Viega 4987.41 Instructions For Use Manual

Page 1
for wastewater pipe containing faeces Model Year built:
4987.41 from 01/2010
en_INT
Grundfix Plus Control backflow trap type 3
Instructions for Use
Page 2
Page 3
Table of contents
1 About these instructions for use 5
1.1
Target groups 5
1.2
Labelling of notes 5
1.3
About this translated version 6
2 Product information 7
2.1
Standards and regulations 7
2.2
Safety advice 8
2.3
Intended use 8
2.3.1
Areas of use 8
2.3.2
Place of installation and installation conditions 9
2.3.3
Maintenance 11
2.4
Product description 11
2.4.1
Overview 11
2.4.2
Technical data 12
2.4.3
Operating mode 13
2.4.4
Control elements 13
3 Handling 15
3.1
Assembly information 15
3.1.1
Installation dimensions 15
3.2
Assembly 16
3.2.1
Mount base unit 16
3.2.2
Connecting connection cable and pressure hose 17
3.2.3
Connecting the control 18
3.3
Commissioning 21
3.3.1
Commissioning the control 21
3.3.2
Pressure test 22
3.4
Control 25
3.4.1
Operating conditions 25
3.4.2
Operating condition - normal operation 26
3.4.3
Operating condition – back pressure 29
3.4.4
Operating condition – malfunction 29
3.4.5
Operating condition – battery-powered emergency operation 30
3.5
Errors, faults and remedy 31
3.6
Care and maintenance 33
3.6.1
Inspection 33
Table of contents
Page 4
3.6.2
Maintenance 34
3.6.3
Replacing the rechargeable battery 40
3.7
Disposal 41
Table of contents
Page 5
1 About these instructions for use
Trade mark rights exist for this document; for further information, go to
viega.com/legal
.
1.1 Target groups
The information in this instruction manual is directed at the following groups of people:
n Heating and sanitary professionals and trained personnel n Qualified electricians n Operators
Individuals without the abovementioned training or qualification are not permitted to mount, install and, if required, maintain this product. This restriction does not extend to possible operating instructions.
The installation of Viega products must take place in accordance with the general rules of engineering and the Viega instructions for use.
1.2 Labelling of notes
Warning and advisory texts are set aside from the remainder of the text and are labelled with the relevant pictographs.
DANGER! This symbol warns of possible life-threatening injury.
WARNING! This symbol warns of possible serious injury.
CAUTION! This symbol warns of possible injury.
NOTICE! This symbol warns of possible damage to property.
This symbol gives additional information and hints.
About these instructions for use
Page 6
1.3 About this translated version
This instruction for use contains important information about the choice of product or system, assembly and commissioning as well as intended use and, if required, maintenance measures. The information about the products, their properties and application technology are based on the current standards in Europe (e. g. EN) and/or in Germany (e. g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/ Germany. These should serve as recommendations in the absence of corresponding national regulations. The relevant national laws, stand­ards, regulations, directives and other technical provisions take priority over the German/European directives specified in this manual: The information herein is not binding for other countries and regions; as said above, they should be understood as a recommendation.
About these instructions for use
Page 7
2 Product information
2.1 Standards and regulations
The following standards and regulations apply to Germany / Europe. National regulations can be found on the relevant web site of your country at
viega.com/standards
.
Regulations from section: Place of installation and installation condi­tions
Scope / Notice Regulations applicable in Ger-
many
Correct place of installation of the backflow trap
EN 12056
Regulations from section: Fields of application
Scope / Notice Regulations applicable in Ger-
many
Grundfix Plus Control meets the requirements as type 3 backflow trap with double backflow protec­tion
EN 13564
Regulations from section: Disposal
Scope / Notice Regulations applicable in Ger-
many
Disposal of electronic compo­nents
WEEE-Richtlinie 2012/19/EU
Regulations from section: Inspection
Scope / Notice Regulations applicable in Ger-
many
Monthly inspection DIN 1986-3
Product information
Page 8
2.2 Safety advice
DANGER! Danger due to electrical current
An electric shock can lead to burns and serious injury and even death.
