for concealed cistern 2L, combination with WC flush plates
Visign for Public 2, Visign for Style 11, 12, and Visign for More
100, 102, 103 flush actuation via on-site potential-free contact
ModelYear built:
8350.32from 05/2012
en_INT
Page 2
WC flush actuation2 from 48
Page 3
Table of contents
1About these instructions for use4
Table of contents
1.1
1.2
1.3
Target groups4
Labelling of notes4
About this translated version5
2Product information6
2.1
2.2
2.3
2.3.1
2.4
2.4.1
2.4.2
2.4.3
2.4.4
2.4.5
2.5
Standards and regulations6
Safety advice6
Intended use6
Areas of use6
Product description8
Overview8
Technical data9
Operating mode10
System expansions11
Setting options14
Accessories15
3Handling17
3.1
3.1.1
3.1.2
3.2
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.3
3.3.1
3.3.2
3.4
3.5
3.5.1
3.5.2
3.6
Assembly information17
Mounting conditions17
Required material and tools18
Assembly19
Mounting the power pack19
Preparing the installation20
Mounting the flush actuation (cistern 2H)23
Mounting the flush actuation (cistern 2L)30
Connecting external sensors37
Commissioning39
Setting the flush39
Setting Hygiene+ function41
Faults, faults and remedy46
Care and maintenance47
Maintenance tips47
Replacing the battery47
Disposal48
WC flush actuation3 from 48
Page 4
About these instructions for use
1About these instructions for use
Trade mark rights exist for this document, further information can be
found at viega.com/legal.
1.1Target groups
The information in this instruction manual is directed at the following
groups of people:
n Heating and sanitary professionals and trained personnel
n Trained electricians
n Operators
n Consumers
1.2
It is not permitted for individuals without the abovementioned training or
qualification to mount, install and, if required, maintain this product. This
restriction does not extend to possible operating instructions.
The installation of Viega products must take place in accordance with
the general rules of engineering and the Viega instructions for use.
Labelling of notes
Warning and advisory texts are set aside from the remainder of the text
and are labelled with the relevant pictographs.
DANGER!
This symbol warns against possible life-threatening injury.
WARNING!
This symbol warns against possible serious injury.
CAUTION!
This symbol warns against possible injury.
NOTICE!
This symbol warns against possible damage to property.
WC flush actuation4 from 48
Page 5
1.3About this translated version
This instruction for use contains important information about the choice
of product or system, assembly and commissioning as well as intended
use and, if required, maintenance measures. The information about the
products, their properties and application technology are based on the
current standards in Europe (e. g. EN) and/or in Germany
(e. g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/
Germany. These should serve as recommendations in the absence of
corresponding national regulations. The relevant national laws, stand‐
ards, regulations, directives and other technical provisions take priority
over the German/European directives specified in this manual: The
information herein is not binding for other countries and regions; as said
above, they should be understood as a recommendation.
About these instructions for use
Notes give you additional helpful tips.
WC flush actuation5 from 48
Page 6
2Product information
2.1Standards and regulations
The following standards and regulations apply to Germany / Europe.
National regulations can be found on the relevant web site of your
country at viega.com/standards.
Regulations from section: Fields of application / Mounting conditions
Scope / NoticeRegulations applicable in Ger‐
suitable masonry wallsEN 1996-1-1
Product information
many
2.2Safety advice
Protection area for installation of
the power pack in shower and
bath rooms
Regulations from section: Technical data
Scope / NoticeRegulations applicable in Ger‐
Electrical approvalsEN 60950
Electrical approvalsEN 60335
Electrical approvalsEN 61558
DANGER!
Danger due to electrical current
An electric shock can lead to burns and serious injury and
even death.
VDE 0100-701
many
– Work on the electrics may only be carried out by trained
electricians.
2.3Intended use
2.3.1Areas of use
WCs in barrier-free sanitary rooms should be equipped with flush actua‐
tors that can be easily reached by users and carers. For this purpose,
the flush plate of the WC can be combined with a radio-controlled or
cabled sensor using an electronic flush actuation. A sensor such as this
can be fitted on e. g. the handles of the WC or in any position in the
room.
