Viega Basic Heating Control Installation Manual

Page 1
Radiant Basic Heating Control
Installation Manual
March 2009
Page 2
The Viega Basic Heating Control is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset operation. The Basic Heating Control uses a oating action actuator mounted on a divert­ing or mixing valve to regulate the supply water temperature. The control has a Liquid Crystal Display (LCD) to view system status and operating information.
Additional functions include:
• User comfort adjustment to increase or decrease building space temperature
• Advanced settings to ne-tune building requirements
• Optional indoor sensor for room air temperature control
• Test sequence to ensure proper component operation
• 120 VAC power supply
• Powered system circulator pump output
• CSA C US certied (approved to applicable UL standards)
2VIEGA 1-800-976-9819 PI-16015-03/09
Page 3
CONTENTS
1 General Operation
1.1 Using the Control 4
1.2 Description of Display 4
2 Control Operation
2.1 General Operation 5
2.2 Control Features 5
3 Temperature Control
3.1 General Information 6
3.2 Installer Information 6
3.3 Advanced Information 6
4 Boiler Control 7
5 Installation
5.1 Mounting & Rough-in 8
5.2 Electrical Connections 10
5.3 Testingthe Wiring 11
5.4 DIP Switch Settings 13
5.5 View Menu Settings 13
5.6 Adjust Menu Settings 14
5.7 Testing 15
6 Troubleshooting 16
7 Mechanical and Electrical Diagrams 18
8 Technical Data 20
How To Use This Instruction Manual
This manual is organized into the following four main topics:
Operation (Sections 1 and 2), which describes how to read the control and use the LCD display Control (Sections 3 and 4), which discusses how the mixing device and boiler are controlled Installation (Section 5), which details the mounting and connection process for the control and sensors Troubleshooting, Mechanical, and Technical Data (Sections 6, 7, and 8), which provide help with xing problems
and correcting errors.
We recommend rst reading Sections 1 and 2, as these contain important information on the overall operation and use of the control. For a quick installation and setup of the control, refer to Section 5, Installation. Mount and connect the control as described in Sections 5.1 - 5.3, and then set the DIP switches and the parameters of the control as discussed in Sections 5.4 and 5.6.
The Installation section (starting at 5.4 DIP Switch Settings) of this manual describes the various items that are adjusted and displayed by the control. The control functions of each adjustable item are described in Sections 3 and 4.
3VIEGA 1-800-976-9819 PI-16015-03/09
Page 4
GENERAL OPERATION - CHAPTER 1
1 General Operation
1.1 Using the Control
The Basic Heating Control uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to set up and monitor the operation of your system. The Basic Heating Control
has three push buttons (Item, , ) for selecting and adjusting settings. As you program your control, record your Adjust Menu settings for future reference or troubleshooting.
Item
The abbreviated name of the selected item will be displayed in the item eld of the display. To view the next available item, press and release the Item button. Once you have reached the last available item,
pressing and releasing the Item
button will return the display to the rst item.
Adjust
To make an adjustment to a setting in the control, press and hold simultaneously for 1 second, the
Item, and buttons. The display will then show the word ADJUST in the top right corner. Then select the desired item using the Item button.
Finally, use the and/or button to make the adjustment.
To exit the adjust menu, the control must be left alone for 20 seconds.
When the Item button is pressed
and held in the VIEW menu, the control scrolls through all the control
adjust items in both access levels.
Additional information can be gained by observing the Status eld and Pointers of the LCD. The Status eld
will indicate which of the control’s outputs are currently active. Most
symbols in the status eld are only visible when the VIEW menu
is selected.
1.2
Description of Display
Circulator Displays when the system
circulator is in operation
Burner
Displays when the boiler
relay is turned on
°F, °C
Displays the units of
°F
measurement that all of
°C
the temperatures are to be
displayed in the control
Pointer Displays the actuator
operation as indicated (open/close)
4VIEGA 1-800-976-9819 PI-16015-03/09
Page 5
CONTROL OPERATION - CHAPTER 2
2 Control Operation
2.1 General Operation
When the Basic Heating Control is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally,
the control enters into the normal operating mode.
The Basic Heating Control uses a
oating action mixing or injection valve
to vary the supply water temperature to a hydronic system. The supply water temperature is based on the outdoor temperature.
The maximum water temperature setting in the Basic Heating Control
should not be used as a safety high
limit control. To protect oors from high water temperatures in case of
main control failure or removal, use a Viega Modulating Safety High Limit Control (stock code 16116) on the outlet injection valve of the Injection Station.
2.2 Control Features
2.2.1 Outdoor Reset
The Basic Heating Control calculates a mixing supply water temperature
based on the outdoor air temperature.
The Basic Heating Control uses a heating curve and optional indoor
temperature feedback from an indoor
sensor in this calculation.
2.2.2 Floating action
A 24 V (AC) oating action actuator
motor is connected directly to the Basic Heating Control on the
Com, Opn and Cls terminals (7, 8,
and 9). The Basic Heating Control pulses the actuator motor open or closed to maintain the correct mixed supply water temperature at the supply sensor. The valve that the actuator is connected to can
be either an injection valve (on the Injection Station), a mixing valve, or
a diverting valve. A visual indication as to whether the control is currently opening or closing the mixing valve is displayed in the LCD.
2.2.3 Warm Weather Shut Down
The Basic Heating Control monitors the outdoor temperature and shuts off the heating system seasonally when outdoor temperatures exceed
the WWSD setting. This reduces
energy use during the summer when the heating system is not needed and saves wear on system components. To prevent the system from seizing due to long periods of
no use, the circulator, actuator, and
valve are exercised periodically (see
below).
2.2.4 Exercising
The Basic Heating Control has a
built-in exercising function. If the
system pump or valve has not
been operated at least once every 3 days, the control turns on the output for a minimum of 10 seconds. This minimizes the possibility of
a circulator pump or valve seizing during a long period of inactivity. The Basic Heating Control ensures that the mixing valve operates over its entire range at least once each
exercising period. While the control is exercising, the Test LED ashes.
Note: The exercising function does
not work if power to the control, circulator, or valve is disconnected.
5VIEGA 1-800-976-9819 PI-16015-03/09
Page 6
TEMPERATURE CONTROL - CHAPTER 3
3 Temperature Control
3.1 General Information
SYSTEM CIRCULATOR PUMP OPERATION (Sys Pmp)
The system circulator pump contact
(Sys Pmp, terminal 3) remains closed
as long as the Basic Heating Control
is not in Warm Weather Shut Down. During WWSD, the system Circulator is operated periodically based on the Exercise feature.
MIXING TARGET TEMPERATURE (MIX TARGET)
The MIX TARGET temperature is
calculated from the heating curve
settings, outdoor air temperature, and optionally, indoor air
temperature. The control displays the temperature that it is currently trying to maintain as the mixing supply temperature.
3.2 Installer Information
OUTDOOR DESIGN (OUTDR DSGN)
The OUTDR DSGN is the outdoor
air temperature that is typically the coldest temperature of the
year where the building is located.
