Viessmann FB2B, Vitodens 242-F Installation And Service Instructions Manual

Page 1
Installation and service instructions
for contractors
VIESMANN
Vitodens 242-F Type FB2B, 4.8 to 26 kW
Gas condensing/solar storage combi boiler Natural gas and LPG version Gas Council no.: 47-819-18 (19 kW) 47-819-19 (26 kW)
For applicability, see the last page
VITODENS 242-F
5412 755 GB 5/2010
Please keep safe.
Page 2
2
Please follow these safety instructions closely to prevent accidents and mate­rial losses.
Safety instructions explained
Danger
This symbol warns against the risk of injury.
!
Please note
This symbol warns against the risk of material losses and envi­ronmental pollution.
Note
Details identified by the word "Note" con­tain additional information.
Target group
These instructions are exclusively designed for qualified personnel.
■ Work on gas equipment must only be carried out by a qualified gas fitter.
■ Work on electrical equipment must only be carried out by a qualified elec­trician.
■ The system must be commissioned by the system installer or a qualified per­son authorised by the installer.
Regulations
Observe the following when working on this system
■ all legal instructions regarding the pre­vention of accidents,
■ all legal instructions regarding envi­ronmental protection,
■ the Code of Practice of relevant trade associations,
■ all current safety regulations as defined by DIN, EN, DVGW, TRGI, TRF, VDE and all locally applicable standards,
■ Gas Safety (Installation & Use) Regu­lations – the appropriate Building Regulation
either the Building regulations, the Building Regulation (Scotland), Building Regulations (Northern Ire­land),
– the Water Fittings Regulation or
Water Bylaws in Scotland,
– the current I.E.E. Wiring Regula-
tions.
If you smell gas
Danger
Escaping gas can lead to explo­sions which may result in serious injury.
■ Never smoke. Prevent naked flames and sparks. Never switch lights or electrical appli­ances ON or OFF.
■ Close the gas shut-off valve.
■ Open windows and doors.
■ Remove all people from the danger zone.
■ Notify your gas or electricity supplier from outside the build­ing.
■ Shut off the electricity supply to the building from a safe place (outside the building).
Safety instructions
Safety instructions
5412 755 GB
Page 3
3
If you smell flue gas
Danger
Flue gas can lead to life-threat­ening poisoning.
■ Shut down the heating system.
■ Ventilate the boiler room.
■ Close all doors leading to the living space.
Working on the system
■ When using gas as fuel, also close the main gas shut-off valve and safeguard against unauthorised reopening.
■ Isolate the system from the power sup­ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a main isolator.
■ Safeguard the system against unau­thorised reconnection.
!
Please note
Electronic modules can be dam­aged by electro-static dis­charges. Touch earthed objects, such as heating or water pipes, to dis­charge static loads.
Repair work
!
Please note
Repairing components which ful­fil a safety function can compro­mise the safe operation of your heating system. Replace faulty components only with original Viessmann spare parts.
Ancillary components, spare and wearing parts
!
Please note
Spare and wearing parts which have not been tested together with the heating system can com­promise its function. Installing non-authorised components and non-approved modifications/con­version can compromise safety and may invalidate our warranty. For replacements, use only orig­inal spare parts from Viessmann or those which are approved by Viessmann.
Safety instructions
Safety instructions
(cont.)
5412 755 GB
Page 4
4
Installation instructions
Preparing for installation
Product information.............................................................................................. 6
Preparing for installation....................................................................................... 6
Installation sequence
Installing the boiler............................................................................................... 11
Opening the control unit casing............................................................................ 15
Electrical connections........................................................................................... 16
Closing the control unit casing............................................................................. 22
Service instructions
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance.......................................... 24
Further details regarding the individual steps....................................................... 26
Code 1
Calling up coding level 1...................................................................................... 66
General................................................................................................................. 67
Select boiler ......................................................................................................... 69
DHW..................................................................................................................... 70
Solar..................................................................................................................... 70
Heating circuit 1, heating circuit 2, heating circuit 3............................................. 71
Code 2
Calling up coding level 2...................................................................................... 76
General................................................................................................................. 76
Select boiler.......................................................................................................... 84
DHW..................................................................................................................... 86
Solar..................................................................................................................... 88
Heating circuit 1, heating circuit 2, heating circuit 3............................................. 91
Diagnosis and service scans
Calling up the service menu................................................................................. 98
Diagnosis.............................................................................................................. 98
Checking outputs (actuator test).......................................................................... 101
Troubleshooting
Fault display......................................................................................................... 103
Fault codes........................................................................................................... 104
Repairs................................................................................................................. 114
Index
Index
5412 755 GB
Page 5
5
Function description
Control unit........................................................................................................... 127
Internal extensions............................................................................................... 129
External extensions (accessories)........................................................................ 131
Control functions.................................................................................................. 135
Allocating heating circuits to the remote control................................................... 143
Electronic combustion controller.......................................................................... 143
Designs
Internal connection diagram................................................................................. 145
External connection diagram................................................................................ 146
Connection diagram, solar control module........................................................... 148
Parts lists............................................................................................................ 149
Commissioning/service reports........................................................................ 159
Specification....................................................................................................... 160
Certificates
Declaration of conformity...................................................................................... 161
Manufacturer's certificate according to the 1st BImSchV [Germany]................... 162
Keyword index.................................................................................................... 163
Index
Index
(cont.)
5412 755 GB
Page 6
6
Vitodens 242-F, FB2B
Set up for operation with natural gas H. For conversion to LPG P (without conversion kit), see page 32. The Vitodens 242-F should generally only be delivered to those countries specified on the type plate. For deliveries to alternative countries, an approved contractor, on his own initiative, must arrange individual approval in accordance with the law of the land.
Preparing for installation
Handling
If possible, leave the boiler on the pallet during handling. If space constraints make it necessary, the boiler can be split for handling.
Installation instructions provided
!
Please note
To prevent equipment damage, never set the boiler down on its front or side panels or apply loads to these areas.
Installation
Required room height at least 2100 mm. The boiler weight is 161 kg (19 kW) to 165 kg (26 kW) (dry).
Preparing the boiler for installation
Use a connection set, available as an accessory, to make the connection on the gas and water sides. The following overview shows sample connection sets for installation on finished walls to the top or side.
!
Please note
To prevent equipment damage, install all pipework free of load and torque stresses.
Preparing the connections on site:
Connection set installation instructions.
Preparing for installation
Product information
5412 755 GB
Page 7
7
65
1930
2008
100
719
46
40
50
1367
1422
1477
1532
1587
1642
1697
1752
1807
1875
1900
1135
1100
140
60
320
370
436
449
A
H
A
H
B
D F
E G
C
G E
C
B
F D
M
K
K
L
440
55
220
330
a
50
595
50
600
C
F
D
A B
E
G H
A
Solar return R ¾
B
Heating flow R ¾
C
DHW R ½
D
Gas connection R ½
E
DHW circulation R ½ (separate accessory)
F
Cold water R ½
G
Heating return R ¾
H
Solar flow R ¾
K
Condensate drain to the back into the wall
L
Side condensate drain
M
Cable entry area
N
DHW safety valve drain
Preparing for installation
Preparing for installation
(cont.)
5412 755 GB
Installation
Page 8
8
Minimum clearances
Area around the Vitodens for maintenance: min. 700 mm. Maintenance clearances to the l.h. or r.h. side of the Vitodens are not required.
Rated output range 4.8 to 19 kW 6.5 to 26 kW
a (mm) 200 224
Note
The adjustable feet give all height meas­urements a tolerance of +15 mm.
1. Prepare the heating water connec­tions. Flush the heating system thor­oughly.
Note
Should an additional diaphragm expansion vessel be required on site, connect that vessel into the heating return.
Preparing for installation
Preparing for installation
(cont.)
5412 755 GB
Page 9
9
2. Prepare the connections on the DHW
side. Install the safety assembly (accessory or on-site provision) in accordance with the Water Fittings Regulations 1999 in the cold water line (see page 10). Recommendation: Install the safety valve above the DHW cylinder to protect it against contamination, scaling and high tem­peratures. Connect the drain hose to the con­densate collector. Remove plug from condensate collector.
3. Prepare the solar connections.
4.
Route condensate hose O to the back (drain in wall K) or to the side aperture L (see page 6). Route condensate hose with a U­bend and connect to on-site drain line or siphon. Discharge pipes from expansion valves (safety valve) should not be connected directly to a drain and should pass through a visi­ble tundish, with a AUK3 air gap, and be located adjacent to the device.
5. Prepare the gas connection accord­ing to TRGI or TRF or all local regu­lations.
6. Prepare the electrical connections.
Power cable: NYM-J 3 x 1.5 mm2, fuse max. 16 A, 230 V/50 Hz.
■ Accessory cables: NYM with the
required number of conductors for the external connections.
Allow all cables in area "M" (see page 7) to protrude 2000 mm from the wall.
Preparing for installation
Preparing for installation
(cont.)
5412 755 GB
Installation
Page 10
10
Safety assembly to Water Fittings Regulations 1999
A
Safety assembly to Water Fittings Regulations 1999 (acces­sory to connection sets for unfinished walls)
B
Safety valve
C
Visible blow-off line outlet
D
Shut-off valve
E
Flow regulating valve (installation rec­ommended)
F
Pressure gauge connector
G
Non-return valve
H
Drain
K
Cold water
L
Drinking water filter
M
Pressure reducer to Water Fittings Reg­ulations 1999
N
Non-return valve/pipe separator
O
Cold water connection at connection set (accessory)
Preparing for installation
Preparing for installation
(cont.)
5412 755 GB
Page 11
11
Assembling the boiler
9.
8.
7.
6.
5.
1.
3.
2x
4.
2.
Installation sequence
Installing the boiler
5412 755 GB
Installation
Page 12
12
Connections on the heating water and the DHW side
A B
D E
E D
B A
A B D E
C
C
C
Shown with connection sets for finished walls (accessories)
A
Heating flow R ¾
B
DHW R ½
C
DHW circulation R ½ (separate accessory)
D
Cold water R ½
E
Heating return R ¾
Fitting the drain outlet and drain line to the T&P valve
Separate installation instructions
DHW circulation connection
DHW circulation connection with DHW circulation pump connection set (accessory)
Separate installation instructions
Installation sequence
Installing the boiler
(cont.)
5412 755 GB
Page 13
13
Connections on the solar side
B
A
A
B
A
B
Shown with connection sets for finished walls (accessories)
A
Solar return R ¾ or Ø22 mm smooth tube
B
Solar flow R ¾ or Ø22 mm smooth tube
Note
The solar circuit pump is integrated into the boiler.
The expansion vessel, available as an accessory, is installed in the solar return.
Separate installation instructions
The solar safety valve can be fitted in the boiler. Set the pressure gauge for the solar circuit on site.
Note
Route the blow-off pipe for the safety valve on the solar side into a suitable and adequately sized drip container. A drip container (2.5 litres) to be fitted in the boiler is available as an accessory.
Installation sequence
Installing the boiler
(cont.)
5412 755 GB
Installation
Page 14
14
Gas connection
Shown with connection sets for finished walls (accessories)
A
Gas connection R ½
Notes regarding operation with LPG.
We recommend the installation of an external safety solenoid valve when installing the boiler in rooms below ground level.
