Viessmann VITOTRONIC 100, HC1, VITOTRONIC 300-K, MW2S, VITOCONTROL-S Installation And Service Instructions Manual

...
Page 1
Installation and Service Instructions
for use by heating contractor
V
itotronic 100, Model HC1
Digital boiler control unit
Outdoor-reset logic digital cascade control Panel mount, controls up to 4 Vitodens WB2B boilers
Please file in Service Binder
VITOTRONIC 100, HC1 VITOTRONIC 300-K, MW2S
Certified as a component part of Viessmann boilers only
Vitotronic 100, HC1
Vitotronic 300-K, MW2S
5727 946 v1.2 11/2011
Page 2
Safety, Installation and Warranty Requirements
5727946v1.2
Please ensure that this manual is read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
Licensed professional heating contractor
The installation, adjustment, service, and maintenance of this equipment must be performed by a licensed professional heating contractor.
ease see section
Pl entitled “Important Regulatory and Installation Requirements.”
Product documentation
Read all applicable documentation be­fore commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
For a listing of applicable literature, please see section entitled “Important Regulatory and Installation Requirements.”
Advice to owner
Once the installation work is complete, the heating contractor must familiarize the system operator/ultimate owner with all equipment, as well as safety precautions/requirements, shut-down procedure, and the need for professional service annually before the heating season begins.
Warranty
Information contained in this and related product documentation must be read and followed. Failure
to do so renders warranty null and void.
2
Page 3
Index
Table of Contents
Page
Safety, Installation and Warranty Requirements 2
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . ..
General Information
Important Regulatory and Safety Requirements 5 About these Instructions 6
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . ..
Heating System Designs
System design 7
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .
Installation – Vitotronic 300-K
Installing the Cascade Communication Module 10 Summary of electrical connections (Power Pump Module) 11 Installing modules 13 Installing the programming unit 13 Summary of electrical connections 14 Sensor connection 17 Connection of the pumps 19
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. ..
Connection to modulating valve actuators 20 Connection of external contacts 21 Connection to compiled failure alarm 22 Making the LON connection 23 Power supply 24
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. ..
Initial Start-up
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. .
Steps 25 Further step-by-step instructions 26
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . ..
Service Scanning – Vitotronic 100, HC1
Service level summary 36 Temperatures, boiler coding card and quick scans 37 Scanning operating conditions 38 Scanning and resetting service displays 39
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .
Service Scanning – Vitotronic 300-K
Service level summary 40 Temperatures and quick scans 41 Scanning operating conditions 43
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. ..
Troubleshooting – Vitotronic 100, HC1
Retrieving fault codes from the fault memory (fault history) 44 Faults displayed at the programming unit 44
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . ..
Troubleshooting – Vitotronic 300-K
Retrieving fault codes from the fault memory (fault history) 48 Faults with fault display at the programming unit 48
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . ..
Function Description – Vitotronic 100, HC1
Boiler temperature control 54
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .
5727 946 v1.2
3
Page 4
Table of Contents
5727946v1.2
Index (continued)
Function Description – Vitotronic 300-K
Cascade control unit 55 Heating circuit control 60 DHW tank temperature control 63
Components – Vitotronic 300-K
Components from the parts list 65 Mixing valve circuit extension kit 69 Installation examples 70 Remote control 71 Room temperature sensor 77 Input Module 0 to 10 V 78
Coding – Vitotronic 100, HC1
Resetting codes to the factory setting 79 Coding Level 1 79 Coding Level 2 80
Coding – Vitotronic 300-K
Resetting codings to the factory setting 82 Coding Level 1 82 Coding Level 2 85 Slab curing function diagram 101
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . ..
Connection and Wiring Diagrams - Vitotronic 100, HC1
Boiler control, Power Pump Module (models 45, 60) wiring diagram 102 Boiler control, Power Pump Module (models 80, 105) wiring diagram 104
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. .
Appendix
Specification – Vitotronic 100 106 Specification – Vitotronic 300-K 106 Parts list 107
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . ..
Product Information
Vitotronic 100, HC1, and Vitotronic 300-K
Only for integration/installation on Viessmann boilers and for wall mounting.
These application examples are only recommendations, and must therefore be checked on site for completeness and function.
4
Page 5
Important Regulatory and Safety Requirements
5727946v1.2
General Information
Approvals
Viessmann boilers, burners and controls are approved for sale in North America by CSA International.
Codes
The installation of this unit shall be in accordance with local codes. In the absence of local codes, use: CSA C22.1 Part 1 and/or local codes
in Canada
National Electrical Code ANSI/NFPA
70 in the U.S.
Always use latest editions of codes.
Working on the equipment
The installation, adjustment, service, and maintenance of this product must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers.
There are no user serviceable parts on the boiler, burner, or control.
Please carefully read this manual prior to attempting installation. Any warranty is null and void if these instructions are not followed.
For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product.
We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire.
The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, etc.
Ensure main power supply to equipment, the heating system, and all external controls has been deactivated. Close main oil or gas supply valve. Take precautions in both instances to avoid accidental activation of power during service work.
Technical literature
Literature applicable to all aspects of the Vitotronic 300-K:
- Installation & Service Instructions
- Operating & User Instructions
- Instructions of other Viessmann products utilized and installed
- Installation codes mentioned in this manual
WARNING
Turn off electric power supply before servicing. Contact with live electric components can cause shock or loss of life.
Leave all literature at the installation site and advise the system operator/ ultimate owner where the literature can be found. Contact Viessmann for additional copies.
5
Page 6
General Information
5727946v1.2
Important Regulatory and Installation Requirements
Power supply
Install power supply in accordance with the regulations of the authorities having jurisdiction or, in the absence of such requirements, in accordance with National Codes. Viessmann recommends the installation of a disconnect switch to the 120 VAC power supply outside of the boiler room. The installer must provide maximum 15 A overcurrent protection for the 120 VAC power supply (fuse or circuit breaker).
Working with an open control
No static discharge to the internal componentry must ever occur when working with opened control equipment.
About these Installation Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include ”WARNING”, ”CAUTION”, and ”IMPORTANT”. See below.
Warnings draw your attention to the
WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage.
presence of potential hazards or important product information.
CAUTION
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/property damage.
IMPORTANT
Cautions draw your attention to the presence of potential hazards or important product information.
Helpful hints for installation, operation or maintenance which pertain to the product.
This symbol indicates that additional, pertinent information is to be found in column three.
This symbol indicates that other instructions must be referenced.
6
Page 7
System design
5727946v1.2
Heating System Designs
A Vitodens 200-W (models 45 to
105) with the Vitotronic 100, HC1, with KMK cascade communication module as part of the standard delivery
B Vitotronic 300-K with LON
communication module (accessory)
C DHW cylinder D Vitotronic 200-H with LON
communication module (accessories)
E Mixing valve on Vitotronic 300-K F Mixing valve on Viotronic 200-H G Maximum temperature controller
(underfloor heating)
H Low loss header K Two-way valve
! Outdoor temperature sensor ? Supply temperature sensor
common heating flow (low loss header)
?M1 Supply temperature sensor
mixing valve circuit 1 ­extended circuit (Vitotronic 200-H)
?M2/M3Supply temperature sensor
mixing valve circuit 2 or 3 (Vitotronic 300-K)
% DHW temperature sensor Boiler pump (Vitotronic 100,
HC1)
M1 Mixing valve circuit 1
(Vitotronic 200-H)
M2/M3Mixing valve circuit 2 or 3
(Vitocontrol-S)
sA DHW pump sK DHW recirculation pump Power supply, 120 V/60 Hz gSM1 Motor mixing valve circuit 1
(Vitotronic 200-H)
gSM2/M3Motor mixing valve circuit 2
or 3 (Vitotronic 300-K)
aVD/aVH External hook-up
(Vitotronic 300-K), see page 21.
aVG/KMK Connection to
Vitotronic 100, HC1 to Vitotronic 300-K
KMK Interconnection between
boiler controls and Vitotronic 100, HC1
7
Page 8
Heating System Designs
5727946v1.2
System design (continued)
The codes must be set on every Vitotronic 100. (see section on coding page 82)
Vitotronic 100, HC1
Required coding
01 : 2
07 : 2 07 : 3 07 : 4
Vitotronic 300-K
Required coding
00 : 3, 00 : 4, 00 : 7, or 00 : 8
35 : 1 35 : 2 35 : 3 35 : 4
Multi-boiler system with Vitocontrol-S, WB2B
Setting the boiler number at the Vitotronic 100 of the second boiler third boiler fourth boiler
Heating circuit M2 without DHW heating Heating circuit M2 with DHW heating Heating circuit M2 and M3 without DHW heating
Heating circuit M2 and M3 with DHW heating
Setting up Vitotronic 300-K with one Vitotronic 100 two Vitotronic 100 three Vitotronic 100 four Vitotronic 100
Vitotronic 200-H (if installed)
Required coding
97 : 1 The outdoor temperature is accepted by the LON BUS
8
Page 9
System design (continued)
5727946v1.2
DHW and Space Heating Multiple (up to four) Vitodens 200-W, models WB2B 45, 60, 80 and 105 with...
– multiple heating circuits with mixing valves – low-loss header
Vitotronic 300-K
Heating System Designs
DHW Tank
TPV
PPM
Boiler 1 Boiler 2
PRV
PPM PPM PPM
Boiler 3 Boiler 4
PRV
PRV
PRV
Common
Supply Temperature Sensor
Low-Loss
ader
He
M
Fig. 31
When designing a multiple Vitodens system as shown above, please reference applicable multiple Vitodens technical documentation, and contact your local Viessmann Sales Representative for further assistance.
M
IMPORTANT
This installation example depicts a possible piping layout for multiple Vitodens 200-W, WB2B boilers equipped with Viessmann system Technology. Please note that this example is based on a simplified conceptual drawing only! Piping and necessary componentry must be field verified. A low water cut-off (LWCO) must be installed where required by local codes. Proper installation and functionality in the field is the responsibility of the heating contractor.
WARNING
When extending wire, there is the possibility of exposure to electromagnetic interference. Avoid running wires beside or near high voltage 120/240 VAC conductors. If proximity to high voltage conductors cannot be avoided, use stranded, twisted pair or shield design wire. Ensure that only one end of the shielding is grounded.
9
Page 10
Installation – Vitotronic 300-K
Installing the Cascade Communication Module
A
The cascade communication module
2.
A
3.
Installation Instructions shipped with boiler.
1.
X7
A
B
C
C
D
A Vitotronic 300-K B KMK-BUS C Boiler control with Vitotronic 100
and KMK Module (max 4 boilers)
D 2-core Cable
(cable cross-section 2 x 0.5 mm
2
20 AWG total length 164ft. / 50m)
E Connection to the Vitotronic 300-K
(to terminals X9.3 and X9.4 on cascade electronic module A2)
F Terminal strip ”KMK1/KMK2” at
the cascade communication module of the boiler control with Vitotronic 100
X9
4
3
A2
KMK2KMK1 KMK2KMK1
Note: The total length of BUS cables B should not exceed 164ft. / 50m. The wires from the BUS cables are commutable.
1 2 3 41 2 3 4
5727 946 v1.2
10
Page 11
Summary of electrical connections (Power Pump Module)
Power/Pump module
MAIN POWER SUPPLY
120V, 60HZ, 12A
L
N
G
MAIN DISCONNECT
L2 L1 P1 P2
A
-TYPICAL
SAFETY DEVICE
LOW WATER CUT-OFF
SWITCH
120VAC WALL RECEPTACLE
120/230
Transformer
NL
202120A40
L2
L1 G N
40
202120A
M
120VAC
BOILER PUMP
Installation – Vitotronic 300-K
Installation Instructions, Power Pump
31 2
143
NL
NLNLNL
50
50
120VAC
FAULT
ALARM
OUTPUT
1 2 3 1 2 3 1 2 3
28
L G N
144
31 2
31 2
145
145144143
Module
KMK1KMK2
X1
4321
KMK
Module
L
145
X 7
X 8
X 9
X11 LON
KMK
X4
Boiler Control Board
1234567
X3
20 40
N
230 VAC
40962035100
5727 946 v1.2
11
Page 12
Installation – Vitotronic 300-K
Summary of electrical connections (Power Pump Module) (continued)
305
1.
318
2.
129
X10
139
4.
X2
X1
12
5727 946 v1.2
Page 13
Installing modules
5727946v1.2
A4 A3
A1 A2
A1 Power supply module
2 Cascade electronic module
A A3 Power module A4 Extension module, mixing valves
Installing the programming unit
Installation – Vitotronic 300-K
1. Install the modules in accordance
with the layout indicated on DIN rail inside the control panel.
2. Connect the modules in accordance
with the overview on page 14 and 15, using the connecting cables provided.
1. Make a cutout with the dimensions 305 × 129 mm in the front door of the control panel. When installing two programming units, maintain a distance between both of 20 mm.
2. Snap the frame into place.
3. Insert the programming unit.
4. Plug the connecting cable into the
back of the programming unit and into the cascade electronic module (A2).
13
Page 14
Installation – Vitotronic 300-K
5727946v1.2
Summary of electrical connections
14
F1 4A
(slow)
Page 15
Summary of electrical connections (continued)
5727946v1.2
Installation – Vitotronic 300-K
15
Page 16
Installation – Vitotronic 300-K
5727946v1.2
Summary of electrical connections (continued)
A1 Power supply module
Power supply connection
A2 Cascade electronic module
! Outdoor temperature sensor
(accessories)
? Common supply temperature
sensor
% DHW tank temperature sensor
(accessories)
%B 2nd tank temperature sensor
(accessories)
aJA Temperature sensor T1 aJB Temperature sensor T2
or temperature sensor - DHW tank loading system
aVD External connections aVG KM BUS users (accessories) link
to Vitotronic 100 and remote controls Vitocontrol
aVH External connections LON Connecting cable for data
transfer between the control units
S1 Emissions test switch S
(optional)
A3 Power module
A1 Heating circuit pump or
DHW tank loading system
sA DHW tank pump (accessories) sK DHW re-circulation pump sL Shunt or supply pump Compiled failure alarm gSA1 Three-way return elevation valve
A4 Expansion module
?M2/M3 Supply temperature sensorM2/M3 Heating circuit pump gSM2/M3 Mixing valve actuator
A5 Programming unit
incl. connecting cable
*1
Remove both jumpers when connecting the emissions test circuit.
16
Page 17
Sensor connection
Outdoor temperature sensor
Installation – Vitotronic 300-K
The outdoor temperature sensor should be mounted 6.5 to 8ft / 2 to 2.5m above ground level on the north or north-west facing wall of the building. In the case of multi-storey buildings, it should be mounted in the upper half of the second storey. Make sure that the sensor is not located over windows, doors and air vents, nor immediately beneath a balcony or guttering. Do not paint over the outdoor temperature sensor housing.
1. Remove the cap.
2. Mount the bottom part of the sensor
housing.
1.
4.
2.
WARNING
When extending wire, there is the possibility of exposure to electromagnetic interference. Avoid running wires beside or near high voltage 120/240 VAC conductors. If proximity to high voltage conductors cannot be avoided, use stranded, twisted pair or shield design wire. Ensure that only one end of the shielding is grounded.
5.
3.
3. Pull the sensor wire through the opening in the terminal compartment and through the strain relief provided.
4. Connect the wires to the terminals.
5. Place the cap over the outdoor
temperature sensor.
600
580
560
540
520
500
480
460
440
5727 946 v1.2
420
Resistance in
400
-40 -30 -20 -10 0 10 20 30
-40 -22 -4 14 32 50 68 86
Outdoor temperature in °C / °F
17
Page 18
Installation – Vitotronic 300-K
Sensor connection (continued)
DHW tank temperature sensor
The sensor measures the domestic hot water tank temperature.
720
700
680
Heating systems with domestic hot water heating (single-boiler systems only)
1. Install the DHW tank temperature
sensor.
See installation instructions for domestic hot water tank
Note:
When installing the sensor in DHW tanks of other makes, make sure that the sensor is pressed against the sensor well of the DHW tank by means of a suitable device.
2. Ensure that the maximum permissible domestic hot water temperature is not exceeded. If necessary, install a suitable safety device for this purpose.
Check the sensor
1. Disconnect wires from terminals
X2.7 and 2.1 of module A2.
2. Measure resistance of sensor at terminals ”1” and ”2” of the plug.
DHW tank temperature
Resistance in ΩΩΩ
in °F / °C /
104 / 40 122 / 50 140 / 60
578 597 616
3. Compare the value measured with the current temperature. If the value differs significantly, check installation and, if necessary, replace sensor.
