Weather-compensated boiler and heating circuit control unit
in single boiler or multi boiler systems
VITOTRONIC 300, GW6B
Certified as a component
part for Viessmann boilers
5513 463 - 06 03/2015
Product may not be exactly as shown
IMPORTANT
Read and save these instructions
for future reference.
Please file in Service Binder
Page 2
General
Vitotronic 300, GW6B Installation and Service
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with
the instructions listed below and details printed in this manual can cause product/property damage, severe personal
injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information
found in manual subsections).
Product documentationRead all applicable documentation before commencing
installation. Store documentation near boiler in a
readily accessible location for reference in the future
by service personnel.
For a listing of applicable literature,
please see section entitled “Important
Regulatory and Safety Requirements”.
Licensed professional heating contractor
The installation, adjustment, service and maintenance
of this equipment must be performed by a licensed
professional heating contractor.
Please see section entitled
“Important Regulatory and Installation
Requirements”.
Operating and Service Documentation
It is recommended that all product documentation such
as parts lists, operating and service instructions be
handed over to the system user for storage.
Documentation is to be stored near boiler in a readily
accessible location for reference by service personnel.
WARNING
Installers must follow local regulations with respect to
installation of carbon monoxide detectors. Follow the
Viessmann maintenance schedule of the boiler contained
in this manual.
Advice to owner
Once the installation work is complete, the heating
contractor must familiarize the system operator/
ultimate owner with all equipment, as well as safety
precautions/requirements, shutdown procedure, and
the need for professional service annually before the
heating season begin.
Warranty
Information contained in this and
related product documentation must
be read and followed. Failure to do
so renders the warranty null and void.
Product Information
Vitotronic 300, Type GW6B
For installation in or mounting on Viessmann boilers only.
Applicable to the following control units
Order No. Z013557
Serial No. 7542124
2
5513 463 - 06
Page 3
Vitotronic 300, GW6B Installation and Service
General
Table of Contents
Page
Safety, Installation and Warranty Requirements..............2
Blocking the Boiler Externally/Adding to the Boiler
Sequence
External Blocking via Switching Contact
External Demand via Switching Contact
External Demand via 0 – 10V Input
External “Mixing Valve Closed”/”Mixing Valve Open”
External Operating Program Changeover
Power Supply……………….....................................…45
Take note of all symbols and notations intended to draw attention to potential hazards or important product
information. These include “WARNING”, “CAUTION”, and “IMPORTANT”. See below.
Warnings draw your attention to the presence of
WARNING
Indicates an imminently hazardous situation which,
if not avoided, could result in loss of life, serious injury
or substantial product/property damage.
CAUTION
Indicates an imminently hazardous situation which,
if not avoided, may result in minor injury or product/
property damage.
IMPORTANT
potential hazards or important product information.
Cautions draw your attention to the presence of
potential hazards or important product information.
Helpful hints for installation, operation or maintenance
which pertain to the product.
Safety
This symbol indicates that additional, pertinent
information is to be found.
This symbol indicates that other instructions must
be referenced.
5513 463 - 06
5
Page 6
Safety
For your Safety
CAUTION
Follow these safety instructions closely to avoid the risk
of injury and damage to property.
H Operation
Before operating the boiler, make sure you fully
understand its method of operation. Your heating
contractor should always perform the initial start-up
and explain the system. Any warranty is null and void
if these instructions are not followed.
H Flue gas smell
- Deactivate heating equipment.
- Open windows and doors.
- Inform your heating contractor.
H Working on the equipment
All personnel working on the equipment or the heating
system must have the proper qualifications and hold
all necessary licenses. Ensure main power to
equipment, heating system, and all external controls
has been deactivated. Close main gas supply valve.
Take precautions in all instances to avoid accidental
activation of power during service work.
H Dangerous conditions
- Deactivate main power immediately.
- Close gas supply valve.
H Maintenance and cleaning
Regular inspection and service by a qualified heating
contractor is important to the performance of the boiler.
Neglected maintenance impacts on warranty; regular
inspection ensures clean, environmentally friendly and
efficient operation. We recommend a maintenance
contract with a qualified heating contractor.
H Technical documentation
- Installation Instruction and Service Instructions
- Operating Instructions and User’s Information Manual
Additional applicable literature:
- Accessory manuals
Vitotronic 300, GW6B Installation and Service
If you smell gas
H Don’t smoke! Don’t use naked flames or cause sparks
(e.g. by switching lights or electrical appliances on
and off)
H Open windows and doors
H Close the gas shut-off valve
H Inform your heating engineers/service contractors from
outside the building
H Observe the safety regulations of your gas supply
company (see gas meter) and those of your heating
engineers (see start-up or instruction report).
In emergencies
H Immediately switch off the power supply, e.g. at the
separate fuse or power supply disconnect switch
(unless there is a smell of gas).
H Close the shut-off valves in the oil pipes or close the
gas shut-off valve, whichever applicable.
H Use suitable extinguishers in the event of fire.
Installation of additional components
The installation of additional components which have not
been tested together with the boiler can adversely affect
the function and performance of the boiler.
Our warranty does not cover and we accept no liability
for damage attributable to the installation of such
components.
Boiler room conditions
H Do not use a room in which the air is polluted by
halogenated hydro-carbons (e.g. as contained in
aerosols, paints, solvents and cleaning agents)
H Do not use a room subject to high levels of dust
H Do not use a room subject to permanently high humidity
H The room should be frost-protected
H Max. ambient temperature 95°F (35°C).
H Provide good ventilation and do not close or obstruct
vents (if installed).
This symbol indicates a reference to other instructions
which must be observed.
6
5513 463 - 06
Page 7
Vitotronic 300, GW6B Installation and Service
Overview of System Example
Designations in the System Example
Preparing for Installation
This system example is merely a GENERIC LAYOUT
and must therefore be checked on site for completeness
and function.
The heating circuits must be regulated by an external
control unit.
Connect three-phase consumers via additional
contactors.
5513 463 - 06
7
Page 8
Preparing for Installation
System Examples
ID: 4800078_1407_01
Single boiler system
Vitotronic 300, GW6B Installation and Service
8
Note: This schematic is a general example without shutoff
valves or safety equipment. This does not replace
the need for local engineering.
5513 463 - 06
Page 9
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
Required Devices
ID: 4800078_1407_01
PositionEquipment
1
2
3
4
5
wT
wZ
rR
6
7
8
9
qP
qW
qE
qQ
qE
qZ
qR
qZ
qU
qT
qU
uU
wW
wR
eP
eQ
eW
eE
eR
eZ
eU
4
rQ
rW
rE
rR
5513 463 - 06
Boiler
Vitotronic 300 GW6B
Outdoor temperature sensor ATS
Boiler temperature sensor KTS (connection to burner control)
Neutralization system
Junction box
Burner base
Power switch
DHW
DHW tank temperature sensor STS delivered with Vitotronic 300
DHW pump UPSB
DHW re-circulation pump ZP
Heating circuit I
Heating circuit M2 (heating circuit I)
Mixing valve M2 (heating circuit I)
Strap-on temperature sensor
and
Mixing Valve Actuator M2 (heating circuit I)
Mixing valve adapter 24V
Heating circuit II
Heating circuit M3 (heating circuit II)
Mixing valve M3 (heating circuit II)
Strap-on temperature sensor
and
Mixing valve actuator M3 (heating circuit II)
Mixing valve adapter 24V
Accessories
Compiled fault output
Vitotrol 200A or Vitotrol 300A
Extension EA1:
1 analog input (0 to 10 V) - Specification of the boiler water temperature setpoint
3 digital inputs - Separated External switch the operating status for heating circuits 1 to 3 switchable
(with control for weather-compensated operation)
- External blocking with collective fault
- Error messages
- Brief operation DHW re-circulation pump (for weather-compensated control units)
1 switching output (floating changeover contact)- Control system pump to a substation
- Signal reduced mode for one heating circuit external hook
- External demand
- External blocking / mixer to close
- External heating program changeover / mixer on site
KM BUS distributor, with several KM BUS participants
KM BUS subscriber: - Extension EA1
- Vitotrol 200A, 300A
LON communication module to communicate with the following components:
General00:8Two heating circuits with mixing valve M2 (heating circuit 2) and
5513 463 - 06
M3 (circuit 3) DHW heating
11
Page 12
Preparing for Installation
System Examples (continued)
ID: 4800061_1407_01
Multi boiler system
Vitotronic 300, GW6B Installation and Service
12
Note: This schematic is a general example without shutoff
valves or safety equipment. This does not replace
the need for local engineering.
5513 463 - 06
Page 13
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
Required Devices
ID: 4800061_1407_01
PositionEquipment
1
2
3
4
5
6
8
9
rT
uW
uE
uZ
qP
qW
qQ
qE
qR
qT
rT
uR
uT
uO
qZ
qU
qI
qO
wP
wW
wE
wQ
wE
uU
wR
wZ
wU
wT
wU
uI
wI
eE
eR
wO
eR
eT
Boiler 1
Flue gas damper (for boiler I)
Isolation valve
Boiler temperature sensor KTS (connection to burner control)
Common supply temperature sensor
Outdoor temperature sensor ATS
Vitotronic 300 GW6B
Neutralization system
Power switch
Junction box
Burner base
Mixing valve adapter 24V
Boiler II
Isolation valve
Mixing valve adapter 24V
Boiler temperature sensor KTS (connection to burner control)
Vitotronic 300 GW6B
Neutralization system
Power switch
Junction box
Burner base
Flue gas damper (for boiler II)
DHW
DHW tank temperature sensor STS delivered with Vitotronic 300
DHW pump UPSB
DHW re-circulation pump ZP
Heating circuit I
Heating circuit pump M2 (heating circuit I)
Mixing valve M2 (heating circuit I)
Strap-on temperature sensor
and
Mixing valve actuator M2 (heating circuit I)
Mixing valve adapter 24V
Heating circuit II
Heating circuit pump M3 (heating circuit II)
Mixing valve M3 (heating circuit II)
Strap-on temperature sensor
and
Mixing valve actuator M3 (heating circuit II)
Mixing valve adapter 24V
Heating circuit III (low-temperature heating circuit)
Heating circuit pump M1 (heating circuit III)
Mixing valve M1 (heating circuit III)
Strap-on temperature sensor
and
Mixing valve actuator M1 (heating circuit III)
Vitotronic 200-H HK1B
and
LON communication module for Pos. 35
and
LON connecting cable
Preparing for Installation
5513 463 - 06
13
Page 14
Preparing for Installation
System Examples (continued)
Required Devices
ID: 4800061_1407_01
PositionEquipment
eZ
wI
wO
eR
wO
eR
eT
uP
eZ
eP
eQ
eE
rT
eO
rP
rQ
zI
zO
tP
tW
tE
zP
zQ
zW
zE
zE
zU
uP
eT
uQ
Outdoor temperature sensor ATS (ATS-value can be taken from Vitotronic 300 GW6B master and cascade
or
Heating circuit III (underfloor heating)
Supply temperature sensor M1 (circuit III) delivery Pos. 35
Mixing valve M1 (heating circuit III)
or
Strap-on temperature sensor
and
Mixing Valve Actuator M1 (heating circuit III)
Vitotronic 200-H HK1B
and
LON communication module for Pos. 35
and
LON connecting cable
Outdoor temperature sensor ATS (ATS-value can be taken from Vitotronic 300 GW6B master and cascade
Temperature monitor as Maximum temperature limiter for underfloor heating
Heating circuit pump M1 (primary)
Power switch on site / main disconnect
Accessories for boilers
Maximum pressure SDB
Minimum pressure switch or limiter SDB
Water level (Low water cutoff) WB
External blocking / Boilers
Switch on boiler as the last in a row
Accessories
Compiled Fault Output
Vitotrol 200A or Vitotrol 300A
KM BUS subscriber: - Extension EA1, AM1
- Vitotrol 200A, 300A
Extension EA1:
1 switching output (floating changeover contact)
- Control system pump to a substation
- Signal reduced mode for one heating circuit
1 analog input (0 to 10 V)
- Specification of the boiler water temperature setpoint
3 digital inputs
- Separated External switch the operating status for heating circuits 1 to 3 switchable
(with control for weather-compensated operation)
- External blocking
KM BUS distributor, with several KM BUS participants
LON communication module to communicate with the following components:
Vitotronic 200-H (for controlling other heating circuits)
Vitocom 100, type LAN1 with communication module
Vitotronic 300, GW6B Installation and Service
14
5513 463 - 06
Page 15
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
Preparing for Installation
5513 463 - 06
15
Page 16
Preparing for Installation
System Examples (continued)
Vitotronic 300, GW6B Installation and Service
16
5513 463 - 06
Page 17
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
Preparing for Installation
5513 463 - 06
17
Page 18
Preparing for Installation
System Examples (continued)
Vitotronic 300, GW6B Installation and Service
18
5513 463 - 06
Page 19
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
Preparing for Installation
5513 463 - 06
19
Page 20
Preparing for Installation
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
ID: 4800061_1407_01
coding addresses Vitotronic 300, type GW6B; Lead boiler / Pos. 8
Group Coding addressFunction
General
System Layout
Cascade
Number of boilers in cascade
Cascade
Boiler rotation
coding addresses Vitotronic 300 Type GW6B Pos. 14
General
LON Participant Number
Boiler
Boiler number in multiboiler system
coding addresses Vitotronic 200-H, type HK1B / Pos. 35
General81:3The control unit receives time
General97:1Control unit receives the outdoor temperature
00:8Two heating circuits with mixing valve M2 (heating
circuit 2) and M3 (circuit 3) DHW heating
35:2Number of boilers connected in the heating system
38:1Boiler rotation - Monthly
77:2LON Participant Number
07:2Boiler number in multiboiler system
20
5513 463 - 06
Page 21
Vitotronic 300, GW6B Installation and Service
Overview of Electrical Connections
Electrical Connections
WARNING
Incorrect wiring can lead to serious injury from electrical
current and result in appliance damage.
IMPORTANT
Electronic assemblies can be damaged by static loads.
Prior to commencing work, touch an grounded object
such as a heating or water pipe to discharge static load.
H Route low voltage leads and line voltage cables
separately.
H Strip the insulation from the cables as close to the
terminals as possible, and bundle tightly to the
corresponding terminals.
H Secure cables with cable ties.
Connections on the low voltage PCB
PlugComponentSingle boiler system
!
§/?
%A
%B
)
aJA
aJB
5513 463 - 06
Outdoor temperature sensorXX-Common supply temperature
sensor
DHW tank temperature sensorXX--
DHW tank temperature sensor
(bottom) in a tank loading
system
Common supply temperature
sensor, low loss header
Return temperature sensor T1XXX
Temperature sensor tank
loading system
Single boiler control unit
--X--
XX--
X----
X
Multi boiler system
Cascade control unitLag boiler control unit
X
--
21
Page 22
Electrical Connections
Overview of Electrical Connections (continued)
Connections on the low voltage PCB (continued)
PlugComponentSingle boiler system
sÖA1 High temperature heating circuit pump
gSA1 Mixing valve, primary store system
gÖ Compile fault output
fÖ Main power supply
aBÖ Safety circuit connections
aBA Safety circuit connections
gD Flue gas damper
F3
5513 463 - 06
Fuse 250VAC 6.3A
Rated pump and compile fault output 2A~
Note: Maximum output 6FLA shared between all mixing
valve, pump and compile fault outputs.
Note: The 120VAC line out terminals are still live even
when the control is switched off.
23
Page 24
Electrical Connections
Overview of Electrical Connections (continued)
Vitotronic 300, GW6B Installation and Service
Note: The DIN terminals can be used with solid, stranded
or stranded with ferrule termination. The ferrule
will help to prevent ‘fraying’ of the standed wires
during installation.
Specific connections are detailed throughout the manual,
refer to the appropriate section prior to making any
connections.
Top
The junction box terminals include a L, N terminal
connection orientated at the top of the junction box
which is pre-wired to the cable harness set, which is
used to connect the Vitotronic control and Burner Base to
the junction box. The L,N,G terminals orientated at the
bottom of the junction box are used to for connections
to external equipment (ie. Pumps, mixing valves, etc).
