.3 A (slow), 250 V,
ax. power loss ኢ 2.5 W,
m
to protect the actuators, pumps, and
all electronics.
LON communication module
PCB for data exchange with:
Vitotronic 200-H
Vitocom 300
The communication interruption will be
displayed.
65
Page 66
Components – Vitotronic 300-K
Components from the parts list (continued)
DHW tank temperature sensor
720
700
680
660
640
620
600
580
560
Resistance in
540
020406080100
32 68104 140 176 212
DHW tank temperature in °C / °F
Common supply temperature
sensor (Low-loss header)
760
740
720
700
680
660
640
620
600
580
560
540
Resistance in
0
20 40 60 80 100 120 140
3268141 176 212 248 284104
Flow or return temperature in °C / °F
Connection
See page 19.
Check sensor
1. Remove wire from terminal X2.7.
2. Check the sensor resistance of the
plug at terminals 1 and 2 or 2 and 3
(if a second DHW tank temperature
sensor has been connected).
DHW tank
Resistance in ΩΩΩΩ
temperature
in ˚F / ˚C
104 / 40
122 / 50
140 / 60
578
597
616
Connection
See page 16.
Check sensor
1.Remove wire from terminal X2.4.
2.Check the sensor resistance of the
plug at terminals 1 and 2.
3. Compare measurement with the
actual temperature displayed (for
scanning, see page 41).
Check the installation and replace
sensor, if necessary, in case of
severe deviation.
3.Compare measurement with the
actual temperature displayed (for
scanning, see page 41).
Check the installation and replace
sensor, if necessary, in case of
severe deviation.
0 to +100˚C
During storage and transport:
–4 to158˚F
–20 to +70˚C
66
5727 946 v1.2
Page 67
Components from the parts list (continued)
Outdoor temperature sensor
Components – Vitotronic 300-K
Connection
See page 16.
Check sensor
1. Remove wire from terminal X2.2.
1.
600
580
560
540
520
4.
2.
5.
3.
2. Check the sensor resistance at
terminals 1 and 2 of the plug.
Outdoor
temperature in
˚F / ˚C
14 / -10
32 / 0
68 / 20
3. Disconnect cores from the sensor, if
actual values deviate severely from
the curve, repeat the sensor
measurement and compare with the
actual temperature (for scanning,
see page 41).
4. Depending on the result, replace
cable or outdoor temperature sensor.
5. Scan actual temperature (for
scanning, see page 41).
Specification
Protection:IP 43
Permissible ambient temperature
during operation, storage and
transport:
Resistance
in ΩΩΩΩ
480
500
546
–40 to 158˚F
–40 to +70˚C
500
480
460
440
420
Resistance in
400
-40-30-20-100102030
5727 946 v1.2
-40-22-41432506886
Outdoor temperature in °C / °F
67
Page 68
Components – Vitotronic 300-K
Fuse
F1 T4 A, 250V
Max. power loss ኢ 1.6W
A1 Power supply module
68
5727 946 v1.2
Page 69
Mixing valve circuit extension kit
Mixing valve motor
lug in the mixing valve motor
A P
| Mixing valve motor open
~ Mixing valve motor close
B Connect to X1 or X3 on the A4
module
Components – Vitotronic 300-K
Changing the rotational direction
Remove the cover and reinsert 3-pole
plug A turned by 180˚.
Test
The relay test of the control unit moves
the mixing valve to open and close.
Manual mixing motor adjustment
Lift the motorized lever up,
unhook the mixing valve handle and
remove plug A.
For 24V actuators please
refer to instructions supplied
with the actuator.
Specification
Rated voltage:120 VAC~
Rated frequency:60 Hz
Power consumption: 4 W
Protection:IP 42
Torque:3 Nm
Run time from
close to open:120 sec
Power supply via KM BUS.
Safety class:III
Protection:IP 30
Permiss. ambient
1 2 3 4
temperature:
In use:
32 to 104˚F
0 to +40˚C
In storage and transport:
–4 to+149˚F
–20 to +65˚C
Setting range for
Normal set room temp:
50 to+86˚F
10 to 30˚C
adjustable between
37 to 73˚F
3 to 23˚C
or
63 to 97˚F
17 to 37˚C
via coding address E1
Reduced set room temp:
37 to 97˚F
1 2 3 4
3 to 37˚C
Battery type:Use alkaline
manganese
batteries
type MICRO-
LR03 (AAA) which
do not contain
pollutants
When connecting a separate room
temperature sensor, set DIP
switch S30.3 to ON.
1 2 3 4
ON
74
5727 946 v1.2
Page 75
Remote control (continued)
Connecting several remote control units
When connecting several remote controls to the control unit, install a terminal box on site.
Version 1
Components – Vitotronic 300-K
C
max.
50ft. / 15m
}
A
A To control unit A2 terminal aVG
B Terminal box (on site)
C Vitotrol 200/300
D Vitotrol 200/300
E Vitotrol 200/300
D
max.
On-site connection via terminal box:
Connect in accordance with the
diagram.
The total length of all KM BUS cables
should be limited to 164ft. / 50m.
E
max.
50ft. / 15m50ft. / 15m
B
5727 946 v1.2
75
Page 76
Components – Vitotronic 300-K
Remote control (continued)
Version 2
}
A
max. 50ft. / 15m
CD
max.
50ft. / 15m
max. 50ft. / 15m
E
F
B
A To control unit A2 terminal aVG
B Terminal box (on site)
C Vitotrol 200/300
D Vitotrol 200/300
E Vitotrol 200/300
F Further BUS participants
If several remote control units and
additional KM BUS participants are
connected, make the connections via
a terminal box (on-site) as shown in
the diagram.