WC flush actuation6 from 48
Page 7
Hygiene+ function
Suitable cisterns
Product information
An electrical connection must be planned for the electronic
actuation in the area of the cistern when planning.
Flushes can be actuated at certain times via the Hygiene+ function to
prevent stagnation in the drinking water lines.
Installation is only possible in the following Viega concealed cisterns:
n Cistern model 2H
n Cistern model 2L
Ascertain which model is installed before mounting. The following infor‐
mation will help you to determine the model of the cistern installed:
Cistern 2H
The revision shaft of this cistern is found at a height of approx. 1 metre
on the front.
Cistern 2L
The revision shaft of this cistern is either found at a height of approx.
75 cm on the front or on the top.
Suitable manual flush plates
Mounting of the electronic flush actuation is only possible with the fol‐
lowing WC flush plates:
WC flush actuation7 from 48
Page 8
10
1
6
7
9
8
3
4
5
13
12
2
11
Product information
2.4Product description
2.4.1Overview
Product rangeName within the
product range
Visign for Public28327.1
Visign for Style11, 128331.1, 8332.1, 8332.4
Visign for More100, 102, 103, 104 8352.1, 8353.1, 8355.1,
Model number
8354.1
Fig. 1: Scope of delivery
1 - Bowden cable unit
2 - holder for control (for cistern 2H)
3 - holder for control (for cistern 2L)
4 - power pack 230 V
5 - connection cable external button
6 - holder for battery compartment
7 - fixing panel for motor
8 - Control
9 - cable tie
10 - drive unit
11 - Bowden cable
12 - manual actuation of large flush volume
13 - manual actuation of small flush volume
WC flush actuation8 from 48
Page 9
2.4.2Technical data
Flush volume
Product information
The product has the following technical data:
The flush volumes for the manual flush actuation are:
n Small flush volume: 3–4 litres
n Large flush volume: 6–9 litres
The following flush volumes can be set for the electronic actuation:
n Large flush volume: 4.5 / 6 / 9 litres
n Small flush volume: 3 / 4 litres
If the external sensor (e. g. a remote button on the handle) offers two
activation options, the electronic actuation can be used to select
between the large or small flush volume.
Electronics
Hygiene+ function
Input (power pack)100–240 V AC, 50–60 Hz, 180 mA
Output (power pack)6.5 V DC, 920 mA
Electrical approvals see section Ä „Regulations from sec‐
tion: Technical data“ on page 6.
Intervals24 / 72 / 168 hours
Hygiene flush volumes3 / 6 / 9 litres
WC flush actuation9 from 48
Page 10
2.4.3Operating mode
Electronic actuation of a flush
Product information
Fig. 2: Actuation of the flush via an external sensor
A signal is sent to control the flush actuation through an external sensor,
e. g. a button or photo sensor.
Fig. 3: Signal transmission from the control to the motor
The control transmits the electronic signal to the drive unit.
Fig. 4: The motor operates the Bowden cable
The motor opens the drain valve via the Bowden cable.
WC flush actuation10 from 48
Page 11
Product information
Fig. 5: The water flows into WC via the open drain valve
As long as the drain valve is open, the set flush volume will flow into the
WC.
Hygiene+ function
2.4.4
System expansions
Radio controlled actuation
Stagnation can lead to the build up of germs (e. g. legionella) in drinking
water pipes. It is important to rinse the pipeline regularly to prevent the
build up of bacteria. The Viega Hygiene+ function was developed for
this reason.
Flushes can be actuated at certain times with the Hygiene+ function.
Interval and flush volume will be set as required and saved by the con‐
trol. All settings remain saved during a power cut.
The system's range of functions can be expanded through the connec‐
tion of accessories onto the control.