Technical data
Degree of protection: IP 32 Ambient temperature During operation:
32 to + 194°F 0 to + 90°C
During storage and transport:
- 4 to + 158°F
-20 to + 170°C
660
640
620
600
580
560
Resistance in
540
0 20 40 60 80 100 32 68 104 140 176 212
DHW tank temperature in °C / °F
18
ctrical connection
Ele
The sensors are ready to connect. Insert the DHW temperature sensor lead wires to terminals X2.7 and 2.1 of the A2 Module.
Heating systems without domestic hot water heating
Do not connect the DHW tank temperature sensor.
5727 946 v1.2
Page 19
Connection of the pumps
Available pump connections
Heating circuit high temperature
(without mixing valve)
M2 Heating circuit M2 pump
Terminals 2 - L, - G , - N
M3 Heating circuit M3 pump
Terminals 1 - L, - G , - N
sA DHW pump for heating up the
domestic hot water tank ­Terminals 4 - L, - G , - N
sK DHW recirulation pump
Terminals 3 - L, - G, - N.
Installation – Vitotronic 300-K
TERMINAL
4 or 3
A
B
Install pumps: see manufacturer’s instructions.
120 VAC pumps
Note:
The maximum power consumption of all pumps is 4A . Rated current: max. 2 FLA Recommended connection cable: AWG 14
Connect the 3-wire cable from the pump to the corresponding terminals.
240 VAC or 3 PH pumps
Note:
Use contactor to switch pump. For activating the contactor: Rated current: max. 2 FLA Recommended connection cable: AWG 14
Please ensure that all connections and cable gauge comply with local and national codes.
1.Select the contactor and the connecting cable in accordance with the rating of the pump that is to be connected.
2.Connect the pump and power supply to the contactor.
3.Connect contactor coil to the corresponding terminals.
5727 946 v1.2
19
Page 20
Installation – Vitotronic 300-K
Connection of modulating valve actuators
Control unit
20V or 24V valve adaptor
1 1
2 DIN rail in connection enclosure
3 aBH Terminals
120V Valve Adaptor
Rated voltage: 120 VAC Rated current: max. 0.1 FLA Recommended connection wire size: AWG 14
24V Valve Adaptor
Rated voltage: 24 VAC Rated current: max. 0.15 FLA Recommended connection wire size: AWG 14
Operating time:
5 to 199 sec. selected via coding address “40”.
1 120V valve adaptor
2 120V valve actuator
1 24V valve adaptor
2 24V valve actuator
1. Disconnect power to control.
2. Install 120V or 24V valve adaptor on DIN rail inside connection enclosure.
3. Insert the plug gS into socket gS on the control.
4. Fasten cable with tie.
5. Connect black wire of the adaptor to connection aBH on the DIN rail
- Terminal 8, 9 or 10.
6. Connect valve actuator wires to the
adaptor terminals as shown on figures.
20
5727 946 v1.2
Page 21
Connection of external contacts
Implement connection a A2 in accordance with the overview on pages 15 and 16 and the control panel wiring diagram.
VD / aVH on
A External heating program
changeover or “Mixing valve open”
Contact closed:
The manually pre-selected heating program can be changed via this contact, (see table below) enabling the mixing valves to be opened.
The mixing valve open function can be allocated via coding address “9A”, and the heating program changeover can be allocated to the heating circuits via address “91”.
Installation – Vitotronic 300-K
WARNING
Heating circuits are no longer frost protected during mixing valve closed. A minimum boiler return temperature is not maintained during external disabling.
Via coding address “99”, you can pre-select what input aVD should affect.
A External heating program
changeover/external “Mixing valve open”.
B External disable/external “Mixing
valve closed”
C External demand
Manually pre-selected heating program
(with open contact)
9
Room heating OFF/ DHW OFF
or
worRoom heating OFF/
DHW ON
rw Room heating ON/
DHW ON
Coding 2 Changed heating program
d5: 0 (factory default)
d5: 1 <–> Continuous operation with normal room temperature/DHW in
B External disable/external “Mixing
valve closed”
Closing the dry contact causes the burner to shut down or the mixing valve to be closed. Allocated boiler or pumps are switched OFF, and isolation valves are closed. No frost protection!
(with closed contact)
<–> Continuous operation with reduced room temperature/DHW OFF
accordance with coding address “64”
C External demand
Closing the dry contact starts the boiler burners, subject to load via a set supply temperature (coding address “9b”) on Vitotronic 300-K.
The supply temperature is limited via the set min. and max. supply temperature.
5727 946 v1.2
21
Page 22
Installation – Vitotronic 300-K
Connection of the compiled failure alarm
Implement connection on A3 in accordance with overview on page 104 and control panel wiring.
A3
A
B
Rated voltage: 120 VAC 60 Hz Rated current: max. 2 FLA Recommended connection wire size: AWG 14
1. Disconnect power to control and burner.
2. Connect the compiled failure alarm as shown in the diagram.
A Connect terminal strip in
connection enclosure of boiler control
B Visual and/or audible alarm device
(120 VAC)
22
5727 946 v1.2
Page 23
Installation – Vitotronic 300-K
Making the LON connection
The Viessmann LON system is designed for the Line BUS topology with end of line resistors on both ends.
Connection with Viessmann LON cable
A A A
C
23ft. / 7m
B B
A Control unit or Vitocom B LON cable
Connection with
 Viessmann LON cable and  Viessmann LON coupling
A A A
C
23ft. / 7m
B
3ft. / 7m 23ft. / 7m
2
B
A Control unit or Vitocom B LON cable (max. 3 cables
between two devices)
D
23ft. / 7m
C
C End of line resistor
B
23ft. / 7m
B
D
23ft. / 7m
B
DD
23ft. / 7m
B
C
C End of line resistor D LON extension jack,
5727 946 v1.2
23
Page 24
Installation – Vitotronic 300-K
Making the LON connection (continued)
Connection with
Viessmann LON cable, On-site cable for extensions up to 900 m / 3000 ft.
A A A
C
A Control unit or Vitocom B LON cable C End of line resistor (standard
D Up to 99 participants and the
E Junction box F Connecting cable (on site)
23ft. / 7m
B B B
delivery of Vitotronic 300-K)
corresponding number of junction boxes and cables
E E
F
Power supply
23ft. / 7m 23ft. / 7m
B
max. 900 m / 3000 ft.
Note:
The Viessmann LON system always requires two conductors and shielding. Conductors are interchangeable.
Observe the requirements for cabling and operation of the LON interface FTT-10A (see www.echelon.com).
E
D
E
23ft. / 7m
1. Ensure that the main power supply
C
to the control contains overcurrent protection with a minimum rating of 6A and 2-pole disconnect
Legend
L: Line N: Neutral G: Ground
A Power supply 120 VAC, 1PH,
60Hz, provide disconnect means and overcurrent protection as per local codes
B Terminal in connection
enclosure
C Connection enclosure
24
WARNING
The control must be grounded. Ensure that “L”, “N” and “G” are not interchanged.
2. Connect power supply wire to the
connection terminals 11, N and G on the DIN rail inside the connection enclosure.
5727 946 v1.2
Page 25
Initial start-up
Steps
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . ..
1. Commissioning all Vitodens 200-W with Vitotronic 100 Vitodens 200-W Service Instructions 26
2. Controls and display elements
H Vitotronic 100, HC1 26
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. ..
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . ..
.
Page
3. Checking the heating circuit allocation (Vitotronic 300-K) 27
4. Changing the display language (Vitotronic 300-K) 27
5. Configuring a multi-boiler system 28
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. ..
6. Updating the LON participant list on Vitotronic 300-K 29
7. Connecting control units into the LON system 29
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .
8. Carrying out a participant check (Vitotronic 300-K) 29
9. Reducing the maximum burner output (Vitotronic 100) 30
10. Matching the coding addresses to the system version (Vitotronic 100) 30
11. Matching the coding addresses to the system version (Vitotronic 300-K) 30
12. Checking outputs (actuators) and sensors 31
13. Selecting the boiler sequence (Vitotronic 300-K) 32
14. Adjusting the heating curve (Vitotronic 300-K) 33
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. . .. . .
. .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. . .. .. . .. .. . .. . .. .. . .. .. . .. .. . .. .. .
5727 946 v1.2
25
Page 26
Initial start-up
Further step-by-step instructions
Commissioning of all Vitodens 200-W, WB2B with Vitotronic 100, HC1
Service Instructions Vitodens 200-W, WB2B
A
ºC
A Heating programs B No function C Information
+
OK
i
BD CEFGHK
D Fact0ory default setting E Confirmation F Value setting
G No function H Emissions test function K Boiler water temperature
26
5727 946 v1.2
Page 27
Further step-by-step instructions (continued)
Boiler sequence
Initial start-up
A Heating circuit selection B Reduced room temperature C DHW temperature D Normal room temperature E Standby mode F DHW only
G Heating and DHW H Economy mode K Party mode L Information M Standard settings N Confirmation
Checking the heating circuit allocation (Vitotronic 300-K)
heck that the label for heating
H C
circuit allocation has been affixed to the corresponding fields of the programming unit.
H Press the corresponding key before
commencing all adjustments.
Changing the display language (Vitotronic 300-K)
1. Press i.
2. Select the required language
with .
3. Confirm with .
O Adjusting values P Time programs R Holiday program S Time/date T Heating curve level shift U Heating curve slope
5727 946 v1.2
27
Page 28
Initial start-up
Further step-by-step instructions (continued)
Configuring a multi-boiler system
The cascade communication module must be fitted into all Vitotronic 100 boiler control. Setting codes, see page 80 and 86.
Example of a multi-boiler system
Vitotronic 300-K
145
Vitotronic 300-K
––
––
Number of connected boilers < 5 boilers Set code ”35:2”, ”35:3” or ”35:4”
Vitotronic 100 Vitotronic 100
KMK1 KMK2
Vitotronic 100, HC1
Multi-boiler system Set code ”01:2”
Boiler number 1 Coding ”07:1”
–– ––
Connecting control units into the LON system
The LON communication module (accessories) must be fitted.
ote:
N
The data transfer via the LON system can take several minutes.
Vitotronic 200-H
– – – –
– – – –
KMK1
Vitotronic 300-K
Multi-boiler system Set code ”01:2”
Boiler number 4
Set code ”07:4”
Setting up LON participant numbers
In coding 1, set the LON participant number via coding address “77”.
Vitotronic 300-K
1. Set the number of boilers
In coding 1, set coding address “35”. Coding 1 see page 82.
Note: In one LON system, each number must only be allocated once.
Only one Vitotronic may be programmed as fault manager.
28
Installation and service instructions, Vitotronic 200-H.
Note: In one LON system, each number must only be allocated once.
5727 946 v1.2
Page 29
Initial start-up
Further step-by-step instructions (continued)
Update the LON participant list on Vitotronic 300-K
Only possible if all users are connected and the control unit is encoded as fault manager (coding 79 : 1 factory default setting)
Note: In each heating system, only one Vitotronic may be encoded as fault manager.
1. Press w and
for approx. 2 s. The participant check is initiated.
simultaneously
2. Press D. The participant list is updated after approx. 2 min. Participant check completed.
Example of a LON system
Vitotronic 300-K
Participant no. 5 Code ”77:5”
Send time via LON Code ”7b:1”
Transmit outdoor temperature via LON Set code ”97:2”
”79:1” Fault Manager ”79:0” Control is not fault
”9C:20” Monitoring LON Participant
Vitotronic 200-H
LONLON
Participant no. 10 Set code ”77:10”
Accept time via LON Set code ”81:3”
Receive outdoor temperature via LON Set code ”97:1”
manager ”9C:20” Monitoring LON
Participant
Vitotronic 200-H
LON
Participant no. 11 Set code ”77:11”
Accept time via LON Set code ”81:3”
Device receives the time
”79:0” Control is not fault manager
”9C:20” Monitoring LON Participant
Vitocom
Participant no. 99
Time received via LON
Carrying out a participant check (300-K)
The communication with the system devices connected to the fault manager is tested by means of a participant check. Preconditions:
H The control unit must be programmed as fault manager (code 79:1). H The LON participant number must be programmed in all control units
(see page 28).
H The fault manager participant list must be up to date.
Participant check
F01 : 01
1
Participant
Consecutive number in the participant list
5727 946 v1.2
number
1. Press w and simultaneously for approx. 2 seconds.
2. Select the required participant with
and .
3. Activate check with . ”Check” flashes until its completion.
The display and all key illuminations of the selected participant flash for approx. 60 seconds.
H During communication between
both devices ”Check OK” is displayed.
H ”Check not OK” is displayed, if no
communication is established. Check the LON connection and coding.
4. To check further participants proceed as described under points 2 and 3.
5. Press w and approx. 1 second.
simultaneously for
29
Page 30
Initial start-up
Further step-by-step instructions (continued)
Reducing the maximum burner output (Vitotronic 100)
Vitodens 200 service instructions
Matching the coding addresses to respective system version (Vitotronic 100)
In code 1, set the following coding
ddresses:
a 01 Multi-boiler system 06 Maximum boiler temperature
In code 2, set the following coding addresses: 76:2 With cascade communication
module KMK 07 Boiler number 2F Air bleed function
Matching coding addresses to respective system version (Vitotronic 300-K)
In code 1, set the following coding addresses: 00 System design 35 Number of boilers in cascade 36 Minimum limit of the cascade
supply temperature
37 Maximum limit of the cascade
supply temperature
*1
3b Control type 3C Control strategy 77 LON participant number
*2
A2 DHW priority A5 Heating circuit pump logic
function (economy control)
C5 Minimum supply temperature
limit, heating circuits
C6 Maximum supply temperature
limit, heating circuits
In code 2, set the following coding addresses: 38 Lead boiler rotation 39 Permanent lead boiler 3A Permanent last boiler 55 Function DHW temperature
control
78 LON communication enabled 7A Central control 7F Detached house or apartment
building (management system)
98 Viessmann system number
*1
9C Monitoring LON participants
*1
Not higher than (Vitotronic 100 Coding Level 1 - 06:)
*2
Only in conjunction with LON system
30
5727 946 v1.2
Page 31
Further step-by-step instructions (continued)
Checking outputs (actuators) and sensors
Vitotronic 100 Relay test
Initial start-up
1. Press 9 and approx. two seconds.
The following relay outputs may be selected:
Display indication
11 12 13
14
Check sensors
1. Press .
Scanning operating conditions is active, see page 38.
Relay function
Burner modulation lower output
Burner modulation upper output
Internal pump/ output 20 ON (Power Pump module)
Output 50 ON/ fault indicator in Power Pump Module
simultaneously for
2. Select the relay outputs
2. Scan the actual temperature with
with or .
or .
3. Press .
3. Press
Scanning is completed.
.
5727 946 v1.2
31
Page 32
Initial start-up
Further step-by-step instructions (continued)
Vitotronic 300-K
Relay test
1. Press 9 and simultaneously for
approx. two seconds.
The following relay outputs may be selected:
Output 20M1 ONOutput 52A1 open
Output 52A1 ntr. Output 52A1 close
DHW tank heating pump ONDHW recirculation pump ONHeating pump (M2) ONHeating pump (M3) ON
Check sensors
1. Press Scanning operating conditions is active, see page 43.
.
2. Select the relay outputs with
Mixing valve (M2) openMixing valve (M2) closeMixing valve (M3) openMixing valve (M3) closeCentral fault display ON
2. Scan the actual temperature with or .
or .
Selecting the boiler sequence (Vitotronic 300-K)
f required:
1. I In coding 2, set coding addresses 39 (permanent lead boiler) and 3A (permanent last boiler).
2. Press and simultaneously for approx. two seconds.
3. Select the required boiler sequence with or . By pressing and simultaneously, you can exit the adjustment without saving any modifications made.
3. Press
Note:
The illuminated heating circuit selector button indicates the corresponding heating circuit.
3. Press . Scanning is completed.
4. Press . The adjustment has been transferred.
5. In coding 2, set the coding addresses 38, 41, 42, 43 and 44; see also the function description from page 59.
.
32
5727 946 v1.2
Page 33
Initial start-up
Further step-by-step instructions (continued)
Adjusting the heating curve (Vitotronic 300-K)
The heating curves illustrate the relationship between the outdoor temperature and the boiler water or the supply temperature. To put it simply: the lower the outdoor temperature, the higher the boiler water or supply temperature. The room temperature again depends on the boiler water or the supply temperature.
Factory default settings:
Slope:Shift: = 0
Generally, the heating curve is set:
In range A for underfloor heating systems,In range B for low temperature heating systems (according to the Energy Savings Order),
= 1.4
Slope
3.4
3.2
3.0
2.8
2.6
2.4
90/194
80/176
70/158
60/140
50/122
Supply tempertaure in ºC / ºF
40/104
30/86
35 95
30 86
25 77
20 68
15 59
Set room temperature in ºC / ºF
10 50
10 50
5
-1014-15
41032-523
Outdoor temperature in ºC / ºF
5 41
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
-20
-4
5
5727 946 v1.2
33
Page 34
Initial start-up
Further step-by-step instructions (continued)
Changing slope and shift
(for every heating circuit separately)
1. Call up slope with , adjustable value 0.2 to 3.5; call up shift with
; adjustable value 8.6 to 104°F / –13 to +40°C.
