Viessmann KRT 150 series, KRT 540 series, Vitoflex 300-RF series Service Manual

Page 1
Service and Maintenance Instructions
for use by engineers and heating contractors
KRT 150 to KRT 540 Series
Pyrot
r
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable fluids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL FLUE GAS
Deactivate heating equipmentOpen windows and doors.Inform your heating contractor
WARNING
Improper installation, adjustment and/or operation could cause carbon monoxide poisoning resulting in injury or loss of life. This product must be installed and serviced by a professional service technician who is experienced and qualified in hot water boiler installation and wood fuel combustion.
H
5603 880 - 01 12/2014
Product may not be exactly as shown
IMPORTANT
Read and save these instructions for future reference
.
Please file in Service Binder
Page 2
Introduction
Pyrot Service & Maintenance
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing service and/or maintenance. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
Product documentation Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
For a listing of applicable literature, please see section entitled “Important Regulatory and Safety Requirements”.
Warranty Information contained in this and related product documentation must be read and followed. Failure to do so renders the warranty null and void.
Licensed professional heating contractor The installation, adjustment, service and maintenance of this equipment must be performed by a licensed professional heating contractor.
Please see section entitled “Important Regulatory and Installation Requirements”.
Contaminated air Air contaminated by chemicals can cause by-products in the combustion process, which are poisonous to inhabitants and destructive to Viessmann equipment.
For a listing of chemicals which cannot be stored in or near the boiler room, please see subsection entitled “Mechanical Room”.
Carbon monoxide Improper installation, adjustment, service and/or maintenance can cause flue products to flow into living space. Flue products contain poisonous carbon monoxide gas.
For information pertaining to the proper installation, adjustment, service and maintenance of this equipment to avoid formation of carbon monoxide, refer to the installation and operating instructions.
Fresh air This equipment requires fresh air for
safe operation and must be installed ensuring provisions for adequate combustion and ventilation air exist.
For information pertaining to the fresh air requirements of this product, please see subsection entitled “Combustion Air Supply”.
Equipment venting Never operate the boiler without an installed venting
system. An improper venting system can cause carbon monoxide poisoning.
For information pertaining to venting and chimney requirements, refer to the installation and operating instructions. All products of combustion must be safely vented to the outdoors.
Advice to owner Once the installation work is complete, the heating contractor must familiarize the system operator/ ultimate owner with all equipment, as well as safety precautions/requirements, shutdown procedure, and the need for professional service.
2
WARNING
Installers must follow local regulations with respect to installation of carbon monoxide detectors. Follow manufacturer’s maintenance schedule of the boiler contained in the section “Cleaning and Maintenance”.
5603 880 - 01
Page 3
Pyrot Service & Maintenance
About these Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include ”WARNING”, ”CAUTION”, and ”IMPORTANT”. See below.
Indicates an imminently hazardous situation which,
WARNING
Warnings draw your attention to the presence of potential hazards or important product information.
CAUTION
Cautions draw your attention to the presence of potential hazards or important product information.
IMPORTANT
if not avoided, could result in death, serious injury or substantial product/property damage.
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product / property damage.
Helpful hints for installation, operation or maintenance which pertain to the product.
Introduction

Note: Viessmann Manufacturing Company Inc. reserves the right to make product changes or updates without notice and will not be held liable for errors or omissions in the product literature.
This symbol indicates to note additional information
This symbol indicates that other instructions must be
referenced.
5603 880 - 01
3
Page 4
Table of Contents
Pyrot Service & Maintenance
Page
Introduction
General Information
Safety
Maintenance
Safety, Installation and Warranty Requirements..............2
About these Instructions..............................................3
Product Information.....................................................5
Important Regulatory and Installation Requirements ........6
Safety Instructions......................................................8
Carbon Monoxide........................................................9
Extreme Weather Conditions......................................10
Hazardous Material....................................................11
Mechanical Room.....................................................12
Combustion Air Supply..............................................13
Components of the Biomass Boiler..............................14
Cleaning..................................................................15
Boiler.................................................................15
Heat exchanger displacement rods........................16
Installing the displacement rods.............................16
Removing the displacement rods...........................16
Flue gas cyclone (optional)....................................17
Pneumatic cleaning system (optional)...................17
Feed systems...........................................................18
Shutdown...............................................................19
Boiler..................................................................19
Extraction and conveyance systems.......................19
Control system....................................................19
Replacing the buffer battery..................................19
Ash disposal........................................................19
Disposal of the boiler............................................19
Instructions regarding removal...............................19
Waste disposal....................................................19
Troubleshooting
Performance Problems...............................................20
Grate Drive Mechanics Jams.....................................21
Checking for increased Wear of Fireclay......................22
Checking the Inside of the Boiler Door.........................23
Checking Balancing the Oxygen
Heating System Faults..............................................26
Loader System Faults................................................27
the Oxygen Control System.........................24
Sensor.....................................25
4
5603 880 - 01
Page 5
Pyrot Service & Maintenance
Product Information
General Information
Viessmann solid-fuel boiler can only be installed and serviced by qualified trained personnel.
Steel wood-fired hot water heating boiler.
For operation primarily with modulating boiler water temperatures in closed loop forced circulation hot water heating systems. Under certain conditions, open loop systems may also be considered. Contact Viessmann for details.