– Work on the electrics may only be carried out by trained
electricians.
– Remove the mains plug before opening the casing.
2.3 Intended use
2.3.1 Areas of use
The Grundfix Plus Control is operated electrically. It is suitable for use in drain pipelines with household-type wastewater carrying faecal matter (up to a temperature of 95 °C with pH values of ≥ 4 or ≤ 10).
The backflow trap is suitable for use in drain pipelines made of HT or sewer pipe DN 100, 125 or 150. When using other pipes such as e. g. clay pipes or cast-iron pipes, the relevant adapters for HT and sewer pipes must be used.
Use in industrial areas or in pipelines, which transport aggressive liquids is not permitted. This includes cleaning agents, which can damage sani­tary equipment, drainage equipment and pipe materials.
Viega recommends closing the emergency trap if operation, where no wastewater is produced, is interrupted for a number of days.
Product information
Page 9
2.3.2 Place of installation and installation conditions
1
5
4
2
3
Fig. 1: Wrong place of installation of the backflow trap
Product information
Page 10
1
5
4
2
3
Fig. 2: Correct place of installation of the backflow trap
1 - Street = Backflow level 2 - Area safe from backflow 3 - Connection upper floor 4 - Area at risk of backflow 5 - Protection against backflow through backflow trap
The connection of the upper floor (3) onto the underground pipe must be made between the backflow trap and sewer within the building (5) – only then is it possible to ensure that the wastewater system can func­tion faultlessly. To ensure that drainage is permanently guaranteed, backflow traps may not be employed as the central safeguard for a building with drainage equipment installed above the backflow level (1) – in the event of backflow, it would lead to flooding in the building due to wastewater being unable to drain away (4).
See
Ä „Regulations from section: Place of installation and installation
conditions“ on page 7
Backflow seals and their control units should be installed in such a way that they are always accessible.
Product information
Grundfix Plus Control backflow trap type 3 10 from 41
Page 11
The backflow sensor reacts at accumulation heights of 100 mm, measured from the upper edge of the base pipe­line.
Therefore, when planning, the installation heights of the existing floor drains, out of which water could flow in the case of backflow, must be taken into account.
If a backflow trap is retro-fitted in a base pipeline, the height difference of 30 mm between connection pipe and sleeve must be taken into account.
2.3.3 Maintenance
A monthly inspection must be carried out to ensure safe operation. See
Ä Chapter 3.6.1 „Inspection“ on page 33
Maintenance must be carried out twice a year to ensure safe operation. See
Ä Chapter 3.6.2 „Maintenance“ on page 34
2.4 Product description
2.4.1 Overview
1 2 3 4 5 6
7 8
910
Fig. 3: Components backflow trap
1 - measuring funnel 2 - pressure hose 3 - connection cable control 4 - motor 5 - pressure switch 6 - emergency lock actuation 7 - lid 8 - casing 9 - emergency lock shutter 10 - motor-powered flap
Product information
Grundfix Plus Control backflow trap type 3 11 from 41
Page 12
1
6
7
8
9
10
5
2
3
4
Fig. 4: Components control unit
1 - display 2 - pressure hose 3 - connection cable 4 - outlet for potential-free contacts 5 - power pack 6 - casing 7 - mains supply voltage 230 V 8 - terminal strip 15 V 9 - battery fuse 10 - motor fuse
2.4.2 Technical data
Switching power pack 88–264 VAC
50/60 Hz
LCD 20 x 2 with lighting
RTC real time clock power reserve 30 days
rechargeable battery 12 V
1.2 Ah integrated charge and test elec-
tronics for battery operation for up to 24 hours in the case of power failure
Event memory 512 events
Potential-free relay-outlets Back flow and fault
Casing Plastic casing 201 x 151 x 80 mm
without hinges and PG screw fit­ting
Protection class in acc. with VDE 0100
Control casing IP54; Grundfix Plus Control IP67
Battery fuse 4 A – slow
Product information
Grundfix Plus Control backflow trap type 3 12 from 41
Page 13
Motor fuse 4 A – slow
Closing time in case of back flow In mains or battery operation
approx. 10 seconds
2.4.3 Operating mode
The motor-powered flap is open during normal operation. If the pres­sure switch registers the backflow of water, the motor-powered flap is closed, the following display appears
„Back pressure“
and a signal sounds every 10 seconds. The use of the drainage equipment is not possible during this time. A battery emergency power supply ensures the functionality of the system even when the 230 V mains power supply fails.