The individual terminals are a ‘push-in’ design, meaning
to install or release a wire, the orange button must be
pushed in (refer to image below for location of orange
buttons denoted by B), prior to installing or removing
any wires to the terminal.
Bottom
Legend
A DIN terminal (typical)
B Push-in button
C DIN rail (typical)
D Terminal insertion point
Note: Max. wire gauge 12AWG
Min. wire gauge 26AWG
24
5513 463 - 06
Page 25
Vitotronic 300, GW6B Installation and Service
F3
F3
Overview of Electrical Connections (continued)
Accessing the DIN rail mounted fuse F3
A DIN rail mounted fuse block provides protection to the
120V line out connections as shown on page 23.
When fuse F3 requires replacement, the fuse can be
accessed as shown.
Electrical Connections
1. Flip down the front portion of the DIN rail
fuse block.
2. Flip down the front side cover of the DIN rail
fuse block.
3. Replace fuse.
4. Return the DIN rail
original postion.
mounted fuse block back to the
.
mounted
mounted
5513 463 - 06
25
Page 26
Electrical Connections
Boiler Control and Junction Box
B
C
Legend
A Junction box
B Vitotronic control
C Vitocrossal 200 CM2 boiler
Vitotronic 300, GW6B Installation and Service
1. Install the junction box to the rear panel either right or
left. Secure the junction box with four 4.8 mm metal
screws.
2. Route cables from control through the opening in the
control panel. Guide the cables to the junction box
through the opening in the rear panel and along the
top rail to the control. Secure all cables to the rail with
cable ties.
Note: Never allow cables to come in contact with hot
metal components.
3. Mount the control to the top front panel.
4. Secure the control to the top front panel with screws.
Note: Screws to secure control are included in
control’s shipping box.
Mounting the Control Unit
Legend
A Cable retaining tab
26
Note: Route the ribbon cable through retainer A.
5513 463 - 06
Page 27
Vitotronic 300, GW6B Installation and Service
Opening the Control Unit
Electrical Connections
Plugging in the Boiler Coding Card
Only use the boiler coding card supplied with the boiler
junction box.
Insert the boiler coding card into slot “X7”, through the
recess in the cover.
Coding card #Part #
10427543216
5513 463 - 06
27
Page 28
Electrical Connections
Inserting Cables and Applying Strain Relief
H Control unit fitted on the boiler:
Route cables from below through the front panel of the
boiler into the wiring chamber of the control unit.
Vitotronic 300, GW6B Installation and Service
Legend
A Cables with moulded strain relief
B On-site cables; strip up to 4 in. (100 mm) insulation
Connecting Sensors
Outdoor temperature sensor connection
2 wire cable, 18 AWG for a maximum length of 120 ft
(36 m)
28
Connections on the low voltage PCB
PlugComponent
!
§/?
%A
%B
)
aJA
aJB
Outdoor temperature sensor
Fitting location for outdoor temperature sensor
H North or north-westerly wall, 6 to 8 ft (2 to 2.5 m)
above ground level; in multi storey buildings, in the
upper half of the second floor.
H Not above windows, doors or ventilation outlets.
H Not immediately below balconies or gutters.
H Never cover over.
Outdoor temperature sensor
Common supply temperature sensor
Tank temperature sensor
Tank temperature sensor (bottom)
in a tank loading system
Temperature sensor, low loss header
Return temperature sensor T1
Temperature sensor tank loading system
5513 463 - 06
Page 29
Vitotronic 300, GW6B Installation and Service
Control Power Supply
Electrical Connections
Connecting the power supply to the Vitotronic control
For burner base unit, see boiler service
instructions
Legend
A To the burner base unit
B Connecting cable
C To the Vitotronic control
Insert plug
burner base.
Route beneath the top B rail in a bundle using plug-in
cable retainers.
Connect plugs fÖ and aBH to the corresponding plugs in
the Vitotronic control unit.
40/156
into the corresponding plug of the
5513 463 - 06
29
Page 30
Electrical Connections
Connecting the Burner
Legend
A To the Vitotronic control
B To the burner (burner control unit)
C KM BUS cable
Vitotronic 300, GW6B Installation and Service
The burner cables are included in the standard boiler
delivery.
Max. power consumption 3A.
Terminal codes
L1 Phase via external safety equipment (if installed)
to the burner
Ground conductor to burner
N Neutral conductor to burner
T1 120V~ from burner control unit
T2 Base load demand
S3 Connection for burner fault
B4 Connection for hours run meter
Insert plug fA and aVG into the corresponding plug of
the burner control.
Route beneath the top B rail in a bundle using plug-in
cable retainers.
Connect plugs fA and aVG to the corresponding plugs in
the Vitotronic control unit.
30
5513 463 - 06
Page 31
Vitotronic 300, GW6B Installation and Service
Connecting Pumps
Electrical Connections
Legend
A Pumps
B To the control unit
Rated voltage120V~
Rated current Max.2A~
Note: Maximum output 6FLA shared between all
120V outputs.
Connections on extension for heating circuit with mixing
valve HC2/M2, HC3/M3
PlugTerminalComponent
sÖ M2
sÖ M3
Connections on the PCB 120V~
sÖA1
sA
sK
sL
5 L, N, GHeating circuit pump
6 L, N, GHeating circuit pump
9 L, N, GHeating circuit pump
for heating circuit A1
or
Primary pump,
primary store system
8 L, N, GDHW pump
7 L, N, GDHW recirculation
pump
10 L, N, Gboiler pump, system
pump
31
Page 32
Electrical Connections
Connecting Pumps (continued)
Vitotronic 300, GW6B Installation and Service
120V pumps with an amperage draw of <2FLA
A Din rail (located in the junction box)
B Pump
120V pumps with an amperage draw of >2FLA
Contactor specification 120VAC 1A
A Din rail (located in the junction box)
B Contactor/relay (field supplied)
C Pump
D Power supply w/disconnect and protection
32
5513 463 - 06
Page 33
Vitotronic 300, GW6B Installation and Service
Connecting Pumps (continued)
Electrical Connections
240V pumps
Contactor specification 120VAC 1A
A Din rail (located in the junction box)
B Contactor/relay (field supplied)
C Pump
D Power supply w/disconnect and protection
208/460/575V 3 phase pumps
Contactor specification 120VAC 1A
A Din rail (located in the junction box)
B Contactor/relay (field supplied)
C Pump
D Power supply w/disconnect and protection
5513 463 - 06
33
Page 34
Electrical Connections
Connecting a Central Fault Message Facility
Plug gÖ (terminal 11 - L, N, G)
Note: On lag boilers, output gÖ will only be switched
in the case of faults on that boiler.
Rated voltage120V~
Rated current Max.2A~
Note: Maximum output 6 FLA shared between all 120V
outputs
Connecting Actuators
Vitotronic 300, GW6B Installation and Service
1. Disconnect power to control.
2. Connect valve actuator wires to the DIN as shown
(based on desired functionality).
Operating time: 5 to 199 sec. selected via coding
address “40”.
Available connections
gS A1 Motor for 3-way mixing valve, primary store system
gS M2 For heating circuit 2
gS M3 For heating circuit 3
Rated voltage120V~
Rated current Max.0.1~/ output
Motor runtime for
3-way mixing valve: 10 to 255 sec, adjustable via
coding addresses “6a” in
the”DHW”group, “c3” in the
heating circuit 2 group and “c3”
in the heating circuit 3 group.
PlugDIN terminals
52A112 (L, N)
13 (L)
52M21 (L, N)
2 (L)
52M33 (L, N)
4 (L)
34
Legend
A DIN Rail (in junction box)
B 120V Valve Actuator
C Valve
5513 463 - 06
Page 35
Vitotronic 300, GW6B Installation and Service
Connecting Actuators (continued)
Electrical Connections
Legend
A 24V Mixing Valve Adaptor
B DIN Rail (in junction box)
C 24V Valve Actuator
D Valve
E 120V power to the mixing valve adaptor
Operating time: 5 to 199 sec. selected via coding
address “40”.
Available connections
gS A1 Motor for 3-way mixing valve, primary store system
gS M2 For heating circuit 2
gS M3 For heating circuit 3
Motor runtime for
3-way mixing valve: 10 to 255 sec, adjustable via
coding addresses “6a” in
the”DHW”group, “c3” in the
heating circuit 2 group and “c3”
in the heating circuit 3 group.
1. Disconnect power to control.
2. Remove plug connect gS from cables BK1, BK2 and
BK3 of the 24V valve adaptor
3. Connect BK1, BK2 and BK3 to DIN terminals for
desired valve application. Refer to the chart below.
4. Connect black wire E of the mixing valve adaptor
to an available terminal 14-17 on the DIN rail.
5. Connect valve actuator wires to the adaptor terminals
as shown in image above.
Refer to the mixing valve adaptor Installation
Instructions for additional information.
PlugDIN terminals
52A112 (L, N)
13 (L)
52M21 (L, N)
2 (L)
52M33 (L, N)
4 (L)
5513 463 - 06
35
Page 36
Electrical Connections
Connection of Low Water Cut-off Device
1. Remove jumper between terminals 21(L) and 22(L).
2. Make connection for switching contact at terminal
(LWCO) 21(L) and 22(L).
3. Power supply for low water cut-off device made at an
available terminal 14, 15, 16 or 17 (L, N, G)
The diagram shown is only a simplified conceptual
drawing of a typical low water cut off (LWCO) device.
Refer to the manual specific to the device for
interconnection details.
Vitotronic 300, GW6B Installation and Service
CAUTION
Legend
aBÖ Connection for external equipment.
A Low water cut-off (typical)
36
5513 463 - 06
Page 37
Vitotronic 300, GW6B Installation and Service
Connecting External Safety Equipment
Electrical Connections
Connection at plug aBÖ.
Note: ‘Live’ contacts lead to short circuits or phase failure.
The external connection must be potential-free.
1. Remove jumper from terminals 21(L) and 22(L).
2. Make connection of the safety equipment to 21(L)
and 22(L).
Legend
A Low water indicator, minimum pressure limiter
B Maximum pressure limiter
C Further safety equipment
Note: Periphery equipment attached to the aBÖ plug must be operated on a normally closed circuit.
5513 463 - 06
37
Page 38
Electrical Connections
Connections to Terminal aBA
Vitotronic 300, GW6B Installation and Service
Low gas pressure switch/external shut-off
1. Remove jumper between terminals 26 (L) and 27(L).
2. Connect auxiliary low gas pressure switch or external
shut-off (dry contact) to terminals 26 (L) and 27(L).
WARNING
The terminals should be used for safety switch-off
purposes only (e.g. through a high limit thermostat).
During switch-off, there is no frost protection of the
heating system and the boiler is not kept at the minimum
boiler water temperature.
Note: The heating system has no frost protection while it
is blocked. The boiler is not held at the lower boiler
water temperature.
Refer to the low gas pressure switch
Installation Instructions
Legend
A DIN rail (junction box)
B Auxiliary low gas pressure switch or external shut-off (dry contact)
38
5513 463 - 06
Page 39
Vitotronic 300, GW6B Installation and Service
Provisional Burner Operation
Electrical Connections
Remove jumper across terminals 23 (L) and 24 (L) (not
shown) and connect terminals 23 (L) and 25 (L) external
control via dry contact (heat demand on close). Upon heat
demand the boiler will maintain low fire until modulation is
externally controlled through BMS.
Legend
A Dry contact between “TR and ON”
B Din rail (located in junction box)
T6 - Common
T7 - Modulating Down
T8 - Modulating Up
Legend
C To burner interface
5513 463 - 06
External modulation via 90 plug (dry contact for
modulation) terminal closure T6 and T8 will drive burner
modulation up and terminal closure T6 and T7 will drive
modulation down.
Note: Only one contact will be closed at a time. Both
contacts open will hold modulation.
Temperature control is now limited by the electronic high
limit setting in the burner control.
Refer to the “combustion controller” group in
coding for adjustment to maximum boiler water
temperature.
39
Page 40
Electrical Connections
Vitotronic 300, GW6B Installation and Service
Blocking the Boiler Externally/Adding to the Boiler Sequence
Only for lag boilers
Connection on plug aVD
Note: ‘Live’ contacts lead to short circuits or phase failure.
The external connection must be potential-free.
Legend
A Blocking the boiler externally
B Start the boiler externally as the last one
in the boiler sequence
ContactClosedOpen
A
aVD.1/aVD.2
B
aVD.2/aVD.3
H The boiler is blocked and has been removed
from the boiler sequence.
H The motorized isolation valve closes and the
boiler circuit pump stops.
H The other boilers provide the required heating.
Note: If all boilers are blocked or there is no
other boiler ready for operation, then
there will be no frost protection for the
heating system.
This boiler is moved from the current position
in the boiler sequence and started as the last
boiler in the sequence.
The boiler is integrated into the current boiler
sequence.
The boiler is integrated into the current boiler
sequence.
40
5513 463 - 06
Page 41
Vitotronic 300, GW6B Installation and Service
External Blocking via Switching Contact
Electrical Connections
Plug aVD.2/aVD.3
Legend
A Floating contact
B Plug aVD of the control unit
EA1 extension
Only for single boiler and cascade control units
Connection options:
H Plug aVD.2/aVD.3
Note: In the case of cascade control units make the
connection on the EA1 extension.
H EA1 extension (accessory, see page 122)
Contact closed:
H Single boiler system
The boiler is shut down.
H Multi boiler system
Controlled shutdown of the burners on each boiler.
Any connected circuit or system pump is stopped.
Shut-off devices are closed.
Note: The heating system has no frost protection while
it is blocked.
Connection
Note: ‘Live’ contacts lead to short circuits or phase failure.
The external connection must be potential-free.
Coding
Plug aVD
With coding “99” set in the “General” group determine
what the input should influence.
Note: Never adjust coding “99:0” in a cascade control
unit.
Legend
A Floating contact
B EA1 extension
EA1 extension
Set “5d” (DE1), “5e” (DE2) or “5f” (DE3) in the “General”
group to 3 or 4.
5513 463 - 06
41
Page 42
Electrical Connections
External Demand via Switching Contact
Vitotronic 300, GW6B Installation and Service
Plug aVH.2/aVH.3
146
Legend
A Floating contact
B Plug aVH of the control unit
EA1 extension
Only for single boiler and cascade control units
Connection options:
H Plug aVH.2/aVH.3
H EA1 extension (accessory, see page 122)
Contact closed:
H Single boiler system
The burner is switched ON subject to load. The boiler
heats to the set boiler water temperature selected in
coding “9b” in the “General” group.
Limiting the boiler water temperature by means of the
set boiler water temperature and the electronic
maximum limit of the boiler water temperature
(coding “06” in the “Combustion Controller” group)
H Multi boiler system
The burners in each boiler are switched ON subject to
load. They heat to the set supply temperature selected
in coding “9b” in the “General” group.
Limiting the supply temperature by means of the set
supply temperature and the electronic maximum limit
of the supply temperature (coding “37” in the
“Cascade” group)
Connection
Note: ‘Live’ contacts lead to short circuits or phase failure.
The external connection must be potential-free.
Legend
A Floating contact
B EA1 extension
Coding
Plug aVH
No coding change required
EA1 extension
Set “5d” (DE1), “5e” (DE2) or “5f” (DE3) in group
“General” to 2.
42
5513 463 - 06
Page 43
Vitotronic 300, GW6B Installation and Service
External Demand via 0 –10V Input
Electrical Connections
Connection at input 0 – 10V to EA1
extension (accessory, see page 122).
Note: Ensure DC separation between the ground
conductor and the negative pole of the on-site
voltage source.
0 –1V
1V Set value 50°F (10°C)
10V Set value 212°F (100°C)
Observe coding “1E” in the “General” group.
Optional setting range
0 –1V No default set supply temperature
1V Set value 86°F (30°C)
10V Set value 248°F (120°C)
Observe coding “1E” in the “General” group.
Connection on plug aVD.
Note: ‘Live’ contacts lead to short circuits or phase failure.
The external connection must be potential-free.
