Viega 4987.2 Instructions For Use Manual

Page 1
Grundfix backflow trap type 1
Instructions for Use
for faeces-free wastewater pipe Model Year built:
4987.2 from 01/1996
en_INT
Page 2
Grundfix backflow trap type 1 2 from 14
Page 3

Table of contents

Table of contents
1.1
1.2
1.3
Target groups 4 Labelling of notes 4 About this translated version 5
2 Product information 6
2.1
2.2
2.2.1
2.2.2
2.2.3
2.3
2.3.1
2.3.2
2.3.3
Standards and regulations 6 Intended use 6 Areas of use 6 Place of installation and installation conditions 7 Maintenance 8 Product description 9 Overview 9 Operating mode 9 Control elements 9
3 Handling 10
3.1
3.1.1
3.2
3.2.1
3.3
3.3.1
3.4
Assembly information 10 Installation dimensions 10 Assembly 10 Mount base unit 10 Care and maintenance 11 Maintenance 11 Disposal 14
Grundfix backflow trap type 1 3 from 14
Page 4
About these instructions for use

1 About these instructions for use

Trade mark rights exist for this document; for further information, go to
viega.com/legal

1.1 Target groups

The information in this instruction manual is directed at the following groups of people:
n Heating and sanitary professionals and trained personnel n Operators
Individuals without the abovementioned training or qualification are not permitted to mount, install and, if required, maintain this product. This restriction does not extend to possible operating instructions.
.

1.2 Labelling of notes

The installation of Viega products must take place in accordance with the general rules of engineering and the Viega instructions for use.
Warning and advisory texts are set aside from the remainder of the text and are labelled with the relevant pictographs.
DANGER! This symbol warns of possible life-threatening injury.
WARNING! This symbol warns of possible serious injury.
CAUTION! This symbol warns of possible injury.
NOTICE! This symbol warns of possible damage to property.
This symbol gives additional information and hints.
Grundfix backflow trap type 1 4 from 14
Page 5

1.3 About this translated version

This instruction for use contains important information about the choice of product or system, assembly and commissioning as well as intended use and, if required, maintenance measures. The information about the products, their properties and application technology are based on the current standards in Europe (e. g. EN) and/or in Germany (e. g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/ Germany. These should serve as recommendations in the absence of corresponding national regulations. The relevant national laws, stand­ards, regulations, directives and other technical provisions take priority over the German/European directives specified in this manual: The information herein is not binding for other countries and regions; as said above, they should be understood as a recommendation.
About these instructions for use
Grundfix backflow trap type 1 5 from 14
Page 6

2 Product information

2.1 Standards and regulations

The following standards and regulations apply to Germany / Europe. National regulations can be found on the relevant web site of your country at
Regulations from section: Place of installation and installation condi­tions
Scope / Notice Regulations applicable in Ger-
viega.com/standards
Product information
.
many

2.2 Intended use

2.2.1 Areas of use

Correct place of installation of the backflow trap
Regulations from section: Fields of application
Scope / Notice Regulations applicable in Ger-
Grundfix Plus Control meets the requirements as type 3 backflow trap with double backflow protec­tion
The backflow trap is suitable for use in drain pipelines made of HT or sewer pipe DN 100, 125 or 150. When using other pipes such as e. g. clay pipes or cast-iron pipes, the relevant adapters for HT and sewer pipes must be used.
EN 12056
many
EN 13564
The backflow trap is suitable for faecal matter free, typical household wastewater up to a temperature of 95 °C with pH values ≥ 4 or ≤ 10.
Use in industrial areas or in pipelines, which transport aggressive liquids is not permitted. This includes cleaning agents, which can damage sani­tary equipment, drainage equipment and pipe materials.
Viega recommends closing the emergency trap if operation, where no wastewater is produced, is interrupted for a number of days.
Grundfix backflow trap type 1 6 from 14
Page 7

2.2.2 Place of installation and installation conditions

1
5
4
2
3
Product information
Fig. 1: Wrong place of installation of the backflow trap
Grundfix backflow trap type 1 7 from 14
Page 8
1
5
4
2
3
Product information
2.2.3
Maintenance
Fig. 2: Correct place of installation of the backflow trap
1 - Street = Backflow level 2 - Area safe from backflow 3 - Connection upper floor 4 - Area at risk of backflow 5 - Protection against backflow through backflow trap
The connection of the upper floor (3) onto the underground pipe must be made between the backflow trap and sewer within the building (5) – only then is it possible to ensure that the wastewater system can func­tion faultlessly. To ensure that drainage is permanently guaranteed, backflow traps may not be employed as the central safeguard for a building with drainage equipment installed above the backflow level (1) – in the event of backflow, it would lead to flooding in the building due to wastewater being unable to drain away (4).
See
Ä „Regulations from section: Place of installation and installation
conditions“ on page 6
Backflow seals should be installed in such a way that they are always accessible.
Maintenance must be carried out twice a year to ensure safe operation. See
Ä Chapter 3.3.1 „Maintenance“ on page 11
Grundfix backflow trap type 1 8 from 14
Page 9

2.3 Product description

1 2
34
1

2.3.1 Overview

Product information

2.3.2 Operating mode

2.3.3 Control elements

Fig. 3: Backflow trap Grundfix type 1
1 - lid 2 - emergency lock actuation 3 - shutter valve 4 - base unit
In the case of backflow, the pipeline will be closed by the shutter valve in the backflow trap. In addition, the shutter valve can be closed man­ually using a manual actuator.
Fig. 4: Control elements backflow trap
1 - Emergency shut-off
Grundfix backflow trap type 1 9 from 14
Page 10

3 Handling

3.1 Assembly information

3.1.1 Installation dimensions

Handling

3.2 Assembly

3.2.1 Mount base unit

Fig. 5: Installation dimensions
D H1 H2 H3 L1 L2 L3
110 260 100 65 405 215 545
125 260 105 75 405 215 550
160 295 125 95 470 245 640
The installation in the drainage pipeline may only be carried out by con­struction or specialised sanitary companies observing the building regu­lations and following this instruction for use.
Grundfix backflow trap type 1 10 from 14
Page 11
Install the base unit horizontally into the base pipeline. Observe flow direction!
At maximum, line up to the middle of the drainpipe. Close emergency shut-off (position "OFF).
Handling

3.3 Care and maintenance

3.3.1 Maintenance

DIN 1986-3 requires "Maintenance" of the system twice a year to ensure safe operation.
Requirements:
n Maintenance must be carried out by a professional. n Only use original parts for repairs, maintenance and extensions. n Replace defective components, do not repair. n When using cameras and cleaning devices (cleaning spiral, high-
n Only begin maintenance work when is certain that there is no back
In this way, damage from flooding can be avoided before commis­sioning.
pressure cleaner), protect the backflow trap against mechanical damage.
flow situation and the drainage fittings upstream from the Backflow trap are not being used.
Clean
Grundfix backflow trap type 1 11 from 14
Page 12
Place the emergency lock to "ZU (OFF)" position.
Loosen screws on the lid.
Handling
Carefully remove lid.
Remove and clean flap.
Grundfix backflow trap type 1 12 from 14
Page 13
Check seal, if necessary, replace. Clean casing.
Grease the seal of the partition on the casing side with silicon grease.
Handling
Install flap.
Position and screw on lid.
Grundfix backflow trap type 1 13 from 14
Page 14

3.4 Disposal

Handling
Open and close the emergency lock with the manual actuator – check functionality.
Separate the product and packaging materials (e. g. paper, metal, plastic or non-ferrous metals) and dispose of in accordance with valid national legal requirements.
Grundfix backflow trap type 1 14 from 14