Maximum allowable working pressure (water)…30 or 60 psi
Maximum water temperature…250°F (120°C) (closed loop)
Maximum boiler temperature……210°F (99°C) (open loop)
This boiler does not require a flow switch.
WARNING
Exposing the boiler to pressures and temperatures in excess of those listed will result in damages and will render the warranty null and void.
Codes
CSA B366.1-M91 Solid Fuel Fired Central Heating Appliances
CSA C.22.2#3-M88 (R2004) Electrical Features of Fuel Burning Equipment
UL2523 Solid Fuel-Fired Hydronic Heating Appliances, Water Heaters and Boilers
CSA B365-10 Installation Code for Solid Fuel Burning Appliances and Equipment
5603 880 - 01
5
Page 6
General Information
Important Regulatory and Installation Requirements
Please carefully read this manual prior to attempting service and maintenance. Any warranty is null and void if these instructions are not followed.
For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product.
We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire.
Pyrot Service & Maintenance
Working on the equipment
The installation, adjustment, service, and maintenance of this boiler must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers.
Ensure main power supply to equipment, the heating system, and all external controls have been deactivated. Take precautions to avoid accidental activation of power during service work.
CAUTION
RISK OF INJURY: Shut the system off before starting any cleaning. Be absolutely sure to wear protective gloves, protective eyewear if required and use the cleaning tools that come with the system (danger of blow-ups, burns and getting crushed)!
Technical literature
Literature applicable to all aspects of the Pyrot wood-fired boiler:
- Installation and Operating Instructions
- Service and Maintenance Instructions
- Field Wiring Diagram
The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include low-water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, etc.
Leave all literature at the installation site and advise the system operator/ultimate owner where the literature can be found. Contact Viessmann for additional copies.
This product comes with several safety instruction labels attached. Do not remove! Contact Viessmann immediately if replacement labels are required.
6
5603 880 - 01
Page 7
Pyrot Service & Maintenance
Important Regulatory and Installation Requirements (continued)
Regular maintenance and service
The entire heating system must be cleaned and serviced on a regular basis by a qualified contractor or service agency to ensure reliable, energy-efficient, and environmentally friendly operation.
The build-up of soot on the heat exchanger raises the flue gas temperature and reduces efficiency.
WARNING
Improper installation, adjustment, service or maintenance can cause flue products to flow into living space. Flue products contain poisonous carbon monoxide gas, which can cause nausea or asphyxiation resulting in severe personal injury or loss of life.
General Information
WARNING
The boiler must not be located in areas or rooms where chemicals are stored or aggressive vapors from (i.e. bleach, hair spray, methyl chloride, carbon tetrachloride or perchloroethylene) or high dust levels or humidity levels are present. Heat exchanger corrosion might occur and reduce the lifetime of the boiler significantly. If above criteria are not properly observed and boiler damage results, any warranty on the complete boiler and related components will be null and void.
IMPORTANT
Keep boiler and boiler room clear and free of combustible materials, gasoline and other flammable vapors and liquids. Do not obstruct the flow of combustion and ventilation air. All inspection, maintenance and service must be performed by a qualified heating contractor.
WARNING
Service and maintenance can only be performed by a qualified heating contractor.
Important to know
Do not use this boiler if any part has been under, or exposed to, water. Immediately call a qualified heating contractor to inspect the boiler and to replace any part of the control system, which has been under or exposed to water.
5603 880 - 01
7
Page 8
Safety
Safety Instructions
Pyrot Service & Maintenance
IMPORTANT
The local building codes and regulations must be followed by the heating contractor.
IMPORTANT
Please refer to the Installation and Operating Instructions for installation, commissioning and technical specification information. The “Installation and Operating Instructions” contain the necessary safety and national/local code requirements which, if not followed exactly, may lead to property damage, personal injuries and/or death.
Important Information
Safety instructions
When carrying out work on the heating system, such as cleaning and maintenance, wear appropriate protective equipment when required.
There is a danger of getting injured through: burning, knocking against corners and edges, crushing in moving parts and noise.
Power supply: 120V or 240V/1/ and 208V/3/ 60Hz In case of an emergency, the Pyrot can be disconnected from the electrical power supply at all the leads by the main switch on the control cabinet.
If you notice fire coming from the appliance, call the fire department immediately! DO NOT attempt to extinguish the fire unless qualified to do so.
Doors: for safety keep firing and ash pit doors tightly closed
CAUTION
FIRE HAZARD: The boiler must NEVER be operated with the doors open! Any burning bits that escape could start a fire.
RISK OF INJURY: If the doors are open during operation, sparks or flames could leap out.
Equipment for dissipating excess heat: a competent specialist should examine the operational reliability of the thermal safety flush valve annually. The safety heat exchanger must not by any means be used as an operational heat exchanger.
Seals: for the functioning and controllability of the boiler, it is important that no unwanted air can enter unchecked through leaks.
The doors and lids have to shut tight - any damaged seals must be replaced immediately. Tighten the retaining screws and handles well.
Operation, cleaning and maintenance: bear in mind that even the best product can only fulfill its functions well, doing so for a long time and free of malfunctions, if operated and maintained properly.
IMPORTANT
Compliance with the “Cleaning” section is mandatory!
WARNING
Fire causes a risk of burns and explosion!
Shut down the boiler Close fuel shut-off valves Use a tested fire extinguisher, class ABC.
