Outdoor-reset logic digital boiler and
heating circuit control unit
Please file in Service Binder
VITOTRONIC 300
Certified as a component part
of Viessmann boilers only
5285 941 v1.6 12/2012
IMPORTANT
Read and save these instructions
for future reference.
1
Page 2
General information
Safety, Installation and Warranty Requirements
Please ensure that this manual is read and understood before commencing installation. Failure to comply with the issues
listed below and details printed in this manual can cause product/property damage, and/or severe personal injury. Ensure all
requirements below are understood and fulfilled (including detailed information found in manual subsections).
Licensed professional heating
contractor
The installation, adjustment, service,
and maintenance of this equipment
must be performed by a licensed
professional heating contractor.
Please see section
entitled “Important
Regulatory and
Installation
Requirements.”
Product documentation
Read all applicable documentation
before commencing installation. Store
documentation near boiler in a readily
accessible location for reference in the
future by service personnel.
For a listing of
applicable literature,
please see section
entitled “Important
Regulatory and
Installation Requirements.”
Advice to owner
Once the installation work is complete,
the heating contractor must familiarize
the system operator/ultimate owner
with all equipment, as well as safety
precautions/requirements, shut-down
procedure, and the need for
professional service annually before
the heating season begins.
Warranty
Information contained in
this and related product
documentation must be
read and followed. Failure
to do so renders warranty
null and void.
Safety Terminology
The following terms are used throughout this manual to bring attention to the presence of potential hazards or important
product information. Please heed the advice given!
DANGER
Indicates an imminently hazardous
situation which, if not avoided, will
result in death, serious injury or
substantial product / property damage.
2
WARNING
Indicates an imminently hazardous
situation which, if not avoided, could
result in substantial product/property
damage, serious injury or loss of life.
WARNING
Indicates an imminently hazardous
situation which, if not avoided, may
result in minor injury or product /
property damage.
IMPORTANT
Helpful hints for installation,
operation or maintenance which
pertain to the product.
5285 941 v.1.6
Page 3
Product Information
Vitotronic 300, Model GW2
For installation in or mounting on
Viessmann boilers only.
Applicable to the following control
units
Order No. 7134 555, 7143 156, 7511 362 from
Serial No. 7143 000
Order No. 7134 555, 7143 156, 7511 362 from
Serial No. 7187 101
Order No. 7134 555, 7143 156, 7511 362 from
Serial No. 7248 248
lÖBurner (2nd stage/modulating)
aVDConnection of external
equipment (see page 38)
aVHConnection of external
equipment (see page 39)
5285 941 v.1.6
Page 7
Heating system types
Heating system types for modulating boilers
Possible applications
Heating systems with manifold
arranged close to the boiler. The boiler
water flow is required to be reduced.
Please note:
This circuit diagram represents a
recommendation only. It is the
responsibility of the customer and/or
the heating contractor to check that
this recommendation is complete and
fully functional. Three-phase equipment
must be connected via additional
power contactors.
When the return temperature falls
below the required minimum value,
the temperature sensor T2 switches
on the shunt pump. If the minimum
return temperature is not reached
despite raising the return temperature,
the flow must be reduced by at least
50% via the temperature sensor T1.
The shunt pump must be sized so that
bypassed water accounts for approx.
30% of the total flow rate of the
boiler.
(continued)
Temperature sensor T1
Wiring of the temperature sensor
T1 in heating systems with heating
circuit control units which are not
connected via the LON BUS to the
boiler control unit.
Coding required: ”4C : 2” – use
plug sÖ for closing the mixing
valves of the heating circuits
connected downstream.
sÖ A1 Close mixing valves
AContactor relay, field supplied
BHeating circuit controls
connected downstream
Switch contact closed: signal
for ”close mixing valve”.
Available system accessories
Vitotrol remote control
Flue gas temperature sensor
Coding of
system type
00: 1If no system circuit A1 is connected, set
02: 1Set coding ”02: 2” for operation with
03: 0Set coding ”03: 1” for oil-fired operation
4A: 0––Connection of the temperature sensor T1 at
4b: 0––Connection of the temperature sensor T2 at
Change requiredAutomatic change
The system type is recognized automatically
coding ”00: 3”, ”00: 4”, ”00: 7” or ”00: 8”
(see page 101)
modulating burner
(re-setting is not possible)
when the sensors are connected
plug aJA;
Coding ”4A: 1” is set automatically
plug aJB;
Coding ”4b: 1” is set automatically
––
––
5285 941 v.1.6
7
Page 8
Heating system types
Circuit Diagram 1
Single-boiler system with Therm-Control and three-way mixing valve
in conjunction with Vitorond 200, VD2A
A Heating circuit with mixing valves
B DHW tank
Plug
!Outdoor temperature sensor
?M2Flow temperature sensor,
mixing valve
?M3Flow temperature sensor,
mixing valve
§Boiler water temperature
sensor
%DHW tank temperature sensor
aJATherm-Control temperature
sensor
8
sÖM2Heating circuit pump, mixing
valve
sÖM3Heating circuit pump, mixing
valve
sÖA1Closing the mixing valves with
external heating circuit control
units
sADHW primary pump
sKDHW circulation pump
fÖPower supply, 120 VAC
60 Hz
Install the main isolator in
accordance with regulations
fABurner (stage 1)
gSM2Mixing valve motor
gSM3Mixing valve motor
lÖBurner
(burner stage 2 / mod.)
aVD/aVH External connections
Please refer to the control
manual Vitocontrol-S,
VD2/CT3.
5285 941 v1.6
Page 9
Heating system types
Circuit Diagram 1
(continued)
sÖ A1 Close mixing valves
AContactor relay, field supplied
BHeating circuit controls
connected downstream
Switch contact closed: signal
for ”close mixing valve”.
Wiring diagram
Wiring of the Therm-Control in heating
systems with heating circuit control units
are not connected to the boiler control
unit via the LON.
Required coding:
Change “4C” to “2” - use the plug-in
connector 20 A1 to close the
downstream mixing valve. Change “0D”
to “1” - the Therm-Control acts on the
mixing valve of the downstream heating
circuits (for Vitotronic 200 and 300,
delivered condition).
5285 941 v1.6
9
Page 10
Heating system types
Heating system types for modulating boilers
(continued)
System type 2 – Single-boiler system with shunt pump and return valve for raising the return temperature
in conjunction with
Vitorond 200, VD2
CC
M3
2
20
52
1
28
21
5
M2M3
22052220
41
40
M2
2
20
52
A1
29
52
52
17B
17A
3
90
146
143
T2
T1
B
A Boiler with Vitotronic 300
B Domestic hot water tank
C Heating circuit with mixing valve
*1
On the Vitorond the boiler supply and return are at the rear of the boiler.
10
*1
A
plugs
!Outdoor temperature sensor
? M2 Supply temperature sensor,
mixing valve circuit 2
? M3 Supply temperature sensor,
mixing valve circuit 3
§Boiler temperature sensor
%DHW tank temperature sensor
aJA Temperature sensor T1
aJB Temperature sensor T2
sÖ M2 Heating circuit pump, mixing
fABurner (1st stage)
gS A1 Mixing valve motor for raising
the return temperature
gS M2 Mixing valve motor, mixing
valve circuit 2
gS M3 Mixing valve motor, mixing
valve circuit 3
lÖBurner (2nd stage/modulating)
aVDConnection of external
equipment (see page 38)
aVHConnection of external
equipment (see page 39)
5285 941 v.1.6
Page 11
Heating system types
Heating system types for modulating boilers
Possible applications
Heating systems with distributor
arranged close to the boiler. The boiler
water flow is required to be reduced.
Please note:
This circuit diagram represents a
recommendation only. It is the
responsibility of the customer and/or
the heating contractor to check that
this recommendation is complete and
fully functional. Three-phase equipment
must be connected via additional
power contactors.
Available system accessories
Vitotrol remote control
Flue gas temperature sensor
Coding
system type
00: 1If no system circuit A1 is connected, set
02: 1Set coding ”02: 2” for operation with
03: 0Set coding ”03: 1” for oil-fired operation
0C: 0Set coding ”0C: 1” for continuous return
4A: 0––Connection of the temperature sensor T1 at
4b: 0––Connection of the temperature sensor T2 at
Change requiredAutomatic change
coding ”00: 3”, ”00: 4”, ”00: 7” or ”00: 8”
(see page 114)
modulating burner
(re-setting is not possible)
temperature control
When the return temperature falls
below the required minimum value,
the temperature sensor T2 switches
on the shunt pump. If, as a result,
the required minimum return
temperature is not reached, the
return valve is proportionally closed
via the temperature sensor T1 and
the minimum return temperature is
assured.
The shunt pump must be sized so that
bypassed water accounts for approx.
30% of the total flow rate of the
boiler.
(continued)
The system type is recognized automatically
when the sensors are connected
––
––
––
plug aJA;
Coding ”4A: 1” is set automatically
plug aJB;
Coding ”4b: 1” is set automatically
5285 941 v.1.6
11
Page 12
Heating system types
Heating system types for condensing boilers
System type 3 – Single-boiler system with Vitocrossal 300
CC
A1M2M3
20220
1
28
21
5
41
40
52220
90
143
M2
2
20
52
52
3
146
M3
2
20
52
B
A Boiler with Vitotronic 300
B Domestic hot water tank
C Heating circuit with mixing valve
D Neutralizing unit
D
A
plugs
!Outdoor temperature sensor
? M2 Supply temperature sensor,
mixing valve circuit 2
? M3 Supply temperature sensor,
mixing valve circuit 3
§Boiler temperature sensor
%DHW tank temperature sensor
sÖ A1 Heating circuit without mixing
lÖBurner (2nd stage/modulating)
aVDConnection of external
equipment (see page 38)
aVHConnection of external
equipment (see page 39)
5285 941 v.1.6
12
Page 13
Heating system types
Heating system types for condensing boilers
Please note:
This circuit diagram represents a
recommendation only. It is the
responsibility of the customer and/or
the heating contractor to check that
this recommendation is complete and
fully functional. Three-phase equipment
must be connected via additional
power contactors.
Available system accessories
Vitotrol remote control
Flue gas temperature sensor
Coding
system type
00: 1If no system circuit A1 is connected, set
02: 1Set coding ”02: 2” for operation with
0d: 1Set coding ”0d: 0”––
Change requiredAutomatic change
coding ”00: 3”, ”00: 4”, ”00: 7” or ”00: 8”
(see page 114)
modulating burner
The Vitocrossal 300 is operated with
modulating boiler water temperature
by means of the outdoor re-set boiler
control unit. Viessmann modulating
burner is operated through Vitotronic
control.
The boiler water temperature which
is established in the heating mode is
higher than the maximum heating
circuit supply temperature by an
adjustable difference.
(continued)
The system type is recognized automatically
when the sensors are connected
––
5285 941 v.1.6
13
Page 14
Heating system types
Heating system types for condensing boilers
(continued)
System type 4 - Single-boiler system with Vitocrossal 300 with several heating circuits and one modulating supply
temperature heating circuit
M3
2
F
20
52
or
A1M2M3
20220
1
28
21
5
41
40
52220
90
143
CD
M2
2
20
52
52
3
146
M3
2
20
52
E
B
G
A Boiler with Vitotronic 300
B Domestic hot water tank
C Heating circuit with mixing valve
D Modulating supply temperature
heating circuit
or
E Underfloor heating circuit
F High limit thermostat (max. limit)
G Neutralizing unit
14
A
plugs
!Outdoor temperature sensor
? M2 Supply temperature sensor,
mixing valve circuit 2
? M3 Supply temperature sensor,
mixing valve circuit 3
§Boiler temperature sensor
%DHW tank temperature sensor
sÖ A1 Heating circuit without mixing
lÖBurner (2nd stage/modulating)
aVDConnection of external
equipment (see page 38)
aVHConnection of external
equipment (see page 39)
5285 941 v.1.6
Page 15
Heating system types
Heating system types for condensing boilers
Possible applications
For heating circuits with different
temperatures.
Please note:
This circuit diagram represents a
recommendation only. It is the
responsibility of the customer and/or
the heating contractor to check that
this recommendation is complete and
fully functional. Three-phase equipment
must be connected via additional
power contactors.
The Vitocrossal 300 is operated with
modulating boiler water temperature
by means of the outdoor re-set boiler
control unit. Two-stage or modulating
burners can be controlled.
The Vitocrossal 300 has two return
connections. The heating circuits with
the higher return temperature are
connected to the return connection
at the top, those with the lower
temperatures to the return connection
at the bottom. Please note: At least
15% of the take-off from the rated
output must be connected to the
return connection at the bottom.