Using the manual actuator, the backflow trap can be closed manually and independently of the motor-powered flap.
2.4.4 Control elements
1
Fig. 5: Control elements backflow trap
1 - Emergency shut-off
Product information
Grundfix Plus Control backflow trap type 3 13 from 41
Page 14
1
2
3
Fig. 6: Control elements control unit
1 - Menu T1 2 - Test T2 3 - Reset T3
Product information
Grundfix Plus Control backflow trap type 3 14 from 41
Page 15
3 Handling
3.1 Assembly information
3.1.1 Installation dimensions
Fig. 7: Installation dimensions
D H1 H2 H3 L1 L2 L3
110 260 100 65 405 215 545
125 260 105 75 405 215 550
160 295 125 95 470 245 640
The backflow sensor reacts at accumulation heights of 100 mm, measured from the upper edge of the base pipe­line.
Therefore, when planning, the installation heights of the existing floor drains, out of which water could flow in the case of backflow, must be taken into account.
If a backflow trap is retro-fitted in a base pipeline, the height difference of 30 mm between connection pipe and sleeve must be taken into account.
Handling
Grundfix Plus Control backflow trap type 3 15 from 41
Page 16
3.2 Assembly
3.2.1 Mount base unit
The installation in the drainage pipeline may only be carried out by con­struction or specialised sanitary companies observing the building regu­lations and following this instruction for use.
Install the base unit horizontally into the base pipeline. Observe flow direction!
At maximum, line up to the middle of the drainpipe. Close emergency shut-off (position "OFF). In this way, damage from flooding can be avoided before commis-
sioning.
Lay empty pipe from the base unit to the mounting position of the control unit.
Close the empty pipe at both side using plugs.
Handling
Grundfix Plus Control backflow trap type 3 16 from 41
Page 17
3.2.2 Connecting connection cable and pressure hose
Do not loosen factory-fitted threaded cable and hose screw fittings on the casing. Otherwise, the anti-flooding function cannot be ensured.
Loosen union nut and push onto the pressure hose. Tighten the union nut of the pressure hose slightly using tools. Remove black closing cap.
Remove closing cap.
Plug in electric plug connection straight. Tighten union nut by hand.
INFO! The union nut must not be tightened using pliers.
Connecting the pressure hose
Connecting connection cable
Handling
Grundfix Plus Control backflow trap type 3 17 from 41
Page 18
Lead the connection cable and pressure hose through the empty pipe to the control. If necessary, use cable grip device.
3.2.3 Connecting the control
DANGER! Danger due to electrical current
An electric shock can lead to burns and serious injury and even death.
– Only allow electrical work to be carried out by specialist
companies.
– Remove mains plug before opening the casing.
Attach the control unit onto the wall with 4 screws.
Connect the pressure hose to the control using the quick connec­tion.
Lead the connection cable via the PG screw fitting into the internal space of the control.
Handling
Grundfix Plus Control backflow trap type 3 18 from 41
Page 19
Connect clamping strip.
Clamping strip configuration
Pos. cable Functions Marking on
the connection strip
1 black – fac-
tory-fitted
15 V mains connection
GND
2 red – factory-
fitted
15 V mains connection
+ 15V
3 black – fac-
tory-fitted
rechargeable battery con­nection
GND
4 red – factory-
fitted
rechargeable battery con­nection
+ AKKU
5 green motor connec-
tion
motor -
6 yellow motor connec-
tion
motor +
7
signalises back flow
RÜCK (BACK)
8
signalises back flow
RÜCK (BACK)
9
signalises fault STÖR (FAULT)
10
signalises fault STÖR (FAULT)
11 brown pressure
switch
sensor
12 white pressure
switch
sensor
Handling
Grundfix Plus Control backflow trap type 3 19 from 41
Page 20
Clamping strip configuration 20 m cable
Pos. cable Functions Marking on
the connection strip
5 conductor 3 motor connec-
tion
motor -
6 conductor 4 motor connec-
tion
motor +
11 conductor 2 pressure
switch
sensor
12 conductor 1 pressure
switch
sensor
Insert battery fuse (right).
