Viessmann Vitotronic 300 GW6B, Vitotronic 300, GW6B Installation Instructions Manual

Page 1
Installation and Service Instructions
for use by heating contractor
Vitotronic 300, Type GW6B
Weather-compensated boiler and heating circuit control unit in single boiler or multi boiler systems
VITOTRONIC 300, GW6B
Certified as a component part for Viessmann boilers
5513 463 - 06 03/2015
Product may not be exactly as shown
IMPORTANT
Read and save these instructions for future reference.
Please file in Service Binder
Page 2
General
Vitotronic 300, GW6B Installation and Service
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
Product documentation Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
For a listing of applicable literature,
please see section entitled “Important Regulatory and Safety Requirements”.
Licensed professional heating contractor The installation, adjustment, service and maintenance of this equipment must be performed by a licensed professional heating contractor.
Please see section entitled
“Important Regulatory and Installation Requirements”.
Operating and Service Documentation
It is recommended that all product documentation such as parts lists, operating and service instructions be handed over to the system user for storage. Documentation is to be stored near boiler in a readily accessible location for reference by service personnel.
WARNING
Installers must follow local regulations with respect to installation of carbon monoxide detectors. Follow the Viessmann maintenance schedule of the boiler contained in this manual.
Advice to owner Once the installation work is complete, the heating contractor must familiarize the system operator/ ultimate owner with all equipment, as well as safety precautions/requirements, shutdown procedure, and the need for professional service annually before the heating season begin.
Warranty Information contained in this and related product documentation must be read and followed. Failure to do so renders the warranty null and void.
Product Information
Vitotronic 300, Type GW6B For installation in or mounting on Viessmann boilers only. Applicable to the following control units
Order No. Z013557 Serial No. 7542124
2
5513 463 - 06
Page 3
Vitotronic 300, GW6B Installation and Service
General
Table of Contents
Page
Safety, Installation and Warranty Requirements..............2
Product Information....................................................2
Safety
Preparing for Installation
Electrical Connections
About these Instructions.............................................5
For your Safety..........................................................6
Overview of System Example.......................................7
Designations in the Example.........................................7
System Examples........................................................8
Single boiler system...........................................8
Multi boiler system..........................................12
Overview of Electrical Connections.............................21
Boiler Control and Junction Box.................................26
Mounting the Control Unit.........................................26
Opening the Control Unit..........................................27
Plugging in the Boiler Coding Card Inserting Cables and Applying Strain Relief
Connecting Sensors……………................................…28
Control Power Supply……………..............................…29
Connecting the Burner..............................................30
Connecting Pumps....................................................31
Connecting a Central Fault Massage Facility................34
Connecting Actuators...............................................34
Connection of Low Water Cut-off Device Connecting External Safety Equipment
Connections to Terminal 151………………………….……38
Provisional Burner Operation.......................................39
Blocking the Boiler Externally/Adding to the Boiler Sequence External Blocking via Switching Contact External Demand via Switching Contact External Demand via 0 – 10V Input External “Mixing Valve Closed”/”Mixing Valve Open” External Operating Program Changeover
Power Supply……………….....................................…45
Making the LON Connection
................................................................40
..............................27
.................28
.....................36
……………......…37
......................41
......................42
……..……...........…43
....43
......................44
………………………….…..…46
Commissioning
Service Scans
5513 463 - 06
Commissioning the System Adjusting Coding Connecting the Control Unit to the LON
Setting the Boiler Sequence at the Cascade Control Unit...52 Carrying Out an
Checking Sensors Adjusting the Heating Curve
Calling up the Service Menu Leaving the Service Menu Change Passwords
Resetting all Passwords to Factory Settings.................58
Scanning Operating Data Resetting Operating Data Brief Scan Maintenance Display
......................................................49
Actuator Test
.....................................................54
……………………………..……...........58
...............................................................60
........................................48
......................50
...................................53
……..............................…54
......................................57
..........................................58
...........................................59
...........................................59
.................................................61
3
Page 4
Table of Contents
Vitotronic 300, GW6B Installation and Service
Page
Troubleshooting
Function Description
Coding Levels
Coding Level 1
Coding Level 2
Fault Display Boiler System Fault Codes Burner Fault Codes
Boiler Water Temperature Control. Cascade Control Unit. Heating Circuit Control Unit DHW Tank Temperature Control
Calling up Coding Levels Resetting Coding to their Factory Set Condition
“General” Group “Combustion Controller” Group “Boiler” Group “Cascade” Group “DHW” Group “Solar” Group “Heating Circuit...” Group
“General” Group “Combustion Controller” Group “Boiler” Group “Cascade” Group “DHW” Group “Solar” Group “Heating Circuit...” Group
............................................................62
.........................................63
....................................................69
..............................72
...............................................72
.......................................77
.................................81
............................................85
.......................................................86
..................................88
..........................................................88
......................................................89
..........................................................91
...........................................................91
..........................................92
.......................................................95
................................102
........................................................103
....................................................103
.........................................................106
.........................................................108
........................................111
............85
Diagrams
Components
Parts
Specification
Connection and Wiring Diagram EA1 Extension
Sensors. Extension EA1 Accessory (optional).
Parts List – Programming Module Parts List – Connection Module.
Specification Vitotronic 300, GW6B
........................................................120
................................................................121
................................117
..............................123
...............................124
.........................122
.........................125
4
5513 463 - 06
Page 5
Vitotronic 300, GW6B Installation and Service
About these Instructions
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include “WARNING”, “CAUTION”, and “IMPORTANT”. See below.
Warnings draw your attention to the presence of
WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in loss of life, serious injury or substantial product/property damage.
CAUTION
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/ property damage.
IMPORTANT
potential hazards or important product information.
Cautions draw your attention to the presence of
potential hazards or important product information.
Helpful hints for installation, operation or maintenance
which pertain to the product.
Safety
This symbol indicates that additional, pertinent
information is to be found.
This symbol indicates that other instructions must
be referenced.
5513 463 - 06
5
Page 6
Safety
For your Safety
CAUTION
Follow these safety instructions closely to avoid the risk of injury and damage to property.
H Operation
Before operating the boiler, make sure you fully understand its method of operation. Your heating contractor should always perform the initial start-up and explain the system. Any warranty is null and void if these instructions are not followed.
H Flue gas smell
- Deactivate heating equipment.
- Open windows and doors.
- Inform your heating contractor.
H Working on the equipment
All personnel working on the equipment or the heating system must have the proper qualifications and hold all necessary licenses. Ensure main power to equipment, heating system, and all external controls has been deactivated. Close main gas supply valve. Take precautions in all instances to avoid accidental activation of power during service work.
H Dangerous conditions
- Deactivate main power immediately.
- Close gas supply valve.
H Maintenance and cleaning
Regular inspection and service by a qualified heating contractor is important to the performance of the boiler. Neglected maintenance impacts on warranty; regular inspection ensures clean, environmentally friendly and efficient operation. We recommend a maintenance contract with a qualified heating contractor.
H Technical documentation
- Installation Instruction and Service Instructions
- Operating Instructions and User’s Information Manual
Additional applicable literature:
- Accessory manuals
Vitotronic 300, GW6B Installation and Service
If you smell gas
H Don’t smoke! Don’t use naked flames or cause sparks (e.g. by switching lights or electrical appliances on and off)
H Open windows and doors H Close the gas shut-off valve H Inform your heating engineers/service contractors from
outside the building H Observe the safety regulations of your gas supply company (see gas meter) and those of your heating engineers (see start-up or instruction report).
In emergencies
H Immediately switch off the power supply, e.g. at the separate fuse or power supply disconnect switch (unless there is a smell of gas). H Close the shut-off valves in the oil pipes or close the gas shut-off valve, whichever applicable. H Use suitable extinguishers in the event of fire.
Installation of additional components
The installation of additional components which have not been tested together with the boiler can adversely affect the function and performance of the boiler. Our warranty does not cover and we accept no liability for damage attributable to the installation of such components.
Boiler room conditions
H Do not use a room in which the air is polluted by halogenated hydro-carbons (e.g. as contained in aerosols, paints, solvents and cleaning agents)
H Do not use a room subject to high levels of dust H Do not use a room subject to permanently high humidity H The room should be frost-protected H Max. ambient temperature 95°F (35°C). H Provide good ventilation and do not close or obstruct
vents (if installed).
This symbol indicates a reference to other instructions which must be observed.
6
5513 463 - 06
Page 7
Vitotronic 300, GW6B Installation and Service
Overview of System Example
Designations in the System Example
Preparing for Installation
This system example is merely a GENERIC LAYOUT
and must therefore be checked on site for completeness and function.
The heating circuits must be regulated by an external
control unit.
Connect three-phase consumers via additional
contactors.
5513 463 - 06
7
Page 8
Preparing for Installation
System Examples
ID: 4800078_1407_01 Single boiler system
Vitotronic 300, GW6B Installation and Service
8
Note: This schematic is a general example without shutoff valves or safety equipment. This does not replace the need for local engineering.
5513 463 - 06
Page 9
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
Required Devices ID: 4800078_1407_01
Position Equipment
1 2 3 4 5 wT wZ rR 6 7 8 9 qP qW qE qQ
qE qZ qR qZ qU qT
qU uU
wW wR eP eQ eW
eE
eR eZ eU 4
rQ rW rE rR
5513 463 - 06
Boiler
Vitotronic 300 GW6B
Outdoor temperature sensor ATS
Boiler temperature sensor KTS (connection to burner control)
Neutralization system
Junction box
Burner base
Power switch
DHW
DHW tank temperature sensor STS delivered with Vitotronic 300
DHW pump UPSB
DHW re-circulation pump ZP
Heating circuit I
Heating circuit M2 (heating circuit I)
Mixing valve M2 (heating circuit I)
Strap-on temperature sensor
and
Mixing Valve Actuator M2 (heating circuit I)
Mixing valve adapter 24V
Heating circuit II
Heating circuit M3 (heating circuit II)
Mixing valve M3 (heating circuit II)
Strap-on temperature sensor
and
Mixing valve actuator M3 (heating circuit II)
Mixing valve adapter 24V
Accessories
Compiled fault output
Vitotrol 200A or Vitotrol 300A
Extension EA1:
1 analog input (0 to 10 V) - Specification of the boiler water temperature setpoint
3 digital inputs - Separated External switch the operating status for heating circuits 1 to 3 switchable (with control for weather-compensated operation)
- External blocking with collective fault
- Error messages
- Brief operation DHW re-circulation pump (for weather-compensated control units) 1 switching output (floating changeover contact)- Control system pump to a substation
- Signal reduced mode for one heating circuit external hook
- External demand
- External blocking / mixer to close
- External heating program changeover / mixer on site
KM BUS distributor, with several KM BUS participants KM BUS subscriber: - Extension EA1
- Vitotrol 200A, 300A LON communication module to communicate with the following components:
Vitotronic 200-H (for controlling additional heating circuits)
Vitocom 100, type LAN1 with communication module
Power switch on site / main disconnect
Preparing for Installation
9
Page 10
Preparing for Installation
System Examples (continued)
Vitotronic 300, GW6B Installation and Service
10
5513 463 - 06
Page 11
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
Preparing for Installation
ID: 4800078_1407_01
Group Coding address Function
General 00:8 Two heating circuits with mixing valve M2 (heating circuit 2) and
5513 463 - 06
M3 (circuit 3) DHW heating
11
Page 12
Preparing for Installation
System Examples (continued)
ID: 4800061_1407_01 Multi boiler system
Vitotronic 300, GW6B Installation and Service
12
Note: This schematic is a general example without shutoff valves or safety equipment. This does not replace the need for local engineering.
5513 463 - 06
Page 13
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
Required Devices ID: 4800061_1407_01
Position Equipment
1 2 3 4 5 6 8 9 rT uW uE uZ qP qW qQ qE qR qT rT uR uT uO qZ qU qI qO wP wW wE wQ
wE uU wR wZ wU wT
wU uI wI eE eR wO
eR eT
Boiler 1 Flue gas damper (for boiler I) Isolation valve Boiler temperature sensor KTS (connection to burner control) Common supply temperature sensor Outdoor temperature sensor ATS Vitotronic 300 GW6B Neutralization system Power switch Junction box Burner base Mixing valve adapter 24V Boiler II Isolation valve Mixing valve adapter 24V Boiler temperature sensor KTS (connection to burner control) Vitotronic 300 GW6B Neutralization system Power switch Junction box Burner base Flue gas damper (for boiler II) DHW DHW tank temperature sensor STS delivered with Vitotronic 300 DHW pump UPSB DHW re-circulation pump ZP Heating circuit I Heating circuit pump M2 (heating circuit I) Mixing valve M2 (heating circuit I) Strap-on temperature sensor and Mixing valve actuator M2 (heating circuit I) Mixing valve adapter 24V Heating circuit II Heating circuit pump M3 (heating circuit II) Mixing valve M3 (heating circuit II) Strap-on temperature sensor and Mixing valve actuator M3 (heating circuit II) Mixing valve adapter 24V Heating circuit III (low-temperature heating circuit) Heating circuit pump M1 (heating circuit III) Mixing valve M1 (heating circuit III) Strap-on temperature sensor and Mixing valve actuator M1 (heating circuit III) Vitotronic 200-H HK1B and LON communication module for Pos. 35 and LON connecting cable
Preparing for Installation
5513 463 - 06
13
Page 14
Preparing for Installation
System Examples (continued)
Required Devices ID: 4800061_1407_01
Position Equipment
eZ
wI wO eR
wO
eR eT
uP
eZ eP
eQ eE rT
eO rP rQ zI zO
tP tW tE
zP zQ
zW
zE
zE
zU uP eT uQ
Outdoor temperature sensor ATS (ATS-value can be taken from Vitotronic 300 GW6B master and cascade
or
Heating circuit III (underfloor heating) Supply temperature sensor M1 (circuit III) delivery Pos. 35 Mixing valve M1 (heating circuit III) or Strap-on temperature sensor and Mixing Valve Actuator M1 (heating circuit III) Vitotronic 200-H HK1B and LON communication module for Pos. 35 and LON connecting cable Outdoor temperature sensor ATS (ATS-value can be taken from Vitotronic 300 GW6B master and cascade Temperature monitor as Maximum temperature limiter for underfloor heating
- Immersion thermostat or - Contact thermostat Heating circuit M1 (secondary)
Heating circuit pump M1 (primary) Power switch on site / main disconnect Accessories for boilers Maximum pressure SDB Minimum pressure switch or limiter SDB Water level (Low water cutoff) WB External blocking / Boilers Switch on boiler as the last in a row Accessories Compiled Fault Output Vitotrol 200A or Vitotrol 300A KM BUS subscriber: - Extension EA1, AM1
- Vitotrol 200A, 300A Extension EA1:
1 switching output (floating changeover contact)
- Control system pump to a substation
- Signal reduced mode for one heating circuit 1 analog input (0 to 10 V)
- Specification of the boiler water temperature setpoint 3 digital inputs
- Separated External switch the operating status for heating circuits 1 to 3 switchable (with control for weather-compensated operation)
- External blocking with collective fault
- Error messages
- Brief operation DHW re-circulation pump (for weather-compensated control units) external hook-up
- Switch on boiler as the last boiler
- External blocking KM BUS distributor, with several KM BUS participants
LON communication module to communicate with the following components: Vitotronic 200-H (for controlling other heating circuits) Vitocom 100, type LAN1 with communication module
Vitotronic 300, GW6B Installation and Service
14
5513 463 - 06
Page 15
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
Preparing for Installation
5513 463 - 06
15
Page 16
Preparing for Installation
System Examples (continued)
Vitotronic 300, GW6B Installation and Service
16
5513 463 - 06
Page 17
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
Preparing for Installation
5513 463 - 06
17
Page 18
Preparing for Installation
System Examples (continued)
Vitotronic 300, GW6B Installation and Service
18
5513 463 - 06
Page 19
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
Preparing for Installation
5513 463 - 06
19
Page 20
Preparing for Installation
Vitotronic 300, GW6B Installation and Service
System Examples (continued)
ID: 4800061_1407_01
coding addresses Vitotronic 300, type GW6B; Lead boiler / Pos. 8
Group Coding address Function
General System Layout
Cascade Number of boilers in cascade
Cascade Boiler rotation
coding addresses Vitotronic 300 Type GW6B Pos. 14
General LON Participant Number
Boiler Boiler number in multiboiler system
coding addresses Vitotronic 200-H, type HK1B / Pos. 35
General 81:3 The control unit receives time
General 97:1 Control unit receives the outdoor temperature
00:8 Two heating circuits with mixing valve M2 (heating
circuit 2) and M3 (circuit 3) DHW heating
35:2 Number of boilers connected in the heating system
38:1 Boiler rotation - Monthly
77:2 LON Participant Number
07:2 Boiler number in multiboiler system
20
5513 463 - 06
Page 21
Vitotronic 300, GW6B Installation and Service
Overview of Electrical Connections
Electrical Connections
WARNING
Incorrect wiring can lead to serious injury from electrical current and result in appliance damage.
IMPORTANT
Electronic assemblies can be damaged by static loads. Prior to commencing work, touch an grounded object such as a heating or water pipe to discharge static load.
H Route low voltage leads and line voltage cables
separately.
H Strip the insulation from the cables as close to the
terminals as possible, and bundle tightly to the corresponding terminals.
H Secure cables with cable ties.
Connections on the low voltage PCB Plug Component Single boiler system
!
§/?