1. Fix gas shut-off valve to gas connec­tion A.
2. Carry out a tightness test.
Note
For the tightness test, use only suita­ble and approved leak detecting agents (EN 14291) and devices. Leak detecting agents with unsuita­ble contents (e.g. nitrides, sulphides) can lead to material damage. Remove residues of the leak detect­ing agent after testing.
Installation sequence
Installing the boiler
(cont.)
5412 755 GB
Page 15
15
!
Please note
Excessive test pressure may damage the boiler and the gas valve. Max. test pressure 150 mbar. Where higher pressure is required for tightness tests, separate the boiler and the gas valves from the gas sup­ply pipe (undo the fitting).
3. Vent the gas line.
For conversion to a different gas type see page 32
Flue gas connection
Connect the balanced flue. The flue ter­minals have to be installed as described in accordance with the Building Regula­tions Part J and BS 5440.
Flue gas system installation instructions.
Opening the control unit casing
1.
3.
2.
2x
Installation sequence
Installing the boiler
(cont.)
5412 755 GB
Installation
Page 16
16
5.
4.
7x
Electrical connections
Information regarding the connection of accessories
For the connection, observe the separate installation instructions provided with the accessory components.
!
Please note
Electronic modules can be damaged by electrostatic discharges. Before beginning work, touch earthed objects, such as heating or water pipes, to discharge static loads.
Installation sequence
Opening the control unit casing
(cont.)
5412 755 GB
Page 17
17
X4
C
D
B
L
M
1~
L N
230V~
230V~
3217654
X3
40962035100
LN
L1N
2153
%
aVG
?
!
A
N L
?? ? ?
A
Solar control module KM BUS con­nection (connected in the delivered condition)
B
Power supply, solar control module (connected in the delivered condi­tion)
C
External safety solenoid valve (LPG)
D
Cylinder primary pump
Plug 230 V~
sA Cylinder primary pump D (fitted
and connected)
Power supply
■ Remove any existing individual cores.
Danger
Incorrect core termination can cause severe injuries and damage to the equip­ment.
Installation sequence
Electrical connections
(cont.)
5412 755 GB
Installation
Page 18
18
Never interchange cores
"L1" and "N".
■ Install an isolator in the power supply line that simultaneously isolates all non-earthed conduc­tors from the mains with at least 3 mm contact separation. We additionally recommend installing an AC/DC-sensitive RCD (RCD class B ) for DC (fault) currents that can occur with energy efficient equipment. Remove the existing cable grom­met when using larger cross-sec­tions (up to 714 mm). Secure the cable with cable grommet F (see page 21) integrated into the cas­ing base.
■ Max. fuse rating 16 A.
gD
External safety solenoid valve (LPG)
C
Do not remove jumper between "1" and "L" when making this connec­tion.
lH
Power supply of accessories Where the boiler is installed in a wet area, the connection of accessories to the power supply must not be car­ried out at the control unit. If the boiler is installed outside wet areas, the power supply for accessories can be connected directly to the control unit (230 V/50 Hz). The con­nection is switched by the system ON/OFF switch.
Note
If the total system current exceeds 6 A, connect one or more extensions via a mains isolator directly to the mains supply; see page 19.
Low voltage plug X3
!
Outside temperature sensor
Installation:
■ North or north-western wall, 2 to
2.5 m above ground level; in multi­storey buildings, in the upper half of the second floor
■ Not above windows, doors or ven­tilation outlets
■ Not immediately below balconies or gutters
■ Never render over
■ Cable length max. 35 m with a cross-section of 1.5 mm
2
?
Flow temperature sensor for low loss header (accessories)
%
Cylinder temperature sensor (fitted and connected)
aVG
KM BUS subscriber (accessory)
■ Vitotrol 200A or 300A remote control
■ Vitocom 100
■ Extension kit for one heating cir­cuit with mixer
■ Extension AM1 or EA1
■ Open Therm extension
Installation sequence
Electrical connections
(cont.)
5412 755 GB
Page 19
19
Connection of accessories
145
145
40A
40
145
145
40A
40
B C
145
40
96
A
145
145
40A
40
D
E
A
Boiler control unit
B
Extension kit for a heating circuit with mixer M2
C
Extension kit for heating circuit with mixer M3
D
Extension AM1, EA1 and/or solar control module SM1
E
ON/OFF switch
If a current flows to the actuators con­nected (e.g. circulation pumps) that is higher than the safety level of the acces­sory, only use the output concerned to control an on-site relay.
Accessories Internal fuse protection
Extension kit for one heating circuit with mixer 2 A Extension AM1 4 A Extension EA1 2 A Solar control module SM1 2 A
Connecting the collector temperature sensor
Note
Solar control module A is attached to the l.h. side of the air box.
Installation sequence
Electrical connections
(cont.)
5412 755 GB
Installation
Page 20
20
B
% &aVG
A
Connect collector temperature sensor
&
to terminal box B of solar control module A. On-site extension cable: 2-core, cross­section 1.5 mm2.
Note
The cylinder temperature sensor for solar heating % is delivered fitted and connected.
Installation sequence
Electrical connections
(cont.)
5412 755 GB
Page 21
21
Routing the connecting cables
!
Please note
Connecting cables will be damaged if they touch hot parts. When routing and securing power cables on site, ensure that the maximum permissible temperatures for these cables are not exceeded.
A
Low voltage connections
B
230 V connections
C
Internal extension
D
Main PCB
E
Communication module (accesso­ries)
F
Cable grommet for power cable
Remove the existing cable grommet when using larger cross-sections (up to
7
14 mm). Secure the cable with cable grommet F (black) integrated into the casing base.
Installation sequence
Electrical connections
(cont.)
5412 755 GB
Installation
Page 22
22
1.
4.
2.
5.
3.
2x
6.
Insert programming unit (packed sepa­rately) into the control unit support.
Note
The programming unit can also be used in a wall mounting base (accessory) near the boiler.
Installation sequence
Closing the control unit casing
5412 755 GB
Page 23
23
Wall mounting base installation instructions
Installation sequence
Closing the control unit casing
(cont.)
5412 755 GB
Installation
Page 24
24
For further information regarding the individual steps, see the page indicated
Commissioning steps
Inspection steps
Maintenance steps Page
1. Removing the front panels............................................ 26
2. Filling the heating system.............................................. 26
3. Checking the power supply connection
4. Changing the language (if required)............................. 27
5. Setting the time and date (if required).......................... 28
6. Venting the boiler........................................................... 28
7. Venting the heating system........................................... 28
8. Filling siphon with water................................................ 29
9. Filling the solar circuit................................................... 30
10. Checking all connections on the heating water side and DHW side for leaks
11. Naming the heating circuits........................................... 31
12. Checking the gas type.................................................... 31
13. Gas type conversion (only for operation with LPG).... 32
14. Function sequence and possible faults....................... 32
15. Checking the static and supply pressure..................... 34
16. Setting the maximum output......................................... 36
17. Checking the balanced flue system tightness (annular
gap check)....................................................................... 37
18. Removing the burner...................................................... 38
19. Checking the burner gasket and burner gauze
assembly......................................................................... 39
20. Checking and adjusting the ignition and ionisation
electrodes........................................................................ 40
21. Cleaning the heat exchanger and fitting the burner.... 40
22. Checking the condensate drain and cleaning the
siphon.............................................................................. 42
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance
5412 755 GB
Page 25
25
Commissioning steps
Inspection steps
Maintenance steps Page
23. Checking the neutralising system (if installed)
24. Checking the anode connection................................... 43
25. Testing the anode earth current with an anode tester 43
26. Draining the boiler on the DHW side............................ 45
27. Cleaning the primary store............................................ 46
28. Checking and replacing the magnesium anode (if
required).......................................................................... 47
29. Returning the primary store into use............................ 48
30. Checking the diaphragm expansion vessel and
system pressure............................................................. 49
31. Checking the function of safety valves
32. Checking electrical connections are firmly seated
33. Checking gas equipment for tightness at operating
pressure........................................................................... 49
34. Checking the combustion quality................................. 50
35. Checking the external LPG safety valve (if installed)
36. Matching the control unit to the heating system......... 51
37. Adjusting the heating curves........................................ 58
38. Connecting the control unit to the LON....................... 61
39. Scanning and resetting the "Service" display............. 63
40. Fitting the front panels................................................... 64
41. Instructing the system user........................................... 65
Commissioning, inspection, maintenance
Steps - commissioning, inspection and…
(cont.)
5412 755 GB
Service
Page 26
26
Removing the front panels
See page 11, steps 1 to 5.
Filling the heating system
!
Please note
Unsuitable fill water increases the level of deposits and corrosion and may lead to boiler damage.
■ Thoroughly flush the entire heating system prior to filling it with water.
■ Only use fill water of potable quality.
■ Soften fill water with hardness exceeding 300 ppm (3.0 mmol/l), e.g. with a small softening system for heating water (see Vitoset pricelist).
■ An antifreeze additive suitable for heating systems can be added to the fill water.
Shown with connection set for finished walls (accessory)
1. Check the pre-charge pressure of the diaphragm expansion vessel.
2. Close the gas shut-off valve.
3. Fill heating system via boiler drain &
fill valve A in the heating return (depending on connection set either on the side or above the boiler). (Min­imum system pressure > 1.0 bar).
Commissioning, inspection, maintenance
Further details regarding the individual steps
5412 755 GB
Page 27
27
Note
If the control unit has not been switched on prior to filling the system, then the servomotor of the diverter valve will still be in its central position, and the system will be completely fil­led.
Note
Lever on valve B must be in the "l.h." position.
4. If the control unit had already been switched on before filling began: Switch control unit ON and activate filling program (see next steps).
Note
For function and details of the fill pro­gram, see page 137.
5.
Close boiler drain & fill valve A.
Activating the filling function:
1. Press OK and simultaneously for
approx. 4 s.
2. "Service functions"
3. "Filling"
4. Ending filling function: Press OK or .
Changing the language (if required)
Note
At the commissioning stage, the display is in German (default setting)
Extended menu:
1. å
2. "Settings"
3. "Language"
Sprache
Cesky
CZ
Deutsch
DE
Dansk English
DK GB
Wählen mit
Ø
ç
4. Set the required language with / .
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 28
28
Setting the time and date (if required)
During commissioning, or after pro­longed time out of use, the time and date need to be reset.
Extended menu:
1. å
2. "Settings"
3. "Time / Date"
4. Set current time and date.
Venting the boiler
A
C
B
1. Close the shut-off valves on the heat­ing water side.
2.
Remove cover panel A.
3. Connect the drain hose on air vent valve B with a drain.
4.
Open air vent valve B and fill valve C
in the heating return and vent using mains pressure (flush) until no more air noise can be heard.
5.
Close air vent valve B and fill valve C
in the heating return, and open the shut-off valves on the heating water side.
Venting the heating system
1. Close the gas shut-off valve and
switch the control unit ON.
2. Activate venting program (see next steps).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 29
29
Note
For function and sequence of the venting program, see page 137.
3. Check the system pressure.
Activate venting program:
1. Press OK and å simultaneously
for approx. 4 s.
2. "Service functions"
3. "Venting"
4. Terminating venting program: Press OK or ä.
Filling siphon with water
A
B
C
1. Pivot control unit forward.
2.
Pull retaining clip A off.
3.
Pull filler pipe B upwards.
4.
Pull off trap C downwards.