The boiler water temperature which
is established in the heating mode is
higher than the maximum heating
circuit supply temperature by an
adjustable difference.
(continued)
Pumps in the underfloor heating
circuit
20
20
LN
ABC
sÖ Heating circuit control unit
A Primary pump of underfloor
heating circuit
B High limit thermostat (max. limit)
C Secondary pump of underfloor
heating circuit (after system
separation)
Coding
system type
00: 1If no system circuit A1 is connected, set
02: 1Set coding ”02: 2” for operation with
0d: 1Set coding ”0d: 0”––
5285 941 v.1.6
Change requiredAutomatic change
The system type is recognized automatically
coding ”00: 3”, ”00: 4”, ”00: 7” or ”00: 8”
(see page 114)
modulating burner
when the sensors are connected
––
15
Page 16
Heating system types
Heating system types for condensing boilers
System type 5 – Single-boiler system with Vitocrossal 200
A Boiler with Vitotronic 300
B Domestic hot water tank
C Heating circuit with mixing valve
D Neutralizing unit
16
plugs
!Outdoor temperature sensor
? M2 Supply temperature sensor,
mixing valve circuit 2
? M3 Supply temperature sensor,
mixing valve circuit 3
§Boiler temperature sensor
%DHW tank temperature sensor
sÖ A1 Heating circuit without mixing
lÖBurner (2nd stage/modulating)
aVDConnection of external
equipment (see page 38)
aVHConnection of external
equipment (see page 39)
5285 941 v.1.6
Page 17
Heating system types
Heating system types for condensing boilers
Please note:
This circuit diagram represents a
recommendation only. It is the
responsibility of the customer and/or
the heating contractor to check that
this recommendation is complete and
fully functional. Three-phase equipment
must be connected via additional
power contactors.
Available system accessories
Vitotrol remote control
Coding
system type
00: 1If no system circuit A1 is connected, set
02: 1Set coding ”02: 2” for operation with
0d: 1Set coding ”0d: 0”––
Change requiredAutomatic change
coding ”00: 3”, ”00: 4”, ”00: 7” or ”00: 8”
(see page 114)
modulating burner
The Vitocrossal 200 is operated with
modulating boiler water temperature
by means of the outdoor re-set boiler
control unit. Viessmann modulating
burner is operated through Vitotronic
control.
The boiler water temperature which
is established in the heating mode is
higher than the maximum heating
circuit supply temperature by an
adjustable difference.
(continued)
The system type is recognized automatically
when the sensors are connected
––
5285 941 v.1.6
17
Page 18
Installation
Overview of electrical connections
52
M3
52
M2
20
M3
20
M2
2
M3
2
M2
145
145
1
17
B
17
A
5
3/2
15
143
146
28
21
52
20
29
50
40
156
156
A1
A1
151
90
41
150
Mixing valve extension circuit board
? M2/M3 Supply temperature sensor
sÖ M2/M3 Heating circuit pump
gS M2/M3 Mixing valve motor
18
Low-voltage motherboard
!Outdoor temperature sensor
(ATS)
§Boiler temperature sensor (BTS)
%DHW tank temperature sensor
(STS)
aGFlue gas temperature sensor
(AGS) (accessory)
aJA Therm-Control temperature
sensor
or
return temperature sensor T1
(RLS) (accessory)
temperature control
or
3-way mixing valve for DHW
tank loading system
lÖBurner (2nd stage/modulating)
aBÖConnection of external
equipment, e.g. additional
safety equipment
aBASafety circuit, potential free
aBHPower supply connection for
accessories
5285 941 v.1.6
Page 19
Overview of electrical connections(for VD2/VD2A/CT3 only)
Installation
5285 941 v.1.6
19
Page 20
Installation
Overview of electrical connections (for CM2 only)
20
5285 941 v.1.6
Page 21
Routing and strain relief of cables
1. Run the cables from the connection enclosure into the control unit.
2. Apply strain relief to cables (see below).
Installation
Cables with moulded strain relief
clamp
Connect cable and strain relief
clamp.
OR
Fasten cable to the cable lead with
cable tie.
5285 941 v.1.6
21
Page 22
Installation
Inserting the boiler coding card
CAUTION
For matching the operation of the
control unit to the boiler, only the
boiler coding card which is supplied
as part of the standard delivery of
the boiler may be used.
Only use the boiler coding card included with the boiler.
BoilerCoding cardPart No.
Vitocrossal 300, type CT310407820 144
Vitorond 200, VD2 / VD2A10207820 142
Vitocrossal 200 CM210417820 145
1. Push the boiler coding card
through the recess in the cover
and insert it in plug-in location
”X7”.
22
5285 941 v.1.6
Page 23
Installation
Adjustment of the fixed high limit
The fixed high limit is supplied with a factory setting of 110°C / 230°F.
3.
(if required)
A
Adjustment to 99°C / 210°F
¨ Disconnect power to control
and burner!
1. Unclip the fuse box and swing
upwards.
2. Turn the slotted screw on the
rear of the fixed high limit until
the slot points to 99°C / 210°F
(once adjusted, the fixed high limit
cannot be reset to 110°C/ 230°F).
3. Re-fit the fuse box.
WARNING
If adjusted to 99°C / 210°F, do
not set the adjustable high limit
above 75°C / 167°F.
Coding for the electronic maximum
temperature limiter of Vitotronic 100;
set code 06 to the temperature as
shown or less
93 / 20087 / 18887 / 18888 / 190
Condensing boiler
(CT3) °C / °F
Condensing boiler
(CM2) °C / °F
5285 941 v.1.6
23
Page 24
Installation
Adjustment of the adjustable high limit
The adjustable high limit is supplied with a factory setting of 95°C.
A
3.
2.
(if required)
Adjustment to 100°C / 212°F
1. Using a suitable screwdriver,
lever out and remove the
selector knob ”R” behind the
hinged cover.
2. Using a pair of pointed pliers,
break off the cams identified by
the shaded areas in the Fig.
from the stop dial.
A75 to 100°C
167 to 212°F
3. Fit the selector knob ”R” so
that the marking is in the centre
of the selected range.
Please note:
Note the setting of coding address
”06”!
1.
WARNING
If the system is operated in
conjunction with a domestic hot
water tank, ensure that the
maximum permissible domestic
hot water temperature is not
exceeded. If necessary, install a
suitable safety device for this
purpose.
24
5285 941 v.1.6
Page 25
Connection of the outdoor temperature sensor
The outdoor temperature sensor should be mounted 2 to 2.5 metres / 6.5 to
8 ft above ground level on the north or north-west facing wall of the building.
In the case of multi-storey buildings, it should be mounted in the upper half of
the second storey.
Make sure that the sensor is not located over windows, doors and air vents,
nor immediately beneath a balcony or guttering.
Do not paint over the outdoor temperature sensor housing.
1.
5.
3.
Installation
1. Remove the cap.
2. Mount the bottom part of the
sensor housing.
3. Pull the sensor wire through the
opening in the terminal
compartment and through the
strain relief provided.
4. Connect the wires to the
terminals.
600
580
560
540
520
500
480
460
4.
2.
5. Place the cap over the outdoor
temperature sensor.
WARNING
When extending wire, there is the
possibility of exposure to
electromagnetic interference. Avoid
running wires beside or near high
voltage 120/240 VAC conductors.
If proximity to high voltage
conductors cannot be avoided, use
stranded, twisted pair or shield design
wire. Ensure that only one end of the
shielding is grounded.
440
420
Resistance in
400
-40-30-20-100102030
-40-22
Outdoor temperature sensor °C / °F
5285 941 v.1.6
-4
1432506886
25
Page 26
Installation
Connection of the boiler temperature sensor
The sensor measures the boiler
water temperature.
3
760
740
The boiler temperature sensor is
installed at the same time as the
boiler insulation.
Check the sensor
1. Disconnect plug § in the
terminal compartment of the
boiler control.
2. Measure resistance of sensor
at terminals ”1” and ”2” of the
plug.
Boiler water
temperature
in °C / °F
40 / 104
50 / 122
60 / 140
3. Compare the value measured
with the current temperature.
If the value differs significantly,
check installation and, if
necessary, replace sensor.
Resistance
in ΩΩΩΩ
578
597
616
720
700
680
660
640
620
Resistance in
600
580
560
4000540
3268141176212248284104
Boiler temperature in
Technical data
Degree of protection: IP 32
Ambient temperature
During operation:
0 to + 130°C
32 to + 266°F
During storage and transport:
-20 to + 70°C
-4 to + 158°F
Electrical connection
The sensors are ready to plug in.
Insert the boiler temperature
sensor in socket ”3” of the boiler
control.
20406080100120140
°C / °F
26
5285 941 v.1.6
Page 27
Connection of the DHW tank temperature sensor
Installation
The sensor measures the domestic hot
water tank temperature.
5
sensor and tank
temperature sensor
720
Heating systems with domestic hot
water heating (single-boiler systems
only)
1. Install the DHW tank temperature
sensor.
See Installation
Instructions for domestic
hot water tank.
Please note:
When installing the sensor in DHW
tanks of other makes, make sure
that the sensor is pressed against
the sensor well of the DHW tank
by means of a suitable device.
2. Ensure that the maximum
permissible domestic hot water
temperature is not exceeded. If
necessary, install a suitable safety
device for this purpose.
Heating systems without domestic
hot water heating
Do not connect the DHW tank
temperature sensor.
Check the sensor
1. Disconnect plug % in the
terminal compartment of the
boiler control.
2. Measure resistance of sensor
at terminals ”1” and ”2” of the
plug.
DHW tank
temperature
in °C / °F
40 / 104
50 / 122
60 / 140
3. Compare the value measured
with the current temperature.
If the value differs significantly,
check installation and, if
necessary, replace sensor.
Technical data
Degree of protection: IP 32
Ambient temperature
During operation:
0 to + 90 °C
32 to + 194 °F
During storage and transport:
-20 to + 70 °C
-4 to + 158 °F
Resistance
in ΩΩΩΩ
578
597
616
700
Electrical connection
680
660
640
620
The sensors are ready to plug in.
Insert the DHW temperature
sensor in socket ”5” of the boiler
control.
Resistance in
600
580
560
540
020406080100
3268104140176212
DHW tank temperature in ºC / ºF
5285 941 v.1.6
27
Page 28
Installation
740
R
e
s
i
s
t
a
n
c
e
i
n
Connection of the return temperature sensor
Strap-on temperature sensor and immersion temperature sensor
17A or 17B
17A or 17B
For measuring the boiler return
temperature.
Electrical connection
The sensor is inserted in socket
”17A” or ”17B” on the boiler
control.
Check the sensor
1. Disconnect plug aJA or aJB
in the terminal compartment of
the boiler control.
2. Measure resistance of sensor
at terminals ”1” and ”2” of the
plug.
720
700
680
660
640
620
Return
temperature
in °C / °F
30 / 86
40 / 104
60 / 140
3. Compare the value measured
with the current temperature. If
the value differs significantly,
check installation and, if
necessary, replace sensor.
Technical data
Degree of protection: IP 32
Ambient temperature
During operation:
0 to + 100°C
32 to + 212°F
During storage and transport:
-20 to + 70°C
-4 to + 158°F
Resistance
in ΩΩΩΩ
569
592
643
600
580
560
540
28
3040506070708090
20100
6886104122140158176194 212
Return temperature in
°C / °F
5285 941 v.1.6
Page 29
Connection of the flue gas temperature sensor (VD2/VD2A/CT3 only)
The sensor measures the flue gas
temperature and monitors the
selected limit value.
Electrical connection
The sensor is inserted in socket
”15” on the boiler control.
Check flue gas temperature sensor
1. Disconnect plug aG in the
terminal compartment .
2. Measure resistance of sensor
at terminals ”1” and ”2” of the
plug.
Installation
1020
980
940
900
860
820
Ω
Ω
Ω
Ω
780
740
700
Resistance in
660
Flue gas
temperature
in °C / °F
180 / 176
160 / 320
200 / 392
3. Compare the value measured
with the actual temperature If
the value differs significantly,
check installation and, if
necessary, replace sensor.
