Viessmann Vitotronic 300, GW2 Installation And Service Instructions Manual

Page 1
Installation and Service Instructions
for use by heating contractor
Vitotronic 300, Model GW2
Outdoor-reset logic digital boiler and heating circuit control unit
Please file in Service Binder
VITOTRONIC 300
Certified as a component part of Viessmann boilers only
5285 941 v1.6 12/2012
IMPORTANT
Read and save these instructions for future reference.
1
Page 2
General information
Safety, Installation and Warranty Requirements
Please ensure that this manual is read and understood before commencing installation. Failure to comply with the issues
listed below and details printed in this manual can cause product/property damage, and/or severe personal injury. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
Licensed professional heating contractor
The installation, adjustment, service, and maintenance of this equipment must be performed by a licensed professional heating contractor.
Please see section entitled “Important Regulatory and Installation Requirements.”
Product documentation
Read all applicable documentation
before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.
For a listing of applicable literature, please see section entitled “Important Regulatory and Installation Requirements.”
Advice to owner
Once the installation work is complete, the heating contractor must familiarize the system operator/ultimate owner with all equipment, as well as safety precautions/requirements, shut-down procedure, and the need for professional service annually before the heating season begins.
Warranty
Information contained in this and related product documentation must be read and followed. Failure
to do so renders warranty null and void.
Safety Terminology
The following terms are used throughout this manual to bring attention to the presence of potential hazards or important product information. Please heed the advice given!
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial product / property damage.
2
WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in substantial product/property damage, serious injury or loss of life.
WARNING
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product / property damage.
IMPORTANT
Helpful hints for installation, operation or maintenance which pertain to the product.
5285 941 v.1.6
Page 3
Product Information
Vitotronic 300, Model GW2
For installation in or mounting on Viessmann boilers only.
Applicable to the following control units
Order No. 7134 555, 7143 156, 7511 362 from Serial No. 7143 000
Order No. 7134 555, 7143 156, 7511 362 from Serial No. 7187 101
Order No. 7134 555, 7143 156, 7511 362 from Serial No. 7248 248



General information
5285 941 v.1.6
3
Page 4
Index
General information
Page
Safety Requirements 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heating system types
Installation
Product information 3
System types for modulating boilers 6
System types for condensing boilers 12
Overview of electrical connections 18
Routing and strain relief of cables 21
Inserting the boiler coding card 22
Adjustment of the fixed high limit 23
Adjustment of the adjustable high limit 24
Connection of the outdoor temperature sensor 25
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
Connection of the boiler temperature sensor and other sensors 26
Connection of the pumps 30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection of boiler return mixing-valve or modulating valve actuator 32
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Making space for accessory adaptors on the DIN rail (CM2 only) 34
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start-up
Connections to plug aBÖ 35
Compiled failure alarm indicator 36
Connection of external equipment to plug aVD 38
Connection of external equipment to plug aVH 39
Connection of external controls 40
Connection of combustion air device 45
Connection of low water cut-off device 49
Burner connection, burner control wiring 51
Power supply connection, boiler control 55
Mounting the front part of the control unit 57
Opening the control unit 59
Procedure (overview) 63
Steps 64
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
5285 941 v.1.6
Page 5
Index
Page
Scanning service information
Troubleshooting
Functional description
Additional information
Overview of service levels 72
Temperatures, boiler coding cards and scanning 73
Scanning operating status information 77
Scanning and resetting the ”Service” display 78
Troubleshooting steps 79
Diagnosis 80
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Boiler temperature control 86
Heating circuit control 87
DHW tank temperature control 90
Overview 92
Technical data 93
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System components 94
Coding 1 114
Coding 2 116
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring diagram 135
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5285 941 v.1.6
5
Page 6
Heating system types
Heating system types for modulating boilers
System type 1 – Single-boiler system with shunt pump for raising the return temperature
in conjunction with Vitorond 200, VD2
C C
A1 M2 M3
202205222052
1
28 21
5
40
M2
2
20
52
29
17B 17A
3
90
41
146
143
T2
T1
M3
2
20
52
B
A Boiler with Vitotronic 300 B Domestic hot water tank C Heating circuit with mixing valve
*1
On the Vitorond the boiler supply and return are at the rear of the boiler.
6
*1
A
plugs
! Outdoor temperature sensor ? M2 Supply temperature sensor,
mixing valve circuit 2
? M3 Supply temperature sensor,
mixing valve circuit 3
§ Boiler temperature sensor % DHW tank temperature sensor aJA Temperature sensor T1 aJB Temperature sensor T2A1 Close mixing valves with
external heating circuit controls
M2 Heating circuit pump, mixing
valve circuit 2
M3 Heating circuit pump, mixing
valve circuit 3
sA DHW pump sK DHW re-circulation pump sL Shunt pump Power supply connection,
120 VAC
fA Burner (1st stage) gS M2 Mixing valve motor, mixing
valve circuit 2
gS M3 Mixing valve motor, mixing
valve circuit 3
Burner (2nd stage/modulating) aVD Connection of external
equipment (see page 38)
aVH Connection of external
equipment (see page 39)
5285 941 v.1.6
Page 7
Heating system types
Heating system types for modulating boilers
Possible applications
Heating systems with manifold arranged close to the boiler. The boiler water flow is required to be reduced.
Please note:
This circuit diagram represents a recommendation only. It is the responsibility of the customer and/or the heating contractor to check that this recommendation is complete and fully functional. Three-phase equipment must be connected via additional power contactors.
When the return temperature falls below the required minimum value, the temperature sensor T2 switches on the shunt pump. If the minimum return temperature is not reached despite raising the return temperature, the flow must be reduced by at least 50% via the temperature sensor T1.
The shunt pump must be sized so that bypassed water accounts for approx. 30% of the total flow rate of the boiler.
(continued)
Temperature sensor T1
Wiring of the temperature sensor T1 in heating systems with heating circuit control units which are not connected via the LON BUS to the boiler control unit. Coding required: ”4C : 2” – use plug for closing the mixing valves of the heating circuits connected downstream.
A1 Close mixing valves
A Contactor relay, field supplied B Heating circuit controls
connected downstream Switch contact closed: signal for ”close mixing valve”.
Available system accessories
Vitotrol remote controlFlue gas temperature sensor
Coding of system type
00: 1 If no system circuit A1 is connected, set
02: 1 Set coding ”02: 2” for operation with
03: 0 Set coding ”03: 1” for oil-fired operation
4A: 0 –– Connection of the temperature sensor T1 at
4b: 0 –– Connection of the temperature sensor T2 at
Change required Automatic change
The system type is recognized automatically coding ”00: 3”, ”00: 4”, ”00: 7” or ”00: 8” (see page 101)
modulating burner
(re-setting is not possible)
when the sensors are connected
plug aJA;
Coding ”4A: 1” is set automatically
plug aJB;
Coding ”4b: 1” is set automatically
––
––
5285 941 v.1.6
7
Page 8
Heating system types
Circuit Diagram 1
Single-boiler system with Therm-Control and three-way mixing valve
in conjunction with Vitorond 200, VD2A
A Heating circuit with mixing valves B DHW tank
Plug
! Outdoor temperature sensor ?M2 Flow temperature sensor,
mixing valve
?M3 Flow temperature sensor,
mixing valve
§ Boiler water temperature
sensor
% DHW tank temperature sensor aJA Therm-Control temperature
sensor
8
M2 Heating circuit pump, mixing
valve
M3 Heating circuit pump, mixing
valve
A1 Closing the mixing valves with
external heating circuit control units
sA DHW primary pump sK DHW circulation pump
Power supply, 120 VAC
60 Hz Install the main isolator in accordance with regulations
fA Burner (stage 1) gSM2 Mixing valve motor gSM3 Mixing valve motor Burner
(burner stage 2 / mod.)
aVD/aVH External connections
Please refer to the control manual Vitocontrol-S, VD2/CT3.
5285 941 v1.6
Page 9
Heating system types
Circuit Diagram 1
(continued)
A1 Close mixing valves
A Contactor relay, field supplied B Heating circuit controls
connected downstream Switch contact closed: signal for ”close mixing valve”.
Wiring diagram
Wiring of the Therm-Control in heating systems with heating circuit control units are not connected to the boiler control unit via the LON. Required coding: Change “4C” to “2” - use the plug-in connector 20 A1 to close the downstream mixing valve. Change “0D” to “1” - the Therm-Control acts on the mixing valve of the downstream heating circuits (for Vitotronic 200 and 300, delivered condition).
5285 941 v1.6
9
Page 10
Heating system types
Heating system types for modulating boilers
(continued)
System type 2 – Single-boiler system with shunt pump and return valve for raising the return temperature
in conjunction with Vitorond 200, VD2
C C
M3
2
20
52
1
28 21
5
M2 M3
22052220
41
40
M2
2
20
52
A1
29
52
52
17B 17A
3
90
146
143
T2
T1
B
A Boiler with Vitotronic 300 B Domestic hot water tank C Heating circuit with mixing valve
*1
On the Vitorond the boiler supply and return are at the rear of the boiler.
10
*1
A
plugs
! Outdoor temperature sensor ? M2 Supply temperature sensor,
mixing valve circuit 2
? M3 Supply temperature sensor,
mixing valve circuit 3
§ Boiler temperature sensor % DHW tank temperature sensor aJA Temperature sensor T1 aJB Temperature sensor T2M2 Heating circuit pump, mixing
valve circuit 2
M3 Heating circuit pump, mixing
valve circuit 3
sA Circulation pump for heating
the DHW tank
sK DHW re-circulation pump sL Shunt pump Power supply connection,
120 VAC
fA Burner (1st stage) gS A1 Mixing valve motor for raising
the return temperature
gS M2 Mixing valve motor, mixing
valve circuit 2
gS M3 Mixing valve motor, mixing
valve circuit 3
Burner (2nd stage/modulating) aVD Connection of external
equipment (see page 38)
aVH Connection of external
equipment (see page 39)
5285 941 v.1.6
Page 11
Heating system types
Heating system types for modulating boilers
Possible applications
Heating systems with distributor arranged close to the boiler. The boiler water flow is required to be reduced.
Please note:
This circuit diagram represents a recommendation only. It is the responsibility of the customer and/or the heating contractor to check that this recommendation is complete and fully functional. Three-phase equipment must be connected via additional power contactors.
Available system accessories
Vitotrol remote controlFlue gas temperature sensor
Coding system type
00: 1 If no system circuit A1 is connected, set
02: 1 Set coding ”02: 2” for operation with
03: 0 Set coding ”03: 1” for oil-fired operation
0C: 0 Set coding ”0C: 1” for continuous return
4A: 0 –– Connection of the temperature sensor T1 at
4b: 0 –– Connection of the temperature sensor T2 at
Change required Automatic change
coding ”00: 3”, ”00: 4”, ”00: 7” or ”00: 8” (see page 114)
modulating burner
(re-setting is not possible)
temperature control
When the return temperature falls below the required minimum value, the temperature sensor T2 switches on the shunt pump. If, as a result, the required minimum return temperature is not reached, the return valve is proportionally closed via the temperature sensor T1 and the minimum return temperature is assured.
The shunt pump must be sized so that bypassed water accounts for approx. 30% of the total flow rate of the boiler.
(continued)
The system type is recognized automatically
when the sensors are connected
––
––
––
plug aJA;
Coding ”4A: 1” is set automatically
plug aJB;
Coding ”4b: 1” is set automatically
5285 941 v.1.6
11
Page 12
Heating system types
Heating system types for condensing boilers
System type 3 – Single-boiler system with Vitocrossal 300
C C
A1 M2 M3
20220
1
28 21
5
41
40
52220
90
143
M2
2
20
52
52
3
146
M3
2
20
52
B
A Boiler with Vitotronic 300 B Domestic hot water tank C Heating circuit with mixing valve D Neutralizing unit
D
A
plugs
! Outdoor temperature sensor ? M2 Supply temperature sensor,
mixing valve circuit 2
? M3 Supply temperature sensor,
mixing valve circuit 3
§ Boiler temperature sensor % DHW tank temperature sensorA1 Heating circuit without mixing
valve (if installed)
M2 Heating circuit pump, mixing
valve circuit 2
M3 Heating circuit pump, mixing
valve circuit 3
sA Circulation pump for heating
the DHW tank
sK DHW re-circulation pump Power supply connection,
120 VAC
fA Burner (1st stage) gS M2 Mixing valve motor, mixing
valve circuit 2
gS M3 Mixing valve motor, mixing
valve circuit 3
Burner (2nd stage/modulating) aVD Connection of external
equipment (see page 38)
aVH Connection of external
equipment (see page 39)
5285 941 v.1.6
12
Page 13
Heating system types
Heating system types for condensing boilers
Please note:
This circuit diagram represents a recommendation only. It is the responsibility of the customer and/or the heating contractor to check that this recommendation is complete and fully functional. Three-phase equipment must be connected via additional power contactors.
Available system accessories
Vitotrol remote controlFlue gas temperature sensor
Coding system type
00: 1 If no system circuit A1 is connected, set
02: 1 Set coding ”02: 2” for operation with
0d: 1 Set coding ”0d: 0” ––
Change required Automatic change
coding ”00: 3”, ”00: 4”, ”00: 7” or ”00: 8” (see page 114)
modulating burner
The Vitocrossal 300 is operated with modulating boiler water temperature by means of the outdoor re-set boiler control unit. Viessmann modulating burner is operated through Vitotronic control.
The boiler water temperature which is established in the heating mode is higher than the maximum heating circuit supply temperature by an adjustable difference.