8
5603 880 - 01
Page 9
Pyrot Service & Maintenance
Carbon Monoxide
Carbon monoxide
The U.S. Consumer Product Safety Commission strongly recommends the installation of carbon monoxide detectors in buildings in which wood-burning equipment is installed. Carbon monoxide (CO) is a colorless, odorless gas, which may be produced during incomplete combustion of fuel and/or when the flame does not receive an adequate supply of combustion air. Carbon monoxide can cause severe personal injury or loss of life.
Therefore, carbon monoxide detectors that are in compliance with a nationally recognized standard (e.g. ANSI/UL 2034-2002, CSA 6.19-01) should be installed and maintained in buildings that contain wood-burning equipment.
Note: Viessmann does not test any detectors and makes no representation regarding any brand or type of detector.
Safety
Service/inspection of the boiler and the system must be performed on a regular basis. Maintenance, service and cleaning are specified in the section “Maintenance”.
Before the heating season begins, it is recommended that the boiler be serviced by a qualified heating contractor.
WARNING
Improper installation, adjustment, service or maintenance can cause flue products to flow into living space. Flue products contain poisonous carbon monoxide gas, which can cause nausea or asphyxiation resulting in severe personal injury or loss of life.
WARNING
For safe operation
We recommend that you frequently:
- Check for debris which could obstruct the flow of flue gases. The vent or chimney must not be blocked. A blocked or partially blocked vent or chimney can cause flue gases to leak into the structure. Flue gases leaking into the house can cause injury or death. Blocked or partially blocked chimneys must have the blockage removed by a qualified heating contractor.
- Check pressure gage for correct system (water) pressure. Check for water on the floor from the discharge pipe of the pressure relief valve or any other pipe, pipe joint, valve or air vent.
- Check for moisture, water, or appearance of rust on the flue gas pipes, their joints as well as vent dampers, or side wall vent terminals (if so equipped).
- Ensure that nothing is obstructing the flow of combustion and ventilation air and no chemicals, garbage, gasoline, combustible materials, flammable vapors and liquids are stored (not even temporarily) in the vicinity of the boiler.
- DO NOT allow unsupervised children near the boiler.
The operator/ultimate owner is required to have the heating boiler and controls checked, as a minimum once per year, by the original installer or by a competent heating contractor familiar with the equipment. Defects must be corrected immediately.
5603 880 - 01
9
Page 10
Safety
Extreme Weather Conditions
Frozen water pipe hazard
Your heating boiler is designed to provide a warm and comfortable living environment. It is NOT designed to ensure against freezing of water pipes. The boiler is equipped with several safety devices that are designed to shut down the boiler and to prevent it from restarting in the event of various unsafe conditions.
Pyrot Service & Maintenance
If the building will be unattended for an extended period of time during cold weather, you should...
Shut off the water supply to the building, drain the water pipes and add antifreeze for potable water to drain traps and toilet tanks. Open faucets where appropriate.
If your boiler remains off for an extended period of time during cold weather, water pipes may freeze and burst, resulting in extensive water damage and conditions in which mold could grow. Certain molds are known to cause respiratory problems, as well as to pose other serious health risks. In case of water damage, immediate measures should be taken to dry out affected areas as quickly as possible to prevent mold from developing.
WARNING
As there are no user-serviceable parts on the boiler, or control, the end-user must not perform service activities of any kind on system components. Failure to heed this warning can cause property damage, severe personal injury or loss of life.
or…
Have someone check the building frequently during cold weather and call a qualified service agency if required.
or...
Install a reliable remote temperature sensor that will notify somebody of freezing conditions within the building.
10
5603 880 - 01
Page 11
Pyrot Service & Maintenance
Hazardous Material
Fiberglass wool and ceramic fiber materials
WARNING
Inhaling of fiberglass wool and/or ceramic fiber materials is a possible cancer hazard. These materials can also cause respiratory, skin and eye irritation.
The state of California has listed the airborne fibers of these materials as a possible cancer hazard through inhalation. When handling these materials, special care must be applied.
WARNING
Appliance materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause serious injury or loss of life and which are known to the State of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing or working nearby the appliance.
First aid measures
- If eye contact occurs, flush eyes with water to remove dust. If symptoms persist, seek medical attention.
- If skin contact occurs, wash affected areas gently with soap and warm water after handling.
Safety
Suppliers of ceramic fiber products recommend the following first aid measures:
- Respiratory tract (nose and throat) irritation: If respiratory tract irritation develops, move the person to a dust free location.
- Eye irritation: If eyes become irritated, flush immediately with large amounts of lukewarm water for at least 15 minutes. Eyelids should be held away from the eyeball to ensure thorough rinsing. Do not rub eyes.
- Skin irritation: If skin becomes irritated, remove soiled clothing. Do not rub or scratch exposed skin. Wash area of contact thoroughly with soap and water. Using a skin cream or lotion after washing may be helpful.
- Gastrointestinal irritation: If gastrointestinal tract irritation develops, move the person to a dust free environment.
Suppliers of fiberglass wool products recommend the following precautions be taken when handling these materials:
- Avoid breathing fiberglass dust and contact with skin and eyes.
- Use NIOSH approved dust/mist respirator.
- Wear long-sleeved, loose fitting clothing, gloves and eye protection.
- Wash work clothes separately from other clothing. Rinse washer thoroughly.
- Operations such as sawing, blowing, tear-out and spraying may generate airborne fiber concentration requiring additional protection.