The total length of all KM BUS cables
should be limited to 164ft. / 50m.
76
5727 946 v1.2
Page 77
Components – Vitotronic 300-K
Room temperature sensor
The room temperature sensor measures the actual room temperature, if the remote Vitotrol unit cannot be installed in a
suitable location.
600
590
580
570
560
550
540
530
520
510
Resistance in
500
0
510152025303540
3241505968778695104
Room temperature in °C / °F
Connection
See page 71 to 76.
Check sensor
1. Disconnect the wires from the
sensor.
2. Check the sensor resistance at
terminals 9 and 13b.
Room temperature
in ˚F / ˚C
50 / 10
59 / 15
77 / 25
3. Compare measurement with the
actual temperature displayed (for
scanning, see page 41).
Check the installation and replace
sensor, if necessary, in case of
severe deviation.
For external control of the boiler/supply temperature via a 0 to 10VDC signal
30 to 120˚C or 10 to 100˚C
(86 to 248˚F or 50 to 212˚F)
or
to signal reduced mode and regulate a heating circuit pump to a lower speed.
24V
5V
Electronics
F1
50mA
(slow)
L1
NS Ö P1 2 31 2 3
40
120 VAC
A
ON
OFF
157144145
fÖPower connection
aVF 0 to 10VDC input
aVG KM BUS to control unit
aBJ Potential free output contact
DIP switch
1 to 3:
1:
2:
3:
4:
4:
Function
OFF
Switch for pre-set value
ON
Reduced mode – system circuit A1
ON
Reduced mode – mixing valve circuit M2
ON
Reduced mode – mixing valve circuit M3
ON
Pre-set value default 10 to 100˚C / 50 to 212˚F
OFF
Pre-set value default 30 to 120˚C / 86 to 248˚F
B
1 2 3 4
_
+
A Power supply
(provide disconnect if required by
code)
B DIP switch (see table)
Note:
For switches 1 to 3, only one switch may be set to ON.
78
5727 946 v1.2
Page 79
Resetting codings to the factory setting
2F:0Airbleedprogram/programdisabled
.
1. Press w and rw simultaneously
for approx. two seconds, until the
first two arrows appear in the
display.
2. Press D.
Coding Level 1
Calling up coding level 1
1. Press “9“ + “w“ simultaneously
for approx. 2 seconds.
2. Press “/” for the required
coding address, the address flashes.
5. “” to confirm. The display briefly
shows “accepted”, and the address
flashes again.
6. “/” to select other addresses.
Coding – Vitotronic 100, HC1
3. Press “” to confirm.
4. “/” for the selected value.
7. Press “9“ + “w“ simultaneously
for approx. 1 second. Coding level 1
is terminated.
Summary
Coding (factory default setting)Possible change
System design
00: 1No function00: 0Boiler control connected to the cascade; this
automatically occurs if 01: 2 has been programmed
System type
01: 1Single boiler system01: 2Multi-boiler system with cascade control
(e.g. Vitocontrol-S, WB2B)
06: *1 Maximum boiler water temperature limit.06: 20
to
06: *1
Boiler
07: 1Consecutive boiler number in multi-boiler systems
(in conjunction with coding address 01)
Air bleed / filling
2F: 0Air bleed program/program disabled.
*1
The factory setting and upper limit is defaulted by the boiler coding card.
07: 2
to
07: 4
2F:1 Air bleed function enabled
2F:2 Filling function enabled
Maximum boiler water temperature limit
adjustable from 68˚F to *1 / 20˚C to *1
Consecutive boiler number in multi-boiler systems
(in conjunction with coding address 01)
5727 946 v1.2
79
Page 80
Coding – Vitotronic 100, HC1
Coding Level 2
Calling up coding level 2
1. Press “w” and “rw”
simultaneously for approx. 2
seconds. until the first two arrows
appear in the display; confirm with
2. Press “” to confirm.
3. Press “
coding address, the address flashes.
4. Press “” to confirm.
5. “
/” for the required
/” for the selected value.
6. “
” to confirm. The display briefly
shows “accepted”, and the address
flashes again.
7. “/” to select other addresses.
8. Press “w” and “rw”
simultaneously for approx. 1 sec.
Coding level 2 is terminated.
Overall summary
Coding (factory default setting)
System design
00: 1No function00: 0Boiler control included in cascade; this automatically occurs if 01: 2
System type
01: 1Single boiler system01: 2Multi-boiler system with cascade control
Boiler/burner
06: *1 Maximum boiler water
temperature limit
Boiler
07: 1Consecutive boiler number in
multi-boiler systems
(in conjunction with coding
address 01)
Boiler/burner
11:≠9No access to the coding
addresses for parameters of the
combustion controller
12: 0Special function OFF
Always reset to 12:0 if
“possible change” used.
21: 0No maintenance interval
(operating hours) selected
23: 0No time interval for burner
service selected
24: 0The service display is reset24: 1Service display (value displayed automatically)
28: 0No burner interval ignition28: 1
2E: 0KM-BUS connection of
power/pump module not
recognized
*1
The factory setting and upper limit is defaulted by the boiler coding card.
Possible change
has been programmed
(e.g. Vitotronic 300-K)
06: 20
to
06: *1
07: 2
to
07: 4
11: 9Access open to the coding addresses for the parameters of the
12: 1
12: 2
21: 1
to
21:100
23: 1
to
23: 24
to
28: 24
2E: 1KM-BUS connection of power/pump moduleautomatically recognized.
Maximum boiler water temperature limit adjustable from 68˚F to *1 /
20˚C to *1
Consecutive boiler number in multi-boiler systems
(in conjunction with coding address 01)
combustion controller (see coding address 82).
