Viega 8350.32, 8350.31 Instructions For Use Manual

Page 1
WC flush actuation
Instructions for Use
for concealed cistern 2L, combination with WC flush plates Visign for Public 2, Visign for Style 11, 12, and Visign for More 100, 102, 103 flush actuation via on-site potential-free contact
Model Year built:
8350.32 from 05/2012
en_INT
Page 2
Page 3

Table of contents

1 About these instructions for use 4
Table of contents
1.1
1.2
1.3
Target groups 4
Labelling of notes 4
About this translated version 5
2 Product information 6
2.1
2.2
2.3
2.3.1
2.4
2.4.1
2.4.2
2.4.3
2.4.4
2.4.5
2.5
Standards and regulations 6
Safety advice 6
Intended use 6
Areas of use 6
Product description 8
Overview 8
Technical data 9
Operating mode 10
System expansions 11
Setting options 14
Accessories 15
3 Handling 17
3.1
3.1.1
3.1.2
3.2
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.3
3.3.1
3.3.2
3.4
3.5
3.5.1
3.5.2
3.6
Assembly information 17
Mounting conditions 17
Required material and tools 18
Assembly 19
Mounting the power pack 19
Preparing the installation 20
Mounting the flush actuation (cistern 2H) 23
Mounting the flush actuation (cistern 2L) 30
Connecting external sensors 37
Commissioning 39
Setting the flush 39
Setting Hygiene+ function 41
Faults, faults and remedy 46
Care and maintenance 47
Maintenance tips 47
Replacing the battery 47
Disposal 48
Page 4
About these instructions for use

1 About these instructions for use

Trade mark rights exist for this document, further information can be found at viega.com/legal.

1.1 Target groups

The information in this instruction manual is directed at the following groups of people:
n Heating and sanitary professionals and trained personnel n Trained electricians n Operators n Consumers
1.2
It is not permitted for individuals without the abovementioned training or qualification to mount, install and, if required, maintain this product. This restriction does not extend to possible operating instructions.
The installation of Viega products must take place in accordance with the general rules of engineering and the Viega instructions for use.
Labelling of notes
Warning and advisory texts are set aside from the remainder of the text and are labelled with the relevant pictographs.
DANGER! This symbol warns against possible life-threatening injury.
WARNING! This symbol warns against possible serious injury.
CAUTION! This symbol warns against possible injury.
NOTICE! This symbol warns against possible damage to property.
Page 5

1.3 About this translated version

This instruction for use contains important information about the choice of product or system, assembly and commissioning as well as intended use and, if required, maintenance measures. The information about the products, their properties and application technology are based on the current standards in Europe (e. g. EN) and/or in Germany (e. g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/ Germany. These should serve as recommendations in the absence of corresponding national regulations. The relevant national laws, stand‐ ards, regulations, directives and other technical provisions take priority over the German/European directives specified in this manual: The information herein is not binding for other countries and regions; as said above, they should be understood as a recommendation.
About these instructions for use
Notes give you additional helpful tips.
Page 6

2 Product information

2.1 Standards and regulations

The following standards and regulations apply to Germany / Europe. National regulations can be found on the relevant web site of your country at viega.com/standards.
Regulations from section: Fields of application / Mounting conditions
Scope / Notice Regulations applicable in Ger‐
suitable masonry walls EN 1996-1-1
Product information
many

2.2 Safety advice

Protection area for installation of the power pack in shower and bath rooms
Regulations from section: Technical data
Scope / Notice Regulations applicable in Ger‐
Electrical approvals EN 60950
Electrical approvals EN 60335
Electrical approvals EN 61558
DANGER! Danger due to electrical current
An electric shock can lead to burns and serious injury and even death.
VDE 0100-701
many
– Work on the electrics may only be carried out by trained
electricians.