%A %B
)
aJA aJB
5513 463 - 06
Outdoor temperature sensor X X -­Common supply temperature
sensor DHW tank temperature sensor X X --
DHW tank temperature sensor (bottom) in a tank loading system Common supply temperature sensor, low loss header Return temperature sensor T1 X X X
Temperature sensor tank loading system
Single boiler control unit
-- X --
XX--
X----
X
Multi boiler system
Cascade control unit Lag boiler control unit
X
--
21
Page 22
Electrical Connections
Overview of Electrical Connections (continued)
Connections on the low voltage PCB (continued) Plug Component Single boiler system
Single boiler control unit
aVD.1/aVD.2
aVD.2/aVD.3
aVG
aVH.2/aVH.3
LON LON communication module
External operating program changeover
External “mixing valve open” X -- -­External blocking boiler -- -- X External blocking boiler X -- -­Start the boiler externally
as the last one in the boiler sequence
External “mixing valve close” X -- -­KM BUS participant
(accessory), e.g. EA1 extension
External demand via switching contact
for data exchange between control units, Vitocom and Vitogate
X----
-- -- X
XXX
XX--
XXX
Vitotronic 300, GW6B Installation and Service
Multi boiler system
Cascade control unit Lag boiler control unit
PCB connections 120V~ Plug Component Single boiler system
Single boiler control unit
A1
sA sK sL fÖ fA gÖ gSA1
aBÖ
aBH
Connections on extension for heating circuit with mixing valve HC2/M2, HC3/M3 Plug Component Single boiler system
? M2/M3 M2/M3 gS M2/M3
Heating circuit pump for heating circuit A1 (high temp.)
Primary pump, primary store system
DHW pump X X --
DHW recirculation pump X X --
Boiler pump or system pump -- X X
Power supply X X X
Burner X X X
Central fault message X X X
Motorized isolation valve -- X X Motor, 3-way mixing valve,
tank loading system External safety equipment X X X Provisional burner operation X X X Power supply for accessories X X X
Single boiler control unit
Supply temperature sensor X X --
Heating circuit pump X X --
Mixing valve motor X X --
-- X --
XX--
XX--
Cascade control unit Lag boiler control unit
Cascade control unit Lag boiler control unit
Multi boiler system
Multi boiler system
22
5513 463 - 06
Page 23
Vitotronic 300, GW6B Installation and Service
Overview of Electrical Connections (continued)
Electrical Connections
Legend
A Vitotronic control B Burner base C DIN rail (located in junction box)
gSM2 Mixing valve heating circuit M2 gSM3 Mixing valve heating circuit M3 sÖM2 Pump heating circuit M2 sÖM3 Pump heating circuit M3 sK DHW recirculation pump sA DHW pump sL Boiler pump
A1 High temperature heating circuit pump gSA1 Mixing valve, primary store system
Compile fault output Main power supply aBÖ Safety circuit connections aBA Safety circuit connections gD Flue gas damper
F3
5513 463 - 06
Fuse 250VAC 6.3A
Rated pump and compile fault output 2A~
Note: Maximum output 6FLA shared between all mixing valve, pump and compile fault outputs.
Note: The 120VAC line out terminals are still live even when the control is switched off.
23
Page 24
Electrical Connections
Overview of Electrical Connections (continued)
Vitotronic 300, GW6B Installation and Service
Note: The DIN terminals can be used with solid, stranded or stranded with ferrule termination. The ferrule will help to prevent ‘fraying’ of the standed wires during installation.
Specific connections are detailed throughout the manual, refer to the appropriate section prior to making any connections.
Top
The junction box terminals include a L, N terminal connection orientated at the top of the junction box which is pre-wired to the cable harness set, which is used to connect the Vitotronic control and Burner Base to the junction box. The L,N,G terminals orientated at the bottom of the junction box are used to for connections to external equipment (ie. Pumps, mixing valves, etc). The individual terminals are a ‘push-in’ design, meaning to install or release a wire, the orange button must be pushed in (refer to image below for location of orange buttons denoted by B), prior to installing or removing any wires to the terminal.
Bottom
Legend
A DIN terminal (typical) B Push-in button C DIN rail (typical) D Terminal insertion point
Note: Max. wire gauge 12AWG Min. wire gauge 26AWG
24
5513 463 - 06
Page 25
Vitotronic 300, GW6B Installation and Service
F3
F3
Overview of Electrical Connections (continued)
Accessing the DIN rail mounted fuse F3
A DIN rail mounted fuse block provides protection to the 120V line out connections as shown on page 23.
When fuse F3 requires replacement, the fuse can be accessed as shown.
Electrical Connections
1. Flip down the front portion of the DIN rail fuse block.
2. Flip down the front side cover of the DIN rail fuse block.
3. Replace fuse.
4. Return the DIN rail
original postion.
mounted fuse block back to the
.
mounted
mounted
5513 463 - 06
25
Page 26
Electrical Connections
Boiler Control and Junction Box
B
C
Legend
A Junction box B Vitotronic control
C Vitocrossal 200 CM2 boiler
Vitotronic 300, GW6B Installation and Service
1. Install the junction box to the rear panel either right or left. Secure the junction box with four 4.8 mm metal screws.
2. Route cables from control through the opening in the control panel. Guide the cables to the junction box through the opening in the rear panel and along the top rail to the control. Secure all cables to the rail with cable ties.
Note: Never allow cables to come in contact with hot metal components.
3. Mount the control to the top front panel.
4. Secure the control to the top front panel with screws.
Note: Screws to secure control are included in
control’s shipping box.
Mounting the Control Unit
Legend
A Cable retaining tab
26
Note: Route the ribbon cable through retainer A.
5513 463 - 06
Page 27
Vitotronic 300, GW6B Installation and Service
Opening the Control Unit
Electrical Connections
Plugging in the Boiler Coding Card
Only use the boiler coding card supplied with the boiler junction box.
Insert the boiler coding card into slot “X7”, through the recess in the cover.
Coding card # Part #
1042 7543216
5513 463 - 06
27
Page 28
Electrical Connections
Inserting Cables and Applying Strain Relief
H Control unit fitted on the boiler:
Route cables from below through the front panel of the boiler into the wiring chamber of the control unit.
Vitotronic 300, GW6B Installation and Service
Legend
A Cables with moulded strain relief B On-site cables; strip up to 4 in. (100 mm) insulation
Connecting Sensors
Outdoor temperature sensor connection
2 wire cable, 18 AWG for a maximum length of 120 ft (36 m)
28
Connections on the low voltage PCB
Plug Component
!
§/? %A %B
) aJA aJB
Outdoor temperature sensor
Fitting location for outdoor temperature sensor
H North or north-westerly wall, 6 to 8 ft (2 to 2.5 m)
above ground level; in multi storey buildings, in the upper half of the second floor.
H Not above windows, doors or ventilation outlets.
H Not immediately below balconies or gutters.
H Never cover over.
Outdoor temperature sensor
Common supply temperature sensor
Tank temperature sensor
Tank temperature sensor (bottom) in a tank loading system
Temperature sensor, low loss header
Return temperature sensor T1
Temperature sensor tank loading system
5513 463 - 06
Page 29
Vitotronic 300, GW6B Installation and Service
Control Power Supply
Electrical Connections
Connecting the power supply to the Vitotronic control
For burner base unit, see boiler service instructions
Legend
A To the burner base unit B Connecting cable C To the Vitotronic control
Insert plug burner base.
Route beneath the top B rail in a bundle using plug-in cable retainers.
Connect plugs and aBH to the corresponding plugs in the Vitotronic control unit.
40/156
into the corresponding plug of the
5513 463 - 06
29
Page 30
Electrical Connections
Connecting the Burner
Legend
A To the Vitotronic control B To the burner (burner control unit) C KM BUS cable
Vitotronic 300, GW6B Installation and Service
The burner cables are included in the standard boiler delivery.
Max. power consumption 3A.
Terminal codes L1 Phase via external safety equipment (if installed) to the burner Ground conductor to burner N Neutral conductor to burner T1 120V~ from burner control unit T2 Base load demand S3 Connection for burner fault B4 Connection for hours run meter
Insert plug fA and aVG into the corresponding plug of the burner control.
Route beneath the top B rail in a bundle using plug-in cable retainers.
Connect plugs fA and aVG to the corresponding plugs in the Vitotronic control unit.
30
5513 463 - 06
Page 31
Vitotronic 300, GW6B Installation and Service
Connecting Pumps
Electrical Connections
Legend
A Pumps B To the control unit
Rated voltage 120V~
Rated current Max. 2A~
Note: Maximum output 6FLA shared between all 120V outputs.
Pumps 120V Available pump connections
M1/A1 Heating circuit 1 pumpM2 Heating circuit 2 pumpM3 Heating circuit 3 pump
sA DHW pump sK DHW recirculation pump
sL Boiler pump
5513 463 - 06
Available connections
Connections on extension for heating circuit with mixing valve HC2/M2, HC3/M3
Plug Terminal Component
M2 M3
Connections on the PCB 120V~
A1
sA sK
sL
5 L, N, G Heating circuit pump 6 L, N, G Heating circuit pump
9 L, N, G Heating circuit pump
for heating circuit A1 or Primary pump, primary store system
8 L, N, G DHW pump 7 L, N, G DHW recirculation
pump
10 L, N, G boiler pump, system
pump
31
Page 32
Electrical Connections
Connecting Pumps (continued)
Vitotronic 300, GW6B Installation and Service
120V pumps with an amperage draw of <2FLA
A Din rail (located in the junction box) B Pump
120V pumps with an amperage draw of >2FLA
Contactor specification 120VAC 1A
A Din rail (located in the junction box) B Contactor/relay (field supplied) C Pump D Power supply w/disconnect and protection
32
5513 463 - 06
Page 33
Vitotronic 300, GW6B Installation and Service
Connecting Pumps (continued)
Electrical Connections
240V pumps
Contactor specification 120VAC 1A
A Din rail (located in the junction box) B Contactor/relay (field supplied) C Pump D Power supply w/disconnect and protection
208/460/575V 3 phase pumps
Contactor specification 120VAC 1A
A Din rail (located in the junction box) B Contactor/relay (field supplied) C Pump D Power supply w/disconnect and protection
5513 463 - 06
33
Page 34
Electrical Connections
Connecting a Central Fault Message Facility
Plug (terminal 11 - L, N, G) Note: On lag boilers, output will only be switched
in the case of faults on that boiler.
Rated voltage 120V~
Rated current Max. 2A~
Note: Maximum output 6 FLA shared between all 120V outputs
Connecting Actuators
Vitotronic 300, GW6B Installation and Service
1. Disconnect power to control.
2. Connect valve actuator wires to the DIN as shown
(based on desired functionality).
Operating time: 5 to 199 sec. selected via coding address “40”.
Available connections
gS A1 Motor for 3-way mixing valve, primary store system gS M2 For heating circuit 2 gS M3 For heating circuit 3
Rated voltage 120V~
Rated current Max. 0.1~/ output
Motor runtime for 3-way mixing valve: 10 to 255 sec, adjustable via coding addresses “6a” in the”DHW”group, “c3” in the heating circuit 2 group and “c3” in the heating circuit 3 group.
Plug DIN terminals
52A1 12 (L, N)
13 (L)
52M2 1 (L, N)
2 (L)
52M3 3 (L, N)
4 (L)
34
Legend
A DIN Rail (in junction box) B 120V Valve Actuator C Valve
5513 463 - 06
Page 35
Vitotronic 300, GW6B Installation and Service
Connecting Actuators (continued)
Electrical Connections
Legend
A 24V Mixing Valve Adaptor B DIN Rail (in junction box) C 24V Valve Actuator D Valve E 120V power to the mixing valve adaptor
24V Valve Adaptor
Rated voltage: 24 VAC Rated current: max. 0.15 FLA
Operating time: 5 to 199 sec. selected via coding address “40”.
Available connections
gS A1 Motor for 3-way mixing valve, primary store system gS M2 For heating circuit 2 gS M3 For heating circuit 3
Motor runtime for 3-way mixing valve: 10 to 255 sec, adjustable via coding addresses “6a” in the”DHW”group, “c3” in the heating circuit 2 group and “c3” in the heating circuit 3 group.
1. Disconnect power to control.
2. Remove plug connect gS from cables BK1, BK2 and
BK3 of the 24V valve adaptor
3. Connect BK1, BK2 and BK3 to DIN terminals for
desired valve application. Refer to the chart below.
4. Connect black wire E of the mixing valve adaptor
to an available terminal 14-17 on the DIN rail.
5. Connect valve actuator wires to the adaptor terminals
as shown in image above.
Refer to the mixing valve adaptor Installation Instructions for additional information.
Plug DIN terminals
52A1 12 (L, N)
13 (L)
52M2 1 (L, N)
2 (L)
52M3 3 (L, N)
4 (L)
5513 463 - 06
35
Page 36
Electrical Connections
Connection of Low Water Cut-off Device
1. Remove jumper between terminals 21(L) and 22(L).
2. Make connection for switching contact at terminal
(LWCO) 21(L) and 22(L).
3. Power supply for low water cut-off device made at an
available terminal 14, 15, 16 or 17 (L, N, G)
The diagram shown is only a simplified conceptual drawing of a typical low water cut off (LWCO) device. Refer to the manual specific to the device for interconnection details.
Vitotronic 300, GW6B Installation and Service
CAUTION
Legend
aBÖ Connection for external equipment.
A Low water cut-off (typical)
36
5513 463 - 06
Page 37
Vitotronic 300, GW6B Installation and Service
Connecting External Safety Equipment
Electrical Connections
Connection at plug aBÖ.
Note: ‘Live’ contacts lead to short circuits or phase failure. The external connection must be potential-free.
1. Remove jumper from terminals 21(L) and 22(L).
2. Make connection of the safety equipment to 21(L)
and 22(L).
Legend
A Low water indicator, minimum pressure limiter B Maximum pressure limiter C Further safety equipment
Note: Periphery equipment attached to the aBÖ plug must be operated on a normally closed circuit.
5513 463 - 06
37
Page 38
Electrical Connections
Connections to Terminal aBA
Vitotronic 300, GW6B Installation and Service
Low gas pressure switch/external shut-off
1. Remove jumper between terminals 26 (L) and 27(L).
2. Connect auxiliary low gas pressure switch or external shut-off (dry contact) to terminals 26 (L) and 27(L).
WARNING
The terminals should be used for safety switch-off purposes only (e.g. through a high limit thermostat). During switch-off, there is no frost protection of the heating system and the boiler is not kept at the minimum boiler water temperature.
Note: The heating system has no frost protection while it
is blocked. The boiler is not held at the lower boiler water temperature.
Refer to the low gas pressure switch Installation Instructions
Legend
A DIN rail (junction box) B Auxiliary low gas pressure switch or external shut-off (dry contact)
38
5513 463 - 06
Page 39
Vitotronic 300, GW6B Installation and Service
Provisional Burner Operation
Electrical Connections
Remove jumper across terminals 23 (L) and 24 (L) (not shown) and connect terminals 23 (L) and 25 (L) external control via dry contact (heat demand on close). Upon heat demand the boiler will maintain low fire until modulation is externally controlled through BMS.
Legend
A Dry contact between “TR and ON” B Din rail (located in junction box)
T6 - Common T7 - Modulating Down T8 - Modulating Up
Legend
C To burner interface
5513 463 - 06
External modulation via 90 plug (dry contact for modulation) terminal closure T6 and T8 will drive burner modulation up and terminal closure T6 and T7 will drive modulation down.
Note: Only one contact will be closed at a time. Both contacts open will hold modulation.
Temperature control is now limited by the electronic high limit setting in the burner control.
Refer to the “combustion controller” group in coding for adjustment to maximum boiler water temperature.
39
Page 40
Electrical Connections
Vitotronic 300, GW6B Installation and Service
Blocking the Boiler Externally/Adding to the Boiler Sequence
Only for lag boilers Connection on plug aVD
Note: ‘Live’ contacts lead to short circuits or phase failure. The external connection must be potential-free.
Legend
A Blocking the boiler externally B Start the boiler externally as the last one
in the boiler sequence
Contact Closed Open
A
aVD.1/aVD.2
B
aVD.2/aVD.3
H The boiler is blocked and has been removed
from the boiler sequence.
H The motorized isolation valve closes and the
boiler circuit pump stops.
H The other boilers provide the required heating.
Note: If all boilers are blocked or there is no other boiler ready for operation, then there will be no frost protection for the heating system.
This boiler is moved from the current position in the boiler sequence and started as the last boiler in the sequence.
The boiler is integrated into the current boiler sequence.
The boiler is integrated into the current boiler sequence.
40
5513 463 - 06
Page 41
Vitotronic 300, GW6B Installation and Service
External Blocking via Switching Contact
Electrical Connections
Plug aVD.2/aVD.3
Legend
A Floating contact B Plug aVD of the control unit
EA1 extension
Only for single boiler and cascade control units
Connection options:
H Plug aVD.2/aVD.3
Note: In the case of cascade control units make the connection on the EA1 extension.
H EA1 extension (accessory, see page 122)
Contact closed:
H Single boiler system
The boiler is shut down.
H Multi boiler system Controlled shutdown of the burners on each boiler. Any connected circuit or system pump is stopped. Shut-off devices are closed.
Note: The heating system has no frost protection while it is blocked.
Connection Note: ‘Live’ contacts lead to short circuits or phase failure.
The external connection must be potential-free.
Coding
Plug aVD With coding “99” set in the “General” group determine what the input should influence.