Special function ON:
During calibration, the control automatically sets the boiler water
temperature to max.
If automatic calibration is initiated, the boiler will not start unless the
temperature falls below 108°F / 42°C (see fault Eb before adjusting).
Number of hours run before the burner is serviced is adjustable from 0
to 100
(each increment = 100h)
Time interval adjustable from 1 to 24 months
Time interval adjustable from 1 to 24 hr. The burner is forced-started
once every 30 sec. within selected time interval.
5727 946 v1.2
80
Page 81
Coding – Vitotronic 100, HC1
2F:0Airbleedprogram/fillprogramdisabled
Pumpincontrolfunction
80:1Afaultmessageisdisplayed,providingafaulti
s
F5:12Delayofftimeofthecirculationpumpintheheating
(notused)
heatingcircuitconnectionwillbestarted10time
s
Coding 2 (continued)
Coding (factory default setting)Possible change
Boiler
2F: 0Air bleed program/fill program disabled
32: 0 Signal “External blocking”: acting on the boiler
circuit connection set circulation pump:
Pump in control function
38: 0 Status burner control unit: Operational (no fault)38: ≠0Status fault, burner control unit
53: 1 Do not adjust
76: 0 Without cascade communication module76: 2With cascade communication module; automatic
80: 1 A fault message is displayed, providing a fault is
active for at least 5 sec
82: 0 Operation with natural gas82: 1Operation with LPG (only adjustable if coding
85: 0Standard mode85:1Manual calibration of the combustion controller
88: 0 Temperature display in ºC (Celsius)88: 1Temperature display in ºF (Fahrenheit)
F5: 12 Delay off time of the circulation pump in the heating
circuit connection set in heating mode: 12 min
(not used)
F6: 0Circulation pump in the heating circuit connection is
permanently OFF in operating mode “DHW only”
(not used)
F7: 10 In the “Standby mode”, the circulation pump in the
heating circuit connection will be started 10 times
per day for 10 minutes respectively (not used)
2F: 1Air bleed program enabled
2F: 2Filling program enabled
32: 1
to
32: 7
32: 8Internal circulation pump OFF
32: 9
to
32: 15
80: 0Immediate fault message
80: 2
to
80: 199
F5: 0No start delay of the internal circulation pump
F5:1
to
F5: 20
F6: 1
to
F6: 24
F6: 25 In the “DHW only” operating mode, the internal
F7: 0In the “Standby mode”, the internal circulation
F7: 1
to
F7: 24
F7: 25 In the “Standby mode”, the internal circulation
No function
No function
recognition
The fault message is issued after a delay that is
adjustable from 10 sec to 995 sec;
1 increment = 5 sec
address 11:9 has been set)
(only adjustable if coding address 11:9 has been
set). The red fault indicator also flashes during calibration. The process has terminated when the red
fault indicator no longer
flashes (after approx. 1 min.).
Note!
Heat generated by the boiler must be dispersed during manual calibration.
Delay off time of the circulation pump in the
heating circuit connection set adjustable from 1 to
20 min
In the “DHW only” operating mode, the internal
circulation pump will be started 1 to 24 times per
day for 10 minutes respectively
circulation pump is permanently ON
pump is permanently OFF
In the “Standby mode”, the internal circulation
pump will be started 1 to 24 times per day for 10
minutes respectively
pump is permanently ON
5727 946 v1.2
81
Page 82
Coding – Vitotronic 300-K
Resetting codes into the factory setting
1. Press w and rw simultaneously
for approx. 2 seconds.
2. Press D.
Confirm “Base setting? Yes” with
.
Select “Base setting? Yes” or “Base
setting? No” withor.
Coding Level 1
Calling up coding level 1
1
2
3
Cod. 1
Code 1
1. Press 9 and w simultaneously for
approx. 2 seconds.
2. Select the required coding address
withor;
the address flashes;
confirm with,
the value flashes.
Summary
Coding (factory default setting)Possible change
System design
00: 1System circuit A1,
without DHW heating
Number of boilers
35: 44 boilers connected to Vitotronic 300-K35: 1
00: 2System circuit A1,
with DHW heating
00: 3Mixing valve circuit M2,
without DHW heating
00: 4Mixing valve circuit M2,
with DHW heating
00: 5System circuit A1 and
mixing valve circuit M2,
without DHW heating
00: 6System circuit A1 and
mixing valve circuit M2,
with DHW heating
00: 7Mixing valve circuit M2 and M3,
without DHW heating
00: 8Mixing valve circuit M2 and M3,
with DHW heating
00: 9System circuit A1 and
mixing valve circuits M2 and M3,
without DHW heating
00: 10System circuit A1 and
mixing valve circuits M2 and M3,
with DHW heating
1 to 3 boilers connected to Vitotronic 300-K
to
35: 3
3. Change the value withor;
confirm with.
The display briefly shows Accepted,
then the address flashes again.
Call up further addresses
withor.
4. Press 9 and w simultaneously for
approx. 1 second.