2.3 Intended use

2.3.1 Areas of use

WCs in barrier-free sanitary rooms should be equipped with flush actua‐ tors that can be easily reached by users and carers. For this purpose, the flush plate of the WC can be combined with a radio-controlled or cabled sensor using an electronic flush actuation. A sensor such as this can be fitted on e. g. the handles of the WC or in any position in the room.
Page 7
Hygiene+ function
Suitable cisterns
Product information
An electrical connection must be planned for the electronic actuation in the area of the cistern when planning.
Flushes can be actuated at certain times via the Hygiene+ function to prevent stagnation in the drinking water lines.
Installation is only possible in the following Viega concealed cisterns:
n Cistern model 2H n Cistern model 2L
Ascertain which model is installed before mounting. The following infor‐ mation will help you to determine the model of the cistern installed:
Cistern 2H
The revision shaft of this cistern is found at a height of approx. 1 metre on the front.
Cistern 2L
The revision shaft of this cistern is either found at a height of approx. 75 cm on the front or on the top.
Suitable manual flush plates
Mounting of the electronic flush actuation is only possible with the fol‐ lowing WC flush plates:
Page 8
10
1
6
7
9
8
3
4
5
13
12
2
11
Product information

2.4 Product description

2.4.1 Overview

Product range Name within the
product range
Visign for Public 2 8327.1
Visign for Style 11, 12 8331.1, 8332.1, 8332.4
Visign for More 100, 102, 103, 104 8352.1, 8353.1, 8355.1,
Model number
8354.1
Fig. 1: Scope of delivery
1 - Bowden cable unit 2 - holder for control (for cistern 2H) 3 - holder for control (for cistern 2L) 4 - power pack 230 V 5 - connection cable external button 6 - holder for battery compartment 7 - fixing panel for motor 8 - Control 9 - cable tie 10 - drive unit 11 - Bowden cable 12 - manual actuation of large flush volume 13 - manual actuation of small flush volume
Page 9

2.4.2 Technical data

Flush volume
Product information
The product has the following technical data:
The flush volumes for the manual flush actuation are:
n Small flush volume: 3–4 litres n Large flush volume: 6–9 litres
The following flush volumes can be set for the electronic actuation:
n Large flush volume: 4.5 / 6 / 9 litres n Small flush volume: 3 / 4 litres
If the external sensor (e. g. a remote button on the handle) offers two activation options, the electronic actuation can be used to select between the large or small flush volume.
Electronics
Hygiene+ function
Input (power pack) 100–240 V AC, 50–60 Hz, 180 mA
Output (power pack) 6.5 V DC, 920 mA
Electrical approvals see section Ä „Regulations from sec‐ tion: Technical data“ on page 6.
Intervals 24 / 72 / 168 hours
Hygiene flush volumes 3 / 6 / 9 litres
Page 10