This temperature is used when performing the heat loss calculations
for the building. If a cold outdoor design temperature is selected, the
mixing supply temperature rises gradually as the outdoor temperature drops. If a warm outdoor design
temperature is selected, the mixing
supply temperature rises rapidly as
the outdoor temperature drops.
of the Heating Curve. The room
temperature desired by the
occupants is often different from the design indoor temperature (MIX INDR). If the room temperature is not
correct, adjusting the ROOM setting
increases or decreases the amount
of heat available to the building.
MIX DESIGN (MIX DSGN)
The MIX DSGN temperature is the
supply water temperature required to heat the mixing zones when the
outdoor air is as cold as the OUTDR DSGN temperature.
3.3 Advanced Information
MIXING INDOOR (MIX INDR)
The MIX INDR is the room temperature used in the original heat loss calculations for the
building. This setting establishes the beginning of the Heating Curve for
the mixing zones.
INDOOR SENSOR (optional) An indoor sensor may be used in
order to provide indoor temperature
feedback. The indoor sensor is
connected to the Com and Indr
terminals (11 and 13). With the indoor sensor connected, the Basic Heating Control is able to sense the actual room temperature. With this information, the Basic Heating Control ne-tunes the supply water
temperature in the mixing system to prevent overheating or underheating.
To adjust the room temperature for the mixing zone, use the ROOM
setting in the ADJUST menu at the control.
If a multiple zone system with thermostats is used with an indoor
sensor, proper placement of the
indoor sensor is essential. The
indoor sensor should be located in an area that best represents the
highest heat loss of the zones.
Mount it on an inside wall, away from drafts, heat sources, or
direct sunlight.
ROOM (ROOM)
The ROOM is the desired room
temperature for the mixing zones and it provides a parallel shift
MIXING MAXIMUM (MIX MAX)
The MIX MAX sets the highest water temperature that the control is allowed to calculate as the MIX
TARGET temperature. If the control does target the MIX MAX setting,
and the MIX temperature is near the
MIX MAX, the MAX segment will be
displayed in the LCD while either the
MIX TARGET temperature or the MIX temperature is being viewed.
WARM WEATHER SHUT DOWN (WWSD)
When the outdoor air temperature rises above the WWSD setting, the
Basic Heating Control turns on the
WWSD segment in the display. When the control is in Warm Weather Shut Down, the control does not operate
the heating system (except for
exercising - see section 2.2.4).
6VIEGA 1-800-976-9819 PI-16015-03/09
Page 7
BOILER CONTROL - CHAPTER 4
4 Boiler Control
4.1 Boiler Operation
When the Basic Heating Control determines that boiler operation is required, the Boiler contact terminals (5 and 6) close. While the Boiler contact is closed, the burner
segment in the LCD is displayed.
4.2 Boiler Enable
(Boiler Enable 30% / Boiler Enable 10%)
The Basic Heating Control has
a DIP switch that allows for the selection between a 30% boiler enable and a 10% boiler enable. In the 30% position, the Basic Heating Control closes the boiler
contact when the position of the
mixing valve exceeds 30%. The boiler contact remains closed until
the position of the mixing valve
reduces below 15%. This setting would normally be chosen for low mass boilers (copper n tube, etc.),
or systems with low thermal mass in
the loop between the boiler and the
mixing valve (recommended for most Viega applications).
In the 10% position, the Basic Heating Control closes the boiler
contact when the position of the
mixing valve exceeds 10%. The boiler contact remains closed until
the position of the mixing valve
reduces below 5%. This setting
is normally chosen for high mass
boilers (cast iron, steel re tube, etc.)
or systems with large thermal mass
in the loop between the boiler and
the mixing valve.
7VIEGA 1-800-976-9819 PI-16015-03/09
Page 8
5 Installation
CAUTION
Improper installation and operation of this control could result in damage
to the equipment and possibly even personal injury. It is your responsibility to ensure that this
control is safely installed according
to all applicable codes and
standards. This electronic control is not intended for use as a primary
limit control. Other controls that are intended and certied as safety limits must be placed into the control
circuit.
INSTALLATION - CHAPTER 5
Press down at grips on top of cover, then
pull out and down to release cover.
Wiring can enter from bottom or back of enclosure. Knockouts allow wiring to be
run in conduit.
Rough-in
5.1 Mounting and Rough-in
Check the contents of this package. If any of the contents listed are
missing or damaged, please
contact your wholesaler or sales representative for assistance.
The Basic Heating Control includes:
One Basic Heating Control, One Outdoor Sensor, and One Supply Sensor.
Note: Carefully read the details of
the Sequence of Operation to ensure
that you have chosen the proper control for your application.
Mounting
Remove the control from its base by
pressing down on the release clip in
the wiring chamber and sliding the control upward. The base may then be mounted by screwing it to a wall or mounting board (screws
not included).
Mounting holes
Release clip
Conduit knockouts on back and bottom
Loosen screws at front and pull wiring cover straight out.
Remove safety dividers by pulling them
straight out.
Press release clip on base and slide
control upward.
The control lifts up and away from the
base, which is ready for mounting.
All electrical wiring terminates in the
control base wiring chamber. The base has standard 7/8" (22 mm) knockouts, which accept common wiring hardware and conduit ttings. Before removing the knockouts,
check the wiring diagram and select
those sections of the chamber with
common voltages. Do not allow the
wiring to cross between sections as
the wires will interfere with safety
dividers that should be installed at a
later time.
Power must not be applied to any of the wires during the rough-in wiring stage.
• Install the Outdoor Sensor and Supply Sensor according to the
instructions on page 9 and run the
wiring back to the control.
• If an Indoor Sensor (optional) is used, install the sensor according to
the instructions included with it and
run the wiring back to the control.
• Run wire from other system components (circulator pump, boiler, actuating motor, etc.) to the control.
• Run wires from the 120 VAC power to the control. Use a clean power
source to ensure proper operation.
Multi-strand 16 AWG wire is recommended for all 120 VAC wiring due to its superior exibility and ease
of installation into the terminals.
8VIEGA 1-800-976-9819 PI-16015-03/09
Page 9
INSTALLATION - CHAPTER 5
Installing the Outdoor Sensor
The Outdoor Sensor includes a 10kthermistor that provides an
accurate measurement of the outdoor temperature. The sensor
is protected by a white U.V. resistant
plastic enclosure.
Remove the screw and pull the front cover off the sensor enclosure.
The Outdoor Sensor can either be
mounted directly onto a wall or a
2" x 4" electrical box. When the sensor is wall mounted, the wiring should enter through the back or bottom of the enclosure. Do not
mount the sensor with the conduit knockout facing upward as rain could enter the enclosure and damage the sensor.
In order to prevent heat transmitted through the wall from affecting the
sensor reading, it may be necessary to install an insulating barrier behind
the enclosure.
The Outdoor Sensor should be mounted on a wall that best
represents the heat load on the
building (a northern wall for most buildings, and a southern facing wall for buildings with large south facing
glass areas). The sensor should not
be exposed to heat sources such as
ventilation or window openings.
