Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the
instructions listed below can cause product/property damage, severe personal injury, and/or loss of life.
Working on the equipment
The installation, adjustment, service,
and maintenance of this product must
Please file in Service Binder
be done by a licensed professional
heating contractor who is qualified and
experienced in the installation, service,
and maintenance of hot water boilers.
There are no user serviceable parts on
the boiler, burner, or control.
Ensure main power supply to
equipment, the heating system, and all
external controls has been deactivated.
Close main oil supply valve. Take
precautions in both instances to avoid
accidental activation of power during
service work.
Ensure that the installation
literature of other applicable
components is referenced.
General Information
Standard installation
Boiler
Model
Rear
Sides
Flue
FloorCombustibles
Alcove installation
Boiler
Model
Rear
Sides
Flue
Top*
FloorCombustibles
VR1-22-27-33
inches
mm
inches
mm
inches
mm
VR1-22-27-33
inches
mm
inches
mm
inches
mm
inches
mm
150
25
150
25
150
6
150
0
0
1
6
0
0
1
6
25
150
25
150
IMPORTANT
Advise owner to keep direct vent
6
150
0
0
1
6
150
0
0
1
6
150
termination and air intake free of
6
debris, snow and ice.
0
0
1
25
6
0
0
1
25
6
WARNING
Viessmann will not assume any
responsibility for possible effects of
an obstructed air intake or exhaust
termination.
NOTE: Surface discoloration on the
outside of the building may occur if the
burner is not properly adjusted.
Viessmann will not accept any
responsibility for such discoloration.
NOTE: Direct Vent exhaust system
operates under a positive pressure
developed by the burner. Make sure all
vent connections and observation port
on the boiler are sealed air-tight by
tightening screws and using high
temperature silicone sealant if
necessary.
NOTE: The vent components must be
supplied without any alteration except
for the length of the flex pipe to be cut
to the desired length.
* 24” with Vitotronic control.
The insulated oil direct vent system is
rated for a 1” clearance to
combustibles.
5351 050 v2.5 09/2012
Page 2
Installation
Installation of Insulated Stainless Steel Flexible Oil Vent
In addition to the following
instructions, also consult
Field Controls Direct Vent
System manual for detailed
instructions on how to install
the venting system.
Ø4”
a
*Boiler-to-vent
transition adaptor
(stainless steel)
Refer to Vitorond 100
Installation and Service
Instructions.
Supports
max. 3’
b
Air intake
Exhaust
12” min. above
anticipated snow line
VRV-4
Vacuum
Relief
Valve
Fig. 1
Use a 4” to 3” reducer (not supplied)
to connect an intake pipe to the Riello
burner.
If no air intake is required a=0 then
provide combustion air supply to
mechanical room where the burner is
installed. The burner requires fresh air
for safe operation and must be installed
in a mechanical room where there are
provisions for adequate combustion
and ventilation air.
Smoke test port
R
1
Avoid dips in the venting system when
using the flexible insulated stainless
steel oil vent.
The direct vent kit includes a VRV-4
vacuum relief valve which must be
installed in the air intake pipe as close
as possible to the burner when using a
Beckett burner (see Fig. 1).
*The direct vent kit includes a
Viessmann-specific stainless steel
boiler-to-vent transition adaptor.
b=15’
a=20’
(max. 2 x 90°elbows)
Each 90° elbow = 3’ e.q.L.
R1=min. wall clearance 28”
(for min. bend radius of
flexible vent pipe)
IMPORTANT
Do not install the regular galvanized
vent pipe adaptor shipped with the
boiler. This galvanized vent pipe
adaptor is intended for chimney venting
application and therefore must be
discarded in a direct vent application.
2
5351 050 v2.5
Page 3
Burner Set-up (Beckett)
Electrical connections (with Aquastat control)
Burner - Beckett
Installations must follow these codes
WARNING
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
"
All field supplied nominal 120 VAC voltage wiring must be sheathed in a flexible metal conduit.
"
Disconnect means, overload protection and low water cut-off must be provided as required by local codes.
"
Connect incoming line voltage HOT (L1) wire to terminal L1, and N to terminal L2 of the Honeywell high limit control (see
wiring diagram on page 5.
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any addtional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
Burner wiring
IMPORTANT
The R7184 or GeniSys 7505P primary
control with valve-on delay (pre-purge)
and burner motor-off delay (post-purge
- factory default settings can be field
adjusted), requires a constant 120
VAC power source supplied to the
BLACK wire on the control (see wiring
diagram on following page).