5603 880 - 01
11
Page 12
Safety
Mechanical Room
Pyrot Service & Maintenance
No combustible materials may be stored in the heating room. The heating boiler may only be set up on a fire­resistant and temperature-resistant floor. No temperature­sensitive pipes or lines may be installed in the floor beneath the heating boiler.
A sufficient supply of fresh air must be provided directly from outdoors into the heating room. Induced ventilation is necessary for heating rooms that are confined or enclosed.
See “Installation and Operating Instructions” for more details.
The temperature in the heating room must not exceed 104°F (40°C) while the system is in operation (in the area approx. 3 ft. (1 m) away from the boiler). The temperature in the heating room must not fall below 50°F (10°C) while the system is in operation (measured at the inner side of exterior walls).
IMPORTANT
Always follow the most up-to-date local, municipal and building regulations and codes.
Mechanical room conditions
WARNING
Incorrect ambient conditions can lead to damage to the heating system and put safe operation at risk.
Prevent the air from becoming contaminated by homogenate hydrocarbons (e.g. as contained in paints solvents or cleaning fluids) and excessive dust (e.g. through grinding or polishing work). Combustion air for the heating process, and ventilation of the boiler room must be free of corrosive contaminants. To that end, any boiler must be installed in an area that has no chemical exposure. The list to the right indicates the main, currently known sources.
Avoid continuously high levels of humidity (e.g. through frequent drying of laundry).
Never close existing ventilation openings.
IMPORTANT
Components which are not tested with the heating system may damage the heating system or affect its functions. Installation or replacement may only be carried out by a qualified heating contractor.
Sources of combustion and ventilation air contaminants
Areas likely to contain contaminants:
- New building construction
- Swimming pools
- Remodeling areas, hobby rooms
- Garages with workshops
- Furniture refinishing areas
- Dry cleaning/laundry areas and establishments
- Auto body shops
- Refrigeration repair shops
- Metal fabrication plants
- Plastic manufacturing plants
- Photo processing plants
- Beauty salons
Products containing contaminants:
- Chlorine-type bleaches, detergents and cleaning solvents found in household laundry rooms
- Paint and varnish removers
- Hydrochloric acid, muriatic acid
- Chlorine-based swimming pool chemicals
- Spray cans containing chlorofluorocarbons
- Chlorinated waxes and cleaners
- Cements and glues
- Refrigerant leaks
- Calcium chloride used for thawing
- Sodium chloride used for water softening salt
- Permanent wave solutions
- Adhesives used to fasten building products and other similar item
- Antistatic fabric softeners used in clothes dryers
12
5603 880 - 01
Page 13
Pyrot Service & Maintenance
Combustion Air Supply
Safety
Codes
Provision for combustion and ventilation air must be made in accordance with applicable local codes.
In the absence of local codes, use:
CSA B365-10, Installation Code for Solid Fuel Burning Appliances and Equipment. Always use latest edition codes.
WARNING
Failure to provide an adequate supply of fresh combustion air can cause poisonous flue gases to enter living space. Flue gases entering living space can cause carbon monoxide poisoning which can result in severe personal injury or loss of life.
WARNING
Never cover the boiler or store debris or other materials near the boiler, or in any way block the flow of adequate fresh air to the boiler. Never cover the combustion air opening. Advise system operator/ultimate owner accordingly.
WARNING
The boiler must not be located in areas or rooms where chemicals are stored, or aggressive vapors (i.e. bleach, hair spray, methyl chloride, carbon tetrachloride or perchloroethylene) or high dust levels or humidity levels are present. Heat exchanger corrosion might occur and reduce the lifetime of the boiler significantly. If above criteria are not properly observed and boiler damage results, any warranty on the complete boiler and related components will be null and void.
General
This equipment requires fresh air for safe operation.
The boiler location must never be under negative pressure. Exhaust fans, attic fans, or dryer fans may cause air to be exhausted at a rate higher than air can enter the structure for safe combustion.
The heating contractor shall ensure all of the following requirements are met:
- An adequate supply of combustion air must be available to ensure proper combustion.
- Ambient air temperatures must be maintained within safe operating limits.
- When a damper is provided in any opening intended to admit combustion air into the room within which the appliance is installed, the damper shall be interlocked to prevent any boiler from starting before the damper is fully open.
- Each duct used to convey air from the outdoors shall have:
1. a cross-sectional area throughout its length at least equal to the free area of the inlet and outlet openings which it connects,
2. making a provision for outside combustion air, the intake shall not be less than 1 ft. (0.3 m) above the anticipated snow level for the location.
- The heating contractor must check with local authorities (municipal building department) for combustion air requirements particular to the area.
See “Installation and Operating Instructions” for more details.
5603 880 - 01
13
Page 14
Maintenance
Components of the Biomass Boiler
Pyrot Service & Maintenance
1 In-feed auger with isolating layer 2 Drive for moving grate 3 Moving grate 4 Drive for automatic de-ashing system (optional) 5 Igniter 6 Controlled combustion air supply system 7 Rotary blower (Viessmann-patented)
14
8 Boiler door 9 Heat exchanger
qP Rotary combustion chamber (Viessmann-patented) qQ Safety heat exchanger for thermal safety flush valve qW Frequency-controlled flue gas exhaust blower
qE Pneumatic cleaning system (optional) qR Flue gas recirculation pipe
5603 880 - 01
Page 15
Pyrot Service & Maintenance
Cleaning
Boiler
The heat exchanger, flue gas pipe, and chimney must be cleaned regularly to remove accumulated creosote and ash.
