Viessmann Vitotronic 100 HC1, Vitotronic 300-K MW2, Vitotronic 100, HC1, Vitocontrol-S User's Manual And Operating Instructions

...
Page 1
Operating Instructions and User’s Information Manual
Vitodens 200-W, WB2B Series
Multi-boiler system with control units for operation with a constant temperature and weather-compensated cascade control unit
For operation with natural gas and liquid propane gas
Please file in Service Binder
VITOTRONIC 100, HC1 VITOTRONIC 300-K, MW2S
of Viessmann boilers only
Vitotronic 100, HC1
Vitotronic 300-K, MW2S
5728 417 v1.0 09/2010
Page 2
Safety, Installation and Warranty Requirements
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions
listed below and details printed in this manual can cause product / property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in the manual subsections).
H Licensed professional heating
contractor
The installation, service, and maintenance of this equipment must be performed by a licensed professional heating contractor.
"
Please see section entitled “Important Regulatory and Installation Requirements” in the Installation Instructions.
H Product documentation
Read all applicable documentation
before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
"
For a listing of applicable literature, please see section entitled “Important Regulatory and Installation Requirements” in the Installation Instructions.
H Carbon monoxide
Improper installation, service and/or maintenance can cause flue products to flow into living space. Flue products contain poisonous carbon monoxide gas.
"
For information pertaining to the proper installation, service and maintenance of this equipment to avoid formation of carbon monoxide, please see the Installation Instructions of the Vitodens 200-W Direct Vent System.
WARNING
Installers must follow local regulations with respect to installation of carbon monoxide detectors. Follow manufacturer’s maintenance schedule of boiler.
H E
quipment venting
Never operate boiler without an installed venting system. An improper venting system can cause carbon monoxide poisoning.
H Warranty
Information contained in this and related product documentation must be read and followed. Failure
to do so renders warranty null and void.
dvice to owner
H A
Once the installation work is complete, the heating contractor must familiarize the system operator / ultimate owner with all equipment, as well as safety precautions / requirements, shut-down procedure, and the need for professional service annually before the heating season begins.
2
5728 417 v1.0
Page 3
Table of Contents
Page
General Information / Safety
Safety
Inform Yourself
Start-up / Shutdown
Adjusting the Room Temperature
About these Instructions 5. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. .
For your Safety 5. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .. . .. . . .. . .. . . .
Getting Started 9. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .. . .. . . .. . .. . . .. .
Overview of Controls and Indicators 10. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . .
Opening the control unit 10. . . . . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . ..
Opening the programming unit 12. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. .
Select the Heating Circuit - Before Every Setting and
Scanning Operation 14. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .. . .. . . .
Starting the Heating System 15. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . ..
Shutting Down the Heating System 16. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .
Starting a Heating Circuit and DHW Heating 17. . . . . . .. . . .. . .. . ..
Stopping DHW Heating and the Heating Circuit 17. . . . . . .. . . ..
Starting DHW Heating Only 18. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . ..
Stopping DHW Heating 18. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .
Setting a Permanent Room Temperature 19. . . . . . .. . . .. . .. . .. . . .. . .. . .
Selecting the normal room temperature 19. . . . . . .. . . .. . .. . .. . . .. . .. . .
Selecting a reduced room temperature 20. . . . . . .. . . .. . .. . .. . . .. . .. . . ..
Changing the room temperature for a few days 22. . . . . . .. . . .. .
Setting the holiday program 22. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . ..
Selecting DHW Heating
Further Adjustments
Changing the Room Temperature for a
Few Hours Only 23. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .. . .. . . .. . .. . .
Setting energy saving mode 23.. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. . .. . . .. .
Setting party mode 23. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .. . .. . . .
Selecting Constant DHW Heating 24. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .
Setting the DHW temperature 24. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . ..
Selecting a time program (switching times) 25. . . . . . .. . . .. . .. . .. . . .
Selecting automatic mode (if required) 26. . . . . .. . .. . . .. . .. . . .. . .. . .. . .
Setting up an individual time program 26. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . ..
Selecting DHW Heating for a Few Hours Only 27. . . . . . .. . . .. . ..
Selecting DHW Heating Only Once 28. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . ..
Setting Time and Date 29. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .. .
Setting the display language 29. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .
Adjusting the display contrast 29. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .
Selecting the Boiler Sequence 30. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. . .. . . .. . .
Actual boiler sequence (standard display) 30. . . . . . .. . . .. . .. . .. . . .. . ..
Controlled boiler sequence 30. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .
Changing the Heating Pattern 31. . . . . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . ..
Changing the slope and shift 31.. .. . .. . . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .
Modifying the Boiler Heating Characteristics 33. . . .. . .. . . .. . .. . . .
5728 417 v1.0
3
Page 4
Table of ContentsTable of Contents
Page
Scanning Options
Other Settings
Scanning Temperatures and
Operating Status Information 34.. .. . .. . . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .
Scanning the Fault Display 35. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . .
Scanning Temperatures 36. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . .
Scanning Time Programs 37. . . . . . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . ..
Scanning party or energy saving mode 37. . . . . . .. . . .. . .. . .. . . .. . .. . . ..
Scanning Fault Display 38. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . ..
Selecting the Time Programs 39.. .. . .. . . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .
Rooms are too cold 39. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. .. . . .. . .. . . .
Rooms are too hot 40. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .. . .. . . .. .
There is no hot water 40. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .. . .
The DHW is too hot 41. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .. . .. . .
”OFF” is displayed by the Vitotronic 100 41. . . . . . .. . . .. . .. . .. . . .. . .
Fault symbol flashes in the display of
the Vitotronic 100 41. . . . . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . .. . .. . . .. . .. .
Fault flashes in the display
of the Vitotronic 300-K, MW2S 41. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .
The service display is shown by the Vitotronic 100 41. . . .
“Service” is displayed by the Vitotronic 300-K, MW2S 41. . . ”Remote control” is displayed by the
Vitotronic 300-K, MW2S 42. . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .
”External control” is displayed by the
Vitotronic 300-K, MW2S 42. . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .
”Central control” is displayed by the
Vitotronic 300-K, MW2S 42. . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .
“Slab curing program” is displayed by the
Vitotronic 300-K, MW2S 42. . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .
“Without function.” is displayed by the
Vitotronic 300-K, MW2S 42. . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . .. . . .. .. . . .
Service Instructions
Additional Information
Service Instructions for Your Heating System 43. . . . . . .. . . .. . .. . .
Lighting and Operating Instructions 44. . . . . . .. . . .. . .. . .. . . .. . .. . . .. . .. . . ..
4
5728 417 v1.05728 417 v1.0
Page 5
General Information/Safety
About these Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include ”WARNING”, ”CAUTION”, and ”IMPORTANT”. See below.
Warnings draw your attention to the
WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage.
CAUTION
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/property damage.
IMPORTANT
presence of potential hazards or important product information.
Cautions draw your attention to the presence of potential hazards or important product information.
Helpful hints for installation, operation or maintenance which pertain to the product.
For your Safety
H Operation
Before operating the boiler, make sure you fully understand its method of operation. Your heating contractor should always perform the initial start-up and explain the system. Any warranty is null and void if these instructions are not followed.
H Flue gas smell
H Working on the equipment
All personnel working on the equipment or the heating system must have the proper qualifications and hold all necessary licenses.