Coding
External “mixing valve open”
With coding “9a” in the “General”group assign the
function to the heating circuits.
Legend
A External “mixing valve open” (floating contact)
B External “mixing valve close” (floating contact)
External “mixing valve close”
With coding “99” in the “General” group assign the
function to the heating circuits.
5513 463 - 06
43
Page 44
Electrical Connections
External Operating Program Changeover
Vitotronic 300, GW6B Installation and Service
Plug aVD
Legend
A Floating contact
B Plug aVD of the control unit
EA1 extension
The changeover can be achieved separately for heating
circuits 1 to 3.
Legend
A Dry contact (potential free)
B EA1 extension
Only for single boiler and cascade control units
Connection options:
H Plug aVD.1/aVD.2
Note: In the case of cascade control units make the
connection on the EA1 extension.
H EA1 extension (accessory, see page 122)
Connection
Note: ‘Live’ contacts lead to short circuits or phase failure.
The external connection must be potential-free.
Preselected operating
program
(Contact open)
9
or
w
or
w
Central
heating OFF/
DHW OFF
Central
heating OFF/
DHW
heating ON
Central
heating ON/
DHW
heating ON
CodingChanged operating
program
(Contact closed)
“d5:0” in
the
“Heating
circuit ...”
group
(Factory
set
condition)
“d5:1” in
the
“Heating
circuit ...”
group
Constant
operation with
reduced
room temperature/
DHW heating OFF
Constant
operation with
standard
room temperature,
DHW heating
in accordance
with coding
“64” in the
“DHW” group
44
Coding
Plug aVD
This function can be assigned to the heating circuits
at coding “91” in the “General” group.
Note: Never adjust coding “91:0” in a cascade
control unit.
EA1 extension
Set “5d” (DE1), “5e” (DE2) or “5f” (DE3) in group
“General” to 1.
This function can be assigned to the heating circuits
at coding “d8” in the “Heating circuit...” group.
5513 463 - 06
Page 45
Vitotronic 300, GW6B Installation and Service
Power Supply
Electrical Connections
WARNING
If system components are not grounded, serious injury
from electric current can result if an electrical fault
occurs.
Connect the appliance and pipework to the
equipotential bonding of the building in question.
WARNING
Incorrectly executed electrical installations can lead to
injuries from electrical current and result in appliance
damage.
Connect the power supply to the mains filter unit
(part of standard burner delivery).
Isolators for non-grounded conductors
H The mains isolator or “Emergency stop” must
simultaneously isolate from the power supply all
non-grounded conductors.
H We additionally recommend installing an AC/DC-
sensitive RCD, type B
that can occur with energy efficient equipment.
H If no mains isolator or “Emergency stop” is set,
isolate all non-grounded conductors simultaneously
from the power supply by means of an upstream
isolator with a minimum contact separation of 3 mm.
H Connection to the same MCB/fuse provides additional
safety when the power is switched off. Observe the
power consumption of the connected consumers.
, for DC (fault) currents
Legend
A Power supply 120V~
(CM2 - 186, 246, 311 requires 12A)
(CM2 - 400, 500, 620 and 620TX requires 16A)
B Fuse 250VAC 6.3A
C Mains isolator, (on-site)
D Boiler junction box
5513 463 - 06
Connect the power supply and implement all safety
measures (e.g. RCD circuit) in accordance with local and
national codes.
45
Page 46
Electrical Connections
Making the LON Connection
Vitotronic 300, GW6B Installation and Service
Connection with Viessmann LON cable
The line may be up to ≤ 23 ft. (7 m) long
Legend
A Control unit or Vitocom
B LON cable, 23 ft. (7 m) long
C Terminator
Connection with Viessmann LON cable and coupling
The Viessmann LON is designed for “Line” BUS topology
with a terminator at both ends (accessories).
Further information can be found in the “Viessmann LON
manual”; see www.viessmann.de/lon.
The transfer distances for LON are subject to the electrical
properties of the respective cable. For this reason, only
use the stated cable types. Use only one cable type
within one LON.
Cable types (on site):
H 2-core cable, CAT5, screened
H JY(St)Y 2 x 2 x 0.8 mm (telephone cable)
Observe the cabling requirements for the operation
of the LON interface FTT 10-A (see www.echelon.com).
All Viessmann appliances are connected with RJ45
connectors. The Viessmann LON always requires
the cores “1” and “2” and the screen. The cores are
interchangeable.
Installation spacing 23 to 69 ft. (7 to 21 m)
Legend
A Control unit or Vitocom
B LON cable, 23 ft. (7 m) long
Max. 3 cables between 2 appliances
C Terminator
D LON coupling
46
5513 463 - 06
Page 47
Vitotronic 300, GW6B Installation and Service
Making the LON Connection (continued)
Connection with LON cable, on-site cable and LON junction box
≤ 3000 ft.
The line may be up to ≤ 3000 ft. (900 m) (with LON junction boxes)
Legend
A Control unit or Vitocom
B LON cable, 23 ft. (7 m) long
C Terminator
D LON sockets
E On-site cable
F Up to 30 participants
Electrical Connections
Connection with on-site cable and LON plug
≤ 3000 ft.
The line may be up to ≤ 3000 ft. (900 m)
(with LON plug)
Legend
A Control unit or Vitocom
B On-site cable
C Terminator
D LON plug
E Up to 30 participants
5513 463 - 06
47
Page 48
Commissioning
Commissioning the System
Vitotronic 300, GW6B Installation and Service
1. Turn ON the ON/OFF switch on all control units.
The commissioning assistant starts automatically.
2. Make required settings:
- “Language”
- “Date / Time”
- “Measuring units”
3. Tap “Application” and select the required application.
- ‘single boiler’
- ‘lead boiler and cascade’
- ‘lag boiler’
4. Confirm with OK until symbol
5. Important coding can be set during commissioning
(see the following table). For this tap “Yes”.
Note: Flue gas damper coding address 0a is factory
defaulted to 0a:1 (with flue gas damper) when
the application is set ‘lead boiler & cascade’ or
‘lag boiler’.
If a flue gas damper is not used with the boiler,
the coding address must be adjusted to 0a:0.
If the coding address is not adjusted through the
commissioning assistant at the boiler control,
then the burner will check for the presence of
a flue gas damper and then the functionality of
the flue gas damper can only be adjusted through
the burner control.
and “Setup” appear.
Single boiler
Weather-compensated single boiler system capable of
controlling DHW production and space heating of one high
temperature heating loop and 2 low temperature heating
loops with mixing valves.
Lead boiler and cascade
Master boiler in a multiboiler system capable of cascading
a maximum of 8 x GW6B equipped CM2 series boilers.
This boiler is responsible for generating system and boiler
setpoints, capable of DHW production and and space
heating of one high temperature heating loop and 2 low
temperature heating loops complete with mixing valves.
Lag boiler
Slave tothe master boiler, and operates on setpoints
generated by the master boiler.
Refer to the burner section of the CM2
Service Instructions
Tap “No” if no further settings are to be made.
6. Confirm with OK.
- Single boiler system
The standard menu appears.
- Multi boiler system
The default display will appear.
Refer to the Operating Instructions
Note: If commissioning was unsuccessful, the following
fault symbol
Tap and check the fault messages.
- ‘single boiler’
- ‘lead boiler + cascade’
- ‘lag boiler’
If the Vitocrossal 200 CM2 boiler is operated in a multiple
boiler application, a fault message will be displayed during
initial start-up, which indicates that the boiler controller
commissioning process is not yet completed.
Please ackowledge this message and complete the
commissioning process.
appears in the footer.
48
5513 463 - 06
Page 49
Vitotronic 300, GW6B Installation and Service
Commissioning
Commissioning the System (continued)
Coding are show in the “Setup” menu in the following order:
FunctionGroupCoding
“Max operational output”“Combustion controller”02
“Gas type”03
“Altitude”04
“Design”0a
“System design”“General”00
“Consecutive boiler number in multi boiler systems”“Boiler”07
“Number of boilers connected to the cascade” “Cascade” “Cascade”35
“LON participant number”“General”77
“Control strategy”“Cascade”3c
Adjusting Coding
Single boiler system
Check all addresses on Coding level 1 and set if required.
Check the following coding on Coding level 2 and set if required.
For steps and overviews on coding, see chapter “Coding”.
FunctionGroupCoding
“Connection at plug 20A1”“General”4c
“With LON communication module”
(control unit is fault manager)
“Viessmann system number”“General”98
“With LON communication module:
Monitoring LON participants”
“General”79
“General”9c
Multi boiler system
Check all addresses on Coding level 1 and set if required.
Check the following coding on Coding level 2 and set if required.
For steps and overviews on coding, see chapter “Coding”.
FunctionGroupCoding
On all control units
“Single boiler and multi boiler system”“Boiler”01
“Connection at plug 29”“General”4d
“Viessmann system number”“General”98
“With LON communication module:
Monitoring LON participants”
Only on cascade control units
“Connection at plug 20A1”“General”4c
“Connection at plug 29”“General”4d
“Connection at plug 52A1”“General”4e
“With LON communication module”
(control unit is fault manager)
“Central control of heating circuits”“General”7a
“Viessmann system number”“General”98
“With LON communication module:
Monitoring LON participants”
“Permanent last boiler”“Cascade”3a
“Permanent lead boiler”“Cascade”39
“Storage tank heating, hysteresis”“DHW”55
“General”9c
“General”79
“General”9c
5513 463 - 06
49
Page 50
Commissioning
Connecting the Control Unit to the LON
Example of a single boiler system with Vitotronic 200-H
and Vitocom
Vitotronic 300, GW6B Installation and Service
H The LON communication module is factory installed.
H Vitotronic 200-H:
The LON communication module (accessories) must
be fitted.
Refer to the Installation and Service
Instructions for Vitotronic 200-H
H Within one LON, the same participant number must
not be allocated twice.
H Within one LON, the system number (coding “98”
in the “General” group) must always be the same.
H Only one control unit may be programmed as fault
manager.
H The data transfer via LON can take several minutes.
A Single boiler control unit
B Vitotronic 200-H
C Vitocom
D LON
All coding in the table are listed in the "General" group.
ABC
Participant no. 1,
Coding “77:1”
Control unit is fault manager,
Coding “79:1”
Control unit transmits the time,
Coding “7b:1”
Control unit sends outdoor
temperature, Coding “97:2”
Viessmann system number,
Coding “98:1”
LON participant fault monitoring,
Coding “9c:20”
Participant no. 10,
Coding “77:10”
Control unit is not fault manager,
Coding “79:0”
Control unit receives the time,
Set coding “81:3”
Control unit receives outdoor
temperature, Set coding “97:1”
Viessmann system number,
Coding “98:1”
LON participant fault monitoring,
Coding “9c:20”
Participant no. 99
Appliance is fault manager
Device receives the time
--
--
--
50
5513 463 - 06
Page 51
Vitotronic 300, GW6B Installation and Service
Connecting the Control Unit to the LON (continued)
Example of a multi boiler system
Commissioning
A Lag boiler control unit
B Lag boiler control unit
C Cascade control unit
ABCDE
Multi boiler system
Set coding “01:2” in
the “Boiler” group
Boiler number 3
Set coding “07:3” in
the “Boiler” group
----Number of connected
Participant no. 3.
Coding “77:3” in the
“General” group
Control unit is not
fault manager.
Coding “79:0” in the
“General” group
----Control unit transmits
----The control unit
Viessmann system
number, Coding
“98:1” in the
“General” group.
LON participant fault
monitoring Coding
“9c: 20” in the
“General” group
Multi boiler system
Set coding “01:2” in
the “Boiler” group
Boiler number 2
Set coding “07:2” in
the “Boiler” group
Participant no. 2.
Set coding “77:2” in
the “General” group
Control unit is not
fault manager.
Coding “79:0” in the
“General” group
Viessmann system
number, Coding
“98:1” in the
“General” group.
LON participant fault
monitoring Coding
“9c: 20” in the
“General” group
Multi boiler system
Set coding “01:2” in
the “Boiler” group
Boiler number 1
Set coding “07:1” in
the “Boiler” group
boilers Set coding
“35:1” to “35:8” in
the “Cascade” group
Participant no. 1.
Coding “77:1” in the
“General” group
Control unit is fault
manager.
Coding “79:1” in the
“General” group
the time. Coding
“7b:1” in the
“General” group
sends the outdoor
temperature.
Coding “97:2” in the
“General” group
Viessmann system
number, Coding
“98:1” in the
“General” group.
LON participant fault
monitoring Coding
“9c: 20” in the
“General” group
D Vitotronic 200-H
E Vitocom
F LON system
----
----
----
Participant no. 10.
Coding “77:10” in
the “General” group
Control unit is not
fault manager.
Coding “79:0” in the
“General” group
The control unit
receives the time.
Set coding “81:3” in
the “General” group
The control unit
receives the outdoor
temperature.
Set coding “97:1” in
the “General” group
Viessmann system
number, Coding
“98:1” in the
“General” group.
LON participant fault
monitoring Coding
“9c: 20” in the
“General” group
Participant no. 99
Appliance is fault
manager
Device receives the
time
--
--
--
5513 463 - 06
51
Page 52
Commissioning
Connecting the Control Unit to the LON (continued)
Carrying out a LON participant check
The participant check is used to test communication with
the system devices connected to the fault manager.
Preconditions:
H The control unit must be programmed as fault manager
(coding “79:1” in the “General” group).
H The LON participant no. must be programmed in all
control units.
H The LON participant list in the fault manager must be
up to date.
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Service functions”
5. “LON participant check”
The list of all connected LON participants appears.
6. Select participant and start participant check with “OK”.
“Participant ...” appears on the display” Check running”.
Note: During the participant check, the display for the
relevant participant flashes the participant no. for
approx. 1 min. and displays “Wink”.
Vitotronic 300, GW6B Installation and Service
H Successfully tested participants are designated with “OK”.
H Unsuccessfully tested participants are designated with
“Subscribe ... Check not OK”.
Update the participant list with “New list” in order to
carry out another participant check.
Setting the Boiler Sequence at the Cascade Control Unit
Boiler sequence subject to the coding set in the “Cascade” group and internal control calculations:
FunctionCoding
“Lead boiler or boiler sequence changeover”38
“Permanent lead boiler”39
“Permanent last boiler”3a
“ECO threshold boiler”...41 to 44, 65, 6f, 74, 7d
H Every boiler can be blocked or enabled subject to
outdoor temperature by means of the ECO threshold.
H The ECO threshold has no effect if a boiler is required
to achieve the set supply temperature in the case of
enabled boilers failing.
H At least the lead boiler remains in operation when all
boilers in a system would otherwise be blocked via the
ECO threshold.
Tap the following buttons:
1. “Menu”
2. “Boiler sequence”
3. Select the required boiler sequence and confirm with “OK”.
52
5513 463 - 06
Page 53
Vitotronic 300, GW6B Installation and Service
Carrying Out an Actuator Test
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Actuator test”
Note: Before an actuator is selected, all actuators are
switched to zero volt.
The actuators listed in the table can be tested at the relay
outputs subject to system equipment level and control
unit configuration (single or multi boiler system).
DisplayExplanation
“All actuators”OFFAll actuators have been switched off.
“Output 20”ON
“Output 52”Open
“Output 52”Neutral
“Output 52”Close
“DHW tank primary pump” ON
“DHW circ pump”ON
“Output 29”ON
“Central fault message”ON
“Htg circ pump HC2”ON
“Mixing valve HC2”Open
“Mixing valve HC2”Close
“Htg circ pump HC3”ON
“Mixing valve HC3”Open
“Mixing valve HC3”Close
“EA1 output 1”ON
“AM1 output 1”ONActuator at output A1
“AM1 output 2”ONActuator at output A2
“Solar circuit pump”ON
“Solar circ pump min”ON
“Solar circ pump max”ON
“SM1 output 22”ON
Actuator at output sÖ A1
Actuator at output gS A1
Actuator at output gS A1
Actuator at output gS A1
Actuator at output sA
Actuator at output sK
Actuator at output sL
Central fault message facility at output gÖ
Actuator at output sÖ M2
Actuator at output gS M2
Actuator at output gS M2
Actuator at output sÖ M3
Actuator at output gS M3
Actuator at output gS M3
Contact “P - S” on plug aBJ of EA1 extension closed.