5. Fill siphon with water and reassem­ble.
6. Refit cover panel.
7. Secure control unit back in operating
position.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 30
30
Filling the solar circuit
Solar thermal system installation and service instructions
A
Solar circuit fill valve
!
Please note
Overheated collector areas and overheated heat transfer medium can cause burns/scalding and equipment damage. When working on the collector and the solar circuit, protect the collector area against solar irra­diation.
1. Thoroughly flush the on-site pipe­work.
2.
Fill the solar circuit via fill valve A with "Tyfocor LS". Minimum system pressure: 1.7 bar. Permiss. operating pressure: 6 bar.
!
Please note
To prevent equipment dam­age, use only "Tyfocor LS". Never fill with water.
3.
Close ball valve of fill valve A.
4. Open the air vent valve at the solar collector.
5. Start solar circuit pump via a relay test (see page 101).
6. Let the solar circuit pump run until the solar circuit is fully vented. At a sys­tem pressure below 1.7 bar top up with "Tyfocor LS".
7. Close the air vent valve at the solar collector.
8. Check system pressure. Below
1.7 bar top up with "Tyfocor LS".
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 31
31
Naming the heating circuits
In the delivered condition, the heating circuits are designated "Heating circuit
1", "Heating circuit 2" and "Heating circuit 3" (if installed).
If the system user prefers, the heating circuits can be designated differently to suit the specific system.
Enter names for heating cir­cuits:
Operating instructions
Checking the gas type
The boiler is equipped with an electronic combustion controller that adjusts the burner for optimum combustion in accordance with the prevailing gas quality.
■ Consequently, for natural gas there is no adjustment required across the entire Wobbe index range. The boiler can be operated in the Wobbe index range 9.5 to 15.2 kWh/m3 (34.2 to
54.7 MJ/m3).
■ Convert the burner for operation with LPG (see "Gas type conversion" on page 32).
1. Determine the gas type and Wobbe
index by asking your local gas supply utility or LPG supplier.
2. Convert the burner for operation with
LPG (see page 32).
3. Record the gas type in the service report on page 159.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 32
32
Gas type conversion (only for operation with LPG)
1
2
A
1.
Set adjusting screw A on the gas train to "2".
2.
Turn ON/OFF switch ON.
3. Select the gas type in coding address "82":
■ Call up code 2
■ Call up "General"
■ In coding address "11", select
value "9"
■ In coding address "82", select
value "1" (LPG operation)
In code "11" select value "9".
■ End service functions.
4. Open the gas shut-off valve.
5. Affix label "G31" (supplied with the
technical documentation) adjacent to the type plate on the cover panel.
Function sequence and possible faults
Display Measures
Control unit issues a heat demand
no
Increase set value and ensure heat is drawn off
yes
Fan starts
no
After approx. 51 s fault F9
Check the fan, fan connecting cables, power at the fan and fan control
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 33
33
yes
Ignition
no
Fault EE
Check the ignition module (control voltage 230 V across plugs "X2.1" and "X2.2")
yes
Gas train opens
no
Fault EE
Check the gas train (control voltage 230 V); check the gas supply pres­sure
yes
Ionisation current builds Symbol
A
no
Fault EE
Check the ionisa­tion electrode adjustment and the gas line for air­locks
yes
Burner in opera­tion
no
Stops below the set boiler water temperature and restarts immedi­ately
Check the flue gas system for tight­ness (flue gas recirculation), check the gas flow pressure
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 34
34
yes
Automatic calibra­tion of the com­bustion controller
no
Fault E3
Ensure adequate heat transfer. Press reset button R.
Fault Eb Check gap
between ionisation electrode and burner gauze assembly. Check allocation of gas type (coding address 82, gas train setting). Check flue system; remedy flue gas recirculation if required. Press reset button R.
For further details regarding faults, see page 103.
Checking the static and supply pressure
Danger
CO build-up as a result of an incorrect burner setup can have serious health implications. Carry out a CO test prior to and after work on gas equipment.
Operation with LPG
Flush the LPG tank twice during commissioning/replacement. Vent the tank and gas supply lines thoroughly after flushing.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 35
35
A
1. Close the gas shut-off valve.
2. Release the screw inside test nipple
"PE" A on the gas train but do not remove it, then connect the pressure gauge.
3. Open the gas shut-off valve.
4. Check the static pressure and record
it in the service report on page 159. Set value: max. 37 mbar
5. Start the boiler.
Note
During commissioning, the boiler can enter a fault state because of airlocks in the gas line. After approx. 5 s, press the reset button R (see operat- ing instructions) to reset the burner.
6. Check the supply (flow) pressure.
Set value:
■ Natural gas: 20 mbar
■ LPG: 37 mbar
Note
Use suitable test equipment with a resolution of at least 0.1 mbar to check the supply pressure.
7. Record the actual values in the serv­ice report on page 159. Take the action shown in the follow­ing table.
8. Shut down the boiler, close the gas shut-off valve, remove the pressure gauge and close the screw in test nip­ple A.
9. Open the gas shut-off valve and start the appliance.
Danger
Gas escaping from the test nipple leads to a risk of explo­sion. Check test nipple A for tight­ness.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 36
36
Supply (flow) pres­sure for natural gas
Supply (flow) pressure for LPG
Measures
below 15 mbar below 25 mbar Do not start the boiler. Notify your gas
supply utility or LPG supplier. 15 to 25 mbar 25 to 45 mbar Start the boiler. above 25 mbar above 45 mbar Install a separate gas pressure governor
upstream of the system and regulate the
pre-charge pressure to 20 mbar for natu-
ral gas or 37 mbar for LPG. Notify your
gas supply utility or LPG supplier.
Setting the maximum output
You can limit the maximum output for heating operation. The limit is set via the modulation range. The max. adjustable output is limited upwards by the boiler coding card.
1. Press OK and å simultaneously
for approx. 4 s.
2. "Service functions"
3. "Max. output"
4. "Change?" Select "Yes".
A value flashes on the display (e.g. "85"). In the delivered condition, this value represents 100 % of rated out­put.
5. Set the required value.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 37
37
Checking the balanced flue system tightness (annular gap check)
A
Combustion air aperture (ventilation air)
For balanced flue systems tested together with the wall mounted gas fired boiler, the requirement for a tightness test during commissioning by the flue gas inspector is not applicable.
We recommend that your heating engi­neer carries out a simple leak/tightness test during the commissioning of your system. For this, it would be sufficient to check the CO2 or O2 concentration in the
combustion air at the annular gap of the balanced flue pipe. The flue pipe is deemed to be gas-tight if the CO2 concentration in the combus-
tion air is no higher than 0.2 % or the O2 concentration is at least 20.6 %.
If actual CO2 values are higher or O2 val­ues are lower, then pressure test the flue
pipe with a static pressure of 200 Pa.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 38
38
Removing the burner
4x
1. Switch OFF the main power supply
and the ON/OFF switch at the con­trol unit.
2. Close the gas shut-off valve and safe­guard against reopening.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 39
39
3. Pull electrical cables from fan motor
A
, gas valve B, ionisation elec­trode C, ignition unit D and earth tab E.
4.
Release gas supply pipe fitting F.
5.
Undo four screws G and remove the burner.
!
Please note
Prevent damage to the wire gauze. Never rest the burner on the gauze assembly!
Checking the burner gasket and burner gauze assembly
Check burner gasket A and burner gauze assembly E for damage; replace if required.
CADE 3xFB
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 40
40
1.
Remove electrodes B.
2.
Undo three retaining clips C at ther­mal insulation ring D and remove thermal insulation ring D.
3. Undo four Torx screws and remove burner gauze assembly E with its gasket F.
4. Insert and secure a new burner gauze assembly E with a new gas­ket F. Torque: 3.5 Nm.
5.
Refit thermal insulation ring D.
6.
Refit electrodes B. Torque: 4.5 Nm.
Checking and adjusting the ignition and ionisation electrodes
6
+2
0
4
+0,5
0
10
±1
A
A B
A
Ignition electrodes
B
Ionisation electrode
1. Check the electrodes for wear and contamination.
2. Clean the electrodes with a small brush (not with a wire brush) or sand paper.
3. Check the electrode gaps. If the gaps are not as specified or the electrodes are damaged, replace and align the electrodes together with new gas­kets. Tighten the electrode fixing screws with 4.5 Nm torque.
Cleaning the heat exchanger and fitting the burner
!
Please note
Scratches on parts that are in contact with flue gas can lead to corrosion.
Never use brushes to clean the heat exchanger.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 41
41
A
1. Use a vacuum cleaner to remove deposits from heat exchanger
A
inside the combustion chamber.
2. If required, spray slightly acidic, chloride-free cleaning agents based on phosphoric acid onto heat exchanger A and let the solution soak in for approx. 20 min.
3.
Thoroughly flush heat exchanger A with water.
4. Install the burner. Fit the screw with a serrated washer as well as the remaining screws, then apply torque diagonally with 8.5 Nm.
5. Fit the gas supply pipe with a new gasket.
6. Check the gas connections for tight­ness.
Danger
Escaping gas leads to a risk of explosion. Check all fittings for gas tight­ness.
7. Connect the electrical cables/leads to each corresponding component.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 42
42
Checking the condensate drain and cleaning the siphon
A
B
C
1. Check that the condensate can drain freely at the siphon.
2.
Pull retaining clip A off.
3.
Pull filler pipe B upwards.
4.
Pull off trap C downwards.
5. Pull the condensate hose from trap
C
.
6. Clean the siphon.
7. Fill siphon with water and reassem-
ble.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 43
43
Checking the anode connection
Check that the earth lead is connected to the magnesium anode.
AB
1.
2.
A
Magnesium anode
B
Earth cable
Testing the anode earth current with an anode tester
Note
We recommend that the magnesium anode function is checked annually. This func­tion test can be carried out without interrupting operation, by measuring the earth current with an anode tester.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 44
44
ACB
1.
Remove cover A.
2.
Pull earth lead B from tab C.
3. Connect the tester (up to 5 mA) in series between tab C and earth cable B.
■ The anode is OK if the indicated
current is > 0.3 mA.
■ Visually inspect the anode if the
current measures < 0.3 mA, or if there is no current at all (see page 47).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 45
45
Draining the boiler on the DHW side
1. Connect hose to drain valve and
route into a suitable container or drain outlet.
Note
Ensure adequate ventilation in the DHW pipework.
2. Turn drain valve from lever position
A
to lever position B or C as
required.
Lever position B: Drain heating system excluding cylinder via the cold water connection.
Lever position C: Drain heating system and cylinder via the DHW connection. Cold water connection remains filled.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 46
46
Cleaning the primary store
Note
EN 806 specifies a visual inspection and (if required) cleaning every two years after commissioning and thereafter according to requirements.
A
B
E
C D
1. Drain the primary store.
2.
Remove flange lid A.
3.
Remove T&P valve B.
4.
Undo eight screws C and remove flange lid D.
5.
Dispose of gasket E.
6. Disconnect the primary store from the pipework to prevent contamination from entering the pipe system.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 47
47
7. Remove loose deposits with a high
pressure cleaner.
!
Please note
When cleaning the inside, only use plastic cleaning uten­sils.
8. Use a chemical cleaning agent to remove hard deposits that cannot be removed by a high pressure cleaner.
!
Please note
Never use hydrochloric acid based cleaning agents.