Note: Never adjust coding “99:0” in a cascade control unit.
Legend
A Floating contact B EA1 extension
EA1 extension Set “5d” (DE1), “5e” (DE2) or “5f” (DE3) in the “General” group to 3 or 4.
5513 463 - 06
41
Page 42
Electrical Connections
External Demand via Switching Contact
Vitotronic 300, GW6B Installation and Service
Plug aVH.2/aVH.3
146
Legend
A Floating contact B Plug aVH of the control unit
EA1 extension
Only for single boiler and cascade control units
Connection options:
H Plug aVH.2/aVH.3
H EA1 extension (accessory, see page 122)
Contact closed:
H Single boiler system The burner is switched ON subject to load. The boiler heats to the set boiler water temperature selected in coding “9b” in the “General” group. Limiting the boiler water temperature by means of the set boiler water temperature and the electronic maximum limit of the boiler water temperature (coding “06” in the “Combustion Controller” group)
H Multi boiler system The burners in each boiler are switched ON subject to load. They heat to the set supply temperature selected in coding “9b” in the “General” group. Limiting the supply temperature by means of the set supply temperature and the electronic maximum limit of the supply temperature (coding “37” in the “Cascade” group)
Connection Note: ‘Live’ contacts lead to short circuits or phase failure.
The external connection must be potential-free.
Legend
A Floating contact B EA1 extension
Coding
Plug aVH No coding change required
EA1 extension Set “5d” (DE1), “5e” (DE2) or “5f” (DE3) in group “General” to 2.
42
5513 463 - 06
Page 43
Vitotronic 300, GW6B Installation and Service
External Demand via 0 –10V Input
Electrical Connections
Connection at input 0 – 10V to EA1 extension (accessory, see page 122).
Note: Ensure DC separation between the ground conductor and the negative pole of the on-site voltage source.
0 –1V 1V Set value 50°F (10°C) 10V Set value 212°F (100°C) Observe coding “1E” in the “General” group.
Optional setting range 0 –1V No default set supply temperature 1V Set value 86°F (30°C) 10V Set value 248°F (120°C) Observe coding “1E” in the “General” group.
No default set supply temperature
External “Mixing Valve Closed”/”Mixing Valve Open”
Connection on plug aVD. Note: ‘Live’ contacts lead to short circuits or phase failure. The external connection must be potential-free.
Coding
External “mixing valve open” With coding “9a” in the “General”group assign the function to the heating circuits.
Legend
A External “mixing valve open” (floating contact) B External “mixing valve close” (floating contact)
External “mixing valve close” With coding “99” in the “General” group assign the function to the heating circuits.
5513 463 - 06
43
Page 44
Electrical Connections
External Operating Program Changeover
Vitotronic 300, GW6B Installation and Service
Plug aVD
Legend
A Floating contact B Plug aVD of the control unit
EA1 extension The changeover can be achieved separately for heating circuits 1 to 3.
Legend
A Dry contact (potential free) B EA1 extension
Only for single boiler and cascade control units
Connection options:
H Plug aVD.1/aVD.2
Note: In the case of cascade control units make the connection on the EA1 extension.
H EA1 extension (accessory, see page 122)
Connection Note: ‘Live’ contacts lead to short circuits or phase failure.
The external connection must be potential-free.
Preselected operating program (Contact open)
9
or
w
or
w
Central heating OFF/ DHW OFF
Central heating OFF/ DHW heating ON
Central heating ON/ DHW heating ON
Coding Changed operating
program (Contact closed)
“d5:0” in the “Heating circuit ...” group (Factory set condition)
“d5:1” in the “Heating circuit ...” group
Constant operation with reduced room temperature/ DHW heating OFF
Constant operation with standard room temperature, DHW heating in accordance with coding “64” in the “DHW” group
44
Coding
Plug aVD
This function can be assigned to the heating circuits at coding “91” in the “General” group. Note: Never adjust coding “91:0” in a cascade control unit.
EA1 extension
Set “5d” (DE1), “5e” (DE2) or “5f” (DE3) in group “General” to 1. This function can be assigned to the heating circuits at coding “d8” in the “Heating circuit...” group.
5513 463 - 06
Page 45
Vitotronic 300, GW6B Installation and Service
Power Supply
Electrical Connections
WARNING
If system components are not grounded, serious injury
from electric current can result if an electrical fault
occurs.
Connect the appliance and pipework to the
equipotential bonding of the building in question.
WARNING
Incorrectly executed electrical installations can lead to
injuries from electrical current and result in appliance
damage.
Connect the power supply to the mains filter unit (part of standard burner delivery).
Isolators for non-grounded conductors
H The mains isolator or “Emergency stop” must
simultaneously isolate from the power supply all
non-grounded conductors.
H We additionally recommend installing an AC/DC-
sensitive RCD, type B that can occur with energy efficient equipment.
H If no mains isolator or “Emergency stop” is set, isolate all non-grounded conductors simultaneously from the power supply by means of an upstream isolator with a minimum contact separation of 3 mm.
H Connection to the same MCB/fuse provides additional
safety when the power is switched off. Observe the power consumption of the connected consumers.
, for DC (fault) currents
Legend
A Power supply 120V~ (CM2 - 186, 246, 311 requires 12A) (CM2 - 400, 500, 620 and 620TX requires 16A)
B Fuse 250VAC 6.3A C Mains isolator, (on-site) D Boiler junction box
5513 463 - 06
Connect the power supply and implement all safety measures (e.g. RCD circuit) in accordance with local and national codes.
45
Page 46
Electrical Connections
Making the LON Connection
Vitotronic 300, GW6B Installation and Service
Connection with Viessmann LON cable
The line may be up to 23 ft. (7 m) long
Legend
A Control unit or Vitocom B LON cable, 23 ft. (7 m) long C Terminator
Connection with Viessmann LON cable and coupling
The Viessmann LON is designed for “Line” BUS topology with a terminator at both ends (accessories). Further information can be found in the “Viessmann LON manual”; see www.viessmann.de/lon. The transfer distances for LON are subject to the electrical properties of the respective cable. For this reason, only use the stated cable types. Use only one cable type within one LON.
Cable types (on site):
H 2-core cable, CAT5, screened
H JY(St)Y 2 x 2 x 0.8 mm (telephone cable)
Observe the cabling requirements for the operation of the LON interface FTT 10-A (see www.echelon.com). All Viessmann appliances are connected with RJ45 connectors. The Viessmann LON always requires the cores “1” and “2” and the screen. The cores are interchangeable.
Installation spacing 23 to 69 ft. (7 to 21 m)
Legend
A Control unit or Vitocom B LON cable, 23 ft. (7 m) long
Max. 3 cables between 2 appliances
C Terminator D LON coupling
46
5513 463 - 06
Page 47
Vitotronic 300, GW6B Installation and Service
Making the LON Connection (continued)
Connection with LON cable, on-site cable and LON junction box
3000 ft.
The line may be up to 3000 ft. (900 m) (with LON junction boxes)
Legend
A Control unit or Vitocom B LON cable, 23 ft. (7 m) long C Terminator D LON sockets E On-site cable F Up to 30 participants
Electrical Connections
Connection with on-site cable and LON plug
3000 ft.
The line may be up to 3000 ft. (900 m) (with LON plug)
Legend
A Control unit or Vitocom B On-site cable C Terminator D LON plug E Up to 30 participants
5513 463 - 06
47
Page 48
Commissioning
Commissioning the System
Vitotronic 300, GW6B Installation and Service
1. Turn ON the ON/OFF switch on all control units. The commissioning assistant starts automatically.
2. Make required settings:
- “Language”
- “Date / Time”
- “Measuring units”
3. Tap “Application” and select the required application.
- ‘single boiler’
- ‘lead boiler and cascade’
- ‘lag boiler’
4. Confirm with OK until symbol
5. Important coding can be set during commissioning (see the following table). For this tap “Yes”.
Note: Flue gas damper coding address 0a is factory defaulted to 0a:1 (with flue gas damper) when the application is set ‘lead boiler & cascade’ or ‘lag boiler’. If a flue gas damper is not used with the boiler, the coding address must be adjusted to 0a:0. If the coding address is not adjusted through the commissioning assistant at the boiler control, then the burner will check for the presence of a flue gas damper and then the functionality of the flue gas damper can only be adjusted through the burner control.
and “Setup” appear.
Single boiler Weather-compensated single boiler system capable of controlling DHW production and space heating of one high temperature heating loop and 2 low temperature heating loops with mixing valves.
Lead boiler and cascade Master boiler in a multiboiler system capable of cascading a maximum of 8 x GW6B equipped CM2 series boilers. This boiler is responsible for generating system and boiler setpoints, capable of DHW production and and space heating of one high temperature heating loop and 2 low temperature heating loops complete with mixing valves.
Lag boiler Slave tothe master boiler, and operates on setpoints generated by the master boiler.
Refer to the burner section of the CM2 Service Instructions
Tap “No” if no further settings are to be made.
6. Confirm with OK.
- Single boiler system The standard menu appears.
- Multi boiler system The default display will appear.
Refer to the Operating Instructions
Note: If commissioning was unsuccessful, the following fault symbol Tap and check the fault messages.
- ‘single boiler’
- ‘lead boiler + cascade’
- ‘lag boiler’
If the Vitocrossal 200 CM2 boiler is operated in a multiple boiler application, a fault message will be displayed during initial start-up, which indicates that the boiler controller commissioning process is not yet completed. Please ackowledge this message and complete the commissioning process.
appears in the footer.
48
5513 463 - 06
Page 49
Vitotronic 300, GW6B Installation and Service
Commissioning
Commissioning the System (continued)
Coding are show in the “Setup” menu in the following order: Function Group Coding
“Max operational output” “Combustion controller” 02 “Gas type” 03 “Altitude” 04 “Design” 0a “System design” “General” 00 “Consecutive boiler number in multi boiler systems” “Boiler” 07 “Number of boilers connected to the cascade” “Cascade” “Cascade” 35 “LON participant number” “General” 77 “Control strategy” “Cascade” 3c
Adjusting Coding
Single boiler system
Check all addresses on Coding level 1 and set if required. Check the following coding on Coding level 2 and set if required. For steps and overviews on coding, see chapter “Coding”.
Function Group Coding
“Connection at plug 20A1” “General” 4c “With LON communication module”
(control unit is fault manager) “Viessmann system number” “General” 98 “With LON communication module:
Monitoring LON participants”
“General” 79
“General” 9c
Multi boiler system
Check all addresses on Coding level 1 and set if required. Check the following coding on Coding level 2 and set if required. For steps and overviews on coding, see chapter “Coding”.
Function Group Coding
On all control units “Single boiler and multi boiler system” “Boiler” 01 “Connection at plug 29” “General” 4d “Viessmann system number” “General” 98 “With LON communication module:
Monitoring LON participants”
Only on cascade control units “Connection at plug 20A1” “General” 4c “Connection at plug 29” “General” 4d “Connection at plug 52A1” “General” 4e “With LON communication module”
(control unit is fault manager) “Central control of heating circuits” “General” 7a “Viessmann system number” “General” 98 “With LON communication module:
Monitoring LON participants” “Permanent last boiler” “Cascade” 3a “Permanent lead boiler” “Cascade” 39 “Storage tank heating, hysteresis” “DHW” 55
“General” 9c
“General” 79
“General” 9c
5513 463 - 06
49
Page 50
Commissioning
Connecting the Control Unit to the LON
Example of a single boiler system with Vitotronic 200-H and Vitocom
Vitotronic 300, GW6B Installation and Service
H The LON communication module is factory installed.
H Vitotronic 200-H: The LON communication module (accessories) must be fitted.
Refer to the Installation and Service Instructions for Vitotronic 200-H
H Within one LON, the same participant number must
not be allocated twice.
H Within one LON, the system number (coding “98” in the “General” group) must always be the same.
H Only one control unit may be programmed as fault
manager.
H The data transfer via LON can take several minutes.
A Single boiler control unit B Vitotronic 200-H C Vitocom D LON
All coding in the table are listed in the "General" group.
ABC
Participant no. 1, Coding “77:1”
Control unit is fault manager, Coding “79:1”
Control unit transmits the time, Coding “7b:1”
Control unit sends outdoor temperature, Coding “97:2”
Viessmann system number, Coding “98:1”
LON participant fault monitoring, Coding “9c:20”
Participant no. 10, Coding “77:10”
Control unit is not fault manager, Coding “79:0”
Control unit receives the time, Set coding “81:3”
Control unit receives outdoor temperature, Set coding “97:1”
Viessmann system number, Coding “98:1”
LON participant fault monitoring, Coding “9c:20”
Participant no. 99
Appliance is fault manager
Device receives the time
--
--
--
50
5513 463 - 06
Page 51
Vitotronic 300, GW6B Installation and Service
Connecting the Control Unit to the LON (continued)
Example of a multi boiler system
Commissioning
A Lag boiler control unit B Lag boiler control unit C Cascade control unit
ABCDE
Multi boiler system Set coding “01:2” in the “Boiler” group
Boiler number 3 Set coding “07:3” in the “Boiler” group
-- -- Number of connected
Participant no. 3. Coding “77:3” in the “General” group
Control unit is not fault manager. Coding “79:0” in the “General” group
-- -- Control unit transmits
-- -- The control unit
Viessmann system number, Coding “98:1” in the “General” group.
LON participant fault monitoring Coding “9c: 20” in the “General” group
Multi boiler system Set coding “01:2” in the “Boiler” group
Boiler number 2 Set coding “07:2” in the “Boiler” group
Participant no. 2. Set coding “77:2” in the “General” group
Control unit is not fault manager. Coding “79:0” in the “General” group
Viessmann system number, Coding “98:1” in the “General” group.
LON participant fault monitoring Coding “9c: 20” in the “General” group
Multi boiler system Set coding “01:2” in the “Boiler” group
Boiler number 1 Set coding “07:1” in the “Boiler” group
boilers Set coding “35:1” to “35:8” in the “Cascade” group
Participant no. 1. Coding “77:1” in the “General” group
Control unit is fault manager. Coding “79:1” in the “General” group
the time. Coding “7b:1” in the “General” group
sends the outdoor temperature. Coding “97:2” in the “General” group
Viessmann system number, Coding “98:1” in the “General” group.
LON participant fault monitoring Coding “9c: 20” in the “General” group
D Vitotronic 200-H E Vitocom F LON system
-- --
-- --
-- --
Participant no. 10. Coding “77:10” in the “General” group
Control unit is not fault manager. Coding “79:0” in the “General” group
The control unit receives the time. Set coding “81:3” in the “General” group
The control unit receives the outdoor temperature. Set coding “97:1” in the “General” group
Viessmann system number, Coding “98:1” in the “General” group.
LON participant fault monitoring Coding “9c: 20” in the “General” group
Participant no. 99
Appliance is fault manager
Device receives the time
--
--
--
5513 463 - 06
51
Page 52
Commissioning
Connecting the Control Unit to the LON (continued)
Carrying out a LON participant check
The participant check is used to test communication with the system devices connected to the fault manager.
Preconditions:
H The control unit must be programmed as fault manager
(coding “79:1” in the “General” group).
H The LON participant no. must be programmed in all
control units.
H The LON participant list in the fault manager must be
up to date.
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Service functions”
5. “LON participant check” The list of all connected LON participants appears.
6. Select participant and start participant check with “OK”. “Participant ...” appears on the display” Check running”.
Note: During the participant check, the display for the relevant participant flashes the participant no. for approx. 1 min. and displays “Wink”.
Vitotronic 300, GW6B Installation and Service
H Successfully tested participants are designated with “OK”.
H Unsuccessfully tested participants are designated with
“Subscribe ... Check not OK”. Update the participant list with “New list” in order to carry out another participant check.
Setting the Boiler Sequence at the Cascade Control Unit
Boiler sequence subject to the coding set in the “Cascade” group and internal control calculations:
Function Coding
“Lead boiler or boiler sequence changeover” 38
“Permanent lead boiler” 39
“Permanent last boiler” 3a
“ECO threshold boiler”... 41 to 44, 65, 6f, 74, 7d
H Every boiler can be blocked or enabled subject to
outdoor temperature by means of the ECO threshold.
H The ECO threshold has no effect if a boiler is required to achieve the set supply temperature in the case of enabled boilers failing.
H At least the lead boiler remains in operation when all
boilers in a system would otherwise be blocked via the
ECO threshold.
Tap the following buttons:
1. “Menu”
2. “Boiler sequence”
3. Select the required boiler sequence and confirm with “OK”.
52
5513 463 - 06
Page 53
Vitotronic 300, GW6B Installation and Service
Carrying Out an Actuator Test
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Actuator test”
Note: Before an actuator is selected, all actuators are switched to zero volt.
The actuators listed in the table can be tested at the relay outputs subject to system equipment level and control unit configuration (single or multi boiler system).
Display Explanation
“All actuators” OFF All actuators have been switched off.
“Output 20” ON
“Output 52” Open
“Output 52” Neutral
“Output 52” Close
“DHW tank primary pump” ON
“DHW circ pump” ON
“Output 29” ON
“Central fault message” ON
“Htg circ pump HC2” ON
“Mixing valve HC2” Open
“Mixing valve HC2” Close
“Htg circ pump HC3” ON
“Mixing valve HC3” Open
“Mixing valve HC3” Close
“EA1 output 1” ON
“AM1 output 1” ON Actuator at output A1
“AM1 output 2” ON Actuator at output A2
“Solar circuit pump” ON
“Solar circ pump min” ON
“Solar circ pump max” ON
“SM1 output 22” ON
Actuator at output A1 Actuator at output gS A1 Actuator at output gS A1 Actuator at output gS A1 Actuator at output sA Actuator at output sK Actuator at output sL Central fault message facility at output Actuator at output M2 Actuator at output gS M2 Actuator at output gS M2 Actuator at output M3 Actuator at output gS M3 Actuator at output gS M3 Contact “P - S” on plug aBJ of EA1 extension closed.