“Solar circuit pump” On Solar circuit pump at output sF at solar control
module, type SM1
“Solar circ pump min” On Solar circuit pump at output sF at solar control
module, type SM1 set to min. speed.
“Solar circ pump min” On Solar circuit pump at output sF at solar control
module, type SM1 set to max. speed.
Actuator at output sS at solar control module type SM1
Information regarding the mixing valve motor rotational
direction.
The supply temperature must rise when the mixing valve
opens.
If the temperature drops, either the motor is turning in
the wrong direction or the mixing valve set is incorrectly
fitted (observe the mixing valve installation instructions).
Commissioning
5513 463 - 06
53
Page 54
Commissioning
Checking Sensors
Adjusting the Heating Curve
Vitotronic 300, GW6B Installation and Service
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Diagnosis”
5. Select group.
6. Scan actual temperature of the relevant sensor.
Only for single boiler and cascade control units
The heating curves represent the relationship between
the outdoor temperature and the boiler water or supply
temperature.
Simplified: The lower the outdoor temperature, the higher
the boiler water or supply temperature.
The boiler water or supply temperature in turn affects the
room temperature.
Slope
Boiler water or supply
temperature
Room
set-point
temperature
For outdoor temperature 7°F (−14°C)
Legend
A Underfloor heating system, slope 0.2 to 0.8
B Low temperature heating system, slope 0.8 to 1.6
C Heating systems with a boiler water temperature in
excess of 167°F (75°C), slope greater than 1.6
Outdoor temperature
Settings in the factory set condition:
H Slope = 1.4
H Shift = 0
54
5513 463 - 06
Page 55
Vitotronic 300, GW6B Installation and Service
Adjusting the Heating Curve (continued)
Commissioning
Standard set room temperature
Adjustment of the standard set room temperature
from 68 to 79°F (20 to 26°C)
Legend
A Boiler water temperature or supply temperature
B Outdoor temperature
C Set room temperature
D Heating circuit pump “Off”
E Heating circuit pump “On”
Selecting the set room temperature
Individually adjustable for each heating circuit.
The heating curve is offset along the set room
temperature axis. With the heating circuit pump logic
function enabled, the curve modifies the starting and
stopping characteristics of the heating circuit pump.
Changing the standard set room temperature
Refer to the Operating Instructions
Reduced set room temperature
Adjustment of the reduced set room temperature
from 37 to 52°F (3 to 14°C)
Legend
A Boiler water temperature or supply temperature
B Outdoor temperature
C Set room temperature
D Heating circuit pump “Off”
E Heating circuit pump “On”
Changing the standard set room temperature
Refer to the Operating Instructions
5513 463 - 06
55
Page 56
Commissioning
Adjusting the Heating Curve (continued)
Boiler water or
supply temperature
Vitotronic 300, GW6B Installation and Service
Changing the slope and shift
Individually adjustable for each heating circuit.
From the home screen tap the following buttons:
1. Tap “Menu”.
2. “Heating circuit 1”, “Heating circuit 2” or “Heating
circuit 3” as the required heating circuit
3. Heating.
4. “Heating curve”
5. +/– for the required value for “Slope” or “Shift”
Outdoor temperature
Legend
A Changing the slope
B Changing the shift (vertical parallel offset of the
heating curve)
6. Tap OK to confirm
Example: Heating curve setting with slope 1.5:
56
5513 463 - 06
Page 57
Vitotronic 300, GW6B Installation and Service
Calling up the Service Menu
Service Scans
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. Select the required menu range.
Note: In the “Diagnosis” menu area submenus are shown
subject to control unit, e.g. “Cascade” will only be
shown for a cascade control unit.
“Service main menu”
“Diagnosis”
“General”
“Cascade”
“DHW”
“Heating circuit 1/2/3”
“Solar energy”
“Short query”
“Reset data”
“Actuator test”
“System configuration”
“Coding level 1”
“Coding level 2”
“History of faults”
“Service functions”
“LON participant check”
“System log”
“Vitocom PIN input”
“Startup”
“The heating system is reset
to the factory state”
“Change passwords”
“Service level”
“Coding level 2”
“Reset all passwords”
“Exit service”
5513 463 - 06
Note: - “Coding level 2” is only displayed if this level
has been enabled: Enter “viexpert” password.
- Tap
to return to the “Service main menu”
57
Page 58
Service Scans
Leaving the Service Menu
Change Passwords
Vitotronic 300, GW6B Installation and Service
From the service main menu tap the following buttons:
1. “Exit service”
2. Confirm “Terminate service?” with OK.
Note: The system exits the service menu automatically
after 30 min.
In the factory set condition, the following passwords have
been assigned:
H “viservice” for access to the “Service main menu”
H “viexpert” for access to “Coding level 2”
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Change passwords”
5. “Service level” or “Coding level 2”
6. Enter current password.
7. Confirm with OK.
8. Enter new password.
9. Tap OK twice
Resetting all Passwords to Factory Settings
From the home screen tap the following buttons:
1. Request the master password from the Technical
Service at the Viessmann Group.
2. “Menu”
3. “Service”
4. Enter “viservice” password.
5. “Change passwords”
6. “Reset all passwords”
7. Enter master password. This must be requested from
the service hotline.
8. Confirm twice with OK.
58
5513 463 - 06
Page 59
Vitotronic 300, GW6B Installation and Service
Scanning Operating Data
Resetting Operating Data
Service Scans
Operating data can be scanned in various areas
(see “Diagnosis” on page 54).
Operating data on heating circuits with mixing valves and
a solar thermal system can only be scanned if the
relevant components are installed in the system.
For further information on operating data, see chapter
“Brief scan”.
Note: “- - -” appears on the display if a scanned
sensor is faulty.
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Diagnosis”
5. Select required group, e.g. “General”.
Saved operating data (e.g. hours run) can be reset to 0.
The value "Dampened outdoor temp" is reset to the
actual value.
From the home screen tap the following buttons:
1. "Menu"
2. "Service"
3. Enter "viservice" password.
4. "Diagnosis"
5. "Reset data"
6. Select required value or "All details".
5513 463 - 06
59
Page 60
Service Scans
Brief Scan
Vitotronic 300, GW6B Installation and Service
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Diagnosis”
5. “Short query”
6. “Code” An overview of brief scans appears with 11
lines and 6 fields.
with the following tables.
for the required brief scan in line
123456
1:System schemes 01 to 10Control unit software versionSoftware version, programming unit
2:000Appliance identification CU-ID
3:00Number of KM BUS participantsSoftware version
Solar control module type SM1
4:000000
5:0000Software version,
Connection on
plug aVD.2/3
0: Contact open
1: Contact closed
Software version
Communic.
coproc.
Software version
Remote control
0000
00
Connection on plug aVD.2/3
Neuron Chip
Software version
Remote control
0: Without
1: Vitotrol 200A
2: Vitotrol 300A
version,
extension
for heating
circuits 2
and 3 with
mixing valve
Note: The displays in fields 3 and 5 are the same.
Software version
Remote control
0Software
Participant number
Remote control
0: Without
1: Vitotrol 200A
2: Vitotrol 300A
version,
extension
for heating
circuits 2
and 3 with
mixing valve
Software version,
EA1 extension
Software version
Remote control
0
60
5513 463 - 06
Page 61
Vitotronic 300, GW6B Installation and Service
Maintenance Display
Service Scans
Set limits in coding “21” and “23” in the “Boiler” group.
Once these values have been reached, “Service” and
symbol
Tap the following buttons:
1. “Confirm” The footer shows
2.
Note: After tapping the following will be displayed if your heating system has several fault messages
simultaneously:
3. “Service messages”
The service messages appear yellow in a list.
After maintenance has been carried out
Note: If a service is carried out prematurely, set
coding “24:1” in the “Boiler” group to “24:0”.
The selected maintenance coding for hours run
and time intervals restart at 0.
If coding “24” is not reset, “Service” will be
displayed again on the following Monday.
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Service functions”
5. “Reset service” The set service coding for hours
run and interval restart at 0 and coding “24” in
the “Boiler” group is set to “24:0”.
appear on the display.
.
5513 463 - 06
61
Page 62
Troubleshooting
Fault Display
Vitotronic 300, GW6B Installation and Service
In the event of a fault, the red fault display flashes at the
control unit. The display shows symbol
Note: If a central fault message facility is connected,
this is started.
For an explanation of fault messages, see chapter
“Fault messages”.
Acknowledge fault display
Tap “Close”. The footer shows
Note: Any connected central fault message facility stops.
If an acknowledged fault is not remedied, the fault
message will be re-displayed the following day at
07:00 h, and the fault message facility restarts.
Calling up acknowledged fault messages
Tap the following buttons:
1.
Note: After tapping the following will be displayed if your heating system has several fault messages
simultaneously:
2. “Faults” The fault messages appear in red and in
chronological order in a list.
.
and “Fault”.
Calling up fault codes from the fault memory (fault history)
The 10 most recent faults (including those remedied) are
saved and can be scanned. Faults are sorted by date.
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “History of faults”
5. Call up further information in the relevant fault with
6. Tap “Reset” to delete the list.
?.
62
5513 463 - 06
Page 63
Vitotronic 300, GW6B Installation and Service
Boiler System Fault Codes
Troubleshooting
Displayed
fault code
0fControl mode.Service “0f” is only displayed in
10Operates as if the outdoor
18Operates as if the outdoor
20Standalone control unit without
28Standalone control unit without
30H With DHW tank: DHW pump
38H With DHW tank: DHW pump
40Mixing valve is being closed.Short circuit, supply temperature
44Mixing valve is being closed.Short circuit, supply temperature
48Mixing valve is being closed.Lead break, supply temperature
4cMixing valve is being closed.Lead break, supply temperature
System characteristicsCauseMeasures
the fault history.
Short circuit, outdoor
temperature was 32°F (0°C).
temperature was 32°F (0°C).
supply temperature sensor
(possibly supply temperature not
high enough)
supply temperature sensor
(possibly supply temperature not
high enough)
ON, boiler is maintained at set
tank temperature.
H Without DHW tank: Boiler is
regulated by the temperature
controller.
ON, boiler is maintained at set
tank temperature.
H Without DHW tank: Boiler is
regulated by the temperature
controller.
temperature sensor.
Lead break, outdoor temperature
sensor.
Short circuit, common supply
temperature sensor
Lead break, common supply
temperature sensor
Short circuit, boiler water
temperature sensor
Lead break, boiler water
temperature sensor
sensor, heating circuit with mixing
valve M2 (heating circuit 2).
sensor, heating circuit with mixing
valve M3 (heating circuit 3).
sensor, heating circuit with mixing
valve M2 (heating circuit 2).
sensor, heating circuit with mixing
valve M3 (heating circuit 3).
Service required
Note: After servicing, set code
“24:0”.
Check outdoor temperature
sensor (see page 121).
Check outdoor temperature
sensor (see page 121).
Check the supply temperature
sensor (see page 121).
Check the supply temperature
sensor (see page 121).
Check boiler water temperature
sensor.
Check boiler water temperature
sensor.
Check supply temperature sensor
(see page 121).
Check supply temperature sensor
(see page 121).
Check supply temperature sensor
(see page 121).
Check supply temperature sensor
(see page 121).
5513 463 - 06
63
Page 64
Troubleshooting
Boiler System Fault Codes (continued)
Vitotronic 300, GW6B Installation and Service
Displayed
fault code
50Tank loading pump on:
51With tank loading system:
52Control modeShort circuit, supply temperature
58Tank loading pump on:
59With tank loading system:
5aControl modeLead break, low loss header
60Boiler with maximum
68Boiler with maximum
System characteristicsCauseMeasures
Short circuit, tank temperature
DHW temperature target =
set supply temperature
Priority control is cancelled.
or
With tank loading system:
Tank heating is started and
stopped via tank temperature
sensor 2.
Tank heating is started and
stopped via tank temperature
sensor 1.
DHW temperature target =
set supply temperature
Priority control is cancelled.
or
With tank loading system:
Tank heating is started and
stopped via tank temperature
sensor 2.
Tank heating is started and
stopped via tank temperature
sensor 1.
temperature, no output
reduction, mixing valve return
temperature control open
temperature, no output
reduction, mixing valve return
temperature control open
sensor 1
Short circuit, DHW tank
temperature sensor 2.
sensor low loss header.
Lead break, DHW tank
temperature sensor 1.
Lead break, DHW tank
temperature sensor 2.
supply temperature sensor.
Short circuit, temperature
sensor aJA.
Lead break, temperature
sensor aJA.
Check tank temperature
sensor (see page 121).
Check the DHW tank
temperature sensor
(see page 121).
Check supply temperature
sensor (see page 121).
Check DHW tank temperature
sensor (see page 121).
Check DHW tank temperature
sensor (see page 121).
Check supply temperature
sensor (see page 121).
Without supply temperature
sensor:
Set code “52:0” in the “General”
group.
Check temperature sensor
(see page 121).
Check temperature sensor
(see page 121).
Without temperature sensor:
Set coding “4a:0” in the
“General” group.
64
5513 463 - 06
Page 65
Vitotronic 300, GW6B Installation and Service
Boiler System Fault Codes (continued)
Troubleshooting
Displayed
fault code
70Shunt pump constantly ON.
78Shunt pump constantly ON
90Control modeShort circuit, temperature sensor
91Control modeShort circuit, temperature sensor
92No solar DHW heating.Short circuit, collector
93Control mode.Short circuit, temperature sensor,
94No solar DHW heating.Short circuit, DHW tank
System characteristicsCauseMeasures
Short circuit, temperature
With tank loading system:
close 3-way mixing valve;
no DHW heating
With tank loading system:
close 3-way mixing valve;
no DHW heating
sensor aJB.
Lead break, temperature
sensor aJA.
/ connection at solar control
module, type SM1.
aÖ, connection at solar control
module, type SM1.
temperature sensor, connection
of temperature sensor & at solar
control module, type SM1 or
sensor at S1 of the Vitosolic.
connection at S3 of the Vitosolic.
temperature sensor, connection
of temperature sensor % at solar
control module, type SM1 or
sensor at S2 of the Vitosolic.
Check temperature sensor (see
page 121).
Check temperature sensor
(see page 121).
Without temperature sensor:
Set code “4b:0” in the
“General” group.
Check temperature sensor /
(see separate installation and
service instructions).
Check temperature sensor aÖ
(see separate installation and
service instructions).
Check sensor at the solar control
unit (see separate installation and
service instructions).
Check sensor at the solar control
unit (see separate installation and
service instructions).
Check sensor at the solar control
unit (see separate installation and
service instructions).
5513 463 - 06
65
Page 66
Troubleshooting
Boiler System Fault Codes (continued)
Vitotronic 300, GW6B Installation and Service
Displayed
fault code
98Control modeLead break, temperature sensor
99Control modeLead break, temperature sensor
9aNo solar DHW heating.Lead break, collector temperature
9bControl modeLead break, temperature sensor,
9cNo solar DHW heating.Lead break, DHW tank temperature
9eControl modeNo supply rate in solar circuit or
9fControl modeFault, solar control module, type
a7Control modeProgramming unit faultReplace the programming unit.
abControl mode, DHW tank may be
System characteristicsCauseMeasures
Check temperature sensor /
(see separate installation and
service instructions).
Check coding address “20” in
the “Solar” group.
Check temperature sensor aÖ
(see separate installation and
service instructions).
Check coding address “20” in
the “Solar” group.
Check sensor at the solar control
unit (see separate installation and
service instructions).
Check sensor at the solar control
unit (see separate installation and
service instructions).
Check sensor at the solar control
unit (see separate installation and
service instructions).
Check solar circuit. Acknowledge
fault message (see separate
installation and service
instructions).
Check solar control unit
(see separate installation
and service instructions).