Ensure that the heat exchanger, flue gas pipe, and chimney are cleaned at the end of the heating season to minimize corrosion during the summer months. The appliance, flue gas pipe, and chimney must be in good condition.
With pneumatic cleaning system, after approx. 600 operating hours; without pneumatic cleaning system, after approx. 300 operating hours:
Open the boiler door and clean all heat exchanger with a wire cleaning brush. Use the ash rake to carefully draw the fly ash lying in the rotary combustion chamber to the front.
Maintenance
Regular cleaning and maintenance of the boiler system is of the utmost importance to assure trouble-free operation and to obtain the largest possible output at the best efficiency.
The cleaning intervals listed here are for wood chip fuel material with clinging bark with 0.8% ash content. The cleaning intervals may vary, depending on the fuel, the amount of fine matter and the operating conditions.
After approx. 1000 operating hours:
Disconnect the power from the flue gas exhaust blower, loosen the butterfly nuts, pull out the motor with impeller and clean the assembly with a broom or wire brush.
CAUTION
DANGER OF INJURY – be absolutely sure to turn OFF the main switch.
IMPORTANT
With pneumatic cleaning system, disconnect the compressed air line before opening the boiler door – danger of injury!
After approx. 300 operating hours:
Open the lid across the in-feed auger and clear the slots in the grate.
CAUTION
RISK OF INJURY: Shut the system
off before starting any cleaning. Be
absolutely sure to wear protective
gloves, protective eyewear if required
and use the cleaning tools that come
with the system (danger of blow-ups,
burns and getting crushed)!
Check the level of the ash bin regularly and empty the bin before it is completely full.
IMPORTANT
NEVER operate the boiler without the ash bin.
5603 880 - 01
After approx. 1000 operating hours:
Clean the recirculated flue gas line.
After approx. 300 operating hours:
Loosen and clean the light barriers and the inspection windows on the combustion chamber. Remove dust and ash in the openings.
15
Page 16
Maintenance
Pyrot Service & Maintenance
Cleaning (continued)
Heat exchanger displacement rods
The displacement rods improve the heat transmission in the heat exchanger and reduce the temperature of the exhaust gas, thus improving the efficiency of the heating system. They have to be taken out to clean the heat exchanger and put back in after cleaning.
Installing the displacement rods
Insert the displacement rods into the heat exchanger with the thick end first. Push until they are flush with the edge of the tube. Tolerance +/- a” (5 mm).
Removing the displacement rods
Remove the displacement rods with a pair of pliers, as shown above. The heat exchanger should be cleaned at the intervals prescribed so that performance and efficiency are maintained and the displacement rods can be easily removed.
16
CAUTION
RISK OF INJURY: Shut the system off before starting any cleaning. Be absolutely sure to wear protective gloves, protective eyewear if required and use the cleaning tools that come with the system (danger of blow-ups, burns and getting crushed)!
5603 880 - 01
Page 17
Pyrot Service & Maintenance
Cleaning (continued)
Flue gas cyclone (optional)
The flue gas cyclone minimizes dust emissions and is designed as a multi-cyclone with an axial function. The cyclone is completely insulated and provided with a total of three lids for cleaning. The untreated exhaust flue gas chamber is cleaned via the cleaning lid on the side. The clean exhaust flue gas chamber is cleaned via the top or rear cleaning lid (unused blower connection).
The ash container, which is provided with a trolley, connects to the cyclone by quick-action fasteners and easily moves out for emptying. The flue gas exhaust blower can be mounted either on top or on the side, as desired.
After approx. 1000 operating hours:
Disconnect the power, unscrew the butterfly nuts, pull out the motor with impeller and clean the assembly with a broom or wire brush.
After every cleaning of the boiler heat exchanger:
Open the side lids and clean the guide blades of the cyclone with a hand-brush.
Maintenance
CAUTION
RISK OF INJURY: Shut the system off before starting any cleaning. Be absolutely sure to wear protective gloves, protective eyewear if required and use the cleaning tools that come with the system (danger of blow-ups, burns and getting crushed)!
Check the level of the ash container regularly and empty the bin before it is completly full.
IMPORTANT
Never operate the boiler without an ash bin!
Pneumatic cleaning system (optional)
- Operation and maintenance of the air compressor (optional) according to the manual that comes with the system.
- For a field supplied air compressor, the compressor has to be suited for continuous operation or be secured against continuous operation (e.g. timer for limiting running time).
- Continuous operation of the compressor indicates leakage in the air system. Check air supply line and valves for leakage.
Regularly drain condensation water in the compressed air distribution bar.
5603 880 - 01
17
Page 18
Maintenance
Feed Systems
Pyrot Service & Maintenance
When storage facilities for wood are required the wood should be kept at least 5 ft. (1.5 m) from the heating appliance.
All geared motors on the feed systems are maintenance-free.
- A change of lubricant and/or oil is recommended every 20,000 operating hours or every three years.
- Re-lubricate flange bearings and other lubricating points regularly with lithium soap grease.
- Check chain drives for wear and if necessary, tighten them up and lubricate with chain oil.
- Check all bolts for tightness.
- Once a year check the extraction components in the silo and/or bunker for damage and soiling. Remove any foreign matter.
Funnel extraction system (AP/APS):
Lubricate the gasket between the extraction casing and the geared motor and universal joint for the auger.