Technical data
Degree of
protection:IP 60
Ambient temperature
During operation:
0 to + 600°C
32 to + 1112°F
During storage and transport:
-20 to + 70°C
-4 to + 158°F
Resistance
in ΩΩΩΩ
650
800
880
620
580
540
500
0
4080
32104 176
Flue gas temperature in °C / °F
5285 941 v.1.6
120 160 200 240 280
248 360 392 464 536
29
Page 30
Installation
Connection of the Pumps (VD2/VD2A/CT3 only)
Available pump connections
sÖA1/M1Heating circuit high
temperature (without mixing valve)
Terminals 5 - L, - G , - N
sACirculation pump for heating
up the domestic hot water tank Terminals 4 - L, - G , - N
sLShunt pump, boiler circuit pump
Terminals 6 - L, - G, - N.
sK
DHW recirculattion pump
terminals 3 - L, - G, - N
sÖM2
M2 Heating circuit high
temperature (with mixing valve)
Terminals 2 - L, - G , - N
sÖM3
M3 Heating circuit high
temperature (with mixing valve)
Terminals 1 - L, - G , - N
Install pumps: see
manufacturer’s
instructions.
120 VAC pumps
Note:
The maximum power consumption of
all pumps is 4A .
Rated current: max. 2 FLA
Recommended connection
cable: AWG 14
Use contactor for pumps with higher
current rating
Connect the 3-wire cable from the
pump to the corresponding terminals.
240 VAC or 3 PH pumps
Please note:
Use contactor and/or motor starter to
power pump.
For activating the contactor:
Rated current: max. 2 FLA
Recommended connection
wire size: AWG 14
Please ensure that all connections and
wire sizes comply with local and
national codes.
1.Select the contactor and the
connecting wire in accordance with
the rating of the pump that is to be
connected.
2.Connect pump and power supply to
the contactor.
3.Connect contactor coil to the
corresponding terminals.
30
5285 941 v1.6
Page 31
Connection of the Pumps (CM2 only)
Available pump connections
Installation
sÖA1/M1Heating circuit high
temperature (without mixing valve)
Terminals 7 - L, - G , - N
sACirculation pump for heating
up the domestic hot water tank Terminals 6 - L, - G , - N
sLShunt pump, boiler circuit pump
Terminals 8 - L, - G, - N.
sK
DHW recirculattion pump
terminals 5 - L, - G, - N
sÖM2
M2 Heating circuit high
temperature (with mixing valve)
Terminals 4 - L, - G , - N
sÖM3
M3 Heating circuit high
temperature (with mixing valve)
Terminals 3 - L, - G , - N
Install pumps: see
manufacturer’s
instructions.
120 VAC pumps
Note:
The maximum power consumption of
all pumps is 4A .
Rated current: max. 2 FLA
Recommended connection
cable: AWG 14
Use contactor for pumps with higher
current rating
Connect the 3-wire cable from the
pump to the corresponding terminals.
240 VAC or 3 PH pumps
Please note:
Use contactor and/or motor starter to
power pump.
For activating the contactor:
Rated current: max. 2 FLA
Recommended connection
wire size: AWG 14
Please ensure that all connections and
wire sizes comply with local and
national codes.
1.Select the contactor and the
connecting wire in accordance with
the rating of the pump that is to be
connected.
2.Connect pump and power supply to
the contactor.
3.Connect contactor coil to the
corresponding terminals.
5285 941 v1.6
31
Page 32
Installation
Connection of boiler return mixing valve or modulating valve actuator
2. Install 120V or 24V Valve
Adaptor on DIN rail inside
connection enclosure.
3. Insert the plug gS into socket
gS on the control.
4. Fasten cable with tie
(see page.21).
5. Connect black wire of the
adaptor to connection 120V L
out the DIN rail
- Terminals 10,11 or 12.
6. Connect valve actuator wires
to the adaptor terminals as
shown on figures.
5285 941 v1.6
33
Page 34
Installation
Making Space for Accessory Adaptors on the DIN Rail (CM2 only)
1. Push up on the bottom front of
the DIN rail clamp to remove and
set aside.
2. Using a flat head screwdriver,
remove the 4 ’spare’ DIN
terminals 23, 24, 25 and 26 one
at a time. Place the screwdriver
between the rail and the base of
the terminal and turn the
screwdriver clockwise . Discard
the removed terminals.
3. Re-install the DIN rail clamp by
hooking the latch of the clamp
around the top of the rail and then
push down on the front of the
clamp.
Note: See separate Installation
Instructions for accessory
adaptors.
34
5285 941 v1.6
Page 35
Connections to terminal aBÖ (VD2/VD2A/CT3 only)
Installation
External shut-off
1. Remove jumper between
terminals 16 and 17.
2. Connect dry contact.
Controlled switch-off takes
place when the contact is
opened.
WARNING
The terminals should be used for
safety switch-off purposes only
(e.g. through a high limit thermostat).
Start at page 52 for details of
controlled switch-off.
During switch-off, there is no frost
protection of the heating system
and the boiler is not kept at the
minimum boiler water temperature.
A Jumper
B External shut-off (dry contact)
Emergency operation
Move jumper from terminals 16
and 17 to terminals 17 and 18.
5285 941 v.1.6
35
Page 36
Installation
Connection of the compiled failure alarm indicator (VD2/VD2A/CT3 only)
B External disable/”Close mixing valves” externally
(floating contact)
The manually preselected heating
program can be changed over (see
table) and the mixing valves opened
via the contact.
Via coding address ”9A” the function
”Open mixing valves” and via coding
address ”91” the changeover of the
heating program can be assigned to
the heating circuits.
External disable/”Close mixing valves”
Connect floating contact to terminals
”2” and ”3”.
Controlled switch-off of the burner
takes place or the mixing valves are
closed when the floating contact is
closed.
The shunt pump is switched off.
Please note:
During controlled switch-off or
”Close mixing valves”, there is no
frost protection of the boiler or
heating circuits and no minimum
boiler water temperature is
maintained.
Manually preselected heating program
(with contact open)
9
or
w
or
rwSpace heating ON/DHW ON
38
Space heating OFF/DHW OFFd5: 0
Space heating ON/DHW ONd5: 1<–>
Coding address ”99” can be used to
select the equipment for which the
input aVD is to be effective.
Coding 2Heating program after changeover
(with contact closed)
<–>Continuous operation with reduced room
(factory default)
temperature/DHW OFF
Continuous operation with normal room
temperature/DHW according to coding
address ”64”
5285 941 v.1.6
Page 39
Connection of external equipment to plug aVH
B
A
Installation
External demand
Connect floating contact to
terminals ”2” and ”3”.
The burner of the boiler is switched
in on a load-dependent basis when
the floating contact is closed.
The boiler water temperature is
limited by the preset max. boiler
water temperature or by the value
set on the mechanical adjustable
high limit.
The required boiler set-point value is
set via the coding address ”9b”.
146
A External demand (floating contact)
B External changeover,
staged/modulating burner
(floating contact)
External changeover between
staged/modulating burner
Connect floating contact to
terminals ”1” and ”2”.
Contact open:modulating
operation
Contact closed: two-stage
operation
The burner type must be set to
”modulating” in coding 1
(coding ”02: 2”).
Please note:
When the burner type is scanned,
”modulating” continues to be
displayed after external changeover
(the display is not changed).
5285 941 v.1.6
39
Page 40
Installation
Connection of external controls
Operation with two-stage burner
Settings on the control unit
The settings for the fixed high limit and
the other settings are dependent on the
safety equipment installed in
accordance with applicable codes.
Coding for the electronic maximum
temperature limiter of Vitotronic 100;
set code 06 to the temperature as
shown or less
93 / 20087 / 18887 / 18888 / 190
Single-boiler systems:
Coding ”01: 1”
(factory setting)
When a building automation system is
connected, only the connections on
plug aVD are required. The DHW tank
control unit is activated when the DHW
tank temperature sensor is connected.
The boiler water temperature must be
set to the minimum value.
Condensing boiler
(CT3) °C / °F
Multi-boiler systems:
Set coding ”01: 3”
When a building automation system
is connected, the connections on
plugs aVD and aVH are required.
The DHW tank temperature and the
load-dependent cascade control must
be controlled through the building
automation system.
Condensing boiler
(CM2) °C / °F
40
CAUTION
The boiler activation contact is
essential on multi-boiler systems.
The contact on the lead boiler MUST
be constantly closed.
5285 941 v.1.6
Page 41
Installation
Connection of external controls (VD2/VD2A only)
Modulating boilers – operation with external modulation controller
1st stage burner fA from Vitotronic.
Plug lÖ from Vitotronic via
modulation controller (BAS).
On the bulding automation unit with
modulation controller set the
minimum temperatures 5°C / 9°F
above the minimum boiler water
temperature of the boiler.
(continued)
Boiler activation, isolation valve
open or closed
Connect dry contact at terminals
”2” and ”3” of the plug aVH.
Contact closed:
First, the preheat function for followup boilers is activated (coding
address ”2b”).
When the preheat function finishes,
the minimum temperature is
maintained for the boiler, and the
burner stages/modulation can be
switched externally.
The boiler water temperature is
limited by the preset maximum
boiler water temperature or via the
mechanical adjustable high limit.
The setpoint value is selected via
the coding address ”9b”.
Contact open:
The isolation valve is closed after
approx. 5 minutes (coding address
”2C”).
External override of the burner
stages is not possible, and no
minimum temperature is maintained.
Switch on 1st stage burner (basic
load)
Connect dry contact at terminals ”1”
and ”2” of the plug aVD.
Contact closed:
The 1st stage burner is switched on.
The full load is only switched on to
maintain the minimum temperature
(not with Vitocrossal 300). The
boiler water temperature is limited
by the electronic maximum
temperature limit (coding address
”06”) if this is set below the value
preset on the mechanical adjustable
high limit ”R”.
Contact open:
The 1st stage burner is switched
off.
5285 941 v.1.6
41
Page 42
Installation
Connection of external controls (VD2/VD2A only)
Modulating boilers – operation with external modulation controller (continued)
Settings on the control unit
The settings for the fixed high limit and
the other settings are dependent on the
safety equipment installed in
accordance with applicable codes.
Coding for the electronic maximum
temperature limiter of Vitotronic 100;
set code 06 to the temperature as
shown or less
93 / 20087 / 18887 / 18888 / 190
Single-boiler systems:
Coding ”01: 1”
(factory setting)
Condensing boiler
(CT3) °C / °F
(continued)
Condensing boiler
(CM2) °C / °F
Multi-boiler systems:
Set coding ”01: 3”
When a building automation system is
connected, only the connections on
plug aVD are required. The DHW tank
control unit is activated when the DHW
tank temperature sensor is connected.
The boiler water temperature must be
set to the minimum value.
When a building automation
system is connected, the
connections on plugs aVD and
aVH are required.
The DHW tank temperature and
the load-dependent cascade control
must be controlled through the
external building automation
system.
CAUTION
The boiler activation contact is
essential on multi-boiler systems.
The contact on the lead boiler
MUST be constantly closed.
42
5285 941 v.1.6
Page 43
Installation
Connection of external controls (CT3 only)
Vitocrossal 300 – operation with external modulation controller
1st stage burner fA from
Vitotronic 100.
Connection lÖ from Vitotronic has
no function.
Connection lÖ from building
automation system to the burner.
1st stage burner activated by the
modulation controller via connection
aVH.
(continued)
Boiler activation, isolation valve
open or closed
Connect dry contact at terminals
”2” and ”3” of the plug aVH.
Contact closed:
First, the preheat function for
follow-up boilers is activated
(coding address ”2b”).
When the preheat function finishes,
the burner stages/modulation can
be switched externally.
The boiler water temperature is
limited by the preset maximum
boiler water temperature or via the
mechanical adjustable high limit.
The setpoint value is selected via
the coding address ”9b”.
Contact open:
The isolation valve is closed after
approx. 5 minutes (coding address
”2C”).
External override of the burner
stages is not possible, and no
minimum temperature is maintained.
Switch on 1st stage burner (basic
load)
Connect dry contact at terminals
”1” and ”2” of the plug aVD.
Contact closed:
The 1st stage burner is switched on.
The boiler water temperature is
limited by the electronic maximum
temperature limit (coding address
”06”) if this is set below the value
preset on the mechanical adjustable
high limit ”R”.
Contact open:
The 1st stage burner is switched off.
5285 941 v.1.6
43
Page 44
Installation
Connection of external controls (CT3 only)
Vitocrossal 300 – operation with external modulation controller (continued)
Settings on the control unit
The settings for the fixed high limit and
the other settings are dependent on the
safety equipment installed in
accordance with applicable codes.