Insert plug aJB and check
codes.
cold
/, connection at solar control
module, type SM1.
aÖ, connection at solar control
module, type SM1.
sensor, connection of
temperature sensor & at solar
control module, type SM1 or
sensor at S1 of the Vitosolic.
connection to S3 of the Vitosolic.
sensor, connection of
temperature sensor % at solar
control module, type SM1 or
sensor at S2 of the Vitosolic.
flow rate too low, or temperature
limiter has responded.
SM1 or Vitosolic
Displayed if a fault occurs at
these devices that has no fault
message in the Vitotronic.
Tank loading system
configuration fault:
Coding “55:3” in the “DHW”
group has been set, but plug
aJB is not plugged in and/or
codes “4c:1” and “4e:2” in the
“General” group have not been set.
66
5513 463 - 06
Page 67
Vitotronic 300, GW6B Installation and Service
Boiler System Fault Codes (continued)
Troubleshooting
Displayed
fault code
b1Control modeCommunication error,
b5Control modeInternal faultCheck PCB is plugged in
b6Constant modeInvalid hardware recognitionCheck coding address “92” in
b7Boiler water temperature controlCoding card faultPlug in or replace the boiler
baMixing valve closeCommunication error, PCB,
bcControl mode without
bdControl mode without
beControl mode without
bfControl mode
c1Boiler cools downExternal safety equipment at plug
c2Control modeLead break, KM BUS to solar
System characteristicsCauseMeasures
Check connections, and replace
remote control.
remote control
remote control
No communication via LON
programming unit
extension for heating circuits 2
and 3 with mixing valve.
Communication error, Vitotrol
remote control unit, heating
circuit without mixing valve A1
(heating circuit 1).
Communication error, Vitotrol
remote control unit, heating
circuit with mixing valve M2
(heating circuit 2)
Communication error, Vitotrol
remote control unit, heating
circuit with mixing valve M3
(heating circuit 3)
Incorrect LON communication
module.
aBÖ.
control module, type SM1 or
Vitosolic.
the programming unit if required.
correctly.
the “General” group;
H 161: Single boiler system
H 190: Cascade control unit
H 166: Lag boiler control unitNote: Coding “8a:176” in the
“General” group must be
set in order for coding
“92” to be able to be
displayed.
coding card (see page 25).
Check that the PCB and ribbon
cable are plugged in correctly,
and replace PCB if required.
Check connections, lead (see
separate installation and service
instructions) and coding address
“a0” in the “Heating circuit...”
group.
Check connections, lead (see
separate installation and service
instructions) and coding address
“a0” in the “Heating circuit...”
group.
Check connections, lead (see
separate installation and service
instructions)
and coding address “a0” in the
“Heating circuit...” group.
Replace LON communication
module.
Check connection and external
safety equipment
(see page 36 and 37)
Check KM BUS cable and
appliance.
Without solar control unit:
Set code “54:0” in the “General”
group.
5513 463 - 06
67
Page 68
Troubleshooting
Boiler System Fault Codes (continued)
Vitotronic 300, GW6B Installation and Service
Displayed
fault code
c3Control modeCommunication error, AM1
cFControl mode
d3Control modeCommunication error, extension
d4Boiler cools downMCB F2 has responded.Check MCB F2 and jumper
d6Control modeInput DE1 at extension EA1
d7Control modeInput DE2 at extension EA1
d8Control modeInput DE3 at extension EA1
daControl mode without
dbControl mode without
dcControl mode without
ddControl mode without
deControl mode without
dfControl mode without
System characteristicsCauseMeasures
Check connections.
No communication
via LON.
room influence.
room influence
room influence.
room influence.
room influence.
room influence.
extension
Communication error, control
unit
LON communication module.
EA1.
reports a fault.
reports a fault.
reports a fault.
Short circuit, room temperature
sensor, heating circuit without
mixing valve A1 (heating circuit 1).
Short circuit, room temperature
sensor, heating circuit with mixing
valve M2 (heating circuit 2).
Short circuit, room temperature
sensor, heating circuit with mixing
valve M3 (heating circuit 3).
Lead break, room temperature
sensor, heating circuit without
mixing valve A1 (heating circuit 1).
Lead break, room temperature
sensor, heating circuit with mixing
valve M2 (heating circuit 2).
Lead break, room temperature
sensor, heating circuit with mixing
valve M3 (heating circuit 3).
Without AM1 extension:
Set coding “32:0” in the
“General” group.
Check LON communication
module and replace if required.
If no LON communication module
is installed, set code “76:0” in
the “General” group.
Check connections (see page
122). Without extension EA1:
Set code “5b:0” in the
“General” group.
on plug aBA.
Remove fault at appliance
concerned.
Remove fault at appliance
concerned.
Remove fault at appliance
concerned.
Check room temperature
sensor (see page 121).
Check room temperature
sensor (see page 121).
Check room temperature
sensor (see page 121).
Check room temperature
sensor (see page 121).
Check room temperature
sensor (see page 121).
Check room temperature
sensor (see page 121).
68
5513 463 - 06
Page 69
Vitotronic 300, GW6B Installation and Service
Burner Fault Codes
Troubleshooting
Displayed
fault code
d1Boiler cools downBurner faultCheck the burner.
d5Boiler ramps to the electronic
E1Burner control unit in a fault
E2Burner control unit in
E3Burner control unit in a fault
E4Burner shuts downMultiple detection of
E5Burner control unit in
EEBurner control unit in a fault
EFBurner control unit in a fault
E0Operation according to internal
F1Burner control unit in a fault
F2Burner control unit in a fault
F3Ionization flame monitor reports
System characteristicsCauseMeasures
maximum boiler water
temperature limit.
state.
a fault state.
Shortage of gas to gas pressure
switch 2; valve leak test.
state.
a fault state.
state.
state.
burner control unit defaults.
state; system cools down.
state; system cools down.
faulty flame signal during startup or after the post-purge.
No communication between
boiler circuit and cascade
control unit
Valve 1 not tight / gas pressure
switch 2 does not open.
Valve 2 not tight; gas pressure
switch 2 does not close.
Gas valve does not open; gas
valve leaking; gas pressure
switch 2 faulty.
Lead break, strapping plug fJ.Check strapping plug fJ.
undervoltage with return and
renewed undervoltage.
Internal fault of the burner
control unit and during test of
ionization input.
Internal error in feedback from
gas safety valves; output relay
does not respond.
Internal error in feedback from
gas safety valves; output
relay does not respond.
Communication error, burner
control unit.
Flue gas excess temperature;
excessive gas throughput.
Excessive boiler water
temperature.
Gas valve not gas tight (gas is
escaping and burning);
incorrect coding card.
Check communication by
means of a participant check.
Check setting of gas pressure
switch 2; check connecting
cable; replace gas valve.
Check setting of gas pressure
switch 2; check connecting
cable; replace gas valve.
Replace gas valve.
Check the power supply.
Replace burner control unit.
Reset burner control unit;
replace burner control unit.
Reset burner control unit;
replace burner control unit.
Check plug and KM BUS
to burner control unit.
Wait until temperature falls
below the permissible flue gas
temperature. Reset burner
control unit. Check water level;
check heat exchanger surfaces
for contamination; check CO
setting; set gas throughput
according to rated heating
output of boiler (for connection
values, see boiler service
instructions).
Wait until temperature falls
below the permissible boiler
water temperature.
Reset burner control unit.
Check ionization path; replace
coding card; replace gas valve.
2
5513 463 - 06
69
Page 70
Troubleshooting
Burner Fault Codes (continued)
Vitotronic 300, GW6B Installation and Service
Displayed
fault code
F4No flame formation during safety
F5Air pressure switch shows no air
F6Gas pressure switch notifies no
F7Fan pressure is produced during
F8Flame extinguishes during
System characteristicsCauseMeasures
time; ionization flame monitor
reports no flame signal.
No flame formation during safety
time; ionization flame monitor
reports no flame signal.
No flame formation during safety
time; ionization flame monitor
reports no flame signal.
Poor start-up characteristics;
rotary damper does not close.
Flame does not build during the
safety time, no signal captured
by the ionization flame monitor.
Flame does not build during the
safety time, no signal captured
by the ionization flame monitor.
Flame does not build during the
safety time, no signal captured
by the ionization flame monitor.
pressure, fan not running.
Air pressure switch switches off
during operation.
gas pressure.
the air pressure switch idle
state check.
Air pressure switch contact is not
in the idle state.
operation.
Flame extinguishes during
operation.
Flame extinguishes during
operation.
Ionization electrode incorrectly
adjusted; ionization electrode not
plugged in. Ground leakage of
electrode or cable.
Ignition electrodes incorrectly
adjusted, electrodes grounded,
faulty ignition unit, faulty burner
control unit.
Insulation body of ignition or
ionization electrode cracked.
Insert plug of ionization electrode;
check cables; adjust ionization
electrode (see boiler service
instructions)
Adjust ignition electrodes
(see boiler service instructions);
replace ignition unit; replace
burner control unit.
Replace ignition or ionization
electrode
Replace connecting cable;
replace servomotor; replace
burner control unit.
service instructions).
gas valve and replace if required.
Adjust the burner (see boiler
service instructions); if necessary
also adjust the setting screws
when the burner is off to be able
to start the burner).
Replace air pressure switch,
connect or set correctly.
Remove flue gas back pressure;
check if condensate banked up;
reset burner control unit; replace
hose.
Open gas shut-off valve; check
gas flow pressure; replace gas
filter if required; reset burner
control unit; replace gas valve.
instructions).
replace if damaged.
Adjust burner (see boiler service
instructions).
70
5513 463 - 06
Page 71
Vitotronic 300, GW6B Installation and Service
Burner Fault Codes (continued)
Troubleshooting
Displayed
fault code
F9Fan not running; fan speed not
FaFan runs without demand; burner
FdBurner control unit in a fault
80Burner control unit in a fault
81Burner control unit in a fault
82Burner control unit in a fault
83Burner control unit in a fault
88Burner control unit in a fault
89Burner control unit in a fault
b8Constant modeLead break, flue gas temperature
System characteristicsCauseMeasures
Fan faulty; cables are faulty or
reached.
Status duration too long, fan
ramp-up.
Varying fan speed
No fan feedback.Fan faulty, external fan power
control unit in a fault state.
state; system cools down; burner
control unit locked out.
state; system cools down;
burner control unit locked out.
state.
state; system cools down;
burner control unit locked out.
state.
state.
state.
broken.
Internal fault; fan cannot reach
its set value.
Fan faulty, cable a-ÖA faulty or
broken. Check cable a-ÖA;
check external power supply;
replace the cable or fan; remove
foreign bodies.
supply not connected or faulty
cable a-ÖA or cable broken, fan
blocked (poss. by foreign bodies).
Fan does not reach idle state,
cable a-ÖA faulty, fan faulty,
faulty burner control unit.
Burner control unit in a fault
state.
Short circuit, boiler water
temperature sensor, burner
control unit.
Sensor drift, boiler water
temperature sensor, burner
control unit.
Short circuit, flue gas
temperature sensor (A or B),
burner control unit.
Sensor drift, flue gas temperature
sensor (A or B), burner control
unit.
Lead break, boiler water
temperature sensor, burner
control unit.
Lead break, flue gas temperature
sensor (A or B), burner control
unit.
sensor
Check cables and replace the fan
if required
Replace fan or burner control
unit.
Check cable; replace cable
a-ÖA or fan.
Check cable a-ÖA; check
external power supply; replace
cable or fan; remove foreign
bodies.
Fan subject to wind influence,
check flue outlet and fan, replace
cable a-ÖA, replace fan,
replace burner control unit.
Read off fault at the burner
control unit display and
programming unit (boiler service
instructions).
Check lead and dual sensor;
replace sensor if required.
Check lead and dual sensor;
replace sensor if required.
Check lead and sensors (A or B),
replace sensor if required.
Check lead and sensors (A and
B), replace sensor if required.
Check lead and dual sensor;
replace sensor if required.
Check lead and sensors (A and
B), replace sensor if required.
Remove temperature sensor.
Set code “1f:0” in the “Boiler”
group.
Fault message to the burner control unit:
Refer to the Boiler Service Instructions
Note: If LON participant faults occur, “Fault participant”
... is displayed.
5513 463 - 06
71
Page 72
Function Description
Boiler Water Temperature Control
Vitotronic 300, GW6B Installation and Service
Brief description
H The boiler water temperature is regulated by modulating
the burner.
H The set boiler water temperature is determined from
the following coding:
– Set supply temperature of the heating circuits
connected to the control unit and the heating circuits
connected via the LON BUS
– External demand
– DHW temperature target
H When the DHW tank is heated, the default set boiler
water temperature is 20 K above the set DHW
temperature (adjustable via coding “60” in the
“DHW” group).
Emissions test function
In multi boiler systems, enable the emissions test function
on all control units.
The following functions are activated:
H Burner start
H Starting all pumps
Note: Only the heating circuit pump is switched ON
in the case of lag boiler control.
H Mixing valve remains set to control function
Function duration < 30 min:
The burner operates at 100% output until the
temperature limiter in the burner control unit switches
off. The burner then cycles, with 100% output, around
the value at the temperature limiter.
Function duration > 30 min (continuous):
Boiler water temperature at max. set value,
e.g. 194°F (90°C).
The burner is operated in modulating mode.
This prevents excessive cycling if emissions testing
is carried out over an extended period.
Cascade Control Unit
72
Brief description
The supply temperature is regulated by starting or
stopping the burners or by starting/stopping individual
burner
stages.
H Standalone control (see page 73)
H Sequential control (see page 73)
H Subject to system version, a difference is made
between the condensing strategy (see page 74)
and 2 conventional boiler strategies (see pages 75
and 76).
5513 463 - 06
Page 73
Vitotronic 300, GW6B Installation and Service
Cascade Control Unit (continued)
Function Description
Set supply temperature
The set supply temperature is determined from the
following coding:
H Set supply temperature of heating circuit without
mixing valve A1 (heating circuit 1) and heating circuits
with mixing valve M2 (heating circuit 2) and M3
(heating circuit 3).
H Set supply temperature of further consumers.
H DHW temperature target.
H External demands.
Upper control range limits:
Maximum system supply temperature limit
(coding “37” in the “Cascade” group).
Lower control range limits:
Minimum system supply temperature limit
(coding “36” in the “Cascade” group).
Standalone control
Note: Vitocrossal 200, type CM2, operate in parallel
and with condensing strategy
Boilers connected in parallelBoilers connected in series
H Without and with supply temperature sensor
(see the following table).
H The cascade control specifies the set boiler water
temperature for all currently active boilers. Every boiler
control unit regulates to the specified set value.
The following control strategies are available:
H Condensing strategy (see page 77)
H Conventional boiler strategy 1 (see page 79)
H Conventional boiler strategy 2 (see page 79)
With supply temperature sensorWithout supply temperature sensor
Set coding “3b:1” or “3b:3” in the “Cascade” group.
The control deviation is calculated from the set supply
temperature and the actual supply temperature to
determine the start and shutdown criteria.
5513 463 - 06
H Without and with supply temperature sensor
(see the following table).
H The control strategy is set automatically to
conventional boiler strategy 2, coding “3c:2” in the
“Cascade” group (see page 79).
H The cascade control specifies the set boiler water
temperature for all currently active boilers. Every boiler
control unit regulates to the specified set value. If the
lead boiler (condensing boiler) does not achieve the
specified set value, it will only act to control the return
temperature of the conventional boiler downstream.
The conventional boiler is started late and is also shut
down late.
Set coding “3b:0” or “3b:2” in the “Cascade” group.
To determine the start and stop criteria, the control
deviation is calculated from the set boiler water
temperature and the estimated average actual boiler
water temperature of the currently active boilers.
Only boilers with open motorized isolation valves are
taken into consideration.
Sequential control
H With supply temperature sensor.
H Set coding “3b:4” in the “Cascade” group.
H The control strategy is set automatically to
conventional boiler strategy 2, coding “3c:2”
in the “Cascade”group (see page 76).
H The cascade control unit regulates to the specified set
supply temperature by stipulating the output for each
individual boiler. The lead boiler can be operated in
modulating mode. All other boilers are operated in two
stages via a specified output (incl. modulating burners).