If a fuel hopper is installed, do not alter equipment in any way. May be connected to an existing boiler or solar system.
IMPORTANT
Never use inflammable lubricants!
CAUTION
RISK OF INJURY: Shut the system off before starting any cleaning. Be absolutely sure to wear protective gloves, protective eyewear if required and use the cleaning tools that come with the system (danger of blow-ups, burns and getting crushed)!
Note: Viessmann recommends the installation of carbon
monoxide detector(s) inside the fuel storage area.
IMPORTANT
The fuel storage area/room must be designed, operated and maintained to national, provincial and local codes and requirements.
WARNING
The wood chip/pellet storage room must be adequately and permanently ventilated. Ensure the door or latches are securely locked open during presence in the room. No smoking, fires or open flames are permitted.
18
5603 880 - 01
Page 19
Pyrot Service & Maintenance
Shutdown
Maintenance
Boiler
Heat exchanger:
- When the Pyrot is not in operation for a long period (such as for summer breaks), be sure to carefully clean the heat exchanger with a steel brush as required.
- If the heating room is moist or there is any other atmosphere that promotes corrosion (e.g. poor ventilation, residual enamel near the heating room, etc.), spray the heat exchanger with biodiesel after cleaning.
- If there is a danger of frost, empty the heating system or add antifreeze.
Extraction and conveyance systems
When the Pyrot is not in operation for a long period (such as for summer breaks), it is recommended to empty the fuel extraction and conveyance system of all fuel to avoid corrosion of the equipment and decay of the wood fuel. Refill with new fuel after checking the system and before the boiler startup.
Control system
Even when the Pyrot is not in operation for long periods, the power supply to the control system should not be interrupted (do not turn off the main switch).
- The “intermittent control system” switches on the boiler pump for five seconds every 24 hours. This prevents the pump from jamming during long stand stills and prevents expensive repairs.
- Prevent the formation of condensation in the oxygen sensor.
- Extend the service life of the buffer battery.
Disposal of the boiler
- Switch off the Pyrot by pressing the F1 button. When the burn-out has taken place and the boiler has cooled down, turn off the main switch.
- Disconnect the power supply to the control cabinet.
CAUTION
DANGEROUS VOLTAGE! Only a licensed electrician is allowed to disconnect and dismantle the connection to the electrical network.
- Close the supply and return valves.
- Open the drain valve on the bottom of the boiler and drain the water.
IMPORTANT
Only a qualified heating contractor may drain the boiler and dismantle the connections to the heating system.
- Disconnect the supply pipe and return pipe from the boiler.
Instructions regarding removal
Personnel removing equipment must be aware of the risks and use suitable safety precautions.
Waste disposal
- Comply with customary laws and local regulations on waste disposal.
- Contact a disposal company to dispose and recycle waste in a environmental friendly way.
Replacing the buffer battery
The buffer battery is built in beneath the removable lid on the control module (type Panasonic Lithium BR2330). It is for buffering the time, date and settings.
Note: The battery needs replacing every five years. DO NOT disconnect the main power or turn off the main switch while changing the battery.
Ash disposal
- Ashes should be stored in covered metal containers on non-combustible floors away from combustible material.
- Comply with customary laws and local regulations on ash disposal.
5603 880 - 01
19
Page 20
Troubleshooting
Performance Problems
The boiler does not provide its original performance.
Performance
problems
Pyrot Service & Maintenance
Boiler temp.
ACTUAL <
Boiler temp.
TARGET
Yes
Exhaust
gas temp.
ACTUAL <
Exhaust gas
temp. limit
value
Yes
Residual oxygen
ACTUAL
Residual oxygen
TARGET
Yes
Fuel < W35
1 Check settings 2 Heat cannot be dissipated
No
3 Check the function of the boiler pump and the 3-way mixing valve F3 parametercontrol menu
1 Clean heat exchanger F3 parametercontrol menu
No
1 Clean grate 2 Clean all four sight glasses and pipes of the ember monitoring
No
system light barrier 3 Check the position of the light barrier
F3 parameter control menu
1 Use proper fuel 2 Close recirculation temporarily
No
3 Open ash chamber door that is closer to the feed auger by 2” (50 mm) temporarily
Boiler
re-establishes
its performance
No
Boiler
re-establishes
its performance
No
Boiler
re-establishes
its performance
No
Boiler
re-establishes
its performance
Yes
Yes
Yes
Yes
Fault rectified
Fault rectified
Fault rectified
Fault rectified
Yes
Open primary air vent
1 Check air vent moves smoothly 2 Compare opening angle on the
No
operating console 3 Check electrical connections
Yes
Check that
grate vents
move
smoothly
No
Yes
Contact Viessmann
20
1 Clean grate vents of cinder coatings 2 Remove impurities
No
Boiler
reestablishes
its performance
No
Boiler
re-establishes
its performance
No
Yes
Yes
Fault rectified
Fault rectified
5603 880 - 01
Page 21
Pyrot Service & Maintenance
Grate Drive Mechanics Jams
Grate drive mechanics are no longer running causing cinders to accumulate on the grate.
Grate drive
mechanics jammed
Troubleshooting
Check electrical
triggering system
Check shear-off pin
Clean the connecting
rod and bronze bearing
Check grate
 Set the system to “Cleaning”, this
causes the grate drive motor to run continuously.
 Check that the shear-off pin on the
connecting rod is OK.