82
5727 946 v1.2
Page 83
Coding Level 1 (continued)
Coding (factory default setting)Possible change
Multi-boiler control unit
36: 0Electronic minimum system supply temperature
limit set to 32˚F / 0˚C
37: 80Electronic maximum system supply temperature
limit set to 176˚F / 80˚C
Control type
3b: 1Boiler parallel connection with supply temperature
sensor (LLH)
Control strategy
3C: 0Gross calorific strategy 2
(see page 57)
36: 1
to
36:127
37: 20
to
37:127
3b: 0Boiler parallel connection without supply
3C: 1Net calorific strategy 1
3C: 2Net calorific strategy 2
Electronic minimum system supply temperature
limit adjustable from 32 to 261˚F / 0 to 127˚C
Electronic maximum system supply temperature
limit adjustable from 68 to 261˚F / 20 to 127˚C
temperature sensor (LLH)
(see page 57)
(see page 57)
Coding – Vitotronic 300-K
5727 946 v1.2
83
Page 84
Coding – Vitotronic 300-K
circuitpumpandmixingvalve
Coding Level 1 (continued)
Coding (factory default setting)Possible change
General (continued)
77: 5LON participant number77: 1
to
77: 99
DHW priority A1/M2/M3
A0: 0 Without remote controlA0: 1With Vitotrol 200
A0: 2With Vitotrol 300
A2: 2
Summer econ. A1/M2/M3
A5: 5 With heating circuit pump logic functionA5: 0Without heating circuit pump logic function
Supply min. temp. A1/M2/M3
C5: 20 Electronic minimum supply temperature limit:
With DHW tank priority applicable to heating
circuit pump and mixing valve
68˚F / 20˚C
A2: 0Without DHW tank priority applicable to heating
A2: 1With DHW tank priority for mixing valve:
A2: 3
to
A2: 15
C5: 1
to
C5:127
LON participant number, adjustable from 1 to 99
Note:
Allocate each number only once.
circuit pump and mixing valve
Mixing valve is closed during DHW heating; heating
circuit pump operates
Do not adjust
Note: for additional information see coding level 2
Min. limit adjustable from 34 to 261˚F / 1 to 127˚C
(limited by boiler coding card); only effective with central
heating with normal temperature
Supply max. temp. A1/M2/M3
C6: 75 Electronic maximum supply temperature limit
176˚F / 80˚C
C6: 10
to
C6:127
Maximum limit adjustable from 50 to 261˚F / 10 to
127˚C (limited by boiler coding card)
84
5727 946 v1.2
Page 85
Coding Level 2
The summary from page 86 lists all possible coding addresses.
The coding addresses are grouped in
System design
Cod. 00
Multi-boiler control unit
Cod. 35 to 49
General
Cod. 4A to 4F
DHW
Cod. 54 to 75
General
Cod. 76 to 9F
System circuit A1
Cod. A0 to F2
accordance with the adjacent
sequence.
Coding – Vitotronic 300-K
Mixing valve circuit M2
Cod. A0 to F2
Mixing valve circuit M3
Cod. A0 to F2
Calling up coding level 2
1
2
3
Cod. 2
Code 2
Initially the possible coding addresses
A0 to F2 for the system circuit A1 are
scrolled through, then those for mixing
valve circuits M2 and M3, again
starting with coding address A0.
ress w and rw simultaneously
1. P
for approx. 2 seconds;
confirm with.
2. Select the required coding address
withor;
the address flashes;
confirm with,
the value flashes.
3. Change the value withor;
confirm with.
The display briefly shows Accepted,
then the address flashes again.
Call up further addresses
withor.
4. Press w and rw simultaneously
for approx. one second.
5727 946 v1.2
85
Page 86
Coding – Vitotronic 300-K
Inmulti-boilersystems,whereoneboileri
s
Coding Level 2 (continued)
Overall summary
Coding (factory default setting)Possible change
System design
00: 1See page 82
Multi-boiler control unit
35: 44 boilers connected to Vitotronic 300-K35: 2
to
35: 3
36: 0Electronic minimum system supply temperature limit
set to 32˚F / 0˚C
37: 80 Electronic maximum system supply temperature
limit set to 176˚F / 80˚C
38: 0
39: 0No permanent lead boiler39: 1
3A: 0 No permanent last boiler3A: 1
3b: 1Boiler parallel connection with supply temperature
3C: 0 Gross calorific strategy
3d: 1Output balance for gross calorific strategy and net
3E: 0Do not adjust
3F: 0Without DHW tank priority for common supply
No changing of lead boiler and the boiler sequence
Note:
In multi-boiler systems, where one boiler is
permamently selected as standby boiler, change
that boiler over to become the active boiler only in
longer intervals, e.g. as part of the annually required
system inspection.