Fig. 2
Legend
Cable strap (supplied)
Honeywell high limit control
Burner wiring harness (supplied)
5351 050 v2.5
WARNING
Ensure that burner wiring harness is
properly attached and secured to the
boiler side panel using the supplied
cable straps as depicted above. The
cable strap must be coiled on the
boiler side panel so that no slack is
left, allowing the burner/boiler door
to be swung open without
disconnecting the burner wiring
harness from the burner. Failure to
heed this warning may result in
personal injury.
1. The cover mounting plate is not a
conduit connection point. Pass
conduit and attached connector
through the front opening in the
mounting plate or through one of the
knockouts on either side of the cover
and attach it directly to the
burner-mounted 4x4 electrical
junction box.
Room thermostat wiring
1. Install thermostat on inside wall
away from influences of drafts, hot
or cold water pipes, lighting fixtures,
television, sun rays or fireplaces.
2. Follow instructions supplied with
room thermostat. If it has a heat
anticipator, set heat anticipator in
thermostat to match power
requirements of equipment
connected to it. Boiler wiring
diagrams give setting for standard
equipment.
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any addtional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
Burner wiring harness (supplied)
white
black
ground
red
15” *
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
ground
1/4 quick
connect
insulated
flag
red
Fig. 3
white
black
4
5351 050 v2.5
Page 5
Burner - Beckett
Burner Set-up (Beckett)
Wiring diagram (with Aquastat control) with outdoor reset module
WARNING
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
"
All field supplied nominal 120 VAC voltage wiring must be sheathed in a flexible metal conduit.
"
Disconnect means, overload protection and low water cut-off must be provided as required by local codes.
"
Connect incoming line voltage HOT (L1) wire to terminal L1, and N to terminal L2 of the Honeywell high limit control (see
wiring diagram below).
(continued)
Installations must follow these codes
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any additional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
Fig. 4
Legend
Oil solenoid valve
Ignition transformer
Burner motor
CAD cell flame detector
Burner grounding screw
R7184 Series primary control
with post-purge (factory default
setting: 30 sec. - can be field
adjusted; see Beckett burner
manual)
Factory-installed jumper
5351 050 v2.5
WARNING
Ensure that the burner cycles ON and
OFF on proper call for heat before
leaving the job site. Failure to do so
may lead to boiler runaway situation,
which may lead to property damage,
personal injury or death.
CAUTION
A field supplied manual reset high
limit control must be installed at the
outlet pipe of the boiler to interrupt
burner operation should the factory
supplied high limit control fail. This
field supplied high limit control must
be set 20°F above the setting of the
factory supplied high limit control.
The setting of this field supplied high
limit control must never be greater
than 220°F.
5
Page 6
Burner - Beckett
Burner Set-up (Beckett burner with GeniSys primary control)
Wiring diagram (Vitorond 100 with Beckett (NX) burner and Honeywell Aquastat)
Installations must follow these codes
WARNING
Electric shock hazard. Can cause
severe personal injury or loss of life
if power source, including service
switch on boiler, is not disconnected
before installing or servicing.
"
All field supplied nominal 120 VAC voltage wiring must be sheathed in a flexible metal conduit.
"
Disconnect means, overload protection and low water cut-off must be provided as required by local codes.
"
Connect incoming line voltage HOT (L1) wire to terminal L1, and N to terminal L2 of the Honeywell high limit control (see
wiring diagram below).
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any additional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
(continued)
Fig. 5
6
WARNING
Ensure that the burner cycles ON and
OFF on proper call for heat before
leaving the job site. Failure to do so
may lead to boiler runaway situation,
which may lead to property damage,
personal injury or death.
CAUTION
A field supplied manual reset high
limit control must be installed at the
outlet pipe of the boiler to interrupt
burner operation should the factory
supplied high limit control fail. This
field supplied high limit control must
be set 20°F above the setting of the
factory supplied high limit control.
The setting of this field supplied high
limit control must never be greater
than 220°F.
5351 050 v2.5
Page 7
Burner - Beckett
Burner Set-up (Beckett)
Electrical connections (with Vitotronic control)
WARNING
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
(continued)
Installations must follow these codes
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any addtional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
41
#41 plug-in connector
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
Burner wiring
IMPORTANT
The R7184 primary control with
valve-on delay (pre-purge) and burner
motor-off delay (post-purge - factory
default settings can be field
adjusted), requires a constant 120
VAC power source supplied to the
BLACK wire on the control (see
wiring diagram on page 9).
Fig. 6
1.
2.
1. The cover mounting plate is not a
conduit connection point. Pass
conduit and attached connector
through the front opening in the
mounting plate or through one of the
knockouts on either side of the cover
and attach it directly to the
burner-mounted 4x4 electrical
junction box.