(continued)
The system type is recognized automatically
when the sensors are connected
––
5285 941 v.1.6
13
Page 14
Heating system types
Heating system types for condensing boilers
(continued)
System type 4 - Single-boiler system with Vitocrossal 300 with several heating circuits and one modulating supply temperature heating circuit
M3
2
F
20
52
or
A1 M2 M3
20220
1
28 21
5
41
40
52220
90
143
C D
M2
2
20
52
52
3
146
M3
2
20
52
E
B
G
A Boiler with Vitotronic 300 B Domestic hot water tank C Heating circuit with mixing valve D Modulating supply temperature
heating circuit or
E Underfloor heating circuit F High limit thermostat (max. limit) G Neutralizing unit
14
A
plugs
! Outdoor temperature sensor ? M2 Supply temperature sensor,
mixing valve circuit 2
? M3 Supply temperature sensor,
mixing valve circuit 3
§ Boiler temperature sensor % DHW tank temperature sensorA1 Heating circuit without mixing
valve (if installed)
M2 Heating circuit pump, mixing
valve circuit 2
M3 Heating circuit pump, mixing
valve circuit 3
sA Circulation pump for heating
the DHW tank
sK DHW re-circulation pump Power supply connection
120 VAC
fA Burner (1st stage) gS M2 Mixing valve motor, mixing
valve circuit 2
gS M3 Mixing valve motor, mixing
valve circuit 3
Burner (2nd stage/modulating) aVD Connection of external
equipment (see page 38)
aVH Connection of external
equipment (see page 39)
5285 941 v.1.6
Page 15
Heating system types
Heating system types for condensing boilers
Possible applications
For heating circuits with different temperatures.
Please note:
This circuit diagram represents a recommendation only. It is the responsibility of the customer and/or the heating contractor to check that this recommendation is complete and fully functional. Three-phase equipment must be connected via additional power contactors.
The Vitocrossal 300 is operated with modulating boiler water temperature by means of the outdoor re-set boiler control unit. Two-stage or modulating burners can be controlled.
The Vitocrossal 300 has two return connections. The heating circuits with the higher return temperature are connected to the return connection at the top, those with the lower temperatures to the return connection at the bottom. Please note: At least 15% of the take-off from the rated output must be connected to the return connection at the bottom.
The boiler water temperature which is established in the heating mode is higher than the maximum heating circuit supply temperature by an adjustable difference.
(continued)
Pumps in the underfloor heating circuit
20
20
LN
A B C
Heating circuit control unit
A Primary pump of underfloor
heating circuit
B High limit thermostat (max. limit) C Secondary pump of underfloor
heating circuit (after system separation)
Coding system type
00: 1 If no system circuit A1 is connected, set
02: 1 Set coding ”02: 2” for operation with
0d: 1 Set coding ”0d: 0” ––
5285 941 v.1.6
Change required Automatic change
The system type is recognized automatically coding ”00: 3”, ”00: 4”, ”00: 7” or ”00: 8” (see page 114)
modulating burner
when the sensors are connected
––
15
Page 16
Heating system types
Heating system types for condensing boilers
System type 5 – Single-boiler system with Vitocrossal 200
A Boiler with Vitotronic 300 B Domestic hot water tank C Heating circuit with mixing valve D Neutralizing unit
16
plugs
! Outdoor temperature sensor ? M2 Supply temperature sensor,
mixing valve circuit 2
? M3 Supply temperature sensor,
mixing valve circuit 3
§ Boiler temperature sensor % DHW tank temperature sensorA1 Heating circuit without mixing
valve (if installed)
M2 Heating circuit pump, mixing
valve circuit 2
M3 Heating circuit pump, mixing
valve circuit 3
sA Circulation pump for heating
the DHW tank
sK DHW re-circulation pump Power supply connection,
120 VAC
fA Burner (1st stage) gS M2 Mixing valve motor, mixing
valve circuit 2
gS M3 Mixing valve motor, mixing
valve circuit 3
Burner (2nd stage/modulating) aVD Connection of external
equipment (see page 38)
aVH Connection of external
equipment (see page 39)
5285 941 v.1.6
Page 17
Heating system types
Heating system types for condensing boilers
Please note:
This circuit diagram represents a recommendation only. It is the responsibility of the customer and/or the heating contractor to check that this recommendation is complete and fully functional. Three-phase equipment must be connected via additional power contactors.
Available system accessories
Vitotrol remote control
Coding system type
00: 1 If no system circuit A1 is connected, set
02: 1 Set coding ”02: 2” for operation with
0d: 1 Set coding ”0d: 0” ––
Change required Automatic change
coding ”00: 3”, ”00: 4”, ”00: 7” or ”00: 8” (see page 114)
modulating burner
The Vitocrossal 200 is operated with modulating boiler water temperature by means of the outdoor re-set boiler control unit. Viessmann modulating burner is operated through Vitotronic control.
The boiler water temperature which is established in the heating mode is higher than the maximum heating circuit supply temperature by an adjustable difference.
(continued)
The system type is recognized automatically when the sensors are connected
––
5285 941 v.1.6
17
Page 18
Installation
Overview of electrical connections
52
M3
52
M2
20
M3
20
M2
2
M3
2
M2
145 145
1
17
B
17
A
5
3/2
15
143
146
28 21 52 20 29 50
40 156 156
A1 A1
151
90
41
150
Mixing valve extension circuit board
? M2/M3 Supply temperature sensorM2/M3 Heating circuit pump gS M2/M3 Mixing valve motor
18
Low-voltage motherboard
! Outdoor temperature sensor
(ATS)
§ Boiler temperature sensor (BTS) % DHW tank temperature sensor
(STS)
aG Flue gas temperature sensor
(AGS) (accessory)
aJA Therm-Control temperature
sensor or return temperature sensor T1 (RLS) (accessory)
aJB Return temperature sensor T2
(RLS) (accessory)
aVD Connection of external
equipment
aVG KM BUS participant, e.g.
Vitotrol remote control (accessory)
aVH Connection of external
equipment
Line voltage motherboard
A1 Heating circuit pump or
control output
sA Circulation pump for heating
the DHW tank (accessory)
sK DHW re-circulation pump
(provided by customer)
sL Shunt pump Power supply connection fA Burner (1st stage) Central fault indicator gSA1 Continuous return
temperature control or 3-way mixing valve for DHW tank loading system
Burner (2nd stage/modulating) aBÖ Connection of external
equipment, e.g. additional safety equipment
aBA Safety circuit, potential free aBH Power supply connection for
accessories
5285 941 v.1.6
Page 19
Overview of electrical connections(for VD2/VD2A/CT3 only)
Installation
5285 941 v.1.6
19
Page 20
Installation
Overview of electrical connections (for CM2 only)
20
5285 941 v.1.6
Page 21
Routing and strain relief of cables
1. Run the cables from the connection enclosure into the control unit.
2. Apply strain relief to cables (see below).
Installation
Cables with moulded strain relief clamp
Connect cable and strain relief clamp.
OR
Fasten cable to the cable lead with cable tie.
5285 941 v.1.6
21
Page 22
Installation
Inserting the boiler coding card
CAUTION
For matching the operation of the control unit to the boiler, only the boiler coding card which is supplied as part of the standard delivery of the boiler may be used.
Only use the boiler coding card included with the boiler.
Boiler Coding card Part No.
Vitocrossal 300, type CT3 1040 7820 144
Vitorond 200, VD2 / VD2A 1020 7820 142
Vitocrossal 200 CM2 1041 7820 145
1. Push the boiler coding card through the recess in the cover and insert it in plug-in location ”X7”.
22
5285 941 v.1.6
Page 23
Installation
Adjustment of the fixed high limit
The fixed high limit is supplied with a factory setting of 110°C / 230°F.
3.
(if required)
A
Adjustment to 99°C / 210°F
¨ Disconnect power to control
and burner!
1. Unclip the fuse box and swing
upwards.
2. Turn the slotted screw on the rear of the fixed high limit until the slot points to 99°C / 210°F (once adjusted, the fixed high limit
cannot be reset to 110°C/ 230°F).
3. Re-fit the fuse box.
WARNING
If adjusted to 99°C / 210°F, do not set the adjustable high limit above 75°C / 167°F.
Please note:
Adjustment is required for the
1.
Vitocrossal 300.
See Service Instructions for Vitocrossal 300.
2.
Non-condensing boiler (VD2/VD2A) °C / °F
Fixed high limit 110 / 230 99 / 210 99 / 210 99 / 210
Adjustable high limit 100 / 212 95 / 203 95 / 203 95 / 203
Coding for the electronic maximum temperature limiter of Vitotronic 100; set code 06 to the temperature as shown or less
93 / 200 87 / 188 87 / 188 88 / 190
Condensing boiler (CT3) °C / °F
Condensing boiler (CM2) °C / °F
5285 941 v.1.6
23
Page 24
Installation
Adjustment of the adjustable high limit
The adjustable high limit is supplied with a factory setting of 95°C.
A
3.
2.
(if required)
Adjustment to 100°C / 212°F
1. Using a suitable screwdriver,
lever out and remove the selector knob ”R” behind the hinged cover.
2. Using a pair of pointed pliers, break off the cams identified by the shaded areas in the Fig. from the stop dial.
A 75 to 100°C
167 to 212°F
3. Fit the selector knob ”R” so that the marking is in the centre of the selected range.
Please note:
Note the setting of coding address ”06”!
1.
WARNING
If the system is operated in conjunction with a domestic hot water tank, ensure that the maximum permissible domestic hot water temperature is not exceeded. If necessary, install a suitable safety device for this purpose.
24
5285 941 v.1.6
Page 25
Connection of the outdoor temperature sensor
The outdoor temperature sensor should be mounted 2 to 2.5 metres / 6.5 to 8 ft above ground level on the north or north-west facing wall of the building. In the case of multi-storey buildings, it should be mounted in the upper half of the second storey. Make sure that the sensor is not located over windows, doors and air vents, nor immediately beneath a balcony or guttering. Do not paint over the outdoor temperature sensor housing.
1.
5.
3.
Installation
1. Remove the cap.
2. Mount the bottom part of the
sensor housing.
3. Pull the sensor wire through the opening in the terminal compartment and through the strain relief provided.
4. Connect the wires to the terminals.
600
580
560
540
520
500
480
460
4.
2.
5. Place the cap over the outdoor temperature sensor.
WARNING
When extending wire, there is the possibility of exposure to electromagnetic interference. Avoid running wires beside or near high voltage 120/240 VAC conductors. If proximity to high voltage conductors cannot be avoided, use stranded, twisted pair or shield design wire. Ensure that only one end of the shielding is grounded.
440
420
Resistance in
400
-40 -30 -20 -10 0 10 20 30
-40 -22
Outdoor temperature sensor °C / °F
5285 941 v.1.6
-4
14 32 50 68 86
25
Page 26
Installation
Connection of the boiler temperature sensor
The sensor measures the boiler water temperature.
3
760
740
The boiler temperature sensor is installed at the same time as the boiler insulation.
Check the sensor
1. Disconnect plug § in the
terminal compartment of the boiler control.
2. Measure resistance of sensor at terminals ”1” and ”2” of the plug.
Boiler water temperature in °C / °F
40 / 104 50 / 122 60 / 140
3. Compare the value measured with the current temperature. If the value differs significantly, check installation and, if necessary, replace sensor.
Resistance in ΩΩΩ
578 597 616
720
700
680
660
640
620
Resistance in
600
580
560
4000540
32 68 141 176 212 248 284104
Boiler temperature in
Technical data
Degree of protection: IP 32 Ambient temperature During operation:
0 to + 130°C
32 to + 266°F
During storage and transport:
-20 to + 70°C
-4 to + 158°F
Electrical connection
The sensors are ready to plug in. Insert the boiler temperature sensor in socket ”3” of the boiler control.
20 40 60 80 100 120 140
°C / °F
26
5285 941 v.1.6
Page 27
Connection of the DHW tank temperature sensor
Installation
The sensor measures the domestic hot water tank temperature.
5
sensor and tank temperature sensor
720
Heating systems with domestic hot water heating (single-boiler systems only)
1. Install the DHW tank temperature
sensor.
See Installation Instructions for domestic hot water tank.
Please note:
When installing the sensor in DHW tanks of other makes, make sure that the sensor is pressed against the sensor well of the DHW tank by means of a suitable device.
2. Ensure that the maximum permissible domestic hot water temperature is not exceeded. If necessary, install a suitable safety device for this purpose.
Heating systems without domestic hot water heating
Do not connect the DHW tank temperature sensor.
Check the sensor
1. Disconnect plug % in the
terminal compartment of the boiler control.
2. Measure resistance of sensor at terminals ”1” and ”2” of the plug.
DHW tank temperature in °C / °F
40 / 104 50 / 122 60 / 140
3. Compare the value measured with the current temperature. If the value differs significantly, check installation and, if necessary, replace sensor.
Technical data
Degree of protection: IP 32 Ambient temperature During operation:
0 to + 90 °C
32 to + 194 °F
During storage and transport:
-20 to + 70 °C
-4 to + 158 °F
Resistance in ΩΩΩ
578 597 616
700
Electrical connection
680
660
640
620
The sensors are ready to plug in. Insert the DHW temperature sensor in socket ”5” of the boiler control.
Resistance in
600
580
560
540
0 20 40 60 80 100 32 68 104 140 176 212
DHW tank temperature in ºC / ºF
5285 941 v.1.6
27
Page 28
Installation
740
R
e
s
i
s
t
a
n
c
e
i
n
Connection of the return temperature sensor
Strap-on temperature sensor and immersion temperature sensor
17A or 17B
17A or 17B
For measuring the boiler return temperature.
Electrical connection
The sensor is inserted in socket ”17A” or ”17B” on the boiler control.
Check the sensor
1. Disconnect plug aJA or aJB
in the terminal compartment of the boiler control.
2. Measure resistance of sensor at terminals ”1” and ”2” of the plug.
720
700
680
660
640
620
Return temperature in °C / °F
30 / 86 40 / 104 60 / 140
3. Compare the value measured with the current temperature. If the value differs significantly, check installation and, if necessary, replace sensor.