INFO! The battery fuse is attached to the inside of the casing with adhesive tape.
NOTICE! Depending on the length of the connection cable, a jumper may be required to make a connection onto the control. An incorrect jumper position can lead to malfunctions. Back flow protection is no longer ensured.
When using the cable set (20 m, art.-no. 483 500), place jumpers onto both contacts (see illustration).
Handling
Grundfix Plus Control backflow trap type 3 20 from 41
Page 21
When using cables under 8 m in length, only attach jumper to one contact (see graphic, factory condition).
The control unit is provided with two potential-free outlets, through which acoustic and optical alarm devices can be connected.
Both contacts function as N.O. The alarm contact (clamping strip con­nection 7/8) at "Rück (Back)" is closed in the event of back flow. The fault indicating contacts (clamping strip connection 9/10) at "Stör (Fault)" closes when an operating fault is reported.
Observe the following when connecting on-site alarm devices:
n When allocating the contacts, ensure that a maximum current of
500 mA / 24 V is not exceeded.
n Allocation of the outlets must only take place using safety low
voltage and galvanic separation of the network.
n Only connect purely ohmic loads. n The use of a safety transformer in accordance with VDE 0551 or
DIN EN 60742 is permitted.
3.3 Commissioning
3.3.1 Commissioning the control
As soon as the mains voltage is connected, the control begins the auto­mated commissioning process.
Display:
„Commissioning“
There is a self-test of the rechargeable battery, mains connection and motor control components. The motor-powered flap is opened and closed once.
After a successful self-test, the control switches to normal operation ­the motor-powered flap is opened.
Display:
„Normal operation / NRV opened“
Faults detected during the self-test are shown on the screen.
Ä Chapter
3.5 „Errors, faults and remedy“ on page 31
Alarm and fault indicating contacts (optional)
Handling
Grundfix Plus Control backflow trap type 3 21 from 41
Page 22
Date and time must be set after the initial commissioning, as a prerequisite that the maintenance reminder, error log­ging and daily self-test can function.Ä Chapter 3.4.2 „Oper­ating condition - normal operation“ on page 26
3.3.2 Pressure test
After commissioning of the control, the function of the pressure switch must be tested using the pressure test.
Place the emergency lock to "ZU (OFF)" position.
Close the motor-powered flap by pressing the button T2.
ð
Display:
„Test NRV closed“
Screw the brass plug out of the lid.
Handling
Grundfix Plus Control backflow trap type 3 22 from 41
Page 23
Screw in test funnel.
Fill water to the top marking of the test funnel.
ð
When the pressure switch is intact, the control will report a back flow:
Display:
„Test NRV closed“, „Back pressure NRV closed“
If necessary, a positive opening is possible. Press the button T3 for 5 seconds.
Keep the water level in the test funnel constant for 10 minutes by replenishing. Observe loss.
ð
If the loss is greater than 0.5 l, check and, if required, replace the seals on the flaps.
Place the emergency lock to "AUF (ON)" position.
ð
The water drains away. Display:
„Test NRV closed“
Handling
Grundfix Plus Control backflow trap type 3 23 from 41
Page 24
Open the motor-powered flap by pressing button T2.
Remove test funnel.
Screw in brass plug.
ð
The control automatically changes back to normal operation after a successful procedure.
Display:
„Normal operation / NRV opened“
Handling
Grundfix Plus Control backflow trap type 3 24 from 41
Page 25
3.4 Control
3.4.1 Operating conditions
On the front of the control unit the LC display and T1, T2 and T3 buttons are located. The button functions depend on the current operating con­dition.