“Solar circuit pump” On Solar circuit pump at output sF at solar control module, type SM1
“Solar circ pump min” On Solar circuit pump at output sF at solar control module, type SM1 set to min. speed.
“Solar circ pump min” On Solar circuit pump at output sF at solar control module, type SM1 set to max. speed.
Actuator at output sS at solar control module type SM1
Information regarding the mixing valve motor rotational direction. The supply temperature must rise when the mixing valve opens. If the temperature drops, either the motor is turning in the wrong direction or the mixing valve set is incorrectly fitted (observe the mixing valve installation instructions).
Commissioning
5513 463 - 06
53
Page 54
Commissioning
Checking Sensors
Adjusting the Heating Curve
Vitotronic 300, GW6B Installation and Service
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Diagnosis”
5. Select group.
6. Scan actual temperature of the relevant sensor.
Only for single boiler and cascade control units The heating curves represent the relationship between the outdoor temperature and the boiler water or supply temperature. Simplified: The lower the outdoor temperature, the higher the boiler water or supply temperature. The boiler water or supply temperature in turn affects the room temperature.
Slope
Boiler water or supply
temperature
Room set-point
temperature
For outdoor temperature 7°F (14°C)
Legend
A Underfloor heating system, slope 0.2 to 0.8 B Low temperature heating system, slope 0.8 to 1.6 C Heating systems with a boiler water temperature in
excess of 167°F (75°C), slope greater than 1.6
Outdoor temperature
Settings in the factory set condition:
H Slope = 1.4
H Shift = 0
54
5513 463 - 06
Page 55
Vitotronic 300, GW6B Installation and Service
Adjusting the Heating Curve (continued)
Commissioning
Standard set room temperature
Adjustment of the standard set room temperature from 68 to 79°F (20 to 26°C)
Legend
A Boiler water temperature or supply temperature B Outdoor temperature C Set room temperature D Heating circuit pump “Off” E Heating circuit pump “On”
Selecting the set room temperature
Individually adjustable for each heating circuit. The heating curve is offset along the set room temperature axis. With the heating circuit pump logic function enabled, the curve modifies the starting and stopping characteristics of the heating circuit pump.
Changing the standard set room temperature
Refer to the Operating Instructions
Reduced set room temperature
Adjustment of the reduced set room temperature from 37 to 52°F (3 to 14°C)
Legend
A Boiler water temperature or supply temperature B Outdoor temperature C Set room temperature D Heating circuit pump “Off” E Heating circuit pump “On”
Changing the standard set room temperature
Refer to the Operating Instructions
5513 463 - 06
55
Page 56
Commissioning
Adjusting the Heating Curve (continued)
Boiler water or
supply temperature
Vitotronic 300, GW6B Installation and Service
Changing the slope and shift
Individually adjustable for each heating circuit.
From the home screen tap the following buttons:
1. Tap “Menu”.
2. “Heating circuit 1”, “Heating circuit 2” or “Heating circuit 3” as the required heating circuit
3. Heating.
4. “Heating curve”
5. +/– for the required value for “Slope” or “Shift”
Outdoor temperature
Legend
A Changing the slope B Changing the shift (vertical parallel offset of the
heating curve)
6. Tap OK to confirm
Example: Heating curve setting with slope 1.5:
56
5513 463 - 06
Page 57
Vitotronic 300, GW6B Installation and Service
Calling up the Service Menu
Service Scans
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. Select the required menu range.
Note: In the “Diagnosis” menu area submenus are shown subject to control unit, e.g. “Cascade” will only be shown for a cascade control unit.
“Service main menu”
“Diagnosis”
“General”
“Cascade”
“DHW”
“Heating circuit 1/2/3”
“Solar energy”
“Short query”
“Reset data”
“Actuator test”
“System configuration”
“Coding level 1”
“Coding level 2”
“History of faults”
“Service functions”
“LON participant check”
“System log”
“Vitocom PIN input”
“Startup”
“The heating system is reset to the factory state”
“Change passwords”
“Service level”
“Coding level 2”
“Reset all passwords”
“Exit service”
5513 463 - 06
Note: - “Coding level 2” is only displayed if this level has been enabled: Enter “viexpert” password.
- Tap
to return to the “Service main menu”
57
Page 58
Service Scans
Leaving the Service Menu
Change Passwords
Vitotronic 300, GW6B Installation and Service
From the service main menu tap the following buttons:
1. “Exit service”
2. Confirm “Terminate service?” with OK.
Note: The system exits the service menu automatically after 30 min.
In the factory set condition, the following passwords have been assigned:
H “viservice” for access to the “Service main menu”
H “viexpert” for access to “Coding level 2”
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Change passwords”
5. “Service level” or “Coding level 2”
6. Enter current password.
7. Confirm with OK.
8. Enter new password.
9. Tap OK twice
Resetting all Passwords to Factory Settings
From the home screen tap the following buttons:
1. Request the master password from the Technical Service at the Viessmann Group.
2. “Menu”
3. “Service”
4. Enter “viservice” password.
5. “Change passwords”
6. “Reset all passwords”
7. Enter master password. This must be requested from the service hotline.
8. Confirm twice with OK.
58
5513 463 - 06
Page 59
Vitotronic 300, GW6B Installation and Service
Scanning Operating Data
Resetting Operating Data
Service Scans
Operating data can be scanned in various areas (see “Diagnosis” on page 54). Operating data on heating circuits with mixing valves and a solar thermal system can only be scanned if the relevant components are installed in the system. For further information on operating data, see chapter “Brief scan”.
Note: “- - -” appears on the display if a scanned sensor is faulty.
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Diagnosis”
5. Select required group, e.g. “General”.
Saved operating data (e.g. hours run) can be reset to 0. The value "Dampened outdoor temp" is reset to the actual value.
From the home screen tap the following buttons:
1. "Menu"
2. "Service"
3. Enter "viservice" password.
4. "Diagnosis"
5. "Reset data"
6. Select required value or "All details".
5513 463 - 06
59
Page 60
Service Scans
Brief Scan
Vitotronic 300, GW6B Installation and Service
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Diagnosis”
5. “Short query”
6. “Code” An overview of brief scans appears with 11 lines and 6 fields. with the following tables.
for the required brief scan in line
123456
1: System schemes 01 to 10 Control unit software version Software version, programming unit 2: 0 0 0 Appliance identification CU-ID 3: 0 0 Number of KM BUS participants Software version
Solar control module type SM1 4:000000 5:0000Software version,
AM1 extension
6: Connection on
plug aVD.1/2 0: Contact open 1: Contact closed
7: LON subnet address/system number LON node address
8: SNVT config.
0: Auto 1: Tool
Heating circuit HC1 Heating circuit HC2 Heating circuit HC3
9: Remote control
0: Without 1: Vitotrol 200A
2: Vitotrol 300A 10:000000 11: 0 0 Software
Connection on plug aVD.2/3 0: Contact open 1: Contact closed
Software version Communic. coproc.
Software version Remote control
0000
00
Connection on plug aVD.2/3 Neuron Chip Software version
Remote control 0: Without 1: Vitotrol 200A 2: Vitotrol 300A
version, extension for heating circuits 2 and 3 with mixing valve Note: The displays in fields 3 and 5 are the same.
Software version Remote control
0 Software
Participant number
Remote control 0: Without 1: Vitotrol 200A 2: Vitotrol 300A
version, extension for heating circuits 2 and 3 with mixing valve
Software version, EA1 extension
Software version Remote control
0
60
5513 463 - 06
Page 61
Vitotronic 300, GW6B Installation and Service
Maintenance Display
Service Scans
Set limits in coding “21” and “23” in the “Boiler” group. Once these values have been reached, “Service” and symbol
Tap the following buttons:
1. “Confirm” The footer shows
2.
Note: After tapping the following will be displayed if your heating system has several fault messages simultaneously:
3. “Service messages” The service messages appear yellow in a list.
After maintenance has been carried out
Note: If a service is carried out prematurely, set
coding “24:1” in the “Boiler” group to “24:0”. The selected maintenance coding for hours run and time intervals restart at 0. If coding “24” is not reset, “Service” will be displayed again on the following Monday.
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “Service functions”
5. “Reset service” The set service coding for hours run and interval restart at 0 and coding “24” in the “Boiler” group is set to “24:0”.
appear on the display.
.
5513 463 - 06
61
Page 62
Troubleshooting
Fault Display
Vitotronic 300, GW6B Installation and Service
In the event of a fault, the red fault display flashes at the control unit. The display shows symbol
Note: If a central fault message facility is connected, this is started.
For an explanation of fault messages, see chapter “Fault messages”.
Acknowledge fault display
Tap “Close”. The footer shows
Note: Any connected central fault message facility stops. If an acknowledged fault is not remedied, the fault message will be re-displayed the following day at 07:00 h, and the fault message facility restarts.
Calling up acknowledged fault messages
Tap the following buttons:
1.
Note: After tapping the following will be displayed if your heating system has several fault messages simultaneously:
2. “Faults” The fault messages appear in red and in chronological order in a list.
.
and “Fault”.
Calling up fault codes from the fault memory (fault history)
The 10 most recent faults (including those remedied) are saved and can be scanned. Faults are sorted by date.
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “History of faults”
5. Call up further information in the relevant fault with
6. Tap “Reset” to delete the list.
?.
62
5513 463 - 06
Page 63
Vitotronic 300, GW6B Installation and Service
Boiler System Fault Codes
Troubleshooting
Displayed fault code
0f Control mode. Service “0f” is only displayed in
10 Operates as if the outdoor
18 Operates as if the outdoor
20 Standalone control unit without
28 Standalone control unit without
30 H With DHW tank: DHW pump
38 H With DHW tank: DHW pump
40 Mixing valve is being closed. Short circuit, supply temperature
44 Mixing valve is being closed. Short circuit, supply temperature
48 Mixing valve is being closed. Lead break, supply temperature
4c Mixing valve is being closed. Lead break, supply temperature
System characteristics Cause Measures
the fault history.
Short circuit, outdoor
temperature was 32°F (0°C).
temperature was 32°F (0°C).
supply temperature sensor (possibly supply temperature not high enough)
supply temperature sensor (possibly supply temperature not high enough)
ON, boiler is maintained at set tank temperature.
H Without DHW tank: Boiler is
regulated by the temperature controller.
ON, boiler is maintained at set tank temperature.
H Without DHW tank: Boiler is
regulated by the temperature controller.
temperature sensor.
Lead break, outdoor temperature sensor.
Short circuit, common supply temperature sensor
Lead break, common supply temperature sensor
Short circuit, boiler water temperature sensor
Lead break, boiler water temperature sensor
sensor, heating circuit with mixing valve M2 (heating circuit 2).
sensor, heating circuit with mixing valve M3 (heating circuit 3).
sensor, heating circuit with mixing valve M2 (heating circuit 2).
sensor, heating circuit with mixing valve M3 (heating circuit 3).
Service required
Note: After servicing, set code “24:0”.
Check outdoor temperature sensor (see page 121).
Check outdoor temperature sensor (see page 121).
Check the supply temperature sensor (see page 121).
Check the supply temperature sensor (see page 121).
Check boiler water temperature sensor.
Check boiler water temperature sensor.
Check supply temperature sensor (see page 121).
Check supply temperature sensor (see page 121).
Check supply temperature sensor (see page 121).
Check supply temperature sensor (see page 121).
5513 463 - 06
63
Page 64
Troubleshooting
Boiler System Fault Codes (continued)
Vitotronic 300, GW6B Installation and Service
Displayed fault code
50 Tank loading pump on:
51 With tank loading system:
52 Control mode Short circuit, supply temperature
58 Tank loading pump on:
59 With tank loading system:
5a Control mode Lead break, low loss header
60 Boiler with maximum
68 Boiler with maximum
System characteristics Cause Measures
Short circuit, tank temperature DHW temperature target = set supply temperature Priority control is cancelled. or With tank loading system: Tank heating is started and stopped via tank temperature sensor 2.
Tank heating is started and stopped via tank temperature sensor 1.
DHW temperature target = set supply temperature Priority control is cancelled. or With tank loading system: Tank heating is started and stopped via tank temperature sensor 2.
Tank heating is started and stopped via tank temperature sensor 1.
temperature, no output reduction, mixing valve return temperature control open
temperature, no output reduction, mixing valve return temperature control open
sensor 1
Short circuit, DHW tank
temperature sensor 2.
sensor low loss header.
Lead break, DHW tank
temperature sensor 1.
Lead break, DHW tank
temperature sensor 2.
supply temperature sensor.
Short circuit, temperature
sensor aJA.
Lead break, temperature
sensor aJA.
Check tank temperature sensor (see page 121).
Check the DHW tank temperature sensor (see page 121).
Check supply temperature sensor (see page 121).
Check DHW tank temperature sensor (see page 121).
Check DHW tank temperature sensor (see page 121).
Check supply temperature sensor (see page 121). Without supply temperature sensor: Set code “52:0” in the “General” group.
Check temperature sensor (see page 121).
Check temperature sensor (see page 121). Without temperature sensor: Set coding “4a:0” in the “General” group.
64
5513 463 - 06
Page 65
Vitotronic 300, GW6B Installation and Service
Boiler System Fault Codes (continued)
Troubleshooting
Displayed fault code
70 Shunt pump constantly ON.
78 Shunt pump constantly ON
90 Control mode Short circuit, temperature sensor
91 Control mode Short circuit, temperature sensor
92 No solar DHW heating. Short circuit, collector
93 Control mode. Short circuit, temperature sensor,
94 No solar DHW heating. Short circuit, DHW tank
System characteristics Cause Measures
Short circuit, temperature With tank loading system: close 3-way mixing valve; no DHW heating
With tank loading system: close 3-way mixing valve; no DHW heating
sensor aJB.
Lead break, temperature
sensor aJA.
/ connection at solar control
module, type SM1.
, connection at solar control
module, type SM1.
temperature sensor, connection
of temperature sensor & at solar
control module, type SM1 or
sensor at S1 of the Vitosolic.
connection at S3 of the Vitosolic.
temperature sensor, connection
of temperature sensor % at solar
control module, type SM1 or
sensor at S2 of the Vitosolic.
Check temperature sensor (see page 121).
Check temperature sensor (see page 121). Without temperature sensor: Set code “4b:0” in the “General” group.
Check temperature sensor / (see separate installation and service instructions).
Check temperature sensor (see separate installation and service instructions).
Check sensor at the solar control unit (see separate installation and service instructions).
Check sensor at the solar control unit (see separate installation and service instructions).
Check sensor at the solar control unit (see separate installation and service instructions).
5513 463 - 06
65
Page 66
Troubleshooting
Boiler System Fault Codes (continued)
Vitotronic 300, GW6B Installation and Service
Displayed fault code
98 Control mode Lead break, temperature sensor
99 Control mode Lead break, temperature sensor
9a No solar DHW heating. Lead break, collector temperature
9b Control mode Lead break, temperature sensor,
9c No solar DHW heating. Lead break, DHW tank temperature
9e Control mode No supply rate in solar circuit or
9f Control mode Fault, solar control module, type
a7 Control mode Programming unit fault Replace the programming unit.
ab Control mode, DHW tank may be
System characteristics Cause Measures
Check temperature sensor / (see separate installation and service instructions). Check coding address “20” in the “Solar” group.
Check temperature sensor (see separate installation and service instructions). Check coding address “20” in the “Solar” group.
Check sensor at the solar control unit (see separate installation and service instructions).
Check sensor at the solar control unit (see separate installation and service instructions).
Check sensor at the solar control unit (see separate installation and service instructions).
Check solar circuit. Acknowledge fault message (see separate installation and service instructions).
Check solar control unit (see separate installation and service instructions).
Insert plug aJB and check codes.
cold
/, connection at solar control
module, type SM1.
, connection at solar control
module, type SM1.
sensor, connection of
temperature sensor & at solar
control module, type SM1 or
sensor at S1 of the Vitosolic.
connection to S3 of the Vitosolic.
sensor, connection of
temperature sensor % at solar
control module, type SM1 or
sensor at S2 of the Vitosolic.
flow rate too low, or temperature
limiter has responded.
SM1 or Vitosolic
Displayed if a fault occurs at
these devices that has no fault
message in the Vitotronic.
Tank loading system
configuration fault:
Coding “55:3” in the “DHW”
group has been set, but plug
aJB is not plugged in and/or
codes “4c:1” and “4e:2” in the
“General” group have not been set.
66
5513 463 - 06
Page 67
Vitotronic 300, GW6B Installation and Service
Boiler System Fault Codes (continued)
Troubleshooting
Displayed fault code
b1 Control mode Communication error,
b5 Control mode Internal fault Check PCB is plugged in
b6 Constant mode Invalid hardware recognition Check coding address “92” in
b7 Boiler water temperature control Coding card fault Plug in or replace the boiler
ba Mixing valve close Communication error, PCB,
bc Control mode without
bd Control mode without
be Control mode without
bf Control mode
c1 Boiler cools down External safety equipment at plug
c2 Control mode Lead break, KM BUS to solar
System characteristics Cause Measures
Check connections, and replace
remote control.
remote control
remote control
No communication via LON
programming unit
extension for heating circuits 2
and 3 with mixing valve.
