![](/html/9f/9f31/9f3122304fac9a70f3bf3904bc4b86b444b506d33b5a4e7a9f723c5298de48a8/bg1.png)
2019-02-19 08:06 1/10 Victron & Pylontech US2000B and Phantom-S
Victron & Pylontech US2000B and Phantom-S
The combination of Victron products with Pylontech lithium batteries has been tested and certified by
the Victron and Pylontech R&D departments.
General information about the battery is found in Pylontech's documentation.
This manual is intended to be used in conjunction with the product manual supplied by Pylontech. It
provides additional and specific information regarding integration with Victron systems.
The Pylontech includes a Battery Management System (BMS) with each battery module. This
interfaces with the Victron Venus-device and can support multiple battery modules connected in
parallel.
1. Product & system compatibility
Battery US2000B US2000B Plus US3000 Plus
Module capacity 2.4 kWh 2.4 kWh 3.5 kWh
1.1 Offgrid, Backup and Energy Storage Systems are possible
Victron + Pylontech can be used for the following system types:
Off-grid
Grid Backup
Energy Storage Systems - Self Consumption (ESS - Start page)
1.2 A Venus-device is required, eg Color Control GX (CCGX) or Venus GX (VGX)
It is essential to use the CAN-bus connection of the Venus-device (eg CCGX or VGX) with the batteries
for the keep-alive signal, communication of charge and discharge limits, error codes and state of
charge.
The minimum required firmware version for the Color Control GX is v2.15. It is highly recommended to
use the latest firmware version on all connected devices, including CCGX/VGX, Inverter/Charger and
Victron Energy - https://www.victronenergy.com/live/
![](/html/9f/9f31/9f3122304fac9a70f3bf3904bc4b86b444b506d33b5a4e7a9f723c5298de48a8/bg2.png)
Last update:
2019-02-18 22:06
battery_compatibility:pylontech_phantom https://www.victronenergy.com/live/battery_compatibility:pylontech_phantom
MPPTs. There are regular updates to improve performance and reliability.
1.3 All 48V Multi, MultiPlus, MultiGrid and Quattro are compatible
The minimum firmware version is 422. Though updating to the latest firmware is recommended where
possible.
These inverter/charger units must be connected to the Venus-device via the VE.Bus connection port.
1.4 All 48V VE.direct BlueSolar and SmartSolar MPPT Chargers are compatible
For proper operation, the Pylontech battery needs to be able to control the charge current. Therefor it
is recommended to use Victron 48V compatible MPPTs models with VE.Direct port for charging.
MPPTs with a VE.Direct port
MPPTs are controlled via the Venus-device. Make sure the Venus-device runs v2.15 or later, and the
MPPTs to 1.37 or the latest available version.
The MPPT requires connection to the Venus-device to regulate charge currents as the batteries
require (due to temperature, etc) To test operation, try disconnecting the Venus-device from the
MPPT. After a time-out, the MPPT will stop charging and flash an error code on its LEDs. The error
code is error #67: no BMS.
MPPTs with a VE.Can port
Use of VE.Can MPPT's with Pylontech batteries is not supported or documented.
2. Minimum Battery Sizing Recommendations
Each US2000B Plus battery module is approximately 50Ah at 48V, can provide 25A continuous charge
and discharge and 100A peak for 1 minute.
The charge and discharge rates are managed automatically by the Pylontech battery and Venus-
device.
Using very large solar arrays with battery banks that are too small can exceed the limits of the
batteries ability to charge and possibly lead to the BMS triggering over-current alarms.
You must have the minimum number of units to supply the potential current demand of the load
connected to the inverter. It is more desirable to have the inverter/charger overload than the battery.
Some suggested battery sizings for common Victron inverter/chargers are listed below. These are
suggestions for reliable operation for single phase off grid and are not specified by Pylontech.
https://www.victronenergy.com/live/ Printed on 2019-02-19 08:06
![](/html/9f/9f31/9f3122304fac9a70f3bf3904bc4b86b444b506d33b5a4e7a9f723c5298de48a8/bg3.png)
2019-02-19 08:06 3/10 Victron & Pylontech US2000B and Phantom-S
Inverter
peak
watts
surge
rating
Number of
Pylontech
modules
Battery
continuous
discharge
watt rating
Battery
peak
discharge
watt rating
Inverter / Charger Model
Inv
continuous
watts @ 25
degrees
Multiplus 48/500/6 430 900 1 1200 4800
Multiplus 48/800/9 700 1600 1 1200 4800
Multiplus 48/1200/13 1000 2400 1 1200 4800
Multiplus 48/3000/35 2400 6000 2 2400 9600
Multiplus 48/5000/70 4000 10000 4 4800 19200
Quattro 48/8000/110-100/100 6500 16000 6 7200 28800
Quattro
48/10000/140-100/100
Quattro
48/15000/200-100/100
8000 20000 7 8400 33600
12000 25000 10 12000 48000
3. CAN-bus Wiring
You can connect multiple battery modules together to form a single large battery by connecting the
RJ-45 cable supplied by Pylontech using the link ports on the battery. This is shown in more detail in
the example wiring diagram and Pylontech manual.
The batteries will automatically detect and link to each other, no adjustment of dip switches or
software changes are necessary on the batteries.
The battery with the empty link port 0 is the master battery. Using the VE.Can to CAN-bus BMS type B
Cable, part number ASS030720018, Plug the side which is labeled Battery BMS into the Pylontech
CAN port of the master battery. Plug the side labeled Victron VE.Can into the Venus-device.
Victron Energy - https://www.victronenergy.com/live/