9. Thoroughly flush the primary store after cleaning.
Checking and replacing the magnesium anode (if required)
Check the magnesium anode. If the anode is found to have degraded to 10 to 15 mm Ø, we recommend replacing the magnesium anode.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 48
48
Returning the primary store into use
F
E
A
C
D
B
1. Reconnect the primary store to the pipework.
2.
Insert new gasket A underneath flange lid B.
3.
Fit flange lid B and tighten eight screws D with up to 25 Nm torque.
4.
Push earth cable C onto the tab.
5.
Fit T&P valve E.
6.
Fit cover F.
7. Fill the primary store with drinking water.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 49
49
Checking the diaphragm expansion vessel and system pressure
A
Note
Carry out this test on a cold system.
1. Drain the system, until the pressure gauge indicates "0".
2. If the diaphragm expansion vessel inlet pressure is lower than the static system pressure: Top up with nitro­gen via connection A, until the inlet pressure is 0.1 to 0.2 bar.
3. Top up your heating system with water and vent until the filling pres­sure of a cooled system is 0.1 to 0.2 bar higher than the inlet pressure of the diaphragm expansion vessel. Permiss. operating pressure: 3 bar
Checking gas equipment for tightness at operating pressure
Danger
Escaping gas leads to a risk of explosion. Check gas equipment for tight­ness.
Note
For the tightness test, use only suitable and approved leak detecting agents (EN
14291) and devices. Leak detecting
agents with unsuitable contents (e.g. nitrides, sulphides) can lead to material damage. Remove residues of the leak detecting agent after testing.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 50
50
Checking the combustion quality
The electronic combustion controller automatically ensures an optimum combustion quality. The combustion values only need to be checked during commissioning and service. For this, check the CO2 or O2 content. For a description of the electronic
combustion controller functions, see page 143.
!
Please note
To prevent operating faults and equipment damage, never operate with dirty combustion air.
CO2 or O2 content
■ The CO2 content must be within the following limits for the upper and lower output: – 7.7 to 9.2 % for natural gas H
– 9.3 to 10.9 % for LPG P
■ For all gas types, the O2 content must be between 4.4 and 6.9 %.
If the actual CO2 or O2 values lie outside their respective ranges, proceed with the following steps:
■ Checking the balanced flue system for tightness, see page 37.
■ Checking the ionisation electrode and connecting cable, see page 40.
Note
During commissioning, the combustion controller carries out an automatic calibration. Only test the emissions approx. 30 s after the burner has started.
1. Connect a flue gas analyser at flue
gas aperture A on the boiler flue connection.
2. Open the gas shut-off valve, start the boiler and create a heat demand.
3. Select the lower output (see page 51).
4. Check the CO2 content. Should the actual value deviate from the above
ranges by more than 1 %, implement steps from page 50.
5. Enter actual values into the service report.
6. Select the upper output (see page 51).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 51
51
7. Check the CO2 content. Should the
actual value deviate from the above ranges by more than 1 %, implement steps from page 50.
8. After testing, press OK.
9. Enter actual values into the service
report.
To set the upper/lower output:
1. Press OK and simultaneously for
approx. 4 s.
2. "Actuator test"
3. Select the lower output:
Select "Base load" "ON" and con­firm with OK.
4. Select the upper output: Select "Full load" "ON" and confirm with OK.
Matching the control unit to the heating system
Subject to the equipment level, the control unit must be matched to the system. Var­ious system components are recognised automatically by the control unit and the relevant codes are adjusted automatically.
■ For the selection of an appropriate scheme, see the following diagrams.
■ For coding steps, see page 66.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 52
52
System version 1
One heating circuit without mixer A1
3
1
2
wP
wQ
1
Vitodens 242-F
2
Outside temperature sensor
3
Heating circuit without mixer A1
wP
Solar collectors
wQ
Collector temperature sensor
Function/system components Code
Adjust Delivered con-
dition
Operation with LPG 82:1 82:0 System with DHW circulation pump: DHW circulation pump connection at extension AM1, terminal A2
34:0
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 53
53
System version 2
One heating circuit with mixer M2 and a low loss header
1
M
3
4 5
6
7
2
9
8
wP
wQ
1
Vitodens 242-F
2
Outside temperature sensor
3
Heating circuit with mixer M2
4
Temperature limiter for limiting the maximum temperature of underfloor heating systems
5
Flow temperature sensor M2
6
Heating circuit pump M2
7
Extension kit for one heating circuit with mixer M2
8
Low loss header
9
Flow temperature sensor, low loss header
wP
Solar collectors
wQ
Collector temperature sensor
Function/system components Code
Adjust Delivered con-
dition
Operation with LPG 82:1 82:0 System only with one heating circuit with mixer with extension kit for mixer with DHW heating
00:4 00:6
System with DHW circulation pump:
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 54
54
Function/system components Code
Adjust Delivered con-
dition
DHW circulation pump connection at extension AM1, terminal A2
34:0
System with low loss header 04:0 04:1
System version 3
One heating circuit without mixer A1 and one heating circuit with mixer M2
1
M
3 4
5 6
7
8
2
wP
wQ
1
Vitodens 242-F
2
Outside temperature sensor
3
Heating circuit without mixer A1
4
Heating circuit with mixer M2
5
Temperature limiter for limiting the maximum temperature of underfloor heating systems
6
Flow temperature sensor M2
7
Heating circuit pump M2
8
Extension kit for one heating circuit with mixer M2
wP
Solar collectors
wQ
Collector temperature sensor
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 55
55
Note
The flow rate of the heating circuit with­out mixer must be at least 30 % greater than the flow rate of the heating circuit with mixer.
Function/system components Code
Adjust Delivered con-
dition
Operation with LPG 82:1 82:0 System only with one heating circuit with mixer with extension kit for mixer with DHW heating
00:4 00:6
System with DHW circulation pump: DHW circulation pump connection at extension AM1, terminal A2
34:0
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 56
56
System version 4
One heating circuit without mixer A1, one heating circuit with mixer M2 and system separation
1
2
3
4
5
7
6
9
M
8
wP
wQ
1
Vitodens 242-F
2
Outside temperature sensor
3
Heating circuit without mixer A1
4
Heating circuit with mixer M2
5
Temperature limiter for limiting the maximum temperature of underfloor heating systems
6
Flow temperature sensor M2
7
Heating circuit pump M2
8
Extension kit for one heating circuit with mixer M2
9
Heat exchanger for system separa­tion
wP
Solar collectors
wQ
Collector temperature sensor
Function/system components Code
Adjust Delivered con-
dition
Operation with LPG 82:1 82:0 System only with one heating circuit with mixer with extension kit for mixer with DHW heating
00:4 00:6
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 57
57
Function/system components Code
Adjust Delivered con-
dition
System with DHW circulation pump: DHW circulation pump connection at extension AM1, terminal A2
34:0
System version 5
One heating circuit without mixer A1, one heating circuit with mixer M2 (with extension kit), one heating circuit with mixer M3 (with extension kit) and low loss header (with/without DHW heating)
M M
1
qT
8
7
6
5
9
qP
qQ
qW
qE
qR
2
wP
wQ
4
3
1
Vitodens 242-F
2
Outside temperature sensor
3
Heating circuit without mixer A1 (heating circuit 1)
4
Heating circuit pump A1
5
Heating circuit with mixer M2 (heat­ing circuit 2)
6
Flow temperature sensor M2
7
Heating circuit pump M2
8
Extension kit for one heating circuit with mixer M2
9
Heating circuit with mixer M3 (heat­ing circuit 3)
qP
Temperature limiter for limiting the maximum temperature of underfloor heating systems
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 58
58
qQ
Flow temperature sensor M3
qW
Heating circuit pump M3
qE
Extension kit for one heating circuit with mixer M3
qR
Low loss header
qT
Flow temperature sensor, low loss header
wP
Solar collectors
wQ
Collector temperature sensor
Function/system components Code
Adjust Delivered con-
dition
Operation with LPG 82:1 82:0 System only with two heating circuits with mixer with extension kit for mixer with DHW heating
00:8 00:10
System without DHW circulation pump: Heating circuit pump A1 connection at extension AM1, terminal A1
33:1
System with DHW circulation pump: Heating circuit pump A1 connection at extension AM1, terminal A1
33:1
DHW circulation pump connection at extension AM1, terminal A2
34:0
System with low loss header 04:0 04:1
Adjusting the heating curves
The heating curves illustrate the relation­ship between the outside temperature and the boiler water or flow tempera­ture. To put it simply, the lower the outside temperature, the higher the boiler water or flow temperature. The room temperature, again, depends on the boiler water or the flow tempera­ture.
Note
If the heating system includes heating circuits with mixers, then the flow tem­perature of the heating circuit without mixer is higher by a selected differential (8 K in the delivered condition) than the flow temperature of the heating circuits with mixers. The differential temperature can be changed at coding address 9F.
Settings in the delivered condition:
■ Slope = 1.4
■ Level = 0
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 59
59
0.2
Outside temperature in °C
Boiler water or
flow temperature in °C
Slope
2.4
2.6
2.8
3.0
3.2
3.4
90
80
70
60
50
40
30
0 -5 -10 -15 -20510
A
B
2.0
2.2
Set room temperature in °C
35
30
25
20
15
10
5
0.4
0.6
0.8
1.0
1.2
1.4
-30-25
1.8
1.6
A
Heating curve slope for underfloor heating systems
B
Heating curve slope for low temper­ature heating systems (according to the Energy Savings Order [Ger­many])
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 60
60
Changing the slope and level
A
B
Boiler water or
flow temperature in °C
90
+20 -20
Outside temperature in °C
3.5
1.4
0.2
A
Changing the slope
B
Changing the level (vertical parallel offset of the heating curve)
Extended menu:
1. å
2. "Heating"
3. Select heating circuit.
4. "Heating curve"
5. "Slope" or "Level"
6. Select heating curve according to the
system requirements.
Adjusting the set room temperature
Standard room temperature
90
-20
26 + 20
A
C
D
E
B
Example 1: Adjustment of the standard room temperature from 20 to 26°C
A
Boiler water temperature or flow temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Adjustment of the standard room temperature:
Operating instructions
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 61
61
Reduced room temperature
+20 14 5
90
-20
D E
A
C
B
Example 2: Adjustment of reduced room temperature from 5 °C to 14 °C
A
Boiler water temperature or flow temperature in °C
B
Outside temperature in °C
C
Set room temperature in °C
D
Heating circuit pump "OFF"
E
Heating circuit pump "ON"
Adjustment of the reduced room tem­perature:
Operating instructions
Connecting the control unit to the LON
The LON communication module (accessories) must be plugged in.
Installation instructions LON communication module
Note
The data transfer via LON can take sev­eral minutes.
Single boiler system with Vitotronic 200-H and Vitocom 300 (example)
Set the LON subscriber numbers and further functions via code 2 (see the fol­lowing table).
Note
In the same LON system, the same num­ber cannot be allocated twice. Only one Vitotronic may be program­med as fault manager.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 62
62
Boiler control unit Vitotronic 200-H Vitotronic 200-H Vitocom
LON LON LON
Subscriber no. 1 Code "77:1"
Subscriber no. 10 Code "77:10"
Subscriber no. 11 Set code "77:11"
Subscriber no.