Communication error, Vitotrol
remote control unit, heating
circuit without mixing valve A1
(heating circuit 1).
Communication error, Vitotrol
remote control unit, heating
circuit with mixing valve M2
(heating circuit 2)
Communication error, Vitotrol
remote control unit, heating
circuit with mixing valve M3
(heating circuit 3)
Incorrect LON communication
module.
aBÖ.
control module, type SM1 or
Vitosolic.
the programming unit if required.
correctly.
the “General” group;
H 161: Single boiler system
H 190: Cascade control unit
H 166: Lag boiler control unit Note: Coding “8a:176” in the “General” group must be set in order for coding “92” to be able to be displayed.
coding card (see page 25).
Check that the PCB and ribbon cable are plugged in correctly, and replace PCB if required.
Check connections, lead (see separate installation and service instructions) and coding address “a0” in the “Heating circuit...” group.
Check connections, lead (see separate installation and service instructions) and coding address “a0” in the “Heating circuit...” group.
Check connections, lead (see separate installation and service instructions) and coding address “a0” in the “Heating circuit...” group.
Replace LON communication module.
Check connection and external safety equipment (see page 36 and 37)
Check KM BUS cable and appliance. Without solar control unit: Set code “54:0” in the “General” group.
5513 463 - 06
67
Page 68
Troubleshooting
Boiler System Fault Codes (continued)
Vitotronic 300, GW6B Installation and Service
Displayed fault code
c3 Control mode Communication error, AM1
cF Control mode
d3 Control mode Communication error, extension
d4 Boiler cools down MCB F2 has responded. Check MCB F2 and jumper
d6 Control mode Input DE1 at extension EA1
d7 Control mode Input DE2 at extension EA1
d8 Control mode Input DE3 at extension EA1
da Control mode without
db Control mode without
dc Control mode without
dd Control mode without
de Control mode without
df Control mode without
System characteristics Cause Measures
Check connections.
No communication via LON.
room influence.
room influence
room influence.
room influence.
room influence.
room influence.
extension
Communication error, control unit LON communication module.
EA1.
reports a fault.
reports a fault.
reports a fault.
Short circuit, room temperature sensor, heating circuit without mixing valve A1 (heating circuit 1).
Short circuit, room temperature sensor, heating circuit with mixing valve M2 (heating circuit 2).
Short circuit, room temperature sensor, heating circuit with mixing valve M3 (heating circuit 3).
Lead break, room temperature sensor, heating circuit without mixing valve A1 (heating circuit 1).
Lead break, room temperature sensor, heating circuit with mixing valve M2 (heating circuit 2).
Lead break, room temperature sensor, heating circuit with mixing valve M3 (heating circuit 3).
Without AM1 extension: Set coding “32:0” in the “General” group.
Check LON communication module and replace if required. If no LON communication module is installed, set code “76:0” in the “General” group.
Check connections (see page
122). Without extension EA1: Set code “5b:0” in the “General” group.
on plug aBA.
Remove fault at appliance concerned.
Remove fault at appliance concerned.
Remove fault at appliance concerned.
Check room temperature sensor (see page 121).
Check room temperature sensor (see page 121).
Check room temperature sensor (see page 121).
Check room temperature sensor (see page 121).
Check room temperature sensor (see page 121).
Check room temperature sensor (see page 121).
68
5513 463 - 06
Page 69
Vitotronic 300, GW6B Installation and Service
Burner Fault Codes
Troubleshooting
Displayed fault code
d1 Boiler cools down Burner fault Check the burner.
d5 Boiler ramps to the electronic
E1 Burner control unit in a fault
E2 Burner control unit in
E3 Burner control unit in a fault
E4 Burner shuts down Multiple detection of
E5 Burner control unit in
EE Burner control unit in a fault
EF Burner control unit in a fault
E0 Operation according to internal
F1 Burner control unit in a fault
F2 Burner control unit in a fault
F3 Ionization flame monitor reports
System characteristics Cause Measures
maximum boiler water temperature limit.
state.
a fault state.
Shortage of gas to gas pressure switch 2; valve leak test.
state.
a fault state.
state.
state.
burner control unit defaults.
state; system cools down.
state; system cools down.
faulty flame signal during start­up or after the post-purge.
No communication between boiler circuit and cascade control unit
Valve 1 not tight / gas pressure switch 2 does not open.
Valve 2 not tight; gas pressure switch 2 does not close.
Gas valve does not open; gas valve leaking; gas pressure switch 2 faulty.
Lead break, strapping plug fJ. Check strapping plug fJ.
undervoltage with return and renewed undervoltage.
Internal fault of the burner control unit and during test of ionization input.
Internal error in feedback from gas safety valves; output relay does not respond.
Internal error in feedback from gas safety valves; output relay does not respond.
Communication error, burner control unit.
Flue gas excess temperature; excessive gas throughput.
Excessive boiler water temperature.
Gas valve not gas tight (gas is escaping and burning); incorrect coding card.
Check communication by means of a participant check.
Check setting of gas pressure switch 2; check connecting cable; replace gas valve.
Check setting of gas pressure switch 2; check connecting cable; replace gas valve.
Replace gas valve.
Check the power supply.
Replace burner control unit.
Reset burner control unit; replace burner control unit.
Reset burner control unit; replace burner control unit.
Check plug and KM BUS to burner control unit.
Wait until temperature falls below the permissible flue gas temperature. Reset burner control unit. Check water level; check heat exchanger surfaces for contamination; check CO setting; set gas throughput according to rated heating output of boiler (for connection values, see boiler service instructions).
Wait until temperature falls below the permissible boiler water temperature. Reset burner control unit.
Check ionization path; replace coding card; replace gas valve.
2
5513 463 - 06
69
Page 70
Troubleshooting
Burner Fault Codes (continued)
Vitotronic 300, GW6B Installation and Service
Displayed fault code
F4 No flame formation during safety
F5 Air pressure switch shows no air
F6 Gas pressure switch notifies no
F7 Fan pressure is produced during
F8 Flame extinguishes during
System characteristics Cause Measures
time; ionization flame monitor reports no flame signal.
No flame formation during safety time; ionization flame monitor reports no flame signal.
No flame formation during safety time; ionization flame monitor reports no flame signal.
Poor start-up characteristics; rotary damper does not close.
Flame does not build during the safety time, no signal captured by the ionization flame monitor.
Flame does not build during the safety time, no signal captured by the ionization flame monitor.
Flame does not build during the safety time, no signal captured by the ionization flame monitor.
pressure, fan not running.
Air pressure switch switches off during operation.
gas pressure.
the air pressure switch idle state check.
Air pressure switch contact is not in the idle state.
operation.
Flame extinguishes during operation.
Flame extinguishes during operation.
Ionization electrode incorrectly adjusted; ionization electrode not plugged in. Ground leakage of electrode or cable.
Ignition electrodes incorrectly adjusted, electrodes grounded, faulty ignition unit, faulty burner control unit.
Insulation body of ignition or ionization electrode cracked.
Servomotor faulty, servomotor connecting cable faulty, output relay faulty (burner control unit).
Incorrect gas type selected. Select gas type (see boiler
Gas valve does not open. Check connecting cable; check
Combustion characteristics not ideal.
Air pressure switch is faulty, incorrectly connected or incorrectly set.
Flue gas back pressure; condensate banked up; air pressure switch hose faulty; connecting hose leaking.
Gas shut-off valve closed; gas pressure switch faulty; multiple problems with gas supply.
Wind influence on fan. Check the flue draught (chimney)
Air pressure switch faulty. Replace the air pressure switch.
Incorrect gas type selected. Select gas type (see boiler service
Burner gauze assembly faulty. Check burner gauze assembly;
Combustion characteristics not ideal.
Insert plug of ionization electrode; check cables; adjust ionization electrode (see boiler service instructions)
Adjust ignition electrodes (see boiler service instructions); replace ignition unit; replace burner control unit.
Replace ignition or ionization electrode
Replace connecting cable; replace servomotor; replace burner control unit.
service instructions).
gas valve and replace if required.
Adjust the burner (see boiler service instructions); if necessary also adjust the setting screws when the burner is off to be able to start the burner).
Replace air pressure switch, connect or set correctly.
Remove flue gas back pressure; check if condensate banked up; reset burner control unit; replace hose.
Open gas shut-off valve; check gas flow pressure; replace gas filter if required; reset burner control unit; replace gas valve.
instructions).
replace if damaged.
Adjust burner (see boiler service instructions).
70
5513 463 - 06
Page 71
Vitotronic 300, GW6B Installation and Service
Burner Fault Codes (continued)
Troubleshooting
Displayed fault code
F9 Fan not running; fan speed not
Fa Fan runs without demand; burner
Fd Burner control unit in a fault
80 Burner control unit in a fault
81 Burner control unit in a fault
82 Burner control unit in a fault
83 Burner control unit in a fault
88 Burner control unit in a fault
89 Burner control unit in a fault
b8 Constant mode Lead break, flue gas temperature
System characteristics Cause Measures
Fan faulty; cables are faulty or
reached.
Status duration too long, fan ramp-up.
Varying fan speed
No fan feedback. Fan faulty, external fan power
control unit in a fault state.
state; system cools down; burner control unit locked out.
state; system cools down; burner control unit locked out.
state.
state; system cools down; burner control unit locked out.
state.
state.
state.
broken.
Internal fault; fan cannot reach its set value.
Fan faulty, cable a-ÖA faulty or broken. Check cable a-ÖA; check external power supply; replace the cable or fan; remove foreign bodies.
supply not connected or faulty cable a-ÖA or cable broken, fan blocked (poss. by foreign bodies).
Fan does not reach idle state, cable a-ÖA faulty, fan faulty, faulty burner control unit.
Burner control unit in a fault state.
Short circuit, boiler water temperature sensor, burner control unit.
Sensor drift, boiler water temperature sensor, burner control unit.
Short circuit, flue gas temperature sensor (A or B), burner control unit.
Sensor drift, flue gas temperature sensor (A or B), burner control unit.
Lead break, boiler water temperature sensor, burner control unit.
Lead break, flue gas temperature sensor (A or B), burner control unit.
sensor
Check cables and replace the fan if required
Replace fan or burner control unit.
Check cable; replace cable a-ÖA or fan.
Check cable a-ÖA; check external power supply; replace cable or fan; remove foreign bodies.
Fan subject to wind influence, check flue outlet and fan, replace cable a-ÖA, replace fan, replace burner control unit.
Read off fault at the burner control unit display and programming unit (boiler service instructions).
Check lead and dual sensor; replace sensor if required.
Check lead and dual sensor; replace sensor if required.
Check lead and sensors (A or B), replace sensor if required.
Check lead and sensors (A and B), replace sensor if required.
Check lead and dual sensor; replace sensor if required.
Check lead and sensors (A and B), replace sensor if required.
Remove temperature sensor. Set code “1f:0” in the “Boiler” group.
Fault message to the burner control unit:
Refer to the Boiler Service Instructions
Note: If LON participant faults occur, “Fault participant” ... is displayed.
5513 463 - 06
71
Page 72
Function Description
Boiler Water Temperature Control
Vitotronic 300, GW6B Installation and Service
Brief description
H The boiler water temperature is regulated by modulating
the burner.
H The set boiler water temperature is determined from
the following coding: – Set supply temperature of the heating circuits connected to the control unit and the heating circuits connected via the LON BUS – External demand – DHW temperature target
H When the DHW tank is heated, the default set boiler
water temperature is 20 K above the set DHW
temperature (adjustable via coding “60” in the “DHW” group).
Emissions test function
In multi boiler systems, enable the emissions test function on all control units.
The following functions are activated:
H Burner start
H Starting all pumps
Note: Only the heating circuit pump is switched ON in the case of lag boiler control.
H Mixing valve remains set to control function Function duration < 30 min: The burner operates at 100% output until the temperature limiter in the burner control unit switches off. The burner then cycles, with 100% output, around the value at the temperature limiter. Function duration > 30 min (continuous): Boiler water temperature at max. set value, e.g. 194°F (90°C). The burner is operated in modulating mode. This prevents excessive cycling if emissions testing is carried out over an extended period.
Cascade Control Unit
72
Brief description
The supply temperature is regulated by starting or stopping the burners or by starting/stopping individual burner stages.
H Standalone control (see page 73)
H Sequential control (see page 73)
H Subject to system version, a difference is made
between the condensing strategy (see page 74) and 2 conventional boiler strategies (see pages 75 and 76).
5513 463 - 06
Page 73
Vitotronic 300, GW6B Installation and Service
Cascade Control Unit (continued)
Function Description
Set supply temperature
The set supply temperature is determined from the following coding:
H Set supply temperature of heating circuit without
mixing valve A1 (heating circuit 1) and heating circuits
with mixing valve M2 (heating circuit 2) and M3
(heating circuit 3).
H Set supply temperature of further consumers.
H DHW temperature target.
H External demands.
Upper control range limits: Maximum system supply temperature limit (coding “37” in the “Cascade” group). Lower control range limits: Minimum system supply temperature limit (coding “36” in the “Cascade” group).
Standalone control
Note: Vitocrossal 200, type CM2, operate in parallel
and with condensing strategy
Boilers connected in parallel Boilers connected in series
H Without and with supply temperature sensor
(see the following table).
H The cascade control specifies the set boiler water
temperature for all currently active boilers. Every boiler control unit regulates to the specified set value.
The following control strategies are available:
H Condensing strategy (see page 77)
H Conventional boiler strategy 1 (see page 79)
H Conventional boiler strategy 2 (see page 79)
With supply temperature sensor Without supply temperature sensor
Set coding “3b:1” or “3b:3” in the “Cascade” group. The control deviation is calculated from the set supply temperature and the actual supply temperature to determine the start and shutdown criteria.
5513 463 - 06
H Without and with supply temperature sensor
(see the following table).
H The control strategy is set automatically to
conventional boiler strategy 2, coding “3c:2” in the “Cascade” group (see page 79).
H The cascade control specifies the set boiler water
temperature for all currently active boilers. Every boiler control unit regulates to the specified set value. If the lead boiler (condensing boiler) does not achieve the specified set value, it will only act to control the return temperature of the conventional boiler downstream. The conventional boiler is started late and is also shut down late.
Set coding “3b:0” or “3b:2” in the “Cascade” group. To determine the start and stop criteria, the control deviation is calculated from the set boiler water temperature and the estimated average actual boiler water temperature of the currently active boilers. Only boilers with open motorized isolation valves are taken into consideration.
Sequential control
H With supply temperature sensor.
H Set coding “3b:4” in the “Cascade” group.
H The control strategy is set automatically to conventional boiler strategy 2, coding “3c:2” in the “Cascade”group (see page 76).
H The cascade control unit regulates to the specified set
supply temperature by stipulating the output for each individual boiler. The lead boiler can be operated in modulating mode. All other boilers are operated in two stages via a specified output (incl. modulating burners).
73
Page 74
Function Description
Cascade Control Unit (continued)
Vitotronic 300, GW6B Installation and Service
Control strategies
Condensing strategy
Benefit: Optimum utilization of the condensing effect and long burner runtimes Set coding “3c:0” in the “Cascade” group. It is the aim of the condensing strategy to operate as many boilers as possible at the lowest output level.
H Starting criterion: An output statement causes the boilers to be started (coding “3d:1” in the “Cascade” group). An additional boiler will start if the current heat demand can also be covered by the currently active boilers plus the next boiler in the boiler sequence (see page 52).
H Shutdown criterion: The boilers are shut down via a shutdown integral. The shutdown criterion is met when the shutdown integral exceeds a limit set at coding “46” in the “Cascade” group and the boiler started last will be shut down.
Example (coding “3c:0” in the “Cascade” group) Two-boiler system with modulating burners:
H Boiler 1: 100% rated heating output (base load set to 33%)
H Boiler 2: 100% rated heating output (base load set to 33%)
Starting
Shutdown
74
5513 463 - 06
Page 75
Vitotronic 300, GW6B Installation and Service
Cascade Control Unit (continued)
Function Description
Control strategies
Conventional boiler strategy 1
Benefit: As few boilers as possible are active. Set coding “3c:1” in the“Cascade” group. Conventional boilers are preferably operated at their upper output range, to reliably prevent formation of condensate due to low return temperatures. An additional boiler will only be started if the maximum output of all currently active burners is insufficient to achieve the set supply temperature. A boiler will be shut down when the remaining boilers can achieve the required output on their own.
H Starting criterion: The boilers are started via a starting integral. The next boiler in the boiler sequence will be started if the value set in coding “45” in the “Cascade” group is exceeded (see page 52).
H Shutdown criterion: An output reduction causes the boiler to shut down (coding “3d:1” in the “Cascade” group). A boiler is shut down when the current heat demand can be covered without the boiler that was started last.
Example: Two-boiler system with modulating burners:
H Boiler 1: 100% rated heating output (base load set to 33%)
H Boiler 2: 100% rated heating output (base load set to 33%)
Conventional boiler strategy 1 (coding “3c:1” in the “Cascade” group)
Starting
Shutdown
5513 463 - 06
75
Page 76
Function Description
Cascade Control Unit (continued)
Vitotronic 300, GW6B Installation and Service
Control strategies
Conventional boiler strategy 2
Benefit: Long burner runtimes. Coding “3c:2” in the “Cascade” group (factory set condition). An additional boiler will only be started if the maximum output of all currently active burners is insufficient to achieve the set supply temperature. A boiler will be shut down if the burners were ramped down to their minimum output because of a major negative control deviation and the output is still too high.