Electrical connections
1.Run theplug-in connector cable of
the Vitotronic control down behind
the front panel of the boiler and out
through the bottom. (Fig. 5)
2.Connect the femaleplug of the
burner to the maleplug of the
Vitotronic control. (Fig. 5)
away from influences of drafts, hot
or cold water pipes, lighting fixtures,
television, sun rays or fireplaces.
2. Follow instructions supplied with
room thermostat. If it has a heat
anticipator, set heat anticipator in
thermostat to match power
requirements of equipment
connected to it. Boiler wiring
diagrams give setting for standard
equipment.
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any addtional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
Burner wiring harness (supplied)
Closed end connectors are factory installed on
RED, ORANGE and BLUE wires. These RED,
ORANGE and BLUE wires may or may not be
used in your burner application. See wiring
diagram in this manual which is specific to your
burner application. Do not remove or cut any of
the closed end connectors of the RED, ORANGE
or BLUE wires, unless it is necessary to do so.
RED wire is live (120VAC) at all times. Do not
remove or cut its closed end connector unless it
Viessmann #41-plug
control connection
is necessary to do so. Failure to heed the above
instructions may cause severe personal injury or
loss of life.
B4
BL
O
S3
BK
T2
T1
W
N
G
G
R
L1
Jumper
RED
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
cut this length to 6” for connection
to burner junction box (located
under the burner primary control).
5351 050 v2.5
9
Page 10
Connections
Burner Set-up (Beckett)
(continued)
Wiring diagram (with Vitotronic control)
WARNING
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
Blue and orange wires not used in this
application. DO NOT cut or remove closed
end connector from the wires.
Installations must follow these codes
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any additional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
Burner junction box
2
G
BL
O
BK
R
W
R
BK
W
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
WARNING
Ensure that the burner cycles ON and
OFF on proper call for heat before
leaving the job site. Failure to do so
may lead to boiler runaway situation,
which may lead to property damage,
personal injury or death.
(Refer to corresponding Vitotronic Control manual)
Fig. 8
2
O
Refer to Vitotronic
200/300 (KW2/KW3)
for alternate connection
location of LWCO.
120 VAC
power
supply
to boiler
120 VAC receptacle
(field supplied)
Power supply. Provide disconnect
1
means and overload protection as
required.
Control case must be connected
2
to earth ground.
V
BL
T
O
T
Y
Y
120 VAC
1
power supply
installer must
provide 15A
overcurrent
protection
Main
ON/OFF
switch
(field supplied)
Low water
cut-off
(if required)
(field supplied)
Legend
Oil solenoid valve
Ignition transformer
Burner motor
CAD cell flame detector
Burner grounding screw
R7184 Series primary control
with post-purge (factory default
setting: 30 sec. - can be field
adjusted; see Beckett burner
manual)
Factory-installed jumper
5351 050 v2.5
10
Page 11
Burner Set-up (Beckett burner with GeniSys primary control)
Wiring diagram (Vitorond 100 with Beckett (NX) burner, GeniSys control and Vitotronic control)
Connections
WARNING
Electric shock hazard. Can cause
severe personal injury or loss of life
if power source, including service
switch on boiler, is not disconnected
before installing or servicing.
Installations must follow these codes
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any additional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
WARNING
Ensure that the burner cycles ON and
OFF on proper call for heat before
leaving the job site. Failure to do so
may lead to boiler runaway situation,
which may lead to property damage,
personal injury or death.
VIESMANN
Fig. 9
5351 050 v2.5
11
Page 12
Burner - Riello
Burner Set-up (Riello)
Electrical connections (with Aquastat control)
Installations must follow these codes
WARNING
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
"
All field supplied nominal 120 VAC voltage wiring must be sheathed in a flexible metal conduit.
"
Disconnect means, overload protection and low water cut-off must be provided as required by local codes.
"
Connect incoming line voltage HOT (L1) wire to terminal L1, and N to terminal L2 of the Honeywell high limit control (see
wiring diagram on page 12).
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any additional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
Burner wiring
1. Secure control harnessusing 2
supplied cable straps.
WARNING
Ensure that burner wiring harness is
properly attached and secured to the
boiler side panel using the supplied
cable straps as depicted above. The
cable strap must be coiled on the
boiler side panel so that no slack is
left, allowing the burner/boiler door
to be swung open without
disconnecting the burner wiring
harness from the burner. Failure to
heed this warning may result in
personal injury.
Room thermostat wiring
Fig. 10
Legend
Burner and control harness, (see
wiring diagram on page 12)
Cable strap (supplied)
Honeywell high limit control
12
1. Install thermostat on inside wall
away from influences of drafts, hot
or cold water pipes, lighting fixtures,
television, sun rays or fireplaces.
2. Follow instructions supplied with
room thermostat. If it has a heat
anticipator, set heat anticipator in
thermostat to match power
requirements of equipment
connected to it. Boiler wiring
diagrams give setting for standard
equipment.