The current operating condition is shown on the display as follows:
Operating conditions
Display Operating condition Warning signals Operation in accordance with
chapter
„Normal operation“ „NRV opened“
Motor-powered flap open, main supply 230 V
Backflow protection is assured
Operating condition - normal
operation
Ä Chapter 3.4.2 „Operating condition - normal opera­tion“ on page 26
„Back pressure“ „NRV closed“
Motor-powered flap closed
Backflow protection is assured
Warning signal every 10 seconds
Operating condition – back pressure
Ä Chapter 3.4.3 „Operating condition – back pressure“ on page 29
„Back pressure“ „Close emergency
lock“
Suggestion to close emergency lock
Risk of flooding!
Continuous signal Operating condition – back
pressure
Ä Chapter 3.4.3 „Operating condition – back pressure“ on page 29
Fig. 8: Control elements control unit
Handling
Grundfix Plus Control backflow trap type 3 25 from 41
Page 26
Display Operating condition Warning signals Operation in accordance with
chapter
„Error motor fault“ „NRV opened“
Pressure switch detects backflow, the motor-powered flap cannot be closed, it is blocked or the motor is defective
Risk of flooding!
Continuous signal Operating condition – malfunc-
tion
Ä Chapter 3.4.4 „Operating condition – malfunction“ on page 29
„Battery operation“ „NRV opened“
Mains voltage 230 V fails
Rechargeable battery has taken over the power supply
Backflow protection is assured four the next 24 hours
Warning signal every 10 seconds
Operating condition – battery­powered emergency operation
Ä Chapter 3.4.5 „Operating condition – battery-powered emergency operation“ on page 30
3.4.2 Operating condition - normal operation
In normal operation, control parameters can be entered and information can be called up with the T1, T2 and T3 buttons. The button functions are combined as follows:
Button
Function
T1 – Menu Scroll through menus with
repeated pressing / Display ascending values in the sub-menu
T2 – Test Display descending values in the
sub-menu
T3 – Reset first press = enter menu
second press = exit menu and save selected value
The available menus to set the control parameters are displayed by pressing the menu T1 button repeated on the display.
With the T3 button, you can access a menu and save and exit the menu after selected a suitable value.
Within the menus, you can scroll up and down through the values with the T1 and T2 buttons.
Button functions in normal operation
Handling
Grundfix Plus Control backflow trap type 3 26 from 41
Page 27
Press T1 Display Press T3 Press T1 Press T2 Press T3 Result
„Normal
operation “
„NRV
opened“
1x
„Maintenanc
e“
Option
Motor-pow­ered flap open/close
Return to normal oper­ation after maintenance
Maintenance successfully completed
2x
„Self-test
On / Off“
On / Off On / Off Save and
return to normal oper­ation
Self-test active/inac­tive
3x
„Time self-
test adjust“
up down Call up one
after another: Hours/
Minutes
Clock set
4x
„Date / time
adjust“
up down Call up one
after another: Date/ Time
Current date/ time (for log display and self-test)
Note: The adjustment from daylight saving time is carried out manually.
5x
„Event
memory“
Back to event memory
Call up events one after another
Log display
6x
„Software
vers.“
Back to soft­ware version
Display of current soft­ware version
7x
„Operating
hours“
Back to oper­ating hours
Display oper­ating hours
8x
„Language
adjust“
Select lan­guages
forward
Select lan­guages
backward
Save and return to select lan­guage
Display in selected lan­guage
9x
„Normal
operation “
„NRV
opened“
Menu display starts at the beginning
Menu order in normal operation
Handling
Grundfix Plus Control backflow trap type 3 27 from 41
Page 28
Press T1 Display Press T3 Press T1 Press T2 Press T3 Result
„Normal
operation “
„NRV
opened“
Press once Test backflow
trap closes
Test NRV closed
Press once Test backflow
trap opens
Normal oper­ation NRV opened
„Normal
operation “
„NRV
opened“
Press once Commis-
sioning Backflow trap
closes / Backflow trap opens
Normal oper­ation NRV opened
Example The unit is in normal operation and the self-test should be switched on
Press T1 button until the following appears on the display:
„Self-test
on / off“
Press T3 button – Display:
„Off“
Press T2 button – Display:
„On“
Press T3 button.