Fig. 6: Connection of the radio receiver
One requires the following accessories to be able to connect a radio
receiver – instead of a cable-connected external sensor – as shown:
WC flush actuation11 from 48
Page 12
Additional external sensors
Product information
Signals to actuate the flush (e. g. on support hinged handles) sent by
HEWI radio transmitters can be received by the radio receiver model
8350.35.
Fig. 7: Connection of a second external button
One requires the following accessories to be able to connect an addi‐
tional external sensor as shown:
Multiple sensors can be connected at the same time using the exten‐
sion cable adapter model 8350.36. This is how e. g. two external, cableconnected buttons can be connected.
Buttons, switches or photo sensors for actuating the flush can be con‐
nected to the control on site via the connection cable sensitive model
8355.90.
Fig. 8: Connection of radio and cable sensors
One requires the following accessories to be able to connect a radio
controlled actuator alongside an external sensor as shown:
Multiple sensors can be connected at the same time using the exten‐
sion cable adapter model 8350.36. This is how e. g. a button can be
combined with a radio controlled actuation.
WC flush actuation13 from 48
Page 14
Redundant power supply
Product information
Signals to actuate the flush (e. g. on support hinged handles) sent by
HEWI radio transmitters can be received by the radio receiver model
8350.35.
2.4.5
Setting options
Flush settings
Fig. 9: Connection of the redundant power supply
To create a redundant power supply with an additional battery compart‐
ment as shown, you will need the following accessories:
The battery compartment can be connected for a redundant power
supply using the adapter model 8355.91. The battery compartment is
included in the adapter's scope of delivery.
Flush volume
This criterion relates exclusively to the flush volume for flush cycles
actuated electronically. The flush volume for hygiene flushes is set sep‐
arately.
WC flush actuation14 from 48
Page 15
Product information
The following settings are possible:
n Small flush volume 3 litres, large flush volume 4.5 litres
n Small flush volume 3 litres, large flush volume 6 litres (factory setting)
n Small flush volume 4 litres, large flush volume 9 litres
The Hygiene+ interval
The following settings are possible:
n Hygiene+ function deactivated (factory setting)
n Hygiene flush 24 hours after the last use
n Hygiene flush 72 hours after the last use
n Hygiene flush 168 hours after the last use
Hygiene+ flush volume
The following settings are possible:
n Hygiene+ flush volume 3 litres (factory setting)
n Hygiene+ flush volume 6 litres
n Hygiene+ flush volume 9 litres
2.5Accessories
Required accessories
Optional accessories
You require a flush plate so that the flush can be actuated directly at the
WC. The Viega models that can be used are found at Ä „Suitable
manual flush plates“ on page 7.
Installation set
The set model 8350.14 contains a hollow wall socket to house the
power pack and an empty pipe with the right clip to connect the cistern
(2H).
WC flush actuation15 from 48
Page 16
Product information
Extension cable
2 metre cable model 8352.690 for the extension of the power supply to
a maximum of 4.75 metres in length.
Programming set
This programming set is required to change the flush setting or activate
the Hygiene+ function. It contains a connection cable with a program‐
ming contact and a magnetic pin. The programming contact is mounted
behind the panel and connected to the blue terminal on the control. The
programming can then take place using the magnetic pin.
WC flush actuation16 from 48
Page 17
3Handling
X1
X2
X3
3.1Assembly information
3.1.1Mounting conditions
The model may only be used for the models mentioned in Ä Chapter
2.3.1 „Areas of use“ on page 6.
Installation position of the power pack
The power pack should be mounted in an easily accessible place to
allow subsequent access.
Before beginning to tile, a concealed socket should be installed for the
power pack with protective pipe to the cistern (installation set
Ä
Handling
„Optional accessories“ on page 15).
If necessary, the power pack cable can be extended to a length of
X1 max. 0.75 m
X2 max. 2.75 m with an extension cable (article number 628 505)
X3 max. 4.75 m with two extension cables (article number 628 505)
An extension of the mains supply by more than 5 metres can
lead to a situation in which the power is not sufficient to
actuate the flush.