H Starting criterion: The boilers are started via a starting integral. The next boiler in the boiler sequence will be started if the value set in coding “45” in the “Cascade” group is exceeded (see page 52).
H Shutdown criterion: The boilers are shut down via a shutdown integral. The shutdown criterion is met when the shutdown integral exceeds a limit set at coding “46” in the “Cascade” group and the boiler started last will be shut down.
Example: Two-boiler system with modulating burners:
H Boiler 1: 100% rated heating output (base load set to 33%)
H Boiler 2: 100% rated heating output (base load set to 33%)
Conventional boiler strategy 2 (coding “3c:2” in the “Cascade” group)
Starting
Shutdown
76
5513 463 - 06
Page 77
Vitotronic 300, GW6B Installation and Service
Heating Circuit Control Unit
Function Description
Only for single boiler and cascade control units
Brief description
H The control unit features control circuits for one heating
circuit without mixing valve A1 (heating circuit 1) and two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3).
H The set supply temperature of each boiler is determined
from the following coding: – Outdoor temperature – Set room temperature – Operating mode – Heating curve slope and shift
H The supply temperature of the heating circuit without
mixing valve corresponds to the common system supply
temperature.
H The supply temperature of the heating circuits with
mixing valve is regulated by the stepped opening or
closing of the mixing valves. The mixing valve motor control changes the actuating and pause times subject to the control differential (control deviation).
Functions
The heating circuit without mixing valve is subject to the boiler water temperature and its control range limits. The heating circuit pump is the only actuator. The supply temperature of the heating circuits with mixing valve is captured by the supply temperature sensor of the relevant heating circuit.
H Upper control limit: Electronic maximum supply temperature limit coding address “c6” in the “Heating circuit...” group.
H Lower control range limit: Electronic minimum supply temperature limit coding address “c5” in the “Heating circuit...” group.
Time program
The control unit switches over according to the time program. In the “Heating and DHW” operating program, the control unit switches between “Central heating with standard room temperature” and “Central heating with reduced room temperature”. Every operating mode has its own set level. 4 time phases per day can be selected.
Outdoor temperature
A heating curve must be set for matching the control unit to the building and the heating system. The heating curve characteristics determine the set boiler water temperature subject to outdoor temperature. The control unit uses an average outdoor temperature. This comprises the actual and the adjusted outdoor temperature.
Room temperature
In conjunction with a remote control and room temperature hook-up (coding “b0” in the “Heating circuit...”) group: Compared with the outdoor temperature, the room temperature has a greater influence on the set boiler water temperature (changed at coding “b2” in the “Heating circuit...” group). In conjunction with heating circuits with mixing valve: For control differentials (actual value deviation) above 2 K room temperature, the influence can be increased further (coding “b6” in the “Heating circuit...” group):
H Quick heat-up The set room temperature must be raised by at least 2 K by the following measures: – Enabling comfort mode – Changing from central heating with reduced temperature to central heating with standard temperature – Start optimization (coding “b7” in the “Heating circuit...” group) Quick heat-up will stop when the set room temperature has been reached.
H Quick setback The set room temperature must be reduced by at least 2 K by the following measures: – Activating economy mode – Changing from central heating with standard temperature to central heating with reduced temperature – Shutdown time optimization (coding address “c1” in the “Heating circuit...” group) Quick setback ends when the set room temperature has been reached.
5513 463 - 06
77
Page 78
Function Description
Heating Circuit Control Unit (continued)
Vitotronic 300, GW6B Installation and Service
DHW temperature Priority control
H With priority control: (coding address “a2:2” in the
“Heating circuit...” group): The set supply temperature will be adjusted to 32°F (0°C) during tank heating. The mixing valve closes and the heating circuit pump is switched off.
H Without priority control: The heating circuit control unit continues to operate with the same set value.
H With modulating priority control in conjunction with
heating circuits with mixing valve: The heating circuit pump remains switched on. During tank heating the set supply temperature of the heating circuit will be reduced until the set boiler water temperature has been reached. The set supply temperature is determined from the following coding: – Outdoor temperature – Differential between the set and the actual boiler water temperature – Heating curve slope and shift – Set coding “a2” in the “Heating circuit...” group
Heating circuit pump logic – Economy circuits
The heating circuit pump is switched OFF [set supply temperature set to 32°F (0°C)] if one of the following criteria is met:
H The outdoor temperature selected in coding “a5”
in the “Heating circuit...” group exceeds the set value.
H The adjusted outdoor temperature exceeds the value
set in coding“a6” in the “Heating circuit...” group.
H The mixing valve has been attempting to close for more
than 12 min. (mixing valve economy function, coding
“a7” in the “Heating circuit...” group).
H The pump idle time selected in coding “a9” in the “Heating circuit ...” group is reached. Requirements: – There is no risk of frost. – Coding “b0” in the “Heating circuit...” group must be set to 0.
Note: If, during the pump idle time, the system is switched to heating mode or the set room temperature is increased, the heating circuit pump is switched ON,even if the time has not yet elapsed.
H The actual room temperature exceeds the value set in coding “b5” in the “Heating circuit ...” group.
System dynamics The mixing valve control characteristics can be influenced at coding “c4” in the “Heating circuit...” group.
Central control
Coding “7a” in the “General” group enables you to program central control to one heating circuit. The operating and holiday program then applies to all additional heating circuits of the system. For these heating circuits, when the operating and holiday program is enabled,“Central control” is displayed. Any holiday programs that may have been set will be deleted. Party and economy modes cannot be enabled on all control units.
Frost protection
The supply temperature is held in accordance with the heating curve for the reduced set room temperature, but at least at 50°F (10°C). A variable frost limit can be set in line with coding address “a3” in the “Heating circuit...” group.
78
5513 463 - 06
Page 79
Vitotronic 300, GW6B Installation and Service
Heating Circuit Control Unit (continued)
Legend
A Max. boiler water temperature B Slope = 1.8 for heating circuit without mixing valve C Slope = 1.2 for heating circuit with mixing valve D Boiler water temperature (with a differential
temperature = 8 K) E Lower boiler water temperature, defaulted by the boiler coding card
Supply temperature
Legend
A Maximum supply temperature limit (coding “37” in the “Cascade” group)
B Slope = 1.8 for heating circuit without mixing valve C Slope = 1.2 for heating circuit with mixing valve D Common supply temperature (at a differential
temperature = 8 K) E Lower common supply temperature
Function Description
Supply temperature control single boiler control unit
Differential temperature: The differential temperature can be set at coding “9f” in the “General”group, factory set condition: 8 K. The differential temperature is the minimum value by which the boiler water temperature should be higher than the highest currently required supply temperature of the heating circuit with mixing valve.
H System with only one heating circuit with mixing valve: The set boiler water temperature will be automatically regulated to 8 K above the set supply temperature.
H System with heating circuit without mixing valve and
heating circuit with mixing valve: The set boiler water temperature operates in accordance with its own heating curve. The differential temperature of 8 K towards the set supply temperature is set at the factory.
Supply temperature control cascade control unit
Differential temperature: The differential temperature can be set at coding “9f” in the “General” group, factory set condition 8 K. The differential temperature is the value by which the common supply temperature should be higher than the highest currently required supply temperature of the heating circuit with mixing valve.
H System with only one heating circuit with mixing valve: The common set supply temperature is regulated automatically to 8 K above the set supply temperature of the heating circuit with mixing valve.
H System with heating circuit without mixing valve and
heating circuits with mixing valve: The common set supply temperature operates in accordance with its own heating curve. The differential temperature of 8 K towards the set supply temperature of the heating circuits with mixing valve is set at the factory.
5513 463 - 06
79
Page 80
Function Description
Heating Circuit Control Unit (continued)
Vitotronic 300, GW6B Installation and Service
Example using the settings in the factory set condition
Legend
A Heating curve for operation with standard room temperature B Heating curve for operation with reduced room temperature
Example using the settings in the factory set condition
Raising the reduced room temperature
During operation with reduced room temperature, the reduced set room temperature can be automatically raised subject to the outdoor temperature. The temperature is raised in accordance with the selected heating curve, but no higher than the set standard room temperature. The outdoor temperature limits for the start and end of temperature raising can be set in coding “f8” and “f9” in the “Heating circuit...” group.
Reducing the heat-up time
During the transition from operation with reduced room temperature to operation with standard room temperature, the boiler water or supply temperature will be raised in accordance with the selected heating curve. The boiler water or supply temperature increase can be automatically raised. The value and duration for the additional raising of the boiler water temperature or set supply temperature can be set in coding “fa” and “fb” in the “Heating circuit...” group.
Control sequence
Mixing valve circuit
The mixing valve motor will not be switched within the “neutral zone” (±1 K).
Supply temperature drops (Set value –1 K)
The mixing valve motor receives the signal “mixing valve open”. The signal duration lengthens with an increasing control differential. The duration of pauses reduces with an increasing control differential.
Legend
A Start of operation with standard room temperature B Set boiler water or supply temperature in accordance
with the selected heating curve C Set boiler water or supply temperature in accordance with coding “fa”: 122°F (50°C) + 20% = 146°F (60°C) D Duration of operation with higher boiler water or set supply temperature in accordance with coding “fb”: 60 min
80
Supply temperature rises (set value +1 K)
The mixing valve motor receives the signal “mixing valve close”. The signal duration lengthens with an increasing control differential. The duration of pauses reduces with an increasing control differential.
5513 463 - 06
Page 81
Vitotronic 300, GW6B Installation and Service
DHW Tank Temperature Control
Function Description
Brief description
H The tank temperature control is a constant temperature
control function. This is achieved by starting and stopping the DHW pump. The switching differential is ±2.5 K.
H When the DHW tank is heated, a set supply
temperature is specified that is 20 K higher than the set DHW temperature (adjustable at coding “60” in the “DHW” group).
Functions
Time program
An automatic or an individual time program may be selected for DHW pump and the DHW recirculation pump. Compared with the heating circuit heatup phase, DHW heating starts 30 min earlier in automatic mode. The individual time program enables up to 4 time phases per day to be set for DHW pump and the DHW recirculation pump for every day of the week. All tank heating sequences will be completed independently of the time program.
In conjunction with coding “7f” in the “General” group
H Detached house Coding “7f:1”: – Automatic mode The heating times for heating circuit 1 are applied to systems with two or three heating circuits. – Individual time program The time phases for DHW pump and the DHW recirculation pump have the same effect on all heating circuits.
H Apartment building Coding “7f:0”: – Automatic mode For systems with two or three heating circuits, the heating times for the respective heating circuit will be applied. – Individual time program The time phases for DHW pump and the DHW recirculation pump can be adjusted individually for each heating circuit.
Priority control
H With priority control: (coding “a2:2” in the “Heating circuit...” group): The set supply temperature will be adjusted to 32°F (0°C) during tank heating. The mixing valve closes and the heating circuit pump is switched off.
H Without priority control: The heating circuit control unit continues to operate with the same set value.
H With modulating priority control in conjunction with
heating circuits with mixing valve: The heating circuit pump remains switched on. During tank heating the set supply temperature of the heating circuit will be reduced until the set boiler water temperature has been reached. The set supply temperature is determined from the following coding: – Outdoor temperature – Differential between the set and the actual boiler water temperature – Heating curve slope and shift – Set coding “a2” in the “Heating circuit...” group
Frost protection
The DHW tank will be heated to 68°F (20°C) if the DHW temperature falls below 41°F (5°C).
Forth phase heating function (auxiliary function for DHW heating) This function is activated by providing a second set DHW temperature at coding “58” in the “DHW” group and activating the fourth DHW phase for DHW heating.
Set DHW temperature
The set DHW temperature can be adjusted between 50 and 140°F (10 and 60°C). Coding “56” in the “DHW” group enables the set range to be extended to 203°F (95°C). Coding “66” in the “DHW” group enables the set value of the programming unit and/or remote control Vitotrol 300 to be assigned.
DHW recirculation pump
This delivers hot water to the draw-off points at adjustable times. Four time phases can be selected at the control unit for every day.
5513 463 - 06
81
Page 82
Function Description
DHW Tank Temperature Control (continued)
Vitotronic 300, GW6B Installation and Service
Auxiliary circuits
DHW heating in conjunction with the heating circuits can be disabled or enabled by changing over the operating program (see coding “d5” in the “Heating circuit...” group).
System with tank loading system
The above functions also apply in conjunction with tank loading systems. Set the following coding: “55:3” in the “DHW” group; “4c:1”, “4e:2” in the “General” group. The DHW tank is only reheated by the boiler if the temperature falls below this value.
System with solar control unit
A third set DHW temperature can be assigned at coding “67” in the “DHW” group. The DHW tank is only reheated by the boiler if the temperature falls below this value.
Controlled sequence single boiler control
Coding “55:0” in the “DHW” group; tank heating
The DHW tank goes cold (set value –2.5 K, adjustable via coding “59”):
H The set boiler water temperature is set 20 K higher than the set DHW temperature (adjustable via coding “60”).
H Pump on: – Starting the DHW pump is subject to boiler water temperature (coding “61:0”). The DHW pump starts when the boiler water temperature is 7 K higher than the DHW temperature. – Starting the DHW pump for tank heating immediately (coding “61:1”). The DHW tank is hot (set value +2.5 K):
H The set boiler water temperature is reset to the
weather-compensated set value.
H Pump delay off: The DHW pump runs on after tank heating until one of the following criteria is met: – The differential between the boiler water temperature and the DHW temperature is less than 7 K. – The weather-compensated set boiler water temperature has been reached. – The set DHW temperature is exceeded by 5 K. – The set max. delay off time is reached (coding “62”).
H Without pump delay off (coding “62:0”).
Coding “55:1” in the “DHW” group; adaptive tank heating
With adaptive tank heating, the speed of the temperature rise during DHW heating is taken into account. The DHW tank goes cold (set value –2.5 K, adjustable via coding “59”):
H The set boiler water temperature is set 20 K higher
than the set DHW temperature (adjustable via coding “60”).
H Pump on: – Starting the DHW pump is subject to boiler water temperature (coding “61:0”): The DHW pump starts when the boiler water temperature is 7 K higher than the DHW temperature. – Starting the DHW pump immediately (coding “61:1”).
The DHW tank is hot:
H The control unit checks whether the boiler will still be required to supply heating energy after the tank has been heated up or whether residual boiler heat should be transferred to the DHW tank. Accordingly, the control unit determines the burner and DHW pump stop times to prevent the set DHW temperature being substantially exceeded after the tank has been heated up.
Coding “55:2” in the “DHW” group; tank temperature control with 2 tank temperature sensors
Tank temperature sensor 1 enables the DHW pump and is evaluated for stop conditions during the pump delay off time. Tank temperature sensor 2: Tank heating will start early if a lot of hot water is drawn off. Tank heating will terminate early if no hot water is drawn off.
DHW tank goes cold:
H Set value 2.5 K, change at coding “59” or
H Actual DHW temperature at sensor 2 < set DHW
temperature x factor for start time (adjustment at coding “69”)
The DHW tank is hot:
H set value +2.5 K and
H Actual DHW temperature at sensor 2 > set DHW
temperature x factor for stop time (adjustment at coding “68”)
82
5513 463 - 06
Page 83
Vitotronic 300, GW6B Installation and Service
DHW Tank Temperature Control (continued)
Function Description
Coding “55:3” in the “DHW” group; tank temperature control tank loading system
The DHW tank goes cold (set value 2.5 K; change at coding “59”):
H The set boiler water temperature is set 20 K higher than
the set DHW temperature (adjustable via coding “60”).
H The primary pump in the tank loading system starts.
H The 3-way mixing valve opens and then regulates to
the specified set value.
H The DHW pump cycles (briefly switches on and off)
until the set supply temperature has been reached (set
DHW temperature + 5 K). Then it runs constantly. If, during heating, the actual value falls below the required set temperature, the DHW pump will temporarily cycle again.
The DHW tank is hot:
H Tank temperature sensor 1: Actual value ≥ set value and Tank temperature sensor 2: Actual value > set value –1.5 K:
H The set boiler water temperature is reset to the
weather-compensated set value.
H The DHW pump stops immediately when the 3-way
mixing valve is fully opened.
or
H The DHW pump stops after expiry of the delay off time
that is selected at coding “62”.
Controlled sequence cascade control
The following coding in the “DHW” group influence the controlled sequence.
Tank heating (coding “55:0”)
The DHW tank goes cold (set value –2.5 K, adjustable via coding “59”):
H The common set supply temperature is set 20 K higher
than the set DHW temperature (adjustable via coding “60”).
The DHW tank is hot (set value +2.5 K):
H The common set supply temperature is returned to
the set weather-compensated value.
H With pump delay off: The DHW pump runs on after tank heating until one of the following criteria is met: – The set DHW temperature is exceeded by 5 K. – The set max. delay off time is reached (coding “62”).
H Without pump delay off (coding “62:0”).
Adaptive storage tank heating enabled (coding “55:1”)
With adaptive tank heating, the speed of the temperature rise during DHW heating is taken into account. The DHW tank goes cold (set value –2.5 K, adjustable via coding “59”):
H The common set supply temperature is set 20 K higher
than the set DHW temperature (adjustable via coding “60”).