110 230
A
Supply temperature in °C / °F
3.5
2. Change the value with
3. Confirm the set value with
B
1.4
0.2
or .
.
+20 / 68
Outdoor temperature in °C / °F
A Change slope B Change shift
-20 / -4
34
5727 946 v1.2
Page 35
Further step-by-step instructions (continued)
Adjusting the normal room temperature
(for every heating circuit separately)
Initial start-up
D
1
Standard roomtemp.
2 3
1 2 3
20
Reduced roomtemp.
14
Select the normal day temperature with the set value adjuster.
Reduced room temperature:
1. Call up the reduced night
temperature with tm.
Normal room temperature:
The value will be automatically transferred after approx. 2 seconds.
2. Change the value with
or .
3. Confirm the set value with .
Temperature conversion:
˚F ˚C
-4 -20 41 5 57 14 68 20 79 26
230 110
E
D E
Example 1:
Adjustment of the normal room temperature from 68 to 79˚F / 20 to 26˚C.
A Boiler water temperature or supply
temperature in ˚F / ˚C
B Outdoor temperature in ˚F / ˚C C Set room temperature in ˚F / ˚C D Heating circuit pump OFF E Heating circuit pump ON
5727 946 v1.2
Example 2:
Adjustment of the reduced room temperature from 41 to 57˚F / 5 to 14˚C.
Accordingly, the heating curve is adjusted along the set room temperature axis, resulting in modified start/shutdown characteristics for the heating circuit pumps, if the heating circuit pump logic is active.
35
Page 36
Service scanning – Vitotronic 100, HC1
Service level summary
Function Entry Exit Page
Reducing the max. burner output
Relay test Press 9 and “OK”
Temperatures, boiler coding card and brief scans
Operating conditions
Troubleshooting Press “OK” 44 Fault history Press rw and “OK”
Resetting codes to the factory default setting
Coding Level 1 Press 9 and w
Coding Level 2 Press w and rw
Press 9 and tw simultaneously for approx. 2 seconds
simultaneously for approx. 2 seconds
Press 9 and rw simultaneously for approx. 2 seconds
Press 8 Press 8 43
simultaneously for approx. 2 seconds
Press w and rw simultaneously for approx. 2 seconds press D
simultaneously for approx. 2 seconds
simultaneously for approx. 2 seconds
Press “OK” 29
Press “OK” 32
Press “OK” 32
Press “OK” 44
–– 82
Press 9 and w simultaneously for approx. 1 second
Press w and rw simultaneously for approx. 1 second
79
80
Vitodens 200-W Service Instructions
36
5727 946 v1.2
Page 37
Temperatures, boiler coding card and quick scans
Service scanning – Vitotronic 100, HC1
1. Press 9 and rw simultaneously for approx. two seconds.
Brief scans
8
0 System
1 Burner control unit software
E No function 3 Set boiler temperature A Highest demand temperature 4 Burner control unit type Boiler type 5 No function b Maximum heating output in % C Boiler coding card (hexadecimal) c Equipment version (EEPROM) Burner control unit version
d Variable speed
8 8 8 8 8
2. Select the required scan with or .
Control unit software version Programming
design 1
version
(EEPROM)
pump 0 without 1 Wilo 2 Grundfos
unit software version
Cascade module software version
Variable speed pump software version 0: No variable
speed pump
5727 946 v1.2
37
Page 38
Service scanning – Vitotronic 100, HC1
Scanning operating conditions
1. Press 8. 2. Select the required operating
condition scan with or .
Scans
Display
indication
0 01
3__65
263572
030417
Explanation Notes
Boiler number ––
°C Boiler temperature ––
h Burner hours run The hours run can be reset to 0 with D.
The hours run displayed are only approximate values.
Burner starts The burner starts can be reset to 0
with D.
3. Press .
38
5727 946 v1.2
Page 39
Service scanning – Vitotronic 100, HC1
Scanning and resetting service displays
After the limits set up via coding addresses 21 and 23 (see page 80) have been reached, the programming unit display flashes one of the following messages.
Note:
Set code 24:1 and then code 24:0, if maintenance is implemented before a maintenance message is displayed; the set maintenance parameters for hours run and maintenance intervals are then reset to 0.
Display indication
35510
___12
After maintenance has been carried out
1. Reset coding 24: 1 (see page 80) to
24: 0.
Note:
If coding address 24 is not reset, a new maintenance message will be displayed on Monday morning.
2. If required:
PressReset burner run hours and burner
starts with D select the value to 0 (see page 80)
Press or for further queriesPress query is complete
Explanation
Burner run hours have
h
been reached
Time interval
u
(e.g. 12 months) has been reached
1. Scan maintenance messages with
or .
2. Press . The maintenance indication in the display is cleared.
Note:
An acknowledged maintenance message can be redisplayed by pressing (approx. three seconds).
5727 946 v1.2
39
Page 40
Service scanning – Vitotronic 300-K
Service level summary
Function Entry Exit Page
Adjusting display contrast
Participant check Press the w and “OK” buttons
Relay test Press the 9 and “OK” buttons
Boiler sequence Press the g and û buttons
Temperatures and quick scans
Operating status Press the button Press the button 43
Troubleshooting Press the button Press the “OK” button 48
Error history Press the rw and “OK”
Resetting codings to factory default settings
Coding Level 1 Press 9 and w simultaneously
Coding Level 2 Press the w and rw buttons
Press the “OK” and “+” buttons simultaneously; the display will darken
Press the “OK” and “-” buttons simultaneously; the display will get lighter
simultaneously for approx. 2 seconds
simultaneously for approx. 2 seconds
simultaneously for approx. 2 seconds
Press 9 and rw simultaneously for approx. 2 seconds
buttons simultaneously for approx. 2 seconds
Press the w and rw buttons simultaneously for approx. 2 seconds; press the D button; confirm by pressing the “OK” button
for approx. 2 seconds
simultaneously for approx. 2 seconds; confirm by pressing the “OK” button
–– ––
–– ––
Press the w and “OK” buttons simultaneously for approx. 1 sec 29
Press the “OK” button 32
Press the “OK” button 32
Press the “OK” button 41
Press the “OK” button 48
–– 79
Press the 9 and w buttons simultaneously for approx. 1 sec 79
Press the w and rw buttons simultaneously for approx. 1 sec 80
40
5727 946 v1.2
Page 41
Temperatures and quick scans
Service scanning – Vitotronic 300-K
1. Press 9 and rw simultaneously for approx. 2 seconds.
2. Select the required scan with or .
The following values can be scanned subject to the actual equipment level:
Outdoor temperature adjustedOutdoor temperature actualBoiler sequenceP-actual % boiler 1 to 4Output red. %Integral
Boiler temperature actual boiler . . . .
1 to 4
Sensor 17B actual (not used)Set DHW temperatureActual DHW temperature
Supply temperature setSupply temperature actualRoom temperature setRoomtemperature actual
Quick scan 1 to quick scan 8
3. Press “OK”.
The adjusted outdoor temperature can be reset to the current outdoor temperature with D. Boiler output - actual value. No function. at - 1 to - 100 start-up integral in percent; at 1 to 100 shutdown integral in percent (Y - arrow above
ord, when integral grows).
w
Display only if a sensor is connected. Display only if a system design with
a DHW tankhas been encoded . . . . .
(code 00).
Display only if a remote control unit is installed Quick scans 1 to 7, see page NO TAG.
5727 946 v1.2
41
Page 42
42
Service scans – Vitotronic 300-K
Temperatures and quick scans (continued)
8
N/A
Software version remote control mixing valve circuit M3
N/A
re
8
N/A
Software version mixing valve extension M3 Printed Circuit Board
Operating mode mixing valve circuit M3 0 w/o remote
control
1 with
Vitotrol 200
2 with
Vitotrol 300
Node address Number of
LON participants
N/A
design temperatu
r
8
Number of KM BUS participants
N/A
Software version remote control mixing valve circuit M2
A
stem number
N/A
Maximum system
d
8
N/A
Software version mixing valve extension M2 Printed Circuit Board
Operating mode mixing valve circuit M2 0 w/o remote
control
1 with
Vitotrol 200
2 with
Vitotrol 300
N/
A
Subnet address/s
y
Software version neuron chip
N/A
N/A
8
ee coding
Software version programming unit
Software version remote control system circuit A1
umber
Software version communication co-processor
ition adjustable
“92
/decimal:18
6
N/A
Scan
8
Display acc. to system designs (s address 00)
Software version control unit
Operating mode sys. circuit A1 0 w/o remote
control
1 with
Vitotrol 200
2 with
Vitotrol 300
LON participant n
u
SNVT configuration 0 = Auto 1 = Tool
Equipment recogn
i
viacodingaddres
s
hexa-decimal:b8
/
N/A
Scan
1
2
3
4
5 6
7
8
5727 946 v1.2
Page 43
Scanning operating conditions
Service scanning – Vitotronic 300-K
1. Press .
2. Select the required scan
with or .
The following values can be scanned subject to the actual equipment level:
Participant numberHoliday program with departure and
return date
Holiday program active
Outdoor temperatureBoiler sequenceCommon supply temperatureBoiler temp. 1 to 4Sensor 17B (not used)DHW temperature
Supply temperatureReturn temperatureRoom temperature
TimeDateOutput 20 ON/OFFOutput 29 ON/OFFOutput 52 open/closeDHW tank heating pump ON/OFFDHW recirculation pump ON/OFFHeating pump ON/OFFMixing valve open/closedLanguages
3. Press .
If a holiday program has been entered
If a central holiday program is active
Actual value boilers 1 to 4 Display only if a sensor is connected
Display only if a DHW tank sensor is connected
Display only in conjunction with mixing valve circuits Display only if a remote control unit is installed
Position detail in %
Position detail in %. Each language can be selected as permanent display language with
A fault can be acknowledged with “OK”. The fault message in the display will be hidden, but the red fault indicator U continues to flash. The fault message will be redisplayed, if an acknowledged fault message has not been removed by the following morning.
Calling up acknowledged fault messages
Press “OK” for approximately 2 seconds. Select the acknowledged fault with or .
E in the display indicates that the burner control unit is locked out. After the fault has been removed, acknowledge by pressing reset E.
Note:
After acknowledging the fault, E will be displayed until the burner control unit lockout has been lifted.
5727 946 v1.2
43
Page 44
Troubleshooting – Vitotronic 100, HC1
Retrieving fault codes from the fault memory (fault history)
The most recent 10 faults are saved and may be called up. Faults are sorted by date. The most recent fault is fault number 1.
1. Press rw and for approx. 2 seconds.
2. Press or for individual fault codes.
Note:
All saved fault codes can be deleted with D.
3. Press to finish scan.
Faults displayed at the programming unit
The red faults indicator U flashes for every fault. A fault code flashes in the display if a fault message has been issued.
i Consecutive fault number 38 Fault code
U Fault symbol
Call up further fault codes with
.
A fault can be acknowledged with “OK”. The fault message in the display will be hidden, but the red fault indicator U continues to flash. The fault message will be redisplayed, if an acknowledged fault message has not been removed by the following morning.
Calling up acknowledged fault messages
Press “OK” for approximately 2 seconds. Select the acknowledged fault with or .
or
E in the display indicates that the burner control unit is locked out. After the fault has been removed, acknowledge by pressing reset E.
simultaneously
44
Note:
After acknowledging the fault, E will be displayed until the burner control unit lockout has been lifted.
5727 946 v1.25727 946 v1.2
Page 45
Faults displayed at the programming unit (continued)
Troubleshooting – Vitotronic 100, HC1
Fault code
0000ffff
33330000
33338888
bbbb0000
bbbb1111
bbbb4444
bbbb5555
bbbb7777
bbbb8888
e4444
System characteristics
Control mode Service “0F” is only displayed in the
Burner blocked
Control mode (stays in factory default setting)
regulates as if the outdoor temperature was 32°F / 0°C
Control mode (factory default setting)
Burner blocked
Cause Remedy
fault history
Boiler water temperature sensor shorted out
Boiler water temperature sensor cable broken
Flue gas temperature sensor shorted out.
Communication fault ­programming unit (internal)
Internal fault Replace the control unit.
Boiler coding card missing, faulty or incorrect boiler coding card.
Flue gas temperature sensor cable broken.
Fault, supply voltage 24V Replace the control unit.
Service the equipment.
Note:
After the service, reset coding address “24” to “0”.
Check the boiler water temperature sensor
Check the flue gas temperature sensor (see Vitodens 200-W Start-up/Service Instructions).
Check connections and replace programming unit, if required.
Plug in boiler coding card or replace, if faulty.
Check the flue gas temperature sensor (see Vitodens 200-W Start-up/Service Instructions)
5727 946 v1.2
e5555
e8
e9
ea
Burner in fault mode
Internal fault Check ionization electrode and
connecting cables, check tightness of flue gas system. Press “E RESET”.
The ionization current lies outside the permiss. range.
The ionization current lies outside the permiss. range during calibration.
The ionization current lies outside the permiss. range during calibration.
Check ionization electrode and cable. Press “E RESET”.
Check ionization electrode and cable. Press “E RESET”.
Check ionization electrode and cable. Press “E RESET”.
45
Page 46
Troubleshooting – Vitotronic 100, HC1
Faults displayed at the programming unit (continued)
Fault code
ebbbb
ec
ed ee
effff
ffff0000 ffff1111
ffff2222
ffff3333
System characteristics
Burner blocked Boiler control initiated a combustion
Burner in fault mode
Burner blocked Internal fault. Replace control unit.
Burner in a fault mode Maximum flue gas temperature
Cause Remedy
- Heat generated by boiler must be calibration but could not complete the process
The ionization current lies outside the permiss. range during calibration.
Internal fault. Replace the control unit.
At burner start, flame signal is missing or too week.
Flame is lost immediately after it has built (during the safety time).
exceeded (230ºF / 110ºC).
Fixed high limit switch open (activated).
Flame signal is already present at burner start.
removed (boiler is cycling on temperature limits, before calibration process is complete)
- Check the connecting cable and
the ionization electrode, check the flue gas system (flue gas recirculation).
- Verify pump operation
- Switching points of flow switch
marginal (not enough flow)
- Check coding card
- Check gas valve
- Check coding address 82
- Also see address 12:_
Press “E RESET”. Check ionization electrode and
cable. Press “E RESET”.
Check ionization electrode and cable, test ionization current, check gas supply, check ignition and ignition module, check condensate drain. Press “E RESET”.
Check gas supply, check flue gas/exhaust pipe/air intake for flue gas recirculation, check ionization electrode (replace if necessary) Press “E RESET”.
Check the heating system fill level. Bleed air from system. Press “E RESET” after vent system has cooled down.
Check heating system fill level. Check the circulation pump. Bleed air from the system. Check fixed high limit switch and connecting cables. Press “E RESET”.
Check the ionization electrode and connecting cable. Press “E RESET”.
46
5727 946 v1.2
Page 47
Faults displayed at the programming unit (continued)
controlunitiftheequipmentwillno
t
Troubleshooting – Vitotronic 100, HC1
Fault code
ffff4444
ffff8888
ffff9999
ffffaaaa
ffffcccc
ffffdddd
ffffeeee
ffffffff
No fault
code
System characteristics
Burner in a fault mode
Burner blocked Burner control unit fault. Check ignition electrodes and
Burner blocked or in a fault mode
Boiler/burner in standstill Flow switch open Check pump operation and flow
*1
Cause Remedy
No flame signal is present. Check ionization electrode and
cable, measure the ionization current, check the gas pressure, check the gas valve, ignition, ignition module, ignition electrodes and condensate drain. Press “E RESET”.
The gas valve closes too late. Check gas valve and both control
wiring and connections. Press “E RESET”.
Fan speed too low at burner start. Check fan, fan supply cables, fan
power supply and control. Press “E RESET”.
Fan not at standstill. Check the fan, the fan connecting
cables and fan control. Press “E RESET”.
Gas valve faulty or faulty modulation valve control; or vent system blocked.
Strong interference (EMC) field nearby, or faulty main PCB.
Strong interference (EMC) field nearby, or internal fault.
Check the gas valve. check the vent system. Press “E RESET”.
connecting cables. Check the boiler coding card. Check whether a strong interference (EMC) field exists near the equipment; press “E RESET”. Replace control unit if the fault persists.