Protected zone
WC flush actuation17 from 48
Page 18
Handling
Fig. 11: Protected zones
According to the applicable regulations, installation of the power pack in
the protected zones 0 and 1 of shower rooms and bathrooms is not per‐
mitted, see Ä „Regulations from section: Fields of application /
Mounting conditions“ on page 6.
External sensors (optional)
3.1.2
Required material and tools
Material
Tool
We recommend installing the power pack outside of the protected
zones 0–2.
If external sensors are to be connected to the control, their connection
lines or protective pipes must be laid in the cistern before tiling is
begun.
The following material is required for mounting:
n a suitable flush plate Ä „Suitable manual flush plates“ on page 7
Ä
n Programming set
„Optional accessories“ on page 15
n if necessary, empty pipe from power pack into the cistern
n if necessary, accessories for the extension of the system Ä Chapter
2.4.4 „System expansions“ on page 11
The following tools are required for mounting:
n flat screwdriver
n spanner (SW 19)
n knife (cutter)
WC flush actuation18 from 48
Page 19
3.2Assembly
3.2.1Mounting the power pack
Requirements:
Handling
DANGER!
Danger due to electrical current
An electric shock can lead to burns and serious injury and
even death.
– Work on the electrics may only be carried out by trained
electricians.
– Always de-energise the connection line before work is
commenced.
n A 230 V mains connection is available on site.
n The installation position of the power pack complies with the require‐
ments in acc. with Ä „Installation position of the power pack“
on page 17.
n The connection pipeline is de-energised.
Remove approx. 1 cm of the insulation on the connection pipeline.
Push the connection pipeline into the clamps.
WC flush actuation19 from 48
Page 20
3.2.2Preparing the installation
Requirements:
n The cistern is fitted into the pre-wall.
n If external sensors are to be connected, the cables must be laid
n The electrical connection is laid all the way into the cistern.
n The pre-wall is tiled.
Handling
The following work stages and diagrams differ depending on
the cistern being used. The relevant steps are marked
accordingly.
through to the cistern.
Cut into shaft cover.
Remove shaft cover.
WC flush actuation20 from 48
Page 21
Handling
Score the revision shaft along the edge of the tiles with a knife.
Angle the knife to do this so that the cut is made flush to the surface
of the wall.
Cut the corners of the revision shaft vertically through to the wall
surface.
Bend out and pull down the sides of the revision shaft.
The edge of the revisions shaft must be flush with the wall surface.
Remove cistern cover.
Remove and keep the threaded bolts from the cistern cover.
Dispose of cistern cover.
WC flush actuation21 from 48
Page 22
Handling
INFO! Only for assembly of the flush plate in cistern 2H or on the
front of cistern 2L.
Press the bow backwards from the mounting of the mechanism.
INFO! Only for assembly of the flush plate on the top of cistern
2L.
Press the bow backwards from the mounting of the mechanism.
Turn the mechanism's lock by 90° in an anti-clockwise direction.
The mechanism is unlocked and can be removed.
ð
Remove and keep mechanism.
WC flush actuation22 from 48
Page 23
INFO! Only with the cistern 2H.
Remove and keep spacer.
3.2.3Mounting the flush actuation (cistern 2H)
Requirements:
Handling
n The revision shaft is shortened in such a way that it is flush with the
upper edge of the tiles.
n Mechanism, bow and spacer are removed.
Close corner valve.
Loosen flexible hose on the filling valve (size 19).
WC flush actuation23 from 48
Page 24
Mounting the drive unit
Handling
Open the corner valve for a few seconds to rinse the pipe.
Re-close corner valve.
Lead the panel into the cistern at an angle.
Align the right side of the holding panel with the shaft frame of the
cistern.
The hook on the right side of the holding panel must be positioned
on the projection of the shaft frame.
WC flush actuation24 from 48
Page 25
Handling
Align the holding panel horizontally.
