Victron energy 12/30, 24/16, 12/50, 24/25 User Manual

Page 1
0
victron energy
GB NL F D I DK ΕΛ N P E S Specs
USER MANUAL
12/30 12/50
24/16 24/25
Page 2
1
victron energy
Copyrights 1999, 2000, 2001 Victron Energy B.V.
All Rights Reserved
This publication or parts thereof, may not be reproduced in any form, by any method, for any purpose.
VICTRON ENERGY B.V. MAKES NO WARRANTY, EITHER EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, REGARDING THESE VICTRON ENERGY PRODUCTS AND MAKES SUCH VICTRON ENERGY PRODUCTS AVAILABLE SOLELY ON AN “AS – IS” BASIS.
IN NO EVENT SHALL VICTRON ENERGY B.V. BE LIABLE TO ANYONE FOR SPECIAL, COLLATERAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES IN CONNECTION WITH OR ARISING OUT OF PURCHASE OR USE OF THESE VICTRON ENERGY PRODUCTS. THE SOLE AND EXCLUSIVE LIABILITY TO VICTRON ENERGY B.V., REGARDLESS OF THE FORM OF ACTION, SHALL NOT EXCEED THE PURCHASE PRICE OF THE VICTRON ENERGY PRODUCTS DESCRIBED HEREIN.
For conditions of use and permission to use this manual for publication in other than the English language, contact Victron Energy B.V.
Victron Energy B.V. reserves the right to revise and improve its products as it sees fit. This publication describes the state of this product at the time of its publication and may not reflect the product at all times in the future.
Page 3
2
victron energy
GB NL F D I DK ΕΛ N P E S Specs
SAFETY AND REGULATORY INFORMATION
General
Review related documentation of this product to familiarise yourself with safety markings and instructions before you operate the equipment.
This product has been designed and tested in accordance with international standards. Only use the equipment for the intended purpose of application.
WARNING: RISK OF ELECTRIC SHOCK. The product is used in conjunction with a permanent energy source (battery). Even if the equipment is switched off, dangerous electrical voltages may appear at the in- and/or output terminals. Always disconnect AC power and battery before maintaining or servicing the product. A Ground Fault Circuit Interruptor (GFCI) must be installed in the AC supply circuit.
There are no user-serviceable parts inside. Do not remove the frontplate or operate the product without the frontplate fitted. Refer all servicing to qualified personnel.
Never use the product in locations where there is danger of gas- or dust explosions. Consult your supplier to ensure that the product is intended for use in conjunction with the battery. Always apply the battery manufacturer’s safety instructions.
Caution: never carry heavy loads without assistance.
Explosive gases can be generated during charging of a lead-acid battery. Prevent open flame and sparks. Take care of sufficient ventilation during charging.
Never try to recharge non-rechargeable batteries.
The on/off switch at the front panel of this battery charger does not isolate the main circuits.
A double-pole switch with a minimum contact distance of 3mm must be incorporated in the fixed mains input wiring of the installation
Installation
The installation of this product must be performed by qualified personnel.
Always refer to the installation section in the operator’s manual before applying power to the equipment.
This is a Safety Class I product (provided with a protective earthing terminal). An uninterruptible safety earth ground must be provided at the AC in/output terminals. An additional grounding point is located at the outside of the product. Whenever it is likely that the grounding protection has been impaired, the product must be made inoperative and secured against any unintended operation; refer to qualified service personnel.
Make sure that fuses and circuit breakers are provided in the connecting wires. Never replace a safety component by a different type. Consult the manual for determining the correct component.
Make sure that all cables and wiring in the installation are anchored such that the conductors are relieved from strain and twisting.
Before applying power, verify that the available power source matches the configuration settings of the product as described in the manual.
Ensure that the environmental conditions are suitable for operation of the equipment. Never operate the product in a wet or in a dusty environment.
Always allow enough free space around the product for ventilation and make sure that ventilation vents are not blocked.
Be sure that the demanded power does not exceed the capacity of the product.