The Outdoor Sensor should be installed at an elevation above the
ground that will prevent accidental
damage or tampering, and where it will not be covered by drifting snow
during the winter.
Connect 18 AWG or similar wire to
the two terminals provided in the enclosure and run the wires from the sensor to the control. Do not run the wires parallel to telephone
or power cables. If the sensor
wires are located in an area with strong sources of electromagnetic
interference (EMI), shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit. If using shielded cable, the shield wire should be connected to the COM sensor terminal on the
control and not to earth ground.
Replace the front cover of the sensor enclosure.
When more than one Basic Heating Control is used on a project, the Outdoor Sensors can be combined into one enclosure by adding the Multiple Outdoor Sensor module (stock code 16020). This mounts in the Outdoor Sensor enclosure
and allows up to four controls to have outdoor sensors within one enclosure.
Installing the Supply Sensor
Note: This sensor is designed to mount on a pipe or in a temperature immersion well.
The Supply Sensor can be strapped
directly to the pipe using a plastic cable tie. Insulation should be placed around the sensor to reduce the effect of air currents on the sensor measurement.
The Supply Sensor should be placed
downstream of a pump or after
an elbow or similar tting. This is
especially important if large diameter
pipes are used, as the thermal stratication within the pipe can
result in erroneous sensor readings.
Proper sensor location requires that
the uid is thoroughly mixed within
the pipe before it reaches the sensor. When using the Supply Sensor with a Viega Mixing or Injection Station,
insert the sensor into the immersion
well on the elbow below the
circulator pump.
Connect 18 AWG or similar wire
to the two wires of the sensor and then to the control. Do not run the wires parallel to telephone
or power cables. If the sensor
wires are located in an area with strong sources of electromagnetic
interference (EMI), shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit. If using shielded cable, the shield wire should be connected to the COM sensor terminal on the
control and not to earth ground.
9VIEGA 1-800-976-9819 PI-16015-03/09
Page 10
INSTALLATION - CHAPTER 5
5.2 Electrical Connections
The installer should test to conrm that no voltage is present at any of the wires. Push the control into the base and slide it down until it snaps rmly
into place.
Powered Input Connection
120 VAC POWER
Connect the 120 VAC power supply to the Power L and Power N terminals (1 and 2). This connection provides power to the microprocessor and display of the control. As well, this connection provides power to the Sys Pmp terminal (3) from the Power L terminal (1).
Output Connections
SYSTEM CIRCULATOR PUMP CONTACTS (SYS PMP)
The Sys Pmp output terminal (3) on the Basic Heating Control is a powered output. When the relay in the Basic Heating Control closes, 120 VAC is provided to the Sys Pmp terminal (3) from the Power L terminal (1). To operate the system circulator, connect one side of the system circulator
circuit to terminal (3) and the second side of the circulator circuit to the
neutral (N) terminal (4).
VALVE ACTUATOR
Terminals 7, 8, and 9 are powered with 24 VAC from the control. There is no need to provide a separate 24 VAC power source for the valve actuator. R Opn (7) is connected to the open terminal of the actuating motor and R Cls (8) is connected to the close terminal of the actuating motor. C (9) is then
connected to the common terminal of the actuating motor.
Three Position Actuator for Stations (18003)
White wire is common Green wire is open
Brown wire is close
Mixing Valve Actuator (20040)
Blue wire is common Brown wire is clockwise rotation Black wire is counter-clockwise rotation
(Whether clockwise is open or close will depend on the orientation of the
Mixing Valve – see valve instructions for details)
BOILER CONTACT
The Boiler terminals (5 and 6) are an isolated (dry) output in the Basic Heating Control. There is no power available on these terminals from the control. These terminals are to be used as a switch to either make or break the boiler circuit. When the Basic Heating Control requires the boiler to re, it closes the contact between terminals 5 and 6.
10VIEGA 1-800-976-9819 PI-16015-03/09
Page 11
INSTALLATION - CHAPTER 5
Sensor and Unpowered Input Connections
Do not apply power to these terminals as this will damage the control.
OUTDOOR SENSOR
Connect the two wires from the Outdoor Sensor to the Com and Out terminals (11 and 12). The Outdoor Sensor is used by the Basic Heating
Control to measure the outdoor air temperature.
SUPPLY SENSOR
Connect the two wires from the Supply Sensor to the Com and Mix terminals (10 and 11). The Supply Sensor is used by the Basic Heating Control to
measure the supply water temperature downstream of the mixing or
injection valve.
INDOOR SENSOR
If an optional indoor sensor is used, connect the two wires from the sensor to the Com and Indr terminals (11 and 13).
5.3 Testing the Wiring
Each terminal block must be unplugged from its header on the control before power is applied for testing. To remove the terminal block, pull
straight down from the control.
The following tests are to be performed using standard testing practices and procedures and should only be carried out by properly trained and
experienced persons.
A good quality electrical test meter, capable of reading at least 0 - 300 VAC and at least 0 - 2,000,000 Ohms, is essential to properly test the wiring
and sensors.
Test the Sensors
In order to test the sensors, the actual temperature at each sensor location must be measured. A good quality digital thermometer with a surface temperature probe is recommended for ease of use and accuracy. Where a digital thermometer is not available, a spare sensor can be strapped alongside the one to be tested and the readings compared. Test the sensors according to the instructions on page 15.
Test the Power Supply
Make sure exposed wires and bare terminals are not in contact with other
wires or grounded surfaces. Turn on the power and measure the voltage
between the Power L and Power N terminals (1 and 2) using an AC voltmeter. The reading should be between 108 and 132 VAC.
11VIEGA 1-800-976-9819 PI-16015-03/09
Page 12
INSTALLATION - CHAPTER 5
Test the Outputs
SYSTEM CIRCULATOR PUMP (SYS PMP)
If a system circulator pump is connected to the Sys Pmp terminal (3) and N terminal (4), make sure that power to the terminal block is off and install a jumper between the Power L and the Sys Pmp terminals (1 and 3). Install a second jumper between the Power N and N terminals (2 and 4). When power is applied to the Power L and Power N terminals (1 and 2), the system circulator pump should start. If the circulator pump does not turn on, check the wiring between the terminal block and circulator pump and refer to any installation or troubleshooting information supplied with the circulator pump. If the pump operates properly, disconnect the power and remove the jumpers.
BOILER
If the boiler is connected to the Boiler terminals (5 and 6), make sure power to the boiler circuit is off and install a jumper between the terminals. When the boiler circuit is powered up, the boiler should  re. If the boiler does not turn on, refer to any installation or troubleshooting information supplied with the boiler. (The boiler may have a  ow switch that prevents  ring until the boiler pump is running.) If the boiler operates properly, disconnect the power and remove the jumper.
Connecting the Control
Make sure all power to the devices and terminal blocks is off and remove any remaining jumpers from the terminals.
