Viega Digital Thermostat Product Instructions

Product Instructions
Digital Thermostat
Applications
The Digital Thermostat is ideal for individual room temperature control. A user friendly three button design allows for easy change of settings. Thermostat can sense either room temperature, oor temperature or both. Adjustable temperature setback function allows for energy savings. Thermostat can control up to four Powerheads directly or can be connected to a zone / circulator control box. With optional oor sensor, thermostat provides oor high or low limit function for oor protection or oor warming.
Features
• Compact design
• Digital LCD display
• Regulates oor or room temperature or both
• Optional Floor Sensor
• Setback function
Specifications
Control: Accuracy: Set temperature range: Environment range: Power supply: Output: Optional oor sensor: Floor limiting range: Electrical Protection:
301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 877-843-4262 • Fax: 800-976-9817 • E-Mail: service@viega.com • www.viega.com
PI-PR-18050-0309 (Digital Thermostat)
Microprocessor control 0 . 2 ° F 41 °F - 99 °F, 0.5 °F increments 32 °F - 122 °F
_
24 V +/ TRIAC output 24 VAC, 15 W max NTC thermistor, (10K Ohms) 10' cable 50 °F - 104°F Class II - IP30
10% 60Hz 15 W max
Viega... The global leader in plumbing and heating systems.
1.22"
2.36"
3.15"
3.15"
1 of 4
Product Instructions
24 VAC
TRANSFORMER
120 VAC
INPUT
WHITE
BLACK
Digital Thermostat
Mounting
Thermostats are typically mounted 48" to 60" from the sub oor. Thermostats should not be located in direct sunlight or in areas where solar gain can occur. Other potential heat emitters are large electrical gang boxes and dimmer switches. These give off heat inside the wall and can cause a false reading. Thermostats should always be located on an interior wall. Remove white oval screw cover, located in the middle of the thermostat. Then remove the #1 phillips screw. Pull the front cover off the black back plate. Thermostats have slotted mounting holes simplifying leveling of the thermostat. Thermostats should be installed with sleeves and anchors when mounting into drywall.
Wiring Thermostat to Zone Control
Connect the "R" terminal of the thermostat 1.
Typical Wiring of Digital Thermostats to the "R" terminal of the Zone Control. "R" supplies power to the thermostat. Connect the "W" terminal of the thermostat to 2. the "W" terminal of the Zone Control. "W" is the switching signal. Connect the "C" terminal of the thermostat to 3. the "C" terminal of the Zone Control. "C" is common.
(See diagram to right)
C C R W
C C R W
Wiring Thermostat to Powerhead
Connect a "C" and "R" terminals of the 1. thermostat to transformer. Connect the other "C" terminal and 2. "W" terminal of the thermostat to Viega Powerhead. Up to 4 powerheads per thermostat may be 3. connected.
(See diagram to right)
301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 877-843-4262 • Fax: 800-976-9817 • E-Mail: service@viega.com • www.viega.com
PI-PR-18050-0309 (Digital Thermostat)
Viega... The global leader in plumbing and heating systems.
R W C
Digital Thermostat
Connected to a 4 or
6 Zone Control Box
Digital Thermostat with
Transformer and up to 4
Powerheads
2 of 4
Loading...