The DHW tank is hot:
H The control unit checks whether the boiler will still be
required to supply heating energy after the tank has been heated up or whether residual boiler heat should be transferred to the DHW tank. Accordingly, the control unit determines the burner and circulation pump stop times to prevent the set DHW temperature being substantially exceeded after the tank has been heated up.
5513 463 - 06
83
Page 84
Function Description
DHW Tank Temperature Control (continued)
Vitotronic 300, GW6B Installation and Service
Storage tank temperature control with 2 temperature sensors (coding “55:2”)
Tank temperature sensor 1 enables the DHW pump for tank heating and is evaluated for stop conditions during the pump delay off time. Tank temperature sensor 2: Tank heating will start early if a lot of hot water is drawn off. Tank heating will terminate early if no hot water is drawn off.
DHW tank goes cold:
H Set value –2.5 K, adjustable via coding “59”
or
H Actual DHW temperature at sensor 2 < set DHW
temperature x factor for start time (adjustment at coding “69”)
The DHW tank is hot:
H Set value +2.5 K
and
H Actual DHW temperature at sensor 2 > set DHW
temperature x factor for stop time (adjustment at coding “68”)
Coding “55:3” in the “DHW” group; tank temperature control tank loading system The DHW tank goes cold (set value –2.5 K, adjustable via coding “59”):
H The common set supply temperature is set 20 K higher
than the set DHW temperature (adjustable via coding
“60”).
H The primary pump in the tank loading system starts.
H The 3-way mixing valve opens and then regulates to
the specified set value.
H The DHW pump cycles (briefly switches on and off)
until the set supply temperature has been reached (set
DHW temperature + 5 K). Then it runs constantly. If, during heating, the actual value falls below the required set temperature, the circulation pump for tank heating will temporarily cycle again.
The DHW tank is hot:
H Tank temperature sensor 1: Actual value ≥ set value and Tank temperature sensor 2: Actual value > set value -1.5 K:
H The common set supply temperature is returned to the
set weather-compensated value.
H The DHW pump stops immediately when the 3-way
mixing valve is fully opened. or The DHW pump stops after expiry of the delay off time that is selected at coding “62”.
84
5513 463 - 06
Page 85
Vitotronic 300, GW6B Installation and Service
Calling up Coding Levels
Display for coding levels
Legend
A Coding B Number of coding C Value of coding D Coding description
Coding levels
H Coding are split into the following groups: – “General” – “Combustion controller” – “DHW” – “Solar” – “Heating circuit 1/2/3” – “Boiler” – “Cascade” – “All coding” In this group, all coding in the coding levels are listed in ascending order (except the coding in the “Solar” group).
H Heating systems with one heating circuit without
mixing valve and one or two heating circuits with
mixing valve: In the following, the heating circuit without mixing valve is designated “Heating circuit 1” and the heating circuits with mixing valve as “Heating circuit 2” or “Heating circuit 3”.
H The selected designation appears if the heating circuits
have been designated individually.
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “System configuration”
5. “Coding level 1” or “Coding level 2”: Enter “viexpert” password.
6. Select group.
7. Select coding.
8. “Change”
9.
for the required value in line with the following
tables.
Resetting Coding to their Factory Set Condition
5513 463 - 06
From the home screen tap the following buttons:
1. “Menu”
2. “Service”
3. Enter “viservice” password.
4. “System configuration”
5. “Coding level 1” or “Coding level 2”: Enter “viexpert” password.
6. “Reset coding”
85
Page 86
Coding level 1
“General” Group
Coding Coding in the factory set condition Possible change System design
00:1 System version 1:
One heating circuit without mixing valve A1 (heating circuit 1), without DHW heating
00:2 to 00:10
Vitotronic 300, GW6B Installation and Service
For system schemes, see the following table:
Value address 00: ...
2 One heating circuit without mixing valve A1 (heating circuit 1), with DHW heating;
3 One heating circuit with mixing valve M2 (heating circuit 2), without DHW heating. 4 One heating circuit with mixing valve (heating circuit 2), with DHW heating 5 One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit with mixing valve
6 One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit with mixing valve
7 Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3),
8 Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3), with DHW
9 One heating circuit without mixing valve A1 (heating circuit 1), two heating circuits with mixing
10 One heating circuit without mixing valve A1 (heating circuit 1), two heating circuits with mixing
Coding in the factory set condition Possible change Servomotor runtime
40:...
“Boiler circuit pump”
53:1 With low loss header:
LON participant no.
77:1 LON participant number. 77:1
“Detached house/apartment building”
7f:1 Detached house 7F:0 Apartment building
Description
recognized automatically.
M2 (heating circuit 2), without DHW heating; recognized automatically.
M2 (heating circuit 2), with DHW heating; recognized automatically.
without DHW heating.
heating.
valve M2 (heating circuit 2) and M3 (heating circuit 3), without DHW heating; recognized automatically.
valve M2 (heating circuit 2) and M3 (heating circuit 3), with DHW heating; recognized automatically.
Actuator runtime at plug gSA1.
Boiler circuit pump only runs on demand if the burner is operational (with delay off time)
40:5 to 40:199
53:0 Boiler circuit pump runs permanently -
to 77:99
Adjustable from 5 to 199 sec.
subject to warm weather shutdown
Adjustable from 1 to 99: 1 - 8 = Boiler/heating circuit control unit 9 = Cascade control unit 10 - 97 = Vitotronic 200-H 98 = Vitogate 99 = Vitocom
Separate adjustment of holiday program and time program for DHW heating possible.
86
5513 463 - 06
Page 87
Vitotronic 300, GW6B Installation and Service
Coding level 1
“General” Group (continued)
Coding in the factory set condition Possible change
“Automatic summer/wintertime changeover”
81:1 Automatic summer/wintertime changeover. 81:0 Manual summer/wintertime changeover
81:2 Do not adjust!
81:3 With LON communication module:
The control unit receives the time.
“Summer time starts: Month”
82:3 March 82:1
to 82:12
“Summer time starts: Week of the selected month”
83:2 Week 2 of the selected month 83:1
to 83:5
83:6 83:6 Last week – 1 week
83:7 83:7 Last week – 2 weeks
83:8 83:8 Last week – 3 weeks
83:9 83:9 Last week – 4 weeks
83:10 to 83:14
“Summer time starts: Day of the selected week”
84:7 Last Sunday of the selected month 84:1
to 84:7
“Wintertime starts: Month”
85:11 November 85:1
to 85:12
“Wintertime starts: Week of the selected month”
86:1 Week 1 of the selected month 86:1
to 86:5
“Wintertime starts: Day of the selected week”
87:7 Last Sunday of the selected month 87:1
to 87:7
“Operation enabled/blocked”
8f:0 Do not adjust! -- --
“Set supply temperature for external demand”
9b:70 Set to 158°F (70°C) 9b:0
to 9b:127
January to December
Week 1 to week 5 of the selected month
Special function
Monday to Sunday.
January to December
Week 1 to week 5 of the selected month
Monday to Sunday
Adjustable from 32 to 261°F (0 to 127°C) (limited by boiler specific coding)
5513 463 - 06
87
Page 88
Coding level 1
Vitotronic 300, GW6B Installation and Service
“Combustion Controller” Group
Coding in the factory set condition Possible change
“Max operational output”
02:100 100% of rated heating output 02:0
to 02:100
“Gas type”
03:0 Natural gas 03:1 LPG
“Altitude”
04:0 LA: 1500 m 04:1 HA: > 1500 m
“Max boiler temperature”
06:95 Set to 203°F (95°C) 06:5
to 06:127
“Integral threshold value of controller”
08:30 Set to 30 Kmin 08:1
to 08:255
“Runtime optimization”
09:1 Integral method 09:0 Minimum pause
Adjustable from 0 to 100% (0% represents burner minimum firing rate)
Adjustable from 41 to 261°F (5 to 127°C)
Adjustable from 1 to 255 Kmin
“Boiler” Group
Coding in the factory set condition Possible change
“Single boiler and multi boiler system”
01:2 Multi-boiler system with Viessmann-cascade
or LON-cascade
“Consecutive boiler number in multi boiler systems”
07:1 Consecutive boiler number in multi boiler
systems
“Flue gas temperature sensor”
1f:0 Do not adjust! -- --
“Service interval”
21:0 No service interval (hours run) selected. 21:1
“Interval for service”
23:0 No interval for service 23:1
”Service” display”
24:0 No “Service” display 24:1 “Service” is displayed (the address is
01:1 Single boiler system
01:3 Do not adjust!
07:2 to 07:8
to 21:100
to 23:24
Adjustable from 1 to 8
The number of hours run before the burner should be serviced is adjustable from 100 to 10000 h; 1 step
Adjustable from 1 to 24 months.
automatically set and must be manually reset after a service has been carried out).
100 h
88
5513 463 - 06
Page 89
Vitotronic 300, GW6B Installation and Service
Coding level 1
“Cascade” Group
Coding in the factory set condition Possible change
“Number of boilers connected to the cascade”
35:8 8 boilers 35:1
to 35:8
“Minimum system supply temperature limit”
36:0 Electronic minimum system supply
temperature limit set to 32°F (0°C).
“Maximum system supply temperature limit”
37:80 Electronic maximum system supply
temperature limit set to 176°F (80°C).
“Lead boiler or boiler sequence changeover”
38:0 No lead boiler or boiler sequence
changeover (see function description in chapter “Cascade control”)
“Permanent lead boiler”
39:0 No permanent lead boiler 39:1
“Permanent last boiler”
3a:0 No permanent last boiler 3a:1
“Type of control”
3b:1 Standalone parallel boiler circuit:
With supply temperature sensor (see page 71)
“Control strategy”
3c:0 Condensing strategy (see page 74) 3c:1 Conventional boiler strategy 1 (see page 75)
“Output statement”
3d:1 Output statement for condensing strategy
and conventional boiler strategy 1
36:1 to 36:127
37:20 to 37:127
38:1 Lead boiler changeover:
38:2 to 38:200
to 39:8
to 3a:8
3b:0 Standalone parallel boiler circuit:
3b:2 Standalone serial boiler circuit:
3b:3 Standalone serial boiler circuit:
3b:4 Sequential control method with supply
3c:2 Conventional boiler strategy 2 (see page 76)
3d:0 No output statement
1 to 8 boilers
Adjustable from 32 to 261°F (0 to 127°C) (only when operating with standard room temperature)
Adjustable from 68 to 261°F (20 to 127°C) Note: Value must be lower than the lowest value of coding “06” in the “Combustion controller” group of every control unit.
Every first day of the month, the boiler with the shortest number of hours run by its burner becomes the lead boiler.
Lead boiler changeover after 200 to 20,000 hours run 1 step
Permanent lead boiler is boiler 1, 2, 3 or 8
Permanent last boiler is boiler 1, 2, 3 or 8
With supply temperature sensor (see page 73)
Without supply temperature sensor (see page 73)
With supply temperature sensor (see page 73)
temperature sensor (see page 73)
Note: Control only in accordance with conventional boiler strategy 2
100 hours run
5513 463 - 06
89
Page 90
Coding level 1
“Cascade” Group (continued)
Coding in the factory set condition Possible change
“ECO threshold boiler 1”
41:31 No ECO threshold boiler 1 41:30
to 41:+30
“ECO threshold boiler 2”
42:31 No ECO threshold boiler 2 42:30
to 42:+30
“ECO threshold boiler 3”
43:31 No ECO threshold boiler 3 43:30
to 43:+30
“ECO threshold boiler 4”
44:31 No ECO threshold boiler 4 44:30
to 44:+30
“Start integral threshold”
45:60 Set to 60 K x minute 45:1
to 45:255
“Stop integral threshold”
46:40 Set to 40 K x minute 46:1
to 46:255
“Stop differential”
47:15 Set to 15 K 47:2
to 47:30
“ECO threshold boiler 5”
65:31 No ECO threshold boiler 5 65:30
to 65:+30
“ECO threshold boiler 6”
6F:31 No ECO threshold boiler 6 6F:30
to 6F:+30
“ECO threshold boiler 7”
74:31 No ECO threshold boiler 7 74:30
to 74:+30
“ECO threshold boiler 8”
7d:31 No ECO threshold boiler 8 7d:30
to 7d:+30
Vitotronic 300, GW6B Installation and Service
Adjustable from -22 to 86°F (30 to +30°C)
Adjustable from -22 to 86°F (30 to +30°C)
Adjustable from -22 to 86°F (30 to +30°C)
Adjustable from -22 to 86°F (30 to +30°C)
Adjustable from 1 to 255 K x minute Note: A boiler or burner stage will shut down if this value is exceeded.
Adjustable from 1 to 255 K x minute Note: A boiler or burner stage will shut down if this value is exceeded.
Adjustable from 2 to 30 K Note: One boiler or one burner stage will be shut down if the actual supply temperature exceeds the set supply temperature by this value.
Adjustable from -22 to 86°F (30 to +30°C)
Adjustable from -22 to 86°F (30 to +30°C)
Adjustable from -22 to 86°F (30 to +30°C)
Adjustable from -22 to 86°F (30 to +30°C)
90
5513 463 - 06
Page 91
Vitotronic 300, GW6B Installation and Service
Coding level 1
“DHW” Group
Coding in the factory set condition Possible change
“Storage tank heating, hysteresis”
55:0 Tank heating hysteresis ± 2.5 K 55:1 Adaptive storage tank heating enabled
(see page 82)
55:2 Storage tank temperature control with 2
temperature sensors (see page 82).
55:3 Storage tank temperature control, storage tank
loading system (see page 83)
“For solar DHW heating: DHW temperature target”
67:40 DHW setpoint temperature 104°F (40°C).
Reheating is suppressed above the selected set temperature (DHW heating blocked by the boiler).
“DHW recirculation pump”
73:0 ON according to time program 73:1
67:0 to 67:95
to 73:6 73:7 Permanently ON
Adjustable from 32 to 203°F (0 to 95°C) (limited by boiler-specific coding)
“ON” from once per hour for 5 min up to 6 times per hour for 5 min during the time program.
“Solar” Group
Note: The “Solar” group is only displayed if a solar control module, type SM1, is connected.
Coding in the factory set condition Possible change “Solar circuit pump speed control”
02:0 Solar circuit pump is not speed controlled 02:1 Variable speed solar circuit pump with wave
packet control
02:2 Solar circuit pump speed controlled with PWM
control
“Maximum storage tank temperature”
08:60 DHW setpoint temperature (maximum tank
temperature) 140°F (60°C)
“Stagnation time reduction”
0a:5 Temperature differential for stagnation time
reduction (reduction in the speed of the solar circuit pump to protect system components and heat transfer medium) 5 K.
“Solar circuit flow rate”
0f:70 Solar circuit flow rate at maximum pump
speed 1.8 USG/min (7 L/min)
“Extended control function”
20:0 No extended control function enabled 20:1 Additional function for DHW heating
08:10 to 08:90
0a:0 Stagnation time reduction disabled
0a:1 to 0a:40
0f:1 to 0f:255
20:2 Differential temperature control 2 20:3 Differential temperature control 2 and auxiliary
20:4 Differential temperature control 2 for central
20:5 Thermostat function 20:6 Thermostat function and auxiliary function 20:7 Solar heating via external heat exchanger
20:8 Solar heating via external heat exchanger with
20:9 Solar heating of two DHW storage tanks
Adjustable from 50 to 194°F (10 to 90°C)
Temperature differential adjustable from 1 to 40 K
Adjustable from 0.02 to 6.7 USG/min (0.1 to 25.5 L/min), 1 step
function
heating backup
without additional temperature sensor
additional temperature sensor
[Solar heating of two DHW tanks]
0.02 USG/min (0.1 L/min).
5513 463 - 06
91
Page 92
Coding level 1
“Heating Circuit ...” Group
Coding in the factory set condition Possible change “Storage tank priority”
a2:2 Tank priority control for heating circuit
pump and mixing valve
“Heating circuit pump logic function (economy control)”
a5:5 With heating circuit pump logic function
(economy control): heating circuit pump OFF when the outdoor temperature (OT) is 1 K higher than the set room temperature (RTset) OT > RTset +1 K
a2:0 Without storage tank priority applicable
a2:1 Storage tank priority only applicable to
a2:3 to a2:15
a5:0 Without heating circuit pump logic
a5:1 to a5:15
Vitotronic 300, GW6B Installation and Service
to heating circuit pump and mixing valve
mixing valve Modulating priority applies to mixing
valves, i.e. the heating circuit receives a reduced amount of heat.
function With heating circuit pump logic function:
Heating circuit pump OFF, see the following table
Coding address a5:...
With heating circuit pump logic function: Heating circ pump OFF
1 OT > RTset + 5 K 2 OT > RTset + 4 K 3 OT > RTset + 3 K 4 OT > RTset + 2 K 5 OT > RTset + 1 K 6 OT > RTset 7
OT > RTset – 1 K to 15
OT > RTset – 9 K
Coding in the factory set condition Possible change “Extended economy mode”
a6:36 Extended economy mode disabled a6:5
to a6:35
“Mixing valve economy function”
a7:0 Only for heating circuits with mixing
a7:1 With mixing valve economy function: valve: Without mixing valve economy function
Extended economy mode enabled, i.e. the burner and heating circuit pump will stop and the mixing valve will be closed at a variable value, adjustable between 41 to 95°F (5 and 35°C) plus 2°F (1°C). The base value is the adjusted outdoor temperature. This value is based on the actual outdoor temperature and a time constant, which takes the cooling down of an average building into consideration.