Ensure main power to equipment, heating system, and all external controls has been deactivated. Close main gas supply valve. Take precautions in all instances to avoid accidental activation of power during service work.
H Dangerous conditions
This symbol indicates that additional, pertinent information is to be found in column three.
This symbol indicates that other instructions must be referenced.
H Maintenance and cleaning
Regular inspection and service by a qualified heating contractor is important to the performance of the boiler. Neglected maintenance impacts on warranty; regular inspection ensures clean, environmentally friendly and efficient operation. We recommend a maintenance contract with a qualified heating contractor.
H Technical information
- Deactivate heating equipment.
- Open windows and doors.
- Inform your heating contractor.
5728 417 v1.0
- Deactivate main power immediately.
- Close gas supply valve.
Literature applicable to all aspects of the
Vitotronic 300-K, MW2S:
- Installation Instruction and Service Instructions
- Operating Instructions and User’s Information Manual
Additional applicable literature:
- Accessory manuals
5
Page 6
SafetySafety
For your Safety (continued)
H Carbon monoxide
The U.S. Consumer Product Safety Commission strongly recommends the installation of carbon monoxide detectors in buildings in which gas-burning equipment is installed. Carbon monoxide (CO) is a colorless, odorless gas, which may be produced during incomplete combustion of fuel and/or when the flame does not receive an adequate supply of combustion air.
Carbon monoxide can cause severe personal injury or loss of life.
Therefore, carbon monoxide detectors that are in compliance with a nationally recognized standard (e.g. ANSI/UL 2034-2002, CSA 6.19-01) should be installed and maintained in buildings that contain gas-burning equipment.
Note:
Viessmann does not test any detectors
nd makes no representation regarding
a any brand or type of detector.
H For safe operation
We recommend that you frequently:
- Check for debris which could obstruct the flow of flue gases. The vent or chimney must not be blocked. A blocked or partially blocked vent or chimney can cause flue gases to leak into the structure. Flue gases leaking into the house can cause injury or death. Blocked or partially blocked chimneys must have the blockage removed by a qualified heating contractor.
- Check pressure gage for correct system (water) pressure. Check for water on the floor from the discharge pipe of the pressure relief valve or any other pipe, pipe joint, valve or air vent.
- Check for moisture, water, or appearance of rust on the flue gas pipes, their joints as well as vent dampers, or side wall vent terminals (if so equipped).
- Ensure that nothing is obstructing the flow of combustion and ventilation air and no chemicals, garbage, gasoline, combustible materials, flammable vapors and liquids are stored (not even temporarily) in the vicinity of the boiler.
- Do not allow unsupervised children near the boiler.
Service/inspection of the boiler and the system is recommended once a year. Maintenance, service and cleaning are specified in the Installation Instructions.
Before the heating season begins, it is recommended that the boiler and burner be serviced by a qualified heating contractor. Service contracts may be established through gas suppliers or other licensed contractors in your area.
WARNING
As there are no user-serviceable parts on the boiler, burner or control, the end-user must not perform service activities or adjustments of any kind on system components. Failure to heed this warning can cause property damage, severe personal injury, or loss of life.
WARNING
Improper installation, adjustment, service, or maintenance can cause flue products to flow into living space. Flue products contain poisonous carbon monoxide gas which can cause nausea or asphyxiation resulting in severe personal injury or loss of life.
CAUTION
Should overheating occur or the gas supply fail to shut off, do not disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
WARNING
The operator/ultimate owner is required to have the heating boiler, burners, and controls checked, as a minimum once per year, by the original installer or by a competent heating contractor familiar with the equipment. Defects must be corrected immediately.
CAUTION
Do not use this boiler if any part has been under water. Immediately call a qualified heating contractor to inspect the boiler and to replace any part of the control system and any gas control which has been under water.
6
5728 417 v1.05728 417 v1.0
Page 7
For your Safety (continued)
Safety
Frozen water pipe hazard
WARNING
Failure to protect against frozen pipes could result in burst water pipes, serious property damage and/or personal injury. Boiler may shut down. Do not leave your home unattended for long periods of time during freezing weather conditions without turning off the water supply and draining water pipes or otherwise protecting against the risk of frozen pipes.
Your heating boiler is designed to provide a warm and comfortable living environment. It is not designed to ensure against freezing of water pipes. The boiler is equipped with several safety devices that are designed to shut down the boiler and to prevent it from restarting in the event of various unsafe conditions.
If your boiler remains off for an extended period of time during cold weather, water pipes may freeze and burst, resulting in extensive water damage and conditions in which mold could grow. Certain molds are known to cause respiratory problems, as well as to pose other serious health risks. In case of water damage, immediate measures should be taken to dry out affected areas as quickly as possible to prevent mold from developing.
If your home will be unattended for an extended period of time during cold weather, you should...
H Shut off the water supply to the
building, drain the water pipes and add an antifreeze for potable water to drain traps and toilet tanks. Open faucets where appropriate.
Or..
H Have someone check the building
frequently during cold weather and call a qualified service agency if required.
Or...
H Install a reliable remote temperature
sensor that will notify somebody of freezing conditions within the home.
5728 417 v1.0
7
Page 8
Safety
For your Safety (continued)
If you notice fire coming from the appliance, call the fire department immediately! Do not attempt to extinguish the fire unless qualified to do so.
WARNING
Fire causes a risk of burns and explosion!
HHHH Shut down the boiler HHHH Close fuel shut-off valves HHHH Use a tested fire extinguisher, class
ABC.
Installation area conditions
WARNING
Incorrect ambient conditions can lead to damage to the heating system and put safe operation at risk.
H Ensure ambient temperatures are higher
than 32°F / 0°C and lower than 104°F / 40°C.
H Prevent the air from becoming
contaminated by halogenated hydrocarbons (e.g. as contained in paint solvents or cleaning fluids) and excessive dust (e.g. through grinding or polishing work). Combustion air for the heating process, and ventilation of the boiler room must be free of corrosive contaminants. To that end, any boiler must be installed in an area that has no chemical exposure. The list to the right indicates the main, currently known sources.
H Avoid continuously high levels of
humidity (e.g. through frequent drying of laundry).
H Never close existing ventilation
openings.
Replacement components, spare and wear parts
IMPORTANT
Components which are not tested with the heating system may damage the heating system, or affect its functions. Installation or replacement may only be carried out by a qualified heating contractor.
Sources of combustion and ventilation air contaminants
Areas likely to contain contaminants:
H New building construction H Swimming pools H Remodelling areas, hobby rooms H Garages with workshops H Furniture refinishing areas H Dry cleaning/laundry areas and
establishments
H Auto body shops H Refrigeration repair shops H Metal fabrication plants H Plastic manufacturing plants H Photo processing plants H Beauty salons
Products containing contaminants:
H Chlorine-type bleaches, detergents and
cleaning solvents found in household laundry rooms
H Paint and varnish removers H Hydrochloric acid, muriatic acid H Chlorine-based swimming pool chemicals H Spray cans containing
chlorofluorocarbons
H Chlorinated waxes and cleaners H Cements and glues H Refrigerant leaks H Calcium chloride used for thawing H Sodium chloride used for water
softening salt
H Permanent wave solutions H Adhesives used to fasten building
products and other similar items
H Antistatic fabric softeners used in
clothes dryers
8
5728 417 v1.0
Page 9
Getting Started...