Reconnect the terminal blocks to the control by carefully aligning them with their respective headers on the control and then pushing the terminal blocks into the headers. The terminal blocks should snap  rmly into place.
Install the supplied safety dividers between the unpowered sensor inputs and the powered 120 VAC or 24 VAC wiring chambers.
Apply power to the control. The operation of the control on power up is
described in section 2.1.
MIXING OR INJECTION VALVE ACTUATOR
If a  oating action actuating motor circuit is connected to the R Opn, R Cls, and C terminals (7, 8, and 9), the control’s Test Sequence can be used to check the motor circuit. Once the Test button is pressed, the valve should move to the fully open position. If the motor closes instead of opening, the wiring of the actuating motor must be reversed. Next, the actuator should move the valve to the fully closed position. If it does not, check the wiring between the terminals and the actuating motor. Refer to any installation or troubleshooting information supplied with the actuator.
12VIEGA 1-800-976-9819 PI-16015-03/09
Page 13
INSTALLATION - CHAPTER 5
5.4 DIP Switch Settings
The DIP switch settings on the
control are very important and
should be set to the appropriate
settings prior to making any
adjustments to the control through the User Interface. The DIP switch
settings change the items that
are available to be viewed and/or adjusted in the User Interface.
Advanced / Installer
The Advanced/Installer DIP switch
is used to select which items are
available to be viewed and/or adjusted in the User Interface (see Display Settings below).
5.5 View Menu Display Settings
Visible when the control is operating (no buttons pressed for at least
20 seconds).
Boiler Enable 30% ­Boiler Enable 10%
The position of this switch determines at which valve position the control will close the Boiler contact under normal
conditions. Refer to section 4.2
(page 7) for a description of the
Boiler Enable DIP.
Bloc / Station
The Bloc/Station switch is used to
select which method the system
will use to adjust supply water temperature. The Mixing Station, Injection Station, and Diverting Valves use the Three Position Actuator (stock code 18003) with a 24 VAC oating signal to adjust
the water temperature. It takes 70
seconds for full valve travel. At 50 Hz, it takes 150 seconds to fully open from fully closed. At 60 Hz it takes 120 seconds to fully open from fully closed. If using Mixing Station, Injection Station and/or Diverting Valves, set DIP switch to “Station.” If using Viega’s 3-4 Way Mixing Valves
with Viega’s Mixing Valve Actuator
or the ProBloc, set DIP switch to “Bloc.” The Mixing Valve Actuator (stock code 20040) takes 102
seconds to fully open from fully closed.
OUTDR
Current outdoor air temperature as measured by the outdoor sensor. This is
also the default display for the control.
ROOM
Measured room air temperature as measured by the indoor sensor. (Only visible when Indoor Sensor is connected).
MIX
Current mixed supply water temperature as measured by the supply sensor.
MIX TARGET
Target mixed supply is the temperature the control is currently trying to maintain at the supply sensor.
(Only visible with the Advanced/Installer DIP switch set to Advanced).
13VIEGA 1-800-976-9819 PI-16015-03/09
Page 14
5.6 Adjust Menu Display Settings
INSTALLATION - CHAPTER 5
To make an adjustment to a setting in the control, press and hold simultaneously for 1 second, the Item, and buttons. The display will then show the word ADJUST in the top right corner. Then select the desired item using the
Item button. Finally, use the and/or button to make the adjustment. See sections 3.2 and 3.3 (page 6) for further discussion on these items and their effect on control operation.
ROOM
The desired room temperature.
OUTDR DSGN
The design outdoor temperature used for calculating heat-loss. Obtained from the Design Outdoor Temperature Chart, or Viega’s Radiant Wizard.*
MIX DSGN
The design supply water temperature obtained from the Supply Water Temperature / BTU Output Chart, or Viega’s Radiant Wizard.
MIX INDR
The design indoor air temperature used in the heat loss calculation* for the heating system (only visible with the Advanced/Installer DIP switch set to Advanced). Should be equal to “ROOM,” the desired room temperature.
MIX MAX
The maximum supply temperature for the mixing system (only visible with the Advanced/Installer DIP switch set to Advanced). This setting should not be relied upon for a safety high limit. Install a Modulating Safety High Limit Control (stock code 16108) on the Injection Station to protect control in case of main control failure or removal. Set higher than “MIX DSGN” and account for the heat loss of distribution piping.
WWSD
Warm Weather Shut Down; the design outdoor air temperature at which the control only operates in exercising mode (only visible with the Advanced/ Installer DIP switch set to Advanced).
UNITS
The units of measure that all of the temperatures are to be displayed in the control; either °F or °C.
* See corresponding installation manuals, i.e. Concrete System, Climate Panel, or Climate Trak,
for appropriate charts.
14VIEGA 1-800-976-9819 PI-16015-03/09
Page 15
INSTALLATION - CHAPTER 5
5.7 Testing the Control
The Basic Heating Control has a
built-in test routine that is used to
test the main control functions. The Basic Heating Control continually monitors the sensors and displays an error message whenever a fault
is found. See the following pages for
a list of the Basic Heating Control’s
error messages and possible causes. When the Test button is pressed, the
test light is turned on. The individual outputs and relays are tested in the following test sequence.
TEST SEQUENCE
Testing Sensors
A good quality test meter capable of measuring up to 5,000k (1k= 1000Ω) is required to
measure the sensor resistance.
In addition to this, the actual temperature must be measured with
a good quality digital thermometer.
If a thermometer is not available, a second sensor can be placed alongside the one to be tested and
the readings compared.
First measure the temperature using the thermometer and then measure the resistance of the sensor at the control. The wires from the sensor
must not be connected to the
control while the test is performed.
Using the chart below, estimate the temperature measured by the
sensor. The sensor and thermometer
readings should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring connection, or a defective sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in the sensor, or the sensor may be defective. To test for a defective sensor,
measure the resistance directly at the sensor location.
Do not apply voltage to a sensor at any time as damage to the sensor may result.
Each step in the test sequence lasts 10 seconds.
During the test routine, the test sequence may be paused by pressing the Test button. If the Test button is not pressed again for 5
minutes while the test sequence is
paused, the control exits the entire
test routine. If the test sequence
is paused, the Test button can be
pressed again to advance to the
next step. This can also be used
to rapidly advance through the test sequence. To reach the desired
step, repeatedly press and release
the Test button until the appropriate device and segment in the display turn on.
Step 1 - The mixing valve is run fully open.
Step 2 - The mixing valve is run fully closed, and then the system pump (Sys Pmp) is turned on. Step 3 - The Boiler contact is turned on for 10 seconds. After 10 seconds, the Boiler and Sys Pmp
contacts are shut off.
Step 4 - After the test sequence is completed, the control resumes
its normal operation.
15VIEGA 1-800-976-9819 PI-16015-03/09
Page 16
TROUBLESHOOTING - CHAPTER 6
6 Troubleshooting
When troubleshooting any heating system, it is always a good idea to establish a set routine to follow. By following a consistent routine, many hours of potential headaches can be
avoided. Below is an example of a sequence that can be used when diagnosing or troubleshooting problems in a hydronic heating system.