Coding for the electronic maximum
temperature limiter of Vitotronic 100;
set code 06 to the temperature as
shown or less
93 / 20087 / 18887 / 18888 / 190
Single-boiler systems:
Coding ”01: 1”
(factory setting)
(continued)
Condensing boiler
(CT3) °C / °F
Condensing boiler
(CM2) °C / °F
Multi-boiler systems:
Set coding ”01: 3”
When a building automation system is
connected, only the connections on
plug aVD are required. The DHW tank
control unit is activated when the DHW
tank temperature sensor is connected.
The boiler water temperature must be
set to the minimum value.
When a building automation system
is connected, the connections on
plugs aVD and aVH are required.
The DHW tank temperature and the
load-dependent cascade control
must be controlled through the
building automation system.
CAUTION
The boiler activation contact is
essential on multi-boiler systems.
The contact on the lead boiler
MUST be constantly closed.
44
5285 941 v.1.6
Page 45
Installation
Connections of combustion air device adaptor (VD2/VD2A/CT3 only)
Connection of the Combustion Air
Device Adaptor
1. Disconnect power to control and
burners.
2. Install Combustion Air Device
Adaptor, Part No.: 7134 563
on DIN Rail inside connection
enclosure (refer to installation
manual of Combustion Air
Device Adaptor).
3. Remove jumper between
terminals 16 and 17.
4. Make connection as shown in
the diagram.
IMPORTANT
Wire BK2 must be connected to
terminal 16 and BK3 to terminal
17 - DO NOT reverse.
D
A Combustion Air Device Adaptor
B DIN Rail in connection enclosure
Connection of the combustion air
blower to adaptor
Assure that combustion air blower
device is suitable for this application.
For detailed instruction on
adaptor installation, please refer
to the adaptor’s installation manual.
1. Make connection as shown in
the diagram at left.
A Combustion Air Device Adaptor
in connection enclosure
B Combustion air blower motor
C Proving switch - “normally open”
rated for 120 VAC
D Power supply, 120 VAC
5285 941 v.1.6
CAUTION
Provide disconnect means and
overcurrent protection as required
by local codes.
45
Page 46
Installation
Connection of Combustion Air Device (CM2 only)
D
Connection of the Combustion Air
Device Adaptor
1. Disconnect power to control and
burners.
2. Install Combustion Air Device
Adaptor, Part No. 7134 563
on DIN Rail inside the boiler junction
box (refer to installation manual of
Combustion Air Device
Adaptor).
3. Remove plug 150 from Vitotronic
control. Remove jumper between
the 2 ’TR’ terminals. Using 14 AWG
(field supplied) connect plug
terminals TR(Left), TR(Right) and
neutral to the DIN rail.
Neutral to Terminal 16
TR(Left) to Terminal 18
TR(Right) to Terminal 19
Re-install the 150 plug and DIN rail
connections as shown in the diagram.
IMPORTANT
Connection of the combustion air
blower to adaptor
Ensure that combustion air blower
device is suitable for this application.
For detailed instruction on adaptor
installation please refer to the
adaptor’s installation manual.
1. Make connection as shown in the
diagram at left.
A Combustion Air Device Adaptor
in connection enclosure
B Combustion air blower motor
C Proving switch - “normally open”
rated for 120 VAC.
D Power supply, 120 VAC
¨ Safety instruction!
Provide disconnect means and
overcurrent protection as required
by local codes.
Wire BK2 must be connected to
terminal 18 and BK3 to terminal 19 DO NOT reverse.
46
5285 941 v1.6
Page 47
Installation
Connection of combustion air device
(continued)
E
Connection of the combustion air
damper
See damper manual for correct
installation.
Note:
Assure that the combustion air
damper is suitable for this
application.
1. Disconnect power to control and
burner.
2. Make connection as shown in the
diagram.
A Combustion Air Device Adaptor
in connection enclosure
B Relay 120 VAC coil - field
supplied
C Combustion air damper
D End switch rated for 120 VAC
wired to “normally open”
terminal on device adaptor board
E Power supply, 120 VAC
CAUTION
Provide disconnect means and
overcurrent protection as required
by local codes.
Note:
Spring return air dampers do not
require field supplied relay.
5285 941 v.1.6
47
Page 48
Installation
Flue Gas Temp. Switch (mandatory for PP(s) material collectors)
(CM2 only)
1. Disconnect power.
CAUTION
Please note that the diagram shown
is only a simplified conceptual
drawing of a flue gas temperature
switch. Refer to the manual specific
to the device for interconnection
details.
2. Remove 150 plug from the
Vitotronic control and discard.
3. Install new 150 plug supplied
(attached to flue gas temperature
switch).
48
5285 941 v1.6
Page 49
Connection of low water cut-off device (VD2/VD2A/CT3 only)
1.Remove jumper between
terminals 12 and 15.
2.Make connection as shown in
diagram.
CAUTION
Please note that the diagram at
left is only a simplified conceptual
drawing of a typical low water
cut off (LWCO) device. Refer to
the manual specific to the device
for interconnection details.
Installation
aBH Power supply for accessories.
aBÖ Connection for external
equipment.
5285 941 v.1.6
49
Page 50
Installation
Connection of Low Water Cut-off Device (CM2 only)
1. Remove jumper between terminals
21 and 22.
2. Make connection as shown in
diagram.
CAUTION
Please note that the diagram shown
is only a simplified conceptual
drawing of a typical low water
cut-off (LWCO) device. Refer to the
manual specific to the device for
interconnection details.
50
5285 941 v1.6
Page 51
Burner connection, Burner control wiring (VD2/VD2A/CT3 only)
For burners with plug-in connection
Installation
A
41
120 VAC
B
The burner cables are included in the
standard delivery of the Vitotronic.
Connect the burner in accordance with
applicable codes.
ATo boiler control unit
BTo burner
Terminal codes
L1Phase via fixed high limit to the
burner
?Ground connection
NNeutral connection to the burner
T1,T2 Control circuit
S3Connection for burner fault
indicator
B4Connection for burner hours
counter
1.Disconnect power to burner and
boiler control.
2. Connect plugs fA and plug lÖ to
respective counter plugs in boiler
control unit.
3. Connect the 7-pole plug fA and
the 3-pole plug lÖ to the burner.
Terminal codes
A To plug-in connection in connection
enclosure
B To burner
5285 941 v.1.6
1,2,3 Control circuit ”2nd stage
burner or modulation controller”
(via two-point controller with
2-stage operation; via threepoint controller with modulating
operation)
1From burner
2Modulating down
3Modulating up/2nd stage ON
Colour codes as applicable
BKBlack
BNBrown
BUBlue
51
Page 52
Installation
Burner Connection, Burner Control Wiring (VD2/VD2A/CT3 only)
CAUTION
This is a generic connection drawing
only! Follow the burner
manufacturer’s connection drawings
for Viessmann controls.
Write the terminal numbers or
markings on the drawing for future
reference.
(continued)
ab
A Control unit
(Legend: see wiring diagram)
B 2nd stage or modulating *
C Hours counter, stage 1 *
D Burner fault indicator *
E Control circuit, stage 1/
basic load *
F Burner
1
1
Plug connection
located on the
DIN rail.
Burner power supply not shown.
fÖ Power supply connection of control
1
1
unit 120 VAC
fA Burner, 1st stage
lÖ Burner, 2nd stage
aBÖ Plugs for external equipment
a External safety devices
(remove jumper when connecting)
b External controlled switch-off
(remove jumper when connecting)
aBA Safety circuit. Emergency
shut-off
*1Refer to burner manufacturer’s instruction on detailed connections for Viessmann controls.
52
5285 941 v1.6
Page 53
Installation
Burner Connection, Burner Control Wiring (VD2/VD2A/CT3 only)
Burner motor power supply connection
(continued)
See burner manual for correct fuse
For burners with 240 VAC, 1PH power
supply and connection in conduit.
and wire gauge sizing, and specific
connections for Viessmann controls.
1.Disconnect power to burner and
boiler control.
2.Connect 240 VAC power to the
terminals 21, 22 and 23 on the
DIN rail inside the connection
enclosure. Provide fuseable
disconnect means according to
local codes.
3.Connect supplied power cable to
the motor terminals on the burner.
4.Connect cable plug to the socket
on the DIN rail in the connection
enclosure.
(continued)
A Burner motor power supply
240 VAC, 1PH
B Connection terminals and plug
inside connection enclosure
C Cable and conduit- factory supplied
D Burner
E Motor starter
F Burner motor
G Connection enclosure on boiler
control
5285 941 v1.6
53
Page 54
Installation
Burner Connection, Burner Control Wiring (VD2/VD2A/CT3 only)
Burner motor power supply connection
(continued)
For burners with 3PH 208, 460 or
575V power supply.
See burner manual for correct fuse
and wire gauge sizing, and specific
connections for Viessmann controls.
1.Disconnect power to burner and
boiler control.
2.Connect 3PH power to the
terminals 21, 22, 23 and 24 on
the DIN rail inside the connection
enclosure. Provide fuseable
disconnect means according to
local codes.
3.Connect supplied power cable to
the motor terminals on the burner.
4.Connect cable plug to the socket
on the DIN rail in the connection
enclosure.
(continued)
A Burner motor power supply 3PH
208, 460 or 575V
B Connection terminals and plug
inside connection enclosure
C Cable and conduit - factory
supplied
D Burner
E Motor starter
F Overload
G Burner motor
H Connection enclosure
CAUTION
During commissioning check for
correct motor rotation. If motor
rotates in opposite direction than
indicated on the burner, disconnect
power supply and reverse wires BK1
and BK2 on the burner terminals.
54
5285 941 v1.6
Page 55
Power Supply Connection, Boiler Control (VD2/VD2A/CT3 only)
Installation
Legend
L: Line
N: Neutral
G: Ground
A Power supply 120 VAC, 1 PH .
Provide disconnect means and
overcurrent protection as per local
codes
B Terminals [40]
C Connection enclosure
1. Ensure that the main power supply
to the control contains overcurrent
protection with a maximum rating
of 15 A and 2 pole disconnect.
CAUTION
The control must be grounded.
Ensure that “L”, “N” and “G” are not
interchanged.
2. Connect power supply wire to the
Connection fÖ terminals 11, N and
G on the DIN rail inside the
connection enclosure.
5285 941 v1.6
55
Page 56
Installation
Burner Connection, Burner Control Wiring (CM2 only)
For burners with plug-in connection
A
B
The burner cables are included in the
standard delivery of the Vitotronic.
Connect the burner in accordance with
applicable codes.
ATo boiler control unit
BTo burner interface
Terminal codes
L1Phase via fixed high limit to the
burner
?Ground connection
NNeutral connection to the burner
T1,T2 Control circuit
S3Connection for burner fault
indicator
B4Connection for burner hours
counter
1.Disconnect power to burner and
boiler control.
2. Connect plugs fA and plug lÖ to
respective counter plugs in boiler
control unit.
3. Connect the 7-pole plug fA and
the 3-pole plug lÖ to the burner.
A
B
A To plug-in connection in connection
enclosure
B To burner interface
Terminal codes
1,2,3 Control circuit ”2nd stage
burner or modulation controller”
(via two-point controller with
2-stage operation;
via three-point controller with
modulating operation)
1From burner
2Modulating down
3Modulating up/2nd stage ON
Colour codes as applicable
BKBlack
BNBrown
BUBlue
5285 941 v1.6
56
Page 57
Mounting the Front Part of the Control Unit (VD2/VD2A/CT3 only)
1.
8.
1. Position the front part of the housing
and clip hinges to counter-parts on
main housing.
Installation
7.
2. Release the stay bar, open it up
and lock in position at point A.
3. Insert the flat cable from the
Optolink into plug ”X20”.
4. Insert the plug of the programming
unit into socket ”X10”. Use cable
guides in cover for routing.
5. Engage the stay bar in the front
housing.
6. Close the front of the housing.
7. Secure front housing with supplied
screws.
8. Install cover of the connection
enclosure and support with supplied
screw.
2.
6.
A
5.
4.
3.
5285 941 v1.6
57
Page 58
Installation
Mounting the Front Part of the Control Unit (VD2/VD2A/CT3 only)
1.
8.
1. Position the front part of the housing
and clip hinges to counter-parts on
main housing.
7.
2. Release the stay bar, open it up
and lock in position at point A.
3. Insert the flat cable from the
Optolink into plug ”X20”.
4. Insert the plug of the programming
unit into socket ”X10”. Use cable
guides in cover for routing.
5. Engage the stay bar in the front
housing.
6. Close the front of the housing.
7. Secure front housing with supplied
screws.
8. Install cover of the connection
enclosure and support with supplied
screw.
2.
6.
A
5.
4.
3.