Inform Yourself
The timer of the control unit switches between ”normal room temperature” and ”reduced room temperature” at the required times.
1. Normal room temperature
for the times you spend at home and require a comfortably warm room temperature (e.g. 68ºF / 20ºC).
2. Reduced room temperature
for the times you are away from home. To save energy, a lower temperature is typically selected (e.g. 57ºF / 14ºC).
The timer of the control unit switches domestic hot water production on and off at the required times.
1. Domestic hot water heating can be
set to take place
during the times you spend at home and require hot water for your daily DHW requirements (e.g. for showering).
2. Domestic hot water heating can be
set not to take place
for the times you spend sleeping, for example.
Times and duration of the two room temperatures can be set on the programming unit of your control. The temperature settings for both the ”normal room temperature” and ”reduced room temperature” can be set according to your personal preference.
Times and duration of the domestic hot water production period can be set on the programming unit of your control.
You may select a DHW temperature setting based on your personal preference of up to 140ºF / 60ºC.
The domestic hot water recirculation pump (if installed) ensures that domestic hot water is readily available when domestic hot water is drawn.
5728 417 v1.0
9
Page 10
Inform Yourself
Overview of Controls and Indicators
You can change all settings of your heating system centrally at the Vitotronic 100 of every boiler and at the Vitotronic 300-K, MW2S. All possible adjustments / settings are described in these operating instructions. You no longer need the individual operating instructions for the Vitotronic 100, HC1. You may also make such adjustments at the remote control, if your system is equipped with one.
Remote control operating instructions.
Opening the control unit
All boiler controls are located behind the control unit flap. To open, lift cover A and pivot control flap B down. On the inside of the control unit flap B, an abridged version of these operating instructions can be found behind a further flap C. The abridged operating instructions can be removed with the flap.
A Cover B Control unit flap (open to make
adjustments)
C Flap with abridged operating
instructions
5728 417 v1.0
10
Page 11
Overview of Controls and Indicators (continued)
Vitotronic 100, HC1
Inform Yourself
A
A Pressure gauge B Fault display (red) (see page 38) C Operating status display (green)
tr Set boiler water temperature tw Set DHW temperature tr+tw Emissions test function
9 Standby mode w DHW only
B
(only for heating contractors)
C D E F
D Factory default setting E User interface F ON / OFF switch (see page 15
and 16)
rw Heating and DHW / No function
/ Setting values
Confirmation Information
D Standard setting (reset)
Symbols in the display
These sysmbols are not permanently displayed, but appear subject to the system version and the operating state. Flashing displays indicate that modifications can be made.
r Boiler enabled by the
Vitotronic 300-K, MW2S
p Heating circuit pump ON A Burner ON S Emissions test ON (only for
service purposes)
E Burner fault u Time adjustment display
Standard display
The standard display shows the boiler water temperature.
i Information U Fault OFF Boiler is locked out of the cascade P Scanning hours run, burner
stage 1
PPP Scanning number of burner starts PPPP Consumption
After completing each adjustment on the control unit, the display will revert to the standard display.
5728 417 v1.0
11
Page 12
Inform Yourself
Overview of Controls and Indicators (continued)
You can change all settings of your heating system centrally at the Vitotronic 100 of every boiler and at the Vitotronic 300-K, MW2S. You may also make such adjustments at the remote control, if your system is equipped with one.
Remote control operating instructions.
Opening the programming unit
The programming unit is located behind the hinged flap.
A
To open, pull flap from the top edge forward.
A Hinged flap
12
5728 417 v1.0
Page 13
Overview of Controls and Indicators (continued)
Boiler sequence
1-23-4
Inform Yourself
Emissions test switch (see pg. 14)
Heating circuit selector buttons (pg.14)
Display window
Normal room temperature (pg. 19)
Heating programs (pg. 17)
Control on/off switch (pg. 15)
Fuse F1
Energy saving mode (pg. 23)
Boiler sequence
1-23-4
Party mode (pg. 23)
Hinged cover of programming unit
Operating status indicator (green)
Fault indicator (red)
Time program for central heating (pg. 19)
Time program for domestic hot water heating (pg. 24)
Other symbols (pg. 14)
Time program for DHW recirculation pump (pg. 24)
Holiday program (pg. 22)
Information
Confirmation
Factory default settings
Setting buttons
5728 417 v1.0
Vitotronic 300-K, MW2S
Domestic hot water temperature (pg. 24) Reduced room temperature (pg. 20)
Time/date
Heating curve shift (pg. 31)
Heating curve slope (pg. 31)
Hinged cover of propgramming unit
13
Page 14
Inform Yourself
Overview of Controls and Indicators (continued)
Boiler sequence
1-23-4
Adjustment of the display window contrast
Open the hinged cover on the programming unit, and press and, at the same time, adjust the contrast with the or button.
factory default settings
Press this button to reset all altered values to their factory default settings. Please note that all altered values are reset to the factory default settings.
Flashing data
Data flashing in the display window means that new settings can be entered.
Basic display
The basic display of the Vitotronic 300-K, MW2S shows the boiler sequence. The display reverts to showing the boiler sequence after each setting is made on the control unit.
Other display symbols
(These are not displayed continuously, but appear according to system type and operating status)
e Risk of frost s Central heating with normal
room temperature
m Central heating with reduced
room temperature
ep sp mp Heating circuit pump ON V Mixing valve open v Mixing valve closed w DHW heating enabled wp DHW pump ON, DHW heating
enabled
+p DHW heating via solar heating
system
A Burner ON u Time adjustment display S Emissions test ON U Fault indicator
Select the Heating Circuit - Before Every Setting and Scanning Operation
Your building may be heated by several independent heating circuits (eg. underfloor heating circuits or radiator circuits). These are selected at the control unit using keys , or3. The fields adjacent to these keys have been individually labelled by your heating contractor. Heating system with a single heating circuit:
One of the keys or and one of the keys rw, w or 9 are illuminated, and you can start the adjustment immediately.
Heating system with two or three heating circuit:
Choose the required heating circuit before every adjustment and scan.
The heating circuits are individually labelled by your heating contractor.
Vitocontrol-S WB2B
Press The following keys will be illuminated:
Key , orKey rw, w or 9Key g or û (if enabled)
Note:
If you make no adjustments, the key illumination will extinguish after a short time.
, or3.
3
14
5728 417 v1.0
Page 15
Starting the Heating System
Vitotronic 100, HC1
Start-up / Shutdown
1. Check the heating system pressure at
the pressure gauge A. If the system pressure is below 12 psi / 0.8 bar the system pressure is too low.
2. For room air dependent operation:
Check whether the ventilation apertures in the boiler room are open and unobstructed.
Note: For room air dependent operation: This boiler requires fresh air for safe operation. The boiler must be vented and supplied with air and exhaust vents.
3. Open the gas shut-off valve B.
4. Switch ON the power supply, (eg. at
the breaker or electrical disconnect switch. Energize power / pump module).
Vitotronic 300-K, MW2S
5. Switch ON / OFF switch “8C ON
on all control units. The green indicator (ON indicator) illuminates on every control unit. After a short while, the standard display appears in the display window of every control unit. Your heating system and, if installed, your remote control units (if installed) are now ready for use.
6. On each Vitotronic 100, “Htg. +
DHW” must be selected, otherwise the Vitotronic 300-K, MW2S cannot use the respective boiler to generate heat.