Technical data
Degree of protection: IP 32 Ambient temperature During operation:
0 to + 100°C
32 to + 212°F
During storage and transport:
-20 to + 70°C
-4 to + 158°F
Resistance in ΩΩΩ
569 592 643
600
580
560
540
28
30 40 50 60 7070 80 90
20 100 68 86 104 122 140 158 176 194 212
Return temperature in
°C / °F
5285 941 v.1.6
Page 29
Connection of the flue gas temperature sensor (VD2/VD2A/CT3 only)
The sensor measures the flue gas temperature and monitors the selected limit value.
Electrical connection
The sensor is inserted in socket ”15” on the boiler control.
Check flue gas temperature sensor
1. Disconnect plug aG in the
terminal compartment .
2. Measure resistance of sensor at terminals ”1” and ”2” of the plug.
Installation
1020
980
940
900
860
820
780
740
700
Resistance in
660
Flue gas temperature in °C / °F
180 / 176
160 / 320 200 / 392
3. Compare the value measured with the actual temperature If the value differs significantly, check installation and, if necessary, replace sensor.
Technical data
Degree of protection: IP 60 Ambient temperature During operation:
0 to + 600°C
32 to + 1112°F
During storage and transport:
-20 to + 70°C
-4 to + 158°F
Resistance in ΩΩΩ
650 800 880
620
580
540
500
0
40 80
32 104 176
Flue gas temperature in °C / °F
5285 941 v.1.6
120 160 200 240 280 248 360 392 464 536
29
Page 30
Installation
Connection of the Pumps (VD2/VD2A/CT3 only)
Available pump connections
A1/M1Heating circuit high
temperature (without mixing valve)
Terminals 5 - L, - G , - N
sA Circulation pump for heating
up the domestic hot water tank ­Terminals 4 - L, - G , - N
sL Shunt pump, boiler circuit pump
Terminals 6 - L, - G, - N.
sK
DHW recirculattion pump
terminals 3 - L, - G, - N
M2
M2 Heating circuit high temperature (with mixing valve) Terminals 2 - L, - G , - N
M3
M3 Heating circuit high temperature (with mixing valve) Terminals 1 - L, - G , - N
Install pumps: see manufacturer’s instructions.
120 VAC pumps
Note:
The maximum power consumption of all pumps is 4A . Rated current: max. 2 FLA Recommended connection cable: AWG 14
Use contactor for pumps with higher current rating
Connect the 3-wire cable from the pump to the corresponding terminals.
240 VAC or 3 PH pumps
Please note:
Use contactor and/or motor starter to power pump. For activating the contactor: Rated current: max. 2 FLA Recommended connection wire size: AWG 14
Please ensure that all connections and wire sizes comply with local and national codes.
1.Select the contactor and the connecting wire in accordance with the rating of the pump that is to be connected.
2.Connect pump and power supply to the contactor.
3.Connect contactor coil to the corresponding terminals.
30
5285 941 v1.6
Page 31
Connection of the Pumps (CM2 only)
Available pump connections
Installation
A1/M1Heating circuit high
temperature (without mixing valve)
Terminals 7 - L, - G , - N
sA Circulation pump for heating
up the domestic hot water tank ­Terminals 6 - L, - G , - N
sL Shunt pump, boiler circuit pump
Terminals 8 - L, - G, - N.
sK
DHW recirculattion pump
terminals 5 - L, - G, - N
M2
M2 Heating circuit high temperature (with mixing valve) Terminals 4 - L, - G , - N
M3
M3 Heating circuit high temperature (with mixing valve) Terminals 3 - L, - G , - N
Install pumps: see manufacturer’s instructions.
120 VAC pumps
Note:
The maximum power consumption of all pumps is 4A . Rated current: max. 2 FLA Recommended connection cable: AWG 14
Use contactor for pumps with higher current rating
Connect the 3-wire cable from the pump to the corresponding terminals.
240 VAC or 3 PH pumps
Please note:
Use contactor and/or motor starter to power pump. For activating the contactor: Rated current: max. 2 FLA Recommended connection wire size: AWG 14
Please ensure that all connections and wire sizes comply with local and national codes.
1.Select the contactor and the connecting wire in accordance with the rating of the pump that is to be connected.
2.Connect pump and power supply to the contactor.
3.Connect contactor coil to the corresponding terminals.
5285 941 v1.6
31
Page 32
Installation
Connection of boiler return mixing valve or modulating valve actuator
(VD2/VD2A/CT3 only)
1 120V or 24V valve adaptor
2 DIN rail in connection enclosure
3 aBH Terminals
120V valve adaptor
Rated voltage: 120 VAC Rated current: max. 0.1 FLA Recommended connection wire size: AWG 14 Part No.: 7134 560
24V valve adaptor
Rated voltage: 24 VAC Rated current: max. 0.15 FLA Recommended connection wire size: AWG 14 Part No.: 7134 559
Operating time:
5 to 199 sec. selected via coding address “40”.
1 120V valve adaptor
2 120V valve actuator
1 24V valve adaptor
2 24V valve actuator
1. Disconnect power to control.
2. Install 120V or 24V valve adaptor on DIN rail inside connection enclosure.
3. Insert the plug gS into socket gS on the control.
4. Fasten cable with tie. (see page 21).
5. Connect black wire of the adaptor to connection aBH on the DIN rail.
- Terminal 8,9 or 10.
6. Connect valve actuator wires to the adaptor terminals as shown in figures.
32
5285 941 v.1.6
Page 33
Installation
Connection of Boiler Return Mixing Valve or Isolation/Modulating Valve
(CM2 only)
10 11 12
1 120V or 24V Valve Adaptor
2 Junction box
3 120V L out power supply
120V Valve Adaptor
Rated voltage: 120 VAC Rated current: max. 0.1 FLA Recommended connection wire size: AWG 14 Part No. 7511367
24V Valve Adaptor
Rated voltage: 24 VAC Rated current: max. 0.15 FLA Recommended connection wire size: AWG 14 Part No. 7511366
Operating time:
5 to 199 sec. selected via coding address “40”.
1 120V Valve Adaptor
2 120V valve actuator
1 24V Valve Adaptor
2 24V valve actuator
1. Disconnect power to control.
2. Install 120V or 24V Valve Adaptor on DIN rail inside connection enclosure.
3. Insert the plug gS into socket gS on the control.
4. Fasten cable with tie (see page.21).
5. Connect black wire of the adaptor to connection 120V L out the DIN rail
- Terminals 10,11 or 12.
6. Connect valve actuator wires to the adaptor terminals as shown on figures.
5285 941 v1.6
33
Page 34
Installation
Making Space for Accessory Adaptors on the DIN Rail (CM2 only)
1. Push up on the bottom front of
the DIN rail clamp to remove and set aside.
2. Using a flat head screwdriver, remove the 4 ’spare’ DIN terminals 23, 24, 25 and 26 one at a time. Place the screwdriver between the rail and the base of the terminal and turn the screwdriver clockwise . Discard the removed terminals.
3. Re-install the DIN rail clamp by hooking the latch of the clamp around the top of the rail and then push down on the front of the clamp.
Note: See separate Installation
Instructions for accessory
adaptors.
34
5285 941 v1.6
Page 35
Connections to terminal aBÖ (VD2/VD2A/CT3 only)
Installation
External shut-off
1. Remove jumper between
terminals 16 and 17.
2. Connect dry contact. Controlled switch-off takes place when the contact is opened.
WARNING
The terminals should be used for safety switch-off purposes only (e.g. through a high limit thermostat). Start at page 52 for details of controlled switch-off. During switch-off, there is no frost protection of the heating system and the boiler is not kept at the minimum boiler water temperature.
A Jumper B External shut-off (dry contact)
Emergency operation
Move jumper from terminals 16 and 17 to terminals 17 and 18.
5285 941 v.1.6
35
Page 36
Installation
Connection of the compiled failure alarm indicator (VD2/VD2A/CT3 only)
Rated voltage: 120 VAC 60 Hz
A
B
Rated current: max. 2 FLA Recommended connection wire size: AWG 14
1. Disconnect power to control and burner.
2. Connect the compiled failure alarm as shown in the diagram.
A Connect terminal strip in
connection enclosure of boiler control.
B Visual ond/or audible alarm
device (120 VAC).
36
5285 941 v.1.6
Page 37
Connection of the compiled failure alarm indicator (CM2 only)
Installation
9
A
B
Rated voltage: 120 VAC 60 Hz Rated current: max. 2 FLA Recommended connection wire size: AWG 14
1. Disconnect power to control and burner.
2. Connect the compiled failure alarm as shown in the diagram.
A Connect terminal strip in
connection enclosure of boiler control.
B Visual ond/or audible alarm
device (120 VAC).
5285 941 v.1.6
37
Page 38
Installation
address64
Connection of external equipment to terminal aVD
A
External changeover of the heating program/”Open mixing valves”
Connect floating contact to terminals ”1” and ”2”.
B
143
A External changeover of the heating program/
”Open mixing valves” externally (floating contact)
B External disable/”Close mixing valves” externally
(floating contact)
The manually preselected heating program can be changed over (see table) and the mixing valves opened via the contact.
Via coding address ”9A” the function ”Open mixing valves” and via coding address ”91” the changeover of the heating program can be assigned to the heating circuits.
External disable/”Close mixing valves”
Connect floating contact to terminals ”2” and ”3”.
Controlled switch-off of the burner takes place or the mixing valves are closed when the floating contact is closed. The shunt pump is switched off.
Please note:
During controlled switch-off or ”Close mixing valves”, there is no frost protection of the boiler or heating circuits and no minimum boiler water temperature is maintained.
Manually preselected heating program
(with contact open)
9
or
w
or rw Space heating ON/DHW ON
38
Space heating OFF/DHW OFF d5: 0
Space heating ON/DHW ON d5: 1 <–>
Coding address ”99” can be used to select the equipment for which the input aVD is to be effective.
Coding 2 Heating program after changeover
(with contact closed)
<–> Continuous operation with reduced room
(factory default)
temperature/DHW OFF
Continuous operation with normal room temperature/DHW according to coding address ”64”
5285 941 v.1.6
Page 39
Connection of external equipment to plug aVH
B
A
Installation
External demand
Connect floating contact to terminals ”2” and ”3”.
The burner of the boiler is switched in on a load-dependent basis when the floating contact is closed.
The boiler water temperature is limited by the preset max. boiler water temperature or by the value set on the mechanical adjustable high limit. The required boiler set-point value is set via the coding address ”9b”.
146
A External demand (floating contact) B External changeover,
staged/modulating burner (floating contact)
External changeover between staged/modulating burner
Connect floating contact to terminals ”1” and ”2”.
Contact open: modulating
operation
Contact closed: two-stage
operation
The burner type must be set to ”modulating” in coding 1 (coding ”02: 2”).
Please note:
When the burner type is scanned, ”modulating” continues to be displayed after external changeover (the display is not changed).
5285 941 v.1.6
39
Page 40
Installation
Connection of external controls
Operation with two-stage burner
Settings on the control unit
The settings for the fixed high limit and the other settings are dependent on the safety equipment installed in accordance with applicable codes.
Non-condensing boiler (VD2/VD2A) °C / °F
Fixed high limit 110 / 230 99 / 210 99 / 210 99 / 210
Adjustable high limit 100 / 212 95 / 203 95 / 203 95 / 203
Coding for the electronic maximum temperature limiter of Vitotronic 100; set code 06 to the temperature as shown or less
93 / 200 87 / 188 87 / 188 88 / 190
Single-boiler systems:
Coding ”01: 1” (factory setting)
When a building automation system is connected, only the connections on plug aVD are required. The DHW tank control unit is activated when the DHW tank temperature sensor is connected. The boiler water temperature must be set to the minimum value.
Condensing boiler (CT3) °C / °F
Multi-boiler systems:
Set coding ”01: 3”
When a building automation system is connected, the connections on plugs aVD and aVH are required. The DHW tank temperature and the load-dependent cascade control must be controlled through the building automation system.
Condensing boiler (CM2) °C / °F
40
CAUTION
The boiler activation contact is essential on multi-boiler systems. The contact on the lead boiler MUST be constantly closed.
5285 941 v.1.6
Page 41
Installation
Connection of external controls (VD2/VD2A only)
Modulating boilers – operation with external modulation controller
1st stage burner fA from Vitotronic.
Plug from Vitotronic via
modulation controller (BAS).
On the bulding automation unit with
modulation controller set the minimum temperatures 5°C / 9°F above the minimum boiler water temperature of the boiler.
(continued)
Boiler activation, isolation valve open or closed
Connect dry contact at terminals ”2” and ”3” of the plug aVH.
Contact closed: First, the preheat function for follow­up boilers is activated (coding address ”2b”). When the preheat function finishes, the minimum temperature is maintained for the boiler, and the burner stages/modulation can be switched externally. The boiler water temperature is limited by the preset maximum boiler water temperature or via the mechanical adjustable high limit. The setpoint value is selected via the coding address ”9b”.
Contact open: The isolation valve is closed after approx. 5 minutes (coding address ”2C”). External override of the burner stages is not possible, and no minimum temperature is maintained.
Switch on 1st stage burner (basic load)
Connect dry contact at terminals ”1” and ”2” of the plug aVD.
Contact closed: The 1st stage burner is switched on. The full load is only switched on to maintain the minimum temperature (not with Vitocrossal 300). The boiler water temperature is limited by the electronic maximum temperature limit (coding address ”06”) if this is set below the value preset on the mechanical adjustable high limit ”R”.
Contact open: The 1st stage burner is switched off.
5285 941 v.1.6
41
Page 42
Installation
Connection of external controls (VD2/VD2A only)
Modulating boilers – operation with external modulation controller (continued)
Settings on the control unit
The settings for the fixed high limit and the other settings are dependent on the safety equipment installed in accordance with applicable codes.