The bow on the left side of the holding panel must be firmly posi‐
tioned between the vertical fins of the back wall.
Push the drive unit onto the holding panel.
The drive unit must be secure in the guiding rail.
If the holding panel for the drive unit is mounted, remove holding
panel.
Push the Bowden cable unit onto the drain valve from the left.
The Bowden cable unit must be felt to click into place on the drain
valve.
WC flush actuation25 from 48
Page 26
Mounting the holder for control
Handling
Position the holder on the domes.
Push rubber plugs onto the dome to secure the holder.
Connecting the control
Observation of the prescribed connection sequence is
required. The power supply must always be connected last,
to ensure that all of the connected components function.
INFO! Mounting is much easier if the plug is inserted into the
control outside of the cistern.
Connect the red plug of the Bowden cable unit motor to the red
connection of the control.
WC flush actuation26 from 48
Page 27
Handling
Connect the blue connection cable from the sensor to the blue con‐
nection of the control.
Also observe section Ä Chapter 3.2.5 „Connecting external sen‐
sors“ on page 37.
Connect the black cable of the power supply to the outer right con‐
nection of the control.
INFO! Settings for the control can also already be made at
this point. The programming set is easier to connect if the
control is not yet installed in the cistern. Ä Chapter 3.3 „Com‐
missioning“ on page 39
Connecting the water supply pipe
Insert the control into the bracket in the cistern.
Fit the cable into the upper part of the cistern and fix with the cable
ties supplied. The cable must not obstruct any moving parts in the
cistern.
WC flush actuation27 from 48
Page 28
Connect the flexible hose onto the filling valve.
Open corner valve.
Handling
Insert spacer.
Mounting the battery compartment (optional)
WC flush actuation28 from 48
Page 29
Handling
Push the holder for the battery compartment onto the spacer from
the left.
Push the battery compartment through the large opening into the
holder.
Push the battery compartment into the smaller opening.
Mounting the mechanism
The battery compartment must be clicked into place directly behind
the cover in the holder.
Hang the mechanism in the bow of the drain valve.
WC flush actuation29 from 48
Page 30
Insert mechanism.
The mechanism must sit exactly in the recesses of the cistern.
Turn the mechanism's lock by 90° in a clockwise direction.
The mechanism is locked.
ð
Handling
As the next step, fitting of the flush plate as per the instruc‐
tion manual supplied.
3.2.4Mounting the flush actuation (cistern 2L)
Requirements:
n The revision shaft is shortened in such a way that it is flush with the
upper edge of the tiles.
n Mechanism and bow have been removed.
Close corner valve.
WC flush actuation30 from 48
Page 31
Loosen flexible hose on the filling valve (size 19).
Open the corner valve for a few seconds to rinse the pipe.
Re-close corner valve.
Handling
Mounting the drive unit
If the holding panel is not mounted on the Bowden cable unit, posi‐
tion the holding panel.
WC flush actuation31 from 48
Page 32
Handling
Place the drive unit onto the holding panel.
Push the Bowden cable unit onto the drain valve from the left.
The Bowden cable unit must be felt to click into place on the drain
valve.
Mounting the holder for control
Position holder with recess on the corner valve.
WC flush actuation32 from 48
Page 33
Connecting the control
Handling
Push holder backwards until it clicks into place on the plug in the
back wall.
Observation of the prescribed connection sequence is
required. The power supply must always be connected last,
to ensure that all of the connected components function.
INFO! Mounting is much easier if the plug is inserted into the
control outside of the cistern.
Connect the red plug of the Bowden cable unit motor to the red
connection of the control.
Connect the blue connection cable from the sensor to the blue con‐
nection of the control.
Also observe section Ä Chapter 3.2.5 „Connecting external sen‐
sors“ on page 37.
WC flush actuation33 from 48
Page 34
Handling
Connect the black cable of the power supply to the outer right con‐
nection of the control.
INFO! Settings for the control can also already be made at
this point. The programming set is easier to connect if the
control is not yet installed in the cistern. Ä Chapter 3.3 „Com‐
missioning“ on page 39
Insert the control into the bracket in the cistern.