Check:
rw must be illuminated, otherwise press rw.
5728 417 v1.0
15
Page 16
Start-up / Shutdown
Shutting Down the Heating System
If you do not need to use your heating system temporarily, i.e. during a summer holiday, switch all heating circuits of the Vitotronic 300-K, MW2S to “Standby mode” 9 (see page 17). If you want to shut down only one boiler of your heating system, switch the relevant Vitotronic 100 to “Standby mode” 9 (see page 17).
Note:
The circulation pumps are briefly started every 24 hours to prevent them from seizing up.
Switch your heating system OFF if you do not need to use it. We recommend you contact your local heating contractor before and after you shut down your heating system for longer periods. Where necessary, your contractor can take certain steps, eg. protecting the system against frost.
Vitotronic 300-K, MW2S
1. Switch ON / OFF switch “8” (see
page 11 and 13) OFF on all control units. The green indicator (ON indicator) extinguishes on every control unit.
2. Close the gas shut-off valve.
3. Switch the main ON / OFF switch on the Vitotronic 300-K, MW2S to OFF.
Note:
Frost protection is no longer enabled. All control unit settings are retained.
16
5728 417 v1.0
Page 17
Starting a Heating Circuit and DHW Heating
Start-up / Shutdown
You want to heat your rooms and have DHW available.
Press the following keys:
1. / /3for the required heating circuit.
2.
for “Htg. + DHW”.
Stopping DHW Heating and the Heating Circuit
You do not want to heat any rooms or have DHW available.
Press the following keys:
/ /3for the required heating
1. circuit.
2.9for “Standby mode”.
Central heating will be provided with
normal or reduced room temperature (frost protection) according to the set time program. Standard setting: From 06:00 to 22:00 hrs. normal room temperature; otherwise reduced room temperature.
DHW heating (if DHW tank is
installed) is enabled and the DHW recirculation pump (if installed) is ON according to the selected time program. Standard setting: From 05:30 to 22:00 hrs. DHW is boosted to the set temperature, and the DHW recirculation pump is switched ON.
The boiler and the DHW tank are
protected against frost.
Central heating is disabled for the
selected heating circuit.
No DHW heating.The boiler and DHW tank are
protected against frost.
Note:
The recirculation pumps are started every 24 hours to prevent them from seizing up.
5728 417 v1.0
17
Page 18
Start-up / Shutdown
Starting DHW Heating Only
Stopping DHW Heating
You do not want to heat any rooms, but you want to make DHW available.
Press the following keys:
1. / /3for the required heating circuit.
2.
You want to heat your rooms, but do not want to make DHW available.
Press the following keys:
1.
2. for “Htg. + DHW”.
3. Delete the time phases for DHW
for “Htg. + DHW”.
/ /3for the required heating
circuit.
heating (see page 27). or Set the DHW temperature to 10°C / 50°F (see page 24).
Central heating is disabled for that
heating circuit.
DHW heating (if DHW tank is
installed) is enabled and the DHW recirculation pump (if installed) is ON according to the selected time program. Standard setting: From 05:30 to 22:00 hrs. DHW is boosted to the set temperature, and the DHW recirculation pump is switched ON.
The boiler and the DHW tank are
protected against frost.
Note:
The heating circuit pumps are briefly started automatically every 24 hours to prevent them from seizing up.
Central heating will be implemented
with normal or reduced room temperature (frost protection) according to the set time program. Standard setting: From 06:00 to 22:00 hrs. normal room temperature; otherwise reduced room temperature.
No DHW heating.The boiler and the DHW tank are
protected against frost.
Note:
The DHW primary pump is briefly started automatically every 24 hours to prevent it from seizing up.
18
5728 417 v1.0
Page 19
Setting a Permanent Room Temperature
Observe the following points if your heating circuit should provide central heating:
Adjusting the Room Temperature
1. For the respective heating circuit , or3, select “Htg. + DHW”
rw. Check: Press illuminate, otherwise press rw.
2. For each respective heating circuit
temperature (day temperature) with rotary selector “ts” (see page 19) and adjust the reduced room temperature (night temperature) with tm (see page 20).
, or3; rw must
, or3, select the normal room
3. The timing of when the heating circuit delivers central heating with normal or reduced room temperature depends on the settings of the time program (four possible time phases) for each respective day.
If no time phases are selected, central
heating will be enabled for the whole day at reduced room temperature.
If one or several time phases are
selected, central heating with normal room temperature will be active for those times. Check:
Press , or3. Press and hold down ur +
simultaneously; a time slot graphic shows the selected time phases.
For changing the time program, see page 20.
Selecting the normal room temperature
1. Press , or3; for the required
5728 417 v1.0
heating circuit.
2. Select the required temperature for the “Normal room temp.” with rotary selector “ts”.
Normal room temp.
19
Page 20
Adjusting the Room Temperature
Setting a Permanent Room Temperature (continued)
Selecting the reduced room temperature
Press the following:
1. / /3for the required heating circuit.
2. tm for “Red. room temp.”; the
current temperature flashes.
Note
When setting the reduced room temperature to 3°C / 37°F, “Frost
protection” will be displayed.
13. / for the required temperature.
14.
to confirm; the temperature no longer flashes and is saved.
Setting time programs (switching times)
For central heating, up to four changes per day between normal and reduced room
temperatue can be programmed (four time phases).
At the factory, time phase 1 is set for every day from 06:00 to 22:00 hrs., i.e.
during that time, all rooms are heated to the normal room temperature.
You can set identical time programs for every day or individual programs for each
day of the week. When setting time programs, bear in mind that your heating system requires some time to heat the rooms to the required temperature.
For a sequence of steps to delete a time phase, see page 21.
Press the following keys:
1. Press heating circuit.
2. ur for “Htg. time program”.
Note
If you want to terminate the time programming early, press ur again and confirm with .
13. / until “1-7” is displayed, if
/ /3; for the required
you want to set up the same time phases for every day
or
14.
/ until “Mo”, “Tu” etc. is
displayed, if you want to set up different time phases for the day displayed
Note
If different time phases are set for individual days and you want to return to identical time phases for every day, press when “1-7” is displayed. All time phases are returned to their original condition.
15. to confirm; “Htg. timer 1” will
be displayed.
Note
Press phase.
if you want to skip a time
5728 417 v1.0
20
Page 21
Setting a Permanent Room Temperature (continued)
Selecting the reduced room temperature (continued)
16. to confirm; “Htg. cycle 1 On”
will then be displayed.
/ for the heating phase starting
17.
point.
18. to confirm; “Htg. cycle 1 Off”
will then be displayed.
19. / for the heating phase end
point.
110. to confirm; “Htg. cycle 2 On”
will then be displayed.
11. Proceed for adjusting the start and end of heating phases 2 to 4 as described under steps 7 to 10.
Adjusting the Room Temperature
Press the following keys if you want to delete a time phase:
1. / /3for the required heating
circuit.
2.ur for “Htg. time program”.
until the required “Htg. cycle
3.
Off” is displayed.
4. until “--:--” is displayed for the
end time.
5. to confirm, until the standard
display (boiler sequence) is displayed.
5728 417 v1.0
21
Page 22
Adjusting the Room Temperature
Changing the Room Temperature for a Few Days
The following energy saving options are available for times when you are not at home:
You can switch central heating OFF completely (see “Switching OFF the heating
circuit and DHW heating” on page 17)
or
You can set central heating to minimum energy consumption (eg. to prevent your
houseplants from being damaged by frost). For this, select the “Holiday program” j.