73
Page 74
Function Description
Cascade Control Unit (continued)
Vitotronic 300, GW6B Installation and Service
Control strategies
Condensing strategy
Benefit:
Optimum utilization of the condensing effect and long
burner runtimes
Set coding “3c:0” in the “Cascade” group.
It is the aim of the condensing strategy to operate
as many boilers as possible at the lowest output level.
H Starting criterion:
An output statement causes the boilers to be started
(coding “3d:1” in the “Cascade” group).
An additional boiler will start if the current heat demand
can also be covered by the currently active boilers plus
the next boiler in the boiler sequence (see page 52).
H Shutdown criterion:
The boilers are shut down via a shutdown integral.
The shutdown criterion is met when the shutdown
integral exceeds a limit set at coding “46” in the
“Cascade” group and the boiler started last will be shut
down.
Example (coding “3c:0” in the “Cascade” group)
Two-boiler system with modulating burners:
H Boiler 1: 100% rated heating output
(base load set to 33%)
H Boiler 2: 100% rated heating output
(base load set to 33%)
Starting
Shutdown
74
5513 463 - 06
Page 75
Vitotronic 300, GW6B Installation and Service
Cascade Control Unit (continued)
Function Description
Control strategies
Conventional boiler strategy 1
Benefit:
As few boilers as possible are active.
Set coding “3c:1” in the“Cascade” group.
Conventional boilers are preferably operated at their
upper output range, to reliably prevent formation of
condensate due to low return temperatures. An additional
boiler will only be started if the maximum output of all
currently active burners is insufficient to achieve the set
supply temperature. A boiler will be shut down when the
remaining boilers can achieve the required output on their
own.
H Starting criterion:
The boilers are started via a starting integral. The next
boiler in the boiler sequence will be started if the value
set in coding “45” in the “Cascade” group is exceeded
(see page 52).
H Shutdown criterion:
An output reduction causes the boiler to shut down
(coding “3d:1” in the “Cascade” group). A boiler is shut
down when the current heat demand can be covered
without the boiler that was started last.
Example:
Two-boiler system with modulating burners:
H Boiler 1: 100% rated heating output
(base load set to 33%)
H Boiler 2: 100% rated heating output
(base load set to 33%)
Conventional boiler strategy 1 (coding “3c:1” in the “Cascade” group)
Starting
Shutdown
5513 463 - 06
75
Page 76
Function Description
Cascade Control Unit (continued)
Vitotronic 300, GW6B Installation and Service
Control strategies
Conventional boiler strategy 2
Benefit:
Long burner runtimes.
Coding “3c:2” in the “Cascade” group (factory set
condition).
An additional boiler will only be started if the maximum
output of all currently active burners is insufficient to
achieve the set supply temperature.
A boiler will be shut down if the burners were ramped
down to their minimum output because of a major
negative control deviation and the output is still too high.
H Starting criterion:
The boilers are started via a starting integral. The next
boiler in the boiler sequence will be started if the value
set in coding “45” in the “Cascade” group is exceeded
(see page 52).
H Shutdown criterion:
The boilers are shut down via a shutdown integral.
The shutdown criterion is met when the shutdown
integral exceeds a limit set at coding “46” in the
“Cascade” group and the boiler started last will be
shut down.
Example:
Two-boiler system with modulating burners:
H Boiler 1: 100% rated heating output
(base load set to 33%)
H Boiler 2: 100% rated heating output
(base load set to 33%)
Conventional boiler strategy 2 (coding “3c:2” in the “Cascade” group)
Starting
Shutdown
76
5513 463 - 06
Page 77
Vitotronic 300, GW6B Installation and Service
Heating Circuit Control Unit
Function Description
Only for single boiler and cascade control units
Brief description
H The control unit features control circuits for one heating
circuit without mixing valve A1 (heating circuit 1) and
two heating circuits with mixing valve M2 (heating
circuit 2) and M3 (heating circuit 3).
H The set supply temperature of each boiler is determined
from the following coding:
– Outdoor temperature
– Set room temperature
– Operating mode
– Heating curve slope and shift
H The supply temperature of the heating circuit without
mixing valve corresponds to the common system supply
temperature.
H The supply temperature of the heating circuits with
mixing valve is regulated by the stepped opening or
closing of the mixing valves.
The mixing valve motor control changes the actuating
and pause times subject to the control differential
(control deviation).
Functions
The heating circuit without mixing valve is subject to the
boiler water temperature and its control range limits.
The heating circuit pump is the only actuator.
The supply temperature of the heating circuits with
mixing valve is captured by the supply temperature sensor
of the relevant heating circuit.
H Upper control limit:
Electronic maximum supply temperature limit
coding address “c6” in the “Heating circuit...” group.
H Lower control range limit:
Electronic minimum supply temperature limit
coding address “c5” in the “Heating circuit...” group.
Time program
The control unit switches over according to the time
program. In the “Heating and DHW” operating program,
the control unit switches between “Central heating with
standard room temperature” and “Central heating with
reduced room temperature”.
Every operating mode has its own set level.
4 time phases per day can be selected.
Outdoor temperature
A heating curve must be set for matching the control
unit to the building and the heating system.
The heating curve characteristics determine the set
boiler water temperature subject to outdoor temperature.
The control unit uses an average outdoor temperature.
This comprises the actual and the adjusted outdoor
temperature.
Room temperature
In conjunction with a remote control and room
temperature hook-up (coding “b0” in the “Heating
circuit...”) group:
Compared with the outdoor temperature, the room
temperature has a greater influence on the set boiler
water temperature (changed at coding “b2” in the
“Heating circuit...” group).
In conjunction with heating circuits with mixing valve:
For control differentials (actual value deviation) above
2 K room temperature, the influence can be increased
further (coding “b6” in the “Heating circuit...” group):
H Quick heat-up
The set room temperature must be raised by at least
2 K by the following measures:
– Enabling comfort mode
– Changing from central heating with reduced
temperature to central heating with standard
temperature
– Start optimization (coding “b7” in the “Heating
circuit...” group) Quick heat-up will stop when the
set room temperature has been reached.
H Quick setback
The set room temperature must be reduced by at least
2 K by the following measures:
– Activating economy mode
– Changing from central heating with standard
temperature to central heating with reduced
temperature
– Shutdown time optimization (coding address “c1”
in the “Heating circuit...” group)
Quick setback ends when the set room temperature
has been reached.
5513 463 - 06
77
Page 78
Function Description
Heating Circuit Control Unit (continued)
Vitotronic 300, GW6B Installation and Service
DHW temperature
Priority control
H With priority control: (coding address “a2:2” in the
“Heating circuit...” group):
The set supply temperature will be adjusted to 32°F
(0°C) during tank heating. The mixing valve closes
and the heating circuit pump is switched off.
H Without priority control:
The heating circuit control unit continues to operate
with the same set value.
H With modulating priority control in conjunction with
heating circuits with mixing valve:
The heating circuit pump remains switched on.
During tank heating the set supply temperature
of the heating circuit will be reduced until the set
boiler water temperature has been reached.
The set supply temperature is determined from the
following coding:
– Outdoor temperature
– Differential between the set and the actual boiler
water temperature
– Heating curve slope and shift
– Set coding “a2” in the “Heating circuit...” group
Heating circuit pump logic – Economy circuits
The heating circuit pump is switched OFF [set supply
temperature set to 32°F (0°C)] if one of the following
criteria is met:
H The outdoor temperature selected in coding “a5”
in the “Heating circuit...” group exceeds the set value.
H The adjusted outdoor temperature exceeds the value
set in coding“a6” in the “Heating circuit...” group.
H The mixing valve has been attempting to close for more
than 12 min. (mixing valve economy function, coding
“a7” in the “Heating circuit...” group).
H The pump idle time selected in coding “a9”
in the “Heating circuit ...” group is reached.
Requirements:
– There is no risk of frost.
– Coding “b0” in the “Heating circuit...” group
must be set to 0.
Note: If, during the pump idle time, the system
is switched to heating mode or the set room
temperature is increased, the heating circuit
pump is switched ON,even if the time has
not yet elapsed.
H The actual room temperature exceeds the value
set in coding “b5” in the “Heating circuit ...” group.
System dynamics
The mixing valve control characteristics can be influenced
at coding “c4” in the “Heating circuit...” group.
Central control
Coding “7a” in the “General” group enables you
to program central control to one heating circuit.
The operating and holiday program then applies to
all additional heating circuits of the system.
For these heating circuits, when the operating and
holiday program is enabled,“Central control” is displayed.
Any holiday programs that may have been set will be
deleted.
Party and economy modes cannot be enabled on all
control units.
Frost protection
The supply temperature is held in accordance with the
heating curve for the reduced set room temperature,
but at least at 50°F (10°C).
A variable frost limit can be set in line with coding
address “a3” in the “Heating circuit...” group.
78
5513 463 - 06
Page 79
Vitotronic 300, GW6B Installation and Service
Heating Circuit Control Unit (continued)
Legend
A Max. boiler water temperature
B Slope = 1.8 for heating circuit without mixing valve
C Slope = 1.2 for heating circuit with mixing valve
D Boiler water temperature (with a differential
temperature = 8 K)
E Lower boiler water temperature, defaulted by the
boiler coding card
Supply temperature
Legend
A Maximum supply temperature limit
(coding “37” in the “Cascade” group)
B Slope = 1.8 for heating circuit without mixing valve
C Slope = 1.2 for heating circuit with mixing valve
D Common supply temperature (at a differential
temperature = 8 K)
E Lower common supply temperature
Function Description
Supply temperature control single boiler control unit
Differential temperature:
The differential temperature can be set at coding “9f”
in the “General”group, factory set condition: 8 K.
The differential temperature is the minimum value by
which the boiler water temperature should be higher
than the highest currently required supply temperature
of the heating circuit with mixing valve.
H System with only one heating circuit with mixing valve:
The set boiler water temperature will be automatically
regulated to 8 K above the set supply temperature.
H System with heating circuit without mixing valve and
heating circuit with mixing valve:
The set boiler water temperature operates in
accordance with its own heating curve. The differential
temperature of 8 K towards the set supply temperature
is set at the factory.
Supply temperature control cascade control unit
Differential temperature:
The differential temperature can be set at coding “9f”
in the “General” group, factory set condition 8 K.
The differential temperature is the value by which the
common supply temperature should be higher than the
highest currently required supply temperature of the
heating circuit with mixing valve.
H System with only one heating circuit with mixing valve:
The common set supply temperature is regulated
automatically to 8 K above the set supply temperature
of the heating circuit with mixing valve.
H System with heating circuit without mixing valve and
heating circuits with mixing valve:
The common set supply temperature operates in
accordance with its own heating curve. The differential
temperature of 8 K towards the set supply temperature
of the heating circuits with mixing valve is set at the
factory.
5513 463 - 06
79
Page 80
Function Description
Heating Circuit Control Unit (continued)
Vitotronic 300, GW6B Installation and Service
Example using the settings in the factory set condition
Legend
A Heating curve for operation with standard room
temperature
B Heating curve for operation with reduced room
temperature
Example using the settings in the factory set condition
Raising the reduced room temperature
During operation with reduced room temperature,
the reduced set room temperature can be automatically
raised subject to the outdoor temperature.
The temperature is raised in accordance with the selected
heating curve, but no higher than the set standard room
temperature.
The outdoor temperature limits for the start and end of
temperature raising can be set in coding “f8” and “f9”
in the “Heating circuit...” group.
Reducing the heat-up time
During the transition from operation with reduced room
temperature to operation with standard room temperature,
the boiler water or supply temperature will be raised in
accordance with the selected heating curve. The boiler
water or supply temperature increase can be automatically
raised.
The value and duration for the additional raising of the
boiler water temperature or set supply temperature can
be set in coding “fa” and “fb” in the “Heating circuit...”
group.
Control sequence
Mixing valve circuit
The mixing valve motor will not be switched within the
“neutral zone” (±1 K).
Supply temperature drops
(Set value –1 K)
The mixing valve motor receives the signal “mixing valve
open”. The signal duration lengthens with an increasing
control differential. The duration of pauses reduces with
an increasing control differential.
Legend
A Start of operation with standard room temperature
B Set boiler water or supply temperature in accordance
with the selected heating curve
C Set boiler water or supply temperature in accordance
with coding “fa”:
122°F (50°C) + 20% = 146°F (60°C)
D Duration of operation with higher boiler water or set
supply temperature in accordance with coding
“fb”: 60 min
80
Supply temperature rises
(set value +1 K)
The mixing valve motor receives the signal “mixing valve
close”. The signal duration lengthens with an increasing
control differential. The duration of pauses reduces with
an increasing control differential.
5513 463 - 06
Page 81
Vitotronic 300, GW6B Installation and Service
DHW Tank Temperature Control
Function Description
Brief description
H The tank temperature control is a constant temperature
control function. This is achieved by starting and
stopping the DHW pump. The switching differential is
±2.5 K.
H When the DHW tank is heated, a set supply
temperature is specified that is 20 K higher than
the set DHW temperature (adjustable at coding
“60” in the “DHW” group).
Functions
Time program
An automatic or an individual time program may be
selected for DHW pump and the DHW recirculation pump.
Compared with the heating circuit heatup phase, DHW
heating starts 30 min earlier in automatic mode.
The individual time program enables up to 4 time
phases per day to be set for DHW pump and the DHW
recirculation pump for every day of the week.
All tank heating sequences will be completed
independently of the time program.
In conjunction with coding “7f” in the “General” group
H Detached house
Coding “7f:1”:
– Automatic mode
The heating times for heating circuit 1 are applied
to systems with two or three heating circuits.
– Individual time program
The time phases for DHW pump and the DHW
recirculation pump have the same effect on all
heating circuits.
H Apartment building
Coding “7f:0”:
– Automatic mode
For systems with two or three heating circuits,
the heating times for the respective heating circuit
will be applied.
– Individual time program
The time phases for DHW pump and the DHW
recirculation pump can be adjusted individually for
each heating circuit.
Priority control
H With priority control: (coding
“a2:2” in the “Heating circuit...” group):
The set supply temperature will be adjusted to 32°F
(0°C) during tank heating. The mixing valve closes
and the heating circuit pump is switched off.
H Without priority control:
The heating circuit control unit continues to operate
with the same set value.
H With modulating priority control in conjunction with
heating circuits with mixing valve:
The heating circuit pump remains switched on.
During tank heating the set supply temperature of the
heating circuit will be reduced until the set boiler water
temperature has been reached.
The set supply temperature is determined from the
following coding:
– Outdoor temperature
– Differential between the set and the actual boiler
water temperature
– Heating curve slope and shift
– Set coding “a2” in the “Heating circuit...” group
Frost protection
The DHW tank will be heated to 68°F (20°C) if the DHW
temperature falls below 41°F (5°C).
Forth phase heating function
(auxiliary function for DHW heating)
This function is activated by providing a second set DHW
temperature at coding “58” in the “DHW” group and
activating the fourth DHW phase for DHW heating.
Set DHW temperature
The set DHW temperature can be adjusted between 50
and 140°F (10 and 60°C).
Coding “56” in the “DHW” group enables the set range
to be extended to 203°F (95°C).
Coding “66” in the “DHW” group enables the set value of
the programming unit and/or remote control Vitotrol 300
to be assigned.
DHW recirculation pump
This delivers hot water to the draw-off points at
adjustable times. Four time phases can be selected
at the control unit for every day.
5513 463 - 06
81
Page 82
Function Description
DHW Tank Temperature Control (continued)
Vitotronic 300, GW6B Installation and Service
Auxiliary circuits
DHW heating in conjunction with the heating circuits can
be disabled or enabled by changing over the operating
program (see coding “d5” in the “Heating circuit...”
group).
System with tank loading system
The above functions also apply in conjunction with tank
loading systems.
Set the following coding:
“55:3” in the “DHW” group; “4c:1”,
“4e:2” in the “General” group.
The DHW tank is only reheated by the boiler
if the temperature falls below this value.
System with solar control unit
A third set DHW temperature can be assigned at coding
“67” in the “DHW” group.