99 Control unit is fault manager Code "79:1"
Control unit is not fault manager Code "79:0"
Control unit is not fault manager Code "79:0"
Device is fault
manager
Control unit transmits the time Code "7b:1"
The control unit receives the time Set code "81:3"
The control unit receives the time Set code "81:3"
Device
receives the
time Control unit transmits outside temperature Set code "97:2"
The control unit receives the outside temperature Set code "97:1"
The control unit receives the outside temperature Set code "97:1"
LON subscriber fault monitoring Code "9C:20"
LON subscriber fault monitoring Code "9C:20"
LON subscriber fault monitoring Code "9C:20"
Carrying out a LON subscriber check
Communication with the system devices connected to the fault manager is tested with a subscriber check.
Preconditions:
■ The control unit must be programmed
as fault manager (code "79:1")
■ The LON subscriber number must be
programmed in all control units (see page 62)
■ The LON subscriber list in the fault
manager must be up to date (see page 62)
Carrying out a subscriber check:
1. Press OK and å simultaneously
for approx. 4 s.
2. "Service functions"
3. "Subscriber check"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 63
63
4. Select subscriber (e.g. subscriber
10). The subscriber check for the selected subscriber is introduced.
■ Successfully tested subscribers are designated with "OK".
■ Unsuccessfully tested subscribers are designated with "Not OK".
Note
To carry out a new subscriber check, create a new subscriber list with menu item "Delete list?"
Note
If the subscriber check is carried out by another control unit, the sub­scriber number and "Wink" are shown on the display for approx. 1 min.
Scanning and resetting the "Service" display
After the limit values specified in coding address "21" and "23" have been reached, "Service" and " " appear on the programming unit display.
Acknowledging and resetting service
Press OK to acknowledge a service message.
Note
An acknowledged service message that was not reset reappears the following Monday.
After a service has been carried out (reset service)
1. Press OK and simultaneously for
approx. 4 s.
2. "Service functions"
3. "Service reset"
Note
The selected service parameters for hours run and time interval restart at 0.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 64
64
Fitting the front panels
4.
2.
2x
1.
5.
3.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Page 65
65
Instructing the system user
The system installer must hand the oper­ating instructions to the system user and instruct him/her in the operation of the system.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5412 755 GB
Service
Page 66
66
Note
■ The codes are displayed as plain text.
■ Codes that have no function due to the heating system equipment level or the setting of other codes are not dis­played.
■ Heating systems with one heating cir­cuit without mixer and one or two heat­ing circuits with mixer: The heating circuit without mixer is designated "Heating circuit 1" and the heating circuits with mixer as
"Heating circuit 2" or "Heating cir­cuit 3".
If the heating circuits were given indi­vidual designations, the selected des­ignation and "HC1", "HC2" or "HC3" appear instead.
1. Press OK and å simultaneously
for approx. 4 s.
2. "Coding level 1"
3. Select group of required coding
address:
"General"
"Boiler"
"DHW"
"Solar"
"Heating circuit 1/2/3"
"All cod. or solar" In this group, all coding addresses from coding level 1 (except the cod-
ing addresses from the "Solar" group) are displayed in ascending order.
4. Select coding address.
5. Select value according to the follow- ing tables and confirm with OK.
6. If you want to reset all codes to their delivered condition: Select "Standard setting" in "Cod­ing level 1".
Note
This also resets codes from coding level 2.
Code 1
Calling up coding level 1
5412 755 GB
Page 67
67
Coding
Coding in the delivered condition Possible change System design
00:2 System version 1:
One heating circuit with­out mixer (A1), with DHW heating
00:2 to 00:10
For system schemes, see the following table:
Value address 00: ...
System version
Description
2 1 One heating circuit without mixer A1 (heating circuit 1), with
DHW heating (code is adjusted automatically)
4 2 One heating circuit with mixer M2 (heating circuit 2), with
DHW heating
6 3, 4 One heating circuit without mixer A1 (heating circuit 1) and
one heating circuit with mixer M2 (heating circuit 2), with DHW heating (code is adjusted automatically)
8 5 One heating circuit with mixer M2 (heating circuit 2) and one
heating circuit with mixer M3 (heating circuit 3), with DHW heating
10 5 One heating circuit without mixer A1 (heating circuit 1), one
heating circuit with mixer M2 (heating circuit 2) and one heat­ing circuit with mixer M3 (heating circuit 3), with DHW heating (code is adjusted automatically)
Code 1
General
5412 755 GB
Service
Page 68
68
Coding in the delivered condition Possible change Internal circulation pump function
51:0 System with low loss
header: Internal circulation pump always starts when there is a heat demand.
51:1 System with low loss
header: When there is a heat demand, the internal circu­lation pump will only be started when the burner is operational.
51:2 System with heating water
buffer cylinder: When there is a heat demand, the internal circu­lation pump will only be started when the burner is operational.
Subscriber no.
77:1 LON subscriber number 77:2
to 77:99
LON subscriber number, adjustable from 1 to 99: 1 - 4 = Boiler 5 = Cascade 10 - 98 = Vitotronic 200-H 99 = Vitocom
Note Allocate each number only once.
Detached house/apartment building
7F:1 Detached house 7F:0 Apartment building
Separate adjustment of holiday program and time program for DHW heating, as option
Lock out controls
8F:0 All control elements
active
8F:1 All control elements locked
out
8F:2 Only standard settings can
be controlled
Code 1
General
(cont.)
5412 755 GB
Page 69
69
Coding in the delivered condition Possible change Set flow temperature in case of ext. Demand
9b:70 Set flow temperature for
external demand 70 °C
9b:0 to 9b:127
Set flow temperature for external demand adjusta­ble from 0 to 127 °C (limited by boiler-specific parame­ters)
Select boiler
Coding
Coding in the delivered condition Possible change Burner service in 100 hours
21:0 No service interval (hours
run) selected
21:1 to 21:100
The number of hours run before the burner should be serviced is adjustable from 100 to 10,000 h One adjusting step
100 h
Service interval in months
23:0 No time interval for
burner service
23:1 to 23:24
Interval adjustable from 1 to 24 months
Service status
24:0 No "Service" display 24:1 "Service" display (the
address is automatically set and must be manually reset after a service has been carried out)
Filling/Venting
2F:0 Venting program/fill pro-
gram disabled
2F:1 Venting program enabled 2F:2 Fill program enabled
Code 1
General
(cont.)
5412 755 GB
Service
Page 70
70
Coding
Coding in the delivered condition Possible change Set DHW temp reheat suppression
67:40 For solar DHW heating:
set DHW temperature 40 °C. Reheating of DHW is suppressed above the selected set tempera­ture.
67:0 to 67:95
Set DHW temperature adjustable from 0 to 95 °C (limited by boiler-specific parameters)
Enable DHW circulation pump
73:0 DHW circulation pump:
"ON" according to time program
73:1 to 73:6
"ON" from once per hour for 5 min up to 6 times per hour for 5 min during the time program
73:7 Constantly "ON"
Solar
Coding
Coding in the delivered condition Possible change Speed control collector pump
02:1 Solar circuit pump (multi-
stage) is speed-control­led with wave pack con­trol
02:0 Solar circuit pump (multi-
stage) is not speed-control­led
02:2 Do not adjust
Cylinder maximum temperature
08:60 The solar circuit pump will
stop when the actual cyl­inder temperature rea­ches 60 °C (maximum cylinder temperature).
08:10 to 08:90
The maximum cylinder temperature can be adjus­ted from 10 to 90 °C
Code 1
DHW
5412 755 GB
Page 71
71
Coding in the delivered condition Possible change Reducing stagnation time
0A:5 To protect the system
components and heat transfer medium, the speed of the solar circuit pump is reduced when the differential between the actual cylinder tem­perature and set cylinder temperature is less than 5 K.
0A:0 to 0A:40
The differential between the set cylinder tempera­ture and the start point for reducing the stagnation time can be adjusted from 0 to 40 K.
Nominal flow rate
0F:70 The flow rate in the col-
lector circuit at the maxi­mum pump speed is set to 7 l/min.
0F:1 to 0F:255
Flow rate in the collector circuit adjustable from 0.1 to 25,5 l/min
Heating circuit 1, heating circuit 2, heating circuit 3
Coding
Coding in the delivered condition Possible change Summer eco function outside temperature
A5:5 With heating circuit pump
logic function (economy circuit): Heating circuit pump "OFF" when the outside temperature (AT) is 1 K higher than the set room temperature (RT
set
)
AT > RT
set
+ 1 K
A5:0 Without heating circuit
pump logic function A5:1 to A5:15
With heating circuit pump
logic function: Heating cir-
cuit pump "OFF"; see the
following table
Parameter address A5:...
With heating circuit pump logic function: Heating cir­cuit pump "OFF"
1 AT > RT
set
+ 5 K
2 AT > RT
set
+ 4 K
3 AT > RT
set
+ 3 K
4 AT > RT
set
+ 2 K
Code 1
Solar
(cont.)
5412 755 GB
Service
Page 72
72
Parameter address A5:...
With heating circuit pump logic function: Heating cir­cuit pump "OFF"
5 AT > RT
set
+ 1 K
6 AT > RT
set
7 to
AT > RT
set
- 1 K
15 AT > RT
set
- 9 K
Coding in the delivered condition Possible change Summer eco function absolute
A6:36 Extended economy mode
disabled
A6:5 to A6:35
Extended economy control enabled, i.e. the burner and heating circuit pump will stop and the mixer close at a variable value, adjustable between 5 and 35 °C plus 1 °C. The base value is the adjusted outside tempera­ture. This value is based on the actual outside temper­ature and a time constant that takes the cooling down of an average building into consideration.
Mixer eco function
A7:0 Without mixer economy
function (only for heating circuits with mixer)
A7:1 With mixer economy func-
tion (extended heating cir­cuit pump logic): Heating circuit pump also "OFF":
■ If a mixer has been attempting to close for longer than 20 min.
Heating circuit pump "ON":
■ If the mixer changes to control function
■ If there is a risk of frost
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5412 755 GB
Page 73
73
Coding in the delivered condition Possible change Pump idle time transition red. mode
A9:7 With pump idle time:
Heating circuit pump "OFF" in case of set value modification by changing the operating mode or changing the set room temperature
A9:0 Without pump idle time A9:1 to A9:15
With pump idle time; adjustable from 1 to 15
Weather-compensated/room temperature hook-up
b0:0 With remote control:
Heating mode/reduced mode: weather-compen­sated (change code only for the heating circuit with mixer)
b0:1 Heating mode: weather-
compensated Reduced mode: with room temperature hook-up
b0:2 Heating mode: with room
temperature hook-up Reduced mode: weather­compensated
b0:3 Heating mode/reduced
mode: with room tempera­ture hook-up
Summer eco function room temperature
b5:0 With remote control: no
room temperature­dependent heating circuit pump logic function (change code only for heating circuit with mixer)
b5:1 to b5:8
Heating circuit pump logic function, see the following table:
Parameter address b5:...
