Victron energy 12 120V, 24 120V, Phoenix 12/3000/120V, Phoenix 24/3000/120V User Manual

Page 1
Manual
EN
Appendix
12 | 3000 | 120V 24 | 3000 | 120V
Page 2
Page 3
Copyrights 2007 Victron Energy B.V.
All Rights Reserved
This publication or parts thereof may not be reproduced in any form, by any method, for any purpose.
For conditions of use and permission to use this manual for publication in other than the English language, contact Victron Energy B.V.
VICTRON ENER GY B.V. MAKES NO WARRANTY, EITHER EXPRESSED O R IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS F OR A PARTI CULAR PURPOSE, REGARDING THESE VICTRON ENERGY PRODUCTS AND MAKES SUCH VICTRON E NERGY PRODUCTS AVAILABLE SOLELY ON AN “AS IS” BASIS.
IN NO EVENT SHALL VICTRON EN ER G Y B.V. BE LIABLE TO ANYONE FOR SPECIAL, COLLATERAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES IN CONNECTION WITH OR ARISING OUT OF PURCHASE OR USE OF THESE VICTRON ENERGY PRODUCTS. THE SOLE AND EXCLUSI VE LIAB ILITY TO VICTRON ENERGY B.V., REGARDLESS OF THE FORM OF ACTION, SHALL NOT EXCEED THE PURCHASE PRICE OF THE VICTRON ENERGY PRODUCTS DESCRIBED HERE IN.
Victron Energy B.V. reserves the right to revise and improve its products as it sees fit. This publication describes the state of this product at the time of its publication and may not reflect the product at all times in the future
Page 4
Page 5
EN Appendix
1. SAFETY INSTRUCTIONS
In general
Please read the documentation supplied with this product first, so that you are familiar with the safety signs en directions before using the product. This product is designed and tested in accordance with international standards. T he equipment should be used for the designated application only.
WARNING: DANGER OF ELECTRIC AL SHOCK The product is used in combination with a permanent energy source (battery). Even if the equipment is switched off, a dangerous electrical voltage can occur at the input and/or output terminals. Always switch the AC power off and disconnect the battery before performing maintenance.
The product contains no internal user-serviceable parts. Do not remove the front panel and do not put the product into operation unless all panels are fitted. All maintenance should be performed by qualified personnel.
Never use the product at sites where gas or dust explosions could occur. Refer to the specifications provided by the manufacturer of the battery to ensure that the battery is suitable for use with this product. The battery manufacturer's safety instructions should always be observed.
WARNING: do not lift heavy objects unassisted.
Installation
Read the installation instructions before commencing installat i on activities. This product is a safety class I device (supplied with a ground terminal for safety
purposes). The chassis must be grounded. A grounding point is located on the outside of the product. If it can be assumed that the grounding protection is damaged, the product should be taken out of operation and prevented from accidentally being put into operation again; contact qualified maintenance pers onnel.
Ensure that the connection cables are provided with fuses and circuit breakers. Never replace a protective device by a component of a different type. Refer to the manual for the correct part.
Check before switching the device on whether the available voltage source conforms to the configuration settings of the product as described in the manual.
Ensure that the equipment is used under the correct operating conditions. Never operate it in a wet or dusty environment. Ensure that there is always sufficient free space around the product for ventilation, and that ventilation openings are not blocked.
Page 6
Install the product in a heatproof environment. Ensure therefore that there are no chemicals, plastic parts, curtains or other textiles, etc. in the immediate vicinit y of the equipment.
Transport and storage
On storage or transport of the product, ensure that the battery leads are disconnected. No liability can be accepted for damage in transit if the equipment is not transported in
its original packaging. Store the product in a dry environment; the storage temperature should range from
–20°C to 60°C. Refer to the battery manufacturer's manual for information on trans port, st orage,
charging, recharging and disposal of the battery.
Page 7
EN Appendix
2. DESCRIPTION
SinusMax - Superior engineering
Developed for professional duty, the Phoenix range of inverters is suitable for the widest range of applications. The design criteria have been to produce a true sine wave inverter with optimised efficiency but without compromise i n performance. Employing hybrid HF technology, the result is a top quality product with compact dimensions, light in weight and capable of supplying power, problem-free, t o any load.