2.4.3 Operating mode

Electronic actuation of a flush
Product information
Fig. 2: Actuation of the flush via an external sensor
A signal is sent to control the flush actuation through an external sensor, e. g. a button or photo sensor.
Fig. 3: Signal transmission from the control to the motor
The control transmits the electronic signal to the drive unit.
Fig. 4: The motor operates the Bowden cable
The motor opens the drain valve via the Bowden cable.
WC flush actuation 10 from 48
Page 11
Product information
Fig. 5: The water flows into WC via the open drain valve
As long as the drain valve is open, the set flush volume will flow into the WC.
Hygiene+ function
2.4.4
System expansions
Radio controlled actuation
Stagnation can lead to the build up of germs (e. g. legionella) in drinking water pipes. It is important to rinse the pipeline regularly to prevent the build up of bacteria. The Viega Hygiene+ function was developed for this reason.
Flushes can be actuated at certain times with the Hygiene+ function. Interval and flush volume will be set as required and saved by the con‐ trol. All settings remain saved during a power cut.
The system's range of functions can be expanded through the connec‐ tion of accessories onto the control.
Fig. 6: Connection of the radio receiver
One requires the following accessories to be able to connect a radio receiver – instead of a cable-connected external sensor – as shown:
WC flush actuation 11 from 48
Page 12
Additional external sensors
Product information
Signals to actuate the flush (e. g. on support hinged handles) sent by HEWI radio transmitters can be received by the radio receiver model
8350.35.
Fig. 7: Connection of a second external button
One requires the following accessories to be able to connect an addi‐ tional external sensor as shown:
Multiple sensors can be connected at the same time using the exten‐ sion cable adapter model 8350.36. This is how e. g. two external, cable­connected buttons can be connected.
WC flush actuation 12 from 48
Page 13
Additional radio controlled actuation
Product information
Additionally required: 1 connection cable sensitive.
Buttons, switches or photo sensors for actuating the flush can be con‐ nected to the control on site via the connection cable sensitive model
8355.90.
Fig. 8: Connection of radio and cable sensors
One requires the following accessories to be able to connect a radio controlled actuator alongside an external sensor as shown:
Multiple sensors can be connected at the same time using the exten‐ sion cable adapter model 8350.36. This is how e. g. a button can be combined with a radio controlled actuation.
WC flush actuation 13 from 48
Page 14
Redundant power supply
Product information
Signals to actuate the flush (e. g. on support hinged handles) sent by HEWI radio transmitters can be received by the radio receiver model
8350.35.
2.4.5
Setting options
Flush settings
Fig. 9: Connection of the redundant power supply
To create a redundant power supply with an additional battery compart‐ ment as shown, you will need the following accessories:
The battery compartment can be connected for a redundant power supply using the adapter model 8355.91. The battery compartment is included in the adapter's scope of delivery.
Flush volume
This criterion relates exclusively to the flush volume for flush cycles actuated electronically. The flush volume for hygiene flushes is set sep‐ arately.
WC flush actuation 14 from 48
Page 15
Product information
The following settings are possible:
n Small flush volume 3 litres, large flush volume 4.5 litres n Small flush volume 3 litres, large flush volume 6 litres (factory setting) n Small flush volume 4 litres, large flush volume 9 litres
The Hygiene+ interval
The following settings are possible:
n Hygiene+ function deactivated (factory setting) n Hygiene flush 24 hours after the last use n Hygiene flush 72 hours after the last use n Hygiene flush 168 hours after the last use
Hygiene+ flush volume
The following settings are possible:
n Hygiene+ flush volume 3 litres (factory setting) n Hygiene+ flush volume 6 litres n Hygiene+ flush volume 9 litres

2.5 Accessories

Required accessories
Optional accessories
You require a flush plate so that the flush can be actuated directly at the WC. The Viega models that can be used are found at Ä „Suitable manual flush plates“ on page 7.
Installation set
The set model 8350.14 contains a hollow wall socket to house the power pack and an empty pipe with the right clip to connect the cistern (2H).
WC flush actuation 15 from 48
Page 16
Product information
Extension cable
2 metre cable model 8352.690 for the extension of the power supply to a maximum of 4.75 metres in length.
Programming set
This programming set is required to change the flush setting or activate the Hygiene+ function. It contains a connection cable with a program‐ ming contact and a magnetic pin. The programming contact is mounted behind the panel and connected to the blue terminal on the control. The programming can then take place using the magnetic pin.
WC flush actuation 16 from 48
Page 17