The DHW tank is only reheated by the boiler
if the temperature falls below this value.
Controlled sequence single boiler control
Coding “55:0” in the “DHW” group; tank heating
The DHW tank goes cold (set value –2.5 K, adjustable
via coding “59”):
H The set boiler water temperature is set 20 K higher
than the set DHW temperature (adjustable via
coding “60”).
H Pump on:
– Starting the DHW pump is subject to boiler water
temperature (coding “61:0”).
The DHW pump starts when the boiler water
temperature is 7 K higher than the DHW temperature.
– Starting the DHW pump for tank heating
immediately (coding “61:1”).
The DHW tank is hot (set value +2.5 K):
H The set boiler water temperature is reset to the
weather-compensated set value.
H Pump delay off:
The DHW pump runs on after tank heating
until one of the following criteria is met:
– The differential between the boiler water temperature
and the DHW temperature is less than 7 K.
– The weather-compensated set boiler water
temperature has been reached.
– The set DHW temperature is exceeded by 5 K.
– The set max. delay off time is reached (coding “62”).
H Without pump delay off (coding “62:0”).
Coding “55:1” in the “DHW” group;
adaptive tank heating
With adaptive tank heating, the speed of the temperature
rise during DHW heating is taken into account.
The DHW tank goes cold (set value –2.5 K,
adjustable via coding “59”):
H The set boiler water temperature is set 20 K higher
than the set DHW temperature (adjustable via coding
“60”).
H Pump on:
– Starting the DHW pump is subject to boiler water
temperature (coding “61:0”):
The DHW pump starts when the boiler water
temperature is 7 K higher than the DHW temperature.
– Starting the DHW pump immediately (coding “61:1”).
The DHW tank is hot:
H The control unit checks whether the boiler will still
be required to supply heating energy after the tank
has been heated up or whether residual boiler heat
should be transferred to the DHW tank.
Accordingly, the control unit determines the burner
and DHW pump stop times to prevent the set
DHW temperature being substantially exceeded after
the tank has been heated up.
Coding “55:2” in the “DHW” group;
tank temperature control with 2 tank
temperature sensors
Tank temperature sensor 1 enables the DHW pump and
is evaluated for stop conditions during the pump delay
off time.
Tank temperature sensor 2:
Tank heating will start early if a lot of hot water
is drawn off. Tank heating will terminate early if
no hot water is drawn off.
DHW tank goes cold:
H Set value −2.5 K, change at coding “59”
or
H Actual DHW temperature at sensor 2 < set DHW
temperature x factor for start time (adjustment at
coding “69”)
The DHW tank is hot:
H set value +2.5 K
and
H Actual DHW temperature at sensor 2 > set DHW
temperature x factor for stop time (adjustment at
coding “68”)
82
5513 463 - 06
Page 83
Vitotronic 300, GW6B Installation and Service
DHW Tank Temperature Control (continued)
Function Description
Coding “55:3” in the “DHW” group;
tank temperature control tank loading system
The DHW tank goes cold (set value −2.5 K; change
at coding “59”):
H The set boiler water temperature is set 20 K higher than
the set DHW temperature (adjustable via coding “60”).
H The primary pump in the tank loading system starts.
H The 3-way mixing valve opens and then regulates to
the specified set value.
H The DHW pump cycles (briefly switches on and off)
until the set supply temperature has been reached (set
DHW temperature + 5 K).
Then it runs constantly. If, during heating, the actual
value falls below the required set temperature,
the DHW pump will temporarily cycle again.
The DHW tank is hot:
H Tank temperature sensor 1:
Actual value ≥ set value
and
Tank temperature sensor 2:
Actual value > set value –1.5 K:
H The set boiler water temperature is reset to the
weather-compensated set value.
H The DHW pump stops immediately when the 3-way
mixing valve is fully opened.
or
H The DHW pump stops after expiry of the delay off time
that is selected at coding “62”.
Controlled sequence cascade control
The following coding in the “DHW” group influence the
controlled sequence.
Tank heating (coding “55:0”)
The DHW tank goes cold (set value –2.5 K, adjustable
via coding “59”):
H The common set supply temperature is set 20 K higher
than the set DHW temperature (adjustable via coding
“60”).
The DHW tank is hot (set value +2.5 K):
H The common set supply temperature is returned to
the set weather-compensated value.
H With pump delay off:
The DHW pump runs on after tank heating
until one of the following criteria is met:
– The set DHW temperature is exceeded by 5 K.
– The set max. delay off time is reached (coding “62”).
H Without pump delay off (coding “62:0”).
Adaptive storage tank heating enabled (coding “55:1”)
With adaptive tank heating, the speed of the temperature
rise during DHW heating is taken into account.
The DHW tank goes cold (set value –2.5 K, adjustable via
coding “59”):
H The common set supply temperature is set 20 K higher
than the set DHW temperature (adjustable via coding
“60”).
The DHW tank is hot:
H The control unit checks whether the boiler will still be
required to supply heating energy after the tank has
been heated up or whether residual boiler heat should
be transferred to the DHW tank.
Accordingly, the control unit determines the burner and
circulation pump stop times to prevent the set DHW
temperature being substantially exceeded after the
tank has been heated up.
5513 463 - 06
83
Page 84
Function Description
DHW Tank Temperature Control (continued)
Vitotronic 300, GW6B Installation and Service
Storage tank temperature control with 2 temperature
sensors (coding “55:2”)
Tank temperature sensor 1 enables the DHW pump for
tank heating and is evaluated for stop conditions during
the pump delay off time.
Tank temperature sensor 2:
Tank heating will start early if a lot of hot water is drawn
off. Tank heating will terminate early if no hot water is
drawn off.
DHW tank goes cold:
H Set value –2.5 K, adjustable via coding “59”
or
H Actual DHW temperature at sensor 2 < set DHW
temperature x factor for start time (adjustment at
coding “69”)
The DHW tank is hot:
H Set value +2.5 K
and
H Actual DHW temperature at sensor 2 > set DHW
temperature x factor for stop time (adjustment at
coding “68”)
Coding “55:3” in the “DHW” group;
tank temperature control tank loading system
The DHW tank goes cold (set value –2.5 K, adjustable via
coding “59”):
H The common set supply temperature is set 20 K higher
than the set DHW temperature (adjustable via coding
“60”).
H The primary pump in the tank loading system starts.
H The 3-way mixing valve opens and then regulates to
the specified set value.
H The DHW pump cycles (briefly switches on and off)
until the set supply temperature has been reached (set
DHW temperature + 5 K).
Then it runs constantly.
If, during heating, the actual value falls below the
required set temperature, the circulation pump for
tank heating will temporarily cycle again.
The DHW tank is hot:
H Tank temperature sensor 1:
Actual value ≥ set value
and
Tank temperature sensor 2:
Actual value > set value -1.5 K:
H The common set supply temperature is returned to the
set weather-compensated value.
H The DHW pump stops immediately when the 3-way
mixing valve is fully opened.
or
The DHW pump stops after expiry of the delay off
time that is selected at coding “62”.
84
5513 463 - 06
Page 85
Vitotronic 300, GW6B Installation and Service
Calling up Coding Levels
Display for coding levels
Legend
A Coding
B Number of coding
C Value of coding
D Coding description
Coding levels
H Coding are split into the following groups:
– “General”
– “Combustion controller”
– “DHW”
– “Solar”
– “Heating circuit 1/2/3”
– “Boiler”
– “Cascade”
– “All coding”
In this group, all coding in the coding levels
are listed in ascending order (except the coding
in the “Solar” group).
H Heating systems with one heating circuit without
mixing valve and one or two heating circuits with
mixing valve:
In the following, the heating circuit without mixing
valve is designated “Heating circuit 1” and the heating
circuits with mixing valve as “Heating circuit 2” or
“Heating circuit 3”.
H The selected designation appears if the heating circuits
have been designated individually.
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “System configuration”
5. “Coding level 1”
or
“Coding level 2”:
Enter “viexpert” password.
6. Select group.
7. Select coding.
8. “Change”
9.
for the required value in line with the following
tables.
Resetting Coding to their Factory Set Condition
5513 463 - 06
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “System configuration”
5. “Coding level 1”
or
“Coding level 2”:
Enter “viexpert” password.
6. “Reset coding”
85
Page 86
Coding level 1
“General” Group
Coding
Coding in the factory set conditionPossible change
System design
00:1System version 1:
One heating circuit without mixing valve
A1 (heating circuit 1), without DHW
heating
00:2
to
00:10
Vitotronic 300, GW6B Installation and Service
For system schemes, see
the following table:
Value address
00: ...
2One heating circuit without mixing valve A1 (heating circuit 1), with DHW heating;
3One heating circuit with mixing valve M2 (heating circuit 2), without DHW heating.
4One heating circuit with mixing valve (heating circuit 2), with DHW heating
5One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit with mixing valve
6One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit with mixing valve
7Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3),
8Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3), with DHW
9One heating circuit without mixing valve A1 (heating circuit 1), two heating circuits with mixing
10One heating circuit without mixing valve A1 (heating circuit 1), two heating circuits with mixing
Coding in the factory set conditionPossible change
Servomotor runtime
40:...
“Boiler circuit pump”
53:1With low loss header:
LON participant no.
77:1LON participant number. 77:1
“Detached house/apartment building”
7f:1Detached house7F:0Apartment building
Description
recognized automatically.
M2 (heating circuit 2), without DHW heating; recognized automatically.
M2 (heating circuit 2), with DHW heating; recognized automatically.
without DHW heating.
heating.
valve M2 (heating circuit 2) and M3 (heating circuit 3), without DHW heating; recognized
automatically.
valve M2 (heating circuit 2) and M3 (heating circuit 3), with DHW heating; recognized automatically.
Actuator runtime at plug gSA1.
Boiler circuit pump only runs on demand
if the burner is operational
(with delay off time)
40:5
to
40:199
53:0Boiler circuit pump runs permanently -
to
77:99
Adjustable from 5 to 199 sec.
subject to warm weather shutdown
Adjustable from 1 to 99:
1 - 8 = Boiler/heating circuit control unit
9 = Cascade control unit
10 - 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
Separate adjustment of holiday program
and time program for DHW heating
possible.
86
5513 463 - 06
Page 87
Vitotronic 300, GW6B Installation and Service
Coding level 1
“General” Group (continued)
Coding in the factory set conditionPossible change
Adjustable from 32 to 261°F (0 to 127°C)
(limited by boiler specific coding)
5513 463 - 06
87
Page 88
Coding level 1
Vitotronic 300, GW6B Installation and Service
“Combustion Controller” Group
Coding in the factory set conditionPossible change
“Max operational output”
02:100100% of rated heating output02:0
to
02:100
“Gas type”
03:0Natural gas03:1LPG
“Altitude”
04:0LA: ≤ 1500 m04:1HA: > 1500 m
“Max boiler temperature”
06:95Set to 203°F (95°C)06:5
to
06:127
“Integral threshold value of controller”
08:30Set to 30 Kmin08:1
to
08:255
“Runtime optimization”
09:1Integral method09:0Minimum pause
Adjustable from 0 to 100%
(0% represents burner minimum firing rate)
Adjustable from 41 to 261°F (5 to 127°C)
Adjustable from 1 to
255 Kmin
“Boiler” Group
Coding in the factory set conditionPossible change
“Single boiler and multi boiler system”
01:2Multi-boiler system with Viessmann-cascade
or LON-cascade
“Consecutive boiler number in multi boiler systems”
07:1Consecutive boiler number in multi boiler
systems
“Flue gas temperature sensor”
1f:0Do not adjust!----
“Service interval”
21:0No service interval (hours run) selected.21:1
“Interval for service”
23:0No interval for service23:1
”Service” display”
24:0No “Service” display24:1“Service” is displayed (the address is
01:1Single boiler system
01:3Do not adjust!
07:2
to
07:8
to
21:100
to
23:24
Adjustable from 1 to 8
The number of hours run before the burner
should be serviced is adjustable from 100 to
10000 h; 1 step
Adjustable from 1 to
24 months.
automatically set and must be manually
reset after a service has been carried out).
100 h
88
5513 463 - 06
Page 89
Vitotronic 300, GW6B Installation and Service
Coding level 1
“Cascade” Group
Coding in the factory set conditionPossible change
“Number of boilers connected to the cascade”
35:88 boilers35:1
to
35:8
“Minimum system supply temperature limit”
36:0Electronic minimum system supply
temperature limit set to 32°F (0°C).
“Maximum system supply temperature limit”
37:80Electronic maximum system supply
temperature limit set to 176°F (80°C).
“Lead boiler or boiler sequence changeover”
38:0No lead boiler or boiler sequence
changeover (see function description
in chapter “Cascade control”)
“Permanent lead boiler”
39:0No permanent lead boiler39:1
“Permanent last boiler”
3a:0No permanent last boiler3a:1
“Type of control”
3b:1Standalone parallel boiler circuit:
With supply temperature sensor
(see page 71)
“Control strategy”
3c:0Condensing strategy (see page 74)3c:1Conventional boiler strategy 1 (see page 75)
“Output statement”
3d:1Output statement for condensing strategy
and conventional boiler strategy 1
36:1
to
36:127
37:20
to
37:127
38:1Lead boiler changeover:
38:2
to
38:200
to
39:8
to
3a:8
3b:0Standalone parallel boiler circuit:
3b:2Standalone serial boiler circuit:
3b:3Standalone serial boiler circuit:
3b:4Sequential control method with supply
3c:2Conventional boiler strategy 2 (see page 76)
3d:0No output statement
1 to 8 boilers
Adjustable from 32 to 261°F (0 to 127°C)
(only when operating with standard room
temperature)
Adjustable from 68 to 261°F (20 to 127°C)
Note: Value must be lower than the lowest
value of coding “06” in the
“Combustion controller” group of every
control unit.
Every first day of the month, the boiler with
the shortest number of hours run by its burner
becomes the lead boiler.
Lead boiler changeover after 200 to 20,000
hours run
1 step
Permanent lead boiler is boiler 1, 2, 3 or 8
Permanent last boiler is boiler 1, 2, 3 or 8
With supply temperature sensor (see page 73)
Without supply temperature sensor
(see page 73)
With supply temperature sensor (see page 73)
temperature sensor (see page 73)
Note: Control only in accordance with
conventional boiler strategy 2
100 hours run
5513 463 - 06
89
Page 90
Coding level 1
“Cascade” Group (continued)
Coding in the factory set conditionPossible change
“ECO threshold boiler 1”
41:31No ECO threshold boiler 141:−30
to
41:+30
“ECO threshold boiler 2”
42:31No ECO threshold boiler 242:−30
to
42:+30
“ECO threshold boiler 3”
43:31No ECO threshold boiler 343:−30
to
43:+30
“ECO threshold boiler 4”
44:31No ECO threshold boiler 444:−30
to
44:+30
“Start integral threshold”
45:60Set to 60 K x minute45:1
to
45:255
“Stop integral threshold”
46:40Set to 40 K x minute46:1
to
46:255
“Stop differential”
47:15Set to 15 K47:2
to
47:30
“ECO threshold boiler 5”
65:31No ECO threshold boiler 565:−30
to
65:+30
“ECO threshold boiler 6”
6F:31No ECO threshold boiler 66F:−30
to
6F:+30
“ECO threshold boiler 7”
74:31No ECO threshold boiler 774:−30
to
74:+30
“ECO threshold boiler 8”
7d:31No ECO threshold boiler 87d:−30
to
7d:+30
Vitotronic 300, GW6B Installation and Service
Adjustable from -22 to 86°F (−30 to +30°C)
Adjustable from -22 to 86°F (−30 to +30°C)
Adjustable from -22 to 86°F (−30 to +30°C)
Adjustable from -22 to 86°F (−30 to +30°C)
Adjustable from 1 to 255 K x minute
Note: A boiler or burner stage will shut
down if this value is exceeded.
Adjustable from 1 to 255 K x minute
Note: A boiler or burner stage will shut
down if this value is exceeded.