sensor (LLH)
(see page 57)
calorific strategy 1
pump
36: 1
to
36:127
37: 20
to
37:127
38: 1Changing the lead boiler:
38: 2
to
38:200
to
39: 4
to
3A: 4
3b: 0Boiler parallel connection with supply temperature
3C: 1Net calorific strategy 1
3C: 2Net calorific strategy 2
3d: 0No output statement
3F: 1With DHW tank priority for common supply pump
2 to 3 boilers connected to Vitotronic 300-K
Electronic minimum system supply temperature
limit adjustable from 32 to 261˚F / 0 to 127˚C
Electronic maximum system supply temperature
limit adjustable from 68 to 261˚F / 20 to 127˚C
Every 1stday of the month, the boiler with the
burner which has operated for the shortest number
of hours, becomes lead boiler
Changing the lead boiler:
After 200 to 20,,000 run hours, the boiler with the
next higher number (coding address 07 of
Vitotronic 100) becomes lead boiler;
1 setting step = 100 run hours
Boiler 1, 2, 3 or 4 is permanent lead boiler
Boiler 1, 2, 3 or 4 is permanent last boiler
sensor (LLH)
(see page 57)
(see page 57)
Note:
Vitotronic 300-K controls only in accordance with
net calorific strategy 2
86
5727 946 v1.2
Page 87
Coding Level 2 (continued)
Coding (factory default setting)Possible change
General
41: 31 No ECO threshold boiler 141:–30
to
41:+30
42: 31 No ECO threshold boiler 242:–30
to
42:+30
43: 31 No ECO threshold boiler 343:–30
to
43:+30
44: 31 No ECO threshold boiler 444:–30
to
44:+30
45: 60 Start-up integral threshold set to
60 Kelvin × minute
46: 10 Shutdown integral threshold set to
10 Kelvin × minute
47: 15 Shutdown differential set to 27˚F / 15˚C47: 2
48: 35 Do not adjust
49: 40 Do not adjust
4A: 0Do not adjust
4b: 0Sensor aJB (not used) not installed4b: 1Sensor aJB installed
4C: 0Connection on plug sÖA1:
Heating circuit pump
4F: 5DHW. Do not adjust
DHW
54: 0Without solar control unit
45: 1
to
45:255
46: 1
to
46:255
to
47: 30
4C: 1Primary pump – DHW tank heating system
54: 1With Vitosolic 100;
54: 2With Vitosolic 200;
ECO threshold boiler 1 adjustable
from –22 to +86˚F / –30 to +30˚C
ECO threshold boiler 2 adjustable
from –22 to +86˚F / –30 to +30˚C
ECO threshold boiler 3 adjustable
from –22 to +86˚F / –30 to +30˚C
ECO threshold boiler 4 adjustable
from –22 to +86˚F / –30 to +30˚C
Start-up integral threshold adjustable
from 1 to 255 Kelvin × minute
Note:
If the threshold is exceeded, one boiler or one burner
stage is switched ON
Shutdown integral threshold adjustable
from 1 to 255 Kelvin × minute
Note:
If the threshold is exceeded, one boiler or one burner
stage is switched OFF
Shutdown differential adjustable
from 3.6 to 54˚F / 2 to 30˚C
Note:
One boiler or one burner stage will be switched OFF,
if actual supply temperature exceeds the set supply
temperature by this value
(e.g. temperature sensor T2);
will be recognised automatically
will be recognized automatically (not used)
will be recognized automatically
Coding – Vitotronic 300-K
5727 946 v1.2
87
Page 88
Coding – Vitotronic 300-K
operatingprogramwithpermanentlynormalroom
operatingprogramwithpermanentlynormalroom
Coding Level 2 (continued)
Coding (factory default setting)Possible change
Multi-boiler control (continued)
DHW (continued)
55: 0DHW heating,
differential ± 4.5˚F / 2.5˚C
56: 0Setting range for DHW temperature:
50 to 140˚F / 10 to 60˚C
58: 0Without auxiliary function for DHW heating58: 10
59: 0DHW tank heating:
Start-up point – 2.5˚C / –4.5˚F /
Shutdown point + 2.5˚C / +4.5˚F
5A: 0 No function5A: 1Supply temperature demand from DHW tank is
60: 20 During DHW heating, boiler water temperature is
max. 36˚F / 20˚C higher than set DHW temperature
62: 10 Delay off time of DHW pump up to max. 10
minutes
64: 2
During party mode and after external changeover of
55: 1Adaptive DHW heating active (speed of
temperature rise for DHW tank temperature is taken
into account during DHW heating)
55: 2DHW tank temperature control with 2 DHW tank
temperature sensors
55: 3DHW loading heating system
56: 1Setting range for DHW temperature:
50 to 203˚F / 10 to 95˚C
Observe the max. permissible DHW temperature
Change adjustable high limit on boiler controls
Input of a 2ndset DHW value; adjustable
to
58: 95
59: 1
to
59: 10
60: 10
to
60: 50
62: 0DHW pump without delay off time
62: 1
to
62: 15
64: 0No DHW heating, DHW recirculation pump OFF
from 34 to 203˚F / 1 to 95˚C (subject to boiler
coding card)
Note:
The DHW tank is heated to the 2ndset value during
the 4thDHW heating phase
Start-up point adjustable from 2 to 18˚F /
1 to 10˚C below set value
maximum value of system
Difference between common supply temperature
and set DHW temperature is adjustable from 10 to
50˚C / 18 to 90˚F
DHW pump delay off time adjustable from 1 to 15
minutes
temperature:
Enable constant DHW heating and DHW recirculation
pump ON
88
64: 1DHW heating and DHW recirculation pump acc. to
time program
5727 946 v1.2
Page 89
Coding Level 2 (continued)
InputofsetDHWvalue:
Vitotrol300remotecontrolunits
67:40WithVitosolic200
:
DHWrecirculationpump:
Coding (factory default setting)Possible change
DHW (continued)
66: 4
67: 40 With Vitosolic 200:
Input of set DHW value:
At programming unit and all installed
3rd DHW set-point 104˚F / 40˚C
Reloading suppression will be active
above set temperature. DHW tank is
heated only by solar heating system.