3 Handling

X1
X2
X3

3.1 Assembly information

3.1.1 Mounting conditions

The model may only be used for the models mentioned in Ä Chapter
2.3.1 „Areas of use“ on page 6.
Installation position of the power pack
The power pack should be mounted in an easily accessible place to allow subsequent access.
Before beginning to tile, a concealed socket should be installed for the power pack with protective pipe to the cistern (installation set
Ä
Handling
„Optional accessories“ on page 15).
If necessary, the power pack cable can be extended to a length of
4.75 metres (two extension cables Ä „Optional accessories“
on page 15).
Fig. 10: Installation position of the power pack
X1 max. 0.75 m X2 max. 2.75 m with an extension cable (article number 628 505) X3 max. 4.75 m with two extension cables (article number 628 505)
An extension of the mains supply by more than 5 metres can lead to a situation in which the power is not sufficient to actuate the flush.
Protected zone
WC flush actuation 17 from 48
Page 18
Handling
Fig. 11: Protected zones
According to the applicable regulations, installation of the power pack in the protected zones 0 and 1 of shower rooms and bathrooms is not per‐ mitted, see Ä „Regulations from section: Fields of application / Mounting conditions“ on page 6.
External sensors (optional)
3.1.2
Required material and tools
Material
Tool
We recommend installing the power pack outside of the protected zones 0–2.
If external sensors are to be connected to the control, their connection lines or protective pipes must be laid in the cistern before tiling is begun.
The following material is required for mounting:
n a suitable flush plate Ä „Suitable manual flush plates“ on page 7
Ä
n Programming set
„Optional accessories“ on page 15
n if necessary, empty pipe from power pack into the cistern n if necessary, accessories for the extension of the system Ä Chapter
2.4.4 „System expansions“ on page 11
The following tools are required for mounting:
n flat screwdriver n spanner (SW 19) n knife (cutter)
WC flush actuation 18 from 48
Page 19

3.2 Assembly

3.2.1 Mounting the power pack

Requirements:
Handling
DANGER! Danger due to electrical current
An electric shock can lead to burns and serious injury and even death.
– Work on the electrics may only be carried out by trained
electricians.
– Always de-energise the connection line before work is
commenced.
n A 230 V mains connection is available on site. n The installation position of the power pack complies with the require‐
ments in acc. with Ä „Installation position of the power pack“ on page 17.
n The connection pipeline is de-energised.
Remove approx. 1 cm of the insulation on the connection pipeline.
Push the connection pipeline into the clamps.
WC flush actuation 19 from 48
Page 20

3.2.2 Preparing the installation

Requirements:
n The cistern is fitted into the pre-wall. n If external sensors are to be connected, the cables must be laid
n The electrical connection is laid all the way into the cistern. n The pre-wall is tiled.
Handling
The following work stages and diagrams differ depending on the cistern being used. The relevant steps are marked accordingly.
through to the cistern.
Cut into shaft cover.
Remove shaft cover.
WC flush actuation 20 from 48
Page 21
Handling
Score the revision shaft along the edge of the tiles with a knife.
Angle the knife to do this so that the cut is made flush to the surface of the wall.
Cut the corners of the revision shaft vertically through to the wall surface.
Bend out and pull down the sides of the revision shaft.
The edge of the revisions shaft must be flush with the wall surface.
Remove cistern cover.
Remove and keep the threaded bolts from the cistern cover.
Dispose of cistern cover.
WC flush actuation 21 from 48
Page 22
Handling
INFO! Only for assembly of the flush plate in cistern 2H or on the front of cistern 2L.
Press the bow backwards from the mounting of the mechanism.
INFO! Only for assembly of the flush plate on the top of cistern 2L.
Press the bow backwards from the mounting of the mechanism.
Turn the mechanism's lock by 90° in an anti-clockwise direction.
The mechanism is unlocked and can be removed.
ð
Remove and keep mechanism.
WC flush actuation 22 from 48
Page 23
INFO! Only with the cistern 2H.
Remove and keep spacer.

