Installation instructions
for contractors
VIESMANN
Vitotrol 300
Remote control for one heating circuit Part no. 7248 907
Safety instructions
Please follow these safety instructions closely to prevent accidents and material losses.
Safety instructions explained
!
Please note
This symbol warns against the risk of material losses and envi­ronmental pollution.
Note
Details identified by the word "Note" con­tain additional information.
Installation, initial start-up, inspection, maintenance and repairs must only be carried out by a competent person (heat­ing engineer/installation contractor).
Before working on the equipment/heat­ing system, isolate the power supply (e.g. by removing a separate mains fuse or by means of a mains isolator) and safeguard against unauthorised recon­nection.
When using gas as fuel, also close the main gas shut-off valve and safeguard against unauthorised reopening.
Repairing components which fulfil a safety function can compromise the safe operation of your heating system. For replacements, use only original spare parts supplied or approved by Viessmann.
Installation location
Weather-compensated mode Installation in any room.
Operation with room temperature-
dependent control
Page 2
2
– On an internal wall in the living
space, at a height of approx. 1.5 m
from the floor – Not near windows and doors – Not above radiators – Not near heat sources (direct sun-
light, fireplace, TV set etc.)
Do not install further controllers in this room. If radiators are equipped with ther­mostatic valves, open them fully.
Installing and connecting the Vitotrol 300
Note
If the remote control cannot be installed in a suitable location, connect the room temperature sensor, part no,7408 012, available as an accessory.
!
Please note
Electronic modules can be dam­aged by electrostatic dis­charges. Before beginning work, touch earthed objects, such as heating or water pipes, to discharge static loads.
A
A
Cable entries
When drilling, watch out for hidden cableways.
Installation location
(cont.)
5592 911 GB
Page 3
3
Connection
Two-core cable with a cross-section of at least 0.75 mm, Cable length up to 50 m.
Note
Never route the cable to the remote con­trol immediately next to 230/400 V cables.
or
145
3 2 17 6 5 4
X3X4
or
or
A
B
F
E
145
D
1 2 3 4
13b
9
C
A
Vitotrol 300
B 3-pin plug aVG to the weather-com-
pensated Vitotronic boiler and heat­ing circuit control unit or to the KM BUS distributor
C 2-pin plug aVG to the weather-com-
pensated Vitotronic boiler and heat­ing circuit control unit or to the KM BUS distributor
D For connection aVG to the A2 elec-
tronic module of the Vitotronic con­trol panel control unit
E
Weather-compensated, wall moun­ted control unit
F
Separate room temperature sensor (accessory)
Installing and connecting the Vitotrol 300
(cont.)
5592 911 GB
Page 4
4
Note
If 2-pin plug
aVG
is plugged into a 3-pin socket, the connection must be made at terminals 1 and 2.
Connecting several remote control units
Version 1
15 m
C
B B B
15 m 15 m
A
A
To the control unit or to the KM BUS distributor (see connection diagram on page 3)
B
Vitotrol
C
Socket (on site)
■ On-site connection via socket:
Connect in accordance with the dia­gram
■ Limit the total length of all KM BUS cables to 50 m.
Version 2
15 m
A
B
D
15 m
C
B B
15 m
A
To the control unit or to the KM BUS distributor (see connection diagram on page 3)
B
Vitotrol
C
Socket (on site)
D
Further BUS subscribers
Installing and connecting the Vitotrol 300
(cont.)
5592 911 GB
Page 5
5
■ If several remote control units and additional KM BUS users are connec­ted, make the connections via an on­site socket as shown in the diagram.
■ Limit the total length of all KM BUS cables to 50 m.
Adjusting the DIP switches
1 2 3 4
ON
S3
3 2 1
RTS
int. ext.
A
PCB DIP switches (back of the cas­ing top)
Remote control DIP switch
setting
Delivered condition: Remote control affects heating circuit A1/M1/ HC1
1 2 3 4
ON
Remote control affects heating circuit M2/HC2
1 2 3 4
ON
Remote control affects heating circuit M3
1 2 3 4
ON
When connecting a sep­arate room temperature sensor, also set DIP switch "S3.3" to "ON".
1 2 3 4
ON
Inserting batteries
To illuminate the display, insert the bat­teries supplied (MICRO/ LR03/AAA) into the battery compartment at the back of the equipment.
Connecting several remote control units
(cont.)
5592 911 GB
Page 6
6
2.
1.
Opening the remote control unit
Changing the setting range for the standard set room temper­ature
Delivered condition: 10 to 30 °C Changeover to
■ 3 to 23 °C
■ 17 to 37 °C
via coding address "E1" on the Vitotronic.
Vitotronic installation and service instructions
Connecting the remote control
5592 911 GB
Page 7
7
Vitotrol operating instructions
Specification
Power supply via KM BUS. Power consumption 0.5 W Protection class III IP rating IP 30 Permiss. ambient tem­perature
■ during operation 0 to + 40 °C
■ during storage and transport:
-20 to + 65 °C
Setting range for stand­ard set room temp. 10 to 30 ºC Setting range for reduced set room temp. 3 to 37ºC
Operating state/scanning temperatures
5592 911 GB
Page 8
8
Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: +44 1952 675000 Fax: +44 1952 675040 E-mail: info-uk@viessmann.com
Viessmann Werke GmbH&Co KG D-35107 Allendorf Telephone: +49 6452 70-0 Fax: +49 6452 70-2780 www.viessmann.com
5592 911 GB Subject to technical modifications.