Viessmann Vitodens 100-W, Vitodens 100-WB1A, 7826 213 Installation Instructions Manual

Installation Instructions
for use by heating contractor
Heating Return Connection Pipe,
for Vitodens 100-W, WB1A boilers
Part No. 7826 213
Safety and Installation Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below can cause product/property damage, severe personal injury, and/or loss of life.
Please file in Service Binder
Working on the equipment
The installation, adjustment, service, and maintenance of this product must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burner, or control.
Ensure main power supply to equipment, the heating system, and all external controls has been deactivated. Close main gas supply valve. Take precautions in both instances to avoid accidental activation of power during service work.
Ensure that the installation literature of other applicable components is referenced.
Removing Front Enclosure Panel
AC
D
1. Remove the screw at the top of boiler .
2. Press down on springs at bottom of boiler and remove the front enclosure panel .
3. Drain heating water from boiler.
4. Flip control console down .
7826 213 v1.0 CA 11/2007
B
Installation
Burner Removal
E
B A
F C
D
1. Disconnect electrical cables from gas valve , and ignition transformer unit .
2. Remove connection hose from air pressure switch.
3. Loosen the fitting on the gas connection pipe.
4. Loosen four screws, remove burner and disconnect all electrical cables from blower motor .
CAUTION
To avoid damage to the burner, do not lay burner on its cylindrical burner tube. Failure to heed this caution may cause damage to the burner tube, which may lead to improper operation.
2
7826 213 v1.0 CA