With heating circuit pump logic function: Heating circuit pump "OFF" Heating circuit pump "ON"
1 RT
actual
> RT
set
+ 5 K RT
actual
< RT
set
+ 4 K
2 RT
actual
> RT
set
+ 4 K RT
actual
< RT
set
+ 3 K
3 RT
actual
> RT
set
+ 3 K RT
actual
< RT
set
+ 2 K
4 RT
actual
> RT
set
+ 2 K RT
actual
< RT
set
+ 1 K
5 RT
actual
> RT
set
+ 1 K RT
actual
< RT
set
6 RT
actual
> RT
set
RT
actual
< RT
set
- 1 K
7 RT
actual
> RT
set
- 1 K RT
actual
< RT
set
- 2 K
8 RT
actual
> RT
set
- 2 K RT
actual
< RT
set
- 3 K
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5412 755 GB
Service
Page 74
74
Coding in the delivered condition Possible change Flow temperature minimum limit
C5:20 Electronic minimum flow
temperature limit 20 °C
C5:1 to C5:127
Minimum limit adjustable from 1 to 127 °C (limited by boiler-specific parameters)
Flow temperature maximum limit
C6:74 Electronic maximum flow
temperature limit set to 74 °C
C6:10 to C6:127
Maximum limit adjustable from 10 to 127 °C (limited by boiler-specific parame­ters)
Heating program - changeover
d5:0 External heating program
changeover changes to "Constant operation with reduced room tempera­ture" or "Standby mode".
d5:1 The external heating pro-
gram changeover changes to "Constant operation with standard room tempera­ture" (independent of cod­ing address 3A, 3b and 3C)
Ext. heating program changeover to heating circuit
d8:0 No heating program
changeover via extension EA1
d8:1 Heating program change-
over via input DE1 at exten­sion EA1
d8:2 Heating program change-
over via input DE2 at exten­sion EA1
d8:3 Heating program change-
over via input DE3 at exten­sion EA1
Screed function
F1:0 Screed function disa-
bled.
F1:1 to F1:6
Screed drying function adjustable in accordance with 6 optional tempera­ture/time profiles (see page 137)
F1:15 Constant flow temperature
20 °C
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5412 755 GB
Page 75
75
Coding in the delivered condition Possible change Party mode time limit
F2:8 Time limit for party mode
or external heating pro­gram changeover via key: 8 h
*1
F2:0 No time limit for party
mode
*1
F2:1 to F2:12
Time limit adjustable from 1 to 12 h
*1
Start temperature raising
F8:-5 Temperature limit for ter-
minating the reduced mode -5 ºC, see example on page 140. Observe the setting of coding address "A3"
F8:+10 to F8:-60
Temperature limit adjusta­ble from +10 to -60 °C
F8:-61 Function disabled
End temperature raising
F9:-14 Temperature limit for rais-
ing the reduced set room temperature -14 ºC, see example on page 140.
F9:+10 to F9:-60
Temperature limit for rais­ing the set room tempera­ture to the value selected for standard mode adjusta­ble from +10 to -60 °C
Increase set flow temperature
FA:20 Raising the set boiler
water temperature or the set flow temperature when changing from operation with reduced room temperature to operation with standard room temperature by 20 %. See example on page 141.
FA:0 to FA:50
Temperature rise adjusta­ble from 0 to 50 %
Duration set flow temperature increase
Fb:30 Duration for raising the
set boiler water tempera­ture or the set flow tem­perature (see coding address "FA") 60 min. See example on page 141.
Fb:0 to Fb:150
Duration adjustable from 0 to 300 min; 1 step ≙ 2 min
*1
Party mode ends automatically in the "Heating and DHW" program, when the system changes over to operation with standard room temperature.
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5412 755 GB
Service
Page 76
76
Note
■ In coding level 2, all codes are acces­sible, including the codes from coding level 1.
■ Codes that have no function due to the heating system equipment level or the setting of other codes are not dis­played.
■ Heating systems with one heating cir­cuit without mixer and one or two heat­ing circuits with mixer: The heating circuit without mixer is designated "Heating circuit 1" and the heating circuits with mixer as
"Heating circuit 2" or "Heating cir­cuit 3".
If the heating circuits were given indi­vidual designations, the selected des­ignation and "HC1", "HC2" or "HC3" appear instead.
1. Press OK and å simultaneously
for approx. 4 s.
2. Press OK and ä simultaneously for
approx. 4 s.
3. "Coding level 2"
4. Select group of required coding
address:
"General"
"Boiler"
"DHW"
"Solar"
"Heating circuit 1/2/3"
"All cod. or solar" In this group, all coding addresses (except the coding addresses from the "Solar" group) are displayed in ascending order.
5. Select coding address.
6. Select value according to the follow- ing tables and confirm with "OK".
7. If you want to reset all codes to their delivered condition: Select "Standard setting" in "Cod­ing level 2".
Note
This also resets codes from coding level 1.
General
Coding
Coding in the delivered condition Possible change
00:2 System version 1:
One heating circuit with­out mixer (A1), with DHW heating
00:2 to 00:10
For system schemes, see the following table:
Code 2
Calling up coding level 2
5412 755 GB
Page 77
77
Value address 00: ...
System version
Description
2 1 One heating circuit without mixer A1 (heating circuit 1), with
DHW heating (code is adjusted automatically)
4 2 One heating circuit with mixer M2 (heating circuit 2), with
DHW heating
6 3, 4 One heating circuit without mixer A1 (heating circuit 1) and
one heating circuit with mixer M2 (heating circuit 2), with DHW heating (code is adjusted automatically)
8 5 One heating circuit with mixer M2 (heating circuit 2) and one
heating circuit with mixer M3 (heating circuit 3), with DHW heating
10 5 One heating circuit without mixer A1 (heating circuit 1), one
heating circuit with mixer M2 (heating circuit 2) and one heat­ing circuit with mixer M3 (heating circuit 3), with DHW heating (code is adjusted automatically)
Coding in the delivered condition Possible change
11:9
No access to the coding addresses for the com­bustion controller param­eters
11:9 Access open to the coding
addresses for the combus­tion controller parameters
32:0 Without extension AM1 32:1 With extension AM1 (auto-
matic recognition)
33:1 Function output A1 at
extension AM1: Heating circuit pump
33:0 Function output A1: DHW
circulation pump
33:2 Function output A1: Circu-
lation pump for cylinder heating
34:0 Function output A2 at
extension AM1: DHW cir­culation pump
34:1 Function output A2: Heat-
ing circuit pump
34:2 Function output A2: Circu-
lation pump for cylinder heating
35:0 Without extension EA1 35:1 With extension EA1 (auto-
matic recognition)
36:0
Function output aBJ at extension EA1: Fault message
36:1
Function output aBJ: Feed pump
36:2
Function output aBJ: DHW circulation pump
Code 2
General
(cont.)
5412 755 GB
Service
Page 78
78
Coding in the delivered condition Possible change
3A:0 Function input DE1 at
extension EA1: without function
3A:1 Function input DE1: Heat-
ing program changeover
3A:2 Function input DE1: Exter-
nal demand with set flow temperature. Function internal circula­tion pump: Coding address 3F
3A:3 Function input DE1: Exter-
nal blocking. Function internal circula­tion pump: Coding address 3E
3A:4 Function input DE1: Exter-
nal blocking with fault mes­sage input Function internal circula­tion pump: Coding address 3E
3A:5 Function input DE1: Fault
message input
3A:6 Function input DE1: Brief
operation, DHW circulation pump (pushbutton func­tion). DHW circulation pump run­time adjustment: Coding address 3d
Code 2
General
(cont.)
5412 755 GB
Page 79
79
Coding in the delivered condition Possible change
3b:0 Function input DE2 at
extension EA1: without function
3b:1 Function input DE2: Heat-
ing program changeover
3b:2 Function input DE2: Exter-
nal demand with set flow temperature. Function internal circula­tion pump: Coding address 3F
3b:3 Function input DE2: Exter-
nal blocking. Function internal circula­tion pump: Coding address 3E
3b:4 Function input DE2: Exter-
nal blocking with fault mes­sage input Function internal circula­tion pump: Coding address 3E
3b:5 Function input DE2: Fault
message input
3b:6 Function input DE2: Brief
operation, DHW circulation pump (pushbutton func­tion). DHW circulation pump run­time adjustment: Coding address 3d
Code 2
General
(cont.)
5412 755 GB
Service
Page 80
80
Coding in the delivered condition Possible change
3C:0 Function input DE3 at
extension EA1: without function
3C:1 Function input DE3: Heat-
ing program changeover
3C:2 Function input DE3: Exter-
nal demand with set flow temperature. Function internal circula­tion pump: Coding address 3F
3C:3 Function input DE3: Exter-
nal blocking. Function internal circula­tion pump: Coding address 3E
3C:4 Function input DE3: Exter-
nal blocking with fault mes­sage input Function internal circula­tion pump: Coding address 3E
3C:5 Function input DE3: Fault
message input
3C:6 Function input DE3: Brief
operation, DHW circulation pump (pushbutton func­tion). DHW circulation pump run­time adjustment: Coding address 3d
3d:5 DHW circulation pump
runtime for brief opera­tion: 5 min
3d:1 to 3d:60
DHW circulation pump run­time adjustable from 1 to 60 min
3E:0 Internal circulation pump
stays in control mode at signal "External block­ing"
3E:1 Internal circulation pump
stops at signal "External blocking"
3E:2 Internal circulation pump
starts at signal "External blocking"
Code 2
General
(cont.)
5412 755 GB
Page 81
81
Coding in the delivered condition Possible change
3F:0 Internal circulation pump
stays in control mode at signal "External demand"
3F:1 Internal circulation pump
stops at signal "External demand"
3F:2 Internal circulation pump
starts at signal "External demand"
51:0 System with low loss
header: Internal circulation pump always starts when there is a heat demand.
51:1 System with low loss
header: When there is a heat demand, the internal circu­lation pump will only be started when the burner is operational.
51:2 System with heating water
buffer cylinder: When there is a heat demand, the internal circu­lation pump will only be started when the burner is operational.
52:0 Without flow temperature
sensor for low loss header
52:1 With flow temperature sen-
sor for low loss header
(automatic recognition) 54:3 Do not adjust 6E:50 Do not adjust 76:0 Without LON communi-
cation module (only for weather-compensated control units)
76:1 With LON communication
module (automatic recog-
nition)
77:1 LON subscriber number
(only for weather-com­pensated control units)
77:2 to 77:99
LON subscriber number,
adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number only
once.
Code 2
General
(cont.)
5412 755 GB
Service
Page 82
82
Coding in the delivered condition Possible change
79:1 With LON communication
module: Control unit is fault manager (only for weather-compensated control units)
79:0 Control unit is not fault
manager
7b:1 With LON communication
module: The control unit transmits the time (only for weather-compensa­ted control units)
7b:0 Does not transmit time
7F:1 Detached house (only for
weather-compensated control units)
7F:0 Apartment building
Separate adjustment of holiday program and time program for DHW heating, as option
80:6 A fault message is dis-
played, providing a fault is active for at least 30 s
80:0 Immediate fault message 80:2 to 80:199
Minimum fault duration until fault message occurs, adjustable from 10 s to 995 s; 1 step ≙ 5 s
81:1 Automatic summer/win-
ter time changeover
81:0 Manual summer/winter
time changeover
81:2 Use of the radio clock
receiver (automatic recog­nition)
81:3 With LON communication
module: The control unit receives the time
82:0 Operation with natural
gas
82:1 Operation with LPG (only
adjustable if coding address 11:9 has been
set) 86:0 Do not adjust 87:0 Do not adjust 88:0 Temperature displayed in
°C (Celsius)
88:1 Temperature displayed in
°F (Fahrenheit) 8A:175 Do not adjust 8F:0 All control elements
active
8F:1 All control elements locked
out
8F:2 Only standard settings can
be controlled
Code 2
General
(cont.)