Extra start-up pow er
A unique feature of the SinusMax technology is very high start-up power. Conventional high frequency technology does not offer s uch extreme performance. Phoenix inverters, however, are well suited to power up difficult loads such as compressors, electric motors and similar appliances.
Virtually unlimited power thanks to parallel and 3-phase operation capability
Up to 6 inverters can operate in parallel to achieve higher power output. Six 24/3000 units, for example, will provide 18kVA output power. Operation in 3-phase configuration is also possible.
To transfer the load to another AC source: the automatic transfer switch
If an automatic transfer switch is required, we recommend to using the MultiPlus or Quattro instead. The switch is included in these products and the charger functi on of the MultiPlus/Quattro can be disabled. Computers and other elect ronic equi pm ent will continue to operate without disruption because the MultiPlus/Quattro features a very short switchover time (less than 20 milliseconds).
Programmable relay
The Phoenix Inverter is equipped with a programmable relay, which by default is set as an alarm relay. The relay can be programmed for all kinds of other applications however, for example as a starter relay for a generating set.
Programmable with DIP switches, VE.Net panel or personal computer
The Phoenix Inverter is supplied ready for use. Three features are available for changing certain settings if desired: The most important settings (including parallel operation of up to three devices
and 3-phase operation) can be changed in a very simple manner, using DIP switches.
All settings, with exception of the programmable relay, can be changed with a
VE.Net panel.
All settings can be changed with a PC and free of charge software,
downloadable from our website www.victronenergy.com
Page 8
3. OPERATION
3.1 On/Off Switch
When switched to "on", the product is fully functional. The inverter will come into operation and the LED "inverter on" will light up.
3.2 Remote control
Remote control is possible with a simple on/off switch or with a Phoenix Inverter Control panel.
3.3 LED Indications
LED off
LED flashes
LED illuminated
Inverter
Inverter
The inverter is on and supplies power to the load.
on
inverter on Overload
low battery
off
Temperature
Inverter
The nominal output of the inverter is exceeded. The “overload” LED flashes.
on
inverter on Overload
low battery
off
Temperature
Page 9
EN Appendix
Inverter
The inverter is switched off due to overload or short circuit.
on
inverter on Overload
low battery
off
Temperature
Inverter
The battery is almost fully exhausted.
on
inverter on Overload
low battery
off
Temperature
Inverter
The inverter has switched off due to low battery voltage.
on
inverter on Overload
low battery
off
temperature
Inverter
The internal temperature is reaching a critical level.
on
inverter on overload
low battery
off
temperature
Page 10
Inverter
The inverter has switched off due to the electronics temperature being too high.
on
inverter on overload
low battery
off
temperature
Inverter
-If the LEDs are flashing alternately, the battery is nearly exhausted and the nominal output is exceeded.
-If "overload" and "low battery" flash simultaneously, the ripple voltage on the battery terminals is too high.
on
inverter on overload
low battery
off
temperature
Inverter
The inverter switched off due to excess ripple voltage on the battery terminals.
on
inverter on overload
low battery
off
temperature
Page 11
EN Appendix
4. INSTALLATION
This product may only be installed by a qualified electrical engineer.
4.1 Location
The product must be installed in a dry and well-ventilated area, as close as possible to the batteries. There should be a clear space of at least 10cm around the appliance for cooling.
Excessively high ambient temperature will result in the following:
Reduced service life.
Reduced peak capacity, or shutdown of the inverter.
Never position the appliance directly above the batteries.
The Phoenix Inverter is suitable for wall mounting. For mounting purposes, a hook and two holes are provided at the back of the casing (see appendix G). The devic e can be fitted either horizontally or vertically. For optimal c ooling, vert ical fitting is preferred.
The interior of the product must remain accessible after installation.
Try to keep the distance between the product and the battery to a minimum in order to minimize cable voltage losses.
For safety purposes, this product should be installed in a heat-resistant
environment. You should prevent the presence of e.g. chemicals, synthetic
components, curtains or other textiles, etc., in the immediate vici nity.
Page 12
4.2 Connection of battery cables
In order to utilize the full capacity of the product, batteries with sufficient capacity and battery cables with sufficient cross section should be used. See table.