Establish the problem. Get as much
information from the customer as
possible about the problem. Is there too much heat, not enough heat, or no heat? Is the problem only in one particular zone or area of the building or does the problem affect the entire system? Is this a consistent problem
or only intermittent? How long has the problem existed? This information is critical in diagnosing
the problem.
Understand the sequence of
operation of the system. If a particular zone is not receiving
enough heat, which circulators or
valves in the system must operate in order to deliver heat to the affected zone? If the zone is receiving too
much heat, which pumps, valves, or
check valves must operate in order to stop the delivery of heat?
Press the Test button on the control
and follow the control through the
test sequence as described in the Testing section. Pause the control as
necessary to ensure that the correct device is operating as it should.
Document the control for future reference. Before making any
adjustments to the control, note
all of the items that the control is currently displaying. This includes
items such as error messages, current temperatures and settings, and which devices should be operating as indicated by the LCD.
This information is an essential step if additional assistance is required to
diagnose the problem.
Isolate the problem between the
control and the system. Now that the sequence of operation is known and
the system is sketched, is the control
operating the proper circulators and valves at the correct times? Is the control receiving the correct signals from the system as to when it should
be operating? Are the proper items
selected in the menus of the control
for the device that is to be operated?
Test the contacts, voltages, and sensors. Using a multimeter, ensure
that the control is receiving adequate voltage to the power terminals as
noted in the technical data. Use
the multimeter to determine if the internal contacts on the control are opening and closing correctly. Follow the instructions in the Testing
the Wiring section on page 11 to
simulate closed contacts on the
terminal blocks as required. Test the sensors as described on page 15.
What to do if the building
temperature is incorrect:
Underheating:
If the building is too cool during cold weather, this indicates that the
upper portion of the programmed
heating curve is too low, or that the
supply water high limit (MIX MAX)
has been reached. If the supply temperature is close to MIX MAX, then this setting must be increased to provide more heat (if possible without damaging oors). Otherwise increase the MIX DSGN temperature,
which will increase the supply water
temperature (by increasing the slope
of the heating curve).
If the building is too cool in warm weather, increase the value of the ROOM setpoint in the Adjust menu.
This will shift the heating curve up to provide higher water temperatures.
Overheating:
If the building is too warm during cold weather, decrease the value of the MIX DSGN setting in the Adjust
menu. This will reduce the slope
of the heating curve, providing less heat to the building at low outdoor
temperatures.
If the building is too warm during warmer weather, reduce the value of the ROOM setpoint in the adjust
menu. This will shift the heating curve downward to reduce water temperatures.
Sketch the piping of the system.
This is a relatively simple step that
tends to be overlooked; however,
it can often save hours of time in
troubleshooting a system. Note
ow directions in the system paying close attention to the location of
circulators, check valves, pressure bypass valves, and mixing valves. Ensure correct ow direction on all
pumps. This is also a very useful step if additional assistance is required.
16VIEGA 1-800-976-9819 PI-16015-03/09
Page 17
TROUBLESHOOTING - CHAPTER 6
Error Messages
E01
The control was unable to read a piece of information from its EEPROM. This error can be caused by a noisy power source. The control will load the factory defaults and stop operation until the settings are veried.
Shr (OUTDR)
The control is no longer able to read the Outdoor sensor due to a short circuit. In this case the control assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate the problem as described in Section
5.7. To clear the error message from the control after the sensor has been repaired, press the Item button.
OPn (OUTDR)
The control is no longer able to read the Outdoor sensor due to an open circuit. In this case the control assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate the problem as described in Section
5.7. To clear the error message from the control after the sensor has been repaired, press the Item button.
Shr (MIX)
The control is no longer able to read the Mixing Supply sensor due to a short circuit. In this case the control will operate the mixing valve at a xed output. Locate the problem as described in Section 5.7. To clear the error message from the control after the sensor has been repaired, press the Item button.
OPn (MIX)
The control is no longer able to read the Mixing Supply sensor due to a open circuit. In this case the control will operate the mixing valve at a xed output. Locate the problem as described in Section 5.7. To clear the error message from the control after the sensor has been repaired, press the Item button.
Shr (ROOM)
The control is no longer able to read the Indoor sensor due to a short circuit.
The control will continue to operate as if there was nothing connected to the
Indoor sensor input. Locate the problem as described in Section 5.7. To clear the error message from the control after the sensor has been repaired, press
the Item button.
OPn (ROOM)
The control is no longer able to read the Indoor sensor due to an open
circuit. The control will continue to operate as if there was nothing connected
to the Indoor sensor input. Locate the problem as described in Section
5.7. To clear the error message from the control after the sensor has been repaired, press the Item button.
17VIEGA 1-800-976-9819 PI-16015-03/09
Page 18
MECHANICAL AND ELECTRICAL DIAGRAMS - CHAPTER 7
Pump
Pump
Pump
Pump
18VIEGA 1-800-976-9819 PI-16015-03/09
Page 19
MECHANICAL AND ELECTRICAL DIAGRAMS - CHAPTER 7
*
* Three Position Actuator: White wire common, green wire open, brown wire close. Mixing Valve Actuator: Blue wire common, brown wire clockwise rotation, black wire counter-clockwise rotation
19VIEGA 1-800-976-9819 PI-16015-03/09
Page 20
Technical Data
TECHNICAL DATA - CHAPTER 8
Control Microprocessor PID control; this is not a safety (limit) control Packaged Weight 3.1 lbs. (1420 g) Enclosure black PVC plastic Dimensions 6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm) Approvals CSA C US, meets ICES & FCC regulations for EMI/RFI Ambient Conditions Indoor use only, 32 to 102°F (0 to 39°C), <90% RH non-condensing Power Supply 120 VAC +/- 10% 50/60 Hz 1300 VA Floating Output 24 VAC 0.34 A 8 VA Relays 240 VAC 10 A 1/3 hp, pilot duty 240 VA Sensors NTC thermistor
Sensor Resistances
20VIEGA 1-800-976-9819 PI-16015-03/09
Page 21
NOTES
21VIEGA 1-800-976-9819 PI-16015-03/09
Page 22
NOTES
22VIEGA 1-800-976-9819 PI-16015-03/09
Page 23
NOTES
23VIEGA 1-800-976-9819 PI-16015-03/09
Page 24
Basic Heating Control
Installation and Operation Manual
ProPress® System
Flameless copper press technology.
ProPress® System
Flameless copper re safety
press technology.
ProPressG™ System
Flameless copper fuel gas
press technology.
PureFlow® System
The global leader in plumbing and
heating systems.
Rely on Viega for the most complete line
of high tech/high quality plumbing, heating,
and snow melting systems…plus the most comprehensive customer support in the industry.
Flexible PEX tubing
plumbing technology.
ProRadiant™ Systems
Comfortable, efcient
heating technology.
S-no-Ice® System
Snow and ice
melting technology.