Non-condensing boiler (VD2/VD2A) °C / °F
Fixed high limit 110 / 230 99 / 210 99 / 210 99 / 210
Adjustable high limit 100 / 212 95 / 203 95 / 203 95 / 203
Coding for the electronic maximum temperature limiter of Vitotronic 100; set code 06 to the temperature as shown or less
93 / 200 87 / 188 87 / 188 88 / 190
Single-boiler systems:
Coding ”01: 1” (factory setting)
Condensing boiler (CT3) °C / °F
(continued)
Condensing boiler (CM2) °C / °F
Multi-boiler systems:
Set coding ”01: 3”
When a building automation system is connected, only the connections on plug aVD are required. The DHW tank control unit is activated when the DHW tank temperature sensor is connected. The boiler water temperature must be set to the minimum value.
When a building automation system is connected, the connections on plugs aVD and aVH are required. The DHW tank temperature and the load-dependent cascade control must be controlled through the external building automation system.
CAUTION
The boiler activation contact is essential on multi-boiler systems. The contact on the lead boiler MUST be constantly closed.
42
5285 941 v.1.6
Page 43
Installation
Connection of external controls (CT3 only)
Vitocrossal 300 – operation with external modulation controller
1st stage burner fA from
Vitotronic 100.
Connection from Vitotronic has
no function.
Connection from building
automation system to the burner.
1st stage burner activated by the
modulation controller via connection aVH.
(continued)
Boiler activation, isolation valve open or closed
Connect dry contact at terminals ”2” and ”3” of the plug aVH.
Contact closed: First, the preheat function for follow-up boilers is activated (coding address ”2b”). When the preheat function finishes, the burner stages/modulation can be switched externally. The boiler water temperature is limited by the preset maximum boiler water temperature or via the mechanical adjustable high limit. The setpoint value is selected via the coding address ”9b”.
Contact open: The isolation valve is closed after approx. 5 minutes (coding address ”2C”). External override of the burner stages is not possible, and no minimum temperature is maintained.
Switch on 1st stage burner (basic load)
Connect dry contact at terminals ”1” and ”2” of the plug aVD.
Contact closed: The 1st stage burner is switched on. The boiler water temperature is limited by the electronic maximum temperature limit (coding address ”06”) if this is set below the value preset on the mechanical adjustable high limit ”R”.
Contact open: The 1st stage burner is switched off.
5285 941 v.1.6
43
Page 44
Installation
Connection of external controls (CT3 only)
Vitocrossal 300 – operation with external modulation controller (continued)
Settings on the control unit
The settings for the fixed high limit and the other settings are dependent on the safety equipment installed in accordance with applicable codes.
Non-condensing boiler (VD2/VD2A) °C / °F
Fixed high limit 110 / 230 99 / 210 99 / 210 99 / 210
Adjustable high limit 100 / 212 95 / 203 95 / 203 95 / 203
Coding for the electronic maximum temperature limiter of Vitotronic 100; set code 06 to the temperature as shown or less
93 / 200 87 / 188 87 / 188 88 / 190
Single-boiler systems:
Coding ”01: 1” (factory setting)
(continued)
Condensing boiler (CT3) °C / °F
Condensing boiler (CM2) °C / °F
Multi-boiler systems:
Set coding ”01: 3”
When a building automation system is connected, only the connections on plug aVD are required. The DHW tank control unit is activated when the DHW tank temperature sensor is connected. The boiler water temperature must be set to the minimum value.
When a building automation system is connected, the connections on plugs aVD and aVH are required. The DHW tank temperature and the load-dependent cascade control must be controlled through the building automation system.
CAUTION
The boiler activation contact is essential on multi-boiler systems. The contact on the lead boiler MUST be constantly closed.
44
5285 941 v.1.6
Page 45
Installation
Connections of combustion air device adaptor (VD2/VD2A/CT3 only)
Connection of the Combustion Air Device Adaptor
1. Disconnect power to control and
burners.
2. Install Combustion Air Device Adaptor, Part No.: 7134 563 on DIN Rail inside connection enclosure (refer to installation manual of Combustion Air Device Adaptor).
3. Remove jumper between terminals 16 and 17.
4. Make connection as shown in the diagram.
IMPORTANT
Wire BK2 must be connected to terminal 16 and BK3 to terminal 17 - DO NOT reverse.
D
A Combustion Air Device Adaptor B DIN Rail in connection enclosure
Connection of the combustion air blower to adaptor
Rated voltage: 120 VAC Rating current: max 5 FLA Recommended connection wire size: AWG 14
Note:
Assure that combustion air blower device is suitable for this application.
For detailed instruction on adaptor installation, please refer to the adaptor’s installation manual.
1. Make connection as shown in the diagram at left.
A Combustion Air Device Adaptor
in connection enclosure
B Combustion air blower motor C Proving switch - “normally open”
rated for 120 VAC
D Power supply, 120 VAC
5285 941 v.1.6
CAUTION
Provide disconnect means and overcurrent protection as required by local codes.
45
Page 46
Installation
Connection of Combustion Air Device (CM2 only)
D
Connection of the Combustion Air Device Adaptor
1. Disconnect power to control and burners.
2. Install Combustion Air Device Adaptor, Part No. 7134 563 on DIN Rail inside the boiler junction box (refer to installation manual of Combustion Air Device Adaptor).
3. Remove plug 150 from Vitotronic control. Remove jumper between the 2 ’TR’ terminals. Using 14 AWG (field supplied) connect plug terminals TR(Left), TR(Right) and neutral to the DIN rail.
Neutral to Terminal 16 TR(Left) to Terminal 18 TR(Right) to Terminal 19
Re-install the 150 plug and DIN rail connections as shown in the diagram.
IMPORTANT
Connection of the combustion air blower to adaptor
Rated voltage: 120 VAC Rating current: max 5 FLA Recommended connection wire size: AWG 14
Ensure that combustion air blower device is suitable for this application.
For detailed instruction on adaptor installation please refer to the adaptor’s installation manual.
1. Make connection as shown in the diagram at left.
A Combustion Air Device Adaptor
in connection enclosure
B Combustion air blower motor C Proving switch - “normally open”
rated for 120 VAC.
D Power supply, 120 VAC
¨ Safety instruction!
Provide disconnect means and overcurrent protection as required by local codes.
Wire BK2 must be connected to terminal 18 and BK3 to terminal 19 ­DO NOT reverse.
46
5285 941 v1.6
Page 47
Installation
Connection of combustion air device
(continued)
E
Connection of the combustion air damper
See damper manual for correct installation.
Note:
Assure that the combustion air damper is suitable for this application.
1. Disconnect power to control and burner.
2. Make connection as shown in the diagram.
A Combustion Air Device Adaptor
in connection enclosure
B Relay 120 VAC coil - field
supplied
C Combustion air damper D End switch rated for 120 VAC
wired to “normally open” terminal on device adaptor board
E Power supply, 120 VAC
CAUTION
Provide disconnect means and overcurrent protection as required by local codes.
Note:
Spring return air dampers do not require field supplied relay.
5285 941 v.1.6
47
Page 48
Installation
Flue Gas Temp. Switch (mandatory for PP(s) material collectors)
(CM2 only)
1. Disconnect power.
CAUTION
Please note that the diagram shown is only a simplified conceptual drawing of a flue gas temperature switch. Refer to the manual specific to the device for interconnection details.
2. Remove 150 plug from the Vitotronic control and discard.
3. Install new 150 plug supplied (attached to flue gas temperature switch).
48
5285 941 v1.6
Page 49
Connection of low water cut-off device (VD2/VD2A/CT3 only)
1.Remove jumper between
terminals 12 and 15.
2.Make connection as shown in diagram.
CAUTION
Please note that the diagram at left is only a simplified conceptual drawing of a typical low water cut off (LWCO) device. Refer to the manual specific to the device for interconnection details.
Installation
aBH Power supply for accessories.
aBÖ Connection for external
equipment.
5285 941 v.1.6
49
Page 50
Installation
Connection of Low Water Cut-off Device (CM2 only)
1. Remove jumper between terminals
21 and 22.
2. Make connection as shown in diagram.
CAUTION
Please note that the diagram shown is only a simplified conceptual drawing of a typical low water cut-off (LWCO) device. Refer to the manual specific to the device for interconnection details.
50
5285 941 v1.6
Page 51
Burner connection, Burner control wiring (VD2/VD2A/CT3 only)
For burners with plug-in connection
Installation
A
41
120 VAC
B
The burner cables are included in the standard delivery of the Vitotronic.
Connect the burner in accordance with applicable codes.
ATo boiler control unit BTo burner
Terminal codes
L1 Phase via fixed high limit to the
burner ? Ground connection N Neutral connection to the burner T1,T2 Control circuit S3 Connection for burner fault
indicator B4 Connection for burner hours
counter
1.Disconnect power to burner and boiler control.
2. Connect plugs fA and plug to respective counter plugs in boiler control unit.
3. Connect the 7-pole plug fA and the 3-pole plug to the burner.
Terminal codes
A To plug-in connection in connection
enclosure
B To burner
5285 941 v.1.6
1,2,3 Control circuit ”2nd stage
burner or modulation controller” (via two-point controller with 2-stage operation; via three­point controller with modulating
operation) 1 From burner 2 Modulating down 3 Modulating up/2nd stage ON
Colour codes as applicable
BK Black BN Brown BU Blue
51
Page 52
Installation
Burner Connection, Burner Control Wiring (VD2/VD2A/CT3 only)
CAUTION
This is a generic connection drawing only! Follow the burner manufacturer’s connection drawings for Viessmann controls.
Write the terminal numbers or markings on the drawing for future reference.
(continued)
a b
A Control unit
(Legend: see wiring diagram)
B 2nd stage or modulating * C Hours counter, stage 1 * D Burner fault indicator * E Control circuit, stage 1/
basic load *
F Burner
1
1
Plug connection located on the DIN rail.
Burner power supply not shown.
Power supply connection of control
1
1
unit 120 VAC
fA Burner, 1st stageBurner, 2nd stage
aBÖ Plugs for external equipment
a External safety devices (remove jumper when connecting) b External controlled switch-off (remove jumper when connecting)
aBA Safety circuit. Emergency
shut-off
*1Refer to burner manufacturer’s instruction on detailed connections for Viessmann controls.
52
5285 941 v1.6
Page 53
Installation
Burner Connection, Burner Control Wiring (VD2/VD2A/CT3 only)
Burner motor power supply connection
(continued)
See burner manual for correct fuse
For burners with 240 VAC, 1PH power supply and connection in conduit.
and wire gauge sizing, and specific connections for Viessmann controls.
1.Disconnect power to burner and
boiler control.
2.Connect 240 VAC power to the
terminals 21, 22 and 23 on the DIN rail inside the connection enclosure. Provide fuseable disconnect means according to local codes.
3.Connect supplied power cable to
the motor terminals on the burner.
4.Connect cable plug to the socket
on the DIN rail in the connection enclosure.
(continued)
A Burner motor power supply
240 VAC, 1PH
B Connection terminals and plug
inside connection enclosure
C Cable and conduit- factory supplied D Burner E Motor starter F Burner motor G Connection enclosure on boiler
control
5285 941 v1.6
53
Page 54
Installation
Burner Connection, Burner Control Wiring (VD2/VD2A/CT3 only)
Burner motor power supply connection
(continued)
For burners with 3PH 208, 460 or 575V power supply.
See burner manual for correct fuse and wire gauge sizing, and specific connections for Viessmann controls.
1.Disconnect power to burner and boiler control.
2.Connect 3PH power to the terminals 21, 22, 23 and 24 on the DIN rail inside the connection enclosure. Provide fuseable disconnect means according to local codes.
3.Connect supplied power cable to the motor terminals on the burner.
4.Connect cable plug to the socket on the DIN rail in the connection enclosure.
(continued)
A Burner motor power supply 3PH
208, 460 or 575V
B Connection terminals and plug
inside connection enclosure
C Cable and conduit - factory
supplied
D Burner E Motor starter F Overload G Burner motor H Connection enclosure
CAUTION
During commissioning check for correct motor rotation. If motor rotates in opposite direction than indicated on the burner, disconnect power supply and reverse wires BK1 and BK2 on the burner terminals.
54
5285 941 v1.6
Page 55
Power Supply Connection, Boiler Control (VD2/VD2A/CT3 only)
Installation
Legend
L: Line N: Neutral G: Ground A Power supply 120 VAC, 1 PH .
Provide disconnect means and overcurrent protection as per local
codes
B Terminals [40] C Connection enclosure
1. Ensure that the main power supply to the control contains overcurrent protection with a maximum rating of 15 A and 2 pole disconnect.
CAUTION
The control must be grounded. Ensure that “L”, “N” and “G” are not interchanged.
2. Connect power supply wire to the
Connection terminals 11, N and G on the DIN rail inside the connection enclosure.
5285 941 v1.6
55
Page 56
Installation
Burner Connection, Burner Control Wiring (CM2 only)
For burners with plug-in connection
A
B
The burner cables are included in the standard delivery of the Vitotronic.
Connect the burner in accordance with applicable codes.
ATo boiler control unit BTo burner interface
Terminal codes
L1 Phase via fixed high limit to the
burner ? Ground connection N Neutral connection to the burner T1,T2 Control circuit S3 Connection for burner fault
indicator B4 Connection for burner hours
counter
1.Disconnect power to burner and boiler control.
2. Connect plugs fA and plug to respective counter plugs in boiler control unit.
3. Connect the 7-pole plug fA and the 3-pole plug to the burner.
A
B
A To plug-in connection in connection
enclosure
B To burner interface
Terminal codes
1,2,3 Control circuit ”2nd stage
burner or modulation controller” (via two-point controller with 2-stage operation; via three-point controller with
modulating operation) 1 From burner 2 Modulating down 3 Modulating up/2nd stage ON
Colour codes as applicable
BK Black BN Brown BU Blue
5285 941 v1.6
56
Page 57
Mounting the Front Part of the Control Unit (VD2/VD2A/CT3 only)
1.