Restart the equipment. Replace the control unit if the equipment will not restart.
switch.
displayed
*1
Control mode: Boiler/burner fully operational (fault code must be verified and reset). Burner in fault mode: Boiler control requires manual reset before burner can resume operation. Burner blocked: If fault cause is corrected, burner resumes operation.
5727 946 v1.2
47
Page 48
Troubleshooting – Vitotronic 300-K
Retrieving fault codes from the fault memory (fault history)
The most recent 10 faults are saved and may be called up. Faults are sorted by date. The most recent fault is fault number 1.
Fault history
1
1
18
1. Press rw and simultaneously for approx. 2 seconds.
2. Call up the individual fault codes with
Note:
All saved fault codes can be deleted with D.
3. Press .
Faults displayed at the programming unit
Red fault indicator U flashes for all faults. The display flashes “Fault” if a fault message is issued.
Troubleshooting
1. Press .
Outdoor temp. sensor
2. Call up further fault codes
DBG-
1
101
Fault
DBG-
1
U Fault symbol
2 Consecutive number (1 to 10) d5 Fault code (for explanations see
page 49)
d52
with or . The fault can be acknowledged with
. The fault message in the display will be hidden, but the red fault lindicator U continues to flash. A new fault message will be displayed if an acknowledged fault is not removed by the following morning. A central fault messaging device connected to plug will be activated.
or
Fault display in plain text
Ext. faultOutdoor temperature sensorSupply sensorDHW tank sensor (1 or 2; display
only, if a second DHW tank temperature sensor is connected)
Return sensorRoom temperature sensorFlue gas sensorCollector sensorSolar DHW sensorParticipant numberParticipant fault (display only if
control unit is programmed as fault manager)
48
Calling up acknowledged fault messages
Press fault will then be displayed. Select the acknowledged fault with or .
for approx. 2 seconds. The
5727 946 v1.2
5727 946 v1.2
Page 49
Faults displayed at the programming unit (continued)
temperaturewas3
2˚F/0˚C
temperaturesensor(suppl
y
Troubleshooting – Vitotronic 300-K
Fault display in plain text
Ext. faultOutdoor temperature sensorSupply sensorDHW tank sensor (1 or 2; display
only, if a second DHW tank temperature sensor is connected)
Room temperature sensorParticipant fault (display only if
control unit is programmed as fault manager)
Fault code
0000ffff
11110000
System characteristics
Control mode Service “0F” is only displayed in the
Controls as if the outdoor temperature was 32˚F / 0˚C
11118888
22220000
Vitocontrol-S, WB2B controls in a stand-alone manner w/o supply
Calling up acknowledged fault messages
Press for approx. 2 seconds. The fault will then be displayed. Select the acknowledged fault with
or .
Cause Remedy
fault history
Outdoor temperature sensor shorted out
Outdoor temperature sensor cable broken
Common supply temperature sensor shorted out
Service the equipment.
Note:
After the service, reset coding address “24” to “0”.
Check outdoor temperature sensor (see page 67)
Check common supply temperature sensor (see page 66)
22228888
44440000
44444444
44448888
4444cccc
temperature may not be high enough)
Mixing valve closes Supply temperature sensor of
Common supply temperature sensor cable broken
mixing valve circuit M2 shorted out
Supply temperature sensor of mixing valve circuit M3 shorted out
Supply temperature sensor cable of mixing valve circuit M2 broken
Supply temperature sensor cable of mixing valve circuit M3 broken
Check supply temperature sensor (see page 66)
5727 946 v1.2
49
Page 50
Troubleshooting – Vitotronic 300-K
returncontrolopen
returncontrolopen
Mixingvalveprimarycircuitclosed
,
Withouttemperaturesensor:
100ofboiler1to4
codeontherespectiveVitotronic
100ofboiler1to4codeontherespectiveVitotroni
c
ofboiler1to
4
communicationmoduleofth
e
ofboiler1to
4
8D-BoilerNo.2
communicationmoduleofth
e
cable,ifrequire
d
8D-BoilerNo.2
8F-BoilerNo.4
cable,ifrequire
d
(seeaddress07:onpage9and80)
8F-BoilerNo.4(seeaddress07:onpage9and80
)
Faults displayed at the programming unit (continued)
Fault code
55550000
55551111
55558888
55559999
66660000
System characteristics
DHW tank primary pump ON:
Set DHW temp.= set boiler water temp., priority controls are cancelled
or
ith DHW tank primary system:
W DHW heating is started and stopped by DHW tank temp. sensor 2 (not used)
With DHW tank primary system: DHW heating is started and stopped by DHW tank temp. sensor
DHW tank primary pump ON:
Set DHW temp.= set boiler water temp., priority controls are cancelled or
With DHW tank primary system: DHW heating is started and stopped by DHW tank temp. sensor 2 (not used)
With DHW tank primary system: DHW heating is started and stopped by DHW tank temp. sensor
Boiler with maximum temp.,
Cause Remedy
DHW tank temperature sensor 1 shorted out
DHW tank temperature sensor 2 (not used) shorted out
DHW tank temperature sensor cable broken
DHW tank temperature sensor 2 (not used) cable broken
Sensor incorrectly connected Set code “4A:0”
Check DHW tank temp. sensor
66668888 77770000
77778888
88884444 88885555 88886666 88887777 8888CCCCCCCCcccc 8888dddd 8888eeee 8888ffff
With DHW tank primary system: Mixing valve primary circuit closed, no DHW heating (not used).
Control mode Maintenance or error on Vitotronic
Temperature sensor aJB shorted out
Temperature sensor aJB cable broken
Communication fault Vitotronic 100
8C - Boiler No. 1
8E - Boiler No. 3
Check temperature sensor Without temperature sensor: Set code “4b:0”
Check maintenance display or fault
100
Check and replace cascade
Vitotronic 100 and connecting
- check for assigned participant no.
- if problem persists, replace all 4 modules with part no. 7441 586.
50
5727 946 v1.2
Page 51
Faults displayed at the programming unit (continued)
Onlysolarcontrolunitfaultcode
s
ifrequired.
ifrequired.
control
codingaddressA0andremot
e
Troubleshooting – Vitotronic 300-K
Fault code
99992222
99993333
99994444
9999aaaa
9999bbbb
9999cccc
9999ffff
aaaabbbb
bbbb1111
bbbb4444
System characteristics
Control mode Only solar control unit fault codes will be displayed
Control operation perhaps DHW tank cold
Control mode Communication error
Emmissions test mode
Cause Remedy
Collector temp. sensor shorted out, connects to S1 at the Vitosolic
DHW tank temp. sensor shorted out, connects to S3 at the Vitosolic
Temp. sensor shorted out, connects to S2 at the Vitosolic
Collector temp. sensor cable broken, connects to S1 at the Vitosolic
DHW tank temp. sensor cable broken, connects to S3 at the Vitosolic
Temp. sensor cable broken, connects to S2 at the Vitosolic
Fault Solar control unit; displayed if a fault without fault code occurs at the solar control unit
DHW tank primary system configuration error: Code “55:3” has been set, but plug aJB is not plugged in (not used) and/or Codes “4C:1” and “4E:1” have not been set
Programming unit
Internal electronics fault Check electronics PCB and replace,
Check solar control unit sensor
Check solar control unit
Insert plug aJB and check the code (not used).
Check connections and replace programming unit if required.
bbbb5555 bbbb6666
bbbbaaaa
bbbbcccc
Control mode
Constant mode Invalid hardware recognized Check the control software circuit
Mixing valve “close” Communication error mixing valve
Control mode without remote control
bbbbdddd
bbbbeeee
bbbbffff
5727 946 v1.2
Control mode Incorrect LON communication
extention PCB
Communication error Vitotrol remote control, heating circuit A1
Communication error Vitotrol remote control, heating circuit M2
Communication error Vitotrol remote control, heating circuit M3
module
board and confirm the coding address:
- Enter coding 2 (see page 80 for instructions).
- Change code 8A to 176.
- Confirm coding 92:186
Check PCB and replace, if required.
Check connections, lead/cable, coding address “A0” and remote control DIP switches.
Replace the communication module.
51
Page 52
Troubleshooting – Vitotronic 300-K
Faults displayed at the programming unit (continued)
Fault code
cccc2222
cccc4444
CCCCcccc5555
cccceeee
ccccffff
dddd6666
dddd7777
dddd8888
ddddaaaa
ddddbbbb
ddddcccc
dddddddd
ddddeeee
ddddffff
System characteristics
Control mode
Control mode, max. pump speed (Not used)
Control mode
Control mode without room influence
Cause Remedy
Cable break KM BUS to solar control unit.
Communication error with function extension 0 to 10 V
Communication fault, variable speed circulation pump, heating circuit connection set
Communication error Plug-in adaptor for external safety equipment
Error LON communication module
Fault at DE1 in plug-in adaptor for external safety equipment (not used)
Fault at DE2 in plug-in adaptor for external safety equipment (not used)
Fault at DE3 in plug-in adaptor for external safety equipment (not used)
Room temperature sensor shorted out, Heating circuit A1
Room temperature sensor shorted out, Heating circuit M2
Room temperature sensor shorted out, Heating circuit M3
Room temperature sensor cable broken, Heating circuit A1
Room temperature sensor able broken, Heating circuit M2
Room temperature sensor cable broken, Heating circuit M3
Check KM BUS cable and the solar control unit Without solar control unit: Set code “54: 0”
Check connections and cables/leads; replace the function extension, if required
Without function extension: Set code “9d: 0”
Check setting of coding address ”30” Set to “0” 30:”0”
Check plug-in adaptor for external safety equipment and cables/leads Without plug-in adaptor: Set coding “94: 0”
Replace communication module
Check connections at “DE1” to “DE3”
Check room temperature sensor
Check the room temperature sensor and the DIP switch on the Vitotrol
52
5727 946 v1.2
Page 53
Faults displayed at the programming unit (continued)
Troubleshooting – Vitotronic 300-K
LON participants fault messages
Preconditions: The control unit must be programmed
as fault manager (code “79:1”)
Fault code
00001111
to
System characteristics
Control mode A participant, e.g. 12
99998888
99999999
Participant
11112222
Cause Remedy
Download fault code to participant (Vitotronic 200-H), has developed a fault or There is no connection to the participant
Fault message active at Vitocom 300 or Fault at the Vitocom 300 or No connection to the Vitocom 300
See the Installation and Service instructions
of the relevant control unit.
- Check coding
- Check LON communication module
- Update participant list
- Carry out a participant check
Check external connections at Vitocom 300
See separate Installation and Service
instructions
- Check coding
- Check LON connection cable
- Update participant list
- Carry out a participant check
5727 946 v1.2
53
Page 54
Function description – Vitotronic 100, HC1
Boiler temperature control
Brief description
The boiler water temperature is regulated by controlling a modulating burner. The set boiler water temperature set-point is controlled by Vitotronic 300-K.
Functions
The boiler water temperature is
ecorded separately:
r
Fixed high limit (FHL)Boiler temperature sensor KTS
(changes in resistance NTC)
Control sequence
Boiler goes cold
(set value 4ºC below set point) The burner start signal is set to the set boiler water temperature less (=less
7.2ºF or 4ºC) and the burner starts its own monitoring program.
Coding addresses which influence the boiler temperature control
06 (see page 80). For a description, see the coding overview.
Upper control limit. Electronic maximum limit Setting range: 20 to boiler coding card default The maximum boiler water temperature limit can be adjusted via coding address 06.
Boiler heats up. The burner shutdown point is determined by the switch-off differential of (=less 14.4ºF or 8ºC) above set point.
Note:
Value on display shown in K (Kelvin). 1 K = 1.8 Fahrenheit degrees or 1 Celsius degree.
Air bleed program
Note:
lose the gas shut-off valve when
C operating the air bleed program.
The air bleed program is activated via coding address 2F:1 (the display shows EL). During the air bleed program, the circulation pump will be alternately switched ON and OFF for 30 seconds respectively over a period of 20 minutes.
The burner is switched OFF during the air bleed program. The program is automatically deactivated after 20 minutes, and the coding address is set to 0.
5727 946 v1.2
54
Page 55
Cascade control unit
Brief description
Function description – Vitotronic 300-K
The supply temperature is regulated by starting or stopping the burner or by starting/stopping individual burners. The boilers will be controlled to the set boiler water temperature determined by the cascade control (stand-alone type of control).
Subject to the system design, you may select between one gross calorific strategy and two net calorific strategies.
Set supply temperature
The set supply temperature is
termined from
de the set supply temperature set-point
values of system circuit A1 and mixing valve circuits M2 and M3,
the set supply temperature values of
additional heating circuits (e.g. Vitotronic 200-H),
the set DHW temperature andexternal demands (e.g. the set
supply temperature defaulted by coding address 9b or via the Input Module 0 to 10 V).
The boiler sequence (see page 59) can be determined via coding 2 and the boiler sequence selection.
Coding addresses which influence the cascade control
35 to 3F, 41 to 4F. For a description, see the coding overview.
Upper control limit
Electronic maximum system supply temperature limit. Setting range: 68 to 26˚ F / 20 to 127˚C. The maximum supply temperature limit can be adjusted via coding address 37. This value must be set no higher than the lowest value of coding address 06 of all connected Vitotronic 100, HC1.
Lower control range limit
Electronic minimum system supply temperature limit. Setting range: 68 to 261˚ F / 20 to 127˚ C. The minimum supply temperature limit can be adjusted via coding address 36.
5727 946 v1.2
55
Page 56
Function description – Vitotronic 300-K
Cascade control (continued)
Control sequence
Stand-alone type of control: Parallel boiler control (coding 3b : 0 without supply temperature sensor or coding 3b : 1 with supply temperature sensor)
The cascade control unit defaults the set boiler water temperature to all currently active boilers. Every Vitotronic 100 individually regulates the dafaulted set temperature.
The control sequence is subject to the start-up and shutdown criteria selected with control strategy (coding address 3C):
Gross calorific strategy.Net calorific strategy 1.Net calorific strategy 2.
With supply temperature sensor:
The contro deviation is calculated from the set supply temperature and the actual supply temperature to determine the start-up and shutdown criteria.
Gross calorific strategy (Condensing strategy)
It is the aim of the gross calorific strategy to operate as many boilers as possible at the lowest output (modulation) level.
Start-up criterion
Boilers are started via an output statement (coding 3d : 1). An additional boiler will be started when the currently required output can also be achieved by the currently active boiler plus the next boiler in the boiler sequence (see page 66).
Without supply temperature sensor: The control deviation is calculated from the set boiler water temperature and the estimated average actual boiler water temperture of the active boiler to determine the start-up and shutdown criteria. Only those boilers are taken into consideration whose boiler circuit pumps are not switched OFF.
Advantages
Optimum utilization of the
Long burner operating times
Shutdown criterion
The boiler is shut down via a shutdown integral. The shutdown criterion is met when the shutdown integral exceeds a limit set via coding address 46, and the boiler started last will be shut down.
condensing effect (as many boilers active as possible)
56
5727 946 v1.2
Page 57
Cascade control (continued)
Net calorific strategy 1
Function description – Vitotronic 300-K
Conventional boilers are preferably operated at their upper output range, to reliably prevent the formation of condensate due to low return temperatures. With net calorific strategy 1, an additional boiler will only be started if the maximum output of all currently active burners is insufficient to achieve the set supply temperature. A boiler will be shut down, when the remaining boiler(s) can achieve the required output on its/their own.
Start-up criteria
The boiler is started via a start-up integral. The start-up criteria is met when the start-up integral exceeds a limit set via coding address 45, and the next boiler in the sequence will be started (see page 59).
Benefit: As few boilers as possible are active.
Shutdown criteria
The boiler is shut down via an output statement (coding 3d: 1). A boiler is shut down when the currently required output can be achieved without the boiler which was started last.
Net calorific strategy 2
With the net calorific strategy 2, an additional boiler will only be started if the maximum output of all currently active burners is insufficient to achieve the set supply temperature. A boiler will be shut down if the burner was returned to its minimum output because of a large negative control deviation, and the output is then still too high.
Start-up criteria
The boiler is started via a start-up integral. The start-up criteria is met when the start-up integral exceeds a limit set via coding address 45, and the next boiler in the sequence will be started (see page 59).
Benefit: Long burner operating times
Shutdown criteria
The boiler is shut down via a shutdown integral. The shutdown criteria is met when the shutdown integral exceeds a limit set via coding 46, and the boiler started last will be shut down.