12/3000
24/3000
Recommended battery capacity (Ah)
400–1200
200–700
Recommended DC fuse 400A 300A Recommended cross-section (mm2)
per + and - connection terminal
0 – 5m
2x 50mm2
50mm2
5 – 10m
2x 70mm2
2x 50mm2
* ‘2x’ means two positive and two negative cables. Remark: Internal resistance is the important factor when working with low capacity
batteries. Please consult your supplier or the relevant sections of our book “elect ricity on board”, downloadable from our website.
Procedure
Proceed as follows to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery. Avoid shorting the battery cables.
Undo the four screws at the front of the enclosure and remove the front panel.
Connect the battery cables: see Appendix A.
Tighten the nuts well for minimal contact res istanc e.
Page 13
EN Appendix
4.3 Connection of the AC cabling
This is a Safety Class I product (supplied with a protective grounding
terminal).
The neutral output of the inverter is connected to the enclusure.
This to ensure proper functioning of a GFCI (or RCCB) to be installed in the AC output of the Inverter. The chassis of the product must be connected to ground, or the frame (of a
vehicle) or the ground plate or hull (of a boat).
The terminal block can be found on the printed circuit board, see Appendix A. Use a three-wire cable with a flexible core and a cross section of 2.5 or 4mm²
Procedure
The AC output cable can be connected directly to the terminal block "AC-out".
4.4 Optional Connections
A number of optional connections are possible:
4.4.1 Remote Control
The product can be remotely controlled in two ways.
- With an external switch (connection terminal H, see appendix A). Operates only if the switch on the Inverter is set to “on”.
- With a Phoenix Inverter Control panel (connected to one of the two RJ48 sockets C, see appendix A). Operates only if the switch on the inverter is set to “on”.
Only one remote control can be connected, i.e. either a switch or a remote control panel.
4.4.2. Programmable relay
The inverters are equipped with a multi-functional relay that by default is programmed as an alarm relay. (VEConfigure software needed to change relay functionality).
Page 14
4.4.3 Parallel Connection
The Phoenix Inverter can be connected in parallel with several identical devices. To this end, a connection is established between the devices by means of standard RJ45 UTP cables. The system (Two or more Inverters plus optional control panel) will require subsequent configuration (see Section 5). In the event of connecting units in parallel, the following requirements must be met:
A maximum of six units connected in parallel.
Only identical devices with the same power ratings may be connected in parallel .
Battery capacity should be sufficient.
The DC connection cables to the devices must be of equal length and cross-
section.
If a positive and a negative DC distribution point is used, the cross -section of the connection between the batteries and the DC distribution point must at least equal the sum of the required cross-sections of the connect i ons bet ween the distribution point and the Inverter units.
Place the units close to each other, but allow at least 10cm for ventilation
purposes under, above and beside the units.
UTP cables must be connected directly from one unit to the other (and to the
remote panel). Connection/splitter boxes are not permitted.
Only one remote control means (panel or switch) can be connected to the system.
4.4.4 Three-phase operati o n
The Phoenix Inverter can also be used in 3-phase configuration. To this end, a connection between the devices is made by means of standard RJ45 UTP cables (the same as for parallel operation). The system (Inverters plus an optional control panel) will require subsequently configuration (s ee Section 5). Pre-requisites: see Section 4.4.3.
Page 15
EN Appendix
5. CONFIGURATION
Settings may only be changed by a qualified electric al engineer.
Read the instructions thoroughly before implementing changes.
5.1 Standard settings: ready for use
On delivery, the Phoenix Inverter is set to standard factory values. In general, these settings are suitable fo stand-alone operation.
Standard factory settings
Inverter frequency 60Hz Inverter voltage 120VAC Stand-alone / parallel / 3-phase stand-alone AES (Automatic Economy Switch) off Programmable relay alarm function
5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the software configuration programs (see Section 5.3).
Inverter frequency Output frequency Adjustability: 50Hz; 60Hz
Inverter voltage Output voltage of the Inverter. Adjustability: 95 –128V
Stand-alone / parallel operation / 2-3 phase setting
Using several devices, it is possible to:
increase total inverter power (several devic es i n paral l el )
create a 3-phase system.