8.
1. Position the front part of the housing and clip hinges to counter-parts on main housing.
Installation
7.
2. Release the stay bar, open it up and lock in position at point A.
3. Insert the flat cable from the Optolink into plug ”X20”.
4. Insert the plug of the programming unit into socket ”X10”. Use cable guides in cover for routing.
5. Engage the stay bar in the front housing.
6. Close the front of the housing.
7. Secure front housing with supplied
screws.
8. Install cover of the connection enclosure and support with supplied screw.
2.
6.
A
5.
4.
3.
5285 941 v1.6
57
Page 58
Installation
Mounting the Front Part of the Control Unit (VD2/VD2A/CT3 only)
1.
8.
1. Position the front part of the housing and clip hinges to counter-parts on main housing.
7.
2. Release the stay bar, open it up and lock in position at point A.
3. Insert the flat cable from the Optolink into plug ”X20”.
4. Insert the plug of the programming unit into socket ”X10”. Use cable guides in cover for routing.
5. Engage the stay bar in the front housing.
6. Close the front of the housing.
7. Secure front housing with supplied
screws.
8. Install cover of the connection enclosure and support with supplied screw.
2.
6.
A
5.
4.
3.
58
5285 941 v1.6
Page 59
Opening the Control Unit (VD2/VD2A/CT3 only)
Installation
1. Remove the cover of the connection enclosure.
1.
2.
2. Unscrew the screws from the front housing.
3. Swing up the front part of the control housing.
4. Position the stay bar so that it supports the front housing.
4.
3.
5285 941 v1.6
59
Page 60
Installation
Control and Junction Box Installation Instructions (for CM2 only)
1. Route cables and capillaries from control through the opening in the control panel. Guide the cables to the junction box through the opening in the rear panel and along the top rail to the control. Secure all cables to the rail with cable ties. Insert capillaries into the sensor well. Note: Never allow cables to come
in contact with hot metal components.
WARNING
Do not bend or kink the capillaries. Damaging the capillaries leads to malfunction.
2. Mount the control to the control panel.
3. Secure the control to the control panel with screws. Note: Screws to secure control are
included with the cosmetic cover in the boiler jacketing package.
4. Install the junction box to the rear panel either right or left. Secure the junction box with 4 x 4.8 metal screws.
Note:The ground screw and ground
wire can be removed and then reinstalled with the boiler back panel attached.
60
5285 941 v1.6
Page 61
Mounting the Front Part of the Control Unit (CM2 only)
1. Position the front part of the housing
and clip hinges to counter-parts on main housing.
Installation
2. Release the stay bar, open it up
and lock in position at point A.
3. Insert the flat cable from the Optolink into plug ”X20”.
4. Insert the plug of the programming unit into socket ”X10”. Use cable guides in cover for routing.
5. Engage the stay bar in the front housing.
6. Close the front of the housing.
7. Secure front housing with supplied
screws.
8. Install control cosmetic cover.
A
5285 941 v1.6
61
Page 62
Installation
Opening the Control Unit (CM2 only)
1. Remove the control cosmetic
cover .
2. Unscrew the screws from the front housing.
3. Swing up the front part of the control housing.
4. Position the stay bar so that it supports the front housing.
62
5285 941 v1.6
Page 63
Procedure (overview)
Start-up
Page
11. Controls and indicators 64
12. Check assignment of heating circuits 64
13. Check the fixed high limit 65
14. Select the language (if required) 65
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15. Integrate the control unit in the LON BUS system
(in conjunction with heating circuits connected downstream) 66
16. Carry out participant check 67
17. Match the control unit to the system type 68
18. Check outputs (actuators) and sensors 68
19. Match the coding addresses 69
10. Adjust the heating curves 71
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5285 941 v.1.6
63
Page 64
Start-up
Steps
1. Controls and indicators
Kesseltemperatur
Mo
Override switch
Heating circuit selection
Display window
Normal room temperature
Heating programs
Adjustable high limit
Fixed high limit reset button
2. Check assignment of heating circuits
Boiler temperature
Mo
61
Control on/off switch
Fuses
TÜV TEST button
Energy saving mode
Party mode
Hinged cover of programming unit
Operating status indicator (green)
Fault indicator (red)
Check that the stickers for the assignment of the heating circuits are affixed in the appropriate locations on the control unit. The corresponding button must be pressed before commencing each setting.
64
5285 941 v.1.6
Page 65
Start-up
Steps
3. Check the fixed high limit
(continued)
The check is made via the ”TÜV TEST” button (see page 64).
When making the check, the ” TÜV TEST” button must be kept continuously pressed. A minimum supply is required during the check. The minimum amount of recirculated water should be 10% of the amount recirculated at the rated load. The amount of heat consumed should be reduced as far as possible. The adjustable high limit ”R” is bridged. The burner is switched on until the boiler water temperature reaches the safety temperature and the fixed high limit operates. When the burner is switched off by the fixed high limit, release the ”TÜV TEST” button, wait until the boiler water temperature has fallen 15 to 20°C / 27 to 36°F below the selected safety temperature and then reset the fixed high limit by pressing the ”E” button.
4. Select the language (if required)
Outdoor temp erature
12
5285 941 v.1.6
1. Press .
2. Select the required language with
.
3. Confirm with .
The outdoor temperature or the participant number is displayed.
65
Page 66
Start-up
Steps
5. Integrate the control unit in the LON BUS system in conjunction with Vitotronic 200-H
(continued)
User check
The LON communication module (accessory) must be inserted (see page 96).
Set the LON participant number
Set the LON participant number via coding address ”77” in coding 1 (factory setting: ”77: 1”).
Update the LON participant list
This is only possible when all participants are connected and the control unit is coded as the fault manager (coding ”79: 1”).
1. Press w and simultaneously for approx. 2 seconds.
2. Press D.
See page 114 for coding 1.
Please note:
The same number must not be assigned twice within a LON BUS system.
The participant check is initiated.
The participant list is updated after approx. 2 minutes. The participant check is terminated.
Example of single-boiler system with Vitotronic 200-H heating circuit controls and Vitocom 300 connected downstream
Vitotronic 300 Vitotronic 200-H Vitotronic 200-H Vitocom
LON LON LON
Participant No. 1 Coding ”77: 1”
Control unit is fault manager Coding ”79: 1”
Transmit time via LON Set coding ”7b: 1”
Transmit outdoor temperature via LON Coding ”97: 2”
Viessmann system number Coding “98: 1”
Fault monitoring LON-Participant Coding “9C: 20”
Participant No. 10 Coding ”77: 10”
Control unit is not fault manager Coding ”79: 0”
Time is received via LON Set coding ”81: 3”
Outdoor temperature is received via LON Set coding ”97: 1”
Viessmann system number Coding “98: 1”
Fault monitoring LON-Participant Coding “9C: 20”
Participant No. 11 Coding ”77: 11”
Control unit is not fault manager Coding ”79: 0”
Time is received via LON Set coding ”81: 3”
Outdoor temperature is received via LON Set coding ”97: 1”
Viessmann system number Coding “98: 1”
Fault monitoring LON-Participant Coding “9C: 20”
Participant No. 99
Unit is fault manager
Time is received via LON
66
5285 941 v.1.6
Page 67
Start-up
Steps
6. Carry out participant check
(continued)
User check
Participant check
The participant check is used to verify the communication of the system units connected to the fault manager. Requirements:
The control unit must be coded as the fault manager (coding ”79: 1”)The LON participant number must be coded in all control unitsThe participant list must be updated in the fault manager
1. Press w and simultaneously for approx. 2 seconds.
The participant check is initiated.
01 : 01
1
Anlagenschema
Cod. 1
Participant number Consecutive list number
2. Select the required participant with or .
3. Activate the check with . If communication between the two units is verified, ”Check OK” appears in the display. If communication is not verified,
”Check not OK” appears.
4. To check further participants,
follow the steps described in points 2 and 3.
5. Press w and simultaneously for approx. 2 seconds.
”Check” flashes until the check is completed. The display of the selected participant flashes for approx. 60 seconds.
Check the LON connection.
The participant check is terminated.
5285 941 v.1.6
67
Page 68
Start-up
Steps
7. Match the control unit to the system type
8. Check outputs (actuators) and sensors
(continued)
Relay test
Set the following coding addresses in Coding 2: ”00” System type ”02” Burner type ”03” Oil or gas-fired operation ”0C” Return temperature raising ”4C” Plug function ”4d” Plug sL function ”4E” Plug gS function
Carry out relay test
1. Press and simultaneously for
2. Select relay outputs with the or
See page 116 for coding 2.
Relay test is activated.
approx. 2 seconds.
button.
3. Press .
The following relay outputs can be selected depending on the system equipment installed:
Burner stage 1 ON
Burner stage 1 + 2 ON
Burner modulation open
Burner modulation neutral
Burner modulation closed
Output 20 ON
Output 29 ON
Output 52 open/closed/neutral
DHW tank pump ON
DHW circulation pump ON
Heating circuit pump (M2) ON
Relay test is terminated.
Mixing valve (M3) Closed
Central fault indicator ON
LED selector button ! illuminated.
LED selector button ! illuminated.
LED selector button ! illuminated.
LED selector button ? illuminated.
LED selector button § illuminated.
LED selector button ? illuminated.
68
Heating circuit pump (M3) ON
Mixing valve (M2) Open
Mixing valve (M2) Closed
Mixing valve (M3) Open
LED selector button ? illuminated.
LED selector button § illuminated.
LED selector button § illuminated.
All LEDs extinguished.
5285 941 v.1.6
Page 69
Start-up
Steps
(continued)
Relaistest
9. Match the coding addresses
Check sensors
1. Press .
Scanning of operating status information is activated
2. Scan actual temperatures with
(see page 77).
or .
3. Press .
Scanning is terminated.
Match control unit to modulating burner
Please note:
The burner must be adjusted. In order to achieve a wide modulation range, the minimum output should be set as low as possible (take chimney/flue system into account).
1. Start up the burner.
Burner mod. open
Burnermod. closed
Burner mod. open
2. Press and simultaneously for approx. 2 seconds.
3. With function Activate ”Burner mod. open” and wait until the actuating drive of the burner is at maximum output.
4. Establish the maximum burner out-put through the fuel consumption.
5. With function Activate ”Burner mod. closed” and measure the time it takes for the actuating drive of the burner to reach the minimum output.
6. Establish the minimum burner output (basic output) through the fuel consumption.
7. With function Activate ”Burner mod. open” and stop the actuating drive by pressing
after one-third of the time
measured in point 5.
The relay test is activated.
Make a note of the value.
Make a note of the value.
Make a note of the value.
5285 941 v.1.6
8. Establish the partial output through the fuel consumption.
9. Press .
Make a note of the value.
The relay test is terminated.
69
Page 70
Start-up
Steps
9. Match the coding addresses (continued)
(continued)
Address Setting of
05 the partial output (see point 8) as a percentage proportion of the
08 units and tens digits of the maximum output established in point
09 hundreds digit of the maximum output established in point 4: e.g.
0A the basic output (see point 6) as a percentage proportion of the
15 the operating time in seconds established in point 5
10. Set the established values in coding Level 1.
max. output; e.g. partial output: 170 kW max. output: 210 kW
170 kW 210 kW
4: e.g. max. output: 210 kW – here set: 10
max. output: 210 kW – here set: 2
max. output; e.g. basic output: 70 kW max. output: 210 kW
70 kW
210 kW
x100 % = 81 %
x100 % = 33 %
See page 114 for coding 1.
Please note:
You will find details of other possible settings in the sections entitled ”Coding 1” and ”Coding 2” (see page 114 and 116).
70
5285 941 v.1.6
Page 71
Start-up
Steps
(continued)
10. Adjust the heating curves
The heating curves represent the relationship between the outdoor temperature and the boiler water or supply temperature. Put simply: The lower the outdoor temperature, the higher the boiler water temperature. In turn, the room temperature is dependent on the boiler water temperature.
Slope
The slope of the heating curve is normally within the range marked
3.4
3.2
3.0
2.8
2.6
2.4
A for underfloor heating systemsB for modulating heating systems
2.2
2.0
1.8
1.6
1.4
1.2
C for heating systems with boiler
water temperatures over 75°C.
Factory settings:
Slope ”n= 1.4Shift ”N= 0
See conversion chart on the back of the manual for °F.
1.0
0.8
0.6
Boiler water
= flow temperature in °C
0.4
0.2
Outdoor temperature in °C
1. Set the desired room temperature
Desired room temperatures can be set separately for each heating circuit.
Normal room temperature
Reduced room temperature
Normal room temperature
Set the desired day temperature with
20
the set-point selector.
Reduced room temperature
14
Press tm to call up the desired night temperature; adjust the desired night
The value is automatically accepted after approx. 2 seconds.
temperature with the or button.
5285 941 v.1.6
Press to confirm the selected value.
The display changes and shows the boiler water temperature.
71
Page 72
Scanning service information
PressOKand+or
Overview of service levels
Function Button combination To exit Page
Temperatures, boiler coding cards and scans
Relay test Press 9 and “OK” simultaneously
Participant check (in conjunction with LON)
Operating status information Press
Service scan (if ”Service” flashing)
Adjustment of display contrast
Press 9 and rw simultaneously for approx. 2 seconds
for approx. 2 seconds
Press w and “OK” simultaneously for approx. 2 seconds
Press “OK” and “+” or
“OK” and “-” simultaneously
Press “OK”
Press “OK”
Press w and “OK” simultaneously for approx. 1 second
Press
Press “OK”
Display darkens Display brightens
73
68
66
77
74
–– ––
72
5285 941 v.1.6
Page 73
Temperatures, boiler coding cards and scans
Scanning service information
Outdoortemp.damped
-5
1. Press 9 and rw simultaneously for approx. 2 seconds.
2. Select the required data for scanning with the or button.
3. Press . Exit diagnosis level.
The following values can be scanned depending on the system equipment installed:
Damped outdoor temp.Current outdoor temp.