This device is a continuous duty automatic charger for rechargeable open, sealed and gel lead acid batteries (max. 12 x 2V cells)
For supply connection use wires suitable for at least 75°C (167°F).
CAUTION: Replace defective cords or wires immediately.
Transport and storage
When storing or transporting the product make certain that mains power and battery leads are disconnected.
No liability can be accepted for any transport damage when equipment is shipped in non­original packaging.
Store the product in a dry location, storage temperature must be between –20°C and 60°C.
Refer to the battery manufacturer manual concerning transport, storage, charging, recharging and disposal of the battery.
Page 4
3
victron energy
DESCRIPTION
Technology
The Phoenix Charger is a fully high-frequency switched battery charger. The input is electronically powerfactor corrected by the first powerstage. The next stage gives provision for galvanic isolation and a perfect DC voltage at the output terminals. A very accurate charging state of the battery is guaranteed because the charging process is microcontroller regulated. The internal electronic parts are protected against moisture and dirt by means of a special coating, which assures a long lifetime of your battery charger. Two high-capacity batteries and an additional low­capacity battery can be charged with this charger.
Adaptive Charging
The new Phoenix Charger uses the Adaptive Charging Characteristic. The Adaptive Charging Characteristic distinguishes from other charging characteristic on several topics. The main 3 topics are Rapid Charging, Battery Safe Mode and All Season Mode. Generally speaking the Phoenix Charger will adapt to the connected batteries.
Rapid charging
In the first stage, the bulk phase, of the charging cycle the batteries are charged with higher current then traditional charging methods. The bulk phase will stop at the point where the battery voltage will be 14,4V or 28,8V. From here the absorption phase will start. Based on the measured bulk time the length of the absorption time will be calculated. For this the charger micro-controller will monitor several parameters of the battery.
BatterySafe mode
But what if your battery needs a higher absorption voltage? The charger will gradually raise the applied voltage to the battery until it reaches the set absorption voltage. This phase we call the BatterySafe Mode. It will safe your battery from destruction by overcharging. The Phoenix Charger is temperature compensated. The charger will recalculate different values based on the battery temperature.
All Season mode
For periods were you do not use your batteries and the mains is applied to the charger, the Phoenix Charger will reduce its float voltage. By doing this we reduce the gassing in your battery so they will not run dry after a longer period of not using your battery.
To keep your batteries in shape the Phoenix Charger will raise the applied voltage once a week. This we call the repetitive absorption.
Operation
The battery charger charges the battery with a 3­stage adaptive charging characteristic, see specifications at the back for details. It can remain connected to the battery continuously, without increased gas formation, caused by overcharging, taking place. The charger can be used for different types of batteries but the default settings are for Sonnenschein A200 dryfit gel batteries. See specifications for other pre-programmed battery types. For use with other types of batteries please contact your battery supplier to inform you about the right charging voltages. If necessary let the Phoenix Charger be readjusted. The full charging current of the Phoenix Charger is divided in two main outputs. An extra output with limited charge capacity is available to charge a starter battery for example. The charger is protected against short-circuit at the outputs and too high ambient temperature.
Temperature sensor
The Phoenix Charger is factory shipped with a temperature sensor. Its function is to measure the battery temperature and adjust the charging voltages accordingly. By this means superiour charging is achieved and a longer lifetime of the battery is assured.
Voltage sense
Using the Voltage sense connection will compensate the battery cable loss.
Page 5
4
victron energy
GB NL F D I DK ΕΛ N P E S Specs
Controls
The Phoenix Charger will start charging by switching it ON with the switch at the front panel. One of the LED’s at the front will indicate the progress of charge state:
Battery is less then 80% charged.
Battery is approximately charged for 80%. If Bulk LED is illuminating as well the set absorption voltage has not yet been reached (Battery Safe Mode).
Battery is fully charged and will be kept charged with trickle charge.
An output fuse is defective or the ambient temperature of the charger is too high.
The Phoenix Charger will stop charging by switching it OFF with the switch at the front panel.
Equalize a traction set
This is done at a higher voltage than most DC­equipment can handle so all consumer electronics should be disconnected before equalizing the battery.