5727 946 v1.2
57
Page 58
Function description – Vitotronic 300-K
Cascade control (continued)
Control strategy example
Two boiler system with modulating burners and separate flue gas systems:
Boiler 1: 100% rated output (basic load set to 25%)Boiler 2: 100% rated output (basic load set to 25%)
Gross calorific strategy (coding 3C: 0)
Start-up Switching OFF
Rated output in %
100
100
200
150
100
Total Boiler 2 Boiler 1
66 25
25
25
0
0
0
Time
Rated output in %
100
66 25
100
25
200
150
100
Total Boiler 2 Boiler 1
25
0
0
0
Net calorific strategy 1 (coding 3C: 1)
Start-up Switching OFF
Rated output in %
100
100
200
150
100
Total Boiler 2 Boiler 1
50 25
50
25
0
0
0
Time
Rated output in %
100
50 25
100
50
200
150
100
Total Boiler 2 Boiler 1
25
0
0
0
Time
Time
58
5727 946 v1.2
Page 59
Cascade control (continued)
Net calorific strategy 2 (coding 3C: 2)
Start-up Switching OFF
Function description – Vitotronic 300-K
100
50 25
0
100
50
0
200
150
100
Rated output in %
Total Boiler 2 Boiler 1
25
0
Time
Boiler sequence
The boiler sequence is determined by
he boiler sequence selection and the
t following coding addresses (see also page 86): 38 Changing the lead boiler and the
boiler sequence. 38: 1 Every 1
month, the boiler with the burner which has operated for the shortest number of hours becomes lead boiler.
38: 2 After 200 to 20,000 run
hours, the boiler with the next higher number (coding address 07 of Vitotronic 100) becomes lead boiler.
st
day of the
100
66 25
0
100
25
0
200
150
100
Rated output in %
Total Boiler 2 Boiler 1
25
0
Time
39 Boiler 1, 2, 3 or 4 permanent lead
boiler.
3A Boiler 1, 2, 3 or 4 permanent last
boiler. 41 ECO threshold boiler 1. 42 ECO threshold boiler 2. 43 ECO threshold boiler 3. 44 ECO threshold boiler 4.
Via the ECO threshold, every boiler can be disabled or enabled subject to the outdoor temperature. The ECO control becomes disabled, if the boiler is required to achieve the set supply temperature, when enabled boilers have failed. At least the lead boiler remains active if all boilers in a system are disabled by the ECO control.
5727 946 v1.2
59
Page 60
Function description – Vitotronic 300-K
Heating circuit control
Brief description
The control unit provides control circuits for one high temperature (boiler) circuit and two mixing valve circuits. The set supply temperature of every heating circuit results from the outdoor temperature, the set room temperature, the operating mode and the heating curve. The supply temperature of the system circuit corresponds to the common system supply temperature. The supply temperature of the mixing valve circuits is regulated by the stepped opening or closing of the mixing valves. The mixing motor control changes the actuating and pause times subject to the control difference (control deviation).
Coding addresses which influence the heating circuit control
9F,A2 to A7, A9, C3 to C8, F1, F2 For a description, see the coding overview (see page 86).
Time program
The control unit timer changes in accordance with the times programmed in the room heating and DHW heating program between the heating with normal room temperature and heating with reduced room temperature operating modes. Every operating mode has its own set level.
Outdoor temperature
A heating curve must be set up for matching the control unit to the building and the heating system. The heating curve characteristics determine the set boiler water temperature subject to outdoor temperature. An average outdoor temperature (dampened) is used for control purposes. This comprises the actual and the adjusted outdoor temperature.
Functions
The high temperature (boiler) circuit is subject to the boiler water temperature and its control range limits. The heating circuit pump is the controlling element. The mixing valve circuit supply temperature is recorded by the supply temperature sensor.
5727 946 v1.2
60
Page 61
Heating circuit control (continued)
Function description – Vitotronic 300-K
Domestic hot water temperature
With priority control:
The set supply temperature will be set to 32˚F / 0˚C during DHW heating. The mixing valve closes, and the heating circuit pumps are switched OFF.
Without priority control:
The heating circuit control unit continues to operate with the same set value.
Room temperature
In conjunction with remote control and room temperature input (observe coding address b0).
Compared to the outdoor temperature, the room temperature has a greater influence on the common set supply temperature. This influence may be adjusted via coding address b2. In conjunction with the mixing valve circuit: For control differences (actual value deviation) above 3.6˚F / 2˚C room temperature, the influence can be increased again (via coding address b6, quick heat-up/quick setback).
Quick heat-up: The set room temperature must be raised by a minimum of 3.6˚F / 2˚C by:
Pressing party buttonChanging from heating with reduced
temperature to heating with normal
temperature. Start-up optimisation. Quick heat-up will stop when the set room temperature has been reached.
.
Heating circuit pump logic (economy circuit)
The heating circuit pump is switched OFF (set supply temperature set to 0˚C / 32˚F), when the outdoor temperature exceeds the value selected via coding address A5.
Extended economy circuit
The heating circuit pump is switched OFF, and the set supply temperature is set to 32˚F / 0˚C, if: The outdoor temperature exceeds the
value selected via coding address A6.
The set room temperature is reduced
via coding address A9.
In conjunction with the mixing valve
circuit: The mixing valve has been closed for 12 minutes (mixing valve economy function, coding address A7).
Slab curing function
(only in conjunction with a mixing valve circuit).
Please note:
Four different temperature profiles can be selected for drying the slab. These profiles are activated via coding address F1.
When the slab curing function is activated, the heating circuit pump of the mixing valve circuit is switched ON, and the supply temperature will be held at the selected profile. After completion (30 days), the mixing valve circuit will be regulated automatically via the set parameters.
System dynamics – mixing valve circuit
(only in conjunction with a mixing valve circuit)
You can influence the control characteristics of the mixing valve via coding address C4.
Central operation
Central operation for all downstream heating circuits can be programmed via coding address 7A. The heating and holiday program then applies to all heating circuits in the system. The programming unit of the other heating circuits displays central control when the heating program and holiday program buttons are activated. Any set holiday programs in the heating circuit programming units will be deleted.
Party and economy buttons on all control units are without effect.
Frost protection
When the outdoor temperature falls below 34˚F / 1˚C, a supply temperature of at least 50˚F / 10˚C will be safeguarded. For changes, see coding address A3, variable frost limit.
Quick setback: The set room temperature must be reduced by a minimum of 3.6˚F / 2˚C by:
Pressing economy button .Changing from room heating with
normal temperature to heating with
reduced temperature. Shutdown optimisation. Quick setback will stop when the set room temperature has been reached.
5727 946 v1.2
61
Page 62
Function description – Vitotronic 300-K
Heating circuit control (continued)
Supply temperature control
Differential temperature: The differential temperature may be adjusted via coding address 9F; factory supplied setting 15˚F / 8˚C.
110 230
The differential temperature is that minimum temperature differential by which the common supply temperature should be higher than the currently required supply temperature of the mixing valve circuit.
System with only one mixing valve
circuit: The common set supply temperature will be automatically held 15˚F / 8˚C above the set supply temperature of the mixing valve circuits.
System with high temperature
(boiler) circuits and mixing valve circuits: The common set supply temperature operates in accordance with its own heating curve. The differential temperature of 15˚F / 8˚C towards the set supply temperature of the mixing valve circuits is set up at the factory.
Upper control limit
Electronic maximum limit: Setting range: 34 to 261˚F / 1 to 127˚C. Changes via coding address C6.
Please note:
The maximum limit is no replacement for the underfloor heating system temperature limiter.
87
189
8K
+8K
+20/ 68 -20/-4
Supply temperature °C / °F
Outdoor temperature in °C / °F
A Max. common supply temperature B Slope = 1.8 high temperature
(boiler) circuit
C Slope = 1.2 mixing valve circuit D Common supply temperature (at a
differential temperature = 15˚F / 8˚C)
E Minimum common supply
temperature
Lower control range limit
Electronic minimum limit: Setting range: 34 to 261˚F / 1 to 127˚C. Changes via coding address C5 (only effective in standard mode).
Control sequence
Mixing valve circuit
he mixing valve motor will not be
T activated within the neutral zone (±2˚F / 1˚C).
62
Supply temperature falls
(set value -2˚F / –1˚C) The mixing valve motor receives the open signal. The signal duration lengthens with an increasing control differential. The duration of pauses reduces with an increasing control differential.
Supply temperature rises
(set value +2˚F / 1˚C) The mixing valve motor receives the close signal. The signal duration lengthens with an increasing control differential. The duration of pauses reduces with an increasing control differential.
5727 946 v1.2
Page 63
DHW tank temperature control
Brief description
Function description – Vitotronic 300-K
The DHW tank control logic is a set-point control. It is the result of starting and stopping the DHW pump. The switching differential is ±4.5˚F /
2.5˚C.
Functions
Time program
n automatic program or an individual
A time program may be selected for DHW heating and the control of the DHW recirculation pump. Compared with the space heating circuit’s heat-up phase, DHW heating in automatic mode starts 30 minutes earlier. The individual time program enables up to four switching periods per day to be set via the time switch to control the DHW heating/heating and the DHW recirculation pump. Any DHW tank heating sequence will be completed, independent of the time program.
During DHW tank heating, a constant boiler supply temperature will be set (36˚F / 20˚C higher than the set DHW tank temperature, adjustable via coding address 60) and space heating is switched OFF (optional DHW tank priority).
In conjunction with coding address 7F
7F: 1 Detached house: Automatic mode:
For systems with two or three space heating circuits, the heating times for the first of the existing heating circuits will be applied.
Individual time program:
The switching times for DHW heating and the DHW recirculation pump have the same effect on all heating circuits.
Coding addresses which influence the DHW tank control
54 to 75, 7F, A2. For a description, see the coding overview.
7F : 0 Apartment building: Automatic mode:
For systems with two or three heating circuits, the heating times for the respective heating circuit will be applied.
Individual time program:
The switching times for DHW heating can be adjusted separately for each heating circuit.
DHW priority
With DHW priority (coding A2: 2):
The set supply temperature will be
set to 32˚F / 0˚C while the DHW
tank is being heated.
The mixing valve closes, and the
heating circuit pumps are switched
OFF. With DHW priority:
The heating circuit control unit
continues to operate with the same
set value.
Frost protection
The DHW tank will be heated to 68˚F / 20˚C, if the DHW temperature falls below 41˚F / 5˚C.
5727 946 v1.2
Auxiliary functions – DHW heating
This function is activated by providing a second set DHW temperature via coding address 58 and activating the
th
DHW phase for DHW heating.
4
Set DHW temperature
The set DHW temperature can be adjusted between 50 and 140˚F / 10 and 60˚C. The set range can be expanded to 203˚F / 95˚C via coding address 56. You can select the set DHW temperature at the programming unit of the control and at every Vitotrol 300 remote control unit (if installed). You can determine the allocation to individual heating circuits via coding address 66.
DHW recirculation pump It delivers hot water to the draw-off points at adjustable times. Up to four control periods can be set at the timer.
Auxiliary circuits
The DHW heating can be disabled or enabled by changing over the heating program.
System with DHW tank heating system
The above functions also apply in conjunction with calorifiers. Set the following codings: 4C: 1, 4E: 1, 55: 3. For a description, see the coding overview.
Systems with Vitosolic
A third DHW temperature set-point can be programmed via coding address 67. Reloading suppression will be active below the set temperature. The DHW tank is heated only by the solar heating system.
63
Page 64
Function description – Vitotronic 300-K
DHW tank temperature control (continued)
Control sequence
Pump delay
The DHW pump continuous operation
(coding 62: 10) after the DHW tank heating, until: – the actual temperature is 9˚F / 5˚C
higher than the set DHW temperature or
– the maximum time delay (adjustable
via coding address 62) has been reached.
Without the pump time-delay for
DHW tank heating (coding 62: 0).
Coding 55: 0: DHW heating
The DHW tank goes cold
(set value 4.5˚F / –2.5 ˚C, adjustable via coding address 59) The common supply temperature is adjusted 36˚F / 20˚C higher than the set DHW (adjustable via coding address
60).
The DHW tank is hot
(set value +4.5˚F / 2.5˚C) The common set supply temperature is returned to the weather-compensated value.
Coding 55: 1: Adaptive DHW tank heating
With adaptive DHW tank heating, the speed of the temperature rise during DHW heating is taken into account. Also taken into account is the question of whether the boiler will be required to supply heat after the DHW tank has been heated or whether residual boiler heat should be transferred to the DHW tank. Accordingly, the control unit determines the burner and DHW recirculation pump shutdown point to prevent the set DHW temperature being substantially exceeded after the DHW tank has been heated.
Coding 55: 2: DHW tank temperature control with 2 DHW tank temperature sensors
st
The 1
DHW tank temperature sensor enables the DHW pump, and is evaluated for stop conditions during
nd
the pump run-on time. The 2
DHW tank temperature sensor (inside the cold water inlet) is designed to prematurely start DHW tank heating when large quantities of DHW are drawn off as well as to prematurely stop DHW tank heating if no DHW is drawn.
Coding 55: 3: DHW tank control – DHW heating (for DHW loading systems only) The DHW tank goes cold
(set value -4.5˚F / –2.5˚C, adjustable via coding address 59), The common set supply temperature
is adjusted 36˚F / 20˚C higher than the set DHW temperature (adjustable via coding address 60).
The primary DHW pump is switched
ON.
The three-way mixing valve opens
and then regulates to the defaulted set value.
The DHW pump cycles (short term
ON and OFF) until the set supply temperature has been reached, then it runs constantly. If, during DHW tank heating, the actual value stays below the required set supply temperature, then the DHW pump will temporarily cycle again.
The DHW tank is hot
(1stDHW tank temperature sensor: Actual value set value and 2ndDHW tank temperature sensor: Actual value > set value -2.7˚F / –1.5˚C) The common set supply temperature
is returned to the weather­compensated value;
The DHW pump:
– is immediately switched OFF, if the
three-way mixing valve is open or
– is switched OFF after run-on time
adjustable via coding 62.
64
5727 946 v1.2
Page 65
Components from the parts list
Components – Vitotronic 300-K
The main PCB comprises:
Relays and outputs for controlling .
pumps and actuators.
Slot for power supply unit.
Main PCB low voltage
The main PCB comprises:
onnection plug for sensors,
C
communication connections and external connections.
Slot for PCB, LON communication
module, programming unit and Optolink PCB.
Supplementary PCB
When replacing the PCB:
1. Record the coding and adjustments made at the control unit.
2. Replace the PCB.
3. Set coding 8A: 176, and coding
address 92 to 92: 186.
Mixing valve extension PCB
Mixing valve extension s
upplementary PCB
This is plugged into the mixing valve extension PCB. All data is processed and outputs (relay) are selected.
Power supply unit PCB
The power supply unit PCB comprises
he low voltage supply for all electronic
t equipment.
Programming unit
Setting the:
Heating programSet valuesSwitching timesHeating curve (slope and shift)DateTimeEconomy and party modeCoding
Displaying:
TemperaturesOperating conditionsFaults
Optolink / override test switch P
CB
The PCB comprises:
Burner standby displayFault displayOptolink laptop interfaceOverride switch
Override switch for testing flue gas with briefly raised boiler water temperature.
The following functions are triggered in position h:
Starting all pumps.Mixing valve in control function.
Front panel with heating circuit
elector keys
s
Display and selection of the heating circuit.
Programming unit ON / OFF switch
The programming unit comprises:
FuseMains ON / OFF switch.
The PCB comprises the relay for the
ontrolling the mixing valve motor and
c the heating circuit pump of the mixing valve circuits.
5727 946 v1.2
Fuses
F1: 6.3 A (slow), 250 V,
ax. power loss 2.5 W,
m to protect the actuators, pumps, and all electronics.
LON communication module
PCB for data exchange with:
Vitotronic 200-HVitocom 300
The communication interruption will be displayed.
65
Page 66
Components – Vitotronic 300-K
Components from the parts list (continued)
DHW tank temperature sensor
720
700
680
660
640
620
600
580
560
Resistance in
540
0 20 40 60 80 100 32 68 104 140 176 212
DHW tank temperature in °C / °F
Common supply temperature sensor (Low-loss header)
760
740
720 700
680
660
640
620 600
580
560 540
Resistance in
0
20 40 60 80 100 120 140
32 68 141 176 212 248 284104
Flow or return temperature in °C / °F
Connection
See page 19.
Check sensor
1. Remove wire from terminal X2.7.
2. Check the sensor resistance of the
plug at terminals 1 and 2 or 2 and 3 (if a second DHW tank temperature sensor has been connected).
DHW tank
Resistance in ΩΩΩ
temperature in ˚F / ˚C
104 / 40 122 / 50 140 / 60
578 597 616
Connection
See page 16.
Check sensor
1.Remove wire from terminal X2.4.
2.Check the sensor resistance of the
plug at terminals 1 and 2.
3. Compare measurement with the actual temperature displayed (for scanning, see page 41). Check the installation and replace sensor, if necessary, in case of severe deviation.
