Viega 1219.6 Instructions For Use Manual

Page 1
Safety temperature limiter
Instructions for Use
for Fonterra radiant heating and cooling, pump circuit at over temperature
Model Year built:
1219.6 from 01/2007
en_INT
Page 2
Safety temperature limiter 2 from 8
Page 3
1 About these instructions for use 4
Table of contents
1.1
1.2
1.3
Target groups 4 Labelling of notes 4 About this translated version 5
2 Product information 6
2.1
2.2
2.3
Intended use 6 Operating mode 6 Technical data 6
3 Handling 7
3.1
3.2
Assembly 7 Disposal 8
Safety temperature limiter 3 from 8
Page 4
About these instructions for use

1 About these instructions for use

Trade mark rights exist for this document, further information can be found at

1.1 Target groups

The information in this instruction manual is directed at the following groups of people:
n Heating and sanitary professionals and trained personnel
It is not permitted for individuals without the abovementioned training or qualification to mount, install and, if required, service this product. This restriction does not extend to possible operating instructions.
viega.com/legal
.

1.2 Labelling of notes

Warning and advisory texts are set aside from the remainder of the text and are labelled with the relevant pictographs.
DANGER! This symbol warns against possible life-threatening injury.
WARNING! This symbol warns against possible serious injury.
CAUTION! This symbol warns against possible injury.
NOTICE! This symbol warns against possible damage to property.
Notes give you additional helpful tips.
Safety temperature limiter 4 from 8
Page 5

1.3 About this translated version

This instruction for use contains important information about the choice of product or system, assembly and commissioning as well as intended use and, if required, maintenance measures. The information about the products, their properties and application technology are based on the current standards in Europe (e. g. EN) and/or in Germany (e. g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/ Germany. These should serve as recommendations in the absence of corresponding national regulations. The pertinent national laws, stand­ards, regulations and guidelines, as well as other technical guidelines, have priority over German/European guidelines in this manual: The information is not binding for other countries and territories and should, as mentioned, be considered as support.
About these instructions for use
Safety temperature limiter 5 from 8
Page 6

2 Product information

38
41
90
107
55

2.1 Intended use

Contact thermostat with sensor head for limiting the temperature of Fonterra surface heating units in combination with control stations.

2.2 Operating mode

In case of a fault, the safety contact thermostat switches off the circula­tion pump and therefore prevents the Fonterra surface heating from overheating. To avoid undesired activation, set the temperature at the safety contact thermostat 10 C° above the desired supply temperature (factory setting 60 °C).
Product information

2.3 Technical data

Overview
NOTICE! Make sure that the permissible maximum floor temperature is not exceeded in the vicinity of the heating pipes.
Fig. 1: Product dimensions
Maximum contact temperature 110 °C
Safety temperature limiter 6 from 8
Temperature setting range 30–90 °C
Factory setting 60 °C
Differential gap approx. 5 K
Switching capacity 16 (4) A, 250 V AC
Page 7

3 Handling

t° C
C 2 1 PE
C
2
1

3.1 Assembly

Handling
DANGER! Danger due to electrical current
An electric shock can lead to burns and serious injury and even death.
– Work on the electrics may only be carried out by trained
electricians.
– Always de-energise the connection line before work is
commenced.
Loosen the screw on the casing with a suitable flat-blade screw­driver.
Remove external casing.
Make the electrical connection as illustrated.
Safety temperature limiter 7 from 8
Page 8
Handling
Position the safety temperature limiter at the supply after the pump or on the manifold supply beam.
Fasten safety temperature limiter with steel tape.

3.2 Disposal

Separate the product and packaging materials (e. g. paper, metal, plastic or non-ferrous metals) and dispose of in accordance with valid national legal requirements.
Safety temperature limiter 8 from 8