5412 755 GB
Page 83
83
Coding in the delivered condition Possible change
90:128 Time constant for calcu-
lating the adjusted out­side temperature 21.3 h
90:1 to 90:199
Fast (low values) or slow (high values) matching of the flow temperature, sub­ject to the set value when the outside temperature changes; 1 step ≙ 10 min
94:0 Without Open Therm
extension
94:1 With Open Therm exten-
sion (automatic recogni­tion)
95:0 Without Vitocom 100
communication interface
95:1 With Vitocom 100 commu-
nication interface (auto­matic recognition)
97:0 With LON communication
module: The outside tem­perature of the sensor connected to the control unit is utilised internally (only for weather-com­pensated control units)
97:1 The control unit receives
the outside temperature
97:2 The control unit transmits
the outside temperature to the Vitotronic 200-H
98:1 Viessmann system num-
ber (in conjunction with monitoring of several sys­tems via Vitocom 300)
98:1 to 98:5
System number adjustable from 1 to 5
99:0 Never adjust 9A:0 Never adjust 9b:70 Set flow temperature for
external demand 70 °C
9b:0 to 9b:127
Set flow temperature for external demand adjusta­ble from 0 to 127 °C (limited by boiler-specific parame­ters)
Code 2
General
(cont.)
5412 755 GB
Service
Page 84
84
Coding in the delivered condition Possible change
9C:20 Monitoring LON subscrib-
ers. If a subscriber fails to respond, the values specified inside the con­trol unit will be used after 20 min. Only then will a fault message be issued. (only for weather-com­pensated control units)
9C:0 No monitoring 9C:5 to 9C:60
The time is adjustable from
5 to 60 min
9F:8 Differential temperature
8 K; only in conjunction with the mixer circuit (only for weather-compensa­ted control units)
9F:0 to 9F:40
Differential temperature
adjustable from 0 to 40 K
Select boiler
Coding
Coding in the delivered condition Possible change
04:1 Minimum burner pause
subject to the boiler load (specified by boiler cod­ing card)
04:0 Minimum burner pause set
permanently (specified by
boiler coding card)
Adjust for systems with low
loss header. 06:... Maximum limit of the
boiler water temperature, specified in °C by the boiler coding card
06:20 to 06:127
Maximum limit of the boiler
water temperature within
the ranges specified by the
boiler 0d:0 Do not adjust 0E:0 Do not adjust 13:1 Do not adjust 14:1 Do not adjust 15:1 Do not adjust
Code 2
General
(cont.)
5412 755 GB
Page 85
85
Coding in the delivered condition Possible change
21:0 No service interval (hours
run) selected
21:1 to 21:100
The number of hours run before the burner should be serviced is adjustable from 100 to 10 000 h One adjusting step
100 h
23:0 No time interval for
burner service
23:1 to 23:24
Interval adjustable from 1 to 24 months
24:0 No "Service" display 24:1 "Service" display (the
address is automatically set and must be manually reset after a service has been carried out)
28:0 No burner interval igni-
tion
28:1 to 28:24
Time interval adjustable from 1 h to 24 h. The burner is force-started once every 30 s (only when operating
with LPG). 2E:0 Never adjust 2F:0 Venting program/fill pro-
gram disabled
2F:1 Venting program enabled
2F:2 Fill program enabled 30:0 Never adjust 38:0 Status burner control unit:
Operational (no fault)
38:0
Status burner control unit: Fault
Code 2
Select boiler
(cont.)
5412 755 GB
Service
Page 86
86
Coding
Coding in the delivered condition Possible change
56:0 Set DHW temperature
adjustable from 10 to 60 °C
56:1 Set DHW temperature
adjustable from 10 to above 60 °C
Note
Maximum value subject to boiler coding card. Observe the max. permis­sible DHW temperature.
58:0 Without auxiliary function
for DHW heating
58:10 to 58:60
Input of a second set DHW temperature, adjustable from 10 to 60 °C (observe coding addresses "56" and "63")
5E:0 Circulation pump for cyl-
inder heating stays in control mode at signal "External blocking"
5E:1 Circulation pump for cylin-
der heating stops at signal "External blocking"
5E:2 Circulation pump for cylin-
der heating starts at signal "External blocking"
5F:0 Circulation pump for cyl-
inder heating stays in control mode at signal "External demand"
5F:1 Circulation pump for cylin-
der heating stops at signal "External demand"
5F:2 Circulation pump for cylin-
der heating starts at signal "External demand"
65:... Information regarding the
type of diverter valve (not adjustable): 1: Viessmann diverter valve 2: Wilo diverter valve 3: Grundfos diverter valve
Code 2
DHW
5412 755 GB
Page 87
87
Coding in the delivered condition Possible change
67:40 For solar DHW heating:
set DHW temperature 40 °C. DHW reheating is suppressed above the selected set temperature (DHW heating blocked by the boiler).
67:0
to
67:95
Set DHW temperature adjustable from 0 to 95 °C (limited by boiler-specific parameters)
6C:100 Set speed; internal circu-
lation pump with DHW heating 100 %
6C:0
to
6C:100
Set speed adjustable from 0 to 100 %
6F:... Maximum output for
DHW heating in %, speci­fied by the boiler coding card
6F:0
to
6F:100
Max. output for DHW heat­ing adjustable from min. output to 100 %
71:0 DHW circulation pump:
"ON" according to time program
71:1 "OFF" during DHW heating
to the first set value
71:2 "ON" during DHW heating
to the first set value
72:0 DHW circulation pump:
"ON" according to time program
72:1 "OFF" during DHW heating
to the second set value
72:2 "ON" during DHW heating
to the second set value
73:0 DHW circulation pump:
"ON" according to time program
73:1
to
73:6
"ON" from once per hour for 5 min up to 6 times per hour for 5 min during the time program
73:7 Constantly "ON"
Code 2
DHW
(cont.)
5412 755 GB
Service
Page 88
88
Coding
Coding in the delivered condition Possible change
00:8 The solar circuit pump
starts when the collector temperature exceeds the actual cylinder tempera­ture by 8 K.
00:2 to 00:30
The differential between the actual cylinder temper­ature and the start point for the solar circuit pump can be adjusted from 2 to 30 K.
01:4 The solar circuit pump
stops when the differen­tial between the collector temperature and the actual cylinder tempera­ture is less than 4 K.
01:1 to 01:29
The differential between the actual cylinder temper­ature and the stop point for the solar circuit pump can be adjusted from 1 to 29 K.
02:1 Solar circuit pump (multi-
stage) is speed-control­led with wave pack con­trol
02:0 Solar circuit pump (multi-
stage) is not speed-control­led
02:2 Do not adjust
03:10 The temperature differen-
tial between the collector temperature and actual cylinder temperature is regulated to 10 K.
03:5 to 03:20
The differential tempera­ture control between col­lector temperature and actual cylinder tempera­ture can be adjusted from 5 to 20 K
04:4 Controller amplification of
the speed control 4 %/K.
04:1 to 04:10
Controller amplification adjustable from 1 to 10 %/K
05:10 Minimum speed of the
solar circuit pump 10 % of the maximum speed
05:2 to 05:100
Minimum speed of the solar circuit pump is adjust­able from 2 to 100 %
06:75 Maximum speed of the
solar circuit pump 75 % of the maximum possible speed
06:2 to 06:100
Maximum speed of the solar circuit pump is adjust­able from 2 to 100 %
Code 2
Solar
5412 755 GB
Page 89
89
Coding in the delivered condition Possible change
07:0 Interval function of the
solar circuit pump switched off
07:1 Interval function of the
solar circuit pump switched on. To capture the collector temperature more accu­rately, the solar circuit pump starts for short cycles.
08:60 The solar circuit pump will
stop when the actual cyl­inder temperature rea­ches 60 °C (maximum cylinder temperature).
08:10
to
08:90
The maximum cylinder temperature can be adjus­ted from 10 to 90 °C
09:130 The solar circuit pump will
be switched off when the collector temperature reaches 130 °C.
09:20
to
09:200
The temperature can be adjusted from 20 to 200 °C
0A:5 To protect the system
components and heat transfer medium, the speed of the solar circuit pump is reduced when the differential between the actual cylinder tem­perature and set cylinder temperature is less than 5 K.
0A:0
to
0A:40
The differential between the set cylinder tempera­ture and the start point for reducing the stagnation time can be adjusted from 0 to 40 K.
0b:0 Collector frost protection
function switched off
0b:1 Collector frost protection
function switched on (not required with Viessmann heat transfer medium).
0C:1 Delta T monitoring
switched on. No flow rate captured in the collector circuit, or flow rate too low.
0C:0 Delta T monitoring
switched off.
0d:1 Night circulation monitor-
ing switched on. Unintentional flow rate is captured in the collector circuit (e.g. at night).
0d:0 Night circulation monitor-
ing switched OFF.
Code 2
Solar
(cont.)
5412 755 GB
Service
Page 90
90
Coding in the delivered condition Possible change
0E:1 Calculation of solar yield
with Viessmann heat transfer medium
0E:2 Calculation of solar yield
with heat transfer medium water (do not adjust)
0E:0 Calculation of solar yield
switched off
0F:70 The flow rate in the col-
lector circuit at the maxi­mum pump speed is set to 7 l/min.
0F:1 to 0F:255
Flow rate in the collector circuit adjustable from 0.1 to 25,5 l/min
10:0 Target temperature con-
trol switched off (see cod­ing address 11)
10:1 Target temperature control
switched on
11:50 Set cylinder temperature
for solar 50 °C.
■ Target temperature control switched on (code 10:1): Temperature at which the solar heated water in the DHW cylinder is to be stratified.
11:10 to 11:90
The set cylinder tempera­ture for solar can be adjus­ted from 10 to 90 °C
12:20 Minimum collector tem-
perature 20 °C. The solar circuit pump is not started until the mini­mum collector tempera­ture set at the collector temperature sensor is exceeded.
12:0 Minimum collector temper-
ature function switched off 12:1 to 12:90
The minimum collector
temperature can be adjus-
ted from 1 to 90 °C
Code 2
Solar
(cont.)
5412 755 GB
Page 91
91
Coding
Coding in the delivered condition Possible change
A0:0 Without remote control A0:1 With Vitotrol 200A (auto-
matic recognition)
A0:2 With Vitotrol 300A or
Vitohome 300 (automatic recognition)
A1:0 All possible settings at
the remote control can be accessed
A1:1 Only party mode can be set
at the remote control (only for Vitotrol 200A)
A3:2 Outside temperature
below 1 °C: Heating cir­cuit pump "ON" Outside temperature above 3 °C: Heating cir­cuit pump "OFF"
A3:-9 to A3:15
Heating circuit pump "ON/ OFF" (see the following table)
!
Please note
If a value below 1 °C is selected, there is a risk that pipes outside the thermal envelope of the house could freeze up. The standby mode, in particular, should be taken into consideration, e.g. dur­ing holidays.