- When “Htg. + DHW” rw is selected, all heating circuits are heated during the
holiday program with the selected reduced room temperature (see page 20), but there will be no DHW heating.
- When “DHW only” w has been selected, the holiday program for all heating
circuits will only deliver frost protection for the DHW tank.
Setting a holiday program
The holiday program starts at 00:00 hrs. following the day of your departure and ends at 00:00 hrs. on the day of your return, i.e. the permanently set time program is enabled on the day of departure and the day of return.
Note
The control unit is set up so that the holiday program applies to all heating circuits. If you want to make changes, contact your local heating contractor.
Press the following keys:
1. j for “Holiday program”.
Note
Press j again if you want to terminate the setting of the holiday program early.
for “Departure date” (the
2. current date is displayed).
13. for the date of the required
departure day.
14. to confirm; “Return date” (a
date following that of the departure day) will be displayed.
15. for the date of the required
return day.
16.Press to confirm.
7. The room temperature during the holiday program is the selected reduced room temperature. If you want to change that temperature:
Press ttttmmmm. Select the required value with
/ .
Press to confirm; the
temperature no longer flashes and is now saved.
Note
This change generally applies to the reduced room temperature and must be modified again, if required, after the holiday program ends.
Terminating the holiday program
The holiday program terminates
automatically on the day of return.
Press j again, if you want to
terminate the holiday program early and confirm “Delete? Yes” with
.
22
5728 417 v1.0
Page 23
Adjusting the Room Temperature
Changing the Room Temperature for a Few Hours Only
The following functions enable you to change the room temperature for a few hours, without permanently altering your control settings.
To save energy, you can reduce the normal room temperature with “Energy saving
mode” ûûûû .
You want to heat spontaneously with the normal room temperature and make
DHW available. For this, set to “Party mode” g .
Setting energy saving mode
In economy mode, the normal room temperature will be reduced automatically.
Press the following keys:
Setting party mode
1. / /3for the required heating circuit.
12. ûûûû for “Energy saving mode”.
Central heating will be enabled at any temperature you select (party temperature).The DHW will be boosted to the set temperature.The DHW recirculation pump is switched ON.
Press the following keys:
1. / /3for the required heating circuit.
12. g for “Party mode”; the party
temperature flashes.
13. / for the required temperature,
if you want to change the room temperature.
Terminating the economy mode
The economy mode ends
automatically with the next changeover to central heating with reduced room temperature.
If you want to prematurely terminate
economy mode, press , , or and ûûûû; the key illumination extinguishes.
14. to confirm; the temperature
no longer flashes and is saved.
Terminating party mode
Party mode ends automatically with
the next changeover to central heating with normal room temperature, but no later than after 8 hours.
If you want to prematurely terminate
party mode, press , , or3and g; the key illumination extinguishes.
3
5728 417 v1.0
23
Page 24
Selecting DHW Heating
Selecting Constant DHW Heating
Note
The control unit is set up so that the setting for DHW heating applies to all heating circuits. If you want to make changes, contact your local heating contractor.
Setting the DHW temperature
Observe the following points if you want to enable DHW heating:
1. For the respective heating circuit or3, select “Htg. + DHW” rrrrwwww
or “DHW only” wwww. Check: Press , or3; rrrrwwww or wwww must be illuminated, otherwise press rrrrwwww or wwww.
Note
You can select the required DHW temperature (see page 28).
,
7. When DHW heating with the selected temperature is enabled for the heating circuit and when the DHW recirculation pump (if installed) runs, depends on the settings of both programs uw or up (each with four possible time phases) for the respective day. Check:
Press , or3. Press and hold down uw + or
up+ simultaneously; the set time phases will then be displayed on a time slot graphic.
For changing the time program, see page 25.
Press the following keys:
1. tw for “DHW temp. setpt.”; the
current temperature will flash.
2. /for the required temperature.
3. to confirm; the temperature no longer flashes and is saved.
5728 417 v1.0
24
Page 25
Selecting Constant DHW Heating (continued)
Setting time programs (switching times)
Heating system without DHW recirculation pump
Note
The control unit is set up so that the setting for DHW heating applies to all heating circuits. If you want to make changes, contact your local heating contractor.
DHW heating can be enabled / disabled up to four times per day (four time
phases).
Automatic mode (factory default setting)
DHW heating is enabled in parallel to the central heating program of the first available heating circuit, but starts 30 min. earlier (from 05:30 to 22:00 hrs.).
Individual time programs
You can set up individual time programs if you do not wish to operate in automatic mode. You can select identical time programs for every day or individual programs for each day.
When setting time programs, bear in mind that your heating system requires some time to heat the DHW tank to the required temperature. For time programming steps, see pages 26. For a sequence of steps to delete a time phase, see page 27.
Selecting DHW Heating
Heating system with DHW recirculation pump
Note
The control unit is set up so that the setting for DHW heating applies to all heating circuits. If you want to make changes, contact your local heating contractor.
The DHW recirculation pump transports hot water through a circuit between the
DHW tank and the draw-off points to deliver DHW to the taps as quickly as possible.
DHW heating and the DHW recirculation pump can be enabled / disabled up to four
times per day (four time phases).
Automatic mode (factory default setting)
The DHW heating and the DHW recirculation pump are enabled in parallel to the central heating time program of the first available heating circuit, however commences 30 min. earlier (from 05:30 to 22:00 hrs.).
Individual time programs
You can set up individual time programs if you do not wish to operate in automatic mode. You can select identical time programs for every day or individual programs for each day.
Also, enabling the DHW recirculation pump is only sensible for those times when
DHW is actually drawn.
The following explains the setting up of a time program using DHW heating uw by way of an example. Proceed the same for the DHW recirculation pump up time program.
When setting time programs, bear in mind that your heating system requires some time to heat the DHW tank to the required temperature. For time programming steps,see pages 26. For a sequence of steps to delete a time phase, see page 27.
5728 417 v1.0
25
Page 26
Selecting DHW Heating
Selecting Constant DHW Heating (continued)
Setting automatic mode (if required)
Setting automatic mode (if required)
In economy mode, the normal room temperature will be reduced automatically.
Press the following keys:
1.
2. uw for “DHW time program”.
Setting up an individual time program
Setting up an individual time program
1. / /3for the required heating
2. uw for “DHW time program”.
3. /for “Individual?”, if “Individual?
4.
5. /until “1-7” is displayed, if you
/ /3for the required heating
circuit.
circuit.
Note
If you want to terminate the time program early, press uw again and confirm with .
is not yet displayed.
to confirm.
want to set up the same time phase for every day
3. /for “Automatic?”, If “Automatic? is not yet displayed.
4. to confirm.
Note
If different time phases are set for individual days and you want to return to identical time phases for every day, press displayed. All time phases are returned to their original delivered condition.
7. to confirm; “DHW timer 1” will then be displayed.
Note:
Press if you want to skip a time phase.
when “1-7” is
26
or
6. /until “Mo”, “Tu” etc. is displayed, if you want to set different time phases for the displayed day.
8. to confirm; “DHW timer 1 On” will then be displayed.
9. /for DHW phase starting point.
10. to confirm; “DHW cycle 1 Off” will be displayed.