3.2.3 Mounting the flush actuation (cistern 2H)

Requirements:
Handling
n The revision shaft is shortened in such a way that it is flush with the
upper edge of the tiles.
n Mechanism, bow and spacer are removed.
Close corner valve.
Loosen flexible hose on the filling valve (size 19).
WC flush actuation 23 from 48
Page 24
Mounting the drive unit
Handling
Open the corner valve for a few seconds to rinse the pipe.
Re-close corner valve.
Lead the panel into the cistern at an angle.
Align the right side of the holding panel with the shaft frame of the cistern.
The hook on the right side of the holding panel must be positioned on the projection of the shaft frame.
WC flush actuation 24 from 48
Page 25
Handling
Align the holding panel horizontally.
The bow on the left side of the holding panel must be firmly posi‐ tioned between the vertical fins of the back wall.
Push the drive unit onto the holding panel.
The drive unit must be secure in the guiding rail.
If the holding panel for the drive unit is mounted, remove holding panel.
Push the Bowden cable unit onto the drain valve from the left.
The Bowden cable unit must be felt to click into place on the drain valve.
WC flush actuation 25 from 48
Page 26
Mounting the holder for control
Handling
Position the holder on the domes.
Push rubber plugs onto the dome to secure the holder.
Connecting the control
Observation of the prescribed connection sequence is required. The power supply must always be connected last, to ensure that all of the connected components function.
INFO! Mounting is much easier if the plug is inserted into the control outside of the cistern.
Connect the red plug of the Bowden cable unit motor to the red connection of the control.
WC flush actuation 26 from 48
Page 27
Handling
Connect the blue connection cable from the sensor to the blue con‐ nection of the control.
Also observe section Ä Chapter 3.2.5 „Connecting external sen‐ sors“ on page 37.
Connect the black cable of the power supply to the outer right con‐ nection of the control.
INFO! Settings for the control can also already be made at this point. The programming set is easier to connect if the control is not yet installed in the cistern. Ä Chapter 3.3 „Com‐ missioning“ on page 39
Connecting the water supply pipe
Insert the control into the bracket in the cistern.
Fit the cable into the upper part of the cistern and fix with the cable ties supplied. The cable must not obstruct any moving parts in the cistern.
WC flush actuation 27 from 48
Page 28
Connect the flexible hose onto the filling valve.
Open corner valve.
Handling
Insert spacer.
Mounting the battery compartment (optional)
WC flush actuation 28 from 48
Page 29
Handling
Push the holder for the battery compartment onto the spacer from the left.
Push the battery compartment through the large opening into the holder.
Push the battery compartment into the smaller opening.
Mounting the mechanism
The battery compartment must be clicked into place directly behind the cover in the holder.
Hang the mechanism in the bow of the drain valve.
WC flush actuation 29 from 48
Page 30
Insert mechanism.
The mechanism must sit exactly in the recesses of the cistern.
Turn the mechanism's lock by 90° in a clockwise direction.
The mechanism is locked.
ð
Handling
As the next step, fitting of the flush plate as per the instruc‐ tion manual supplied.

3.2.4 Mounting the flush actuation (cistern 2L)

Requirements:
n The revision shaft is shortened in such a way that it is flush with the
upper edge of the tiles.
n Mechanism and bow have been removed.
Close corner valve.
WC flush actuation 30 from 48
Page 31
Loosen flexible hose on the filling valve (size 19).
Open the corner valve for a few seconds to rinse the pipe.
Re-close corner valve.
Handling
Mounting the drive unit
If the holding panel is not mounted on the Bowden cable unit, posi‐ tion the holding panel.
WC flush actuation 31 from 48
Page 32
Handling
Place the drive unit onto the holding panel.
Push the Bowden cable unit onto the drain valve from the left.
The Bowden cable unit must be felt to click into place on the drain valve.
Mounting the holder for control
Position holder with recess on the corner valve.
WC flush actuation 32 from 48
Page 33
Connecting the control
Handling
Push holder backwards until it clicks into place on the plug in the back wall.
Observation of the prescribed connection sequence is required. The power supply must always be connected last, to ensure that all of the connected components function.
INFO! Mounting is much easier if the plug is inserted into the control outside of the cistern.
Connect the red plug of the Bowden cable unit motor to the red connection of the control.
Connect the blue connection cable from the sensor to the blue con‐ nection of the control.
Also observe section Ä Chapter 3.2.5 „Connecting external sen‐ sors“ on page 37.
WC flush actuation 33 from 48
Page 34
Handling
Connect the black cable of the power supply to the outer right con‐ nection of the control.
INFO! Settings for the control can also already be made at this point. The programming set is easier to connect if the control is not yet installed in the cistern. Ä Chapter 3.3 „Com‐ missioning“ on page 39
Insert the control into the bracket in the cistern.
Connecting the water supply pipe
Fit the cable into the upper part of the cistern and fix with the cable ties supplied. The cable must not obstruct any moving parts in the cistern.
Connect the flexible hose onto the filling valve.
WC flush actuation 34 from 48
Page 35
Open corner valve.
Mounting the battery compartment (optional)
Place the battery compartment onto the control holder.
Handling
Mounting the mechanism
Vertical installation (flush plate on the front of the cistern)
If necessary, secure the battery compartment with a cable tie.
How to install the mechanism depends on whether the flush plate is to be fitted to the front or top of the cistern.
Hang the mechanism in the bow of the drain valve.
WC flush actuation 35 from 48
Page 36
Insert mechanism.
The mechanism must sit exactly in the recesses of the cistern.
Turn the mechanism's lock by 90° in a clockwise direction.
The mechanism is locked.
ð
Handling
Horizontal installation (flush plate on the top of the cistern)
Hang the mechanism in the bow of the drain valve.
WC flush actuation 36 from 48
Page 37
Handling
Insert mechanism.
In doing so, ensure that the tracks on the top and bottom edge of the mechanism are in the indentations in the revision shaft of the cistern.
Turn the mechanism's lock by 90° in a clockwise direction.
The mechanism is locked.
ð