Put the charger in off position. Switch ON-OFF- ON within 2 seconds.
You’ll see all the LED’s flashing 5 times. After the 5th time all LEDs illuminate in sequence:
Bulk –switch OFF-ON when this LED lights up. Now the charger increases its voltage up to 1 Volt above Absorption voltage for a 12V model or 2 Volts for a 24V model. The maximum current in this mode is limited to ¼ of the adjusted maximum charge current. The charger will stay in this mode for 1 hour and then switches to Float mode. Equalizing will only work with an already charged battery. If the battery voltage remains too low (see specs) for > 60 seconds the charger switches to Bulk mode and continues charging according normal charging characteristic.
Force to Absorption mode for fixed time
In certain circumstances it can be desirable to charge the battery occasionally with Absorption voltage for a fixed time.
Put the charger in off position. Switch ON-OFF- ON within 2 seconds.
You’ll see all the LED’s flashing 5 times. After the 5th time a sequence starts:
Bulk –wait.
Absorption –switch OFF-ON when this LED
lights up. Now the charger will stay in Absorption mode for the default or adjusted fixed Absorption time.
Remote control
The Phoenix Charger can be remote controlled optionally. With the Phoenix Charger Control all indicators can be seen and additionally the charging current. With this remote control it is possible to temporarily limit the charging current. This could be useful in case of a low current mains connection in combination with other utility equipment.
TROUBLESHOOTING
Problem Possible cause Solution
The output fuses are defect
Return the product to your dealer
Failure LED illuminates
The ambient temperature of the charger is too high
Put the charger in a cool and well ventilated
environment The mains voltage is not ok
Measure the mains voltage
and make it within specs
Charger does not function
The input fuse is defect
Return the product to your
dealer A bad battery connection
Check the battery
connections The Absorption voltage is wrongly adjusted The float voltage is wrongly adjusted
Consult your battery
supplier and electrician and
have the charging voltage
adjusted
The battery capacity is too large
Make sure the charger
matches the battery
capacity
The battery doesn’t get fully charged
The output fuses are defect
Return the product to your
dealer The Absorption voltage is wrongly adjusted The float voltage is wrongly adjusted
Consult your battery
supplier and electrician and
have the charging voltage
adjusted
A single battery cell is defect
Replace the battery or the
defect cell Too small a battery Consult your battery
supplier and electrician and
have the charging current
adjusted
The battery is being overcharged
The ambient temperature of the battery is too high
Consult your electrician and
let him connect a
temperature sensor
iiii on
onon
on
Failure
FailureFailure
Failure
Float
FloatFloat
Float
Absorpt
AbsorptAbsorpt
Absorpt
Bulk
BulkBulk
Bulk
Page 6
5
victron energy
INSTALLATION
WARNING: Qualified personnel only
Location
The Phoenix Charger must be installed in a dry, well-ventilated area. Too high an ambient temperature has the consequence of lower output, shorter life or a complete shutdown of the Phoenix Charger. The Phoenix Charger is suitable for floor and wall mounting. However, for optimum cooling, a vertical position is recommended. The cables between the Phoenix Charger and the battery must be kept as short as possible to minimise cable losses.
Required tools and cables
Socketdriver & socket 10 mm.
Screwdriver no. 2.
Crosshead screwdriver no. 2 phillips.
Battery cables and external fuse:
Model Length 0 - 6 m Fuse
12/30 16 mm² 40 AT 12/50 25 mm² 60 AT 24/16 10 mm² 20 AT 24/25 16 mm² 30 AT
Cables longer then 6 m are not recommended. Cable eyes with M6 holes should be used. For supply connection use wires suitable for at least 75°C (167°F). CAUTION: Replace defective cords or wires immediately.
Connection sequence
Disconnect mains.
Disconnect battery cables from the battery.
Remove the frontplate.
Remove carfuses if placed.
Connect the housing of the charger to ground.
The housing is fitted with an M4 ground screw for this purpose.
Connect the accompanying temperature sensor to the +T-sense and –T-sense and mount the M8 cable-eye to one of the battery clamps. The connector is located on the front PCB.
Voltage sense is recommended. Connect 0.75 mm² wires to +V-sense and –V-sense and use a 5 AT fuse near the battery for protection. The connector is located on the front PCB.
Connect the starter battery (if present) to the Trickle-charge connector located near the minus­output bolt. Use a 25 AT carfuse near the battery for protection.
If used, the Phoenix Charger Control panel can be connected by means of a standard 8-pole communication cable with 8-pole communication connector. The maximum length is 100 m.
Connect battery cables to the charger. Note that there’s only one “minus”- output to connect both battery minus poles. Use a fuse according the table near the battery for protection.
Connect battery cables to the battery.
Watch if the POLARITY LED does NOT
illuminate.
If it does reverse battery cables
Put the car fuses in their sockets
Connect the AC-in by means of a 3-core cable of
2.5 – 4 mm² flexible core to the AC-in terminal block. Note that a real PE-connection is strictly necessary.
Replace the frontplate.
Phoenix Charger dimensions
Page 7
6
victron energy
GB NL F D I DK ΕΛ N P E S Specs
20AT 20AT 20AT 20AT
120Vac – 240Vac
Mains i n put
PHOENIX CHARGER CONTROL
PHOENIX CHARGER CONTROLPHOENIX CHARGER CONTROL
PHOENIX CHARGER CONTROL
BATTERY 1
BATTERY 2
STARTER BA T TERY
PE earth connection N AC input : Neutral L AC input : Line
+ battery 1
+ battery 2
- battery
+ Trickle charge
-
Trickle charge
+ Voltage sense
-
Voltage sense
+ Temperature sense
-
Temperature sense
Remote
Connector
12/50: 60AT 12/30: 40AT
24/25: 30AT 24/16: 20AT
12/50: 60AT 12/30: 40AT
24/25: 30AT 24/16: 20AT
5AT
25AT
DOUBLE POLE SWITCH & CIRCUIT BREA KER
GROUND
POLARITY
<==>
CONNECTION DIAGRAM PHOENIX CHARGER
Page 8
7
victron energy
Adjustments without remote panel
WARNING: Always check with your battery supplier if the choosen charge characteristic is suitable for your battery and application
Remove the frontplate and disconnect battery and Voltage sense and Temperature sense and connect a digital voltmeter to – and +1 output.
Bulk-current
While switching on keep both the pushbuttons & pushed.
Release pushbuttons.
Bulk LED is flashing alternately with Failure LED.
Push for up and for down.
Reading as follows:
Discard first digit of DVM then multiply by 10, i.e:
22.50V => ….2.50 => 25 Amps
15.00V => .....5.00 => 50 Amps
Switch the charger Off to store.
Absorption and Float voltage
While switching on keep the pushbutton pushed for Absorption voltage and for Float­voltage.
Release pushbuttons.
Absorption or Float LED is flashing alternately
with Failure LED.
Push for up and for down.
Reading on voltmeter as is.
Switch the charger Off to store.
Please note that in adjust-mode the
Temperature sense compensation is not taken into account.
Warning: If the charger is not switched Off after an adjustment the new value will not be stored but will remain on the outputs. After 4 hours the charger continues the normal sequence with the old values. This can be useful if a forced high voltage is wanted to get some life in an assumed ‘dead’ battery.
Return to factory settings
Switch the charger on.
Keep the pushbutton and/ or pushed while
switching off.
The factory settings are restored.
When ready
Connect battery and if applicable Voltage sense and Temperature sense.
Replace the frontplate.
20AT 20AT 20AT 20AT
PE earth connection
N AC input : Neutral
L AC input : Lin e
+ battery 1
+ battery 2
- battery
+ Trickle charge
- Trickle charge
+ Voltage sense
- Voltage sense
+ Temperature sense
- Temperatu re sense
Remote
connector
<= =>
Adjusting maximum Bulk current
20AT 20AT 20AT 20AT
PE earth connection
N AC input : Neutral
L AC input : Line
+ battery 1
+ battery 2
- battery
+ Trickle charge
- Trickle charge
+ Voltage sense
- Voltage sense
+ Temperature sense
- Temperature sense
Remote
connector
<= =>
Adjusting Float voltage
20AT 20AT 20AT 20AT
PE earth connection
N AC input : Neutr al
L AC input : Line
+ battery 1
+ battery 2
- battery
+ Trickle charge
- Trickle charge
+ Voltage sense
- Voltage sense
+ Temperature sense
- Temperature sense
Remote
connector
<= =>
Adjusting Absorption voltage
20AT 20AT 20AT 20AT
PE earth connection
N AC input : Neutral
L AC input : Line
+ battery 1
+ battery 2
- battery
+ Trickle charge
- Trickle charge
+ Voltage sense
- Voltage sense
+ Temperature sense
- Temperature sense
Remote
connector
<= =>
Restoring defaults
Page 9
8
victron energy
Adjustments with remote panel Phoenix Charger Control
WARNING: Always check with your battery supplier if the choosen charge characteristic is suitable for your battery and application
Remove the frontplate and connect the Phoenix Charger Control panel to the 8-pin modular jack.
Disconnect battery, Voltage sense and Temperature sense. A voltmeter is not required but may be useful.
While switching on keep one of the pushbuttons & pushed.
Release pushbutton.
The adjust knob on the remote panel controls
the adjust-mode; the LED’s on the charger correspond with the knob as follows:
knob adjust mode charger LED’s 0% not impl. Failure 10% Bulk FailureÙ Bulk 20% Absorption FailureÙ Absorption 30% Float FailureÙ Float 40% Rep. Abs. interval FailureÙ Abs./Float 50% Rep. Abs. time FailureÙ Bulk/Abs. 60% Max. Abs. time FailureÙ Bulk/Float 70% Characteristic FailureÙ Bulk/Abs./Float 80% Battery type Failure/Abs.Ù Float 90% not impl. Failure 100% not impl. Failure
Push for up and for down.
LED indicators on remote panel read the
value as follows: LED flashing = 1 step LED on = 2 steps 1 bar flashing = 9 steps Left bar is [step x10], right bar is [step x1]. To read the Float and Absorption adjustment the lowest value in the table has to be added:
12 V models 24V models Bulk 0 – 50 A/30A;step 1A 0 – 25 A / 16 A; step 1 A Abs 12.00 – 16.00 V;
step 0.1 V
24.00 – 32.00 V; step 0.1 V
Float 12.00 – 16.00 V;
step 0.1 V
24.00 – 32.00 V;
step 0.1 V Rep. Abs. int. 0 – 45 days; step 1 day ; def.= 7 days Rep. Abs. time 0 – 72 qu. of an hour; step 1 qu.; def = 4 qu. Max. Abs. time or Fixed Abs. time
1 – 8 hrs ; default = 4 hrs.
Characteristic 1 = Fixed: Fixed Abs. time. default = 4 hrs.
Rep. Abs. int. default = 1 day Rep. Abs. time. default = 2 qu. 2 = Adaptive 3 = Adaptive with BatterySafe mode (default)
Battery type default = 1
Abs. Voltage Float Voltage /
Reduced Float
Max.Abs. time
0: User defined 1: Sonnenschein Dryfit A200 gel
14.4 V 28.8 V 13.8 V/
13.0 V
27.6 V/
26.0 V
4 hrs.
2: Traction (tubular plate)
15.0 V 30.0 V 13.8 V/
13.0 V
27.6 V/
26.0 V
6 hrs.
3: Semitraction1 14.4 V 28.8 V 14.0 V/
13.0 V
28.0 V/
26.0 V
5 hrs.
4: Victory
1
14.8 V 29.6 V 14.0 V/
13.0 V
28.0 V/
26.0 V
5 hrs.
12V
model
24V model
12V model
24V model
Turn the knob to another adjust-mode to store or switch Off to escape.
Switch Off and On to start normal charging sequence.
Replace the frontplate.
Warning: If the knob is not turned after an adjustment the charger will not store this adjustment. If the Float or Absorption voltage was adjusted and the charger is not switched off this voltage will remain on the outputs.
1
The optimum absorption voltage of flat plate lead acid batteries depends on mechanical and chemical properties. Batteries with high antimony doping can general be charged with a lower absorption voltage than batteries with low antimony doping, like the Victory carbon fibre battery. (See the book "Electricity on board" at www.victronenergy.com
)
30
Float voltage = 12+(1x1)+(4x0.2)= 13.8 volts (12V model) 24+(1x1)+(4x0.2)= 25.8 volts (24V model)
50
Repeated Absorption time =
4 quarters of an hour
70
Characteristic =
1. Fixed mode
40
Repeated Absorption interval
= 7 days
20
Absorption voltage = 12+(1x2)+(2x0.2)= 14.4 volts (12V model) 24+(1x2)+(2x0.2)= 26.4 volts (24V model)
60
Maximum Absorption time =
4 hrs.
80
Battery type =
1. Gel
10
Max. Bulk current =
25 amps
Page 10
9
victron energy
After 4 hours the charger continues the normal sequence with the old value. This could be useful if a forced high voltage is wanted to get some life in an assumed ‘dead’ battery.
Return to factory defaults
Switch the charger on.
Keep the pushbutton and/ or pushed while
switching off.
The factory defaults are restored.
Replace the frontplate.
Page 11
10
victron energy
GB NL F D I DK ΕΛ N P E S Specs
SPECIFICATIONS
Model 12/50 12/30 24/25 24/16 Nominal input voltage range 120 - 240 Vac Absolute minimum working voltage 90 Vac Absolute maximum working voltage 265 Vac Frequency range 45 - 65 Hz Maximum input current 4A/230 Vac
10A/120 Vac
Powerfactor (cos ϕ )
1
Input fuse 15 AT 6.3 x 32 mm Absorption charge voltage default 14,4 Vdc 28,8 Vdc Float charge voltage default 13,8 Vdc 27,6 Vdc Adjustment range 12 - 16 Vdc 24 - 32 Vdc
50 Adc 30 Adc
25 Adc 16 Adc Bulk charge current shared
between output +1 and output +2
@ Vin=230Vac/Vout=12Vdc/Ta=25°C @ Vin=230Vac/Vout=24Vdc/Ta=25°C
Short circuit current 50 Adc 30Adc 25 Adc 16 Adc Adjustment range 1 - 50 Adc 1 - 30 Adc 1 - 25 Adc 1 - 16 Adc Maximum trickle charge current 4 Adc 4 Adc Current/voltage stability ±1% Output fuse 4x 20 A carfuse 2x 20 A carfuse
Battery leakage current when charger is switched off
<2 mA
Recommended battery capacity 200 - 400 Ah 100 - 200 Ah 100 - 200 Ah 45 - 100 Ah Environment EMC EEC 89/336 Emission EN55014 (1993) EN61000-3-2 EN61000-3-3 Immunity EN55104 (1995) Safety EN60335-2-29 (1991) Vibration IEC68-2-6 : 10 - 150 Hz / 1.0 G Shock IEC68-2-29: 1000 times XYZ +/- 10 G / 16 ms Operating temperature 0-40°C Transport & storage temperature -20 - +60°C Relative humidity max. 95% non condensing Noise < 45 dB (A) Ventilation Combined convection / forced-air Connections Mains connector connection block provision for 4 mm² Output +1/+2 battery connection M6 bolts Trickle charge connection connection block provision for 1.5 mm² Earthing M4 screw Temperature sensor connection block provision for 1.5 mm² Voltage sense connection block provision for 1.5 mm² Remote panel / RS485 RJ45 connector Mechanical Cabinet Aluminium IP21, RAL5012 (blue) epoxy coated Size (h x w x d) 350 x 200 x 110 (mm) Weight 3.8 kg Weight including box 4.9 kg
Page 12
11
victron energy
Charge current
0%
20%
40%
60%
80%
100%
120%
Time
Amps
Charge voltage
10
11
12
13
14
15
16
Time
Volts
Figure 1: Adaptive charging:
Bulk-mode: Entered after a reset or if the battery voltage becomes 1.3V resp. 2.6V (for 12V and 24V
charger) lower than Float voltage. Constant current is applied until the battery has reached 14.4V resp. 28.8V (for 12V and 24V charger, temperature compensated).
Battery Safe mode: The applied voltage to the battery is raised gradually until the set Absorption voltage is reached. The Battery Safe Mode is part of the calculated absorption time.
Absorption-mode: Absorption voltage is applied until {actual-Bulk-Ah*5 / max.adjusted-Bulk-current} (in hours) is reached. Usually {actual-Bulk-Ah*5} = {max.adjusted-Bulk-current * Bulk-hours *5}, but the actual-Bulk-current can be limited by ambient temperature, or remote-control.The maximum time in Absorption mode is the Maximum Absorption time set with control panel.
Float-mode: Float voltage is applied to keep the battery fully charged and to protect it against self discharge. After one day of Float charge a reduced Float charge is applied. This is 13V resp. 26V (for 12V and 24V charger, temperature compensated). This will limit water loss to a minimum when the battery is stored for the winter season. After an adjustable time (default = 7 days) the charger will enter Repeated Absorption-mode for an adjustable time (default = 4 quarters ).
Bulk-hours Absorption time 1 day 7 days 7 days Float reduced Float reduced Float
30
29
28
27
26
25
24
23
22
21
20
1 hour Repeated Absorption
5 x Bulk-hours or Max. Absorption time
Battery Safe
mode
Page 13
12
victron energy
GB NL F D I DK ΕΛ N P E S Specs
50%
55%
60%
65%
70%
75%
80%
85%
90%
95%
100%
90 110 120 132 150 170 187 230
Uin
Am ps
Figure 3: Maximum output current vs. input voltage:
Output voltage = 12.0V / 24.0V
10.0
10.5
11.0
11.5
12.0
12.5
13.0
13.5
14.0
14.5
15.0
0 5 10 15 20 25 30 35 40 45 50 55 60
Battery temperature
Volts
20
21
22
23
24
25
26
27
28
29
30
Volts
Figure 2: Temperature compensation
Default output voltages for Float and Absorption are at 20°C. In adjust mode temperature compensation does not apply.
Tamb = 25°C
Tamb = 40°C
Page 14
13
victron energy
Default factory settings:
Repeated Absorption interval 7 days Repeated Absorption time 4 quarters of an hour Maximum Absorption time 4 hrs
1 = Fixed
Absorption time Repeated Absorption interval Repeated Absorption time
4 hrs 1 day 2 quarters
Characteristic: Default = 3
2 = Adaptive
3 = Adaptive with
Battery Safe Mode
Battery type: Default = 1 Abs. Voltage Float Voltage / Reduced Float Max.Abs.time 0:User defined 1: Sonnenschein Dryfit A200 Gel 14.4 V 28.8 V 13.8 V / 13.0V 27.6 V / 26.0V 4 hrs 2: Traction (Tubular plate) 15.0 V 30.0 V 13.8 V / 13.0V 27.6 V / 26.0V 6 hrs 3: Semitraction 14.4 V 28.8 V 14.0 V / 13.0V 28.0 V / 26.0V 5 hrs 4: Victory 14.8 V 29.6 V 14.0 V / 13.0V 28.0 V / 26.0V 5 hrs 12V
model
24V model
12V model
24V model
Factory defaults can always be restored by your authorized Victron Energy dealer. Acting sequence is described in the installation part of the manual.
Page 15
14
victron energy
GB NL F D I DK ΕΛ N P E S Specs
Page 16
15
victron energy
Victron Energy B.V. The Netherlands
Phone : ** 31 36 535 97 00 Fax : ** 31 36 531 16 66 Customer support desk : ** 31 36 535 97 77 E-mail : sales@victronenergy.com Internet site : http://www.victronenergy.com
Article Number : ISM010001000 Revision : rev01 Date : 26-03-02
Dealer:
Serialnumber:
Loading...