Connecting the water supply pipe
Fit the cable into the upper part of the cistern and fix with the cable
ties supplied. The cable must not obstruct any moving parts in the
cistern.
Connect the flexible hose onto the filling valve.
WC flush actuation34 from 48
Page 35
Open corner valve.
Mounting the battery compartment (optional)
Place the battery compartment onto the control holder.
Handling
Mounting the mechanism
Vertical installation (flush plate
on the front of the cistern)
If necessary, secure the battery compartment with a cable tie.
How to install the mechanism depends on whether the flush
plate is to be fitted to the front or top of the cistern.
Hang the mechanism in the bow of the drain valve.
WC flush actuation35 from 48
Page 36
Insert mechanism.
The mechanism must sit exactly in the recesses of the cistern.
Turn the mechanism's lock by 90° in a clockwise direction.
The mechanism is locked.
ð
Handling
Horizontal installation (flush
plate on the top of the cistern)
Hang the mechanism in the bow of the drain valve.
WC flush actuation36 from 48
Page 37
Handling
Insert mechanism.
In doing so, ensure that the tracks on the top and bottom edge of
the mechanism are in the indentations in the revision shaft of the
cistern.
Turn the mechanism's lock by 90° in a clockwise direction.
The mechanism is locked.
ð
3.2.5Connecting external sensors
As the next step, fitting of the flush plate as per the instruc‐
tion manual supplied.
NOTICE!
Damage to property due to excess voltage
If you apply voltage to the connection cable for the external
button, you will damage the control.
– Do not apply any external voltage!
WC flush actuation37 from 48
Page 38
Handling
Requirements:
n Button with locking function or potential-free contact (closure time at
least 350 ms) available
n Connection cable model 8355.90 available
Connect the contact to actuate the small flush volume between the
green (1) and yellow cable (3).
Connect the contact to actuate the large flush volume between the
green (1) and white cable (2).
Isolate the brown cable.
Connect the connection cable to the control.
WC flush actuation38 from 48
Page 39
3.3Commissioning
3.3.1Setting the flush
Programming block
Handling
Programming the control can be carried out for 30 minutes after the
supply voltage is applied. The control returns to normal operation after
30 minutes – programming is now blocked. If the settings have to be
changed after this time, the control must be disconnected from the
power supply for at least 10 seconds.
The programming set required to program the device is not
included in the scope of delivery. It can be purchased sepa‐
rately as accessory. Ä „Optional accessories“ on page 15
Observe the following features during programming:
– Only one value can be set per programming step.
– The settings are retained, even if there is an interruption
in the power supply.
– The programming process can be cancelled without a
change of the settings by holding the magnetic key in
front of the programming contact until no acoustic signal
has sounded for more than two seconds.
Setting the flush volume
Requirements:
n The revision shaft is open and the control can be accessed.
n The control programming block is not active.
n The programming set is available.
Remove the protective cap of the programming connection from the
control.
WC flush actuation39 from 48
Page 40
Connect the cable of the programming contact to the control.
Hold the magnetic key over the programming contact.
In the following, signals sound to show which setting is active.
ð
Handling
Remove magnetic key to enable setting.
The following values can be set by removing the magnetic key:
Remove magnetic key afterSetting
1st acoustic signalFlush volume small 3 l and
large 4.5 l
2nd acoustic signalFlush volume small 3 l and
large 6 l (factory setting)
3rd acoustic signalFlush volume small 4 l and
large 9 l
A double acoustic signal is sounded as confirmation. The set‐
ð
ting has been changed successfully.
WC flush actuation40 from 48
Page 41
Remove the cable of the programming contact.
Place a protective cap onto the contact.
Handling
3.3.2Setting Hygiene+ function
The Hygiene+ function is deactivated when delivered. If you wish to use
the Hygiene+ function, you must program the following settings.