ð
The setting
„On“
is saved.
The menu is exited. Display:
„Normal operation“
The self-test is switched onand takes place at the predefined time.
Acoustic signals in case of backflow or error are switched off by pressing T1 button once and confirmed with button T3.
During normal operation, the motor-powered flap can be opened and closed by pressing the T2 button.
If no entry is made for more than one minute after pressing T1 button, the display switches to
„Normal operation“
.
The
„Event memory“
menu enables the display of 512 control unit-rele­vant events with date and time. When the memory is full, the oldest event is overwritten. The following events are displayed:
Special functions in normal operation
Reading of the event memory
Handling
Grundfix Plus Control backflow trap type 3 28 from 41
Page 29
Display Meaning
„Re-init“
Reset or initialisation of the control unit
„Motor fault“
Motor fault
„Maintenance completed“
Successful maintenance
„Date adjustment“
Changing of the date
„Positive opening“
Forced opening of the motor-powered flap in case of backflow
„NRV closes“
Motor-powered flap has been closed because the battery power is less than 11.8 V in battery operation
„Cut-off of rechargeable battery“
Shut-down because the battery power is less than
10.5 V in battery operation
3.4.3 Operating condition – back pressure
In case of a backflow, the motor-powered flap closes. Display:
„Back pressure NRV closed“
with signal every 10 seconds.
If the backflow ends, the motor-powered flap opens and the control unit switches back to
„Normal operation“
.
During the backflow, the buttons have the following functions:
Function
Button
Switch off signal Call up
„Sound off“
with T1
button and confirm with T3 button
Forces motor-powered flap to open
Keep T3 button pressed for five seconds
Display:
„Positive opening NRV
opened"“
If the backflow sensor is defective, the motor-powered flap will remain closed even after the backflow situation has ended. In this case, the motor-powered flap must be forced opened.
The control goes to
„Back pressure“
, if the backflow still exists. If no
backflow exists, the control reverts to
„Normal operation“
.
3.4.4
Operating condition – malfunction
Mechanical faults or errors around the control are shown on the display and an acoustic alarm sounds.
During an error, the following functions can be carried out:
Handling
Grundfix Plus Control backflow trap type 3 29 from 41
Page 30
Function Button
Switch off signal Call up
„Sound off“
with T1
button and confirm with T3 button
Remove possible blockage An initialisation is triggered with
T3 button – the motor-powered flap will open and close three times – if the error is not removed, the display will show
„Fault 1 / Motor error during commissioning“
.
For the procedure in case of errors, see
Ä Chapter 3.5 „Errors, faults
and remedy“ on page 31
.
3.4.5 Operating condition – battery-powered emergency operation
If the power supply fails, the battery automatically takes over the main supply to the control.
Display:
„Battery operation NRV opened“
Acoustic signal: every 10 seconds (can be switched off using T1 button).
If the rechargeable battery is fully charged (12 V), backflow is ensured for:
n maximum 24 hours when using the 8 m connection cable n maximum 10 hours when using the 20 m connection cable
When the rechargeable battery charge is failing, the control unit behaves as follows:
n Rechargeable battery charge falls below 11.8 V – motor-powered
flap closes
n Rechargeable battery charge falls below 10.5 V – control and display
switch off (deep discharge protection). The backflow function is no longer active.
The following functions can be performed during emergency battery operation:
Button
Function
T1 Menu display
T3 Reset with opening and closing of
the motor-powered flap
Maintenance works are not possible during battery opera­tion.
Handling
Grundfix Plus Control backflow trap type 3 30 from 41
Page 31
3.5 Errors, faults and remedy
Mechanical faults or errors are shown on the display and an acoustic alarm sounds. The error search is supported by displays and limited to a few components.
n Power pack, rechargeable battery n Control unit n Motor, motor-powered flap with mechanism n Pressure switch
If the control unit registers a defect – during the daily self-test or due to failure of the mains or battery power – the relevant error messages are shown on the display.
NOTICE! To avoid damage to the mechanism, button functions should only be used if the cover is firmly screwed to the Grundfix Plus-Control.