Output reduction %Desired boiler temp.Current boiler temp.
Sensor 17A, current value
Sensor 17B, current value
Max. flue gas temp.Current flue gas temp.
Access diagnosis level.
The damped outdoor temperature can be reset to the current outdoor temperature by pressing D.
Only displayed if sensor connected. Only displayed if sensor connected.
Only displayed if flue gas temperature sensor connected. The max. flue gas temperature can be reset to the current value by pressing D.
Desired DHW temp.Current DHW temp.Current DHW temp. 1Current DHW temp. 2
Desired supply temp.Current supply temp.
Desired room temp.Current room temp.
Boiler coding card
Scan 1Scan 2Scan 3Scan 4Scan 5
Scan 6
Scan 7
Only displayed if DHW tank temperature sensor connected. Only displayed if two DHW tank temperature sensors are connected.
Only displayed if supply temperature sensor connected.
Only displayed if remote control connected.
See overview of boiler coding cards on page 94.
See page 74 for scans 1 to 7.
Only in conjunction with LON communication module Only in conjunction with LON communication module
5285 941 v.1.6
73
Page 74
Scanning service information
Temperatures, boiler coding cards and scans
Scan 1
Scan 1
8
KM BUS participant
0
No participant connected
1
to
Number of participants
F
(e.g. remote control)
Burner type Coding
Single-stage 02: 0
0 1
2-stage 02: 1
2
Modulating 02: 2
88888
Free
Free
(continued)
System type System circuit A1 Mixing valve Mixing valve DHW Coding
circuit M2 circuit M3 tank
0 1 Yes 00: 11 0 2 Yes Yes 00: 12 0 3 Yes 00: 13 0 4 Yes Yes 00: 14 0 5 Yes Yes 00: 15 0 6 Yes Yes Yes 00: 16 0 7 Yes Yes 00: 17 0 8 Yes Yes Yes 00: 18 0 9 Yes Yes Yes 00: 19 1 0 Yes Yes Yes Yes 00: 10
74
5285 941 v.1.6
Page 75
Scanning service information
Temperatures, boiler coding cards and scans
Scan 2
Scan 2
88888
Software version
0
Plug-in adaptor for external safety equipment
to
F
Software version Extension kit for mixing valve circuit M3
0
to
0
to
F
F
Software version Control unit
8
0
to
F
Free
0
Software version
to
Extension kit for mixing valve circuit M2
F
Software version Programming unit of control unit
(continued)
Scan 3
Scan 3
0 1
5285 941 v.1.6
2
8
0 1
0
to
F
Operating mode of mixing valve circuit M2 Coding
Without remote control A0: 0
0 1
With Vitotrol 200 remote control A0: 1
2
0
to
Software version
F
Remote control for system circuit A1
Operating mode of system circuit A1 Coding
Without remote control A0: 0 With Vitotrol 200 remote control A0: 1 With Vitotrol 300 remote control A0: 2
With Vitotrol 300 remote control A0: 2
2
Software version Remote control for mixing valve circuit M2
88888
0
to
Software version
F
Remote control for mixing valve circuit M3
Operating mode of mixing valve circuit M3 Coding
Without remote control A0: 0 With Vitotrol 200 remote control A0: 1 With Vitotrol 300 remote control A0: 2
75
Page 76
Scanning service information
Scan5
Temperatures, boiler coding cards and scans
Scan 4
Scan 4 is not assigned.
Scan 5 only in conjunction with LON communication module
8
0
0
0
to
F
Scan 6 only in conjunction with LON communication module
0
to
F
to
F
Viessmann participant number
0
to
F
to
F
Subnet address/system number
88888
0
to
Node address
F
(continued)
Scan 6
0
to
Tool/Auto
F
SNVT configuration
Scan 7
Scan 7
8
0
to
0
to
F
F
Software version Communication coprocessor
0
Software version
to
F
Neuron chip
8
to
88888
LON participant
0 1
F
0
No participant connected
1
to
Number of participants
F
88888
0
to
F
76
0
to
Equipment identification code
F
Free
Free
Free
Free
5285 941 v.1.6
Page 77
Scanning operating status information
Scanning service information
Outdoor temp erature
12
1. Press .
2. Select the required operating status
data for scanning with the or button.
3. Press .
The following operating status information can be scanned depending on the system equipment installed:
Participant number
Holiday program
with date of departure and return
Holiday program activeOutdoor temperatureBoiler temperatureFlue gas temperature
Sensor 17ASensor 17BDHW temperature
DHW temperature 1DHW temperature 2Supply temperature
Burner hours run
– 1st stage burner – 2nd stage burner
Number of burner starts
Fuel consumption
Operating status scanning mode is activated.
Exit the operating status scanning mode.
Only displayed when LON communication module is installed. If holiday program has been entered. When the holiday program is activated.
Only displayed if flue gas temperature sensor is connected. Only displayed if sensor is connected. Only displayed if DHW tank temperature sensor is connected. Only displayed if two DHW tank temperature sensors are connected. Only displayed in conjunction with mixing valve circuits. Reset hours runs, number of burner starts and fuel consumption after carrying out maintenance. By pressing D, the values can be individually reset to zero. Only displayed if selected via coding addresses ”26” or ”29”.
5285 941 v.1.6
TimeDate1st stage burner ON/OFF2nd stage burner ON/OFFOutput 20 ON/OFFOutput 29 ON/OFFOutput 52 Open/ClosedDHW tank pump ON/OFFDHW pump ON/OFFHeating circuit pump ON/OFFMixing valve Open/ClosedDifferent languages
Position stated in %.
Position stated in %. Press to select the respective language as the permanent language for all displays.
77
Page 78
Scanning service information
Scanning and resetting the ”Service” display
When the limit values selected via coding addresses ”1F”, ”21” and ”23” (see page 120) are reached, the ”Service” display flashes on the programming unit.
Please note:
If a service is carried out before ”Service” is displayed, set the coding address ”24: 1” and then coding address ”24: 0”.
Service
MFlue gas temperature
220
Boiler temperature
61
°C
Press . Service scan is activated.
Scan the service messages with the
or button.
Press and confirm the display ”Acknowledge: Yes” by pressing
.
Press . Service scan is terminated.
The ”Service” display is extinguished.
Please note:
An acknowledged service message can be displayed again by pressing (for approx. 3 seconds).
78
After carrying out maintenance, reset coding ”24: 1” (see page 120) to ”24: 0”.
If necessary: After carrying out maintenance
Press .Reset burner hours run, number
of burner starts and fuel consumption.
Press .
If necessary: After carrying out maintenance Press and rw simultaneously
for approx. 4 seconds.
Reset ”Max. flue gas temp.” to
the current value by pressing D.
Press .
If coding address ”24” is not reset, the ”Service” display will re-appear at 07:00 hrs on Monday.
See ”Scanning operating status information” on page 77.
See ”Temperatures, boiler coding cards and scans” on page 74.
5285 941 v.1.6
Page 79
Troubleshooting steps
Troubleshooting
Diagnosis 1. Establish fault message or ascertain behaviour of system
2. Look for the corresponding cause of the fault in the diagnosis tables
Please note:
Retrieve fault codes from the fault memory
3. Establish the action required in the table
Correction 4. Correct the fault
5285 941 v.1.6
79
Page 80
Troubleshooting
Diagnosis
Faults with fault display on the programming unit
Fault
57
Fr
Fault
Mo
1
w A
57
ºC
Outdoor sensor
DBG-
1
101
Fault
DBG-
1
672
Acknowledge? Yes
1
Outdoor sensor
DBG-
1
101
When a fault message is transmitted,
--Fault-- flashes in the display 1 of the programming unit.
Search fault
1. Press .
2. Other fault codes which may be
stored can be called up by pressing the or button.
Structure of fault display
Fault display (”Plain language” or ”Fault”) Fault code (meaning: see page 70) Fault number (1 to 10) Fault symbol
The meaning of the fault code is explained in the table on page 81 onwards.
The fault can be acknowledged by pressing . The fault message in the display 1 is blanked out; the red fault indicator 2 continues to flash. The central fault indicator connected to plug is switched off. If an acknowledged fault is not rectified by 07:00 hrs on the following day, the fault message will re-appear in the display.
To retrieve an acknowledged fault message
Press for approx. 3 seconds; select the acknowledged fault by pressing the
or button.
The fault is then displayed
Please note:
The red fault indicator 2 flashes whenever there is a fault.
80
Faults displayed in plain language
BurnerFixed high limitSafety circuit, potential freeExt. faultOutdoor sensorSupply sensorBoiler sensorDHW tank temperature sensor 1
(or 2)
Sensor 17ASensor 17BRoom sensorFlue gas sensorParticipant fault
C1, C8, C9, CA, Cb Meaning: see table on page 84.
Only displayed if a second DHW tank temperature sensor is connected.
Only displayed if the control unit is coded as the fault manager.
5285 941 v.1.6
Page 81
Troubleshooting
Faultcode
Diagnosis
Faults with fault display on the programming unit (continued)
in display
0f
10
18
30
38
40
44
48
4c
50
51
58
59
5285 941 v.1.6
(continued)
Behaviour of system
Controlled operation Service required
Operates on basis of 0°C outdoor temperature
Operates on basis of 0°C outdoor temperature
Burner is switched on and off by the adjustable high limit
Burner is switched on and off by the adjustable high limit
Mixing valve is closed Short circuit
Mixing valve is closed Short circuit
Mixing valve is closed Open circuit
Mixing valve is closed Open circuit
DHW tank heating pump ON: Desired boiler temperature = desired DHW tank temperature, priority controls are cancelled. In conjunction with DHW tank heating system: DHW tank heating is switched on and off by DHW tank temperature sensor 2.
In conjunction with DHW tank loading system: DHW tank heating is switched on and off by DHW tank temperature sensor 1.
DHW tank loading pump ON: Desired boiler temperature = desired DHW tank temperature, priority controls are cancelled. In conjunction with DHW tank loading system: DHW tank heating is switched on and off by DHW tank temperature sensor 2.
In conjunction with DHW tank loading system: DHW tank heating is switched on and off by DHW tank temperature sensor 1.
Cause of fault Action
Carry out maintenance ”0F” is only displayed in the fault history
Short circuit Outdoor temperature sensor
Open circuit Outdoor temperature sensor
Short circuit Boiler temperature sensor
Open circuit Boiler temperature sensor
Supply temperature sensor of mixing valve circuit M2
Supply temperature sensor of mixing valve circuit M3
Supply temperature sensor of mixing valve circuit M2
Supply temperature sensor of mixing valve circuit M3
Short circuit DHW tank temperature sensor 1
Short circuit DHW tank temperature sensor 2
Open circuit DHW tank temperature sensor 1
Open circuit DHW tank temperature sensor 2
Please note:
After carrying out main-
tenance, set coding ”24: 0”.
Check outdoor temperature
sensor (see page 99)
Check outdoor temperature
sensor (see page 99)
Check boiler temperature
sensor (see page 101)
Check boiler temperature
sensor (see page 101)
Check supply temperature
sensor (see page 28)
Check supply temperature
sensor (see page 86)
Check supply temperature
sensor (see page 86)
Check supply temperature
sensor (see page 86)
Check DHW tank
temperature sensor
(see page 101)
Check DHW tank
temperature sensor
(see page 101)
Check DHW tank
temperature sensor (see
page 101)
Check DHW tank
temperature sensor (see
page 101)
81
Page 82
Troubleshooting
Faultcode
Diagnosis
Faults with fault display on the programming unit (continued)
in display
60
68
70
78
92
93
94
9a
9b
9c
9f
(continued)
Behaviour of system
Boiler with maximum temperatureNo output reductionReturn control open
Boiler with maximum temperatureNo output reductionReturn control open
Shunt pump ON continuously Short circuit
In conjunction with DHW tank loading system: Mixing valve of primary circuit closed. No domestic hot water heating
Shunt pump ON continuously
In conjunction with DHW tank loading system: Mixing valve of primary circuit closed. No domestic hot water heating
Controlled operation Only the solar control fault codes are displayed
Controlled operation Only the solar control fault codes are displayed
Controlled operation Only the solar control fault codes are displayed
Controlled operation Only the solar control fault codes are displayed
Controlled operation Only the solar control fault codes are displayed
Controlled operation Only the solar control fault codes are displayed
Controlled operation Only the solar control fault codes are displayed
Cause of fault Action
Short circuit Temperature sensor aJA
Open circuit Temperature sensor aJA
Temperature sensor aJB
Open circuit Temperature sensor aJB
Short circuit Collector temperature sensor S1 on the Vitosolic
Short circuit Temperature sensor S3 on the Vitosolic
Short circuit Collector temperature sensor S2 on the Vitosolic
Open circuit Collector temperature sensor S1 on the Vitosolic
Open circuit Temperature sensor S3 on the Vitosolic
Open circuit DHW tank temperature sensor S2 on the Vitosolic
Fault on solar control message will display if no fault code is assigned to the fault
Check temperature sensor (see page 102)
Check temperature sensor (see page 102)
Check temperature sensor (see page 102)
Check temperature sensor (see page 102)
Check sensor on the solar control
Check sensor on the solar control
Check sensor on the solar control
Check sensor on the solar control
Check sensor on the solar control
Check sensor on the solar control
Check the solar control
82
5285 941 v.1.6
Page 83
Troubleshooting
Faultcode
Diagnosis
Faults with fault display on the programming unit (continued)
in display
aa
ab
ac
b0
b1
b4
(continued)
Behaviour of system
Controlled operation Therm-Control configuration
Controlled operation, DHW tank may be cold
Controlled operation Return temperature raising
Controlled operation Short circuit
Controlled operation Communication fault
Emissions test mode Internal fault Check electronics board
Cause of fault Action
fault: plug aJA of Therm-Control temperature sensor not inserted
DHW tank loading system configuration fault: coding ”55: 3” is set, but plug aJB is not inserted and/ or coding ”4C: 1” and ”4E: 1” not set
configuration fault: coding ”0C: 1” is set, but plug aJA is not inserted and/or coding ”4E: 0” is not set
Flue gas temperature sensor
Programming unit
Insert plug aJA On Vitocrossal: Check that coding ”0d: 0” is set.