The flush volume for the Hygiene+ function can only be
selected if the Hygiene+ function has been activated by
choosing a flushing interval.
If no flush volume is selected after activating the Hygiene
+ function, the flush volume is set automatically to the min‐
imum volume.
WC flush actuation41 from 48
Page 42
Setting the flush interval
Handling
Requirements:
n The revision shaft is open and the control can be accessed.
n The control programming block is not active Ä „ Programming
block “ on page 39.
n The programming set is available.
Remove the protective cap of the programming connection from the
control.
Connect the cable from the programming contact onto the control.
WC flush actuation42 from 48
Page 43
Hold the magnetic key in front of the programming contact.
In the following, signals sound to show which setting is active.
ð
Remove magnetic key to enable setting.
The following values can be set by removing the magnetic key:
Handling
Remove magnetic key afterSetting
8th acoustic signalHygiene+ flush volume 3 l (fac‐
tory setting, if Hygiene+ is
active)
9th acoustic signalHygiene+ flush volume 6 l
10th Acoustic signalHygiene+ flush volume 9 l
A double acoustic signal is sounded as confirmation. The set‐
ð
ting has been successfully changed.
Remove the cable of the programming contact.
WC flush actuation43 from 48
Page 44
Setting Hygiene+ flush volume
Handling
Place a protective cap onto the contact.
Requirements:
n The revision shaft is open and the control can be accessed.
n The control programming block is not active Ä „ Programming
block “ on page 39.
n The programming set is available.
n The Hygiene+ interval is set.
Remove the protective cap of the programming connection from the
control.
WC flush actuation44 from 48
Page 45
Handling
Connect the cable from the programming contact onto the control.
Hold the magnetic key in front of the programming contact.
In the following, signals sound to show which setting is active.
ð
Remove magnetic key to enable setting.
The following values can be set by removing the magnetic key:
Remove magnetic key afterSetting
4th acoustic signalHygiene flush function: OFF
(factory setting)
5th acoustic signalHygiene flush performed
24 hours after the last flush
6th acoustic signalHygiene flush 72 hours after
the last use
7th acoustic signalHygiene flush 168 hours after
the last use
A double acoustic signal is sounded as confirmation. The set‐
ð
ting has been successfully changed.
WC flush actuation45 from 48
Page 46
Remove the cable of the programming contact.
Place a protective cap onto the contact.
Handling
3.4
ErrorCauseRemedy
WC does not flushPower supply failureactuate manual flush
WC flush runs throughDirty seal in filling valveCheck seal, replace if necessary
Faults, faults and remedy
Cistern is not yet completely fullWait until the cistern is sufficiently
No water in cistern, corner valve is
closed
Control defectReplace control
Plug connection power pack /
control not made
Plug connection drive unit / control
not made
Dirty seal in drain valveCheck seal, replace if necessary
manual actuation is not workingThe mechanism is not connected
to the bow
WC flush actuation46 from 48
Hang the mechanism in the bow
Page 47
3.5Care and maintenance
3.5.1Maintenance tips
The flush actuation requires no care.
3.5.2Replacing the battery
Cistern 2L
Handling
When maintaining the flush plate, heed the instructions of
the flush plate manual.
Only for use of a battery compartment for redundant power
supply.
Requirements:
n The flush plate has been removed.
n The mechanism has been removed (compare Ä Chapter 3.2.2 „Pre‐
paring the installation“ on page 20).
n Free access to the cistern can be gained through the revision shaft.
Remove the battery compartment from the cistern.
Open battery compartment and remove flat battery.
WC flush actuation47 from 48
Page 48
Insert new battery and close battery compartment.
Place the battery compartment onto the control holder.
If necessary, secure the battery compartment with a cable tie.
Handling
3.6
Replace and lock mechanism.
Mount flush plate according to manual.
Disposal
Separate the product and packaging materials (e. g. paper, metal,
plastic or non-ferrous metals) and dispose of in accordance with valid
national legal requirements.
WC flush actuation48 from 48
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.