Viega
301 N. Main
Wichita, KS 67202
Phone: 1-877-843-4262
1-800-976-9819
Fax: 1-800-976-9817
www.viega.com
PI-IM-16016-03/09
Page 25
Product
Instructions
3 Position Actuator for Stations
Applications
The Three Position Actuator for Stations is designed to provide oating action control of Viega Mixing Stations, Enhanced Mixing Stations and diverting valves. The actuator is used in electronic temperature control systems which use hot and/or cold water as the controlled medium in radiant heating systems, snowmelting, or other temperature mixing applications. The actuator is designed for operation by any 24V oating signal controller such as the Basic Heating
Control.
Features
• Small size allows installation where space is limited
• Maintenance free actuator in plastic housing
• Synchronous motor
• Magnetic coupling for torque limitation independent of voltage
• Suitable for 3-position modulating control (oating) without proportional feedback
• No tools required for mounting
stock code # 18003
Specifications
Power supply: 24 VAC, 50/60 Hz Power consumption: 0.7 VA Control mode: 3-position (oating) Stroke: 0.25 inches Running time: 150 sec at 50 Hz 120 sec at 60 Hz (70 sec for full valve travel) Stem force: 40 lbs Connecting cable: 5 ft Ambient Temp. Limits: 32 - 140°F Weight: 0.33 lbs Mounting thread: M30 x 1.0
301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 800-976-9819 • Fax: 316-425-7618 • www.viega.com
©2011, ProPress®, FostaPEX®, Seapress®, MegaPress®, MegaPressG
®
, Radiant Wizard®, S-no-Ice®, Snap Panel®, XL® and XL-C® are registered trademarks of Viega LLC. MiniBloc™, ProRadiant™, PolyAlloy™, SmartLoop™, GeoFusion™, and Zero Lead™ are trademarks of
BLOC Viega LLC; GeoFusion
PI-PR-561170 0512 (3 Position Actuator for Stations)
EN0B-0471GE51-VIEGA R0412B
, ProPressG™ and ViegaPEX™ are trademarks of Viega GmbH & Co. KG.
Viega... The global leader in plumbing, heating and pipe joining systems
®
and Viega® are registered trademarks of Viega GmbH & Co. PureFlow®, Smart Connect®, Climate Panel®, Climate Mat®, Climate Trak®, MANA-
1 of 2
Page 26
Product
Instructions
Operation
The movement of the electric actuator is produced by the rotation of a screw spindle which is driven in both directions by a synchronous motor through a set of gears. A magnetic coupling limits the torque of the gear assembly and the driving force of the actuator. The actuator is xed to the valve body by means of a coupling ring requiring no tools for mounting. The actuator is maintenance free and supplied complete with a ready-to-wire connecting cable.
Mounting
For ease of installation, make sure that the actuator is in the open position (factory supplied) before xing the actuator to the valve body. Thread the nut hand tight only (do not use pliers or a wrench).
Troubleshooting
A functional check of the valve actuator can be made by suddenly changing the heating curve adjustment. The movement of the actuator stem indicates whether the valve is opening or closing.
If the direction of travel is incorrect, the green and brown wires should be exchanged.
Dimensions
Wiring Diagram
301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 800-976-9819 • Fax: 316-425-7618 • www.viega.com
©2011, ProPress®, FostaPEX®, Seapress®, MegaPress®, MegaPressG
®
, Radiant Wizard®, S-no-Ice®, Snap Panel®, XL® and XL-C® are registered trademarks of Viega LLC. MiniBloc™, ProRadiant™, PolyAlloy™, SmartLoop™, GeoFusion™, and Zero Lead™ are trademarks of
BLOC Viega LLC; GeoFusion
PI-PR-561170 0512 (3 Position Actuator for Stations)
EN0B-0471GE51-VIEGA R0412B
, ProPressG™ and ViegaPEX™ are trademarks of Viega GmbH & Co. KG.
Viega... The global leader in plumbing, heating and pipe joining systems
Green wire: open valve (warmer water) Brown wire: close valve (cooler water) White wire: ground
®
and Viega® are registered trademarks of Viega GmbH & Co. PureFlow®, Smart Connect®, Climate Panel®, Climate Mat®, Climate Trak®, MANA-
2 of 2
Page 27
Product Instructions
Zone Control
Applications
The Viega Zone Control is a wiring and switching center for individual and / or multi­room control. The Zone Control simplies wiring between Thermostats and Powerheads. LED lights on housing indicate individual zone heat demand. Available as a 4 or 6 zone, both with priority. Zone Control includes optional circulator activation function and built in transformer.
Features
• LED indicator lights
• 4 or 6 Zone Control options
• Simplied wiring
• Built in transformer
Specifications
6 Zone
120 VAC 24 VAC 2 x 40 VA 7 Amp Max 16 per control UL Approval
Control Input: Control Output: Transformer: Fuse: Powerheads: Codes and Standards:
4 Zone
120 VAC 24 VAC 40 VA 5 Amp Max 8 per control UL Approval
Operation
The green LED indicates that the control is powered on. When any thermostat calls for heat that corresponding yellow LED light is illuminated. A call for heat energizes the corresponding powerhead(s) and the end switch relays illuminating the red LED light.
Viega... The global leader in plumbing and heating systems.
301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 877-843-4262 • Fax: 800-976-9817 • E-Mail: service@viega.com • www.viega.com
Stock
Code
18060
18062
Description Width Height Depth
4 Zone with
priority
6 Zone with
priority
10.75" 6.75" 2.75"
11.75" 7.5" 3"
PI-PR-18060 (Zone Control) xxxxxx 0209 Plant ID No.9300-2856 Rev
1 of 2
Page 28
Product Instructions
INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT
24 VAC
FACTORY
INSTALLED
TRANSFORMER
120 VAC
INPUT
WHITE
BLACK
POWER IN
24 VAC
FACTORY
INSTALLED
TRANSFORMER
120 VAC
INPUT
WHITE
BLACK
Zone Control
Wiring Thermostats
Connect the "R" terminal of the thermostat 1. to the "R" terminal of the Zone Control. "R" supplies power to the thermostat. Connect the "W" terminal of the thermostat to 2. the "W" terminal of the Zone Control. "W" is the switching signal. Connect the "C" terminal of the thermostat to 3. the "C" terminal of the Zone Control. "C" is common.
(See diagram to right)
Digital Thermostat
C C R W
Wiring Powerheads
Connect the black wire of the powerhead to 1. the "Y1" terminal of the Zone Control. Connect the white wire of the powerhead to 2. the "Y2" terminal of the Zone Control. Connect a jumper from the "R1" terminal to 3. "R2" terminal of the Zone Control.
(See diagram to right)
Priority Operation
Switching the DIP switch to Priority "ON" will cause all other zones to stop operation until the prioritized zone is satised. When Priority is "OFF" all zones work independently.
Warning
Wiring connections must be made in accordance with all applicable electrical codes. Use copper wire only with a minimum temperature rating of 60/75°C. Failure to follow this instruction can result in personal injury or death and / or property damage. 12 - 18 gauge wire recommended for 120 VAC connections, 14 - 22 gauge wire for 24 VAC connections.