Heating circuit pump also OFF:
H Mixing valve tries closing for more than
20 min
Heating circuit pump ON:
H Mixing valve in control mode
H If there is a risk of frost
92
5513 463 - 06
Page 93
Vitotronic 300, GW6B Installation and Service
Coding level 1
“Heating Circuit ...” Group (continued)
Coding in the factory set condition Possible change “Pump idle time”
a9:0 Without pump idle time a9:7 With pump idle time (heating circuit
pump OFF) Function description page 78 Note: The maximum idle time is 10 h.
a9:1 to a9:15
“Room temperature hook-up”
b0:0 With remote control:*1
Heating mode/reduced mode: Weather-compensated
“Room temperature-dependent heating circuit pump logic function”
b5:0 With remote control:*1
No room temperature-dependent heating circuit pump logic function
b0:1 Heating mode: Weather-compensated
b0:2 Heating mode: with room
b0:3 Heating mode/reduced mode:
b5:1 to b5:8
Pump idle time adjustable from 1 to 15. 1: Short idle time 15: Long idle time
Reduced mode: with room temperature hook-up
temperature hook-up Reduced mode: Weather-compensated
with room temperature hook-up
For heating circuit pump logic function, see the following table:
Coding address a5:...
1 RTactual > RTset + 5 K RTactual > RTset + 4 K 2 RTactual > RTset + 4 K RTactual > RTset + 3 K 3 RTactual > RTset + 3 K RTactual > RTset + 2 K 4 RTactual > RTset + 2 K RTactual > RTset + 1 K 5 RTactual > RTset + 1 K RTactual > RTset 6 RTactual > RTset RTactual > RTset – 1 K 7 RTactual > RTset – 1 K RTactual > RTset – 2 K 8 RTactual > RTset – 2 K RTactual > RTset – 3 K
Coding in the factory set condition Possible change “Minimum supply temperature limit”
c5:20 Electronic supply temperature minimum
“Maximum supply temperature limit”
c6:75 Electronic maximum supply temperature
*1 Only change the coding for the heating circuit without mixing valve A1 for boilers without lower temperature limit or for heating circuits with mixing valve if a remote control is connected to them.
With heating circuit pump logic function: Heating circ pump OFF
limit 68°F (20°C) (only for operation with standard room temperature)
limit set to 167°F (75°C)
c5:1 to c5:127
c6:10 to c6:127
Adjustable from 34 to 261°F (1 to 127°C) (limited by boiler specific coding)
Adjustable from 50 to 261°F (10 to 127°C) (limited by boiler specific coding)
5513 463 - 06
93
Page 94
Coding level 1
Vitotronic 300, GW6B Installation and Service
“Heating Circuit ...” Group (continued)
Coding in the factory set condition Possible change
“External operating program changeover”
d5:0 With external operating program changeover
(observe setting of coding “5d”, “5e”, “5f” and “91” in the “General” group). Changeover “Constant central heating with reduced room temperature” or “Standby mode” (subject to set reduced room temperature)
“EA1 extension: Operating program changeover”
d8:0 No operating program changeover d8:1 Operating program changeover via input DE1
“Time limit for comfort mode”
f2:8 Time limit for comfort mode or external
operating program changeover via push button: 8 h*2 Note: Observe setting of coding “5d”, “5e”, “5f” in the “General” group, as well as “d5” and “d8” in the “Heating circuit...” group.
“Temperature limit for terminating reduced mode”
f8:–5 Temperature limit for terminating reduced
mode 25°F (–5°C), see example on page 80. Observe coding “a3”.
d5:1 Changeover to “Constant operation with
standard room temperature”
d8:2 Operating program changeover via input DE2
d8:3 Operating program changeover via input DE3
f2:0 No time limit*2
f2:1 to f2:12
f8:+10 to f8:–60
f8:–61 Function disabled
Time limit adjustable from 1 to 12 h*2.
Adjustable from 50 to -76°F (+10 to –60°C)
“Temperature limit for raising the reduced room temperature target”
f9:–14 Temperature limit for raising the reduced
room temperature target 7°F (–14°C), see example on page 80.
“Raising the set boiler water or supply temperature when changing from operation with reduced room temperature to operation with standard room temperature”
fa:20 Raising the set boiler water or supply
temperature when changing from operation with reduced room temperature to operation with standard room temperature by 20%. See example on page 80.
“Duration for raising the set boiler water or supply temperature”
fb:60 Duration for raising the set supply
temperature (see coding “fa”) 60 min. See example on page 80.
*2 In the “Heating and DHW” operating program, comfort mode ends automatically when the system changes over to operation with standard room temperature.
f9:+10 to f9:–60
fa:0 to fa:50
fb:0 to fb:300
Adjustable from 50 to -76°F (+10 to –60°C)
Adjustable from 0 to 50%
Adjustable from 0 to 300 min
94
5513 463 - 06
Page 95
Vitotronic 300, GW6B Installation and Service
“General” Group
Coding in the factory set condition Possible change System design
00:1 System version 1:
One heating circuit without mixing valve A1 (heating circuit 1), without DHW heating
00:2 to 00:10
Coding level 2
For system schemes, see the following table:
Value address 00: ...
2 One heating circuit without mixing valve A1 (heating circuit 1), with DHW heating;
3 One heating circuit with mixing valve M2 (heating circuit 2), without DHW heating. 4 One heating circuit with mixing valve (heating circuit 2), with DHW heating. 5 One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit with mixing valve
6 One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit with mixing valve
7 Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3),
8 Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3), with DHW
9 One heating circuit without mixing valve A1 (heating circuit 1), two heating circuits with mixing
10 One heating circuit without mixing valve A1 (heating circuit 1), two heating circuits with mixing
Coding in the factory set condition Possible change “With EA1 extension: DHW recirculation pump runtime for brief operation”
12:5 DHW recirculation pump runtime for
“With EA1 extension: Temperature demand”
1e:0 Analogue input 0-10 V:
“Reset time hydraulic switch/buffer
20:... Controller integral time for low loss
“Controller delay hydraulic switch/buffer
22:... Controller delay low loss header in
Description
recognized automatically.
M2 (heating circuit 2), without DHW heating; recognized automatically.
M2 (heating circuit 2), with DHW heating; recognized automatically.
without DHW heating.
heating.
valve M2 (heating circuit 2) and M3 (heating circuit 3), without DHW heating; recognized automatically.
valve M2 (heating circuit 2) and M3 (heating circuit 3), with DHW heating; recognized automatically.
brief operation: 5 min
Temperature demand from 32 to 212°F (0 to 100°C): 1 V
50°F (10°C)
10 V 212°F (100°C)
header in sec, factory set condition defaulted by the boiler coding card. The greater the integral action time, the more accurate but slower the controller.
minutes, time between burner start and controller start.
12:1 to 12:60
1E:1 Adjustable from 86 to 248°F
20:1 to 20:199
20:1 to 20:199
Adjustable from 1 to 60 min
(30 to 120°C):
86°F (30°C)
1 V 10 V 248°F (120°C)
Adjustable from 10 to 1990 sec, 1 step
Adjustable from 1 to 199 min
10 sec
2f:0 Do not adjust! -- --
“AM1 extension”
32:0 Without AM1 extension 32:1 With AM1 extension
“Function output A2 at AM1 extension”
33:1 Heating circuit pump, heating circuit
without mixing valve A1 (heating circuit 1)
5513 463 - 06
33:0 DHW recirculation pump 33:2 DHW loading pump
95
Page 96
Coding level 2
Vitotronic 300, GW6B Installation and Service
General” Group (continued)
Coding in the factory set condition Possible change “Function output A1 at AM1 extension”
34:1 Heating circuit pump, heating circuit
without mixing valve A1 (heating circuit 1)
“Servomotor runtime”
40:125
“Sensor 17A”
4a:0 Do not adjust! -- --
“Sensor 17B”
4b:0
“Connection at plug 20A1”
4c:0
“Connection at plug 29”
4d:1
“Connection at plug 52A1”
4e:1 Motor for 3-way mixing valve for return
“Delay off time, shunt or distribution pump”
4f:5 Delay off time distribution pump 5 min 4f:0 No pump delay off
“Supply temperature sensor for low loss header”
52:0 Without supply temperature sensor 52:1 With supply temperature sensor;
“Boiler circuit pump”
53:1 With low loss header:
“Solar thermal system”
54:0 Without solar thermal system 54:1 With Vitosolic 100; automatic recognition.
“EA1 extension”
5b:0 Without EA1 extension 5b:1 With EA1 extension; automatic recognition.
Servomotor runtime at plug gSA1 125 sec
No sensor aJB installed
Connection on plug A1: Heating circuit pump
Connection at plug sL: Shunt pump
temperature control
Boiler pump only runs on demand if the burner is operational (with delay off time)
34:0 DHW recirculation pump 34:2 DHW pump
40:5 to 40:199
4b:1
4c:1 Primary pump, primary store system
4d:0 Distribution pump 4d:2 Boiler pump 4d:3 Boiler pump with isolation valve function
4e:0 Motorized isolation valve
4e:2 Motor for 3-way mixing valve, primary store
4e:3 Mixing valve motor for heating circuit without
4f:1 to 4f:60
53:0 Boiler pump runs permanently - subject to
54:2 Vitosolic 200; automatic recognition. 54:3 With solar control module SM1, without
54:4 With solar control module, type SM1, with
Adjustable from 5 to 199 sec.
Sensor aJB installed (e.g. temperature sensor T2); automatic recognition.
Note: Factory set condition for lag boilers
system
mixing valve A1 (heating circuit 1)
Adjustable from 1 to 60 min
automatic recognition.
warm weather shutdown.
auxiliary function; automatic recognition.
auxiliary function, e.g. central heating backup; automatic recognition.
96
5513 463 - 06
Page 97
Vitotronic 300, GW6B Installation and Service
“General” Group (continued)
Coding in the factory set condition Possible change
“Function output 157 at EA1 extension”
5c:0
“Function input DE1 at EA1 extension”
5d:0 No function 5d:1 Operating program changeover
“Function input DE2 at EA1 extension”
5e:0 5e:1 Operating program changeover
“Function input DE3 at EA1 extension”
5f:0 No function 5f:1 Operating program changeover
Function output aBJ at EA1 extension: Central fault message
5c:1 Feed pump
5c:2 No function
5c:3 Heating circuit pump, heating circuit without
mixing valve A1 (heating circuit 1), switched to low speed (reduced mode).
5c:4 Heating circuit pump, heating circuit with
mixing valve M2 (heating circuit 2), switched to low speed (reduced mode).
5c:5 Heating circuit pump, heating circuit with
mixing valve M3 (heating circuit 3), switched to low speed (reduced mode).
5d:2 External demand with minimum set supply
temperature. Set value adjustment at coding “9b” in the “General” group.
5d:3 External blocking
5d:4 External blocking with fault message
5d:5 Fault message input.
5d:6 Brief operation, DHW recirculation pump (push
button function) Set DHW recirculation pump runtime at coding “12” in the “General” group.
5e:2 External demand with minimum set supply
temperature Set value adjustment at coding “9b” in the “General” group
5e:3 External blocking
5e:4 External blocking with fault message
5e:5 Fault message input
5e:6 Brief operation, DHW recirculation pump (push
button function) Set DHW recirculation pump runtime at coding “12” in the “General” group.
5f:2 External demand with minimum set supply
temperature Set value adjustment at coding “9b” in the “General” group.
5f:3 External blocking
5f:4 External blocking with fault message
5f:5 Fault message input
5f:6 Brief operation, DHW recirculation pump (push
button function) Set DHW recirculation pump runtime at coding “12” in the “General” group.
Coding level 2
5513 463 - 06
97
Page 98
Coding level 2
Vitotronic 300, GW6B Installation and Service
General” Group (continued)
Coding in the factory set condition Possible change “Delay off time for circulation pump, neutralizing system at output 1 at extension AM1”
6c:0 Delay off time circulation pump
neutralizing system: None
Delay off time for circulation pump, neutralising system at output 2 at extension AM1”
6d:0 Delay off time circulation pump
neutralizing system: None
“Display correction for outdoor temperature”
6e:50 No display correction for outdoor
temperature
“LON communication module”
76:1 With LON communication module;
automatic recognition. If no LON communication module is installed, set coding “76:0”.
“LON participant number”
77:1 LON participant number 77:2
“LON communication”
78:1 LON communication enabled 78:0 LON communication disabled
“With LON communication module”
79:1 Control unit is fault manager 79:0 Control unit is not fault manager
“Central control of heating circuits”
7a:0 Without central control of heating circuits 7a:1 With central control Heating circuit without
“LON communication module: Time”
7b:1 Control unit transmits the time. 7b:0 No time transmission
“Detached house/apartment building”
7f:1 Detached house 7F:0 Apartment building
“Fault message”
80:6 A fault message is issued if a fault
occurs for at least 30 sec.
6c:1 to 6c:255
6d:1 to 6d:255
6e:0 to 6e:49
6e:51 to 6e:99
76:0 Without LON communication module
to 77:99
7a:2 Heating circuit with mixing valve M2
7a:3 Heating circuit with mixing valve M3
80:0 Immediate fault message. 80:2
to 80:199
Adjustable from 1 to 255 sec
Adjustable from 1 to 255 sec
Display correction –5 K to Display correction –0.1 K
Display correction +0.1 K to Display correction +4.9 K
LON participant number, adjustable from 1 to 99: 1 - 8 = Boiler and heating circuit control unit 9 = Cascade control unit 10 - 97 = Vitotronic 200-H 98 = Vitogate 99 = Vitocom
mixing valve A1 (heating circuit 1)
(heating circuit 2)
(heating circuit 3)
Separate adjustment of holiday program and time program for DHW heating possible.
Adjustable from 10 to 995 sec, 1 step
5 sec.
98
5513 463 - 06
Page 99
Vitotronic 300, GW6B Installation and Service
Coding level 2
“General” Group (continued)
Coding in the factory set condition Possible change “Automatic summer/wintertime changeover”
81:1 Automatic summer/wintertime
changeover
“Summer time starts: Month”
82:3 March 82:1
“Summer time starts: Week of the selected month”
83:2 Week 2 of the selected month 83:1
“Summer time starts: Day of the selected week”
84:7 Last Sunday of the selected month 84:1
“Wintertime starts: Month”
85:11 November 85:1
“Wintertime starts: Week of the selected month”
86:1 Week 1 of the selected month 86:1
“Wintertime starts: Day of the selected week”
87:7 Last Sunday of the selected month 87:1
“Temperature displayed”
88:0 Temperature unit °C (Celsius) 88:1 Temperature unit °F (Fahrenheit)
“Test display conditions”
8a:175 Do not adjust! -- --
“Identification KM bus combustion controller”
8b:1 ID exists 8b:0 ID does not exist
“Operation enabled/blocked”
8f:0 Do not adjust! -- --
“Time constant for calculating adjusted outdoor temperature”
90:128 Time constant 21.3 h 90:1
81:0 Manual summer/wintertime changeover 81:2 Do not adjust! 81:3 With LON communication module:
The control unit receives the time.
January to December to 82:12
Week 1 to week 5 of the to 83:5
83:6 Last week – 1 week 83:7 Last week – 2 week 83:8 Last week – 3 week 83:9 Last week – 4 week 83:10
to 83:14
to 84:7
to 85:12
to 86:5
to 87:7
to 90:199
selected month.
Special function
Monday to Sunday
January to December
Week 1 to week 5 of the selected month
Monday to Sunday
Fast (low values) or slow (high values)
matching of the supply temperature,
subject to the set value when the outdoor
temperature changes 1 step
10 min
5513 463 - 06
99
Page 100
Coding level 2
Vitotronic 300, GW6B Installation and Service
General” Group (continued)
Coding in the factory set condition Possible change
“Connection at terminals 1 and 2 in plug 143”
91:0 Connection disabled (external operating
program changeover)
“Central fault message during emissions test function/service display”
93:0 Does not affect central fault 93:1 Affects central fault message
“Communication interface”
95:0 Without Vitocom 100 communication
interface
“Extension for heating circuits 2 and 3 with mixing valve”
96:0 Without extension PCB for heating
circuits 2 and 3
“With LON communication module: Outdoor temperature”
97:2 The control unit sends the outdoor
temperature to the Vitotronic 200-H.
“Viessmann system number”
98:1 Viessmann system number in
conjunction with monitoring of several systems within one LON system with Vitocom 300
91:1 Contact affects the following heating
circuits: Heating circuit without mixing valve A1 (heating circuit 1)
91:2 Heating circuit with mixing valve M2
(heating circuit 2)
91:3 Heating circuit without mixing valve A1
(heating circuit 1) and heating circuit with mixing valve M2 (heating circuit 2)
91:4 Heating circuit with mixing valve M3
(heating circuit 3)
91:5 Heating circuit without mixing valve A1
(heating circuit 1) and heating circuit with mixing valve M3 (heating circuit 3)
91:6 Heating circuit with mixing valve M2
(heating circuit 2) and M3 (heating circuit 3)
91:7 Heating circuit without mixing valve A1
(heating circuit 1) and heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3)
95:1 With Vitocom 100 communication
interface; automatic recognition.
96:1 With extension PCB for heating circuits
2 and 3; automatic recognition
97:0 The outdoor temperature of the sensor
connected to the control unit is only utilized internally.
97:1 The control unit receives the outdoor
temperature from the Vitotronic 200-H.
98:1 to 98:5
Adjustable from 1 to 5
100
5513 463 - 06
Loading...