Insert plug aJB and check codings
Insert plug aJA and check codings
Check flue gas temperature sensor (see page 29)
Check connections, if necessary replace programming unit
b5 b6
b7
b8 ba
bc
bd
be
bf
Controlled operation Internal fault Check electronics board
Operation at constant temperature
Boiler controlled on basis of adjustable high limit
Controlled operation Open circuit
Mixing valve continues in control mode
Controlled operation without remote control
Controlled operation without remote control
Controlled operation without remote control
Controlled operation Incorrect LON communication module Replace communication
Invalid hardware code
Internal fault Boiler coding card
Flue gas temperature sensor Communication fault
Circuit board for mixing valve extension
Communication fault Vitotrol remote control, system circuit A1
Communication fault Vitotrol remote control, mixing valve circuit M2
Communication fault Vitotrol remote control, mixing valve circuit M3
Check the control software circuit board and confirm the coding address:
- Enter coding 2 (see page 125 for instructions).
- Change code 8A to 176.
- Confirm coding 92:1
Insert boiler coding card or replace if defective (see page 22)
Check flue gas temperature sensor (see page 104)
Check circuit board
Check connections, cable and coding address ”A0” (see Coding 2 page 127)
Check connections, cable and coding address ”A0” see Coding 2 page 127
Check connections, cable and coding address ”A0” see Coding 2 page 127
module
65
5285 941 v.1.6
83
Page 84
Troubleshooting
Faultcode
toDE3
Diagnosis
Faults with fault display on the programming unit (continued)
in display
c1
c2
c4
c8
c9
ca
cb
cd
cEe
cf
d1
(continued)
Behaviour of system
Boiler cools down External safety equipment Check connection of plug
Controlled operation Open circuit
Controlled operation Fault
Boiler cools down Fault
Boiler cools down Fault
Boiler cools down Fault
Boiler cools down Fault
Controlled operation Communication fault
Controlled operation Communication fault
Controlled operation Fault
Boiler cools down Burner fault Check burner
Cause of fault Action
KM-BUS to solar control
Input module 0-10V
Low water indicator
Maximum pressure limiter
Minimum pressure limiter or maximum pressure limiter 2
Additional fixed high limit
Vitocom 300
Plug-in adaptor for external safety equipment
LON communication module
aBÖ
Check external safety
equipment (see page 40)
Check KM-BUS connection and solar control. Without solar control, set coding address “54: 0”
Check all connections, cables etc. Replace function expansion module; without expansion module set coding address “9d: 0”
Check water level of system, reset low water indicator
Check system pressure, reset maximum pressure limiter
Check system pressure, reset minimum or maximum pressure limiter
Check system pressure, reset fixed high limit, reset flue gas damper
Check connections and Vitocom 300
Check plug-in adaptor for external safety equipment
Replace communication module
d4 d6
d7
d8
da
db
84
Boiler cools down Fixed high limit has operated Check fixed high limit
Controlled operation Fault at DE1 in the plug-in
Controlled operation Fault at DE2 in the plug-in
Controlled operation Fault at DE3 in the plug-in
Controlled operation without influence of room temperature
Controlled operation without influence of room temperature
adaptor for external safety equipment
adaptor for external safety equipment
adaptor for external safety equipment Short circuit
Room temperature sensor, system circuit A1
Short circuit Room temperature sensor, mixing valve circuit M2
Check connection at inputs DE1 to DE3
Check room temperature sensor (see page 112)
Check room temperature sensor (see page 112)
5285 941 v.1.6
Page 85
Troubleshooting
Faultcode
Diagnosis
Faults with fault display on the programming unit (continued)
in display
dc
dd
de
df
e0
(continued)
Behaviour of system
Controlled operation without influence of room temperature
Controlled operation without influence of room temperature
Controlled operation without influence of room temperature
Controlled operation without influence of room temperature
Controlled operation Open circuit
Cause of fault Action
Short circuit Room temperature sensor, mixing valve circuit M3
Open circuit Room temperature sensor, system circuit A1
Open circuit Room temperature sensor, mixing valve circuit M2
Open circuit Room temperature sensor, mixing valve circuit M3
LON communication module
Check room temperature sensor (see page 112)
Check room temperature sensor (see page 112)
Check room temperature sensor (see page 112)
Check room temperature sensor (see page 112)
Check connection (see page 96)
Retrieving fault codes from the fault memory (fault history)
All faults which have occurred are stored and can be retrieved by scanning. The scanning sequence starts with the most recently stored fault code.
1 23 4 5 67
1. Press and simultaneously for approx. 2 seconds.
2. Access the individual fault codes by pressing the or button.
Sequence of stored fault codes
1
. . .
10
Fault code
Last (most recent) fault code
. . .
Last fault code but nine
Scanning of fault history is activated.
All stored fault codes can be deleted by pressing .
5285 941 v.1.6
3. Press .
Scanning of fault history is terminated.
85
Page 86
Functional description
Boiler temperature control
Brief description
The boiler water temperature is controlled by switching the burner stages or modulation on and off. The desired boiler water temperature value is determined by the set-point supply temperature value of the boiler circuit (A1), the mixing valve circuits or the heating circuits connected via the LON BUS, through the external request facility and the desired domestic hot water temperature, and is dependent on the boiler and the heating and control facilities installed. In conjunction with Therm-Control: The desired boiler water temperature is increased when the temperature falls below the set-point value on the sensor of the Therm-Control.
Functions
The boiler water temperature is measured via a multiple sensor well by three sensors separately: Fixed high limit FHL (liquid
expansion)
Adjustable high limit AHL (liquid
expansion)
Boiler temperature sensor BTS
(change in resistance PT 500)
When the domestic hot water tank is heated up, a desired boiler water temperature is selected which is 20°C / 36°F higher than the desired DHW tank water temperature (this value can be changed via coding address ”60”).
Upper limits of control range
Fixed high limit FHL 110°C / 230°F,
can be adjusted to 99°C / 210°F
Adjustable high limit AHL 95°C, can
be adjusted to 100°C / 212°F
Electronic maximum limit
Setting range: 20 to 127°C / 68 to 261°F The maximum limit for the boiler water temperature is defined in coding address ”06”.
Coding addresses which influence the boiler temperature control
02 to 06, 08 to 0b, 13 to 1C See page 114 onwards for description.
Lower limit of control range
The control unit regulates the
boiler water temperature in normal operation and in the frost protection mode according to the boiler concerned (boiler coding card).
Control sequence
Boiler temperature falls
The burner switch-on signal is set for a boiler water temperature set-point value of –2°C / -4°F, and the burner starts its own monitoring program. Depending on the range of additional control facilities and the method of firing, burner override can be delayed by a few minutes.
86
Boiler temperature rises
The switch-off point of the burner is defined by the switch-off differential (coding address ”13”).
5285 941 v.1.6
Page 87
Heating circuit control
Brief description
Functional description
The control unit has control loops for a system circuit and two mixing valve circuits.
The supply temperature set-point value is determined by the outdoor temperature, the desired room temperature, the operating mode and the heating curve.
Functions
The heating circuit is dependent on the boiler water temperature and its control range limits. The only control element is the heating circuit pump. The supply temperature of the mixing valve circuits is measured by the supply temperature sensor (contact sensor).
Time program
The timer of the control unit changes the operating mode at the programmed times in the ”Central heating and DHW” heating program, switching between ”Central heating with normal room temperature” and ”Central heating with reduced room temperature”. Each operating mode has its own set-point value.
Outdoor temperature
A heating curve must be adjusted to match the control unit to the building and the heating system. The heating curve determines the set-point boiler water temperature value as a function of the outdoor temperature. Control takes place on the basis of the mean outdoor temperature. This is derived from the actual and the damped outdoor temperature. The heating curve can be changed via the set-point or operating mode selector switches.
The supply temperature of the mixing valve circuits is controlled by opening and closing the mixing valves in steps. The mixing valve motor control varies the actuation and interval times as a function of the control difference (control deviation).
Domestic hot water temperature
With priority control:
While the DHW tank is being heated, the set-point supply temperature value is set to 0°C / 32°F . The heating circuit pump is switched off.
Without priority control:
The heating circuit control continues to operate as normal with the set-point value unchanged.
With modulating priority control
(only in conjunction with mixing valve circuit): The heating circuit pump remains switched on. The set-point supply temperature of the heating circuit is lowered as long as the set-point boiler water temperature is not reached while the DHW tank is being heated. The set-point supply temperature is dependent on the difference between the set-point and the current boiler water temperature, the outdoor temperature, the heating curve slope and the setting of the coding address ”A2”.
The supply temperature of the system circuit corresponds to the boiler water temperature.
Coding addresses which influence the heating circuit control
9F A2 to A7, A9, C4 to C7, C8 F1, F2. See page 114 onwards for description.
Room temperature
In conjunction with room temperature dependent control:
Compared with the outdoor temperature, the room temperature has a greater influence on the set-point boiler water temperature. The magnitude of this influence can be changed via coding address ”b2”. In conjunction with mixing valve circuit: With control differences (i.e. deviations from the current value) of over 2°C / 4°F room temperature, this influence can be intensified (via coding address ”b6”, rapid heating/setback).
5285 941 v.1.6
87
Page 88
Functional description
Heating circuit control
Functions (continued)
Summer energy saving function (heating circuit pump logic)
If the outdoor temperature is higher than the preset room temperature set-point value, the heating circuit pump is switched off and the set-point supply temperature value is set to 0°C / 32°F. The switching threshold can be individually selected via coding address ”A5”.
Extended summer energy saving function
The heating circuit pump can be switched off If the outdoor temperature exceeds a
value preselected via coding address ”A6”
If the set-point room temperature is
reduced via coding address ”A9”
In conjunction with mixing valve
circuit: If the mixing valve has been closed for longer than 12 minutes (mixing valve energy saving function, coding address ”A7”)
Slab curing function
(only in conjunction with mixing valve circuit)
(continued)
System dynamics – mixing valve circuit (only in conjunction with
mixing valve circuit)
The control behaviour of the mixing valve can be influenced via coding address ”C4”.
Frost protection
A supply temperature of 15 to 22°C / 59 to 72°F is assured for outdoor temperatures below +1°C / 34°F (two-point control). For possible changes, see coding address ”A3” (variable frost threshold).
Therm-Control
Heating circuit output reduction takes place if the boiler return temperature falls below the setpoint value (value read on the therm-control sensor). Heating circuit mixing valves modulate closed until the Therm-control sensor is satified.
Supply temperature control
Differential temperature: The differential temperature can be selected via coding address ”9F”, factory setting: 8°C / 14°F.
The differential temperature is the minimum difference by which the boiler water temperature should exceed the highest currently required supply temperature of the mixing valve circuit.
System with only one mixing
valve circuit: The desired boiler water temperature is automatically controlled at 8°C / 14°F above the desired supply temperature value.
System with heating circuit and
mixing valve circuit: The desired boiler water temperature is controlled according to its own heating curve. The temperature difference of 8°C / 14°F. from the desired supply temperature is preset in the factory.
Please note:
The slab curing function is selectable on the basis of four different temperature curves. The curves are activated via coding address ”F1” (see page 134).
When the slab curing function is activated, the heating circuit pump of the mixing valve circuit is switched on and the supply temperature is controlled according to the selected curve. When the slab curing time (30 days) has expired, the mixing valve circuit is automatically controlled on the basis of the preset parameters.
88
Boiler water temperature/
supply temperature in °C
Outdoor temperature in °C
A Max. boiler water temperature B Slope = 1.8 Heating circuit C Slope = 1.2 Mixing valve circuit
D Boiler water temperature
(with differential temperature = 8°C / 14°F.)
E Minimum boiler water
temperature
5285 941 v.1.6
Page 89
Functional description
Heating circuit control
Functions (continued)
Upper limit of control range
Electronic maximum limit Setting range: 1 to 127°C / 34 to 260°F. Change via coding address ”C6”.
Please note:
The maximum limit does not replace the limit thermostat required for underfloor heating systems.
Limit thermostat for underfloor heating systems: The limit thermostat switches the heating circuit pump off when the supply temperature rises above the preset value. In this situation, the supply temperature cools down only slowly, i.e. automatic re-starting can take several hours.
(continued)
Lower limit of control range
Electronic minimum limit Setting range: 1 to 127°C / 34 to 261°F. Change via coding address ”C5”.
Control sequence
Mixing valve circuit
The mixing valve motor is not activated within the ”neutral zone” (±1°C / 2°F).
Supply temperature falls
(Set-point value –1°C / -2°F) The mixing valve motor receives the signal ”Open mixing valve”. The greater the control difference, the longer the duration of the signal and the shorter the duration of the intervals.
Supply temperature rises
(Set-point value +1°C / +2°F): The mixing valve motor receives the signal ”Close mixing valve”. The greater the control difference, the longer the duration of the signal and the shorter the duration of the intervals.
5285 941 v.1.6
89
Page 90
Functional description
DHW tank temperature control
Brief description
The DHW tank temperature control is a constant value control. It operates on the basis of switching the circulation pump for heating the DHW tank on and off. The switching differential is ±2.5°C /
4.5°F.
