Citaplex drain/overflow 2 from 15

Table of contents
1 About these instructions for use 4
1.1
Target groups 4
1.2
Labelling of notes 4
1.3
About this translated version 5
2 Product information 6
2.1
Intended use 6
2.1.1
Areas of use 6
2.2
Product description 7
2.2.1
Overview 7
2.2.2
Technical data 8
3 Handling 9
3.1
Assembly information 9
3.1.1
Mounting conditions 9
3.1.2
Installation dimensions 9
3.1.3
Required tools and materials 9
3.2
Assembly 10
3.2.1
Mounting overflow 10
3.2.2
Mounting the drain 11
3.2.3
Connecting overflow and drain 11
3.2.4
Connecting the wastewater system 12
3.2.5
Mounting equipment set 13
3.2.6
Leakage test 14
3.3
Maintenance 14
3.4
Disposal 15
Table of contents
Citaplex drain/overflow 3 from 15

1 About these instructions for use
Trade mark rights exist for this document, further information can be
found at
viega.com/legal
.
1.1 Target groups
The information in this instruction manual is directed at the following
groups of people:
n Heating and sanitary professionals and trained personnel
n Operators
n Consumers
It is not permitted for individuals without the abovementioned training or
qualification to mount, install and, if required, service this product. This
restriction does not extend to possible operating instructions.
The installation of Viega products must take place in accordance with
the general rules of engineering and the Viega instructions for use.
1.2 Labelling of notes
Warning and advisory texts are set aside from the remainder of the text
and are labelled with the relevant pictographs.
DANGER!
This symbol warns against possible life-threatening injury.
WARNING!
This symbol warns against possible serious injury.
CAUTION!
This symbol warns against possible injury.
NOTICE!
This symbol warns against possible damage to property.
Notes give you additional helpful tips.
About these instructions for use
Citaplex drain/overflow 4 from 15

1.3 About this translated version
This instruction for use contains important information about the choice
of product or system, assembly and commissioning as well as intended
use and, if required, maintenance measures. The information about the
products, their properties and application technology are based on the
current standards in Europe (e. g. EN) and/or in Germany
(e. g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/
Germany. These should serve as recommendations in the absence of
corresponding national regulations. The pertinent national laws, standards, regulations and guidelines, as well as other technical guidelines,
have priority over German/European guidelines in this manual: The
information is not binding for other countries and territories and should,
as mentioned, be considered as support.
About these instructions for use
Citaplex drain/overflow 5 from 15

2 Product information
2.1 Intended use
2.1.1 Areas of use
NOTICE!
Risk of damage due to unsuitable liquids.
To avoid damaging the drain, only introduce the following
liquids:
– Liquids with a pH-value higher than 4
– typical household wastewater with temperatures up to
95 °C
The Citaplex drain/overflow is a combined drain and overflow for bathtubs with a 52 mm drain hole.
Please note, this model has no odour trap. A separate
odour trap must be installed to complete the mounting.
The drain/overflow is suitable for standard bathtubs with the drain on
the head end.
Detailed information regarding all bathtub models and the corresponding Viega drains / overflows can be found in the catalogue or on
the Internet.
Product information
Citaplex drain/overflow 6 from 15

2.2 Product description
2.2.1 Overview
1
2
3
4
6 5789
11 12 13 14 15 16
10
Fig. 1: Component overview
1 - valve plug with fixing chain
2 - fixing screw
3 - valve top
4 - double seal
5 - drain unit
6 - seal
7 - sliding ring
8 - union nut
9 - overflow pipe
10 - sleeve
11 - overflow unit
12 - profile seal
13 - fixing flange
14 - rosette
15 - fixing screw
16 - chain
Product information
Citaplex drain/overflow 7 from 15

2.2.2 Technical data
Drainage capacity (at an accumulation height of 300 mm)
The drainage capacity depends
on the odour trap used.
Overflow capacity (at an accumulation height of 60 mm)
The overflow capacity depends on
the odour trap used.
Diameter of bathtub drain hole 52 mm
Threaded drain unit 1½ inch
Length 120–260 mm
Height 180–440 mm
Dimensions and installation depth
Ä Chapter 3.1.2 „Installation
dimensions“ on page 9
Product information
Citaplex drain/overflow 8 from 15