3.2.5 Connecting external sensors

As the next step, fitting of the flush plate as per the instruc‐ tion manual supplied.
NOTICE! Damage to property due to excess voltage
If you apply voltage to the connection cable for the external button, you will damage the control.
– Do not apply any external voltage!
WC flush actuation 37 from 48
Page 38
Handling
Requirements:
n Button with locking function or potential-free contact (closure time at
least 350 ms) available
n Connection cable model 8355.90 available
Connect the contact to actuate the small flush volume between the green (1) and yellow cable (3).
Connect the contact to actuate the large flush volume between the green (1) and white cable (2).
Isolate the brown cable.
Connect the connection cable to the control.
WC flush actuation 38 from 48
Page 39

3.3 Commissioning

3.3.1 Setting the flush

Programming block
Handling
Programming the control can be carried out for 30 minutes after the supply voltage is applied. The control returns to normal operation after 30 minutes – programming is now blocked. If the settings have to be changed after this time, the control must be disconnected from the power supply for at least 10 seconds.
The programming set required to program the device is not included in the scope of delivery. It can be purchased sepa‐ rately as accessory. Ä „Optional accessories“ on page 15
Observe the following features during programming:
Only one value can be set per programming step.The settings are retained, even if there is an interruption
in the power supply.
– The programming process can be cancelled without a
change of the settings by holding the magnetic key in front of the programming contact until no acoustic signal has sounded for more than two seconds.
Setting the flush volume
Requirements:
n The revision shaft is open and the control can be accessed. n The control programming block is not active. n The programming set is available.
Remove the protective cap of the programming connection from the control.
WC flush actuation 39 from 48
Page 40
Connect the cable of the programming contact to the control.
Hold the magnetic key over the programming contact.
In the following, signals sound to show which setting is active.
ð
Handling
Remove magnetic key to enable setting.
The following values can be set by removing the magnetic key:
Remove magnetic key after Setting
1st acoustic signal Flush volume small 3 l and
large 4.5 l
2nd acoustic signal Flush volume small 3 l and
large 6 l (factory setting)
3rd acoustic signal Flush volume small 4 l and
large 9 l
A double acoustic signal is sounded as confirmation. The set‐
ð
ting has been changed successfully.
WC flush actuation 40 from 48
Page 41
Remove the cable of the programming contact.
Place a protective cap onto the contact.
Handling