11./for DHW phase end point.
12.
13. Proceed for setting the start and
to confirm; “DHW cycle 2 On” will then be displayed.
end of DHW phases 2 to 4 as described in steps 9 to 12.
5728 417 v1.0
Page 27
Selecting Constant DHW Heating (continued)
Press the following keys if you want to delete a time phase:
Selecting DHW Heating
1. / /3for the required heating circuit.
12. uw for “DHW time program”.
3.
until the required “DHW cycle
Off” is displayed.
Selecting DHW Heating for a Few Hours Only
The following functions enable you to heat DHW for several hours, without permanently altering your control settings. For this, select “Party mode g. During party mode, the DHW recirculation pump is active and central heating operates with the party temperature. Set the party temperature to 4ºC / 39.2ºF, if you require no central heating (e.g. in summer).
Press the following keys:
1. / /3for the required heating circuit.
4. until “--:--” is displayed for the end time.
5. to confirm, until the boiler water temperature is displayed.
12. g f
13. / for the required temperature,
or “Party mode”; the party
temperature flashes.
if you want to change the room temperature.
14. to confirm; the temperature
no longer flashes and is saved.
Ending party mode
Party mode ends automatically
with the next changeover to central heating with normal room temperature, but no later than after 8 hours.
If you want to prematurely
terminate party mode, press , or
3
and g; the key illumination
extinguishes.
5728 417 v1.0
27
Page 28
Selecting DHW Heating Only Once
The following function enables you to heat DHW once, without permanently altering your settings. For this, select “Party mode” g.
Preconditions:
Not in “Standby mode” 9 and not in the “Holiday program” jThe DHW temperature must be below the set value (see page 24)
/ /3for the required heating
1. circuit.
12. g for “Party mode”.
3. to confirm; DHW heating begins.
4. After approximately 10 seconds,
press g again; the key illumination extinguishes.
Vitotronic 100, HC1
It is possible to simultaneously reset all changed values for the heating circuit to their factory default settings. For this, press D.
Vitotronic 300-K, MW2S
It is possible to simultaneously reset all changed values for the heating circuit to their factory default settings. For this, press D.
/ /3for the required heating
1. circuit.
2. D for “factory default setting”.
3. to confirm.
28
5728 417 v1.0
Page 29
Setting Time and Date
Further Adjustments
Date and time are factory-set and may be changed manually.
Setting the display language
Press the following keys:
1. for “Time”.
2. /for the required time.
Press the following keys:
1. / /3for the required heating circuit.
2. “Participant No.” is displayed.
3. to confirm; ”Date” is displayed.
4. /for the required date.
5. to confirm.
3. for the required language.
Adjusting the display contrast
4. to confirm.
Open the programming unit flap. Press
and simultaneously adjust the
contrast with or .
5728 417 v1.0
29
Page 30
Further Adjustments
Selecting the Boiler Sequence
Actual boiler sequence (standard display)
Your contractor has allocated a boiler number to each boiler.
The standard display shows the current boiler sequence:
H The enabled boilers are indicated in
H The boilers listed after the first
H The boilers behind the second hyphen
Controlled boiler sequence
front of the first hyphen.
hyphen are available for heating, but are not currently required.
are blocked (not available to the Vitotronic 300-K, MW2S for heating purposes, eg. because they are in “Standby mode”).
When your heating system is commissioned, your contractor selects the boiler sequence criteria (eg. permanent boiler lead, last boiler). You can modify the controlled boiler sequence within the framework of these criteria.
Note
It may be impossible to select a different controlled boiler sequence. The controlled boiler sequence does not have to correspond to the actual boiler sequence, as that is subject to various factors (eg. faults) and settings made by your contractor (eg. temperature-dependent blocking).
Press the following keys:
1. g/û simultaneously for
approximately 2 seconds until the controlled boiler sequence appears.
2. /for the required controlled boiler sequence.
3. to confirm.
30
5728 417 v1.0
Page 31
Changing the Heating Pattern
You can alter the heating characteristics if the room temperature does not meet your requirements for some time. You alter the characteristics by changing the slope and shift of the heating curve. For more information regarding the heating curve, see page 33. Observe the modified heating characteristics over several days (if possible, await a major change in the weather) before making further adjustments. Make short-term room temperature adjustment using rotary selector ts (see page
19) or tm (see page 20).
Changing the slope and shift
For assistance, use the table on page 32.
1. / /3for the required heating
2. n for “Slope”.
Further Adjustments
circuit.
or
3.
4. /for the selected value.
5. to confirm.
for “Shift”.
Shift
Note
Setting the heating curve slope or shift too high or too low will not result in damage to your heating system.
5728 417 v1.0
31
Page 32
Further Adjustments
Changing the Heating Pattern (continued)
Change heating pattern if ... Action Example
... not enough heat is generated in
the cold season
Adjust the slope of the heating curve
upwards by one increment
Slope
... too much heat is generated in the
cold season
... not enough heat is generated at
transitionary times of the year and
in the cold season
... too much heat is generated at
transitionary times of the year and in the cold season
....not enough heat is generated at
transitionary times of the year but adequate in the cold season
Adjust the slope of the heating curve
downwards by one increment
Adjust the shift of the heating curve to a higher value (e.g. +3 K)
Adjust the shift of the heating curve to a lower value (e.g. -3 K)
Adjust the slope of the heating curve downwards by one increment, and the shift to a higher value (e.g. +3 K)
Slope
Shift
Shift
Slope
... the boiler water temperature is too
high at transitionary times of the year, but adequate in the cold
season
32
Adjust the slope of the heating curve upwards by one increment, and the shift to a lower value (e.g. -3 K)
Shift
Slope
Shift
5728 417 v1.0
Page 33
Modifying the Boiler Heating Characteristics
The heating curves demonstrates the relationship between the outdoor temperature and the boiler water or common supply temperature. Put simply: the lower the outdoor temperature, the higher the boiler water or supply temperature. The illustrated heating curves apply subject to the following settings: Heating curve shift = 0
Different shift settings offset the curves parallel in a vertical direction.
Normal room temperature = approx. 20°C / 68°F.
In the factory default settings, the slope is set to 1.4; the shift to 0.
Further Adjustments
Slope
C
The slope of the heating curve is
normally within the range marked
A for underfloor heating systems,B for modulating heating systems,C for heating systems with boiler
water temperatures over 75°C / 167 °F.
B
A
Examples
Well insulated house in protected
position (radiator heating): Slope = 1.2
House in exposed position or
with old heating system (radiator heating): Slope = 1.6
5728 417 v1.0
33
Page 34
Scanning Options
Scanning Temperatures and Operating Status Information
Subject to the connected components and settings you have made, you can scan the current temperatures and operating conditions.
Press the following keys:
1. for “boiler water
temperature”.
Display indication
0__01 3__65.
P
003572 h
PPP
030529
PPPP
030585
Description Notes
LON participant number ––
Boiler water temperature ––
°C
Hours run, burner stage 1 Hours run are only approximate
Burner starts ––
Consumption Fuel consumption subject to
2. / for further scanning of the
list.
3.
values
appropriate settings having been made by the heating contractor
to end scanning.