58
5285 941 v1.6
Page 59
Opening the Control Unit (VD2/VD2A/CT3 only)
Installation
1. Remove the cover of the
connection enclosure.
1.
2.
2. Unscrew the screws from the
front housing.
3. Swing up the front part of the
control housing.
4. Position the stay bar so that it
supports the front housing.
4.
3.
5285 941 v1.6
59
Page 60
Installation
Control and Junction Box Installation Instructions (for CM2 only)
1. Route cables and capillaries from
control through the opening in the
control panel. Guide the cables to
the junction box through the
opening in the rear panel and along
the top rail to the control. Secure
all cables to the rail with cable ties.
Insert capillaries into the sensor well.
Note: Never allow cables to come
in contact with hot metal
components.
WARNING
Do not bend or kink the capillaries.
Damaging the capillaries leads to
malfunction.
2. Mount the control to the control
panel.
3. Secure the control to the control
panel with screws.
Note: Screws to secure control are
included with the cosmetic
cover in the boiler jacketing
package.
4. Install the junction box to the rear
panel either right or left. Secure the
junction box with 4 x 4.8 metal
screws.
Note:The ground screw and ground
wire can be removed and then
reinstalled with the boiler back
panel attached.
60
5285 941 v1.6
Page 61
Mounting the Front Part of the Control Unit (CM2 only)
1. Position the front part of the housing
and clip hinges to counter-parts on
main housing.
Installation
2. Release the stay bar, open it up
and lock in position at point A.
3. Insert the flat cable from the
Optolink into plug ”X20”.
4. Insert the plug of the programming
unit into socket ”X10”. Use cable
guides in cover for routing.
5. Engage the stay bar in the front
housing.
6. Close the front of the housing.
7. Secure front housing with supplied
screws.
8. Install control cosmetic cover.
A
5285 941 v1.6
61
Page 62
Installation
Opening the Control Unit (CM2 only)
1. Remove the control cosmetic
cover .
2. Unscrew the screws from the
front housing.
3. Swing up the front part of the
control housing.
4. Position the stay bar so that it
supports the front housing.
Check that the stickers for the assignment of the heating circuits are affixed in
the appropriate locations on the control unit.
The corresponding button must be pressed before commencing each setting.
64
5285 941 v.1.6
Page 65
Start-up
Steps
3. Check the fixed high limit
(continued)
The check is made via the ”TÜV TEST” button (see page 64).
When making the check, the ” TÜV
TEST” button must be kept
continuously pressed.
A minimum supply is required
during the check.
The minimum amount of recirculated
water should be 10% of the amount
recirculated at the rated load.
The amount of heat consumed
should be reduced as far as possible.
The adjustable high limit ”R” is
bridged. The burner is switched on
until the boiler water temperature
reaches the safety temperature and
the fixed high limit operates.
When the burner is switched off by
the fixed high limit, release the
”TÜV TEST” button, wait until the
boiler water temperature has fallen 15
to 20°C / 27 to 36°F below the
selected safety temperature and
then reset the fixed high limit by
pressing the ”E” button.
4. Select the language (if required)
Outdoor temp erature
12
5285 941 v.1.6
1. Press.
2. Select the required language with
.
3. Confirm with.
The outdoor temperature or the
participant number is displayed.
65
Page 66
Start-up
Steps
5. Integrate the control unit in the LON BUS system in conjunction with Vitotronic 200-H
(continued)
User check
The LON communication module (accessory) must be inserted (see page 96).
Set the LON participant number
Set the LON participant number via
coding address ”77” in coding 1
(factory setting: ”77: 1”).
Update the LON participant list
This is only possible when all participants are connected and the control unit is
coded as the fault manager (coding ”79: 1”).
1. Press w andsimultaneously for
approx. 2 seconds.
2. Press D.
See page 114 for coding 1.
Please note:
The same number must not be
assigned twice within a LON BUS
system.
The participant check is initiated.
The participant list is updated
after approx. 2 minutes.
The participant check is
terminated.
Example of single-boiler system with Vitotronic 200-H heating circuit controls and Vitocom 300 connected downstream
Transmit outdoor
temperature via LON
Coding ”97: 2”
Viessmann system number
Coding “98: 1”
Fault monitoring
LON-Participant
Coding “9C: 20”
Participant No. 10
Coding ”77: 10”
Control unit is not fault
manager
Coding ”79: 0”
Time is received via LON
Set coding ”81: 3”
Outdoor temperature is
received via LON
Set coding ”97: 1”
Viessmann system number
Coding “98: 1”
Fault monitoring
LON-Participant
Coding “9C: 20”
Participant No. 11
Coding ”77: 11”
Control unit is not fault
manager
Coding ”79: 0”
Time is received via LON
Set coding ”81: 3”
Outdoor temperature is
received via LON
Set coding ”97: 1”
Viessmann system number
Coding “98: 1”
Fault monitoring
LON-Participant
Coding “9C: 20”
Participant No. 99
Unit is fault manager
Time is received via LON
66
5285 941 v.1.6
Page 67
Start-up
Steps
6. Carry out participant check
(continued)
User check
Participant check
The participant check is used to verify the communication of the system units
connected to the fault manager.
Requirements:
The control unit must be coded as the fault manager (coding ”79: 1”)
The LON participant number must be coded in all control units
The participant list must be updated in the fault manager
1. Press w andsimultaneously
for approx. 2 seconds.
The participant check is initiated.
01 : 01
1
Anlagenschema
Cod.1
Participant number
Consecutive list number
2. Select the required participant
withor.
3. Activate the check with.
If communication between the two
units is verified, ”Check OK”
appears in the display.
If communication is not verified,
”Check not OK” appears.
4. To check further participants,
follow the steps described in
points 2 and 3.
5. Press w andsimultaneously
for approx. 2 seconds.
”Check” flashes until the check
is completed.
The display of the selected
participant flashes for approx.
60 seconds.
Check the LON connection.
The participant check is
terminated.
5285 941 v.1.6
67
Page 68
Start-up
Steps
7. Match the control unit to the system type
8. Check outputs (actuators) and sensors
(continued)
Relay test
Set the following coding addresses in
Coding 2:
”00” System type
”02” Burner type
”03” Oil or gas-fired operation
”0C” Return temperature raising
”4C” Plug sÖ function
”4d” Plug sL function
”4E” Plug gS function
Carry out relay test
1. Pressandsimultaneously for
2. Select relay outputs with theor
See page 116 for coding 2.
Relay test is activated.
approx. 2 seconds.
button.
3. Press.
The following relay outputs can be
selected depending on the system
equipment installed:
Burner stage 1 ON
Burner stage 1 + 2 ON
Burner modulation open
Burner modulation neutral
Burner modulation closed
Output 20 ON
Output 29 ON
Output 52 open/closed/neutral
DHW tank pump ON
DHW circulation pump ON
Heating circuit pump (M2) ON
Relay test is terminated.
Mixing valve (M3) Closed
Central fault indicator ON
LED selector button ! illuminated.
LED selector button ! illuminated.
LED selector button ! illuminated.
LED selector button ? illuminated.
LED selector button § illuminated.
LED selector button ? illuminated.
68
Heating circuit pump (M3) ON
Mixing valve (M2) Open
Mixing valve (M2) Closed
Mixing valve (M3) Open
LED selector button ? illuminated.
LED selector button § illuminated.
LED selector button § illuminated.
All LEDs extinguished.
5285 941 v.1.6
Page 69
Start-up
Steps
(continued)
Relaistest
9. Match the coding addresses
Check sensors
1. Press.
Scanning of operating status
information is activated
2. Scan actual temperatures with
(see page 77).
or.
3. Press.
Scanning is terminated.
Match control unit to modulating burner
Please note:
The burner must be adjusted. In order to achieve a wide modulation range, the
minimum output should be set as low as possible (take chimney/flue system
into account).
1. Start up the burner.
Burner mod. open
Burnermod. closed
Burner mod. open
2. Pressandsimultaneously
for approx. 2 seconds.
3. Withfunction
Activate ”Burner mod. open” and
wait until the actuating drive of the
burner is at maximum output.
4. Establish the maximum burner
out-put through the fuel
consumption.
5. Withfunction
Activate ”Burner mod. closed” and
measure the time it takes for the
actuating drive of the burner to
reach the minimum output.
6. Establish the minimum burner
output (basic output) through the
fuel consumption.
7. Withfunction
Activate ”Burner mod. open” and
stop the actuating drive by pressing
after one-third of the time
measured in point 5.
The relay test is activated.
Make a note of the value.
Make a note of the value.
Make a note of the value.
5285 941 v.1.6
8. Establish the partial output through
the fuel consumption.
9. Press.
Make a note of the value.
The relay test is terminated.
69
Page 70
Start-up
Steps
9. Match the coding addresses (continued)
(continued)
Address Setting of
05the partial output (see point 8) as a percentage proportion of the
08units and tens digits of the maximum output established in point
09hundreds digit of the maximum output established in point 4: e.g.
0Athe basic output (see point 6) as a percentage proportion of the
15the operating time in seconds established in point 5
You will find details of other possible settings in the sections entitled
”Coding 1” and ”Coding 2” (see page 114 and 116).
70
5285 941 v.1.6
Page 71
Start-up
Steps
(continued)
10. Adjust the heating curves
The heating curves represent the relationship between the outdoor temperature
and the boiler water or supply temperature. Put simply: The lower the outdoor
temperature, the higher the boiler water temperature. In turn, the room
temperature is dependent on the boiler water temperature.
Slope
The slope of the heating curve is
normally within the range marked
3.4
3.2
3.0
2.8
2.6
2.4
A for underfloor heating systems
B for modulating heating systems
2.2
2.0
1.8
1.6
1.4
1.2
C for heating systems with boiler
water temperatures over 75°C.
Factory settings:
Slope ”n” = 1.4
Shift ”N”= 0
See conversion chart on the back
of the manual for °F.
1.0
0.8
0.6
Boiler water
= flow temperature in °C
0.4
0.2
Outdoor temperature in °C
1. Set the desired room temperature
Desired room temperatures can
be set separately for each heating
circuit.
Normal room
temperature
Reduced room
temperature
Normal room temperature
Set the desired day temperature with
20
the set-point selector.
Reduced room temperature
14
Press tm to call up the desired night
temperature; adjust the desired night
The value is automatically
accepted after approx. 2 seconds.
temperature with theor
button.
5285 941 v.1.6
Pressto confirm the selected
value.
The display changes and shows
the boiler water temperature.
71
Page 72
Scanning service information
Press“OK”and“+”or
Overview of service levels
FunctionButton combinationTo exitPage
Temperatures, boiler coding cards
and scans
Relay testPress 9 and “OK” simultaneously
Participant check (in conjunction
with LON)
Operating status informationPress
Service scan (if ”Service” flashing)
Adjustment of display contrast
Press 9 and rw simultaneously
for approx. 2 seconds
for approx. 2 seconds
Press w and “OK” simultaneously
for approx. 2 seconds
Press “OK” and “+” or
“OK” and “-” simultaneously
Press “OK”
Press “OK”
Press w and “OK” simultaneously
for approx. 1 second
Press
Press “OK”
Display darkens
Display brightens
73
68
66
77
74
––
––
72
5285 941 v.1.6
Page 73
Temperatures, boiler coding cards and scans
Scanning service information
Outdoortemp.damped
-5
1. Press 9 and rw simultaneously
for approx. 2 seconds.
2. Select the required data for scanning
with theorbutton.
3. Press.Exit diagnosis level.
The following values can be scanned
depending on the system equipment
installed:
Software version
Extension kit for mixing valve circuit M3
0
to
0
to
F
F
Software version
Control unit
8
0
to
F
Free
0
Software version
to
Extension kit for mixing valve circuit M2
F
Software version
Programming unit of control unit
(continued)
Scan 3
Scan 3
0
1
5285 941 v.1.6
2
8
0
1
0
to
F
Operating mode of mixing valve circuit M2 Coding
Without remote controlA0: 0
0
1
With Vitotrol 200 remote controlA0: 1
2
0
to
Software version
F
Remote control for system circuit A1
Operating mode of system circuit A1 Coding
Without remote controlA0: 0
With Vitotrol 200 remote controlA0: 1
With Vitotrol 300 remote controlA0: 2
With Vitotrol 300 remote controlA0: 2
2
Software version
Remote control for mixing valve circuit M2
88888
0
to
Software version
F
Remote control for mixing valve circuit M3
Operating mode of mixing valve circuit M3 Coding
Without remote controlA0: 0
With Vitotrol 200 remote controlA0: 1
With Vitotrol 300 remote controlA0: 2
75
Page 76
Scanning service information
Scan5
Temperatures, boiler coding cards and scans
Scan 4
Scan 4 is not assigned.