Functions
Time program
An automatic or an individual time program can be selected for domestic hot water heating and the DHW circulation pump. In the automatic program, domestic hot water heating precedes the heat-up phase of the heating circuit by 30 minutes. On systems with several heating circuits, the time program is based on the switching times of the first heating circuit to be heated. In the individual time program, up to four switching times per day can be set on the timer for domestic hot water heating and the DHW circulation pump. Once started, heating of the DHW tank is always completed regardless of the time program. The switching times for domestic hot water heating and the DHW circulation pump are effective for all heating circuits. Individual switching times can be assigned to each heating circuit via the coding address ”7F”.
During DHW tank heating, a constant maximum boiler water temperature is set and space heating is switched off (DHW tank priority control optional).
Frost protection function
If the domestic hot water temperature falls below 10°C / 50°F, the domestic hot water DHW tank is heated to 20°C / 68°F.
Additional function for domestic hot water heating
This function is activated when a second DHW setpoint value is selected via coding address ”58” and the 4th activation period for domestic hot water heating is activated.
Desired domestic hot water temperature
The desired domestic hot water temperature can be set in the range of 10 to 60°C / 50 to 140°F. The set-point range can be extended to 95°C / 203°F via coding address ”56”. The desired domestic hot water temperature can be set on the programming unit of the control unit and on the Vitotrol 300 remote control (if installed). The set-point value can be assigned via coding address ”66”.
Coding addresses which influence the DHW tank temperature control
55, 56, 58 to 62, 64, 66, 70 to 75, 7F, A2. See page 114 onwards for description.
DHW circulation pump
The DHW circulation pump supplies hot water to the take-off points at selectable times. Up to four switching times can be set on the timer.
Additional control facilities
The domestic hot water supply can be blocked and released via changeover of the heating program.
System with DHW tank loading system
The functions described above also apply in conjunction with DHW tank loading systems.
Set the following codings: ”4C: 1”, ”4E: 1”, ”55: 3”.
90
5285 941 v.1.6
Page 91
Functional description
DHW tank temperature control
Control sequence
DHW tank temperature falls
(Set-point value –2.5 °C / 4.5 °F,
selectable via coding address ”59”) The desired boiler water temperature is set 20 K higher than the DHW temperature set-point value (selectable via coding address ”60”).
The circulation pump for heating the DHW tank is switched on immediately (Coding ”61: 01”).
Boiler temperature-dependent switching of the circulation pump for heating the DHW tank (Coding ”61: 00”): The circulation pump is switched on when the boiler water temperature is 7°C / 13°F higher than the domestic hot water temperature.
With priority control:
(Coding ”A2: 2”) The supply temperature set-point value is set to 0 °C / 32°F when the DHW tank is being heated. The mixing valve is closed and the heating circuit pump is switched off.
Without priority control:
The heating circuit control continues to operate as normal with the setpoint value unchanged.
With modulating priority control (only
in conjunction with mixing valve circuit): The heating circuit pump remains switched on. The desired supply temperature is lowered as long as the desired boiler water temperature is not reached while the DHW tank is being heated. The desired supply temperature is dependent on the difference between the desired and the current boiler water temperature, the outdoor temperature, the heating curve slope and the setting of the coding address ”A2”.
5285 941 v.1.6
DHW tank temperature rises
(Set-point value +2.5 / 4.5°F) The boiler water temperature set-point value is reset to the weather­compensated value.
When the DHW tank has been
Circulation pump for heating the
With priority control
With optimized DHW tank heating
(continued)
heated up, the circulation pump for heating the DHW tank continues to run until: the temperature difference between
the boiler water and domestic hot water is less than 7°C / 13°F, or
the desired, weather-compensated
boiler water temperature is reached, or
the desired domestic hot water
temperature is exceeded by
5°C / 9 °F. The max. run-on time is 15 minutes (selectable via coding address ”62”).
DHW tank without run-on time (Coding ”62: 00”): The circulation pump is switched off immediately.
(Coding ”A2: 2”): The supply temperature set-point value is reset to the weather­compensated value. The heating circuit pump is switched on.
(Coding ”55: 1”): Optimized DHW tank heating takes into account the rate at which the temperature increases during domestic hot water heating. It also takes into account whether the boiler must supply heat for space heating purposes after heating up the DHW tank or whether the residual heat of the boiler should be transferred to the domestic hot water DHW tank. The control unit determines the switch-off time of the burner and the circulation pump accordingly so that the desired domestic hot water temperature is not substantially exceeded after DHW tank heating is completed.
91
Page 92
Additional information
Overview
Page
Technical data 93
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System components
Line-voltage motherboard 94 Low-voltage motherboard 94 Power supply unit board 94 Electronics board 94
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mixing valve extension circuit board 95 Electronics board for mixing valve extension 95 Optolink/emissions test switch board 95 Programming unit 95
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Front panel with heating circuit selector buttons 96 Fuse box 96
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LON communication module 96 Boiler coding card 97 Fuses 97
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TEST button 97 Fixed high limit 98
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjustable high limit 98 Outdoor temperature sensor 99 Boiler temperature sensor and DHW tank temperature sensor 101 Strap-on temperature sensor/immersion temperature sensor 102 Flue gas temperature sensor 104 Installation examples 105 Vitotrol 200 106 Vitotrol 300 108
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection of two or more remote controls 110 Room temperature sensor 112 Input Module 0 to 10V 113
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coding 1
Call up coding level 1 114 Codings 114
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coding 2
Call up coding level 2 116 Reset codings to factory settings 116 Overview of all codings 116
Wiring diagram 135
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
92
5285 941 v.1.6
Page 93
Technical data
Additional information
Rated voltage: 120V Rated frequency: 60 Hz Rated current: 2 x 6A Power consumption: 10W Protection class: I Degree of IP 20 D to protection: EN 60 529, to be
guaranteed by
mounting/integration Method of Type 1B to operation: EN 60 730-1
Ambient temperature
During
operation: 0 to 40°C /
32 to 104°F For use in boiler rooms (normal ambient conditions)
During storage and
transport: –20 to 65˚C /
-4 to 149°F
Relay outputs at 120V for Heating circuit
pumps or control output : 2 FLA, 120 VAC
Circulation
pump for heat­ing the DHW tank sA: 2 FLA, 120 VAC
DHW circulation
pump sK: 2 FLA, 120 VAC
Shunt
pump sL: 2 FLA, 120 VAC
Central fault
indicator : 2 FLA, 120 VAC
Mixing valve
motor return temperature raising or 3-way valve DHW tank heating system or mixing valve motor gS: 0.1 FLA,
120 VAC
*1
Burner
plug fA: 4 FLA, 120 VAC plug : – 2-stage 0.5 FLA 120 V~ – modulating 0.1 FLA 120 V~
*1
*1
*1
*1
*1
1
*
Total max. 6 A 120V
5285 941 v.1.6
93
Page 94
Additional information
System components
Line voltage motherboard, Part No. 7165 782
Low-voltage motherboard, Part No. 7820 290
The motherboard contains: Relays and outputs for activating
the pumps, the control elements and the burner
Plug-in location for power supply
unit board and boiler control section
The motherboard contains: Plugs for sensors, communication
connections and external equipment
Plug-in locations for electronics
board, LON communication module, programming unit, boiler coding card and Optolink board
Power supply unit board, Part No. 7823 991
Electronics board, Part No. 7828 193
The power supply unit board contains the low-voltage supply for the entire electronics.
The board contains the microprocessor with the software
When replacing the board:
1. Make a note of codings and settings on the control unit.
2. Replace the board.
3. Set coding ”8A: 176” and set
coding address ”92” (not listed in the overview) to ”92: 165”.
94
5285 941 v.1.6
Page 95
Additional information
System components
Mixing valve extension board, Part No. 7820 193
Electronics board, Part No. 7829 790
(continued)
The board contains the relays for activating the mixing valve motor and the heating circuit pump of the mixing valve circuits M2 and M3.
This is connected to the mixing valve extension board.
All data are processed and the outputs (relays) activated.
Optolink/emissions test switch board, Part No. 7820 165
The circuit board contains:
Operating status indicatorFault indicatorOptolink laptop interfaceEmissions test switch
Programming unit, Part No. 7823 986
Emissions test switch for flue gas measurements with the boiler operated with constant boiler water temperature for a short time. The burner is switched on
(this can be delayed if the system incorporates a fuel preheater)
all pumps are switched onthe mixing valve remains in its
control mode
the boiler water temperature is
controlled by the adjustable high limit ”R”.
The programming unit is inserted in the control unit.
For setting:
Heating programSet-point valuesSwitching timesHeating curve (shift and slope)DateTimeEnergy saving and party mode
5285 941 v.1.6
For displaying:
TemperaturesOperating status informationFaults
95
Page 96
Additional information
System components
Front panel with heating circuit selector buttons, Part No. 7818 623
Fuse box, Part No. 7820 172
(continued)
For displaying and selecting the heating circuit.
The fuse box contains:
Fixed high limitAdjustable high limitFusesHeating system switchTEST button
LON communication module, Part No. 7172 173 Accessory
A
LON
LON
C
A Control unit or Vitocom 300 B Connecting cable for data transfer
between the control units (accessory)
C Terminal resistor,
Part No. 7143 497
A A
LON
B
LON
B
LON
C
The communication module is inserted in the control unit. Interruption of communication is indicated.
LON
1 terminal resistor is inserted on each of the first and last control units.
96
5285 941 v.1.6
Page 97
Additional information
System components
Boiler coding card
Fuses
F1
(continued)
Vitotronic 300 in conjunction with
Vitorond 200 1020 7820 142 Vitocrossal 300, Type CT3 1040 7820 144 Vitocrossal 200, Type CM2 1041 7820 145
Boiler coding card Part No.
F1: 6.3 A, 250 V for protecting the control elements, pumps and electronics Mounting location: see drawing Part No. 7404 365
F2: 6.3 A, 250 V for protecting the burner Mounting location: see drawing Part No. 7404 365
F2
TEST button, Part No. 7819 314
For checking the fixed high limit. See description on page 65.
5285 941 v.1.6
97
Page 98
Additional information
System components
Fixed high limit, Part No. 7820 036
Adjustable high limit, Part No. 7817 531
(continued)
The fixed high limit has a factory setting of 110°C/ 230°F.Electromechanical temperature switch based on the liquid expansion principle
with interlock
Intrinsically safe; interlocking also takes place if the capillary tube is leaking or
if ambient temperatures are below –10°C / 14°F
Limits the boiler water temperature to the maximum permissible value by
cutting out and interlocking
Can be adjusted with the slotted screw A at the rear of the unit to 99°C /
210°F (cannot be reset to 110°C / 230°F once adjusted)
Reset unit by pressing the reset button ”E” on the front of the programming
unit if the temperature has fallen approx. 15 K below the shut down temperature
Central fastening M 10, capillary 3600 mm longTests:
Functional check via TÜV TEST button
The adjustable high limit has a factory setting of 95°C / 203°FElectromechanical temperature switch based on the liquid expansion principleControls the maximum boiler water temperature (e.g. in emissions test mode)Can be adjusted to 100°C / 212°F by altering the setting
of the stop dial or by removing the cams
IMPORTANT
Set the lower limit at least 20°C / 36°F higher than the domestic hot water temperature, the upper limit at least 15°C / 27°F lower than the fixed high limit.
Adjusting shaft 6 mm / 0.27 inches,
flat topped Adjusting knob pushed onto shaft from front
Capillary 3600 mm / 141.7 inches long
Sensor 3 mm / 0.1inches thick, 180 mm / 7.1inches long
Tests:
Functional check via emissions test mode
98
5285 941 v.1.6
Page 99
Additional information
System components
(continued)
Outdoor temperature sensor, Part No. 7820 148
Outdoor temperature sensor
600
580
560
540
520
500
480
Resistance in
460
Connection
Check sensor
1. Remove plug !.
2. Check the sensor resistance at
terminals 1 and 2 of the plug.
Outdoor temperature in
Resistance in ΩΩΩ
ºC / ºF
–10 / 14
0 / 32
20 / 68
480 500 546
3. Disconnect cores from the sensor, if actual values deviate severely from the curve, repeat the sensor measurement and compare with the actual temperature.
440
420
400
-40 -30 -20 -10 0 10 20 30
-40 -22 -4 14 32 50 68 86
Outdoor temperature in ºC / ºF
4. Depending on the result, replace cable or outdoor temperature sensor.
5. Scan actual temperature.
Specification
Protection: IP 43 Permissible ambient temperature during operation, storage and transport:
–40 to +70ºC –40 to 158ºF
5285 941 v.1.6
99
Page 100
Additional information
System components
Outdoor temperature sensor
1.
4.
(continued)
The outdoor temperature sensor should be mounted 2 to 2.5 metres / 6.5 to 8 ft above ground level on the north or north-west facing wall of the building. In the case of multi-storey buildings, it should be mounted in the upper half of the second storey. Make sure that the sensor is not located over windows, doors and air vents, nor immediately beneath a balcony or guttering. Do not paint over the outdoor temperature sensor housing.
5.
3.
1. Remove the cap.
2. Mount the bottom part of the
sensor housing.
3. Pull the sensor wire through the opening in the terminal compartment and through the strain relief provided.
4. Connect the wires to the terminals.
5. Place the cap over the outdoor temperature sensor.
A
2.
WARNING
When extending wire, there is the possibility of exposure to electromagnetic interference. Avoid running wires beside or near high voltage 120/240 VAC conductors. If proximity to high voltage conductors cannot be avoided, use stranded, twisted pair or shield design wire. Ensure that only one end of the shielding is grounded.
A Outdoor temperature sensor
1
100
5285 941 v.1.6
Loading...