3 Handling
3.1 Assembly information
3.1.1 Mounting conditions
The following requirements exist for the mounting of the drain / overflow:
n The bathtub is installed.
n The drainage line is installed all the way to the bathtub.
n The underside of the bathtub is accessible.
3.1.2 Installation dimensions
Ø70
1½˝
120 - 240
70 180 - 400
Fig. 2: Dimensional drawing
3.1.3 Required tools and materials
The following tools are required for mounting:
n fine-toothed saw
n flat-blade screwdriver
Tool
Handling
Citaplex drain/overflow 9 from 15

The following material must be purchased separately and must be available during mounting:
n odour trap
3.2 Assembly
3.2.1 Mounting overflow
Proceed as follows to the mounting of the overflow:
Push the rubber sleeve onto the pipe of the overflow unit.
The lower edge must be flush with the edge of the overflow pipe.
Fit profile seal in the overflow unit.
Hold the overflow unit on the overflow opening of the bathtub from
the outside.
Screw the fixing flange into the overflow unit by hand.
Pliers or other tools may damage the fixing flange. Only turn the
fixing flange by hand.
Material
Handling
Citaplex drain/overflow 10 from 15

3.2.2 Mounting the drain
Proceed as follows to mount the drain:
Place the profile seal in the recess of the drain unit.
Mount the drain unit with profile seal on the drain opening of the
bathtub from below.
Fit the valve top in the drain opening.
Place the fixing screw in the drain unit and tighten using a flat-blade
screwdriver.
3.2.3 Connecting overflow and drain
After the overflow and the drain have been mounted, you must connect
them both using the overflow pipe. Proceed as follows:
Requirements:
n The overflow is mounted in the overflow opening.
n The drain is securely mounted on the base of the bathtub.
NOTICE! Connections where the pipes are not inserted far
enough into each other become leaky. For this reason, maintain
a minimum insertion depth of 15 mm for every connection.
Handling
Citaplex drain/overflow 11 from 15

Hold the pipe of the overflow unit parallel to the overflow pipe and
mark the positions where the drain and the overflow should be connected.
Maintain an insertion depth of at least 15 mm!
Cut the overflow pipe to the marked length and, if necessary,
deburr.
Push the top end of the overflow pipe into the rubber sleeve.
Maintain an insertion depth of at least 15 mm!
Push the union nut, sliding ring and seal onto the bottom end of the
drain elbow.
Screw the union nut on the drain unit.
3.2.4 Connecting the wastewater system
The drain unit must be connected to an external odour trap as there is
no odour trap integrated into the drain fitting. The drain unit is equipped
with a vertical 1½ inch threaded connection for the connection.
Proceed as follows to connect the drain fitting to the wastewater
system:
Requirements:
n The overflow and drain units are installed on the bathtub.
n The connection between overflow and drain has been made.
Screw the drain unit together with the on-site odour trap at the
threaded connection.
Handling
Citaplex drain/overflow 12 from 15

3.2.5 Mounting equipment set
Proceed as follows to mount the equipment set:
Gently bend open the bow of the valve plug.
Thread the eyelet of the chain onto the bow.
Bend the bow of the valve plug back together.
Hang the free eyelet of the chain onto the bottom hook of the fixing
flange.
Place the valve plug into the drain valve.
The chain should hang loosely between fixing flange and drain.
Place the rosette onto the fixing flange of the overflow and tighten
hand-tight with the screw supplied.
Handling
Citaplex drain/overflow 13 from 15

The valve plug can be inserted into the rosette for safe-keeping.
3.2.6 Leakage test
The leakage test is only carried out as a visual inspection.
Check drain/overflow fitting for visible leaks.
3.3 Maintenance
NOTICE!
Risk of damage due to unsuitable cleaning agent.
The following cleaning agents can damage chrome-plated
surfaces and therefore may not be used:
– scouring agent
– abrasive sponges
– lime, plaster or cement dissolver
– solvents or other acidic cleaning agents
Normal soap or a mild cleaning agent can be used for regular care and
prevention of lime scale on the rotatable rosette and valve cone. Under
no circumstances should scouring agent or scratching objects be used.
Strong stains, even around the drain unit and the siphon, can be
removed using typical household cleaner. It should be noted that the
cleaning agent should be rinsed off after the prescribed soaking time.
There should be no residue on the components.
Handling
Citaplex drain/overflow 14 from 15

3.4 Disposal
Separate the product and packaging materials (e. g. paper, metal,
plastic or non-ferrous metals) and dispose of in accordance with valid
national legal requirements.
Handling
Citaplex drain/overflow 15 from 15