R W C
Y1 Y2 R1 R2
MAIN
END
SWITCH
T
BOILER
T
4 & 6 Zone Control
Powerheads
EXTRA
N/OCOM N/C
END
SWITCH
120 VAC
SYSTEM CIRCULATOR
DHW CIRCULATOR
NEUTRAL
HOT
301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 877-843-4262 • Fax: 800-976-9817 • E-Mail: service@viega.com • www.viega.com
Viega... The global leader in plumbing and heating systems.
PI-PR-18060 (Zone Control) xxxxxx 0209 Plant ID No.9300-2856 Rev
2 of 2
Page 29
Application
T200 Series
T200 series thermostats provide temperatur e control on a variety of heating, cooling and single stage heat pump applications.
The large LCD window displays room temperature including degree increments indicated by a series of dashes. The system heat output cycles on a 1 or 2F degree field selectable differential. The cool output differential is fixed at 2F degrees. The setpoint is displayed and changed by pressing one of the setpoin t buttons up or down. Installation is simplified by having all of the field wires mounted to the separate wall pla te.
This is a powered thermostat, which must receive 75 mA of power at all times.
T200 Series
Digital, On/Off Thermostat
General Instructions
Features
LCD window display
Jumper selectable 5 minute time delay for heating
and cooling applications
Mechanical contact for 40
(optional)
°
F limit freeze protection
Printed in U.S.A. 5/10 © Copyright 2010 Schneider Electric All Rights Reserved. F-27027-5
Page 30
SPECIFICATIONS Inputs
Outputs
Environment
Table-1 Model Chart.
Power Input: 20 to 32 Vac, 75 mA to 1.2 amps.
Electrical:
Battery, Setpoint backup (Energizer 357 or equivalent).
Mechanical:
Operating Differential, Heating 1 or 2F degrees (0.6 or 1.1C degrees), Cooling 2F
degrees (1.1C degrees).
Setpoint Adjustment Range, 50 to 86° F (10 to 30°C). Material, Rigid vinyl. Finish, Off-white.
Temperature limits:
Shipping & Storage, -40 to 125°F (-40 to 52°C).
Operating, 40 to 125°F (5 to 53°C). Humidity: 95% non-condensing. Shipping Weight: 0.4 lbs (170 g). Location: NEMA Type 1.
Model Control Outputs
T201 Heating Only None Heat/Off None No No
T201-FP
T205-FP
T207-FP
a On T20X-FP (freeze protection) models a relay will provide power to a valve or relay if the thermostat fails.
a
T204 Cooling Only On/Auto Cool/Off None No No T205 Cooling & Heating On/Auto Cool/Off/Heat Manual No No
a
T207 Cooling & Heating On/Auto Cool/Off/Heat Manual No Yes
a
Heating Only None Heat/Off None Yes No
Cooling & Heating On/Auto Cool/Off/Heat Manual Yes No
Cooling & Heating On/Auto Cool/Off/Heat Manual Yes Yes
Fan
Control
System
Switch
Changeover Mechanical Contact
B & O
Terminals
2 © Copyright 2010 Schneider Electric All Rights Reserved. F-27027-5
Page 31
TYPICAL APPLICATION (wiring diagram)
Figure-1 Terminal Identification.
DISPLAY
HEATING OPERATING
DIFFERENTIAL
HEAT CONTROL
COOL CONTROL
AUTO
FAN
CONTROL
HC
TH
RH RC
W
Y G B O
Table-2 Field Selectable Jumper Options.
Feature Jumpered Not Jumpered
1. Display Celsius Fahrenheit
2. Heating operation differential 2 degrees 1 degree
3. Heat control No delay 5 minute delay
4. Cool control* No delay 5 minute delay
* T201, heat only model, only has jumper options 1 thru 3. A fourth jumper location exists but is non-functional in heat only models.
F-27027-5 © Copyright 2010 Schneider Electric All Rights Reserved. 3
Page 32
RH
Figure-2 T201 Typical Wiring to Heating System With Single Transformer.
24 V AC
TRANSFORMER
24 V AC
120 V AC
FAN
RELAY
COOLING
RELAY
RC
Y
G
Optional 250 Ohm 5 watt resistor is needed only if power drops below 75 milliamps.
1
1
1
Figure-3 Typical T204 Wiring to Cooling System With Single Transformer.
Figure-4 Typical T205 Wiring to Heating/Cooling System With Single Transformer.
W
24 VAC
1
HEATING
RELAY
24 VAC
TRANSFORMER
120 VAC
1
Optional 250W 5 watt resistor is needed only if power drops below 75 milliamps.
FACTORY INSTALLED JUMPER
RH
RC
W
G
24 VAC HEATING
1
TRANSFORMER
24 VAC
Y
HEATING
RELAY
COOLING
RELAY
FAN
RELAY
120 VAC
1
If one of the secondary sides of both transformers are grounded, grounded sides must be connected together.
4 © Copyright 2010 Schneider Electric All Rights Reserved. F-27027-5
Page 33
INSTALLATION
24 VAC HEATING TRANSFORMER
24 VAC
120 VAC
24 VAC COOLING
TRANSFORMER
120 VAC
FAN
RELAY
COOLING
RELAY
RC
RH
Y
W
G
HEATING
RELAY
1
11If one of the secondary sides
of both transformers are grounded, grounded sides must be connected together.
FAC TORY INSTALLED JUMPER
Figure-5 Typical T205 Wiring to Heating/Cooling System With Dual Transformer.
24 VAC HEATING
TRANSFORMER
24 VAC
120 VAC
FAN
RELAY
COOLING
RELAY
RC
RH
Y
W
G
B
O
HEATING
RELAY
REVERSING
VALVE
1
1
Either the B or O output will be connected to the reversing valve. Terminal O supplies 24V on a call for cooling. Terminal B supplies 24V on a call for heat.
FACTORY INSTALLED JUMPER
Figure-6 Typical T207 Wiring To Heating/Cooling System With Single
Transformer & Reversing Valve.
Inspection
F-27027-5 © Copyright 2010 Schneider Electric All Rights Reserved. 5
Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products.
Requirements
Tools (not provided)
— Writer’s Note: Need list.
Training: Installer must be a qualified, experienced technician
Other accessories as appropria te
Page 34
Precautions
]
W A R N I N G
]
C A U T I O N
N O T E
N O T E
]
W A R N I N G
General
Electrical shock hazard! Disconnect power before installation to prevent electrical shock
or equipment damage.
Make all connections in accordance with the electrical wiring diagram and in accordance
with national and local electrical codes.
Avoid locations where excessive moisture, corrosive fumes, explosive vapors, or vibra-
tion are present.
Avoid electrical noise interference. Do not install near large conductors, electrical
machinery, or welding equipment.