3.3.2 Setting Hygiene+ function

The Hygiene+ function is deactivated when delivered. If you wish to use the Hygiene+ function, you must program the following settings.
The flush volume for the Hygiene+ function can only be selected if the Hygiene+ function has been activated by choosing a flushing interval.
If no flush volume is selected after activating the Hygiene + function, the flush volume is set automatically to the min‐ imum volume.
WC flush actuation 41 from 48
Page 42
Setting the flush interval
Handling
Requirements:
n The revision shaft is open and the control can be accessed. n The control programming block is not active Ä „ Programming
block “ on page 39.
n The programming set is available.
Remove the protective cap of the programming connection from the control.
Connect the cable from the programming contact onto the control.
WC flush actuation 42 from 48
Page 43
Hold the magnetic key in front of the programming contact.
In the following, signals sound to show which setting is active.
ð
Remove magnetic key to enable setting.
The following values can be set by removing the magnetic key:
Handling
Remove magnetic key after Setting
8th acoustic signal Hygiene+ flush volume 3 l (fac‐
tory setting, if Hygiene+ is active)
9th acoustic signal Hygiene+ flush volume 6 l
10th Acoustic signal Hygiene+ flush volume 9 l
A double acoustic signal is sounded as confirmation. The set‐
ð
ting has been successfully changed.
Remove the cable of the programming contact.
WC flush actuation 43 from 48
Page 44
Setting Hygiene+ flush volume
Handling
Place a protective cap onto the contact.
Requirements:
n The revision shaft is open and the control can be accessed. n The control programming block is not active Ä „ Programming
block “ on page 39.
n The programming set is available. n The Hygiene+ interval is set.
Remove the protective cap of the programming connection from the control.
WC flush actuation 44 from 48
Page 45
Handling
Connect the cable from the programming contact onto the control.
Hold the magnetic key in front of the programming contact.
In the following, signals sound to show which setting is active.
ð
Remove magnetic key to enable setting.
The following values can be set by removing the magnetic key:
Remove magnetic key after Setting
4th acoustic signal Hygiene flush function: OFF
(factory setting)
5th acoustic signal Hygiene flush performed
24 hours after the last flush
6th acoustic signal Hygiene flush 72 hours after
the last use
7th acoustic signal Hygiene flush 168 hours after
the last use
A double acoustic signal is sounded as confirmation. The set‐
ð
ting has been successfully changed.
WC flush actuation 45 from 48
Page 46
Remove the cable of the programming contact.
Place a protective cap onto the contact.
Handling
3.4
Error Cause Remedy
WC does not flush Power supply failure actuate manual flush
WC flush runs through Dirty seal in filling valve Check seal, replace if necessary
Faults, faults and remedy
Cistern is not yet completely full Wait until the cistern is sufficiently
No water in cistern, corner valve is closed
Control defect Replace control
Plug connection power pack / control not made
Plug connection drive unit / control not made
Dirty seal in drain valve Check seal, replace if necessary
Plug sequence drive unit / control incorrect
full
Open corner valve
Create plug connection Ä „Con‐
necting the control“ on page 26
Create plug connection Ä „Con‐
necting the control“ on page 26
Check plug connection, observe coloured marking Ä „Connecting
the control“ on page 26
manual actuation is not working The mechanism is not connected
to the bow
WC flush actuation 46 from 48
Hang the mechanism in the bow
Page 47

3.5 Care and maintenance

3.5.1 Maintenance tips

The flush actuation requires no care.

3.5.2 Replacing the battery

Cistern 2L
Handling
When maintaining the flush plate, heed the instructions of the flush plate manual.
Only for use of a battery compartment for redundant power supply.
Requirements:
n The flush plate has been removed. n The mechanism has been removed (compare Ä Chapter 3.2.2 „Pre‐
paring the installation“ on page 20).
n Free access to the cistern can be gained through the revision shaft.
Remove the battery compartment from the cistern.
Open battery compartment and remove flat battery.
WC flush actuation 47 from 48
Page 48
Insert new battery and close battery compartment.
Place the battery compartment onto the control holder.
If necessary, secure the battery compartment with a cable tie.
Handling
3.6
Replace and lock mechanism.
Mount flush plate according to manual.
Disposal
Separate the product and packaging materials (e. g. paper, metal, plastic or non-ferrous metals) and dispose of in accordance with valid national legal requirements.
WC flush actuation 48 from 48
Loading...