Specification
Protection: IP 32 Permiss. ambient temperature: During operation:
32 to 194˚F
0 to +90˚C
During storage and transport:
–4 to 158˚F
–20 to +70˚C
3.Compare measurement with the actual temperature displayed (for scanning, see page 41). Check the installation and replace sensor, if necessary, in case of severe deviation.
Specification
Protection: IP 32 Permiss. ambient temperature: During operation:
32 to 212˚F
0 to +100˚C During storage and transport: –4 to 158˚F –20 to +70˚C
66
5727 946 v1.2
Page 67
Components from the parts list (continued)
Outdoor temperature sensor
Components – Vitotronic 300-K
Connection
See page 16.
Check sensor
1. Remove wire from terminal X2.2.
1.
600
580
560
540
520
4.
2.
5.
3.
2. Check the sensor resistance at terminals 1 and 2 of the plug.
Outdoor temperature in ˚F / ˚C
14 / -10
32 / 0 68 / 20
3. Disconnect cores from the sensor, if actual values deviate severely from the curve, repeat the sensor measurement and compare with the actual temperature (for scanning, see page 41).
4. Depending on the result, replace cable or outdoor temperature sensor.
5. Scan actual temperature (for scanning, see page 41).
Specification
Protection: IP 43 Permissible ambient temperature during operation, storage and transport:
Resistance in ΩΩΩ
480 500 546
–40 to 158˚F –40 to +70˚C
500
480
460
440
420
Resistance in
400
-40 -30 -20 -10 0 10 20 30
5727 946 v1.2
-40 -22 -4 14 32 50 68 86
Outdoor temperature in °C / °F
67
Page 68
Components – Vitotronic 300-K
Fuse
F1 T4 A, 250V
Max. power loss 1.6W
A1 Power supply module
68
5727 946 v1.2
Page 69
Mixing valve circuit extension kit
Mixing valve motor
lug in the mixing valve motor
A P
| Mixing valve motor open ~ Mixing valve motor close
B Connect to X1 or X3 on the A4
module
Components – Vitotronic 300-K
Changing the rotational direction
Remove the cover and reinsert 3-pole plug A turned by 180˚.
Test
The relay test of the control unit moves the mixing valve to open and close.
Manual mixing motor adjustment
Lift the motorized lever up, unhook the mixing valve handle and remove plug A.
For 24V actuators please refer to instructions supplied with the actuator.
Specification
Rated voltage: 120 VAC~ Rated frequency: 60 Hz Power consumption: 4 W Protection: IP 42 Torque: 3 Nm Run time from close to open: 120 sec
5727 946 v1.2
69
Page 70
Components – Vitotronic 300-K
Installation examples
Mixing valve insert conversion (if required), see mixing valve installation instructions.
Factory supplied
Mixing valve motor rotational direction Change the mixing valve motor rotational
direction for these installation examples
HV
HR
KV
KV Boiler supply HR Heating return HV Heating supply
HV
HR
KV
70
5727 946 v1.2
Page 71
Components – Vitotronic 300-K
Remote control
Vitotrol 200
(with integral room temperature sensor for room temperature feed-back in conjunction with a mixing valve circuit) Setting of:
Day temperatureHeating programEconomy and party mode
Function changes can be made via coding addresses A0, b0 to b9, C0 to C2, E1, E2 (see coding overview).
Connection
2-wire cable 164ft. / 50m
Room temperature sensor connection
A
Two-wire cable, max. 115 ft. / 35 m length with a cross-section of 1.5 mm (AWG 16) copper.
2
}
B
A Wall mounting base for Vitotrol 200 B To control unit A2 terminal aVG C Separate room temperature sensor
13b
9
C
5727 946 v1.2
71
Page 72
Components – Vitotronic 300-K
Remote control (continued)
ON
S6
D
1 2 3 4
Specification
Power supply via KM BUS. Safety class: III Protection: IP 30 Permiss. ambient temperature During operation:
32 to 104˚F
0 to +40˚C
In storage and transport:
–4 to +149˚F –20 to +65˚C
D Printed circuit board DIP switches
(rear of the top casing)
Remote control affects
System circuit A1
DIP switch setting
Factory setting (Heating circuit selection button !)
Mixing valve circuit M2 (Heating circuit selection button ?)
Mixing valve circuit M3 (Heating circuit selection button §)
When connecting a separate room temperature sensor, set DIP switch S6.3 to ON.
Set room temperature setting range:
50 to 96˚F 10 to 30˚C
adjustable between
37 to 73˚F 3 to 23°C or 63 to 99˚F
17 to 37˚C via coding address E1. Setting of the reduced set room temperature at the control unit.
72
5727 946 v1.2
Page 73
Components – Vitotronic 300-K
Remote control (continued)
Vitotrol 300
(with integral room temperature sensor for room temperature feed-back in conjunction with a mixing valve circuit) Setting of:
Normal and reduced temperatureDomestic hot water temperatureHeating programHoliday programSwitching timesEconomy and party mode
Function changes can be made via coding addresses A0, b0 to b9, C0 to C2, E1, E2 and F2 (see coding overview).
A
}
B
A Wall mounting base for Vitotrol 300 B To the control unit A2 terminal aVG C Separate room temperature sensor
13b
9
C
Connection
2-wire cable 164ft. / 50m.
Room temperature sensor connection
Two-core cable, max. 115ft. / 35 m length with a cross-section of 1.5 mm (AWG 16) copper.
2
5727 946 v1.2
73
Page 74
Components – Vitotronic 300-K
Remote control (continued)
1 2 3 4
RTS
int. ext.
3 2 1
DIP switch setting
Factory setting
ON
ON
S3
1 2 3 4
ON
1 2 3 4
A
S3
ON
A PCB DIP switches (back of the
remote control)
Remote control affects
System circuit A1 (Heating circuit selection button !)
Mixing valve circuit M2 (Heating circuit selection button ?)
Mixing valve circuit M3 (Heating circuit selection button §)
Specification
Power supply via KM BUS. Safety class: III Protection: IP 30 Permiss. ambient
1 2 3 4
temperature: In use:
32 to 104˚F
0 to +40˚C
In storage and transport:
–4 to+149˚F
–20 to +65˚C Setting range for Normal set room temp:
50 to+86˚F
10 to 30˚C adjustable between
37 to 73˚F
3 to 23˚C
or
63 to 97˚F
17 to 37˚C via coding address E1 Reduced set room temp:
37 to 97˚F
1 2 3 4
3 to 37˚C
Battery type: Use alkaline
manganese
batteries
type MICRO-
LR03 (AAA) which
do not contain
pollutants
When connecting a separate room temperature sensor, set DIP switch S30.3 to ON.
1 2 3 4
ON
74
5727 946 v1.2
Page 75
Remote control (continued)
Connecting several remote control units
When connecting several remote controls to the control unit, install a terminal box on site.
Version 1
Components – Vitotronic 300-K
C
max. 50ft. / 15m
}
A
A To control unit A2 terminal aVG B Terminal box (on site) C Vitotrol 200/300 D Vitotrol 200/300 E Vitotrol 200/300
D
max.
On-site connection via terminal box:
Connect in accordance with the diagram.
The total length of all KM BUS cables
should be limited to 164ft. / 50m.
E
max. 50ft. / 15m50ft. / 15m
B
5727 946 v1.2
75
Page 76
Components – Vitotronic 300-K
Remote control (continued)
Version 2
}
A
max. 50ft. / 15m
C D
max.
50ft. / 15m
max. 50ft. / 15m
E
F
B
A To control unit A2 terminal aVG B Terminal box (on site) C Vitotrol 200/300 D Vitotrol 200/300 E Vitotrol 200/300 F Further BUS participants
If several remote control units and
additional KM BUS participants are connected, make the connections via a terminal box (on-site) as shown in the diagram.
The total length of all KM BUS cables
should be limited to 164ft. / 50m.
76
5727 946 v1.2
Page 77
Components – Vitotronic 300-K
Room temperature sensor
The room temperature sensor measures the actual room temperature, if the remote Vitotrol unit cannot be installed in a suitable location.
600
590
580
570
560
550
540
530
520
510
Resistance in
500
0
5 10 15 20 25 30 35 40
32 41 50 59 68 77 86 95 104
Room temperature in °C / °F
Connection
See page 71 to 76.
Check sensor
1. Disconnect the wires from the
sensor.
2. Check the sensor resistance at terminals 9 and 13b.
Room temperature in ˚F / ˚C
50 / 10 59 / 15 77 / 25
3. Compare measurement with the actual temperature displayed (for scanning, see page 41). Check the installation and replace sensor, if necessary, in case of severe deviation.
Specification
Protection: IP 30 Permiss. ambient temperature: During operation:
32 to 104˚F
0 to +40˚C
In storage and transport:
–4 to +149˚F
–20 to +65˚C
Resistance in ΩΩΩ
522 534 557
5727 946 v1.2
77
Page 78
Components – Vitotronic 300-K
Input Module 0 to 10 V
For external control of the boiler/supply temperature via a 0 to 10VDC signal 30 to 120˚C or 10 to 100˚C (86 to 248˚F or 50 to 212˚F) or to signal reduced mode and regulate a heating circuit pump to a lower speed.
24V
5V
Electronics
F1 50mA (slow)
L1
N S Ö P 1 2 3 1 2 3
40
120 VAC
A
ON
OFF
157 144 145
Power connection aVF 0 to 10VDC input aVG KM BUS to control unit aBJ Potential free output contact
DIP switch
1 to 3: 1: 2: 3: 4: 4:
Function
OFF
Switch for pre-set value
ON
Reduced mode – system circuit A1
ON
Reduced mode – mixing valve circuit M2
ON
Reduced mode – mixing valve circuit M3
ON
Pre-set value default 10 to 100˚C / 50 to 212˚F
OFF
Pre-set value default 30 to 120˚C / 86 to 248˚F
B
1 2 3 4
_
+
A Power supply
(provide disconnect if required by code)
B DIP switch (see table)
Note: For switches 1 to 3, only one switch may be set to ON.
78
5727 946 v1.2
Page 79
Resetting codings to the factory setting
2F:0Airbleedprogram/programdisabled
.
1. Press w and rw simultaneously for approx. two seconds, until the first two arrows appear in the display.
2. Press D.
Coding Level 1
Calling up coding level 1
1. Press “9“ + “w“ simultaneously
for approx. 2 seconds.
2. Press “ / ” for the required coding address, the address flashes.
5. ” to confirm. The display briefly shows “accepted”, and the address flashes again.
6. / ” to select other addresses.
Coding – Vitotronic 100, HC1
3. Press “ ” to confirm.
4. / ” for the selected value.
7. Press “9“ + “w“ simultaneously
for approx. 1 second. Coding level 1 is terminated.
Summary
Coding (factory default setting) Possible change
System design
00: 1 No function 00: 0 Boiler control connected to the cascade; this
automatically occurs if 01: 2 has been programmed
System type
01: 1 Single boiler system 01: 2 Multi-boiler system with cascade control
(e.g. Vitocontrol-S, WB2B)
06: *1 Maximum boiler water temperature limit. 06: 20
to 06: *1
Boiler
07: 1 Consecutive boiler number in multi-boiler systems
(in conjunction with coding address 01)
Air bleed / filling
2F: 0 Air bleed program/program disabled.
*1
The factory setting and upper limit is defaulted by the boiler coding card.
07: 2 to 07: 4
2F: 1 Air bleed function enabled 2F: 2 Filling function enabled
Maximum boiler water temperature limit adjustable from 68˚F to *1 / 20˚C to *1
Consecutive boiler number in multi-boiler systems (in conjunction with coding address 01)
5727 946 v1.2
79
Page 80
Coding – Vitotronic 100, HC1
Coding Level 2
Calling up coding level 2
1. Press “w” and “rw
simultaneously for approx. 2 seconds. until the first two arrows appear in the display; confirm with
2. Press “ ” to confirm.
3. Press “
coding address, the address flashes.
4. Press “ ” to confirm.
5.
/ ” for the required
/ ” for the selected value.
6. “
” to confirm. The display briefly shows “accepted”, and the address flashes again.
7. / ” to select other addresses.
8. Press “w” and “rw
simultaneously for approx. 1 sec. Coding level 2 is terminated.
Overall summary
Coding (factory default setting)
System design
00: 1 No function 00: 0 Boiler control included in cascade; this automatically occurs if 01: 2
System type
01: 1 Single boiler system 01: 2 Multi-boiler system with cascade control
Boiler/burner
06: *1 Maximum boiler water
temperature limit
Boiler
07: 1 Consecutive boiler number in
multi-boiler systems (in conjunction with coding address 01)
Boiler/burner
11:9 No access to the coding
addresses for parameters of the combustion controller
12: 0 Special function OFF
Always reset to 12:0 if “possible change” used.
21: 0 No maintenance interval
(operating hours) selected
23: 0 No time interval for burner
service selected
24: 0 The service display is reset 24: 1 Service display (value displayed automatically)
28: 0 No burner interval ignition 28: 1
2E: 0 KM-BUS connection of
power/pump module not recognized
*1
The factory setting and upper limit is defaulted by the boiler coding card.
Possible change
has been programmed
(e.g. Vitotronic 300-K)
06: 20 to 06: *1
07: 2 to 07: 4
11: 9 Access open to the coding addresses for the parameters of the
12: 1
12: 2
21: 1 to
21:100
23: 1 to 23: 24
to 28: 24
2E: 1 KM-BUS connection of power/pump moduleautomatically recognized.
Maximum boiler water temperature limit adjustable from 68˚F to *1 / 20˚C to *1
Consecutive boiler number in multi-boiler systems (in conjunction with coding address 01)
combustion controller (see coding address 82).
Special function ON: During calibration, the control automatically sets the boiler water temperature to max. If automatic calibration is initiated, the boiler will not start unless the temperature falls below 108°F / 42°C (see fault Eb before adjusting).
Number of hours run before the burner is serviced is adjustable from 0 to 100 (each increment = 100h)
Time interval adjustable from 1 to 24 months
Time interval adjustable from 1 to 24 hr. The burner is forced-started once every 30 sec. within selected time interval.
5727 946 v1.2
80
Page 81
Coding – Vitotronic 100, HC1
2F:0Airbleedprogram/fillprogramdisabled
Pumpincontrolfunction
80:1Afaultmessageisdisplayed,providingafaulti
s
F5:12Delayofftimeofthecirculationpumpintheheating
(notused)
heatingcircuitconnectionwillbestarted10time
s
Coding 2 (continued)
Coding (factory default setting) Possible change
Boiler
2F: 0 Air bleed program/fill program disabled
32: 0 Signal “External blocking”: acting on the boiler
circuit connection set circulation pump: Pump in control function
38: 0 Status burner control unit: Operational (no fault) 38: 0 Status fault, burner control unit
53: 1 Do not adjust
76: 0 Without cascade communication module 76: 2 With cascade communication module; automatic
80: 1 A fault message is displayed, providing a fault is
active for at least 5 sec
82: 0 Operation with natural gas 82: 1 Operation with LPG (only adjustable if coding
85: 0 Standard mode 85:1 Manual calibration of the combustion controller
88: 0 Temperature display in ºC (Celsius) 88: 1 Temperature display in ºF (Fahrenheit)
F5: 12 Delay off time of the circulation pump in the heating
circuit connection set in heating mode: 12 min (not used)
F6: 0 Circulation pump in the heating circuit connection is
permanently OFF in operating mode “DHW only” (not used)
F7: 10 In the “Standby mode”, the circulation pump in the
heating circuit connection will be started 10 times per day for 10 minutes respectively (not used)
2F: 1 Air bleed program enabled 2F: 2 Filling program enabled 32: 1
to 32: 7
32: 8 Internal circulation pump OFF 32: 9
to 32: 15
80: 0 Immediate fault message 80: 2
to 80: 199
F5: 0 No start delay of the internal circulation pump F5: 1
to F5: 20
F6: 1 to F6: 24
F6: 25 In the “DHW only” operating mode, the internal
F7: 0 In the “Standby mode”, the internal circulation
F7: 1 to F7: 24
F7: 25 In the “Standby mode”, the internal circulation
No function
No function
recognition
The fault message is issued after a delay that is adjustable from 10 sec to 995 sec; 1 increment = 5 sec
address 11:9 has been set)
(only adjustable if coding address 11:9 has been set). The red fault indicator also flashes during cal­ibration. The process has terminated when the red fault indicator no longer flashes (after approx. 1 min.).
Note!
Heat generated by the boiler must be dispersed dur­ing manual calibration.
Delay off time of the circulation pump in the heating circuit connection set adjustable from 1 to 20 min
In the “DHW only” operating mode, the internal circulation pump will be started 1 to 24 times per day for 10 minutes respectively
circulation pump is permanently ON
pump is permanently OFF
In the “Standby mode”, the internal circulation pump will be started 1 to 24 times per day for 10 minutes respectively
pump is permanently ON
5727 946 v1.2
81
Page 82
Coding – Vitotronic 300-K
Resetting codes into the factory setting
1. Press w and rw simultaneously
for approx. 2 seconds.