66: 0At programming unit
66: 1At programming unit and remote control – system circuit A1
66: 2At programming unit and remote control – mixing valve circuit
M2
66: 3At programming unit and remote control – mixing valve circuit
M3
66: 5At remote control – system circuit A1
66: 6At remote control – mixing valve circuit M2
66: 7At remote control – mixing valve circuit M3
67: 0Without a 3rdset DHW temperature
67: 1
to
67: 95
Input of a 3rdset DHW set point temperature; adjustable
from 34 to above 203˚F / 1 to above 95˚C (subject to the
boiler coding card of the connected boilers)
Coding – Vitotronic 300-K
68: 8With 2 DHW tank temperature sensors
(coding 55: 2):
DHW tank heating switch-off point with
set value × 0.8
69: 7With 2 DHW tank temperature sensors
(coding 55: 2):
DHW tank heating starting point with set
value × 0.7
70: 0DHW recirculation pump ON acc. to time
program when DHW heating is enabled
71: 0
72: 072: 1OFF during DHW heating to second set value
73: 073: 1
75: 0DHW recirculation pump during economy
DHW recirculation pump:
ON acc. to time program
mode:
ON acc. to time program
68: 2
to
68: 10
69: 1
to
69: 9
70: 1DHW recirculation pump ON according to time program
71: 1OFF during DHW heating to first set value
71: 2ON during DHW heating to first set value
72: 2ON during DHW heating to second set value
to
73: 6
73: 7Constantly ON
75: 1OFF
Factor adjustable
from 0.2 to 1;
1 setting step = 0.1
Factor adjustable
from 0.1 to 0.9;
1 setting step = 0.1
During time program
1x/h ON for five minutes
to
6x/h ON for five minutes
5727 946 v1.2
89
Page 90
Coding – Vitotronic 300-K
Afaultmessageisissued
,
Automaticdaylightsavingtime
Codingaddresses82to87onlyfeasible
Coding Level 2 (continued)
Coding (factory default setting)Possible change
General
76: 0Without LON communication module76: 1With LON communication module;
will be recognized automatically
77: 5LON participant number77: 1
to
77: 99
78: 1LON communication enabled78: 0Disable LON communication
79: 1Control unit is fault manager79: 0Control unit is not fault manager
7A: 0Without central control of heating
circuits
7b: 1With LON communication module:
Control unit transmits the time
7E: 0DO NOT ADJUST7E: __
7F: 1Detached house7F: 0Multi-occupancy house
80: 6
81: 1
82: 3Daylight saving time starts:
83: 5Daylight saving time starts:
84: 7Daylight saving time starts:
85: 10 Daylight saving time ends:
86: 5Daylight saving time ends:
87: 7Daylight saving time ends:
88: 0Temperature display in ˚C (Celsius)88: 1Temperature display in ˚F (Fahrenheit)
89: 0Do not adjust!
8A:175 Do not adjust!
A fault message is issued,
if a fault is active for at least 30 seconds
Automatic daylight saving time
changeover
Note:
if coding 81: 1 is set.
March
last week of month
last day of week (Sunday)
October
last week of month
last day of week (Sunday)
7A: 1With central control of:
7A: 2Mixing valve circuit M2
7A: 3Mixing valve circuit M3
7b: 0Do not transmit time
80: 0Immediate fault message
80:...
to
80:199
81: 0Manual changeover - daylight saving time
81: 2Use of a radio clock receiver; recognized automatically (not
81: 3Accept time via LON
82: 1
to
82: 12
83: 1
to
83: 5
84: 1
to
84: 7
85: 1
to
85: 12
86: 1
to
86: 5
87: 1
to
87: 7
LON participant number, adjustable from 1 to 99
Note:
Allocate each number only once
System boiler circuit A1
Minimum fault duration before displaying a fault message is
adjustable from 10 to 995 seconds;
1 setting step = 5 seconds
used)
January
to
December
Week 1
to
week 5 of selected month
Monday
to
Sunday
January
to
December
Week 1
to
week 5 of selected month
Monday
to
Sunday
5727 946 v1.2
90
Page 91
Coding – Vitotronic 300-K
8E:4Displayingandacknowledgingfaults:
97:2Outdoortemperatureatsensorconnectedto
Coding Level 2 (continued)
Coding (factory default setting)Possible change
General (continued)
8E: 4Displaying and acknowledging faults:
At programming unit and all installed Vitotrol
remote control units
90:128 Time constant for calculating adjusted outdoor
temperature:
21.3 hours
91: 0Without heating program changeover (see page 21)
97: 0No transmission via LON BUS
97: 1The control unit receives the outdoor temperature
98: 1
to
98: 5
Fast (low values) or slow (high values) matching of
supply temperature subject to set value when
outdoor temperature changes;
1 setting step = 10 minutes
Connection to terminals 1 and 2 in plug aVD
(External mixing valve open) inactive
99: 1Contact affects:
No function
99: 2Mixing valve close:
Mixing valve circuit M2
99: 3No function
99: 4Mixing valve close:
Mixing valve circuit M3
99: 5No function
99: 6Mixing valve close:
Mixing valve circuits M2 and M3
99: 7No function
99: 8External disable
99: 9No function
99: 10External disable and mixing valve close:
Mixing valve circuit M2
99: 11No function
99: 12External disable and mixing valve close:
Mixing valve circuit M3
99: 13No function
99: 14External disable and mixing valve close:
Mixing valve circuits M2 and M3
99: 15No function
9A: 1Contact affects:
No function
9A: 2Mixing valve open:
Mixing valve circuit M2
9A: 3No function
9A: 4Mixing valve open:
Mixing valve circuit M3
9A: 5No function
9A: 6Mixing valve open:
Mixing valve circuits M2 and M3
99: 7No function
92
5727 946 v1.2
Page 93
Coding Level 2 (continued)
9b:70Setpointtemperatureforexternaldemand
9C:20MonitoringLONparticipants:
pumpandmixingvalv
e
Coding (factory default setting)Possible change
General (continued)
9b: 70 Set point temperature for external demand
(input aVH) 158˚F / 70˚C
9C: 20 Monitoring LON participants:
When there is no response from a participant,
values defaulted inside control unit continue to be
used for a further 20 min. Only then will a fault
message be triggered.