Federal Communications Commission (FCC)
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reason­able protection against harmful interference in residential installations. This equipment gen­erates, uses, and can radiate radio frequency energy and may cause harmful interference if not installed and used in accordance with the instructions. Even when instructions are fol­lowed, there is no guarantee that interference will not occur in a particular installation. If this equipment causes harmful interference to radio and television reception—which can be determined by turning the equipment off and on—the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment to an outlet on a circuit different from that to which the receiver
is connected.
Consult the dealer or an experienced radio/television technician for help.
Canadian Department of Communications (DOC)
This class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le material broilleur du Canada.
European Standard EN 55022
This is a class B (European Classification) product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate mea­sures.
6 © Copyright 2010 Schneider Electric All Rights Reserved. F-27027-5
Page 35
Mounting
N O T E
Wiring
Mount the T200 series to a suitable surface. The T200 is shipped with an adapter plate (4-1/4 x 4-3/4 in.) that covers the mounting blemishes of a previous thermostat. New installation will not need the adapter plate. Do not mount on a surface that exceeds 125°F (52°C).
The T200 series is a powered thermostat which must receive 75 mA of power at all times.
Some systems may require a 250 ohm, 5 watt resistor (includ ed) to be installed across
the "W" and "C" terminals of the furnace or boiler control board (Figure-2) to assure proper current draw for the thermostat. Install the resistor if the thermostat setpoint cannot be adjusted, if the heating relay cycles too often (1-15 seconds), or if the heating relay will not cycle.
The T200 serie s cannot operate with a millivolt automatic self-powered gas heating
system unless an isolation relay and a separate 24 Vac transformer are used. Install an isolation relay if the ignition blower runs continuously or if the furnace will not shut off when the thermostat reaches the set temperature. Another symptom is that the furnace may not turn on.
T201
The T201 models are a heat only model with a "HEAT/OFF" system switch and no fan control. Applications include hydronic and radiant floor heating systems as well as gas and electric forced air heating systems. Refer to Figure-2.
T204
The T204 model is a cool only model with a "COOL/OFF" system switch and a "FAN ON/AUTO" fan switch. Applications include direct expansion cooling only systems. Refer to Figure-3.
T205
The T205 models are heat/cool models with manual changeover. The unit consists of a "COOL/OFF/HEAT" system switch and a "FAN/ON/AUTO" fan switch. Applications include hydronic heating and radiant floor heating systems as well as gas and electric forced air heating with conventional air conditioning systems. Refer to Figure-4 and Figure-5.
T207
The T207 models are heat/cool models with manual changeover and B (powered on heat demand) and O (powered on cool demand) terminals. The unit consists of a "COOL/OFF/HEAT" system switch and a "FAN ON/AUTO" fan switch. Applications include all of the T205 applications plus single stage heat pumps and forced air zoning systems that require B and O outputs. Refer to Figure-6.
For field selectable jumper options see Table-2. For jumper and terminal locations see Figure-1.
Auto Fan Control (HC/TH)
A three-pin jumper (Figure-1) is set to enable the HC or TH mode. The HC mode is used in electric heat applications to energize the fan relay at the same time
the heating relay is energized. The TH mode is used in fossil fuel applications where the furnace, not the thermostat, controls the fan directly. In this application, a call for heat only energizes the heating relay.
F-27027-5 © Copyright 2010 Schneider Electric All Rights Reserved. 7
Optional Freeze Protection
When the T200 thermostat is ordered with the FP option a limit switch is wired in parallel with the terminals R and W. This will provide power to a heating valve or relay if the thermostat fails. This provides freeze protection to 40 source.
°
F (4°C) as long as heat is available from the heat
Page 36
On October 1st, 2009, TAC bec am e t h e Buildings bus iness of its parent c om pany Schneider Electric . This document re flects the visual identity of Schneider Electric, however there remains references to T AC as a corporate brand in the body copy. As each document is updated, the body copy will be cha nged to r e flect ap propriate
g
CHECKOUT
7272
3-1/4
(81)
1-7/16
(36)
4-3/4
(121)
2-1/2
(64)
4-1/4 (108)
SYSTEM
SWITCH
FAN
SWITCH
Figure-7 T200 Series Dimensions.
MAINTENANCE
1. Verify jumper pin selections.
2. Verify that the T200 is wired correctly to your heating and or cooling loads.
3. Confirm that 75 milliamps are available at all times. To measure the current draw connect an ammeter (set to measure milliamps) in series with the heat or cool output. If power value is below 75 milliamps install a 250 ohm 5 watt resistor in parallel across the switched load. Recheck for 75 milliamps. The T200 thermostats must have 75 milliamps to function properly.
4. Verify system Heat/Cool/Fan outputs: Heating — Connect a voltmeter in parallel across the heat output terminal, W, and common of the power source. Cooling — Connect a voltmeter in parallel across the cooling output terminal, Y, and common of the power source. Fan — Connect a voltmeter in parallel across the fan terminal, G, and common of the power source.
5. The display will show the current room temperature as a number. Up to five dashes will appear under the number. Each dash represents 1/5 of a degree. The thermostats ON/OFF switching is based on whole degrees.
The T200 series requires no maintenance. Replace defective modules. Regular maintenance of the total system is recomended to assure sustained, optimum
performance.
FIELD REPAIR
DIMENSIONAL DATA
Replace battery with Energizer 357 or equivalent as needed. Replace any damaged or failed components with functional replacements.
corporate brand chan
Copyright 2010, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
F-27027-5
es.
Schneider Electric
1354 Clifford Avenue P.O. Box 2940 Loves Park, IL 61132-2940
www.schneider-electric.com/buildings
Page 37
TechData
2.36 in
Powerhead for Brass Manifolds
The Powerhead 18028 is a two position actuator for zone control which mounts on the return valve of the manifold. A 24V signal actuates the head to open the valve. The position of the valve is normally closed. The Powerhead may be used on all Brass 1" Viega heating manifolds. These powerheads are not compatible with Viega’s 1-1/4" Stainless Steel Manifolds.
Features
• Grey cap allows for easy distinction between the
brass powerhead and the Stainless Powerhead with the white cap.
• Three indicator windows allow the position of the
valve to be veried (valve is open when red bar is visible in window).
• Compact design provides additional clearance
for installation.
• 48 in. cable length allows most connections to be
made without additional wiring.
Dimensions
Specifications
Operating Voltage: 24 V
Current Consumption: Short increase to max. 2A when unit is cut in. Constant current during operation approx. 0.125 A at 24 V (3 VA).
Cable length: 48 in.
Transformer Capacity Required: Up to 8 Powerheads on a 40 VA transformer up to 15 Powerheads on a 75
VA transformer
This document subject to updates. For the most current Viega technical literature please visit www.viega.us.
Click Services -> Click Electronic Literature Downloads -> Select Product Line -> Select Desired Document
.
1.54 in.
Viega LLC, 100 N. Broadway, 6th Floor • Wichita, KS 67202 • Ph: 800-976-9819 • Fax: 316-425-7618
TD-PR 0412 (Powerhead for Brass Manifolds)
1 of 1
Loading...