2. Press D. Confirm “Base setting? Yes” with
. Select “Base setting? Yes” or “Base setting? No” with or .
Coding Level 1
Calling up coding level 1
1 2 3
Cod. 1
Code 1
1. Press 9 and w simultaneously for approx. 2 seconds.
2. Select the required coding address with or ; the address flashes; confirm with , the value flashes.
Summary
Coding (factory default setting) Possible change
System design
00: 1 System circuit A1,
without DHW heating
Number of boilers
35: 4 4 boilers connected to Vitotronic 300-K 35: 1
00: 2 System circuit A1,
with DHW heating
00: 3 Mixing valve circuit M2,
without DHW heating
00: 4 Mixing valve circuit M2,
with DHW heating
00: 5 System circuit A1 and
mixing valve circuit M2, without DHW heating
00: 6 System circuit A1 and
mixing valve circuit M2, with DHW heating
00: 7 Mixing valve circuit M2 and M3,
without DHW heating
00: 8 Mixing valve circuit M2 and M3,
with DHW heating
00: 9 System circuit A1 and
mixing valve circuits M2 and M3, without DHW heating
00: 10 System circuit A1 and
mixing valve circuits M2 and M3, with DHW heating
1 to 3 boilers connected to Vitotronic 300-K to 35: 3
3. Change the value with or ; confirm with . The display briefly shows Accepted, then the address flashes again. Call up further addresses with or .
4. Press 9 and w simultaneously for approx. 1 second.
82
5727 946 v1.2
Page 83
Coding Level 1 (continued)
Coding (factory default setting) Possible change
Multi-boiler control unit
36: 0 Electronic minimum system supply temperature
limit set to 32˚F / 0˚C
37: 80 Electronic maximum system supply temperature
limit set to 176˚F / 80˚C
Control type
3b: 1 Boiler parallel connection with supply temperature
sensor (LLH)
Control strategy
3C: 0 Gross calorific strategy 2
(see page 57)
36: 1 to 36:127
37: 20 to 37:127
3b: 0 Boiler parallel connection without supply
3C: 1 Net calorific strategy 1
3C: 2 Net calorific strategy 2
Electronic minimum system supply temperature limit adjustable from 32 to 261˚F / 0 to 127˚C
Electronic maximum system supply temperature limit adjustable from 68 to 261˚F / 20 to 127˚C
temperature sensor (LLH)
(see page 57)
(see page 57)
Coding – Vitotronic 300-K
5727 946 v1.2
83
Page 84
Coding – Vitotronic 300-K
circuitpumpandmixingvalve
Coding Level 1 (continued)
Coding (factory default setting) Possible change
General (continued)
77: 5 LON participant number 77: 1
to 77: 99
DHW priority A1/M2/M3
A0: 0 Without remote control A0: 1 With Vitotrol 200
A0: 2 With Vitotrol 300
A2: 2
Summer econ. A1/M2/M3
A5: 5 With heating circuit pump logic function A5: 0 Without heating circuit pump logic function
Supply min. temp. A1/M2/M3
C5: 20 Electronic minimum supply temperature limit:
With DHW tank priority applicable to heating circuit pump and mixing valve
68˚F / 20˚C
A2: 0 Without DHW tank priority applicable to heating
A2: 1 With DHW tank priority for mixing valve:
A2: 3 to A2: 15
C5: 1 to C5:127
LON participant number, adjustable from 1 to 99
Note: Allocate each number only once.
circuit pump and mixing valve
Mixing valve is closed during DHW heating; heating circuit pump operates
Do not adjust
Note: for additional information see coding level 2
Min. limit adjustable from 34 to 261˚F / 1 to 127˚C (limited by boiler coding card); only effective with central heating with normal temperature
Supply max. temp. A1/M2/M3
C6: 75 Electronic maximum supply temperature limit
176˚F / 80˚C
C6: 10 to C6:127
Maximum limit adjustable from 50 to 261˚F / 10 to 127˚C (limited by boiler coding card)
84
5727 946 v1.2
Page 85
Coding Level 2
The summary from page 86 lists all possible coding addresses.
The coding addresses are grouped in
System design
Cod. 00
Multi-boiler control unit
Cod. 35 to 49
General
Cod. 4A to 4F
DHW
Cod. 54 to 75
General
Cod. 76 to 9F
System circuit A1
Cod. A0 to F2
accordance with the adjacent sequence.
Coding – Vitotronic 300-K
Mixing valve circuit M2
Cod. A0 to F2
Mixing valve circuit M3
Cod. A0 to F2
Calling up coding level 2
1 2 3
Cod. 2
Code 2
Initially the possible coding addresses A0 to F2 for the system circuit A1 are scrolled through, then those for mixing valve circuits M2 and M3, again starting with coding address A0.
ress w and rw simultaneously
1. P for approx. 2 seconds; confirm with .
2. Select the required coding address with or ; the address flashes; confirm with , the value flashes.
3. Change the value with or ; confirm with . The display briefly shows Accepted, then the address flashes again. Call up further addresses with or .
4. Press w and rw simultaneously for approx. one second.
5727 946 v1.2
85
Page 86
Coding – Vitotronic 300-K
Inmulti-boilersystems,whereoneboileri
s
Coding Level 2 (continued)
Overall summary
Coding (factory default setting) Possible change
System design
00: 1 See page 82
Multi-boiler control unit
35: 4 4 boilers connected to Vitotronic 300-K 35: 2
to 35: 3
36: 0 Electronic minimum system supply temperature limit
set to 32˚F / 0˚C
37: 80 Electronic maximum system supply temperature
limit set to 176˚F / 80˚C
38: 0
39: 0 No permanent lead boiler 39: 1
3A: 0 No permanent last boiler 3A: 1
3b: 1 Boiler parallel connection with supply temperature
3C: 0 Gross calorific strategy
3d: 1 Output balance for gross calorific strategy and net
3E: 0 Do not adjust
3F: 0 Without DHW tank priority for common supply
No changing of lead boiler and the boiler sequence
Note:
In multi-boiler systems, where one boiler is permamently selected as standby boiler, change that boiler over to become the active boiler only in longer intervals, e.g. as part of the annually required system inspection.
sensor (LLH)
(see page 57)
calorific strategy 1
pump
36: 1 to 36:127
37: 20 to 37:127
38: 1 Changing the lead boiler:
38: 2 to 38:200
to 39: 4
to 3A: 4
3b: 0 Boiler parallel connection with supply temperature
3C: 1 Net calorific strategy 1
3C: 2 Net calorific strategy 2
3d: 0 No output statement
3F: 1 With DHW tank priority for common supply pump
2 to 3 boilers connected to Vitotronic 300-K
Electronic minimum system supply temperature limit adjustable from 32 to 261˚F / 0 to 127˚C
Electronic maximum system supply temperature limit adjustable from 68 to 261˚F / 20 to 127˚C
Every 1stday of the month, the boiler with the burner which has operated for the shortest number of hours, becomes lead boiler
Changing the lead boiler: After 200 to 20,,000 run hours, the boiler with the next higher number (coding address 07 of Vitotronic 100) becomes lead boiler; 1 setting step = 100 run hours
Boiler 1, 2, 3 or 4 is permanent lead boiler
Boiler 1, 2, 3 or 4 is permanent last boiler
sensor (LLH)
(see page 57)
(see page 57)
Note:
Vitotronic 300-K controls only in accordance with net calorific strategy 2
86
5727 946 v1.2
Page 87
Coding Level 2 (continued)
Coding (factory default setting) Possible change
General
41: 31 No ECO threshold boiler 1 41:–30
to 41:+30
42: 31 No ECO threshold boiler 2 42:–30
to 42:+30
43: 31 No ECO threshold boiler 3 43:–30
to 43:+30
44: 31 No ECO threshold boiler 4 44:–30
to 44:+30
45: 60 Start-up integral threshold set to
60 Kelvin × minute
46: 10 Shutdown integral threshold set to
10 Kelvin × minute
47: 15 Shutdown differential set to 27˚F / 15˚C 47: 2
48: 35 Do not adjust
49: 40 Do not adjust
4A: 0 Do not adjust 4b: 0 Sensor aJB (not used) not installed 4b: 1 Sensor aJB installed
4C: 0 Connection on plug A1:
Heating circuit pump
4F: 5 DHW. Do not adjust
DHW
54: 0 Without solar control unit
45: 1 to 45:255
46: 1 to 46:255
to 47: 30
4C: 1 Primary pump – DHW tank heating system
54: 1 With Vitosolic 100;
54: 2 With Vitosolic 200;
ECO threshold boiler 1 adjustable from –22 to +86˚F / –30 to +30˚C
ECO threshold boiler 2 adjustable from –22 to +86˚F / –30 to +30˚C
ECO threshold boiler 3 adjustable from –22 to +86˚F / –30 to +30˚C
ECO threshold boiler 4 adjustable from –22 to +86˚F / –30 to +30˚C
Start-up integral threshold adjustable from 1 to 255 Kelvin × minute
Note:
If the threshold is exceeded, one boiler or one burner stage is switched ON
Shutdown integral threshold adjustable from 1 to 255 Kelvin × minute
Note:
If the threshold is exceeded, one boiler or one burner stage is switched OFF
Shutdown differential adjustable from 3.6 to 54˚F / 2 to 30˚C
Note:
One boiler or one burner stage will be switched OFF, if actual supply temperature exceeds the set supply temperature by this value
(e.g. temperature sensor T2); will be recognised automatically
will be recognized automatically (not used)
will be recognized automatically
Coding – Vitotronic 300-K
5727 946 v1.2
87
Page 88
Coding – Vitotronic 300-K
operatingprogramwithpermanentlynormalroom
operatingprogramwithpermanentlynormalroom
Coding Level 2 (continued)
Coding (factory default setting) Possible change
Multi-boiler control (continued)
DHW (continued)
55: 0 DHW heating,
differential ± 4.5˚F / 2.5˚C
56: 0 Setting range for DHW temperature:
50 to 140˚F / 10 to 60˚C
58: 0 Without auxiliary function for DHW heating 58: 10
59: 0 DHW tank heating:
Start-up point – 2.5˚C / –4.5˚F / Shutdown point + 2.5˚C / +4.5˚F
5A: 0 No function 5A: 1 Supply temperature demand from DHW tank is
60: 20 During DHW heating, boiler water temperature is
max. 36˚F / 20˚C higher than set DHW temperature
62: 10 Delay off time of DHW pump up to max. 10
minutes
64: 2
During party mode and after external changeover of
55: 1 Adaptive DHW heating active (speed of
temperature rise for DHW tank temperature is taken into account during DHW heating)
55: 2 DHW tank temperature control with 2 DHW tank
temperature sensors
55: 3 DHW loading heating system
56: 1 Setting range for DHW temperature:
50 to 203˚F / 10 to 95˚C
Observe the max. permissible DHW temperatureChange adjustable high limit on boiler controls
Input of a 2ndset DHW value; adjustable to 58: 95
59: 1 to 59: 10
60: 10 to 60: 50
62: 0 DHW pump without delay off time
62: 1 to 62: 15
64: 0 No DHW heating, DHW recirculation pump OFF
from 34 to 203˚F / 1 to 95˚C (subject to boiler
coding card)
Note:
The DHW tank is heated to the 2ndset value during
the 4thDHW heating phase
Start-up point adjustable from 2 to 18˚F /
1 to 10˚C below set value
maximum value of system
Difference between common supply temperature
and set DHW temperature is adjustable from 10 to
50˚C / 18 to 90˚F
DHW pump delay off time adjustable from 1 to 15
minutes
temperature: Enable constant DHW heating and DHW recirculation pump ON
88
64: 1 DHW heating and DHW recirculation pump acc. to
time program
5727 946 v1.2
Page 89
Coding Level 2 (continued)
InputofsetDHWvalue:
Vitotrol300remotecontrolunits
67:40WithVitosolic200
:
DHWrecirculationpump:
Coding (factory default setting) Possible change
DHW (continued)
66: 4
67: 40 With Vitosolic 200:
Input of set DHW value: At programming unit and all installed
3rd DHW set-point 104˚F / 40˚C Reloading suppression will be active above set temperature. DHW tank is heated only by solar heating system.
66: 0 At programming unit 66: 1 At programming unit and remote control – system circuit A1 66: 2 At programming unit and remote control – mixing valve circuit
M2
66: 3 At programming unit and remote control – mixing valve circuit
M3
66: 5 At remote control – system circuit A1 66: 6 At remote control – mixing valve circuit M2 66: 7 At remote control – mixing valve circuit M3 67: 0 Without a 3rdset DHW temperature 67: 1
to 67: 95
Input of a 3rdset DHW set point temperature; adjustable from 34 to above 203˚F / 1 to above 95˚C (subject to the boiler coding card of the connected boilers)
Coding – Vitotronic 300-K
68: 8 With 2 DHW tank temperature sensors
(coding 55: 2): DHW tank heating switch-off point with set value × 0.8
69: 7 With 2 DHW tank temperature sensors
(coding 55: 2): DHW tank heating starting point with set value × 0.7
70: 0 DHW recirculation pump ON acc. to time
program when DHW heating is enabled
71: 0
72: 0 72: 1 OFF during DHW heating to second set value
73: 0 73: 1
75: 0 DHW recirculation pump during economy
DHW recirculation pump: ON acc. to time program
mode: ON acc. to time program
68: 2 to 68: 10
69: 1 to 69: 9
70: 1 DHW recirculation pump ON according to time program
71: 1 OFF during DHW heating to first set value 71: 2 ON during DHW heating to first set value
72: 2 ON during DHW heating to second set value
to 73: 6
73: 7 Constantly ON 75: 1 OFF
Factor adjustable from 0.2 to 1; 1 setting step = 0.1
Factor adjustable from 0.1 to 0.9; 1 setting step = 0.1
During time program 1x/h ON for five minutes to 6x/h ON for five minutes
5727 946 v1.2
89
Page 90
Coding – Vitotronic 300-K
Afaultmessageisissued
,
Automaticdaylightsavingtime
Codingaddresses82to87onlyfeasible
Coding Level 2 (continued)
Coding (factory default setting) Possible change
General
76: 0 Without LON communication module 76: 1 With LON communication module;
will be recognized automatically
77: 5 LON participant number 77: 1
to 77: 99
78: 1 LON communication enabled 78: 0 Disable LON communication
79: 1 Control unit is fault manager 79: 0 Control unit is not fault manager
7A: 0 Without central control of heating
circuits
7b: 1 With LON communication module:
Control unit transmits the time
7E: 0 DO NOT ADJUST 7E: __
7F: 1 Detached house 7F: 0 Multi-occupancy house
80: 6
81: 1
82: 3 Daylight saving time starts:
83: 5 Daylight saving time starts:
84: 7 Daylight saving time starts:
85: 10 Daylight saving time ends:
86: 5 Daylight saving time ends:
87: 7 Daylight saving time ends:
88: 0 Temperature display in ˚C (Celsius) 88: 1 Temperature display in ˚F (Fahrenheit)
89: 0 Do not adjust!
8A:175 Do not adjust!
A fault message is issued, if a fault is active for at least 30 seconds
Automatic daylight saving time changeover
Note:
if coding 81: 1 is set.