Scan 5only in conjunction with LON communication module
8
0
0
0
to
F
Scan 6only in conjunction with LON communication module
0
to
F
to
F
Viessmann participant number
0
to
F
to
F
Subnet address/system number
88888
0
to
Node address
F
(continued)
Scan 6
0
to
Tool/Auto
F
SNVT configuration
Scan 7
Scan 7
8
0
to
0
to
F
F
Software version
Communication coprocessor
0
Software version
to
F
Neuron chip
8
to
88888
LON participant
0
1
F
0
No participant connected
1
to
Number of participants
F
88888
0
to
F
76
0
to
Equipment identification code
F
Free
Free
Free
Free
5285 941 v.1.6
Page 77
Scanning operating status information
Scanning service information
Outdoor temp erature
12
1. Press.
2. Select the required operating status
data for scanning with theor
button.
3. Press.
The following operating status
information can be scanned depending
on the system equipment installed:
Participant number
Holiday program
with date of departure and return
Holiday program active
Outdoor temperature
Boiler temperature
Flue gas temperature
Sensor 17A
Sensor 17B
DHW temperature
DHW temperature 1
DHW temperature 2
Supply temperature
Burner hours run
– 1st stage burner
– 2nd stage burner
Number of burner starts
Fuel consumption
Operating status scanning mode
is activated.
Exit the operating status scanning
mode.
Only displayed when LON
communication module is installed.
If holiday program has been
entered.
When the holiday program is
activated.
Only displayed if flue gas
temperature sensor is connected.
Only displayed if sensor is
connected.
Only displayed if DHW tank
temperature sensor is connected.
Only displayed if two DHW tank
temperature sensors are connected.
Only displayed in conjunction with
mixing valve circuits.
Reset hours runs, number of
burner starts and fuel consumption
after carrying out maintenance.
By pressing D, the values can be
individually reset to zero.
Only displayed if selected via
coding addresses ”26” or ”29”.
Position stated in %.
Pressto select the respective
language as the permanent
language for all displays.
77
Page 78
Scanning service information
Scanning and resetting the ”Service” display
When the limit values selected via coding addresses ”1F”, ”21” and ”23” (see
page 120) are reached, the ”Service” display flashes on the programming unit.
Please note:
If a service is carried out before ”Service” is displayed, set the coding address
”24: 1” and then coding address ”24: 0”.
Service
MFlue gas temperature
220
Boiler temperature
61
°C
Press.Service scan is activated.
Scan the service messages with the
orbutton.
Pressand confirm the display
”Acknowledge: Yes” by pressing
.
Press.Service scan is terminated.
The ”Service” display is
extinguished.
Please note:
An acknowledged service
message can be displayed again
by pressing(for approx.
3 seconds).
78
After carrying out maintenance,
reset coding ”24: 1” (see page 120)
to ”24: 0”.
If necessary: After carrying out
maintenance
Press.
Reset burner hours run, number
of burner starts and fuel
consumption.
Press.
If necessary: After carrying out
maintenance
Pressand rw simultaneously
for approx. 4 seconds.
Reset ”Max. flue gas temp.” to
the current value by pressing D.
Press.
If coding address ”24” is not
reset, the ”Service” display will
re-appear at 07:00 hrs on Monday.
See ”Scanning operating status
information” on page 77.
See ”Temperatures, boiler coding
cards and scans” on page 74.
5285 941 v.1.6
Page 79
Troubleshooting steps
Troubleshooting
Diagnosis1. Establish fault message or ascertain behaviour of system
2. Look for the corresponding cause of the fault in the
diagnosis tables
Please note:
Retrieve fault codes from the fault memory
3. Establish the action required in the table
Correction4. Correct the fault
5285 941 v.1.6
79
Page 80
Troubleshooting
Diagnosis
Faults with fault display on the programming unit
Fault
57
Fr
Fault
Mo
1
wA
57
ºC
Outdoor sensor
DBG-
1
101
Fault
DBG-
1
672
Acknowledge? Yes
1
Outdoor sensor
DBG-
1
101
When a fault message is transmitted,
--Fault-- flashes in the display 1 of the
programming unit.
Search fault
1. Press.
2. Other fault codes which may be
stored can be called up by pressing
theorbutton.
Structure of fault display
Fault display
(”Plain language” or ”Fault”)
Fault code
(meaning: see page 70)
Fault number
(1 to 10)
Fault symbol
The meaning of the fault code is
explained in the table on page 81
onwards.
The fault can be acknowledged
by pressing. The fault message
in the display 1 is blanked out;
the red fault indicator 2 continues
to flash.
The central fault indicator
connected to plug gÖ is switched
off. If an acknowledged fault is not
rectified by 07:00 hrs on the
following day, the fault message
will re-appear in the display.
To retrieve an acknowledged fault
message
Pressfor approx. 3 seconds; select
the acknowledged fault by pressing the
orbutton.
The fault is then displayed
Please note:
The red fault indicator 2 flashes
whenever there is a fault.
80
Faults displayed in plain language
Burner
Fixed high limit
Safety circuit, potential free
Ext. fault
Outdoor sensor
Supply sensor
Boiler sensor
DHW tank temperature sensor 1
Only displayed if a second DHW
tank temperature sensor is
connected.
Only displayed if the control unit is
coded as the fault manager.
5285 941 v.1.6
Page 81
Troubleshooting
Faultcode
Diagnosis
Faults with fault display on the programming unit (continued)
in display
0f
10
18
30
38
40
44
48
4c
50
51
58
59
5285 941 v.1.6
(continued)
Behaviour of system
Controlled operationService required
Operates on basis of 0°C outdoor
temperature
Operates on basis of 0°C outdoor
temperature
Burner is switched on and off by the
adjustable high limit
Burner is switched on and off by the
adjustable high limit
Mixing valve is closedShort circuit
Mixing valve is closedShort circuit
Mixing valve is closedOpen circuit
Mixing valve is closedOpen circuit
DHW tank heating pump ON:
Desired boiler temperature = desired
DHW tank temperature, priority controls
are cancelled.
In conjunction with DHW tank heating
system:
DHW tank heating is switched on and off
by DHW tank temperature sensor 2.
In conjunction with DHW tank loading
system:
DHW tank heating is switched on and off
by DHW tank temperature sensor 1.
DHW tank loading pump ON:
Desired boiler temperature = desired
DHW tank temperature, priority controls
are cancelled.
In conjunction with DHW tank loading
system:
DHW tank heating is switched on and off
by DHW tank temperature sensor 2.
In conjunction with DHW tank loading
system:
DHW tank heating is switched on and off
by DHW tank temperature sensor 1.
Cause of faultAction
Carry out maintenance
”0F” is only displayed
in the fault history
Short circuit
Outdoor temperature sensor
Open circuit
Outdoor temperature sensor
Short circuit
Boiler temperature sensor
Open circuit
Boiler temperature sensor
Supply temperature sensor of
mixing valve circuit M2
Supply temperature sensor of
mixing valve circuit M3
Supply temperature sensor of
mixing valve circuit M2
Supply temperature sensor of
mixing valve circuit M3
Short circuit
DHW tank temperature
sensor 1
Short circuit
DHW tank temperature sensor
2
Open circuit
DHW tank temperature sensor
1
Open circuit
DHW tank temperature sensor
2
Please note:
After carrying out main-
tenance, set coding ”24: 0”.
Check outdoor temperature
sensor (see page 99)
Check outdoor temperature
sensor (see page 99)
Check boiler temperature
sensor (see page 101)
Check boiler temperature
sensor (see page 101)
Check supply temperature
sensor (see page 28)
Check supply temperature
sensor (see page 86)
Check supply temperature
sensor (see page 86)
Check supply temperature
sensor (see page 86)
Check DHW tank
temperature sensor
(see page 101)
Check DHW tank
temperature sensor
(see page 101)
Check DHW tank
temperature sensor (see
page 101)
Check DHW tank
temperature sensor (see
page 101)
81
Page 82
Troubleshooting
Faultcode
Diagnosis
Faults with fault display on the programming unit (continued)
in display
60
68
70
78
92
93
94
9a
9b
9c
9f
(continued)
Behaviour of system
Boiler with maximum temperature
No output reduction
Return control open
Boiler with maximum temperature
No output reduction
Return control open
Shunt pump ON continuouslyShort circuit
In conjunction with DHW tank
loading system:
Mixing valve of primary circuit
closed.
No domestic hot water heating
Shunt pump ON continuously
In conjunction with DHW tank
loading system:
Mixing valve of primary circuit
closed.
No domestic hot water heating
Controlled operation
Only the solar control fault codes are
displayed
Controlled operation
Only the solar control fault codes are
displayed
Controlled operation
Only the solar control fault codes are
displayed
Controlled operation
Only the solar control fault codes are
displayed
Controlled operation
Only the solar control fault codes are
displayed
Controlled operation
Only the solar control fault codes are
displayed
Controlled operation
Only the solar control fault codes are
displayed
Cause of faultAction
Short circuit
Temperature sensor aJA
Open circuit
Temperature sensor aJA
Temperature sensor aJB
Open circuit
Temperature sensor aJB
Short circuit
Collector temperature sensor S1
on the Vitosolic
Short circuit
Temperature sensor S3 on the
Vitosolic
Short circuit
Collector temperature sensor S2
on the Vitosolic
Open circuit
Collector temperature sensor S1
on the Vitosolic
Open circuit
Temperature sensor S3 on the
Vitosolic
Open circuit
DHW tank temperature sensor S2
on the Vitosolic
Fault on solar control message
will display if no fault code is
assigned to the fault
Check temperature sensor
(see page 102)
Check temperature sensor
(see page 102)
Check temperature sensor
(see page 102)
Check temperature sensor
(see page 102)
Check sensor on the solar
control
Check sensor on the solar
control
Check sensor on the solar
control
Check sensor on the solar
control
Check sensor on the solar
control
Check sensor on the solar
control
Check the solar control
82
5285 941 v.1.6
Page 83
Troubleshooting
Faultcode
Diagnosis
Faults with fault display on the programming unit (continued)
in display
aa
ab
ac
b0
b1
b4
(continued)
Behaviour of system
Controlled operationTherm-Control configuration
Controlled operation,
DHW tank may be cold
Controlled operationReturn temperature raising
Controlled operationShort circuit
Controlled operationCommunication fault
Emissions test modeInternal faultCheck electronics board
Cause of faultAction
fault: plug aJA of
Therm-Control temperature
sensor not inserted
DHW tank loading system
configuration fault: coding ”55: 3” is
set, but plug aJB is not inserted and/
or coding ”4C: 1” and ”4E: 1” not set
configuration fault: coding ”0C: 1” is
set, but plug aJA is not inserted
and/or coding ”4E: 0” is not set
Flue gas temperature sensor
Programming unit
Insert plug aJA
On Vitocrossal:
Check that coding ”0d: 0”
is set.
Insert plug aJB and check
codings
Insert plug aJA and check
codings
Check flue gas temperature
sensor (see page 29)
Check connections, if
necessary replace
programming unit
Boiler controlled on basis of
adjustable high limit
Controlled operationOpen circuit
Mixing valve continues in control
mode
Controlled operation without
remote control
Controlled operation without
remote control
Controlled operation without
remote control
Controlled operationIncorrect LON communication moduleReplace communication
Invalid hardware code
Internal fault
Boiler coding card
Flue gas temperature sensor
Communication fault
Circuit board for mixing valve
extension
Communication fault
Vitotrol remote control,
system circuit A1
Communication fault
Vitotrol remote control,
mixing valve circuit M2
Communication fault
Vitotrol remote control,
mixing valve circuit M3
Check the control software
circuit board and confirm the
coding address:
- Enter coding 2 (see page 125
for instructions).
- Change code 8A to 176.
