Viega 4989 Instructions For Use Manual

Page 1
Optifix 3 cellar drain Type 5
Instructions for Use
3-way backflow protection (two automatic and one manual emergency shut-off)
Model
4989
en_INT
Page 2
Optifix 3 cellar drain Type 5 2 from 17
Page 3
1 About these instructions for use 4
Table of contents
1.1
1.2
1.3
Target groups 4
Labelling of notes 4
About this translated version 5
2 Product information 6
2.1
2.2
2.2.1
2.2.2
2.2.3
2.3
2.3.1
2.3.2
2.3.3
Standards and regulations 6
Intended use 6
Areas of use 6
Place of installation and installation conditions 7
Maintenance 7
Product description 8
Overview 8
Technical data 8
Operating mode 8
3 Handling 10
3.1
3.1.1
3.2
3.3
3.4
3.5
Assembly information 10
Installation dimensions 10
Assembly 11
Inspection 12
Maintenance 13
Disposal 17
Optifix 3 cellar drain Type 5 3 from 17
Page 4
About these instructions for use

1 About these instructions for use

Trade mark rights exist for this document; for further information, go to viega.com/legal.

1.1 Target groups

The information in this instruction manual is directed at the following groups of people:
n Heating and sanitary professionals and trained personnel
Individuals without the abovementioned training or qualification are not permitted to mount, install and, if required, maintain this product. This restriction does not extend to possible operating instructions.
1.2
The installation of Viega products must take place in accordance with the general rules of engineering and the Viega instructions for use.
Labelling of notes
Warning and advisory texts are set aside from the remainder of the text and are labelled with the relevant pictographs.
DANGER! This symbol warns of possible life-threatening injury.
WARNING! This symbol warns of possible serious injury.
CAUTION! This symbol warns of possible injury.
NOTICE! This symbol warns of possible damage to property.
This symbol gives additional information and hints.
Optifix 3 cellar drain Type 5 4 from 17
Page 5

1.3 About this translated version

This instruction for use contains important information about the choice of product or system, assembly and commissioning as well as intended use and, if required, maintenance measures. The information about the products, their properties and application technology are based on the current standards in Europe (e.g. EN) and/or in Germany (e.g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/ Germany. These should serve as recommendations in the absence of corresponding national regulations. The relevant national laws, stand‐ ards, regulations, directives and other technical provisions take priority over the German/European directives specified in this manual: The information herein is not binding for other countries and regions; as said above, they should be understood as a recommendation.
About these instructions for use
Optifix 3 cellar drain Type 5 5 from 17
Page 6

2 Product information

2.1 Standards and regulations

The following standards and regulations apply to Germany / Europe and are provided as a support feature.
Regulations from section: Place of installation and installation condi‐ tions
Scope / Notice Regulations applicable in Ger‐
Product information
many

2.2 Intended use

2.2.1 Areas of use

Correct place of installation of the backflow trap
Securing of drainage points beneath the backflow level
Securing of drainage points beneath the backflow level
Requirements in backflow traps type 3
The backflow trap is suitable for faecal matter free, typical household wastewater up to a temperature of 95 °C with pH values ≥ 4 or ≤ 10.
Use in industrial areas or in pipelines, which transport aggressive liquids is not permitted. This includes cleaning agents, which can damage sani‐ tary equipment, drainage equipment and pipe materials.
EN 12056
DIN EN 12056-4
DIN 1986-100
EN 13564
Viega recommends closing the emergency trap if operation, where no wastewater is produced, is interrupted for a number of days.
Optifix 3 cellar drain Type 5 6 from 17
Page 7