Adjustable from 2 to 30 K
Note: One boiler or one burner stage will be
shut down if the actual supply
temperature exceeds the set supply
temperature by this value.
Adjustable from -22 to 86°F (−30 to +30°C)
Adjustable from -22 to 86°F (−30 to +30°C)
Adjustable from -22 to 86°F (−30 to +30°C)
Adjustable from -22 to 86°F (−30 to +30°C)
90
5513 463 - 06
Page 91
Vitotronic 300, GW6B Installation and Service
Coding level 1
“DHW” Group
Coding in the factory set conditionPossible change
“Storage tank heating, hysteresis”
55:0Tank heating hysteresis ± 2.5 K55:1Adaptive storage tank heating enabled
(see page 82)
55:2Storage tank temperature control with 2
temperature sensors (see page 82).
55:3Storage tank temperature control, storage tank
loading system (see page 83)
“For solar DHW heating: DHW temperature target”
67:40DHW setpoint temperature 104°F (40°C).
Reheating is suppressed above the selected
set temperature (DHW heating blocked by the
boiler).
“DHW recirculation pump”
73:0ON according to time program73:1
67:0
to
67:95
to
73:6
73:7Permanently ON
Adjustable from 32 to 203°F (0 to 95°C)
(limited by boiler-specific coding)
“ON” from once per hour for 5 min up to
6 times per hour for 5 min during the time
program.
“Solar” Group
Note: The “Solar” group is only displayed if a solar control module, type SM1, is connected.
Coding in the factory set conditionPossible change
“Solar circuit pump speed control”
02:0Solar circuit pump is not speed controlled02:1Variable speed solar circuit pump with wave
packet control
02:2Solar circuit pump speed controlled with PWM
control
“Maximum storage tank temperature”
08:60DHW setpoint temperature (maximum tank
temperature) 140°F (60°C)
“Stagnation time reduction”
0a:5Temperature differential for stagnation time
reduction (reduction in the speed of the solar
circuit pump to protect system components
and heat transfer medium) 5 K.
“Solar circuit flow rate”
0f:70Solar circuit flow rate at maximum pump
speed 1.8 USG/min (7 L/min)
“Extended control function”
20:0No extended control function enabled20:1Additional function for DHW heating
08:10
to
08:90
0a:0Stagnation time reduction disabled
0a:1
to
0a:40
0f:1
to
0f:255
20:2Differential temperature control 2
20:3Differential temperature control 2 and auxiliary
20:4Differential temperature control 2 for central
20:5Thermostat function
20:6Thermostat function and auxiliary function
20:7Solar heating via external heat exchanger
20:8Solar heating via external heat exchanger with
20:9Solar heating of two DHW storage tanks
Adjustable from 50 to 194°F (10 to 90°C)
Temperature differential adjustable from
1 to 40 K
Adjustable from 0.02 to 6.7 USG/min
(0.1 to 25.5 L/min),
1 step
function
heating backup
without additional temperature sensor
additional temperature sensor
[Solar heating of two DHW tanks]
0.02 USG/min (0.1 L/min).
5513 463 - 06
91
Page 92
Coding level 1
“Heating Circuit ...” Group
Coding in the factory set conditionPossible change
“Storage tank priority”
a2:2Tank priority control for heating circuit
pump and mixing valve
“Heating circuit pump logic function (economy control)”
a5:5With heating circuit pump logic function
(economy control): heating circuit pump
OFF when the outdoor temperature
(OT) is 1 K higher than the set room
temperature (RTset) OT > RTset +1 K
a2:0Without storage tank priority applicable
a2:1Storage tank priority only applicable to
a2:3
to
a2:15
a5:0Without heating circuit pump logic
a5:1
to
a5:15
Vitotronic 300, GW6B Installation and Service
to heating circuit pump and mixing valve
mixing valve
Modulating priority applies to mixing
valves, i.e. the heating circuit receives
a reduced amount of heat.
function
With heating circuit pump logic function:
Heating circuit pump OFF, see the
following table
Coding address
a5:...
With heating circuit pump logic function:
Heating circ pump OFF
1OT > RTset + 5 K
2OT > RTset + 4 K
3OT > RTset + 3 K
4OT > RTset + 2 K
5OT > RTset + 1 K
6OT > RTset
7
OT > RTset – 1 K
to
15
OT > RTset – 9 K
Coding in the factory set conditionPossible change
“Extended economy mode”
a6:36Extended economy mode disableda6:5
to
a6:35
“Mixing valve economy function”
a7:0Only for heating circuits with mixing
a7:1 With mixing valve economy function:
valve:
Without mixing valve economy function
Extended economy mode enabled,
i.e. the burner and heating circuit pump
will stop and the mixing valve will be
closed at a variable value, adjustable
between 41 to 95°F (5 and 35°C)
plus 2°F (1°C). The base value is the
adjusted outdoor temperature. This
value is based on the actual outdoor
temperature and a time constant, which
takes the cooling down of an average
building into consideration.
Heating circuit pump also OFF:
H Mixing valve tries closing for more than
20 min
Heating circuit pump ON:
H Mixing valve in control mode
H If there is a risk of frost
92
5513 463 - 06
Page 93
Vitotronic 300, GW6B Installation and Service
Coding level 1
“Heating Circuit ...” Group (continued)
Coding in the factory set conditionPossible change
“Pump idle time”
a9:0Without pump idle timea9:7With pump idle time (heating circuit
pump OFF) Function description page 78
Note: The maximum idle time is 10 h.
Coding in the factory set conditionPossible change
“Minimum supply temperature limit”
c5:20Electronic supply temperature minimum
“Maximum supply temperature limit”
c6:75Electronic maximum supply temperature
*1 Only change the coding for the heating circuit without mixing valve A1 for boilers without lower temperature limit or for heating circuits with mixing valve if a remote control is connected to them.
With heating circuit pump logic function:
Heating circ pump OFF
limit 68°F (20°C) (only for operation
with standard room temperature)
limit set to 167°F (75°C)
c5:1
to
c5:127
c6:10
to
c6:127
Adjustable from 34 to 261°F
(1 to 127°C) (limited by boiler specific
coding)
Adjustable from 50 to 261°F
(10 to 127°C) (limited by boiler specific
coding)
5513 463 - 06
93
Page 94
Coding level 1
Vitotronic 300, GW6B Installation and Service
“Heating Circuit ...” Group (continued)
Coding in the factory set conditionPossible change
“External operating program changeover”
d5:0With external operating program changeover
(observe setting of coding “5d”, “5e”, “5f”
and “91” in the “General” group).
Changeover “Constant central heating with
reduced room temperature” or “Standby
mode” (subject to set reduced room
temperature)
“EA1 extension: Operating program changeover”
d8:0No operating program changeoverd8:1Operating program changeover via input DE1
“Time limit for comfort mode”
f2:8Time limit for comfort mode or external
operating program changeover via push
button: 8 h*2
Note: Observe setting of coding “5d”,
“5e”, “5f” in the “General” group,
as well as “d5” and “d8” in the
“Heating circuit...” group.
“Temperature limit for terminating reduced mode”
f8:–5Temperature limit for terminating reduced
mode 25°F (–5°C),
see example on page 80.
Observe coding “a3”.
d5:1Changeover to “Constant operation with
standard room temperature”
d8:2Operating program changeover via input DE2
d8:3Operating program changeover via input DE3
f2:0No time limit*2
f2:1
to
f2:12
f8:+10
to
f8:–60
f8:–61Function disabled
Time limit adjustable from 1 to 12 h*2.
Adjustable from 50 to -76°F (+10 to –60°C)
“Temperature limit for raising the reduced room temperature target”
f9:–14Temperature limit for raising the reduced
room temperature target 7°F (–14°C),
see example on page 80.
“Raising the set boiler water or supply temperature when changing from operation with reduced room temperature to
operation with standard room temperature”
fa:20Raising the set boiler water or supply
temperature when changing from operation
with reduced room temperature to
operation with standard room temperature
by 20%. See example on page 80.
“Duration for raising the set boiler water or supply temperature”
fb:60Duration for raising the set supply
temperature (see coding “fa”) 60 min.
See example on page 80.
*2 In the “Heating and DHW” operating program, comfort mode ends automatically when the system changes over to
operation with standard room temperature.
f9:+10
to
f9:–60
fa:0
to
fa:50
fb:0
to
fb:300
Adjustable from 50 to -76°F (+10 to –60°C)
Adjustable from 0 to 50%
Adjustable from 0 to 300 min
94
5513 463 - 06
Page 95
Vitotronic 300, GW6B Installation and Service
“General” Group
Coding in the factory set conditionPossible change
System design
00:1System version 1:
One heating circuit without mixing valve
A1 (heating circuit 1), without DHW
heating
00:2
to
00:10
Coding level 2
For system schemes,
see the following table:
Value address
00: ...
2One heating circuit without mixing valve A1 (heating circuit 1), with DHW heating;
3One heating circuit with mixing valve M2 (heating circuit 2), without DHW heating.
4One heating circuit with mixing valve (heating circuit 2), with DHW heating.
5One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit with mixing valve
6One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit with mixing valve
7Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3),
8Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3), with DHW
9One heating circuit without mixing valve A1 (heating circuit 1), two heating circuits with mixing
10One heating circuit without mixing valve A1 (heating circuit 1), two heating circuits with mixing
Coding in the factory set conditionPossible change
“With EA1 extension: DHW recirculation pump runtime for brief operation”
12:5DHW recirculation pump runtime for
“With EA1 extension: Temperature demand”
1e:0Analogue input 0-10 V:
“Reset time hydraulic switch/buffer
20:... Controller integral time for low loss
“Controller delay hydraulic switch/buffer
22:...Controller delay low loss header in
Description
recognized automatically.
M2 (heating circuit 2), without DHW heating; recognized automatically.
M2 (heating circuit 2), with DHW heating; recognized automatically.
without DHW heating.
heating.
valve M2 (heating circuit 2) and M3 (heating circuit 3), without DHW heating; recognized
automatically.
valve M2 (heating circuit 2) and M3 (heating circuit 3), with DHW heating; recognized automatically.
brief operation: 5 min
Temperature demand from 32 to 212°F
(0 to 100°C):
1 V
50°F (10°C)
10 V 212°F (100°C)
header in sec, factory set condition
defaulted by the boiler coding card.
The greater the integral action time,
the more accurate but slower the
controller.
minutes, time between burner start and
controller start.
12:1
to
12:60
1E:1Adjustable from 86 to 248°F
20:1
to
20:199
20:1
to
20:199
Adjustable from 1 to 60 min
(30 to 120°C):
86°F (30°C)
1 V
10 V 248°F (120°C)
Adjustable from 10 to 1990 sec,
1 step
Adjustable from 1 to 199 min
10 sec
2f:0Do not adjust!----
“AM1 extension”
32:0 Without AM1 extension32:1With AM1 extension
“Function output A2 at AM1 extension”
33:1Heating circuit pump, heating circuit
without mixing valve A1
(heating circuit 1)
5513 463 - 06
33:0DHW recirculation pump
33:2DHW loading pump
95
Page 96
Coding level 2
Vitotronic 300, GW6B Installation and Service
General” Group (continued)
Coding in the factory set conditionPossible change
“Function output A1 at AM1 extension”
34:1Heating circuit pump, heating circuit
without mixing valve A1 (heating circuit 1)
“Servomotor runtime”
40:125
“Sensor 17A”
4a:0Do not adjust!----
“Sensor 17B”
4b:0
“Connection at plug 20A1”
4c:0
“Connection at plug 29”
4d:1
“Connection at plug 52A1”
4e:1Motor for 3-way mixing valve for return
“Delay off time, shunt or distribution pump”
4f:5Delay off time distribution pump 5 min4f:0No pump delay off
“Supply temperature sensor for low loss header”
52:0Without supply temperature sensor52:1With supply temperature sensor;
“Boiler circuit pump”
53:1With low loss header:
“Solar thermal system”
54:0Without solar thermal system54:1With Vitosolic 100; automatic recognition.
temperature. Set value adjustment at coding
“9b” in the “General” group.
5d:3External blocking
5d:4External blocking with fault message
5d:5Fault message input.
5d:6Brief operation, DHW recirculation pump (push
button function) Set DHW recirculation pump
runtime at coding “12” in the “General” group.
5e:2External demand with minimum set supply
temperature Set value adjustment at coding
“9b” in the “General” group
5e:3External blocking
5e:4External blocking with fault message
5e:5Fault message input
5e:6Brief operation, DHW recirculation pump (push
button function) Set DHW recirculation pump
runtime at coding “12” in the “General” group.
5f:2External demand with minimum set supply
temperature Set value adjustment at coding
“9b” in the “General” group.
5f:3External blocking
5f:4External blocking with fault message
5f:5Fault message input
5f:6Brief operation, DHW recirculation pump (push
button function) Set DHW recirculation pump
runtime at coding “12” in the “General” group.
Coding level 2
5513 463 - 06
97
Page 98
Coding level 2
Vitotronic 300, GW6B Installation and Service
General” Group (continued)
Coding in the factory set conditionPossible change
“Delay off time for circulation pump, neutralizing system at output 1 at extension AM1”
6c:0Delay off time circulation pump
neutralizing system: None
Delay off time for circulation pump, neutralising system at output 2 at extension AM1”
6d:0Delay off time circulation pump
neutralizing system: None
“Display correction for outdoor temperature”
6e:50No display correction for outdoor
temperature
“LON communication module”
76:1With LON communication module;
automatic recognition. If no LON
communication module is installed,
set coding “76:0”.
“LON participant number”
77:1LON participant number77:2
“LON communication”
78:1LON communication enabled78:0LON communication disabled
“With LON communication module”
79:1Control unit is fault manager79:0Control unit is not fault manager
“Central control of heating circuits”
7a:0Without central control of heating circuits 7a:1With central control Heating circuit without
“LON communication module: Time”
7b:1Control unit transmits the time.7b:0 No time transmission
“Detached house/apartment building”
7f:1Detached house7F:0Apartment building
“Fault message”
80:6A fault message is issued if a fault
occurs for at least 30 sec.
6c:1
to
6c:255
6d:1
to
6d:255
6e:0
to
6e:49
6e:51
to
6e:99
76:0Without LON communication module
to
77:99
7a:2 Heating circuit with mixing valve M2
7a:3Heating circuit with mixing valve M3
80:0Immediate fault message.
80:2
to
80:199
Adjustable from 1 to 255 sec
Adjustable from 1 to 255 sec
Display correction –5 K
to
Display correction –0.1 K
Display correction +0.1 K
to
Display correction +4.9 K
LON participant number, adjustable from
1 to 99:
1 - 8 = Boiler and heating circuit control unit
9 = Cascade control unit
10 - 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
mixing valve A1 (heating circuit 1)
(heating circuit 2)
(heating circuit 3)
Separate adjustment of holiday program
and time program for DHW heating possible.
Adjustable from
10 to 995 sec,
1 step
5 sec.
98
5513 463 - 06
Page 99
Vitotronic 300, GW6B Installation and Service
Coding level 2
“General” Group (continued)
Coding in the factory set conditionPossible change
“Automatic summer/wintertime changeover”
81:1Automatic summer/wintertime
changeover
“Summer time starts: Month”
82:3March82:1
“Summer time starts: Week of the selected month”
83:2Week 2 of the selected month83:1
“Summer time starts: Day of the selected week”
84:7Last Sunday of the selected month84:1
“Wintertime starts: Month”
85:11November85:1
“Wintertime starts: Week of the selected month”
86:1Week 1 of the selected month86:1
“Wintertime starts: Day of the selected week”
87:7 Last Sunday of the selected month87:1
“Temperature displayed”
88:0Temperature unit °C (Celsius)88:1Temperature unit °F (Fahrenheit)
“Test display conditions”
8a:175Do not adjust!----
“Identification KM bus combustion controller”
8b:1ID exists8b:0 ID does not exist
“Operation enabled/blocked”
8f:0Do not adjust!----
“Time constant for calculating adjusted outdoor temperature”
90:128Time constant 21.3 h90:1
81:0Manual summer/wintertime changeover
81:2Do not adjust!
81:3With LON communication module: