About these instructions for use
1About these instructions for use
Trade mark rights exist for this document; for further information, go to
viega.com/legal
1.1Target groups
The information in this instruction manual is directed at the following
groups of people:
n Heating and sanitary professionals and trained personnel
n Operators
Individuals without the abovementioned training or qualification are not
permitted to mount, install and, if required, maintain this product. This
restriction does not extend to possible operating instructions.
.
1.2Labelling of notes
The installation of Viega products must take place in accordance with
the general rules of engineering and the Viega instructions for use.
Warning and advisory texts are set aside from the remainder of the text
and are labelled with the relevant pictographs.
DANGER!
This symbol warns of possible life-threatening injury.
WARNING!
This symbol warns of possible serious injury.
CAUTION!
This symbol warns of possible injury.
NOTICE!
This symbol warns of possible damage to property.
This symbol gives additional information and hints.
Grundfix backflow trap type 14 from 14
Page 5
1.3About this translated version
This instruction for use contains important information about the choice
of product or system, assembly and commissioning as well as intended
use and, if required, maintenance measures. The information about the
products, their properties and application technology are based on the
current standards in Europe (e. g. EN) and/or in Germany
(e. g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/
Germany. These should serve as recommendations in the absence of
corresponding national regulations. The relevant national laws, standards, regulations, directives and other technical provisions take priority
over the German/European directives specified in this manual: The
information herein is not binding for other countries and regions; as said
above, they should be understood as a recommendation.
About these instructions for use
Grundfix backflow trap type 15 from 14
Page 6
2Product information
2.1Standards and regulations
The following standards and regulations apply to Germany / Europe.
National regulations can be found on the relevant web site of your
country at
Regulations from section: Place of installation and installation conditions
Scope / NoticeRegulations applicable in Ger-
viega.com/standards
Product information
.
many
2.2Intended use
2.2.1Areas of use
Correct place of installation of the
backflow trap
Regulations from section: Fields of application
Scope / NoticeRegulations applicable in Ger-
Grundfix Plus Control meets the
requirements as type 3 backflow
trap with double backflow protection
The backflow trap is suitable for use in drain pipelines made of HT or
sewer pipe DN 100, 125 or 150. When using other pipes such as e. g.
clay pipes or cast-iron pipes, the relevant adapters for HT and sewer
pipes must be used.
EN 12056
many
EN 13564
The backflow trap is suitable for faecal matter free, typical household
wastewater up to a temperature of 95 °C with pH values ≥ 4 or ≤ 10.
Use in industrial areas or in pipelines, which transport aggressive liquids
is not permitted. This includes cleaning agents, which can damage sanitary equipment, drainage equipment and pipe materials.
Viega recommends closing the emergency trap if operation, where no
wastewater is produced, is interrupted for a number of days.
Grundfix backflow trap type 16 from 14
Page 7
2.2.2Place of installation and installation conditions
1
5
4
2
3
Product information
Fig. 1: Wrong place of installation of the backflow trap
Grundfix backflow trap type 17 from 14
Page 8
1
5
4
2
3
Product information
2.2.3
Maintenance
Fig. 2: Correct place of installation of the backflow trap
1 - Street = Backflow level
2 - Area safe from backflow
3 - Connection upper floor
4 - Area at risk of backflow
5 - Protection against backflow through backflow trap
The connection of the upper floor (3) onto the underground pipe must
be made between the backflow trap and sewer within the building (5) –
only then is it possible to ensure that the wastewater system can function faultlessly. To ensure that drainage is permanently guaranteed,
backflow traps may not be employed as the central safeguard for a
building with drainage equipment installed above the backflow level (1) –
in the event of backflow, it would lead to flooding in the building due to
wastewater being unable to drain away (4).
See
Ä „Regulations from section: Place of installation and installation
conditions“ on page 6
Backflow seals should be installed in such a way that they are always
accessible.
Maintenance must be carried out twice a year to ensure safe operation.
See
Ä Chapter 3.3.1 „Maintenance“ on page 11
Grundfix backflow trap type 18 from 14
Page 9
2.3Product description
12
34
1
2.3.1Overview
Product information
2.3.2Operating mode
2.3.3Control elements
Fig. 3: Backflow trap Grundfix type 1
1 - lid
2 - emergency lock actuation
3 - shutter valve
4 - base unit
In the case of backflow, the pipeline will be closed by the shutter valve
in the backflow trap. In addition, the shutter valve can be closed manually using a manual actuator.
Fig. 4: Control elements backflow trap
1 - Emergency shut-off
Grundfix backflow trap type 19 from 14
Page 10
3Handling
3.1Assembly information
3.1.1Installation dimensions
Handling
3.2Assembly
3.2.1Mount base unit
Fig. 5: Installation dimensions
DH1H2H3L1L2L3
11026010065405215545
12526010575405215550
16029512595470245640
The installation in the drainage pipeline may only be carried out by construction or specialised sanitary companies observing the building regulations and following this instruction for use.
Grundfix backflow trap type 110 from 14
Page 11
Install the base unit horizontally into the base pipeline.
Observe flow direction!
At maximum, line up to the middle of the drainpipe.
Close emergency shut-off (position "OFF‟).
Handling
3.3Care and maintenance
3.3.1Maintenance
DIN 1986-3 requires "Maintenance" of the system twice a year to ensure
safe operation.
Requirements:
n Maintenance must be carried out by a professional.
n Only use original parts for repairs, maintenance and extensions.
n Replace defective components, do not repair.
n When using cameras and cleaning devices (cleaning spiral, high-
n Only begin maintenance work when is certain that there is no back
In this way, damage from flooding can be avoided before commissioning.
pressure cleaner), protect the backflow trap against mechanical
damage.
flow situation and the drainage fittings upstream from the Backflow
trap are not being used.
Clean
Grundfix backflow trap type 111 from 14
Page 12
Place the emergency lock to "ZU (OFF)" position.
Loosen screws on the lid.
Handling
Carefully remove lid.
Remove and clean flap.
Grundfix backflow trap type 112 from 14
Page 13
Check seal, if necessary, replace.
Clean casing.
Grease the seal of the partition on the casing side with silicon
grease.
Handling
Install flap.
Position and screw on lid.
Grundfix backflow trap type 113 from 14
Page 14
3.4Disposal
Handling
Open and close the emergency lock with the manual actuator –
check functionality.
Separate the product and packaging materials (e. g. paper, metal,
plastic or non-ferrous metals) and dispose of in accordance with valid
national legal requirements.