34
5728 417 v1.0
Page 35
Scanning the Fault Display
Vitotronic 100, HC1
A
B
C
Scanning Options
D
A Fault display (red) B Fault number
If your heating system has developed a fault, it will be displayed and indicated by the flashing red fault indicator A. You can check the fault code on the display by scanning; then notify your local heating contractor accordingly. This allows your heating contractor to better prepare for the service call and may save additional travelling costs.
Press the following keys:
1. /to display further faults, if several faults exist.
2.
Note
The fault message will be displayed again the following day, if the fault has not been rectified. The red fault indicator flashes until the fault has been rectified.
to acknowledge the fault.
C Fault code D Fault symbol
To recall fault codes press the following keys:
1.
2. /to display further faults, if
approximately 3 seconds.
several faults exist.
1
5728 417 v1.0
35
Page 36
Scanning Options
Scanning Temperatures
Subject to the connected components and settings you have made, you can scan the current temperatures and operating conditions.
To exit the setting mode at any time, press the following keys:
1. / /3for the required heating circuit.
2.
for “Participant No.”
3./ for further scanning of the list.
4.
to end scanning.
Order in which temperatures and operating conditions may be scanned:
Participant no.Holiday program - if one has entered
Departure date Return date
Current Outdoor temperatureBoiler sequenceCommon supply temperature - if a
sensor is connected
Boiler water temperature 1-4 (for each
boiler)
Flue gas temperature - if a flue gas
sensor is connected
Sensor aJA - if a sensor is
connected
Sensor aJB - if a sensor is
connected
DHW temperature - DHW temperatureDHW temperature 1 - DHW
temperature, if two tank temperature sensors are connected
DHW temperature 2 - DHW
temperature, if two tank temperature sensors are connected
Supply temperature - for heating
circuit with mixing valve
Normal room temperature - actual
value, if a remote control unit is connected
Solar DHW temperature - DHW
temperature with solar operation
Collector temperature - in conjunction
with a solar heating system
Solar energy - display in kWh, in
conjunction with a solar heating system
TimeDateBurner ON / OFFOutput 20 ON / OFFOutput 29 ON / OFFOutput 52 OPEN / CLOSE
0 Close 1 to 99 (%) 100 Open
DHW tank pump ON / OFFC pump ON / OFF - DHW recirculation
pump
Heating pump ON / OFF - heating
circuit pump
Mixing valve OPEN / CLOSE
0 Close 1 to 99 (%) 100 Open
Solar pump ON / OFF - in conjunction
with a solar heating system
Solar pump ...h - solar circuit pump
hours run, in conjunction with a solar heating system
Language
36
5728 417 v1.0
Page 37
Scanning Temperatures (continued)
Scanning time programs
Press the following keys:
1. circuit.
12. ur+ for heating and DHW time
3. uw+ for DHW time program
4. up+ for DHW recirculation pump
Scanning Options
/ /3for the required heating
program
or
or
time program press and hold down simultaneously; a time slot graphic shows the selected time phases.
Scanning party or energy saving mode
5. For changing the time programs, see page 20 and 25.
Press keys , or3; the selected key and the key of the active program will be illuminated (see page 14).
5728 417 v1.0
37
Page 38
Scanning Options
Scanning the Fault Display
Vitotronic 300-K, MW2S
Fault
DBG-
2
d5
A
A Fault display (red) B Fault number
B CD
C Fault code D Fault symbol
If your heating system has developed a fault, it will be displayed and indicated by the flashing red fault indicator A. You can check the fault code on the display by scanning; then notify your local heating contractor accordingly. This allows your heating contractor to better prepare for the service call and may save additional travelling costs.
Press the following keys:
To recall fault codes press the following keys:
1. for troubleshooting.
1.
approximately 2 seconds.
2. /to display further faults, if several faults exist.
3.
to “Acknowledge” all fault messages.
4. /for “Yes” or “No”. With “Acknowledge? Yes” you confirm that you have noticed
2. /for the acknowledged fault.
Note
If the fault has not been rectified, the fault message will be redisplayed at 07:00 hrs. the following day. The red fault indicator flashes until the fault has been rectified.
the fault.
5. to confirm.
1
38
5728 417 v1.0
Page 39
Scanning Options
Selecting the Time Programs
Rooms are too cold
Cause Remedy
The heating system is switched OFF, ON indicator 8(green) OFF
Control unit or remote control incorrectly adjusted
Only when operating with DHW tank: DHW priority (wp is displayed)
No fuel With LPG:
Faults at the Vitotronic 100: Fault symbol ”U” is displayed and the red fault
indicator flashes (see page 38)
Fault at the Vitotronic 300-K, MW2S: ”Fault” is displayed and the red fault indicator
flashes (see page 38)
Burner fault: EEEE” is displayed by the corresponding Vitotronic
100, and the red fault indicator of the control unit flashes
Remote control fault Contact your local heating contractor
Low water Contact your local heating contractor
Faulty ventilation air or flue gas system Contact your local heating contractor
Mixing valve motor faulty Adjust the mixing valve manually and call your local heating contractor
Switch system ON / OFF switch 8” ON (see page 15)Switch ON the main power supply to all boilers and Vitotronic 300-K,
MW2S, if installed (outside the boiler room)
Check the fuse in the Vitotronic 300-K, MW2S (F1)
Check and correct settings, if required:Room temperature “Htg. + DHW” must be selected on all
Vitotronic 100
The heating circuit must be switched ONRoom temperature (see page 19)
Time (see page 29)Characteristics of the heating circuits at the Vitotronic 300-K, MW2S
(see page 31)
Wait until the DHW tank has been heated up (p disappears from the display)
Check the fuel stock and re-order, if required
With natural gas:
Open the gas shut-off valve or check with your gas supply utility, if required
Check the type of fault and notify your local heating contractor
Check the type of fault and notify your local heating contractor
Press burner fault reset EEEE” - if that attempt to start also fails, contact your local heating contractor
5728 417 v1.0
39
Page 40
Scanning Options
Selecting the Time Programs (continued)
Rooms are too hot
Cause Remedy
Control unit control incorrectly adjusted Check and correct settings, if required:
The heating circuit must be switched ONRoom temperature (see page 19)Time (see page 29)Boiler heating characteristics (see page 31)
Faults at the Vitotronic 100: Fault symbol ”U” is displayed and the red fault
indicator flashes (see page 38)
Fault at the Vitotronic 300-K, MW2S: ”Fault” is displayed and the red fault indicator
flashes (see page 38)
Emissions test switch “S” is set to “h Set emissions test switch “S” to “a
There is no hot water
Check the type of fault (see page 38) and notify your local heating con­tractor
Check the type of fault (see page 38) and notify your local heating con­tractor
Cause Remedy
The heating system is switched OFF, ON indicator 8(green) is OFF
Control unit control incorrectly adjusted Check and correct settings, if required:
No fuel See page 39
Faults at the Vitotronic 100: Fault symbol ”U” is displayed and the red fault
indicator flashes (see page 38)
Fault at the Vitotronic 300-K, MW2S: ”Fault” is displayed and the red fault indicator
flashes (see page 38)
Burner fault: EEEE” is displayed by the corresponding Vitotronic
100, and the red fault indicator of the control unit flashes
Remote control fault Contact your local heating contractor
Low water Contact your local heating contractor
Faulty ventilation air or flue gas system Contact your local heating contractor
DHW primary pump is faulty Contact your local heating contractor
Switch system ON / OFF switch 8ON (see page 15).Switch ON the main power supply to all boilers and Vitotronic 300-K,
MW2S, (outside the boiler room)
Check the fuse in the Vitotronic 300-K, MW2S (F1)
The heating circuit must be switched ON (see page 15)Room temperature (see page 19)Time (see page 29)Boiler heating characteristics Vitotronic 300-K, MW2S (see page 31)
Check the type of fault and notify your local heating contractor
Check the type of fault and notify your local heating contractor
Press burner fault reset EEEE” - if that attempt to start also fails, contact your local heating contractor
40
5728 417 v1.0
Page 41
Scanning Options
Selecting the Time Programs (continued)
The DHW is too hot
Cause Remedy
Control unit control incorrectly adjusted Check and correct the DHW temperature, if required (see page 24)
Sensor fault Contact your local heating contractor
Emissions test switch “S” is set to “h Set emissions test switch “S” to “a
”OFF” is displayed by the Vitotronic 100
Cause Remedy
Boiler is locked out of the cascade Ask your local heating contractor to reset your boiler
Fault symbol “UUUU” flashes in the display of the Vitotronic 100
Cause Remedy
Fault at the respective Vitotronic 100 Check the type of fault (see page 38) and notify your local heating
contractor
“Fault” flashes in the display of the Vitotronic 300-K, MW2S
Cause
Heating system fault Check the type of fault (see page 38) and notify your local heating
The service display is shown by the Vitotronic 100
Cause Remedy
The time for a service of the corresponding boiler has been reached. The following service displays may be shown:
035510 h (hours run)12 u (interval)
”Service” is displayed by the Vitotronic 300-K, MW2S
Remedy
contractor
Arrange a service with your local heating contractor
Note
A service display is not a fault. The boiler remains operational.