 Check that a spare shear-off pin is
present.
 Cleaning of the connecting rod and
of the bronze bearing by means of grease removers.
 Check grate for foreign material.
Check grate factory settings
5603 880 - 01
 Are all grate components properly inserted?  Lateral play - sliding grate for the concrete;
3
/161/32” (51 mm) (applies up to KRT 300)
5
/161/16” (82 mm) (applies up to KRT 400/540)
 Crank axle distance;
KRT 100/150 1e”(35 mm) KRT 220/300 2 KRT 400/540 3
 Setting, stop position, sliding grate “back” crank drive right in
the back - movable grate components, front approx.
5
/32” (55 mm)
5
/32” (80 mm)
1
/16- 5/32
(2-4 mm) play (adjustment via threaded rod)
 Setting, movable grate components, “front” crank drive right
in the front - movable grate components, front project approx.
5
/16” (8 mm) beyond the fixed parts and have approx. 1/16- 5/32
(2-4) mm play (adjustment via adjusting screw at the bottom on the grate).
21
Page 22
Troubleshooting
Pyrot Service & Maintenance
Checking for Increased Wear of Fireclay
Increased fireclay wear can be observed in the substructure or in the curved bricking. Fireclay must only be replaced when:
the curved bricking is broken downwards (not already in the event of formation of cracks or spalling) fireproof panel located on the back of the fireclay can be seen in the substructure
Checking for increased
wear of fireclay
 Cleaning in the area of the arch in the chimney
Check the recirculation system
and in the area of the opening of the shut-off valve
 Recirculation must be hot at partial load
Check damper
Check fireclay for discoloration
 Damper must be installed  Damper must not be fully open (chimney draft
may be too strong)
 If discoloration is visible in the fireclay  If there is discoloration, often halogen
substances have been burned
22
5603 880 - 01
Page 23
Pyrot Service & Maintenance
Troubleshooting
Checking the Inside of the Boiler Door
Checking the inside of the boiler door can indicate whether the fibre glass seal is properly applied. If the seal is not properly applied, higher levels of CO gas can form. Checking the inside of the door can also indicate whether the guide tube is indicating increased wear. This is a danger especially at higher temperatures.
Checking the inside
of the boiler door
 Check guide tube for deformation
(possible cause of deformation:
Check guide tube
Overheating If there is increased wear of the fireclay, perform check (see section checking for increased wear of Fireclay)
 Check guide tube for wear
Check boiler door seal
Check fireclay boiler door
 Seal must fit properly and be caulked  Procedure if a seal is leaking
Replace ceramic packing of the seal, check by means of impression test that the whole surface of the seal lies on the ceramic packing, increase seal contact pressure in KRT-400/540 with the screws outside on the door
 Check fireclay erosion  The formation of cracks and spalling
outside the glass fibre packing only constitutes an optical imperfection
 Complaints must be made in the event
of fireclay erosion inside the glass fibre packing from ~ 3d”(80 mm)
5603 880 - 01
23
Page 24
Troubleshooting
Pyrot Service & Maintenance
Checking Oxygen Control System
A check of the oxygen control is carried out in case of incomplete combustion, dark smoke escaping the chimney or performance problems.
Checking the oxygen
control system
Visual check of wiring
Clean the oxygen sensor
xygen display
o
with fresh air
between
20% - 21%
No
 Check that all electrical lines are
permanently connected
 Clean the outside of the oxygen
sensor using a wire brush
 Hold the oxygen sensor downwards
and gently tap out with the bristles of the wire brush until no more dirt falls out of the probe
 Balance the oxygen sensor (see
section on balancing the oxygen sensor)
Yes
Install the oxygen sensor
so it is leak tight
Check the boiler
24
 Set the heating system to cleaning  Check the leak tightness of the
installation with the flue
 Close the doors of the exhaust gas
collector and boiler door airtight (check with the flue)
 Pneumatic cleaning system is
operational and leak tight
5603 880 - 01
Page 25
Pyrot Service & Maintenance
Troubleshooting
Balancing the Oxygen Sensor
The oxygen sensor is subject to ageing which can be compensated by a oxygen sensor compensation. The oxygen sensor compensation is necessary if the residual oxygen to fresh air is <20%.
CAUTION
The oxygen sensor is constantly heated and is very hot.
Balancing the oxygen sensor
 Clean the oxygen sensor using a wire brush
Remove and clean the oxygen sensor
 Hold the oxygen sensor downwards and gently
tap out with a wire brush until no more dirt falls out of the sensor
 Let the oxygen sensor hang freely in the air
without contact to metal
Measure the oxygen
sensor signal
Boiler status “off”
Balance the oxygen sensor
 The oxygen sensor must be supplied with a
heating voltage in the range between 13.0 and
13.8V (measured at the white/white wires)
 The heating voltage can be adjusted on the main
board
 The signal voltage must be in the range between
-6 and -11 mV (measured at the grey-/black+wires)
 The boiler status must be “off” and the exhaust
gas temperature must be <122°F (50°C)
 The oxygen sensor must be supplied with current
for min. 5 minutes
 Carry out the oxygen sensor balancing in the
operating console Press OK+F3 (simultaneously)parametercontrol menu option 68
 Wait for the confirmation”Active”
Install the oxygen sensor
5603 880 - 01
 Install the oxygen sensor so it is leak tight  Check again with the flue
25
Page 26
Troubleshooting
Heating System Faults
Pyrot Service & Maintenance
Fault No.