9b: 0No default set value
9b: 1
to
9b:127
9C: 0No monitoring
9C: 5
to
9C: 60
Set value adjustable from 34 to 261˚F /
1 to 127˚C (Min. / max. temperature subject to
boiler coding card)
Time adjustable from 5 to 60 minutes
Coding – Vitotronic 300-K
9d: 0Without Input Module
0 to 10V
9F: 8With mixing valve circuit:
Differential temperature 14.4˚F / 8˚C
(only in conjunction with mixing valve circuit)
System circuit/mixing valve circuit
A0: 0 Without remote controlA0: 1With Vitotrol 200
A2: 2
A3: 2 Outdoor temp. below 34˚F / 1˚C:
With DHW tank priority applicable to heating circuit
pump and mixing valve
Heating circuit pump ON
Outdoor temp. above 37˚F / 3˚C:
Heating circuit pump OFF
Note:
For settings below 34˚F / 1˚C pipes outdoor
thermal insulation shell of building can freeze up,
particularly during standby mode, e.g. during
holidays.
9d: 1With Input Module 0 - 10V;
will be recognized automatically
9F: 0
to
9F: 40
A0: 2With Vitotrol 300
A2: 0Without DHW tank priority applicable to heating
With heating circuit pump logic function (economy
circuit):
Heating circuit pump OFF, if outdoor temperature
(AT) is 1 K higher than set room temperature (RT
AT > RT
With pump stop function:
Heating circuit pump OFF during set-point value
changes (by changing operating mode or changes
on rotary selector ts or button tm)
AT > RT
AT > RT
AT > RT
AT > RT
AT > RT
AT > RT
AT > RT
set
set
set
set
set
set
set
+ 5 K
+ 4 K
+ 3 K
+ 2 K
+ 1 K
+ 1 K
– 1 K
to
AT > RT
set
– 9 K
Extended economy function active, i.e. burner and
to
A6: 35
heating circuit pump will be switched OFF, and
mixing valve will be closed at a variable value
which is adjustable between 41 and 95˚F / 5 and
35˚C plus 2˚F / 1˚C.
This value is based on dampened outdoor
temperature, comprising actual outdoor
temperature and a time constant which takes
cooling down of an average building into
consideration.
(extended heating circuit pump logic).
Heating circuit pump also OFF, if mixing valve was
closed longer than 20 minutes.
Heating circuit pump ON:
If mixing valve changes to control mode
or
After DHW tank heating (for 20 minutes)
or
If there is a risk of frost
A9: 0Without pump stop function
A9: 1
Pump stop function adjustable from 1 to 15
to
A9: 15
94
5727 946 v1.2
Page 95
Coding – Vitotronic 300-K
Coding Level 2 (continued)
Coding (factory default setting)Possible change
Systems/mixing valve circuit (continued)
b0: 0*1With remote control:
Heating mode/ reduced mode:
With outdoor reset
b1:Do not adjust
b2: 8*1With remote control unit and for heating circuit,
operation with room temperature feed-back must
be programmed:
Room influencing factor 8
b3: 0*1Do not adjust
b5: 0*1With remote control:
Without room temperature dependent heating
circuit pump logic function
b6: 0*1With remote control unit and for heating circuit,
operation with room temperature feed-back must
be programmed:
Without quick heat-up/quick setback
*1
Change coding – for system circuit A1 only for boilers without lower temperature limit – for mixing valve circuit only, if remote control
unit affects this heating circuit.
b0: 1Heating mode:
With outdoor reset
Reduced mode:
With room temperature feed-back
b0: 2Heating mode:
With room temperature feed-back
Reduced mode:
With outdoor reset
b0: 3Heating mode/ reduced mode:
With room temperature feed-back
b2: 0No room influence
b2: 1
Room influence factor adjustable from 1 to 31
to
b2: 31
Heating circuit pump
b5: 1
b5: 2
b5: 3
b5: 4
b5: 5
b5: 6
b5: 7
b5: 8
ON at RT
OFF at RT
T for ONT for OFF
+4K+5K
+3K+4K
+2K+3K
+1K+2K
+0K+1K
-1K+0K
-2K-1K
-3K-2K
actual
actual
< RT
> RT
set
set
+
+
T
T
b6: 1With quick heat-up/quick setback (see page 61)
5727 946 v1.2
95
Page 96
Coding – Vitotronic 300-K
Coding Level 2 (continued)
Coding (factory default setting)Possible change
Systems/mixing valve circuit (continued)
b7: 0*1With remote control unit and for heating circuit,
operation with room temperature feed-back must
be programmed:
Without start-up optimization
b8:10*1With remote control unit and for heating circuit,
operation with room temperature feed-back must
be programmed:
Heat-up gradient – start-up optimization
10 minutes/ ˚C
b9: 0*1With remote control unit and for heating circuit,
operation with room temperature feed-back must
be programmed:
Without learning start-up optimization
C0: 0*1With remote control:
Without shut-down optimization
C1: 0*1With remote control:
Without shut-down optimization
C2: 0*1With remote control:
Without learning shutdown optimization
Mixing valve circuit
C3:125 Mixing valve operating time:
125 seconds
C4: 1System dynamics – mixing valve control
characteristics
System circuit/mixing valve circuit (continued)
C5: 20Electronic minimum supply temperature limit:
68˚F / 20˚C
C6: 75Electronic maximum supply temperature limit
176˚F / 80˚C
*1
Change coding – for system circuit A1 only for boilers without lower temperature limit – for mixing valve circuit only, if remote control
unit affects this heating circuit.
b7: 1With start-up optimization:
Max. offset
2 hours 30 minutes
b7: 2Max. off-set
15 hours 50 minutes
b8: 11
to
Heat-up gradient adjustable from 11 to
255 minutes / ˚C
b8:255
b9: 1With learning start-up optimization
C0: 1With shutdown optimization:
Max. off-set 1 hour
C0: 2Max. off-set 2 hours
C1: 1
to
C1: 12
With shutdown optimization:
Max. off-set from 10 to 120 minutes;
1 setting step = 10 minutes
C2: 1With learning shutdown optimization
C3: 10
Operating time adjustable from 10 to 255 seconds
to
C3:255
C4: 0
to
C4: 3
Controller responds too quickly (cycles between
open and close):
Select a lower value.