In the event of back flow, set the emergency lock to the "ZU (OFF)" position.
Handling
Grundfix Plus Control backflow trap type 3 31 from 41
Page 32
Repair or have faults repaired in accordance with this table:
NOTICE! If the control does not automatically switch back to
„Normal operation“
after attempted troubleshooting, seek
help from a trade professional.
Display Possible cause Troubleshooting by Troubleshooting meas-
ures
„Battery operation “ „NRV opened“
Power failure, circuit breaker has activated
Operators The power supply is
automatically taken over by the battery (approx. 24 hours) until the mains voltage is restored.
Safety against back flow is guaranteed.
n Check mains cable
connection
n Check mains circuit
breakers
„Battery error / Insert
battery“
Rechargeable battery is missing or rechargeable battery fuse or cabling is defective
Trade professionals n Check rechargeable
battery / Recharge­able battery fuse
n Check cabling
„Battery error / Replace
battery“
Motor fuse and / or rechargeable battery fuse defective
Operators Battery voltage has not
achieved 13.9 V after 10 hours of charging or is less than 5 V.
No safeguarding against back flow in case of power outage.
Replace rechargeable battery
„Error motor fault“ „NRV opened“
This error is displayed if a back flow is recog­nised in normal opera­tion and the motor­powered flap cannot be closed due to an motor defect or foreign body blocking it.
n Motor defective n Motor spindle
broken
n Motor-powered flap
blocked
Operators Note: In case of back
flow, there is a risk of flooding - Set the emer­gency lock to "ZU" (OFF) position.
Trigger the self-test with T3 button:
n If the motor doesn’t
begin immediately, check the cable con­nections in the con­trol unit. If the error message remains, replace cover (model
4987.418)1).
„Back pressure“ „Close emergency
lock“
1)
The components integrated into the cover cannot be replaced individually.
Handling
Grundfix Plus Control backflow trap type 3 32 from 41
Page 33
Display Possible cause Troubleshooting by Troubleshooting meas-
ures
„Commissioning error
1 / motor fault“
This error is displayed if a defect is recognised during a self-test.
n Motor / Mechanism
defective
n Motor-powered flap
blocked
n The motor is turning
and trying to close the motor-powered flap but the error message continues: Open and clean the cover, see
Ä Chapter 3.6.2 „Maintenance“ on page 34
. If the error message remains, replace cover.
Operators
„Back pressure“ „NRV closed“
(Display although there is no back flow occur­ring)
Pressure switch defec­tive
Operators Positive opening with
T3 button – keep pressed down for 5 seconds.
Replace cover.
1)
The components integrated into the cover cannot be replaced individually.
3.6 Care and maintenance
3.6.1 Inspection
To ensure safe operation, a monthly "inspection" must be carried out by a professional, see
Ä „Regulations from section: Inspection“ on page 7
.
Check the functions of the Grundfix Plus-Control:
Close and re-open the motor-powered flap by pressing the button T2.
Handling
Grundfix Plus Control backflow trap type 3 33 from 41
Page 34
Activate the emergency lock and in doing so check the mobility.
3.6.2 Maintenance
DIN 1986-3 requires "Maintenance" of the system twice a year to ensure safe operation.
Requirements:
n Maintenance work is not possible in battery operation as the power
loss is too great.
n Maintenance must be carried out by a professional. n Only use original parts for repairs, maintenance and extensions. n Replace defective components, do not repair. n When using cameras and cleaning devices (cleaning spiral, high-
pressure cleaner), protect the backflow trap against mechanical damage.
n Only begin maintenance work when is certain that there is no back
flow situation and the drainage fittings upstream from the Backflow trap are not being used.
In normal operation, the control shows that maintenance is due every 4320 operating hours (=180 operating days).
Display:
„Perform maintenance“
The acoustic signal can be switched off by pressing the buttons T1
„Sound off“
and T3. The display screen goes blank after maintenance
has been carried out. There is a pressure switch in the lid of the Grundfix Plus control, which
gives the signal to close the motor-powered flap. During cleaning work, the cover must not be cleaned with a high-pressure cleaner, abrasive cleaning agents, blades or similar cleaning equipment.