01 Excess temperature
03-17 Interruption or
09 Oxygen sensor
18 Permanent code
19 Repeat heating up
20 Water level in
25 Light barrier, ember
26 Light barrier,
96 Feed auger pipe
81-93 BUS error, no
53-54 Extraction system
Text displayed Indicator Possible cause Check / remedy
(red light at F1, F2, F3)
short-circuit, sensor
(red light at F3)
(red light at F3)
(red light at F3)
extinguishing Water container
(red light at F3)
monitoring system
(red light at F3)
feed auger
(red light at F3)
too hot
connection to the
(red light at F3)
… silo door open (red light at F4)
Fixed high limit N21
- Sensor . . . - Damaged sensor connection line
- Oxygen sensor in the flue gas pipe
- Operating hours lapsed before the permanent code has been entered
- Exhaust gas temperature sensor
- Oxygen sensor
- Level float switch in extinguishing water container
- Light barrier for ember monitoring system
- Light barrier in the metering container for the feed auger
- Temperature sensor on the feed auger
- Data transmission line for the bus connection
- Limit switch for silo door
- Incorrect setting in the control module
- Defective component (pump or valve)
- Sudden drop in output to zero. The feed auger then has to be emptied. The heat produced by this can result in excess temperature. Activate the function “Dissipate excess heat”
- Indicator defective
- Indicator very soiled
- Indicator defective
- Error in the electronics
- Permanent code has not been entered
- Fuel too moist
- Oxygen sensor imprecise
- Igniter defective
- The combustion chamber filling time is too short
- Not enough water in the extinguishing water container
- Sight glass soiled; deposits of ash in the openings
- Defective indicator
- Light barrier soiled
- Clogging in the metering container
- Power failure
- Consequent malfunction caused by excess temperature
- Light barriers for ember monitoring system soiled
- Bus connection interrupted - Check plug connections
- Silo door open - Check and close silo door
- Why could the heat not be dissipated?
- Check the boiler pump and mixing valve
- Activate the function “Dissipate excess heat”
- Unscrew the protective cap on the fixed high limit and press the reset button (not possible until the boiler temperature is less than 158°F (70°C) and press OK
Call a qualified electrician
- Readjust oxygen sensor
- Acknowledge with OK
- Call Viessmann
- Use suitable, dry fuel
- Readjust oxygen sensor.
- Replace ignition device
- Readjust combustion chamber
- Acknowledge with OK
- Fill extinguishing water container
- Acknowledge with OK
- Remove and clean sight glasses on both sides
- Remove dust and ash deposit from the openings
- Refer to the section, “Cleaning”
- Acknowledge with OK
- Clean light barrier
- Remove clogging
- Acknowledge with OK
- Call a qualified electrician
- Check light barriers for embers
- Acknowledge with OK
- Replace data transmission line
- Call Viessmann
- Acknowledge with OK
26
5603 880 - 01
Page 27
Pyrot Service & Maintenance
Loader System Faults
Troubleshooting
Fault No.
01 Material shortage
11-24 Soft starter …
30 Feed auger
31-45 Conveyor device …
51-52 Extraction system …
Text displayed Indicator Possible cause Check / remedy
(red light at F4)
(red light at F4)
(red light at F4)
(red light at F4)
(red light at F4)
- Light barrier in the metering container
- Light barriers for the ember monitoring system
- Soft starter
- Red light at the soft starter
- Reversed control of in-feed auger
- Maintenance cover limit switch
- Maintenance cover limit switch
- Silo is empty
- Conveyance system is clogged/jammed
- Phase sequence mixed up
- Motor overloaded
- Other causes, depending on the malfunction displayed
- Material clogging in the in-feed auger
- One of the maintenance covers is open or not closed properly
- One of the maintenance covers is open or not closed properly
- Fill silo
- Turn off main switch and remove material clogging
- Acknowledge with OK
- Correct the phase sequence (clockwise rotating magnetic field)
- Remove clogging
- Refer to documentation for soft starter
- Acknowledge with OK
- Remove material clogging
- Check and close all the maintenance covers
- Acknowledge with OK
- Check and close all the maintenance covers
- Acknowledge with OK
53-54 Extraction system
… Hydraulic drive, temperature/level
(red light at F4)
53-54 Extraction system …
silo door open
(red light at F4)
01-27 Interruption or short-
circuit, sensor …
(red light at F4)
- Level float switch in the oil container for the walking floor extraction system
- Thermostat in the oil container
- Limit switch for silo door
- Sensor . . . - Damaged sensor
- Oil level too low, (possible loss of oil)
- Oil has been overheated by too high pressure
- Silo door open - Check and close silo door
connection line
- Indicator defective
- Refill oil. Check oil line for leakage
- Check and adjust operating pressure
- Acknowledge with OK
- Acknowledge with OK
- Call a qualified electrician
5603 880 - 01
27
Page 28
Pyrot Service & Maintenance
Printed on environmentally friendly
(recycled and recyclable) paper.
Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island · 02886 · USA 1-800-288-0667 · Fax (401) 732-0590 www.viessmann-us.com · info@viessmann-us.com
Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario · N2V 2G5 · Canada 1-800-387-7373 · Fax (519) 885-0887 www.viessmann.ca · info@viessmann.ca
Technical information subject to change without notice.
5603 880 - 01
Loading...