To this end, the devices must be mutually connected with RJ45 UTP cables. Standard device settings, however, are such that each device operates in stand-alone operation. Reconfiguration of the devices is therefore required.
AES (Automatic Economy Switch) If this setting is turned ‘on’, the power consumption in no-load operation and with low loads is decreased by approx. 20%, by slightly 'narrowing' the sinusoidal voltage. The AES Mode can be set with a DIP switch. Applicable in stand-alone c onfigurat i on onl y.
Page 16
Search Mode (Applicable in stand-alone configuration only) If search mode is ‘on’, the power consumption in no-load operation is decreased by approx. 70%. In this mode the inverter is switched off in case of no load or very low load, and switches on every two seconds for a short period. If the output current exceeds a set level, the inverter will continue to operate. If not, the inverter will shut down again. Not adjustable with DIP switches. The Search Mode “shut down” and “remain on” load levels can be set with VEConfigure. The standard settings are: Shut down: 40 Watt (linear load) Turn on: 100 Watt (linear load)
Programmable relay
By default, the programmable relay is set as an alarm relay, i.e. the relay will de­energise in the event of an alarm or a pre-alarm (inverter almost too hot, ripple on the input almost too high, battery voltage almost too low). Not adjustable with DIP switches.
5.3 Configuration by computer
All settings can be changed by means of a computer or with a VE.Net panel (except for the multi-functi onal relay and the VirtualSwitch when using VE.Net). The most common settings (including parallel and 3-phase operation) can be changed by means of DIP switches (see Section 5.5).
For changing settings with the computer, the following is required:
- VEConfigure3 software. You can download the VEConfigure3 software free
of charge at www.victronenergy.com .
- A RJ45 UTP cable and the MK2.2b RS485-to-RS232 interface. If your
computer has no RS232 connection, but does have USB, you will also need a RS232-to-USB interface cable. Both are available from Victron Energy.
5.3.1 VE.Bus Quick Configure Setup
VE.Bus Quick Configure Setup is a software program with which systems with a
maximum of three Phoenix Inverters (parallel or three phase operation) can be configured in a simple manner. VEConfigure3 forms part of this program. You can download the software free of charge at www.victronenergy.com . For connection to your computer, a RJ45 UTP cable and the MK2.2b RS485-to­RS232 interface is required. If your computer does not have a RS232 connection but is equipped with USB, you will also need a RS232-to-USB interface cable. Both are available from V ictron Energy.
Page 17
EN Appendix
5.3.2 VE.Bus System Configurator and dongle
For configuring advanced applications and/or systems with four or more Inverters, VE.Bus System Configurator software must be used. You can download the software at www.victronenergy.com . VEConfigure3 forms part of this program. You can configure the system without a dongle, and use it for 15 minutes (as a demonstration facility). For permanent use, a dongle – available at additional charge – is required. For connection to your computer, a RJ45 UTP cable and the MK2.2b RS485-to­RS232 interface is required. If your computer does not have a RS232 connection but is equipped with USB, you will also need a RS232-to-USB interface cable. Both are available from Victron Energy.
5.4 Implementing settings with a VE.Net panel
To this end, a VE.Net panel and the VE.Net to VE.Bus converter is required. With VE.Net you can set all parameters, with the exception of the multi-functional relay and the VirtualSwitch.
5.5 Configuration with DIP switches
A number of settings can be changed using DIP switches (see appendix A, position I). Procedure:
Turn the Inverter on, preferably unloaded.
Set the DIP switches for:
o AES (Automatic Economy Switch) o Inverter voltage o Inverter frequency o selection of stand-al one, parall el or 3-phase operati on.
To store the settings after the required values have been set: press the 'Up'
button for 2 seconds (upper button to the right of t he DIP switches, see appendix A, position J).
Remarks:
- Dipswitches ds8,ds7 and ds6 are not assigned and should remain off.
- The DIP switch functions are described in 'top to bottom' order. Since the uppermost
DIP switch has the highest number (8), descriptions start with the switch numbered 5.
- In parallel mode or 3-phase mode, not all devices require all settings to be made
(see section 5.5.4).
- For parallel or 3-phase mode, read the whole setting procedure and make a note of
the required DIP switch settings before actually implementing them.