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any addtional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
Burner wiring harness (supplied)
white
black
ground
red
15” *
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
ground
1/4 quick
connect
insulated
flag
red
Fig. 11
* If Beckett burner is being installed,
cut this length to 6” for connection
to burner junction box (located
under the burner primary control).
white
black
5351 050 v2.5
13
Page 14
Burner - Riello
Burner Set-up (Riello)
Wiring diagram (with Aquastat control) with outdoor reset module
WARNING
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
"
All field supplied nominal 120 VAC voltage wiring must be sheathed in a flexible metal conduit.
"
Disconnect means, overload protection and low water cut-off must be provided as required by local codes.
"
Connect incoming line voltage HOT (L1) wire to terminal L1, and N to terminal L2 of the Honeywell high limit control (see
wiring diagram below).
(continued)
Installations must follow these codes
and requirements:
- National Electrical Code, ANSI/NFPA
- In Canada, CSA C22.1 Canadian
70, latest edition and any additional
national, state or local codes.
Electrical Code Part 1 and any local
codes.
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
Fig. 12
CAUTION
A field supplied manual reset high
limit control must be installed at the
outlet pipe of the boiler to interrupt
burner operation should the factory
supplied high limit control fail. This
field supplied high limit control must
be set 20°F above the setting of the
factory supplied high limit control.
The setting of this field supplied high
limit control must never be greater
than 220°F.
14
Post-purge timer setting in conjunction
with Honeywell Aquastat Model
L7248C1006
IMPORTANT
If “Err4” fault occurs, set post-purge
timer to a maximum of 45 seconds.
Exceeding 45 seconds may lead to LED
error code “Err4” on the older version
of the Honeywell Aquastat.
Post-purge
timer
5351 050 v2.5
Page 15
Burner Set-up (Riello)
Electrical connections (with Vitotronic control)
Burner - Riello
WARNING
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
Installations must follow these codes
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any additional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
2.
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
Room thermostat wiring
1. Install thermostat on inside wall
away from influences of drafts, hot
or cold water pipes, lighting fixtures,
television, sun rays or fireplaces.
2. Follow instructions supplied with
room thermostat. If it has a heat
anticipator, set heat anticipator in
thermostat to match power
requirements of equipment
connected to it. Boiler wiring
diagrams give setting for standard
equipment.
1.
Fig. 13
5351 050 v2.5
#41 plug-in connector
Electrical connections
1. Run theplug-in connector cable
ofthe Vitotronic control down behind
the front panel of the boiler and
out through the bottom. (Fig. 11)
2. Connect the femaleplug of the
41
41
burner to the maleplug of the
Vitotronic control. (Fig. 11)
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any addtional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
Burner wiring harness (supplied)
Closed end connectors are factory installed on
RED, ORANGE and BLUE wires. These RED,
ORANGE and BLUE wires may or may not be
used in your burner application. See wiring
diagram in this manual which is specific to your
burner application. Do not remove or cut any of
the closed end connectors of the RED, ORANGE
or BLUE wires, unless it is necessary to do so.
RED wire is live (120VAC) at all times. Do not
remove or cut its closed end connector unless it
Viessmann #41-plug
control connection
is necessary to do so. Failure to heed the above
instructions may cause severe personal injury or
loss of life.
B4
BL
O
S3
BK
T2
T1
W
N
G
G
R
L1
Jumper
RED
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
Electric shock hazard. Can cause
severe personal injury or loss of life if
power source, including service
switch on boiler, is not disconnected
before installing or servicing.
and requirements:
- National Electrical Code, ANSI/NFPA
70, latest edition and any additional
national, state or local codes.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1 and any local
codes.
2
G
G
Air pressure
11
Y
switch
BK
BL
WW
BL
41
Blue wire not used
in this application.
DO NOT cut or
remove closed end
connector from
the wire.
Factory
installed
jumper
12
BL
O
BK
R
NO
10
W
M
BL
BL
Oil valve
BRN
NC
Capacitor
W
BK
1 2 3 4 5 6 7
X
L
N
BL
W
R
O
BK
R
AL 1009
Burner Fan-Off
Timer
- Wiring must be N.E.C. Class 1. If
original wire as supplied with boiler
must be replaced, type 105°C wire
or equivalent must be used. Supply
wiring to boiler and additional control
wiring must be 14 ga. or heavier.
- Provide electrical ground at boiler as
required by codes.
WARNING
9
BR
W
BK
8
R
GY
Ensure that the burner cycles ON and
OFF on proper call for heat before
leaving the job site. Failure to do so
may lead to boiler runaway situation,
which may lead to property damage,
personal injury or death.