To avoid damage, only clean casing, flap mechanisms and seals with soft brushes under running water.
The buttons should only be used if the lid is firmly screwed onto the Grundfix Plus-Control.
Choose the menu
„Maintenance“
by pressing button T1 and con-
firming with button T3.
INFO! The display remains unchanged when calling up the menu
„Maintenance“
.
Close the motor-powered flap by pressing the button T2.
Handling
Grundfix Plus Control backflow trap type 3 34 from 41
Page 35
Place the emergency lock to "ZU (OFF)" position.
Loosen screws on the lid.
Carefully remove lid.
Clean the spindle on the underside of the lid. Do not grease the spindle!
Handling
Grundfix Plus Control backflow trap type 3 35 from 41
Page 36
Carefully clean the opening for the pressure switch on the lower side of the cover with a small brush.
Remove and clean flaps.
Check seals, if necessary, replace. Clean casing.
The seals of the partition walls must be greased with silicon grease.
Handling
Grundfix Plus Control backflow trap type 3 36 from 41
Page 37
Install flaps.
Position and screw on lid.
Open the motor-powered flap by pressing button T2.
Open and close the emergency lock with the manual actuator – check functionality.
Handling
Grundfix Plus Control backflow trap type 3 37 from 41
Page 38
Place the emergency lock to "ZU (OFF)" position.
Close the motor-powered flap by pressing the button T2.
ð
Motor-powered flap and emergency lock shutter are closed.
Screw the brass plug out of the lid.
Screw in test funnel.
Handling
Grundfix Plus Control backflow trap type 3 38 from 41
Page 39
Fill water to the top marking of the test funnel.
ð
When the pressure switch is intact, the control will report a back flow:
Display
„Test NRV closed“, „back pressure NRV closed“
If necessary, a positive opening is possible. Press the button T3 for 5 seconds.
Keep the water level in the test funnel constant for 10 minutes by replenishing. Observe loss.
ð
If the loss is greater than 0.5 l, check and, if required, replace the seals on the flaps.
Place the emergency lock to "AUF (ON)" position.
ð
The water drains away. Display:
„Test NRV closed“
Open the motor-powered flap by pressing button T2.
Handling
Grundfix Plus Control backflow trap type 3 39 from 41
Page 40
Remove test funnel.
Screw in brass plug.
ð
The following message appears on the display after the suc­cessful procedure
„Maintenance / Correctly performed“
.
The control returns to
„Normal operation“
after approx.
60 seconds.
Alternatively, normal operation can be activated using but­tons T1 and T3.
3.6.3 Replacing the rechargeable battery
DANGER! Risk of electric shock!
Replacement of the rechargeable battery should only be carried out by specialist companies.
Remove mains plug before opening the casing.
Replacement of the rechargeable battery is required if the rechargeable battery is defective or if after a charging time of 10 hours a level of
13.9 Volt has not been reached. This will be shown on the display using the notice
„Battery fault / Replace battery“
.
The rechargeable battery may only be replaced with an original spare part (art. no. 471 088).
Open control unit. Remove defective rechargeable battery.
Handling
Grundfix Plus Control backflow trap type 3 40 from 41
Page 41
Connect new rechargeable battery.
Clamping strip configuration
Pos. cable Functions Marking on
the connection strip
3 black – fac-
tory-fitted
rechargeable battery con­nection
GND
4 red – factory-
fitted
rechargeable battery con­nection
+ AKKU
Insert replacement battery fuse (right).
ð
The charging time begins approx. 30 seconds after the rechargeable battery fuse has been inserted.
Green LED on the inside of the lid is lit Display:
„Battery charging“
3.7
Disposal
Separate the product and packaging materials (e. g. paper, metal, plastic or non-ferrous metals) and dispose of in accordance with valid national legal requirements.
Electronic components and batteries must not be put in the domestic waste but must be disposed of appropriately in conformity with the applicable directives, see
Ä „Regulations from section: Disposal“
on page 7
.
Handling
Grundfix Plus Control backflow trap type 3 41 from 41
Loading...