- The ‘down’ button is not used in this procedure and must not be pressed!
Page 18
5.5.1 AES (Automatic Economy Switch)
Procedure: set ds5 to the required value:
ds5
off = AES off on = AES on
Note: The AES option is only effective if the unit is used ‘stand alone’.
5.5.2 Inverter voltage
Procedure: set ds4 to the required value:
ds4
off = 115V on = 120V
5.5.3 Inverter frequency
Procedure: set ds3 to the required value:
ds3
off = 60Hz on = 50Hz
5.5.4 Stand-alone, parallel and 3-phase operation
DIP switches ds2 and ds1 are reserved for the selection of stand-alone, parallel or 3-phase operation
NOTE:
When configuring a parall el or 3-phase system, all relat ed dev i c es sho ul d be
interconnected using RJ45 UTP cables (see appendix C, D). All devices must be turned on. They will subsequently return an error code (see Section 7), since they have been integrated into a system and still are configured as ‘stand-alone’. This error message can safely be ignored.
Storing settings (by pressing the ‘Up’ button for 2 seconds) should be done on one
device only. This device is the ‘master’ in a parallel system or the ‘leader’ (L1) in a 3­phase system. In a parallel system, the setting of DIP switches ds5 to ds3 need to be done on the master only. The slaves will follow the master with regard to these settings (hence the master/slave relationship). In a 3-phase system, the ‘Inverter voltage setting’ is required for the other devices, i.e. the followers (for phases L2 and L3). (The followers, therefore, do not follow the leader for all settings, hence the leader/follower terminology).
A change in the setting ‘stand-alone / parallel / 3-phase’ is only activated after the
setting has been stored (by pressing the ‘UP’ button for 2 seconds) and after all devices have bee n turn ed off an d then on again. In order to start up a VE.B us system correctly, all devices should therefore be turned off after the settings have been stored. They can then be turned on in any order. The system will not start until all devices have been turned on.
Note that only identical devices can be integrated in one system. Any attempt to use
different models in one system will fail. Such devices may possibly function correctly again only after individual reconfiguration for ‘stand-alone’ op er atio n.
The combination ds2=on and ds1=on is not used.
Page 19
EN Appendix
Setting ds2 and ds1 for stand-alone operation
DS-8 not used Set off
off
DS-7 not used Set off
off
DS-6 not used Set off
off
DS-5 AES Set as desired
DS-4 Inverter voltage Set as desired
DS-3 Inverter frequency Set as desired
DS-2 Stand-alone operation
off
DS-1 Stand-alone operation
off
Examples of DIP switch settings for stand-alone mode are given below. Example 1 shows the factory setting (since factory settings are entered by computer,
all DIP switches of a new product are set to ‘off’).
Four examples of stand-alone settings:
DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 AES
off
DS-4 Inverter voltage
on DS-3 Inverter frequency
on DS-2 Stand-alone mode
off
DS-1 Stand-alone mode
off DS-8
off
DS-7
off
DS-6
off
DS-5
off
DS-4
off
DS-3
off
DS-2
off
DS-1
off DS-8
off
DS-7
off
DS-6
off
DS-5
off
DS-4
on DS-3
off
DS-2
off
DS-1
off DS-8
off
DS-7
off
DS-6
off
DS-5
on DS-4
off
DS-3
on DS-2
off
DS-1
off
stand-alone
Example 1 (factory setting):
5 AES: off 4 Inverter voltage 120V 3 Inverter frequency 50Hz
2, 1 Stand-alone mode
stand-alone
Example 2:
5 AES: off 4 115V 3 60Hz
2,1 Stand-alone
stand-alone
Example 3:
5 AES: off 4 120V 3 60Hz
2,1 Stand-alone
stand-alone
Example 4:
5 AES: on 4 115V 3 50Hz
2,1 Stand-alone
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of the DIP switches, see appendix A, position J).
The overload and low-battery LEDs will flash to indicate acceptance of the settings.
You can leave the DIP switches in the selected positions, so that the settings can always be recovered.