Parameter Heating circuit pump Address A3:... "ON" "OFF"
-9 -10 °C -8 °C
-8 -9 °C -7 °C
-7 -8 °C -6 °C
-6 -7 °C -5 °C
-5 -6 °C -4 °C
-4 -5 °C -3 °C
-3 -4 °C -2 °C
-2 -3 °C -1 °C
-1 -2 °C 0 °C 0 -1 °C 1 °C 1 0 °C 2 °C 2 to
1 °C to
3 °C to
15 14 °C 16 °C
Code 2
Heating circuit 1, heating circuit 2, heating circuit 3
5412 755 GB
Service
Page 92
92
Coding in the delivered condition Possible change
A4:0 With frost protection A4:1 No frost protection; this set-
ting is only possible if code
"A3:-9" has been selected.
Note
See "Please note" regard-
ing coding address "A3"
A5:5 With heating circuit pump
logic function (economy circuit): Heating circuit pump "OFF" when the outside temperature (AT) is 1 K higher than the set room temperature (RT
set
)
AT > RT
set
+ 1 K
A5:0 Without heating circuit
pump logic function A5:1 to A5:15
With heating circuit pump
logic function: Heating cir-
cuit pump "OFF"; see the
following table
Parameter address A5:...
With heating circuit pump logic function: Heating cir­cuit pump "OFF"
1 AT > RT
set
+ 5 K
2 AT > RT
set
+ 4 K
3 AT > RT
set
+ 3 K
4 AT > RT
set
+ 2 K
5 AT > RT
set
+ 1 K
6 AT > RT
set
7 to
AT > RT
set
- 1 K
15 AT > RT
set
- 9 K
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5412 755 GB
Page 93
93
Coding in the delivered condition Possible change
A6:36 Extended economy mode
disabled
A6:5 to A6:35
Extended economy control enabled, i.e. the burner and heating circuit pump will stop and the mixer close at a variable value, adjustable between 5 and 35 °C plus 1 °C. The base value is the adjusted outside tempera­ture. This value is based on the actual outside temper­ature and a time constant that takes the cooling down of an average building into consideration.
A7:0 Without mixer economy
function (only for heating circuits with mixer)
A7:1 With mixer economy func-
tion (extended heating cir­cuit pump logic): Heating circuit pump also "OFF":
■ If a mixer has been attempting to close for longer than 20 min.
Heating circuit pump "ON":
■ If the mixer changes to control function
■ If there is a risk of frost
A8:1 Heating circuit with mixer
creates a demand for the internal circulation pump
A8:0 Heating circuit with mixer
creates no demand for the internal circulation pump
A9:7 With pump idle time:
Heating circuit pump "OFF" in case of set value modification by changing the operating mode or changing the set room temperature
A9:0 Without pump idle time A9:1 to A9:15
With pump idle time; adjustable from 1 to 15
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5412 755 GB
Service
Page 94
94
Coding in the delivered condition Possible change
b0:0 With remote control:
Heating mode/reduced mode: weather-compen­sated (change code only for the heating circuit with mixer)
b0:1 Heating mode: weather-
compensated Reduced mode: with room temperature hook-up
b0:2 Heating mode: with room
temperature hook-up Reduced mode: weather­compensated
b0:3 Heating mode/reduced
mode: with room tempera­ture hook-up
b2:8 With remote control and
for the heating circuit, operation with room tem­perature hook-up must be programmed: Room influ­ence factor 8 (change code only for heating cir­cuit with mixer)
b2:0 Without room influence b2:1 to b2:64
Room influence factor adjustable from 1 to 64
b5:0 With remote control: no
room temperature­dependent heating circuit pump logic function (change code only for heating circuit with mixer)
b5:1 to b5:8
Heating circuit pump logic function, see the following table:
Parameter address b5:...
With heating circuit pump logic function: Heating circuit pump "OFF" Heating circuit pump "ON"
1 RT
actual
> RT
set
+ 5 K RT
actual
< RT
set
+ 4 K
2 RT
actual
> RT
set
+ 4 K RT
actual
< RT
set
+ 3 K
3 RT
actual
> RT
set
+ 3 K RT
actual
< RT
set
+ 2 K
4 RT
actual
> RT
set
+ 2 K RT
actual
< RT
set
+ 1 K
5 RT
actual
> RT
set
+ 1 K RT
actual
< RT
set
6 RT
actual
> RT
set
RT
actual
< RT
set
- 1 K
7 RT
actual
> RT
set
- 1 K RT
actual
< RT
set
- 2 K
8 RT
actual
> RT
set
- 2 K RT
actual
< RT
set
- 3 K
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5412 755 GB
Page 95
95
Coding in the delivered condition Possible change
C5:20 Electronic minimum flow
temperature limit 20 °C
C5:1 to C5:127
Minimum limit adjustable from 1 to 127 °C (limited by boiler-specific parameters)
C6:74 Electronic maximum flow
temperature limit set to 74 °C
C6:10 to C6:127
Maximum limit adjustable from 10 to 127 °C (limited by boiler-specific parame­ters)
d3:14 Heating curve slope =
1.4
d3:2 to d3:35
Heating curve slope adjust­able from 0.2 to 3.5 (see page 58)
d4:0 Heating curve level = 0 d4:–13
to d4:40
Heating curve level adjust­able from –13 to 40 (see page 58)
d5:0 External heating program
changeover changes to "Constant operation with reduced room tempera­ture" or "Standby mode"
d5:1 The external heating pro-
gram changeover changes to "Constant operation with standard room tempera­ture" (independent of cod­ing address 3A, 3b and 3C)
d6:0 Heating circuit pump
stays in control mode at signal "External block­ing"
d6:1 Heating circuit pump stops
at signal "External block­ing" (subject to coding addresses 3A, 3b and 3C)
d6:2 Heating circuit pump starts
at signal "External block­ing" (subject to coding addresses 3A, 3b and 3C)
d7:0 Heating circuit pump
stays in control mode at signal "External demand"
d7:1 Heating circuit pump stops
at signal "External demand" (subject to coding addresses 3A, 3b and 3C)
d7:2 Heating circuit pump starts
at signal "External demand" (subject to coding addresses 3A, 3b and 3C)
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5412 755 GB
Service
Page 96
96
Coding in the delivered condition Possible change
d8:0 No heating program
changeover via extension EA1
d8:1 Heating program change-
over via input DE1 at exten­sion EA1
d8:2 Heating program change-
over via input DE2 at exten­sion EA1
d8:3 Heating program change-
over via input DE3 at exten-
sion EA1 E1:1 Do not adjust E2:50 With remote control: No
display correction of the actual room temperature
E2:0 to E2:49
Display correction –5 K
to
Display correction –0.1 K
E2:51 to E2:99
Display correction +0.1 K
to
Display correction +4.9 K E5:0 Without external, variable
speed heating circuit pump
F1:0 Screed function disabled F1:1
to F1:6
Screed drying function
adjustable in accordance
with 6 optional tempera-
ture/time profiles (see
page 137)
F1:15 Constant flow temperature
20 °C F2:8 Time limit for party mode
or external heating pro­gram changeover via key: 8 h
*1
F2:0 No time limit for party
mode
*1
F2:1 to F2:12
Time limit adjustable from 1
to 12 h
*1
F8:-5 Temperature limit for ter-
minating the reduced mode -5 ºC, see example on page 140. Observe the setting of coding address "A3"
F8:+10 to F8:-60
Temperature limit adjusta-
ble from
+10 to -60 °C
F8:-61 Function disabled
*1
Party mode ends automatically in the "Heating and DHW" program, when the system changes over to operation with standard room temperature.
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5412 755 GB
Page 97
97
Coding in the delivered condition Possible change
F9:-14 Temperature limit for rais-
ing the reduced set room temperature -14 ºC, see example on page 140.
F9:+10 to F9:-60
Temperature limit for rais­ing the set room tempera­ture to the value selected for standard mode adjusta­ble from +10 to -60 °C
FA:20 Raising the set boiler
water temperature or the set flow temperature when changing from operation with reduced room temperature to operation with standard room temperature by 20 %. See example on page 141
FA:0 to FA:50
Temperature rise adjusta­ble from 0 to 50 %
Fb:30 Duration for raising the
set boiler water tempera­ture or the set flow tem­perature (see coding address "FA") 60 min. See example on page 141.
Fb:0 to Fb:150
Duration adjustable from 0 to 300 min; 1 step ≙ 2 min
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5412 755 GB
Service
Page 98
98
Press OK and å simultaneously for approx. 4 s.
Service menu overview
Service
Diagnosis
Actuator test
Coding level 1
Brief scan
General Heating circuit 1 HC1 Heating circuit 2 HC2
DHW Solar
Service reset
Subscriber check Service PIN
Heating circuit 3 HC3
Coding level 2
Fault history
Service functions
Terminate service?
Reset data
Filling Venting Max. output
Diagnosis
Scanning operating data
Operating data can be scanned in six areas. See "Diagnosis" in the service menu overview. Operating data on heating circuits with mixers and solar can only be scanned if the components are installed in the system. For further information on operating data, see chapter "Brief scan".
Note "- - -" appears on the display if a sensor that has been scanned is faulty.
Calling up operating data
1. Press OK and å simultaneously
for approx. 4 s.
2. "Diagnosis"
3. Select required group, e.g. "Gen­eral".
Diagnosis and service scans
Calling up the service menu
5412 755 GB
Page 99
99
Resetting operating data
Saved operating data (e.g. hours run) can be reset to 0. The value "Adjusted outside temp" is reset to the actual value.
1. Press OK and å simultaneously
for approx. 4 s.
2. "Diagnosis"
3. "Reset data"
4. Select required value (e.g. "Burner starts") or "All details".
Brief scan
In the brief scan, you can scan temperatures, software versions and connected com­ponents, for example.
1. Press OK and å simultaneously for approx. 4 s.
2. "Diagnosis"
3. "Brief scan".
4. Press OK.
The display shows 9 lines with 6 fields each.
Diagnose Kurzabfrage
2:
1:
3: 4:
Wählen mit
Ø
0
0
0
1 F
0 0 0 0
0
0
0 A
0 0 0 0
0
0
1 2
0 0 0
For an explanation of the relevant values in the individual lines and fields, see the following table: Line (brief scan)
Field
1 2 3 4 5 6
1: Software version
Control unit
Equipment version Burner control unit ver-
sion
2: System scheme 01
to 10
Number of KM BUS sub­scribers
Maximum demand temperature
Diagnosis and service scans
Diagnosis
(cont.)
5412 755 GB
Service
Page 100
100
Line (brief scan)
Field
1 2 3 4 5 6
3: Software
version Program­ming unit
Software version Mixer exten­sion 0: No mixer exten­sion
Software version Solar con­trol mod­ule SM1
Software version LON module
0
4: Software version
Burner control unit
Type Burner control unit
Appliance type
5: 0 0 0 0 0 6: Number of LON sub-
scribers
Check digit
Max. output Details in %
Heating circuit A1
(without mixer)
Heating circuit M2 (with mixer)
Heating circuit M3 (with mixer)
7: Remote
control 0: w/o 1: Vitotrol 200A 2: Vitotrol 300A or Vitohome
Software version Remote control 0: no remote control
Remote control 0: w/o 1: Vitotrol 200A 2: Vitotrol 300A or Vitohome
Software version Remote control 0: no remote control
Remote control 0: w/o 1: Vitotrol 200A 2: Vitotrol 300A or Vitohome
Software version Remote control 0: no remote con­trol
Diagnosis and service scans
Diagnosis
(cont.)
5412 755 GB
Loading...