- Confirm coding 92:1
Insert boiler coding card or
replace if defective
(see page 22)
Check flue gas temperature
sensor (see page 104)
Check circuit board
Check connections, cable and
coding address ”A0”
(see Coding 2 page 127)
Check connections, cable and
coding address ”A0”
see Coding 2 page 127
Check connections, cable and
coding address ”A0”
see Coding 2 page 127
module
65
5285 941 v.1.6
83
Page 84
Troubleshooting
Faultcode
toDE3
Diagnosis
Faults with fault display on the programming unit (continued)
in display
c1
c2
c4
c8
c9
ca
cb
cd
cEe
cf
d1
(continued)
Behaviour of system
Boiler cools downExternal safety equipmentCheck connection of plug
Controlled operationOpen circuit
Controlled operationFault
Boiler cools downFault
Boiler cools downFault
Boiler cools downFault
Boiler cools downFault
Controlled operationCommunication fault
Controlled operationCommunication fault
Controlled operationFault
Boiler cools downBurner faultCheck burner
Cause of faultAction
KM-BUS to solar control
Input module 0-10V
Low water indicator
Maximum pressure limiter
Minimum pressure limiter or
maximum pressure limiter 2
Additional fixed high limit
Vitocom 300
Plug-in adaptor for external safety
equipment
LON communication module
aBÖ
Check external safety
equipment (see page 40)
Check KM-BUS connection and
solar control. Without solar
control, set coding address
“54: 0”
Check all connections, cables etc.
Replace function expansion
module; without expansion
module set coding address
“9d: 0”
Check water level of system,
reset low water indicator
Check system pressure, reset
maximum pressure limiter
Check system pressure, reset
minimum or maximum pressure
limiter
Check system pressure, reset
fixed high limit, reset flue gas
damper
Check connections and
Vitocom 300
Check plug-in adaptor for
external safety equipment
Replace communication module
d4
d6
d7
d8
da
db
84
Boiler cools downFixed high limit has operatedCheck fixed high limit
Controlled operationFault at DE1 in the plug-in
Controlled operationFault at DE2 in the plug-in
Controlled operationFault at DE3 in the plug-in
Controlled operation without
influence of room
temperature
Controlled operation without
influence of room
temperature
adaptor for external safety equipment
adaptor for external safety equipment
adaptor for external safety equipment
Short circuit
Room temperature sensor, system
circuit A1
Short circuit
Room temperature sensor,
mixing valve circuit M2
Check connection at inputs DE1
to DE3
Check room temperature sensor
(see page 112)
Check room temperature sensor
(see page 112)
5285 941 v.1.6
Page 85
Troubleshooting
Faultcode
Diagnosis
Faults with fault display on the programming unit (continued)
in display
dc
dd
de
df
e0
(continued)
Behaviour of system
Controlled operation without
influence of room temperature
Controlled operation without
influence of room temperature
Controlled operation without
influence of room temperature
Controlled operation without
influence of room temperature
Controlled operationOpen circuit
Cause of faultAction
Short circuit
Room temperature sensor,
mixing valve circuit M3
Open circuit
Room temperature sensor,
system circuit A1
Open circuit
Room temperature sensor,
mixing valve circuit M2
Open circuit
Room temperature sensor,
mixing valve circuit M3
LON communication module
Check room temperature sensor
(see page 112)
Check room temperature sensor
(see page 112)
Check room temperature sensor
(see page 112)
Check room temperature sensor
(see page 112)
Check connection
(see page 96)
Retrieving fault codes from the fault memory (fault history)
All faults which have occurred are stored and can be retrieved by scanning.
The scanning sequence starts with the most recently stored fault code.
1 23 4 5 67
1. Pressandsimultaneously for
approx. 2 seconds.
2. Access the individual fault codes by
pressing theorbutton.
Sequence of
stored fault
codes
1
.
.
.
10
Fault code
Last (most recent)
fault code
.
.
.
Last fault code but
nine
Scanning of fault history is
activated.
All stored fault codes can be
deleted by pressing.
5285 941 v.1.6
3. Press.
Scanning of fault history is
terminated.
85
Page 86
Functional description
Boiler temperature control
Brief description
The boiler water temperature is
controlled by switching the burner
stages or modulation on and off.
The desired boiler water temperature
value is determined by the set-point
supply temperature value of the boiler
circuit (A1), the mixing valve circuits
or the heating circuits connected via
the LON BUS, through the external
request facility and the desired
domestic hot water temperature, and
is dependent on the boiler and the
heating and control facilities installed.
In conjunction with Therm-Control:
The desired boiler water temperature
is increased when the temperature
falls below the set-point value on
the sensor of the Therm-Control.
Functions
The boiler water temperature is
measured via a multiple sensor well by
three sensors separately:
Fixed high limit FHL (liquid
expansion)
Adjustable high limit AHL (liquid
expansion)
Boiler temperature sensor BTS
(change in resistance PT 500)
When the domestic hot water tank
is heated up, a desired boiler water
temperature is selected which is
20°C / 36°F higher than the desired
DHW tank water temperature (this
value can be changed via coding
address ”60”).
Upper limits of control range
Fixed high limit FHL 110°C / 230°F,
can be adjusted to 99°C / 210°F
Adjustable high limit AHL 95°C, can
be adjusted to 100°C / 212°F
Electronic maximum limit
Setting range: 20 to 127°C / 68 to
261°F
The maximum limit for the boiler
water temperature is defined in
coding address ”06”.
Coding addresses which influence
the boiler temperature control
02 to 06, 08 to 0b, 13 to 1C
See page 114 onwards for
description.
Lower limit of control range
The control unit regulates the
boiler water temperature in
normal operation and in the
frost protection mode according
to the boiler concerned (boiler
coding card).
Control sequence
Boiler temperature falls
The burner switch-on signal is set for
a boiler water temperature set-point
value of –2°C / -4°F, and the burner
starts its own monitoring program.
Depending on the range of additional
control facilities and the method of
firing, burner override can be delayed
by a few minutes.
86
Boiler temperature rises
The switch-off point of the burner is
defined by the switch-off differential
(coding address ”13”).
5285 941 v.1.6
Page 87
Heating circuit control
Brief description
Functional description
The control unit has control loops for a
system circuit and two mixing valve
circuits.
The supply temperature set-point value
is determined by the outdoor
temperature, the desired room
temperature, the operating mode and
the heating curve.
Functions
The heating circuit is dependent on the
boiler water temperature and its control
range limits.
The only control element is the heating
circuit pump.
The supply temperature of the mixing
valve circuits is measured by the
supply temperature sensor (contact
sensor).
Time program
The timer of the control unit changes
the operating mode at the programmed
times in the ”Central heating and
DHW” heating program, switching
between ”Central heating with normal
room temperature” and ”Central
heating with reduced room
temperature”.
Each operating mode has its own
set-point value.
Outdoor temperature
A heating curve must be adjusted to
match the control unit to the building
and the heating system.
The heating curve determines the
set-point boiler water temperature
value as a function of the outdoor
temperature. Control takes place on
the basis of the mean outdoor
temperature. This is derived from the
actual and the damped outdoor
temperature.
The heating curve can be changed via
the set-point or operating mode
selector switches.
The supply temperature of the mixing
valve circuits is controlled by opening
and closing the mixing valves in steps.
The mixing valve motor control varies
the actuation and interval times as a
function of the control difference
(control deviation).
Domestic hot water temperature
With priority control:
While the DHW tank is being heated,
the set-point supply temperature
value is set to 0°C / 32°F .
The heating circuit pump is
switched off.
Without priority control:
The heating circuit control continues
to operate as normal with the
set-point value unchanged.
With modulating priority control
(only in conjunction with mixing
valve circuit):
The heating circuit pump remains
switched on. The set-point supply
temperature of the heating circuit
is lowered as long as the set-point
boiler water temperature is not
reached while the DHW tank is
being heated. The set-point supply
temperature is dependent on the
difference between the set-point and
the current boiler water temperature,
the outdoor temperature, the heating
curve slope and the setting of the
coding address ”A2”.
The supply temperature of the system
circuit corresponds to the boiler water
temperature.
Coding addresses which influence the
heating circuit control
9F
A2 to A7, A9,
C4 to C7, C8
F1, F2.
See page 114 onwards for description.
Room temperature
In conjunction with room
temperature dependent control:
Compared with the outdoor
temperature, the room temperature
has a greater influence on the
set-point boiler water temperature.
The magnitude of this influence can
be changed via coding address ”b2”.
In conjunction with mixing valve
circuit:
With control differences
(i.e. deviations from the current
value) of over 2°C / 4°F room
temperature, this influence can be
intensified (via coding address ”b6”,
rapid heating/setback).
5285 941 v.1.6
87
Page 88
Functional description
Heating circuit control
Functions (continued)
Summer energy saving function
(heating circuit pump logic)
If the outdoor temperature is higher
than the preset room temperature
set-point value, the heating circuit
pump is switched off and the set-point
supply temperature value is set to
0°C / 32°F.
The switching threshold can be
individually selected via coding address
”A5”.
Extended summer energy saving
function
The heating circuit pump can be
switched off
If the outdoor temperature exceeds a
value preselected via coding address
”A6”
If the set-point room temperature is
reduced via coding address ”A9”
In conjunction with mixing valve
circuit:
If the mixing valve has been closed
for longer than 12 minutes (mixing
valve energy saving function, coding
address ”A7”)
Slab curing function
(only in conjunction with mixing valve
circuit)
(continued)
System dynamics – mixing valve
circuit (only in conjunction with
mixing valve circuit)
The control behaviour of the mixing
valve can be influenced via coding
address ”C4”.
Frost protection
A supply temperature of 15 to 22°C /
59 to 72°F is assured for outdoor
temperatures below +1°C / 34°F
(two-point control).
For possible changes, see coding
address ”A3” (variable frost threshold).
Therm-Control
Heating circuit output reduction takes
place if the boiler return temperature
falls below the setpoint value (value
read on the therm-control sensor).
Heating circuit mixing valves modulate
closed until the Therm-control sensor
is satified.
Supply temperature control
Differential temperature:
The differential temperature can be
selected via coding address ”9F”,
factory setting: 8°C / 14°F.
The differential temperature is the
minimum difference by which the
boiler water temperature should
exceed the highest currently required
supply temperature of the mixing
valve circuit.
System with only one mixing
valve circuit:
The desired boiler water
temperature is automatically
controlled at 8°C / 14°F above
the desired supply temperature
value.
System with heating circuit and
mixing valve circuit:
The desired boiler water
temperature is controlled according
to its own heating curve. The
temperature difference of
8°C / 14°F.
from the desired supply
temperature is preset in the
factory.
Please note:
The slab curing function is selectable
on the basis of four different
temperature curves. The curves are
activated via coding address ”F1”
(see page 134).
When the slab curing function is
activated, the heating circuit pump of
the mixing valve circuit is switched on
and the supply temperature is
controlled according to the selected
curve. When the slab curing time (30
days) has expired, the mixing valve
circuit is automatically controlled on
the basis of the preset parameters.
88
Boiler water temperature/
supply temperature in °C
Outdoor temperature in °C
A Max. boiler water temperature
B Slope = 1.8 Heating circuit
C Slope = 1.2 Mixing valve circuit
D Boiler water temperature
(with differential temperature =
8°C / 14°F.)
E Minimum boiler water
temperature
5285 941 v.1.6
Page 89
Functional description
Heating circuit control
Functions (continued)
Upper limit of control range
Electronic maximum limit
Setting range:
1 to 127°C / 34 to 260°F.
Change via coding address ”C6”.
Please note:
The maximum limit does not replace
the limit thermostat required for
underfloor heating systems.
Limit thermostat for underfloor heating
systems:
The limit thermostat switches the
heating circuit pump off when the
supply temperature rises above the
preset value. In this situation, the
supply temperature cools down only
slowly, i.e. automatic re-starting can
take several hours.
(continued)
Lower limit of control range
Electronic minimum limit
Setting range:
1 to 127°C / 34 to 261°F.
Change via coding address ”C5”.
Control sequence
Mixing valve circuit
The mixing valve motor is not activated
within the ”neutral zone”
(±1°C / 2°F).
Supply temperature falls
(Set-point value –1°C / -2°F)
The mixing valve motor receives the
signal ”Open mixing valve”.
The greater the control difference, the
longer the duration of the signal and
the shorter the duration of the
intervals.
Supply temperature rises
(Set-point value +1°C / +2°F):
The mixing valve motor receives the
signal ”Close mixing valve”.
The greater the control difference, the
longer the duration of the signal and
the shorter the duration of the
intervals.
5285 941 v.1.6
89
Page 90
Functional description
DHW tank temperature control
Brief description
The DHW tank temperature control is a
constant value control. It operates on
the basis of switching the circulation
pump for heating the DHW tank on and
off.
The switching differential is ±2.5°C /
4.5°F.
Functions
Time program
An automatic or an individual time
program can be selected for domestic
hot water heating and the DHW
circulation pump.
In the automatic program, domestic
hot water heating precedes the heat-up
phase of the heating circuit by 30
minutes. On systems with several
heating circuits, the time program is
based on the switching times of the
first heating circuit to be heated.