March
last week of month
last day of week (Sunday)
October
last week of month
last day of week (Sunday)
7A: 1 With central control of:
7A: 2 Mixing valve circuit M2
7A: 3 Mixing valve circuit M3
7b: 0 Do not transmit time
80: 0 Immediate fault message 80:...
to 80:199
81: 0 Manual changeover - daylight saving time
81: 2 Use of a radio clock receiver; recognized automatically (not
81: 3 Accept time via LON
82: 1 to 82: 12
83: 1 to 83: 5
84: 1 to 84: 7
85: 1 to 85: 12
86: 1 to 86: 5
87: 1 to 87: 7
LON participant number, adjustable from 1 to 99
Note: Allocate each number only once
System boiler circuit A1
Minimum fault duration before displaying a fault message is adjustable from 10 to 995 seconds; 1 setting step = 5 seconds
used)
January to December
Week 1 to week 5 of selected month
Monday to Sunday
January to December
Week 1 to week 5 of selected month
Monday to Sunday
5727 946 v1.2
90
Page 91
Coding – Vitotronic 300-K
8E:4Displayingandacknowledgingfaults:
97:2Outdoortemperatureatsensorconnectedto
Coding Level 2 (continued)
Coding (factory default setting) Possible change
General (continued)
8E: 4 Displaying and acknowledging faults:
At programming unit and all installed Vitotrol remote control units
90:128 Time constant for calculating adjusted outdoor
temperature:
21.3 hours
91: 0 Without heating program changeover (see page 21)
94: 0 Without plug-in adaptor for external safety
equipment
96: 1 With mixing valve extension printed circuit board 96: 0 Without mixing valve extension printed circuit
97: 2 Outdoor temperature at sensor connected to
control unit will be transmitted via LON BUS to any connected Vitotronic 200-H
98: 1 Viessmann system number
(in conjunction with monitoring several systems within one LON system with Vitocom 300)
8E: 0 At programming unit 8E: 1 At programming unit and remote control – system
circuit A1
8E: 2 At programming unit and remote control – mixing
valve circuit M2
8E: 3 At programming unit and remote control – mixing
valve circuit M3
90: 1 to 90:199
91: 1 With heating program changeover (connection via
91: 2 Mixing valve circuit M2 91: 3 System circuit A1 and
91: 4 Mixing valve circuit M3 91: 5 System circuit A1 and
91: 6 Mixing valve circuits M2 and M3 91: 7 All heating circuits (A1, M2, M3) 94: 1 With plug-in adaptor for external safety equipment;
97: 0 No transmission via LON BUS 97: 1 The control unit receives the outdoor temperature
98: 1 to 98: 5
Fast (low values) or slow (high values) matching of supply temperature subject to set value when outdoor temperature changes; 1 setting step = 10 minutes
plug aVD): Changeover affects: System circuit A1
mixing valve circuit M2
mixing valve circuit M3
will be recognized automatically
board
via LON BUS
System number adjustable from 1 to 5
5727 946 v1.2
91
Page 92
Coding – Vitotronic 300-K
(Externaldisable/externalmixingvalveclose
)
(Externalmixingvalveopen)inactive
Coding Level 2 (continued)
Coding (factory default setting) Possible change
General (continued)
99: 0 Connection to terminals 2 and 3 in plug aVD
(External disable/external mixing valve close) inactive
9A: 0
Connection to terminals 1 and 2 in plug aVD (External mixing valve open) inactive
99: 1 Contact affects:
No function
99: 2 Mixing valve close:
Mixing valve circuit M2
99: 3 No function 99: 4 Mixing valve close:
Mixing valve circuit M3
99: 5 No function 99: 6 Mixing valve close:
Mixing valve circuits M2 and M3
99: 7 No function 99: 8 External disable 99: 9 No function 99: 10 External disable and mixing valve close:
Mixing valve circuit M2
99: 11 No function 99: 12 External disable and mixing valve close:
Mixing valve circuit M3
99: 13 No function 99: 14 External disable and mixing valve close:
Mixing valve circuits M2 and M3
99: 15 No function 9A: 1 Contact affects:
No function
9A: 2 Mixing valve open:
Mixing valve circuit M2
9A: 3 No function
9A: 4 Mixing valve open:
Mixing valve circuit M3
9A: 5 No function
9A: 6 Mixing valve open:
Mixing valve circuits M2 and M3
99: 7 No function
92
5727 946 v1.2
Page 93
Coding Level 2 (continued)
9b:70Setpointtemperatureforexternaldemand
9C:20MonitoringLONparticipants:
pumpandmixingvalv
e
Coding (factory default setting) Possible change
General (continued)
9b: 70 Set point temperature for external demand
(input aVH) 158˚F / 70˚C
9C: 20 Monitoring LON participants:
When there is no response from a participant, values defaulted inside control unit continue to be used for a further 20 min. Only then will a fault message be triggered.
9b: 0 No default set value 9b: 1
to 9b:127
9C: 0 No monitoring 9C: 5
to 9C: 60
Set value adjustable from 34 to 261˚F / 1 to 127˚C (Min. / max. temperature subject to boiler coding card)
Time adjustable from 5 to 60 minutes
Coding – Vitotronic 300-K
9d: 0 Without Input Module
0 to 10V
9F: 8 With mixing valve circuit:
Differential temperature 14.4˚F / 8˚C (only in conjunction with mixing valve circuit)
System circuit/mixing valve circuit
A0: 0 Without remote control A0: 1 With Vitotrol 200
A2: 2
A3: 2 Outdoor temp. below 34˚F / 1˚C:
With DHW tank priority applicable to heating circuit pump and mixing valve
Heating circuit pump ON Outdoor temp. above 37˚F / 3˚C: Heating circuit pump OFF
Note:
For settings below 34˚F / 1˚C pipes outdoor thermal insulation shell of building can freeze up, particularly during standby mode, e.g. during holidays.
9d: 1 With Input Module 0 - 10V;
will be recognized automatically
9F: 0 to 9F: 40
A0: 2 With Vitotrol 300
A2: 0 Without DHW tank priority applicable to heating
A2: 1 With DHW tank priority for mixing valve:
A2: 3 to A2: 15
A3: –9 A3: –8 A3: –7 A3: –6 A3: –5 A3: –4 A3: –3 A3: –2 A3: –1 A3: 0 A3: 1 A3: 2 to A3: 15
Differential temperature adjustable from 0 to 72˚F / 0 to 40˚C
circuit pump and mixing valve
Mixing valve is closed during DHW heating; heating circuit pump operates
Do not adjust
Heating circuit pump (see back of manual for conversion chart) ON at OFF at –10˚C –8˚C – 9˚C –7˚C – 8˚C –6˚C – 7˚C –5˚C – 6˚C –4˚C – 5˚C –3˚C – 4˚C –2˚C – 3˚C –1˚C – 2˚C 0˚C – 1˚C 1˚C
0˚C 2˚C 1˚C 3˚C
to
14˚C 16˚C
5727 946 v1.2
93
Page 94
Coding – Vitotronic 300-K
Withheatingcircuitpumplogicfunction(economy
Withpumpstopfunction:
Coding Level 2 (continued)
Coding (factory default setting) Possible change
System circuit/mixing valve circuit (continued)
A4: 0 With frost protection A4: 1 No frost protection
Adjustment only possible if coding A3: –9 is set.
Note:
Please observe note regarding coding address A3.
A5: 5
With heating circuit pump logic function (economy circuit): Heating circuit pump OFF, if outdoor temperature (AT) is 1 K higher than set room temperature (RT AT > RT
set
+ 1 K
A6: 36 Extended economy function inactive A6: 5
Mixing valve circuit
A7: 0 Without mixing valve economy function A7: 1 With mixing valve economy function
System circuit/mixing valve circuit (continued)
A9: 7
With pump stop function: Heating circuit pump OFF during set-point value changes (by changing operating mode or changes on rotary selector ts or button tm)
A5: 0 Without heating circuit pump logic function
With heating circuit pump logic function:
set
)
A5: 1 A5: 2 A5: 3 A5: 4 A5: 5 A5: 6 A5: 7 to A5: 15
Heating circuit pump OFF, if
AT > RT AT > RT AT > RT AT > RT AT > RT AT > RT AT > RT
set set set set set set set
+ 5 K + 4 K + 3 K + 2 K + 1 K
+ 1 K
– 1 K to AT > RT
set
– 9 K Extended economy function active, i.e. burner and
to A6: 35
heating circuit pump will be switched OFF, and mixing valve will be closed at a variable value which is adjustable between 41 and 95˚F / 5 and 35˚C plus 2˚F / 1˚C. This value is based on dampened outdoor temperature, comprising actual outdoor temperature and a time constant which takes cooling down of an average building into consideration.
(extended heating circuit pump logic). Heating circuit pump also OFF, if mixing valve was closed longer than 20 minutes. Heating circuit pump ON: If mixing valve changes to control mode
or
After DHW tank heating (for 20 minutes)
or
If there is a risk of frost
A9: 0 Without pump stop function A9: 1
Pump stop function adjustable from 1 to 15
to A9: 15
94
5727 946 v1.2
Page 95
Coding – Vitotronic 300-K
Coding Level 2 (continued)
Coding (factory default setting) Possible change
Systems/mixing valve circuit (continued)
b0: 0*1With remote control:
Heating mode/ reduced mode: With outdoor reset
b1: Do not adjust
b2: 8*1With remote control unit and for heating circuit,
operation with room temperature feed-back must be programmed: Room influencing factor 8
b3: 0*1Do not adjust
b5: 0*1With remote control:
Without room temperature dependent heating circuit pump logic function
b6: 0*1With remote control unit and for heating circuit,
operation with room temperature feed-back must be programmed: Without quick heat-up/quick setback
*1
Change coding – for system circuit A1 only for boilers without lower temperature limit – for mixing valve circuit only, if remote control
unit affects this heating circuit.
b0: 1 Heating mode:
With outdoor reset Reduced mode: With room temperature feed-back
b0: 2 Heating mode:
With room temperature feed-back Reduced mode: With outdoor reset
b0: 3 Heating mode/ reduced mode:
With room temperature feed-back
b2: 0 No room influence
b2: 1
Room influence factor adjustable from 1 to 31 to b2: 31
Heating circuit pump
b5: 1 b5: 2 b5: 3 b5: 4 b5: 5 b5: 6 b5: 7 b5: 8
ON at RT
OFF at RT
T for ON T for OFF
+4K +5K +3K +4K +2K +3K +1K +2K +0K +1K
-1K +0K
-2K -1K
-3K -2K
actual
actual
< RT
> RT
set
set
+
+
T

T

b6: 1 With quick heat-up/quick setback (see page 61)
5727 946 v1.2
95
Page 96
Coding – Vitotronic 300-K
Coding Level 2 (continued)
Coding (factory default setting) Possible change
Systems/mixing valve circuit (continued)
b7: 0*1With remote control unit and for heating circuit,
operation with room temperature feed-back must be programmed: Without start-up optimization
b8:10*1With remote control unit and for heating circuit,
operation with room temperature feed-back must be programmed: Heat-up gradient – start-up optimization 10 minutes/ ˚C
b9: 0*1With remote control unit and for heating circuit,
operation with room temperature feed-back must be programmed: Without learning start-up optimization
C0: 0*1With remote control:
Without shut-down optimization
C1: 0*1With remote control:
Without shut-down optimization
C2: 0*1With remote control:
Without learning shutdown optimization
Mixing valve circuit
C3:125 Mixing valve operating time:
125 seconds
C4: 1 System dynamics – mixing valve control
characteristics
System circuit/mixing valve circuit (continued)
C5: 20 Electronic minimum supply temperature limit:
68˚F / 20˚C
C6: 75 Electronic maximum supply temperature limit
176˚F / 80˚C
*1
Change coding – for system circuit A1 only for boilers without lower temperature limit – for mixing valve circuit only, if remote control
unit affects this heating circuit.
b7: 1 With start-up optimization:
Max. offset 2 hours 30 minutes
b7: 2 Max. off-set
15 hours 50 minutes
b8: 11 to
Heat-up gradient adjustable from 11 to 255 minutes / ˚C
b8:255
b9: 1 With learning start-up optimization
C0: 1 With shutdown optimization:
Max. off-set 1 hour
C0: 2 Max. off-set 2 hours
C1: 1 to C1: 12
With shutdown optimization: Max. off-set from 10 to 120 minutes; 1 setting step = 10 minutes
C2: 1 With learning shutdown optimization
C3: 10
Operating time adjustable from 10 to 255 seconds to C3:255
C4: 0 to C4: 3
Controller responds too quickly (cycles between
open and close):
Select a lower value.
Controller acts too slowly (temperature is not
maintained correctly):
Select a higher value.
C5: 1 to C5:127
C6: 10 to
Min. limit adjustable from 34 to 261˚F / 1 to 127˚C
(limited by boiler coding card); only effective with
central heating with normal temperature
Maximum limit adjustable from 50 to 261˚F /
10 to 127˚C (limited by boiler coding card) C6:127
96
5727 946 v1.2
Page 97
Coding Level 2 (continued)
Normaldaytemperatureisadjustableatremot
e
Coding (factory default setting) Possible change
System circuit/mixing valve circuit (continued)
C8:31*1With remote control unit and for heating circuit,
operation with room temperature feed-back must be programmed: Without limiting room influence
d5: 0 External heating program changeover via terminal
X6.1 and X6.2: Heating program changes to constant operation with reduced room temperature
E1: 1
With remote control: Normal day temperature is adjustable at remote control unit from 50 to 86˚F / 10 to 30˚C
E2: 50 With remote control:
No display correction of actual room temperature
Mixing valve circuit
F1: 0 Slab curing function inactive F1: 1
C8: 1 to
Room influence limit adjustable from 1 to 30 K (1.8 to 54 Fahrenheit degrees)
C8: 30
d5: 1 Heating program changes to constant operation
with normal room temperature
E1: 0 Normal day temperature adjustable from
37 to 74˚F / 3 to 23˚C
E1: 2 from 63 to 99˚F / 17 to 37˚C E2: 0
to E2: 49
E2: 51 to E2: 99
Display correction –9˚F / – 5 ˚C to display correction –0.18˚F / – 0.1˚C
Display correction +0.18°F / + 0.1˚C to display correction 8.8°F / + 4.9˚C
Slab curing function adjustable in accordance with to F1: 5
four optional temperature-time profiles (see
page 101)
Coding – Vitotronic 300-K
Note:
Observe slab curing supplier’s instructions.
Observe local regulations.
Report to be provided by heating contractor must
contain following details:
Heat-up data with their respective supply
temperatures
Max. supply temperature achieved
Operating condition and outdoor temperature
during handover Function continues after power failure or after control unit has been switched OFF. Heating program rrrrwwww will be started, after slab curing function has been completed or if address is manually set to 0.
System circuit/mixing valve circuit
F2: 8 Time limit for party mode 8 hours
*1
F2: 0 No time limit for party mode
F2: 1 to
Time limit for party mode adjustable from 1 to 12 hours
*1
*1
F2: 12
*1
Party mode ends automatically with heating program rrrrwwww when system changes over to operation with normal room temperature.
5727 946 v1.2
97
Page 98
Coding – Vitotronic 300-K
ObservethesettingofcodingaddressA3.
fromoperationwithreducedroomtemperatureto
FA:50
fromoperationwithreducedroomtemperatureto
FA:50
Coding Level 2 (continued)
Coding (factory default setting) Possible change
System circuit/mixing valve circuit (continued)
F8: –5 Temperature limit for terminating the reduced
mode 23˚F / – 5 ˚C see example on page 99. Observe the setting of coding address “A3”.
F9: –14 Temperature limit for raising the set temperature
for reduced mode 7˚F / – 14 ˚C, see example on page 99.
FA: 20 Raising the boiler water setpoint temperature or
the supply setpoint temperature when changing
operation with standard room temperature by 20%. See example on page 100.
Fb: 30 Duration for raising the boiler water temperature
setpoint or the supply temperature setpoint (see coding address “FA”) 60 min. See example on page 100.
F8:+10 to F8: –60
F8:–61 Function disabled F9:+10
to F9: –60
FA: 0 to
Fb: 0 to Fb: 150
Temperature limit adjustable from +50 to –76˚F / +10 to –60˚C
Temperature limit adjustable from +50 to –76˚F / +10 to –60˚C
Temperature rise adjustable from 0 to 50%
Duration adjustable from 0 to 300 min.; 1 increment = 2 min.
98
5727 946 v1.2
Page 99
Coding Level 2 (continued)
Example 1 (”F8: –5“, “F9: –14”)
20
A
15
°C
10
5
B
Coding – Vitotronic 300-K
Set room temperature in
0
-30
Outdoor temperature in
Example (using factory default settings)
A Set standard room temperature 68°F / 20°C B Set reduced room temperature 37°F / 3°C C Temperature limit 7°F / – 14 °C in accordance with
coding address “F9”
D Temperature limit 23°F / – 5 °C in accordance with
coding address “F8”
-25
-20 -15 -10
°C
C
D
-5
0 5
5727 946 v1.2
99
Page 100
Coding – Vitotronic 300-K
Coding Level 2 (continued)
Example 2 (”FA: 20“, “Fb: 30”)
During the transition from operation with reduced room temperature to operation with standard room temperature, the boiler water or supply temperature will be raised in accordance with the selected heating curve. The boiler water or supply temperature can be automatically increased. The value and duration of the additional increase of the set boiler water temperature or supply temperature can be adjusted in coding addresses ”FA” and ”Fb”.
C
60
B
50
°C
40
3030
20
D
10
Boiler / Supply Water
Setpoint Temperature in
A
0
00
6
00
7
00
8
Time in h
Fig. 1 Example (using factory default settings)
A Start of operation with standard room
temperature
B Boiler water / supply temperature
based on selected heating curve
C Boiler water / supply temperature
based on coding address ”FA”: 50°C + 20 % = 60°C
D Duration of operation with raised
boiler water / supply temperature based on coding address ”Fb”: 60 min.
00
9
100
5727 946 v1.2
Loading...