Page 20
Setting ds2 and ds1 for parallel operation
Master
Slave 1
Slave 2 (optional)
DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 AES na
x
DS-4 Inv. voltage Set
DS-3 Inv. freq Set
DS-2 Master
off
DS-1 Master
on
DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 na
x
DS-4 na
x
DS-3 na
x
DS-2 Slave 1
off
DS-1 Slave 1
off DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 na
x
DS-4 na
x
DS-3 na
x
DS-2 Slave 2
off
DS-1 Slave 2
on
To store the settings after the required values have been set: press the 'Up' button of the master for 2 seconds (upper button to the right of the DIP switches, see appendix A, position J). The overload and low-battery LEDs will flash to indicate acceptance of the settings.
You can leave the DIP switches in the selected positions, so that the settings can always be recovered.
Setting ds2 and ds1 for 3-phase operation
Leader (L1)
Follower (L2)
Follower (L3)
DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 AES na
x
DS-4 Inv. voltage Set
DS-3 Inv. freq Set
DS-2 Leader
on DS-1 Leader
off DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 na
x
DS-4 Set
DS-3 na
x
DS-2 L2
off
DS-1 L2
off DS-8 not used
off
DS-7 not used
off
DS-6 not used
off
DS-5 na
x
DS-4 Set
DS-3 na
x
DS-2 L3
off
DS-1 L3
on
As the table above shows, the Inverter voltage should be set separately (ds4) for every Inverter AES can be used on stand alone units only.
To store the settings after the required values have been set: press the 'Up' button of the Leader for 2 seconds (upper button to the right of the DIP switches, see appendix A, position J). The overload and low-battery LEDs will flash to indicate
acceptance of the settings.
You can leave the DIP switches in the selected positions, so that the settings can always be recovered.
To start the system: first, turn all devices off. The system will start up as soon as all devices have been turned on.
Page 21
EN Appendix
6. MAINTENANCE
The Phoenix Inverter does not require specific maintenance. It will suffice to check all connections once a year. Avoid moisture and oil/soot/vapours, and keep the devic e clean.
7. FAULT INDICATIONS
With the procedures below, most errors can be quickly identified. If an error cannot be resolved, please refer to your Victron Energy supplier.
7.1 General error indications
Problem
Cause
Solution
Inverter operation not
initiated when
switched on.
The battery voltage is excessively
high or too low. No voltage on DC
connection.
Ensure that the battery voltage is
within the correct ran ge .
“Low battery” LED flashes.
The battery voltage is low.
Charge the battery or check the battery connecti o ns.
“Low battery” LED
lights.
The converter switches off
because the batter y volt ag e is too
low.
Charge the battery or check the
battery connecti o ns.
“Overload” LED flashes.
The converter load is higher than the nominal load.
Reduce the load.
“Overload” LED lights.
The converter is switched off due to excessively high load.
Reduce the load.
“Temperature” LED
flashes or lights.
The environmental temperature is
high, or the load is too high.
Install the converter in cool and
well-ventilated environment, or
reduce the load.
“Low battery” and
“overload” LEDs flash intermittently.
Low battery voltag e and
excessively high load.
Charge the batteries, disconnect
or reduce the load, or install higher capacity ba tte ries. Fit shorter and/or thicker battery
cables.
“Low battery” and
“overload” LEDs flash simultane ously.
Ripple voltage on the DC
connection exceeds 1,5Vrms.
Check the battery cables and
battery connections. Check whether battery capacity is sufficiently hig h, an d inc re ase
this if necessary.
“Low battery” and
“overload” LEDs light.
The inverter is switched off due to
an excessively hig h ripple voltage on the input.
Install batteries with a larger
capacity. Fit short er an d/o r thicker battery cables, and reset the inverter (switch off, and then
on again).
One alarm LED lights
and the second flashes.
The inverter is switched off due to
alarm activation by the lighted LED. The flashing LED indicates that the inverter was about to
switch off due to the related alarm.
Check this table for appropriate
measures in regard to this alarm state.
Page 22
7.2 VE.Bus LED indications
Inverters included in a VE.Bus system (a parallel or 3-phase arrangement) can provide so-called VE.Bus LED indications. These LED indications can be subdivided into two groups: OK codes and error codes.