Cause Remedy
The time for a service of a boiler has been reached
5728 417 v1.0
Arrange a service with your local heating contractor
41
Page 42
Scanning Options
Selecting the Time Programs (continued)
“Remote control” is displayed by the Vitotronic 300-K, MW2S
Cause Remedy
A remote control is connected to the heating circuit
”External control” is displayed by the Vitotronic 300-K, MW2S
Cause Remedy
The heating program selected at the control unit was changed over by an external device
”Central control” is displayed by the Vitotronic 300-K, MW2S
Cause Remedy
The settings or the operating and holiday program will be adopted from that heating circuit, for which “Central control” has been selected
Make adjustments or carry out scanning at the remote control (see separate operating instructions)
No action required. The heating program changeover was manually selected
----
”Slab curing program” is displayed by the Vitotronic 300-K, MW2S
Cause
The slab curing function is enabled Wait until this function has terminated
“Without function” is displayed by the Vitotronic 300-K, MW2S
Cause Remedy
No function has been allocated to the key you pressed, or the function can only be adjusted at your remote control
Remedy
---
42
5728 417 v1.0
Page 43
Service Instructions for Your Heating System
Viessmann strongly recommends inspection/service of the boiler and the system by a licensed professional heating contractor once a year.
Before the heating season begins, the boiler with its burner(s) and direct vent system should be serviced by a qualified heating contractor. Service contracts may be established through gas suppliers or other licensed contractors in your area.
Regular inspection/service ensures trouble-free, energy-efficient and environmentally friendly heating activity of your heating system.
Service Instructions
Boiler
All boilers must be cleaned on a regular basis as debris build-up will result in increased flue gas temperature, and thus in increased energy consumption.
Domestic hot water storage tank
Inspection and (if necessary) cleaning of the tank must take place within 2 years of initial start-up and as required thereafter. Cleaning of the inside surfaces of the DHW storage tank, including DHW connections, may only be performed by a licensed professional heating contractor.
Vitocell 100: Viessmann recommends an annual inspection, and replacement if required, of the consumable anode by a licensed professional heating contractor. The inspection can be carried out during regular operation of the heating system; shut-down is not required. The heating contractor measures the protective current with an anode tester.
Notes on operation:
H Ensure boiler room and boiler
are clean.
H Regularly check heating system
pressure on the pressure gage: If the needle of pressure gage is below 12 psig, the system pressure is too low; in this case, please contact your heating contractor.
IMPORTANT
If the domestic cold water supply to the hot water storage tank has a water treatment device (water softener) installed, ensure its proper working condition is checked regularly by your heating contractor.
The same applies if a dirt trap or a water filter is installed in the domestic cold water supply. Any of these devices installed in the domestic cold water supply must be flushed out and serviced on a regular basis.
5728 417 v1.0
Drinking water filter (if installed) For hygienic reasons H replace filter element every
6 months on filters which cannot be flushed back, and perform a visual inspection every 2 months,
H flush back reversible flow filters
every 2 months.
Safety valve (DHW tank)
The safety valve function should be checked every six months by venting, either by the system user or the local heating contractor. The valve seat may become contaminated.
Please follow manufacturer’s
instructions.
Please follow manufacturer’s instructions.
43
Page 44
Additional Information
Lighting and Operating Instructions
FOR YOUR SAFETY READ BEFORE OPERATING
W A R N I N G: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped
with an ignition device which automatically lights the burner. Do not
B. BEFORE OPERATING smell all around the appliance
area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
try to light the burner by hand.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. Set thermostat or other operating control to lowest setting.
3. Turn off all electric power to the appliance.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
5. Close main gas shut-off valve.
6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow ”B” in the safety information above on this label. If you don’t smell gas, go to the next step.
4. This appliance is equipped with an ignition device which automatically lights the burner. Do not light the burner by hand.
try to
Manual gas shutoff
Closed
Open
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat or other operating control to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Close main gas shut-off valve.
7. Open main gas shut-off valve.
8. Turn on all electric power to the appliance.
9. Set thermostat or other operating control to desired setting.
10. If the appliance will not operate, follow the instructions ”To Turn Off Gas To Appliance” and call your service technician or gas supplier.
44
5728 417 v1.0
Page 45
45
5728 417 v1.0
Page 46
46
5728 417 v1.0
Page 47
47
5728 417 v1.0
Page 48
Quick Reference
T
e
c
h
n
i
c
a
l
i
n
f
o
r
m
a
t
i
o
n
s
u
b
j
e
c
t
t
o
c
h
a
n
g
e
w
i
t
h
o
u
t
n
o
t
i
c
e
.
°C °F
-40 -40
-35 -31
-25 -13
-20 -4
-18 0
-16 +3
-14 +7
-12 +10
-10 +14
-9 +16
-8 +18
-7 +19
-6 +21
-5 +23
-4 +25
-3 +27
-2 +28
-1 +30 0 +32
+1 +34 +2 +36 +3 +37 +4 +39 +5 +41 +6 +43 +7 +45 +8 +46
+9 +48 +10 +50 +12 +54 +14 +57 +16 +61 +18 +64 +20 +68 +25 +77 +30 +86 +35 +95 +40 +104 +50 +122 +60 +140 +70 +158 +80 +176 +90 +194
+100 +212 +110 +230
Printed on environmentally friendly
(recycled and recyclable) paper.
Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island D 02886 D USA Tel. (401) 732-0667 D Fax (401) 732-0590 www.viessmann-us.com D info@viessmann-us.com
48
Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario D N2V 2G5 D Canada Tel. (519) 885-6300 D Fax (519) 885-0887 www.viessmann.ca D info@viessmann.ca
5728 417 v1.0
Loading...