2.2.2 Place of installation and installation conditions

1
2
3
4
5
Product information
1 Street / backflow level 2 Area safe from backflow 3 Backflow level 4 Area at risk of backflow 5 Backflow trap
The connection of the upper floor to the underground pipe must be made between the backflow trap and sewer within the building – only then is it possible to ensure that the wastewater system can function faultlessly. To ensure that drainage is guaranteed, backflow traps may not be employed as the central safeguard for a building with drainage equipment installed above the backflow level – in the event of backflow, it would lead to flooding in the building due to wastewater being unable to drain away.
See Ä „Regulations from section: Place of installation and installation
conditions“ on page 6
2.2.3
Maintenance
Maintenance must be carried out twice a year to ensure safe operation. See Ä Chapter 3.4 „Maintenance“ on page 13
Optifix 3 cellar drain Type 5 7 from 17
Page 8

2.3 Product description

2.3.1 Overview

Product information
1 Grate 2 Odour trap 3 Backflow unit 4 Shutter valves 5 Top, rotatable and height-adjustable 6 Base unit 7 Plug for side inlet 8 Odour trap for side inlet 9 Test device

2.3.2 Technical data

Load class K = 300 kg
Drainage capacity 1.8 l/s at 20 mm accumulation

2.3.3 Operating mode

height
The shutter valves of the backflow trap are closed; they open automati‐ cally when the water drains off.
Optifix 3 cellar drain Type 5 8 from 17
Page 9
Product information
In addition, the backflow trap can be closed manually using a manual actuator.
Optifix 3 cellar drain Type 5 9 from 17
Page 10

3 Handling












3.1 Assembly information

3.1.1 Installation dimensions

Handling
Fig. 1: Installation dimensions
Optifix 3 cellar drain Type 5 10 from 17
Page 11

3.2 Assembly

Handling
Requirements:
n The installation in the drainage pipeline may only be carried out by
construction or specialised plumbing companies observing the building regulations and following these instructions.
Position the drain on the floor and fasten to the reinforcement.
Connect the drain to the wastewater pipe in the direction of flow.
Pull out the top and make level with the floor.
If necessary, insert a height adjustment piece (model 4992).
Optifix 3 cellar drain Type 5 11 from 17
Page 12

3.3 Inspection



Handling
Lay the floor covering.
Remove the site protection.
To ensure safe operation, a monthly inspection must be carried out by a professional, see .
Remove the grate.
Open the manual lock and in doing so check the mobility.
Close the manual lock.
Insert the grate.
Optifix 3 cellar drain Type 5 12 from 17
Page 13

3.4 Maintenance

Handling
NOTICE! To ensure safe operation, carry out maintenance of the system twice a year.
Requirements:
n Maintenance must be carried out by a professional. n Only use original parts for repairs, maintenance and extensions. n Replace defective components, do not repair. n When using cameras and cleaning devices (cleaning spiral, high-
pressure cleaner), protect the backflow trap against mechanical damage.
n Only begin maintenance work when is certain that there is no back
flow situation and the drainage fittings upstream from the Backflow trap are not being used.
Optifix 3 cellar drain Type 5 13 from 17
Page 14
Remove the grate.


Open the manual lock.
Remove the odour trap.
Handling
Remove the odour trap for the side inlet.
Move the fastening lever.
Optifix 3 cellar drain Type 5 14 from 17
Page 15
Remove the backflow unit at the fastening lever.
Clean the casing.
Handling
Clean the backflow unit.
Insert the backflow unit.
Optifix 3 cellar drain Type 5 15 from 17
Page 16
Move the fastening lever.
1.
2.


Unscrew the screw plug.
Screw the test device in.
Handling
Fill the test device with water up to the top marking.
If you need to refill more than 0.5 l in 10 minutes, check the lock again and replace the seals if necessary.
Unscrew the test device.
Screw the screw plug in.
Optifix 3 cellar drain Type 5 16 from 17
Page 17
Insert the odour trap.


Insert the odour trap for the side inlet.
Handling
Close the manual lock.
Insert the grate.
3.5
Disposal
Separate the product and packaging materials (e. g. paper, metal, plastic or non-ferrous metals) and dispose of in accordance with valid national legal requirements.
Optifix 3 cellar drain Type 5 17 from 17
Loading...