In the individual time program, up to
four switching times per day can be
set on the timer for domestic hot water
heating and the DHW circulation pump.
Once started, heating of the DHW tank
is always completed regardless of the
time program.
The switching times for domestic hot
water heating and the DHW circulation
pump are effective for all heating
circuits. Individual switching times can
be assigned to each heating circuit via
the coding address ”7F”.
During DHW tank heating, a constant
maximum boiler water temperature is
set and space heating is switched off
(DHW tank priority control optional).
Frost protection function
If the domestic hot water temperature
falls below 10°C / 50°F, the
domestic hot water DHW tank is
heated to 20°C / 68°F.
Additional function for domestic hot
water heating
This function is activated when a
second DHW setpoint value is selected
via coding address ”58” and the 4th
activation period for domestic hot
water heating is activated.
Desired domestic hot water
temperature
The desired domestic hot water
temperature can be set in the range
of 10 to 60°C / 50 to 140°F. The
set-point range can be extended to
95°C / 203°F via coding address
”56”.
The desired domestic hot water
temperature can be set on the
programming unit of the control unit
and on the Vitotrol 300 remote control
(if installed).
The set-point value can be assigned via
coding address ”66”.
Coding addresses which influence
the DHW tank temperature control
55, 56, 58 to 62, 64, 66, 70 to 75,
7F, A2.
See page 114 onwards for description.
DHW circulation pump
The DHW circulation pump supplies
hot water to the take-off points at
selectable times. Up to four
switching times can be set on the
timer.
Additional control facilities
The domestic hot water supply can
be blocked and released via
changeover of the heating program.
System with DHW tank loading system
The functions described above also
apply in conjunction with DHW tank
loading systems.
Set the following codings:
”4C: 1”, ”4E: 1”, ”55: 3”.
90
5285 941 v.1.6
Page 91
Functional description
DHW tank temperature control
Control sequence
DHW tank temperature falls
(Set-point value –2.5 °C / 4.5 °F,
selectable via coding address ”59”)
The desired boiler water temperature
is set 20 K higher than the DHW
temperature set-point value (selectable
via coding address ”60”).
The circulation pump for heating the
DHW tank is switched on immediately
(Coding ”61: 01”).
Boiler temperature-dependent switching
of the circulation pump for heating the
DHW tank (Coding ”61: 00”):
The circulation pump is switched on
when the boiler water temperature is
7°C / 13°F higher than the domestic
hot water temperature.
With priority control:
(Coding ”A2: 2”)
The supply temperature set-point
value is set to 0 °C / 32°F when the
DHW tank is being heated. The
mixing valve is closed and the
heating circuit pump is switched off.
Without priority control:
The heating circuit control continues
to operate as normal with the
setpoint value unchanged.
With modulating priority control (only
in conjunction with mixing valve
circuit):
The heating circuit pump remains
switched on. The desired supply
temperature is lowered as long as the
desired boiler water temperature is
not reached while the DHW tank is
being heated. The desired supply
temperature is dependent on the
difference between the desired and
the current boiler water temperature,
the outdoor temperature, the heating
curve slope and the setting of the
coding address ”A2”.
5285 941 v.1.6
DHW tank temperature rises
(Set-point value +2.5 / 4.5°F)
The boiler water temperature set-point
value is reset to the weathercompensated value.
When the DHW tank has been
Circulation pump for heating the
With priority control
With optimized DHW tank heating
(continued)
heated up, the circulation pump for
heating the DHW tank continues to
run until:
the temperature difference between
the boiler water and domestic hot
water is less than 7°C / 13°F, or
the desired, weather-compensated
boiler water temperature is
reached, or
the desired domestic hot water
temperature is exceeded by
5°C / 9 °F.
The max. run-on time is 15 minutes
(selectable via coding address ”62”).
DHW tank without run-on time
(Coding ”62: 00”):
The circulation pump is switched off
immediately.
(Coding ”A2: 2”):
The supply temperature set-point
value is reset to the weathercompensated value.
The heating circuit pump is
switched on.
(Coding ”55: 1”):
Optimized DHW tank heating takes
into account the rate at which the
temperature increases during
domestic hot water heating.
It also takes into account whether
the boiler must supply heat for space
heating purposes after heating up the
DHW tank or whether the residual
heat of the boiler should be
transferred to the domestic hot
water DHW tank.
The control unit determines the
switch-off time of the burner and the
circulation pump accordingly so that
the desired domestic hot water
temperature is not substantially
exceeded after DHW tank heating is
completed.
Adjustable high limit98
Outdoor temperature sensor99
Boiler temperature sensor and DHW tank temperature sensor101
Strap-on temperature sensor/immersion temperature sensor102
Flue gas temperature sensor104
Installation examples105
Vitotrol 200106
Vitotrol 300108
Rated voltage:120V
Rated frequency: 60 Hz
Rated current:2 x 6A
Power
consumption:10W
Protection class: I
Degree ofIP 20 D to
protection:EN 60 529, to be
guaranteed by
mounting/integration
Method ofType 1B to
operation:EN 60 730-1
Ambient temperature
During
operation:0 to 40°C /
32 to 104°F
For use in boiler rooms
(normal ambient conditions)
During storage and
transport:–20 to 65˚C /
-4 to 149°F
Relay outputs at 120V for
Heating circuit
pumps or control
output sÖ:2 FLA, 120 VAC
Circulation
pump for heating the DHW tank
sA:2 FLA, 120 VAC
DHW circulation
pump sK:2 FLA, 120 VAC
Shunt
pump sL:2 FLA, 120 VAC
Central fault
indicator gÖ:2 FLA, 120 VAC
Mixing valve
motor return
temperature
raising
or
3-way valve
DHW tank heating system
or
mixing valve
motor gS:0.1 FLA,
The motherboard contains:
Relays and outputs for activating
the pumps, the control elements
and the burner
Plug-in location for power supply
unit board and boiler control
section
The motherboard contains:
Plugs for sensors, communication
connections and external
equipment
Plug-in locations for electronics
board, LON communication module,
programming unit, boiler coding
card and Optolink board
Power supply unit board, Part No. 7823 991
Electronics board, Part No. 7828 193
The power supply unit board
contains the low-voltage supply
for the entire electronics.
The board contains the
microprocessor with the software
When replacing the board:
1. Make a note of codings and
settings on the control unit.
2. Replace the board.
3. Set coding ”8A: 176” and set
coding address ”92” (not listed
in the overview) to ”92: 165”.
94
5285 941 v.1.6
Page 95
Additional information
System components
Mixing valve extension board, Part No. 7820 193
Electronics board, Part No. 7829 790
(continued)
The board contains the relays for
activating the mixing valve motor
and the heating circuit pump of the
mixing valve circuits M2 and M3.
This is connected to the mixing
valve extension board.
All data are processed and the
outputs (relays) activated.
Optolink/emissions test switch board, Part No. 7820 165
The circuit board contains:
Operating status indicator
Fault indicator
Optolink laptop interface
Emissions test switch
Programming unit, Part No. 7823 986
Emissions test switch for flue gas
measurements with the boiler
operated with constant boiler water
temperature for a short time.
The burner is switched on
(this can be delayed if the system
incorporates a fuel preheater)
all pumps are switched on
the mixing valve remains in its
control mode
the boiler water temperature is
controlled by the adjustable high
limit ”R”.
The programming unit is inserted in
the control unit.
For setting:
Heating program
Set-point values
Switching times
Heating curve (shift and slope)
Date
Time
Energy saving and party mode
5285 941 v.1.6
For displaying:
Temperatures
Operating status information
Faults
95
Page 96
Additional information
System components
Front panel with heating circuit selector buttons, Part No. 7818 623
Fuse box, Part No. 7820 172
(continued)
For displaying and selecting the
heating circuit.
The fuse box contains:
Fixed high limit
Adjustable high limit
Fuses
Heating system switch
TEST button
LON communication module, Part No. 7172 173Accessory
A
LON
LON
C
A Control unit or Vitocom 300
B Connecting cable for data transfer
between the control units
(accessory)
C Terminal resistor,
Part No. 7143 497
AA
LON
B
LON
B
LON
C
The communication module is
inserted in the control unit.
Interruption of communication is
indicated.
LON
1 terminal resistor is inserted on
each of the first and last control
units.
96
5285 941 v.1.6
Page 97
Additional information
System components
Boiler coding card
Fuses
F1
(continued)
Vitotronic 300
in conjunction with
Vitorond 20010207820 142
Vitocrossal 300, Type CT310407820 144
Vitocrossal 200, Type CM210417820 145
Boiler coding cardPart No.
F1: 6.3 A, 250 V for protecting
the control elements, pumps and
electronics
Mounting location: see drawing
Part No. 7404 365
F2: 6.3 A, 250 V for protecting
the burner
Mounting location: see drawing
Part No. 7404 365
F2
TEST button, Part No. 7819 314
For checking the fixed high limit.
See description on page 65.
5285 941 v.1.6
97
Page 98
Additional information
System components
Fixed high limit, Part No. 7820 036
Adjustable high limit, Part No. 7817 531
(continued)
The fixed high limit has a factory setting of 110°C/ 230°F.
Electromechanical temperature switch based on the liquid expansion principle
with interlock
Intrinsically safe; interlocking also takes place if the capillary tube is leaking or
if ambient temperatures are below –10°C / 14°F
Limits the boiler water temperature to the maximum permissible value by
cutting out and interlocking
Can be adjusted with the slotted screw A at the rear of the unit to 99°C /
210°F (cannot be reset to 110°C / 230°F once adjusted)
Reset unit by pressing the reset button ”E” on the front of the programming
unit if the temperature has fallen approx. 15 K below the shut down temperature
Central fastening M 10, capillary 3600 mm long
Tests:
Functional check via TÜV TEST button
The adjustable high limit has a factory setting of 95°C / 203°F
Electromechanical temperature switch based on the liquid expansion principle
Controls the maximum boiler water temperature (e.g. in emissions test mode)
Can be adjusted to 100°C / 212°F by altering the setting
of the stop dial or by removing the cams
IMPORTANT
Set the lower limit at least 20°C / 36°F
higher than the domestic hot water
temperature, the upper limit at least
15°C / 27°F lower than the fixed
high limit.
Adjusting shaft 6 mm / 0.27 inches,
flat topped
Adjusting knob pushed onto shaft
from front
Capillary 3600 mm / 141.7 inches long
Sensor 3 mm / 0.1inches thick,
180 mm / 7.1inches long
Tests:
Functional check via emissions test mode
98
5285 941 v.1.6
Page 99
Additional information
System components
(continued)
Outdoor temperature sensor, Part No. 7820 148
Outdoor temperature sensor
600
580
560
540
520
500
480
Resistance in
460
Connection
Check sensor
1. Remove plug !.
2. Check the sensor resistance at
terminals 1 and 2 of the plug.
Outdoor
temperature in
Resistance
in ΩΩΩΩ
ºC / ºF
–10 / 14
0 / 32
20 / 68
480
500
546
3. Disconnect cores from the sensor,
if actual values deviate severely from
the curve, repeat the sensor
measurement and compare with
the actual temperature.
440
420
400
-40-30-20-100102030
-40-22-41432506886
Outdoor temperature in ºC / ºF
4. Depending on the result, replace
cable or outdoor temperature
sensor.
5. Scan actual temperature.
Specification
Protection:IP 43
Permissible ambient temperature
during operation, storage and
transport:
–40 to +70ºC
–40 to 158ºF
5285 941 v.1.6
99
Page 100
Additional information
System components
Outdoor temperature sensor
1.
4.
(continued)
The outdoor temperature sensor should be mounted 2 to 2.5 metres / 6.5 to 8 ft
above ground level on the north or north-west facing wall of the building. In the
case of multi-storey buildings, it should be mounted in the upper half of the
second storey.
Make sure that the sensor is not located over windows, doors and air vents,
nor immediately beneath a balcony or guttering.
Do not paint over the outdoor temperature sensor housing.
5.
3.
1. Remove the cap.
2. Mount the bottom part of the
sensor housing.
3. Pull the sensor wire through the
opening in the terminal
compartment and through the
strain relief provided.
4. Connect the wires to the
terminals.
5. Place the cap over the outdoor
temperature sensor.
A
2.
WARNING
When extending wire, there is the
possibility of exposure to electromagnetic
interference. Avoid running wires
beside or near high voltage 120/240
VAC conductors. If proximity to high
voltage conductors cannot be avoided,
use stranded, twisted pair or shield
design wire. Ensure that only one end
of the shielding is grounded.
A Outdoor temperature sensor
1
100
5285 941 v.1.6
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.