Controller acts too slowly (temperature is not
maintained correctly):
Select a higher value.
C5: 1
to
C5:127
C6: 10
to
Min. limit adjustable from 34 to 261˚F / 1 to 127˚C
(limited by boiler coding card); only effective with
central heating with normal temperature
Maximum limit adjustable from 50 to 261˚F /
10 to 127˚C (limited by boiler coding card)
C6:127
96
5727 946 v1.2
Page 97
Coding Level 2 (continued)
Normaldaytemperatureisadjustableatremot
e
Coding (factory default setting)Possible change
System circuit/mixing valve circuit (continued)
C8:31*1With remote control unit and for heating circuit,
operation with room temperature feed-back must
be programmed:
Without limiting room influence
d5: 0External heating program changeover via terminal
X6.1 and X6.2:
Heating program changes to constant operation
with reduced room temperature
E1: 1
With remote control:
Normal day temperature is adjustable at remote
control unit from 50 to 86˚F / 10 to 30˚C
E2: 50With remote control:
No display correction of actual room temperature
Mixing valve circuit
F1: 0Slab curing function inactiveF1: 1
C8: 1
to
Room influence limit adjustable from 1 to 30 K (1.8
to 54 Fahrenheit degrees)
C8: 30
d5: 1Heating program changes to constant operation
Slab curing function adjustable in accordance with
to
F1: 5
four optional temperature-time profiles (see
page 101)
Coding – Vitotronic 300-K
Note:
Observe slab curing supplier’s instructions.
Observe local regulations.
Report to be provided by heating contractor must
contain following details:
Heat-up data with their respective supply
temperatures
Max. supply temperature achieved
Operating condition and outdoor temperature
during handover
Function continues after power failure or after
control unit has been switched OFF.
Heating program rrrrwwww will be started, after slab
curing function has been completed or if address is
manually set to 0.
System circuit/mixing valve circuit
F2: 8Time limit for party mode 8 hours
*1
F2: 0No time limit for party mode
F2: 1
to
Time limit for party mode adjustable from 1 to
12 hours
*1
*1
F2: 12
*1
Party mode ends automatically with heating program rrrrwwww when system changes over to operation with normal room temperature.
5727 946 v1.2
97
Page 98
Coding – Vitotronic 300-K
Observethesettingofcodingaddress“A3”.
fromoperationwithreducedroomtemperatureto
FA:50
fromoperationwithreducedroomtemperatureto
FA:50
Coding Level 2 (continued)
Coding (factory default setting)Possible change
System circuit/mixing valve circuit (continued)
F8: –5Temperature limit for terminating the reduced
mode 23˚F / – 5 ˚C see example on page 99.
Observe the setting of coding address “A3”.
F9: –14 Temperature limit for raising the set temperature
for reduced mode 7˚F / – 14 ˚C, see example on
page 99.
FA: 20Raising the boiler water setpoint temperature or
the supply setpoint temperature when changing
operation with standard room temperature by
20%.
See example on page 100.
Fb: 30Duration for raising the boiler water temperature
setpoint or the supply temperature setpoint (see
coding address “FA”) 60 min.
See example on page 100.
F8:+10
to
F8: –60
F8:–61Function disabled
F9:+10
to
F9: –60
FA: 0
to
Fb: 0
to
Fb: 150
Temperature limit adjustable from +50 to –76˚F /
+10 to –60˚C
Temperature limit adjustable from +50 to –76˚F /
+10 to –60˚C
Temperature rise adjustable from 0 to 50%
Duration adjustable from 0 to 300 min.;
1 increment = 2 min.
98
5727 946 v1.2
Page 99
Coding Level 2 (continued)
Example 1 (”F8: –5“, “F9: –14”)
20
A
15
°C
10
5
B
Coding – Vitotronic 300-K
Set room temperature in
0
-30
Outdoor temperature in
Example (using factory default settings)
A Set standard room temperature 68°F / 20°C
B Set reduced room temperature 37°F / 3°C
C Temperature limit 7°F / – 14 °C in accordance with
coding address “F9”
D Temperature limit 23°F / – 5 °C in accordance with
coding address “F8”
-25
-20-15-10
°C
C
D
-5
05
5727 946 v1.2
99
Page 100
Coding – Vitotronic 300-K
Coding Level 2 (continued)
Example 2 (”FA: 20“, “Fb: 30”)
During the transition from operation with reduced room temperature to
operation with standard room temperature, the boiler water or supply
temperature will be raised in accordance with the selected heating curve.
The boiler water or supply temperature can be automatically increased.
The value and duration of the additional increase of the set boiler water
temperature or supply temperature can be adjusted in coding addresses
”FA” and ”Fb”.
C
60
B
50
°C
40
3030
20
D
10
Boiler / Supply Water
Setpoint Temperature in
A
0
00
6
00
7
00
8
Time in h
Fig. 1 Example (using factory default settings)
A Start of operation with standard room
temperature
B Boiler water / supply temperature
based on selected heating curve
C Boiler water / supply temperature
based on coding address ”FA”:
50°C + 20 % = 60°C
D Duration of operation with raised
boiler water / supply temperature
based on coding address ”Fb”: 60 min.
00
9
100
5727 946 v1.2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.