7.2.1 VE.Bus OK codes
If the internal status of a device is in order but the device cannot yet be started because one or more other devices in the system indicate an error status, the devices that are in order will indicate an OK code. This facilitates error tracing in a VE.Bus system, since devices not requiring attention are easily identified as suc h.
Important: OK codes will only be displayed if a device is not inverting!
The "inverter on" LED must flash.
A flashing "overload" LED indicat es that the device can perform inverter
operation.
A flashing "temperature" LED indicates that the device is not blocking
charge operation. (This is just a formal indication which originates from the relationship with the Phoenix Multi. This indication has no special meaning on a Phoenix Inverter)
NOTE: The "low battery" LED can function together with the OK code that indicates that the device does not block charge.
7.2.2 VE.Bus error codes
If a VE.Bus error occurs (example: a broken UTP cable) the system will switch off and the ‘inverter on’ LED will flash. If such an error occurs one should switch all units off, verify all cabling and switch the units on again.
Additional information about the errror can be retrieved from the Inverter with the VE.BUS System Configurator or the VE.BUS Quic k Configure tool.
Page 23
EN Appendix
8. TECHNICAL SPECIFICATIONS
Phoenix Inverter
12/3000 24/3000
INVERTER
Input voltage range (V DC) 9,5 – 17 19 – 33
Output (1)
Output voltage: 120VAC ± 2% Frequency: 60Hz ± 0,1%
Cont. output power at 25°C (VA) (3)
3000
Cont. output power at 25°C (W)
2500
Cont. output power at 40°C (W)
2200
Cont. output power at 65°C (W)
1700
Peak power (W)
6000
Maximum efficiency (%)
93 94
Zero-load power (W)
20
GENERAL
Programmable relay
(4)
Yes
Protection
(2)
a - g
Common Characteristics
Operating temp. : -20 to +65°C (fan assi st ed co oli ng )
Humidity (non-condensing): max 95%
ENCLOSURE
Common Characteristics
Material & Colour: aluminium (blue RAL 5012) Protection: IP 21
Battery-connection
M8 bolts (2 plus and 2 minus connections)
230 V AC-connection
Screw terminals 13mm² (6 AWG)
Weight (kg) 19kg 42 lbs Dimensions (hxwxd in mm) 362 x 258 x 218mm 14.3 x 10.2 x 8.6inch
STANDARDS
Safety
EN 60335-1, EN 60335-2-29
Emission / Immunity
EN 55014-1, EN 61000-3-2 / EN 55014-2, EN 61000-3-3
Automotive Directive
2004/104/EC
1) Can be adjusted to 50Hz
2) Protection
a. Output short circuit b. Overload c. Battery voltage too high d. Battery voltage too low e. Temperature too high
f. 120VAC on inverter output g. Input voltage rippl e too hi g h
3) Non linear load, crest factor 3:1
4) Programmable relay which can be set for general alarm, DC undervoltage or genset start signal
function
Page 24
APPENDIX A Overview connections INVERTER 3k
EN:
B
2x RJ45 connector for remote control and/or parallel / three-phase operation.
C
Load connection AC out: (left to right): L (phase), N (neutral), PE (ground).
E
Battery minus. Double M8 battery minus connection.
F
Battery plus. Double M8 battery positive connecti on.
H
Connections for remote switch: Short left and middle terminal to switch the Phoenix “on”.
I
Dipswitches DS1 tm DS8 for set-up mode.
J
Pushbuttons for set-up mode.
K
Alarm contact: (left to right) NC, NO, COM
L
Primary ground connection (PE).
Page 25
EN Appendix
APPENDIX B: Block diagram
* See table in chapter 4.2 “Recommended DC fuse
Page 26
APPENDIX C: Parallel connection
APPENDIX D: Three phase connection
Page 27
EN Appendix
APPENDIX G: Dimensions
Page 28
Dimensions 3k cabinet
Page 29
Page 30
Victron Energy Blue Power
Distributor:
Serial number:
Version : 03a Date : October 13
th
, 2016
Victron Energy B.V. De Paal 35 | 1351 JG Almere PO Box 50016 | 1305 AA Almere | The Netherlands
General phone : +31 (0)36 535 97 00 Fax : +31 (0)36 535 97 40
E-mail : sales@victronenergy.com
www.victronenergy.com
Loading...